This group of objects consists of tabular data which are
used to characterize the performance of HVAC equipment. The
use of performance tables eliminate the need to perform a
regression analysis to calculate the performance curve
equation coefficients. Two performance tables are available to
represent any performance curve having one or two independent
variables. The tabular data is entered as data pairs and
represent each independent variable followed by the table
output at that condition. When using these two performance
table objects, a regression analysis may be performed during
the simulation to create the associated performance curve. The
regression analysis is performed when the user requests to
evaluate the curve to the limits specified (see Interpolation
Method input field). The performance curve that is created is
used throughout the simulation and is also written to the eio
file when the user sets the diagnostics output flag
DisplayAdvancedVariables (ref. Output:Diagnostics,
DisplayAdvancedVariables) This performance curve object may be
directly used in future input files. The following
descriptions define the input requirements for the performance
table objects.
Table:OneIndependentVariable[LINK]
Input for the data table consists of a table name, the
curve type, the interpolation method, and the data pairs
representing the polynomial equation. Optional inputs for
minimum and maximum values for the independent variable and
curve minimum and maximum may be used to limit the output of
the table when evaluating the regression curve (e.g., limit
extrapolation). The existing performance curves represented by
this table object are:
\[Linear\,\,Curve:\,\,\,Output =
{C_1} + {C_2}x\]
\[Quadratic\,\,Curve:\,\,\,Output = {C_1}
+ {C_2}x + {C_3}{x^2}\]
\[Cubic\,\,Curve:\,\,\,Output =
{C_1} + {C_2}x + {C_3}{x^2} + {C_4}{x^3}\]
\[Quartic\,\,Curve:\,\,\,Output
= {C_1} + {C_2}x + {C_3}{x^2} + {C_4}{x^3} +
{C_5}{x^4}\]
\[Exponent\,\,Curve:\,\,\,Output
= {C_1} + {C_2}{x^{{C_3}}}\]
A unique user assigned name for an instance of a
performance table. When a table is used, it is referenced by
this name. The name of this table object may be used anywhere
a valid performance curve object is allowed.
Field: Curve Type[LINK]
The form of the polynomial equation used to represent the
tabular data. Choices are Linear, Quadratic,
Cubic, Quartic and Exponent. This
field is used to determine if this table object is
representative of the type of performance table (curve)
allowed for a particular application (i.e., if this type of
polynomial is allowed to be used as the curve type for other
objects). This input infers the polynomial order (or degree).
This input also specifies the number of interpolation points
if the next field, Interpolation Method is set to
LagrangeInterpolationLinearExtrapolation. The number of
interpolation points for Linear, Quadratic, Cubic, Quartic,
and Exponent are set at 2, 3, 4, 5, and 4, respectively.
Field: Interpolation
Method[LINK]
The method used to evaluate the tabular data. Choices are
LinearInterpolationOfTable,
LagrangeInterpolationLinearExtrapolation and
EvaluateCurveToLimits. When
LinearInterpolationOfTable is selected, the tabular
data is interpolated within the limits of the data set and the
following fields are used only within the boundary of the
table limits (i.e., are only used to limit interpolation).
Extrapolation of the data set is not allowed. When
LagrangeInterpolationLinearExtrapolation is selected,
a polynomial interpolation routine is used within the table
boundaries along with linear extrapolation. Given the valid
one independent variable equations above, the polynomial order
is up to 5th order. When
EvaluateCurveToLimits is selected, the coefficients
(i.e., C in the equations above) of the polynomial equation
are calculated and used to determine the table output within
the limits specified in the following fields. If these fields
are not entered, the limits of the tabular data are used. The
minimum number of data pairs required for this choice are 2,
3, 4, 5, and 4 data pairs for linear, quadratic, cubic,
quartic, and exponent curves, respectively. If insufficient
data is provided, the regression analysis is not performed and
the simulation reverts to interpolating the tabular data. The
performance curve is written to the eio file when the output
diagnotics flag DisplayAdvancedVariables is used (ref. Output:Diagnostics,
DisplayAdvancedVariables).
