The following section describes the use of performance
curves and lookup tables. Each of these objects may be used in
any valid input field where a performance curve name is
required.
Performance curves are used directly to simulate the
performance of HVAC equipment. The curves are typically
created by performing a regression analysis on tabular data
for a particular equipment performance metric. The regression
analysis determines the equation coefficients which are the
primary input to all performance curve objects. Performance
tables are similar to performance curves in that they are
meant to replicate a particular performance curve. Input to
performance tables are made up of data pairs, the same data
pairs that would be used to create performance curve
coefficients. Performance tables can be interpolated using up
to a 4th order polynomial equation for one
independent variable tables or using a 2nd order
polynomial for two independent variable tables. A regression
analysis can be performed on performance tables when the
simulation is instructed to use the regression analysis during
the simulation (i.e., ride the curve). In addition, a
performance curve object is created that can be used in future
simulations and can be written to the eio file. The
performance curve is written to the eio file only when the
diagnostics flag is set to DisplayAdvancedReportVariables
(ref. Output:Diagnostics,
DisplayAdvancedReportVariables;). Lookup tables are similar to
performance tables in that tabular data is used for input,
however, the input 1) is more compact, 2) a regression
analysis may only be performed for one and two independent
variable cases, and 3) the tabular data can be read from an
external file.
Performance curves and data tables are created using
empirical data that are derived from information gathered
through observation, experience, or experimental means. Once a
curve or table object is defined, these objects can be used to
generically describe HVAC equipment performance. Performance
curves and performance tables may be used interchangeably in
Energyplus objects as required.
Performance Curves and Lookup Tables[LINK]
The following section describes the use of performance curves and lookup tables. Each of these objects may be used in any valid input field where a performance curve name is required.
Performance curves are used directly to simulate the performance of HVAC equipment. The curves are typically created by performing a regression analysis on tabular data for a particular equipment performance metric. The regression analysis determines the equation coefficients which are the primary input to all performance curve objects. Performance tables are similar to performance curves in that they are meant to replicate a particular performance curve. Input to performance tables are made up of data pairs, the same data pairs that would be used to create performance curve coefficients. Performance tables can be interpolated using up to a 4th order polynomial equation for one independent variable tables or using a 2nd order polynomial for two independent variable tables. A regression analysis can be performed on performance tables when the simulation is instructed to use the regression analysis during the simulation (i.e., ride the curve). In addition, a performance curve object is created that can be used in future simulations and can be written to the eio file. The performance curve is written to the eio file only when the diagnostics flag is set to DisplayAdvancedReportVariables (ref. Output:Diagnostics, DisplayAdvancedReportVariables;). Lookup tables are similar to performance tables in that tabular data is used for input, however, the input 1) is more compact, 2) a regression analysis may only be performed for one and two independent variable cases, and 3) the tabular data can be read from an external file.
Performance curves and data tables are created using empirical data that are derived from information gathered through observation, experience, or experimental means. Once a curve or table object is defined, these objects can be used to generically describe HVAC equipment performance. Performance curves and performance tables may be used interchangeably in Energyplus objects as required.