UtilityCost:Charge:Simple[LINK]
The UtilityCost:Charge:Simple
is one of the most often used objects for tariff calculation.
It is used to compute energy and demand charges that are very
simple. It may also be used for taxes, surcharges and any
other charges that occur on a utility bill. As many UtilityCost:Charge:Simple
objects as needed may be defined for a single tariff and they
will be added together.
Field: Charge Variable
Name[LINK]
This is the name associated with the UtilityCost:Charge:Simple
object and will appear in the report. In addition, the results
of the UtilityCost:Charge:Simple
calculation are stored in a variable with the same name. That
way, the results may be used for further calculation. Spaces
are not significant in Charge Variable Names. They are removed
during the utility bill calculation process.
Field: Tariff Name[LINK]
The name of the tariff that this UtilityCost:Charge:Simple
is associated with.
Field: Source Variable[LINK]
The name of the source used by the UtilityCost:Charge:Simple.
This is usually the name of the variable holding the energy or
demand but may also be the name of any variable including the
subtotal or basis if other charges are based on those.
Field: Season[LINK]
This is the name (or number) of a season for which the UtilityCost:Charge:Simple
is calculated. If this is set to Annual, the calculations are
performed for the UtilityCost:Charge:Simple
for the entire year (all months) otherwise it is calculated
only for those months in the season defined. The season is
defined by the Season Schedule in the UtilityCost:Tariff
object. The choices for seasons are the following names or
numbers may be used:
- Annual
- Winter
- Spring
- Summer
- Fall
Field: Category Variable
Name[LINK]
All charges get added somewhere in the hierarchy described
in the introduction to EnergyPlus economics above. This field
shows where the charge should be added. The reason to enter
this field appropriately is so that the charge gets reported
in a reasonable category. The charge automatically gets added
to the variable that is the category. The choices for this
field are limited to:
- EnergyCharges
- DemandCharges
- ServiceCharges
- Basis
- Adjustment
- Surcharge
- Subtotal
- Taxes
- Total
- NotIncluded
Field:
Cost per Unit Value or Variable Name[LINK]
This field contains either a single number or the name of a
variable. The number is multiplied with all of the energy or
demand or other source that is specified in the source field.
If a variable is used, then the monthly values of the variable
are multiplied against the variable specified in the source
field. This field makes it easy to include a simple charge
without specifying block sizes. It is added to any of the
block calculations (see later fields) but is most often used
by itself. If no value or variable is entered, a zero is
assumed. This is a good way to include a tax or cost
adjustment. For SellToUtility tariffs, the values in this
field are usually expressed as negative numbers.
UtilityCost:Charge:Simple[LINK]
The UtilityCost:Charge:Simple is one of the most often used objects for tariff calculation. It is used to compute energy and demand charges that are very simple. It may also be used for taxes, surcharges and any other charges that occur on a utility bill. As many UtilityCost:Charge:Simple objects as needed may be defined for a single tariff and they will be added together.
Field: Charge Variable Name[LINK]
This is the name associated with the UtilityCost:Charge:Simple object and will appear in the report. In addition, the results of the UtilityCost:Charge:Simple calculation are stored in a variable with the same name. That way, the results may be used for further calculation. Spaces are not significant in Charge Variable Names. They are removed during the utility bill calculation process.
Field: Tariff Name[LINK]
The name of the tariff that this UtilityCost:Charge:Simple is associated with.
Field: Source Variable[LINK]
The name of the source used by the UtilityCost:Charge:Simple. This is usually the name of the variable holding the energy or demand but may also be the name of any variable including the subtotal or basis if other charges are based on those.
Field: Season[LINK]
This is the name (or number) of a season for which the UtilityCost:Charge:Simple is calculated. If this is set to Annual, the calculations are performed for the UtilityCost:Charge:Simple for the entire year (all months) otherwise it is calculated only for those months in the season defined. The season is defined by the Season Schedule in the UtilityCost:Tariff object. The choices for seasons are the following names or numbers may be used:
Field: Category Variable Name[LINK]
All charges get added somewhere in the hierarchy described in the introduction to EnergyPlus economics above. This field shows where the charge should be added. The reason to enter this field appropriately is so that the charge gets reported in a reasonable category. The charge automatically gets added to the variable that is the category. The choices for this field are limited to:
Field: Cost per Unit Value or Variable Name[LINK]
This field contains either a single number or the name of a variable. The number is multiplied with all of the energy or demand or other source that is specified in the source field. If a variable is used, then the monthly values of the variable are multiplied against the variable specified in the source field. This field makes it easy to include a simple charge without specifying block sizes. It is added to any of the block calculations (see later fields) but is most often used by itself. If no value or variable is entered, a zero is assumed. This is a good way to include a tax or cost adjustment. For SellToUtility tariffs, the values in this field are usually expressed as negative numbers.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.