Field: Minimum Value of
X[LINK]
The minimum allowable value of X. Values of X less than the
minimum will be replaced by the minimum. This field can only
limit extrapolation when the Interpolation Method is
selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
Field: Maximum Value of
X[LINK]
The maximum allowable value of X. Values of X greater than
the maximum will be replaced by the maximum. This field can
only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
Field: Minimum Table
Output[LINK]
The minimum allowable value of the table output. Values
less than the minimum will be replaced by the minimum. This
field can only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
Field: Maximum Table
Output[LINK]
The maximum allowable value of the table output. Values
greater than the maximum will be replaced by the maximum. This
field can only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
This field is used to indicate the kind of units that may
be associated with the x values. It is used by IDF Editor to
display the appropriate SI and IP units for the Minimum Value
of X and Maximum Value of X. The unit conversion is not
applied to the coefficients. The available options are shown
below. If none of these options are appropriate, select
Dimensionless which will have no unit
conversion.
- Dimensionless
- Temperature
- VolumetricFlow
- MassFlow
- Distance
- Power
Field: Output Unit Type[LINK]
This field is used to indicate the kind of units that may
be associated with the output values. It is used by IDF Editor
to display the appropriate SI and IP units for the Minimum
Curve Output and Maximum Curve Output. The unit conversion is
not applied to the coefficients. The available options are
shown below. If none of these options are appropriate, select
Dimensionless which will have no unit
conversion.
- Dimensionless
- Capacity
- Power
Field: Normalization
Reference[LINK]
The normalization point for the data set. This field
provides a method for automatically normalizing a set of data.
Equipment performance data is typically normalized based on a
specific operating condition. Both the output values and
minimum/maximum curve limits are normalized. This
normalization can be performed simply by entering the data at
the reference point. If this field is left blank or a 1 is
entered, the data set is assumed to be in the correct
format.
The following inputs describe the data set. Data pairs are
entered as X and Output pairs where X is the independent
variable (i.e., x in the equation above) and Output is the
dependent variable (i.e., Output in the equation above). Any
number of data pairs may be entered, however, a minimum number
of data pairs must be entered and depends on the polynomial
equation. Linear (1st order), Quadratic
(2nd order), Cubic (3rd order), Quartic
(4th order), and Exponent (nth order) polynomials
require a minimum of 2, 3, 4, 5, and 4 data pairs,
respectively. This minimum requirement is for performing a
regression analysis, not interpolating the tabular data. If a
regression analysis is not performed (i.e., only table
interpolation is used), these minimum requirements are not
enforced. If a regression analysis is performed and these
minimum requirements are not met, the simulation will revert
to table interpolation. These fields may be repeated as many
times as necessary to define the tabular data.
Field: X Value #n[LINK]
The value of the independent variable n (i.e., independent
variable values for data 1 to number of data pairs).
Field: Output Value #n[LINK]
The value of the dependent variable n (i.e., dependent
variable values for data 1 to number of data pairs).
Following is an example input for a Table:OneIndependentVariable
object:
Table:OneIndependentVariable,
WindACCoolCapFFF, !- Name
Linear, !- Curve Type
EvaluateCurveToLimits, !- Interpolation Type
0, !- Minimum Value of X1,
1.5, !- Maximum Value of X1,
0.8, !- Minimum Table Output
1.1, !- Maximum Table Output
Dimensionless, !- Input Unit Type for X1
Dimensionless, !- Output Unit Type
, !- Normalization Point
0,0.8, !- X Value #1, Output Value #1
1.5,1.1; !- X Value #2, Output Value #2
The current value of the performance table. Performance
curves and tables use the same output variable. This value is
averaged over the time step being reported. Inactive or unused
performance curves will show a value of -999 (e.g., equipment
is off, a specific performance curve is not required for this
aspect of the equipment model at this time step, etc.). This
value means that the performance curve was not called during
the simulation and, therefore, not evaluated. This inactive
state value is only set at the beginning of each environment.
When averaging over long periods of time, this inactive state
value may skew results. In this case, use a detaled reporting
frequency (ref. Output:Variable
object) to view results at each HVAC time step.
The current value of the independent variable passed to the
performance curve. This value is averaged over the time step
being reported.
HVAC,Average,Performance Curve Output Value []
HVAC,Average,Performance Curve Input Variable 1 Value []
Table:TwoIndependentVariables[LINK]
Input for the data table consists of a table name, the
curve type, the interpolation method, and the data pairs
representing the polynomial equation. Optional inputs for
minimum and maximum values for the independent variable, and
curve minimum and maximum may be used to limit the output of
the table (e.g., limit extrapolation) when evaluating the
regression curve instead of the tabular data. The polynomial
equations currently represented by this table object are:
\[BiQuadratic\,\,Curve:\,\,\,\,Output =
{C_1} + {C_2}x + {C_3}{x^2} + {C_4}y + {C_5}{y^2} +
{C_6}xy\]
\[QuadraticLinear\,\,Curve:\,\,\,\,Output
= {C_1} + {C_2}x + {C_3}{x^2} + {C_4}y + {C_5}xy +
{C_6}{x^2}y\]
A unique user assigned name for an instance of a
performance table. When a table is used, it is referenced by
this name. The name of this table object may be used anywhere
a valid performance curve object is allowed.
Field: Curve Type[LINK]
The form of the polynomial equation represented by the
entered data. The only valid choices are BiQuadratic
and QuadraticLinear. This field is used to determine
if this table object is representative of the type of
performance table (curve) allowed for a particular equipment
model (i.e., if this type of polynomial is allowed to be used
as the curve type for specific input fields). A minimum of 6
data pairs are required when selecting
EvaluateCurveToLimits in the following field. This
input also specifies the number of interpolation points if the
next field, Interpolation Method is set to
LagrangeInterpolationLinearExtrapolation. The number of
interpolation points for BiQuadratic and QuadraticLinear are
set at 6.
Field: Interpolation
Method[LINK]
The method used to evaluate the tabular data. Choices are
LinearInterpolationOfTable,
LagrangeInterpolationLinearExtrapolation, and
EvaluateCurveToLimits. When
LinearInterpolationOfTable is selected, the data
entered is evaluated within the limits of the data set and the
following fields are used only within the boundary of the
table limits (i.e., are only used to limit interpolation). A
complete data set is required. For each X variable, entries
must include all Y variables and associated curve output
(i.e., a complete table, no gaps or missing data).
Extrapolation of the data set is not allowed. When
LagrangeInterpolationLinearExtrapolation is selected,
a polynomial interpolation routine is used within the table
boundaries along with linear extrapolation. Given the valid
equations above, the polynomial order is fixed at 2 which
infers that 3 data points will be used for interpolation. When
EvaluateCurveToLimits is selected, the coefficients
(i.e., C in the equations above) of the polynomial equation
are calculated and used to determine the table output within
the limits specified in the following fields (or the tabular
data, whichever provide the larger range). If the following
fields are not entered, the limits of the data set are used. A
complete table is not required when using this method,
however, a minimum number of data is required to perform the
regression analysis. The minimum number of data pairs required
for this choice is 6 data pairs for both bi-quadratic and
quadratic-linear curve types. If insufficient data is
provided, the simulation reverts to interpolating the tabular
data. The performance curve is written to the eio file when
the output diagnotics flag DisplayAdvancedVariables is used
(ref. Output:Diagnostics,
DisplayAdvancedVariables).
Field: Minimum Value of
X[LINK]
The minimum allowable value of X. Values of X less than the
minimum will be replaced by the minimum. This field can only
limit extrapolation when the Interpolation Method is
selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
Field: Maximum Value of
X[LINK]
The maximum allowable value of X. Values of X greater than
the maximum will be replaced by the maximum. This field can
only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
Field: Minimum Value of
Y[LINK]
The minimum allowable value of Y. Values of Y less than the
minimum will be replaced by the minimum. This field can only
limit extrapolation when the Interpolation Method is
selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
Field: Maximum Value of
Y[LINK]
The maximum allowable value of Y. Values of Y greater than
the maximum will be replaced by the maximum. This field can
only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
Field: Minimum Table
Output[LINK]
The minimum allowable value of the table output. Values
less than the minimum will be replaced by the minimum. This
field can only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
Field: Maximum Table
Output[LINK]
The maximum allowable value of the table output. Values
greater than the maximum will be replaced by the maximum. This
field can only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
This field is used to indicate the kind of units that may
be associated with the X values. It is used by IDF Editor to
display the appropriate SI and IP units for the Minimum Value
of X and Maximum Value of X. The unit conversion is not
applied to the coefficients. The available options are shown
below. If none of these options are appropriate, select
Dimensionless which will have no unit
conversion.
- Dimensionless
- Temperature
- VolumetricFlow
- MassFlow
- Distance
- Power
This field is used to indicate the kind of units that may
be associated with the Y values. It is used by IDF Editor to
display the appropriate SI and IP units for the Minimum Value
of Y and Maximum Value of Y. The unit conversion is not
applied to the coefficients. The available options are shown
below. If none of these options are appropriate, select
Dimensionless which will have no unit
conversion.
- Dimensionless
- Temperature
- VolumetricFlow
- MassFlow
- Distance
- Power
Field: Output Unit Type[LINK]
This field is used to indicate the kind of units that may
be associated with the output values. It is used by IDF Editor
to display the appropriate SI and IP units for the Minimum
Curve Output and Maximum Curve Output. The unit conversion is
not applied to the coefficients. The available options are
shown below. If none of these options are appropriate, select
Dimensionless which will have no unit
conversion.
- Dimensionless
- Capacity
- Power
Field: Normalization
Reference[LINK]
The normalization point for the data set. This field
provides a method for automatically normalizing a set of data.
Equipment performance data is typically normalized based on a
specific operating condition. Both the output values and
minimum/maximum curve limits are normalized as applicable.
This normalization can be performed simply by entering the
data at the reference point. If this field is left blank or a
1 is entered, the data set is assumed to be in the correct
format.
The following inputs describe the data set. Data pairs are
entered as X, Y and Output pairs where X and Y are the
independent variables (i.e., x and y in the equations above)
and Output is the dependent variable (i.e., Output in the
equation above). Any number of data pairs may be entered,
however, a minimum number of data pairs must be entered and
depends on the polynomial equation. BiQuadratic and
QuadraticLinear (2nd order with 2 independent
variables) require a minimum of 6 data pairs. This minimum
requirement is for performing a regression analysis, not
interpolating the tabular data. If a regression analysis is
not performed (i.e., only table interpolation is used), these
minimum requirements are not enforced. If a regression
analysis is performed and these minimum requirements are not
met, the simulation will revert to table interpolation. These
fields may be repeated as many times as necessary to define
the tabular data.
Field: X Value #n[LINK]
The value of the first independent variable n (i.e., first
independent variable values for data pair 1 to number of data
pairs).
Field: Y Value #n[LINK]
The value of the second independent variable n (i.e.,
second independent variable values for data pair 1 to number
of data pairs).
Field: Output Value #n[LINK]
The value of the dependent variable n (i.e., dependent
variable values for data pair 1 to number of data pairs).
Following is an example input for a
Table:TwoIndependentVariable object:
Table:TwoIndependentVariables,
CCOOLEIRFT, !- Name
BiQuadratic, !- Curve Type
EvaluateCurveToLimits, !- Interpolation Type
5.0, !- Minimum Value of x,
60.0, !- Maximum Value of x,
5.0, !- Minimum Value of y,
70.0, !- Maximum Value of y,
0.01, !- Minimum Table Output
0.5, !- Maximum Table Output
Temperature, !- Input Unit Type for x
Temperature, !- Input Unit Type for y
Dimensionless, !- Output Unit Type
0.258266502, !- Normalization Point
17.2222222,18.3333333,0.18275919, !-X Value #1,Y Value #1,Output #1
17.2222222,23.8888889,0.207383768,!-X Value #2,Y Value #2,Output #2
17.2222222,29.4444444,0.237525541,!-X Value #3,Y Value #3,Output #3
17.2222222,35,0.274217751, !-X Value #4,Y Value #4,Output #4
17.2222222,40.5555556,0.318548624,!-X Value #5,Y Value #5,Output #5
17.2222222,46.1111111,0.374560389,!-X Value #6,Y Value #6,Output #6
19.4444444,18.3333333,0.172982816,!-X Value #7,Y Value #7,Output #7
19.4444444,23.8888889,0.19637691, !-X Value #8,Y Value #8,Output #8
19.4444444,29.4444444,0.224789822,!-X Value #9,Y Value #9,Output #9
19.4444444,35,0.258266502, !-X Value #10,Y Value #10,Output #10
19.4444444,40.5555556,0.299896794,!-X Value #11,Y Value #11,Output #11
19.4444444,46.1111111,0.351242021,!-X Value #12,Y Value #12,Output #12
21.6666667,18.3333333,0.164081122,!-X Value #13,Y Value #13,Output #13
21.6666667,23.8888889,0.185603303,!-X Value #14,Y Value #14,Output #14
21.6666667,29.4444444,0.211709812,!-X Value #15,Y Value #15,Output #15
21.6666667,35,0.243492052, !-X Value #16,Y Value #16,Output #16
21.6666667,40.5555556,0.281757875,!-X Value #17,Y Value #17,Output #17
21.6666667,46.1111111,0.331185659;!-X Value #18,Y Value #18,Output #18
The current value of the performance table. Performance
curves and tables use the same output variable. This value is
averaged over the time step being reported. Inactive or unused
performance curves will show a value of -999 (e.g., equipment
is off, a specific performance curve is not required for this
aspect of the equipment model at this time step, etc.). This
value means that the performance curve was not called during
the simulation and, therefore, not evaluated. This inactive
state value is only set at the beginning of each environment.
When averaging over long periods of time, this inactive state
value may skew results. In this case, use a detaled reporting
frequency (ref. Output:Variable
object) to view results at each HVAC time step.
The current value of the first and second independent
variable passed to the performance curve. The order of the
independent variables is in the same order as the model
equation represented by this performance curve object. This
value is averaged over the time step being reported.
HVAC,Average,Performance Curve Output Value []
HVAC,Average,Performance Curve Input Variable 1 Value []
HVAC,Average,Performance Curve Input Variable 2 Value []
Lookup Tables[LINK]
Lookup tables are useful for determining the results of a
nth order polynomial without the need to calculate the
polynomial coefficients. The Lagrange method for interpolation
is currently the only method available for polynomial
interpolation. LinearInterpolationOfTable and
EvaluateCurveToLimits may also be used. The multi-variable
lookup table can represent from 1 to 5 independent variables
and can interpolate these independent variables up to a
4th order polynomial. The polynomial order is
assumed to be the number of interpolation points (n) minus 1.
Polynomial interpolation of tabular data takes place when the
values of the independent variables are within the upper table
boundary and at least n data points are available when
approaching the lower table boundary for any independent
variable. When any independent variable value is outside the
table limits, linear extrapolation is used to predict the
table result and is based on the two nearest data points in
the table for that particular independent variable.
Table:MultiVariableLookup[LINK]
Input for the multi-variable data table consists of a table
name, the interpolation method, the number of points to be
used for interpolation, an optional external file name, and,
if an external file name is not entered, the tabular data.
Optional inputs for minimum and maximum values for the
independent variable, and curve minimum and maximum may be
used to limit the output of the table (e.g., limit
extrapolation).
A unique user assigned name for an instance of a lookup
table. When a table is used, it is referenced by this name.
The name of this table object may be used anywhere a valid
performance curve object is allowed.
Field: Curve Type[LINK]
The order of the polynomial used to represent the tabular
data. Choices are Linear, Quadratic,
Cubic, Quartic, BiQuadratic, QaudraticLinear,
BuCibic. This field is used to determine if this table
object is representative of the type of performance table
(curve) allowed for a particular application (i.e., if this
type of polynomial is allowed to be used as the curve type for
other objects). This input also infers the polynomial order
(or degree).
Field: Interpolation
Method[LINK]
The method used to evaluate the lookup table. The choices
are LinearInterpolationOfTable,
LagrangeInterpolationLinearExtrapolation, and
EvaluateCurveToLimits. . When
LinearInterpolationOfTable is selected, the data
entered is evaluated within the limits of the data set and the
minimum/maximum value of x and output inputs are used only
within the boundary of the table limits (i.e., are only used
to limit interpolation). A complete data set is required. For
each X variable, entries must include all Y variables and
associated curve output (i.e., a complete table, no gaps or
missing data). Extrapolation of the data set is not allowed.
When LagrangeInterpolationLinearExtrapolation is
selected, the lookup table is evaluated using Lagrange’s form
of the interpolating polynomial. The order of the polynomial
is inferred to be one less than the input in the Number of
Interpolation Points field below. When
EvaluateCurveToLimits is selected, the coefficients
(i.e., C in the equation above) of the polynomial equation are
calculated and used to determine the table output within the
limits specified in the following fields (or the tabular data,
whichever provide the larger range). If the minimum/maximum
fields below are not entered, the limits of the data set are
used. A complete table is not required when using this method,
however, a minimum number of data is required to perform the
regression analysis. The minimum number of data pairs required
for this choice is 6 data pairs for both bi-quadratic and
quadratic-linear curve types. If insufficient data is
provided, the simulation reverts to interpolating the tabular
data. The performance curve is written to the eio file when
the output diagnotics flag DisplayAdvancedVariables is used
(ref. Output:Diagnostics,
DisplayAdvancedVariables). A regression analysis may only be
performed on lookup tables with one or two independent
variables.
The format specifier which determines the method used to
read the lookup table. The only valid choice at this time is
SingleLineIndependentVariableWithMatrix. When
SingleLineIndependentVariableWithMatrix is selected,
a free format is used as shown below. The format shown below
assumes the output values are in ascending order for both
independent variables 1 and 2. Tabular data are entered in 3
groups of data, the header, the independent variable values,
and the tabular data matrix. A summary of the external file
format is shown below.
Key:
IV = independent variable (i.e., the X1, or X2, etc)
NIV = number of independent variables (i.e., number of values for X1, or X2, etc.)
IVV = independent variable value (i.e., the value for X1, or X2, etc.)
NIV1 = number of values for independent variable #1 (i.e., X1)
NIV2 = number of values for independent variable #2 (i.e., X2)
NIV3 = number of values for independent variable #3 (i.e., X3)
NIV4 = number of values for independent variable #4 (i.e., X4)
NIV5 = number of values for independent variable #5 (i.e., X5)
OV = output value
Header:
Row 1: <NIV>, <NIV1>, <NIV2> (only used if NIV>1), <NIV3> (only used if NIV>2),
<NIV4> (only used if NIV>3), <NIV5> (only used if NIV>4)
Independent Variable Values:
Row 2: <IVV1 to IVVn for IV1> where n = NIV1 (max = 10)
Row 2a (row included only when NIV > 1): IVV1 to IVVn for IV2 where n = NIV2 (max = 10)
Row 2b (row included only when NIV > 2): IVV1 to IVVn for IV3 where n = NIV3 (max = 10)
Row 2c (row included only when NIV > 3): IVV1 to IVVn for IV4 where n = NIV4 (max = 10)
Row 2d (row included only when NIV > 4): IVV1 to IVVn for IV5 where n = NIV5 (max = 10)
Tabular Data Matrix Format (repeat rows 3 and 4(1) - 4(m) for each occurrence of a unique data pair for independent variable #3, #4, and #5):
Row 3 (row included only when NIV > 2): IVVn for IV3, IVVn for IV4 (included only when NIV > 3), IVVn for IV5 (included only when NIV > 4), (where n = a unique value for the independent variable)
Row 4(1): OV1/1 to OVn/1 for each value of IV1 where n = NIV1 representing IV2(1)
Row 4(2): OV1/2 to OVn/2 for each value of IV1 where n = NIV1 representing IV2(2)
Row 4(3): OV1/3 to OVn/3 for each value of IV1 where n = NIV1 representing IV2(3)
...
Row 4(m): OV1/m to OVn/m for each value of IV1 where n = NIV1 representing IV2(m) where m = NIV2
Field: Number of
Interpolation Points[LINK]
This field specifies the number of data points to be used
in the lookup table interpolation. The value specified in this
field should be 1 greater than the order (or degree) of the
polynomial used for interpolation. For example, if 2 is
entered here, the polynomial is assumed to be first order
where only 2 data points are required to calculate the table
solution. If 3 is entered here, the polynomial is assumed to
be second order and 3 data points would be required to
calculate the table solution. Linear extrapolation is always
used when the independent variable values are near the lower
edge or outside the range of the table. The interpolation
points selected are always the nearest data point greater than
the independent variable with 1 or more values less than the
independent variable. For example, if 3 interpolation points
are used, the data point greater than the independent variable
and 2 data points less than the indpenedent variable are used
to determine the table solution. If the independent variable
exactly equals a table reference point, that value is used as
the table solution.
Field: External File
Name[LINK]
The name of an external file that represents the tabular
data. This file would include all data after the Output Unit
Type field below starting with the number of independent
variables and continuing until all input and output values
have been entered. The tabular data may use either comma,
space or tab delimited format. The field should include a full
path with file name, for best results. The field must be <=
100 characters. The file name must not include commas or an
exclamation point. A relative path or a simple file name
should work with version 7.0 or later when using EP-Launch
even though EP-Launch uses temporary directories as part of
the execution of EnergyPlus. If using RunEPlus.bat to run
EnergyPlus from the command line, a relative path or a simple
file name may work if RunEPlus.bat is run from the folder that
contains EnergyPlus.exe.
Field: X1 Sort Order[LINK]
The choice field specifies the order of the lookup table
data for the 1st independent variable. Valid
choices are Increasing or Decreasing. If
increasing is selected, then the order of the data is from
lowest value of the 1st independent variable to
highest. If decreasing is selected, then the order of the data
is from highest value of the 1st independent
variable to lowest.
Field: X2 Sort Order[LINK]
The choice field specifies the order of the lookup table
data for the 2nd independent variable. Valid
choices are Increasing or Decreasing. If
increasing is selected, then the order of the data is from
lowest value of the 2nd independent variable to
highest. If decreasing is selected, then the order of the data
is from highest value of the 2nd independent
variable to lowest.
Field: Minimum Value of
X1[LINK]
The minimum allowable value of X1. Values of X1 less than
the minimum will be replaced by the minimum. This field can
only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
Field: Maximum Value of
X1[LINK]
The maximum allowable value of X1. Values of X1 greater
than the maximum will be replaced by the maximum. This field
can only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
Field: Minimum Value of
X2[LINK]
The minimum allowable value of X2. Values of X2 less than
the minimum will be replaced by the minimum. This field can
only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit. This field is only used when the number
of independent variables is greater than 1.
Field: Maximum Value of
X2[LINK]
The maximum allowable value of X2. Values of X2 greater
than the maximum will be replaced by the maximum. This field
can only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit. This field is only used when the number
of independent variables is greater than 1.
Field: Minimum Value of
X3[LINK]
The minimum allowable value of X3. Values of X3 less than
the minimum will be replaced by the minimum. This field can
only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit. This field is only used when the number
of independent variables is greater than 2.
Field: Maximum Value of
X3[LINK]
The maximum allowable value of X3. Values of X3 greater
than the maximum will be replaced by the maximum. This field
can only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit. This field is only used when the number
of independent variables is greater than 2.
Field: Minimum Value of
X4[LINK]
The minimum allowable value of X4. Values of X4 less than
the minimum will be replaced by the minimum. This field can
only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit. This field is only used when the number
of independent variables is greater than 3.
Field: Maximum Value of
X4[LINK]
The maximum allowable value of X4. Values of X4 greater
than the maximum will be replaced by the maximum. This field
can only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit. This field is only used when the number
of independent variables is greater than 3.
Field: Minimum Value of
X5[LINK]
The minimum allowable value of X5. Values of X5 less than
the minimum will be replaced by the minimum. This field can
only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit. This field is only used when the number
of independent variables is greater than 4.
Field: Maximum Value of
X5[LINK]
The maximum allowable value of X5. Values of X5 greater
than the maximum will be replaced by the maximum. This field
can only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit. This field is only used when the number
of independent variables is greater than 4.
Field: Minimum Curve
Output[LINK]
The minimum allowable value of the evaluated curve. Values
less than the minimum will be replaced by the minimum. This
field can only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
Field: Maximum Curve
Output[LINK]
The maximum allowable value of the evaluated curve. Values
greater than the maximum will be replaced by the maximum. This
field can only limit extrapolation when the Interpolation
Method is selected as EvaluateCurveToLimits or
LagrangeInterpolationLinearExtrapolation. This filed can
be used to limit interpolation using any Interpolation
Method. If this field is left blank, the data set
determines the limit.
This field is used to indicate the kind of units that may
be associated with the X1 values. It is used by IDF Editor to
display the appropriate SI and IP units for the Minimum Value
of X1 and Maximum Value of X1. The unit conversion is not
applied to the coefficients. The available options are shown
below. If none of these options are appropriate, select
Dimensionless which will have no unit
conversion.
- Dimensionless
- Temperature
- VolumetricFlow
- MassFlow
- Distance
- Power
This field is used to indicate the kind of units that may
be associated with the X2 values. It is used by IDF Editor to
display the appropriate SI and IP units for the Minimum Value
of X2 and Maximum Value of X2. The unit conversion is not
applied to the coefficients. The available options are shown
below. If none of these options are appropriate, select
Dimensionless which will have no unit
conversion.
- Dimensionless
- Temperature
- VolumetricFlow
- MassFlow
- Distance
- Power
This field is used to indicate the kind of units that may
be associated with the X3 values. It is used by IDF Editor to
display the appropriate SI and IP units for the Minimum Value
of X3 and Maximum Value of X3. The unit conversion is not
applied to the coefficients. The available options are shown
below. If none of these options are appropriate, select
Dimensionless which will have no unit
conversion.
- Dimensionless
- Temperature
- VolumetricFlow
- MassFlow
- Distance
- Power
This field is used to indicate the kind of units that may
be associated with the X4 values. It is used by IDF Editor to
display the appropriate SI and IP units for the Minimum Value
of X4 and Maximum Value of X4. The unit conversion is not
applied to the coefficients. The available options are shown
below. If none of these options are appropriate, select
Dimensionless which will have no unit
conversion.
- Dimensionless
- Temperature
- VolumetricFlow
- MassFlow
- Distance
- Power
This field is used to indicate the kind of units that may
be associated with the X5 values. It is used by IDF Editor to
display the appropriate SI and IP units for the Minimum Value
of X5 and Maximum Value of X5. The unit conversion is not
applied to the coefficients. The available options are shown
below. If none of these options are appropriate, select
Dimensionless which will have no unit
conversion.
- Dimensionless
- Temperature
- VolumetricFlow
- MassFlow
- Distance
- Power
Field: Output Unit Type[LINK]
This field is used to indicate the kind of units that may
be associated with the output values. It is used by IDF Editor
to display the appropriate SI and IP units for the Minimum
Curve Output and Maximum Curve Output. The unit conversion is
not applied to the coefficients. The available options are
shown below. If none of these options are appropriate, select
Dimensionless which will have no unit
conversion.
- Dimensionless
- Capacity
- Power
The following inputs describe the data set. These values
may also be placed in an external file starting with Field #1.
If an external file name is entered above, the following
fields are not used. Data are entered in a specific order
according to the number and quantity of independent variables.
The data input format is described here in 3 groups as Header,
Independent Variable Values, and the Tabular Data. The header
is always the first line in the data set and represents the
number of independent varibles followed by the number of
values for each independent variable. The independent variable
values are listed next and represent the values of each
independent variable on a separate line. These values are only
listed once at the top of the data set and are listed in
ascending order. The number of independent variables, the
first number in the header, specifies how many lines, or rows,
make up this section of tabular data. The remaining lines are
repeated as many times as necessary to completely describe the
tabular data. The values of independent variables 3 - n are
listed on a single line followed by a matrix of data that
represent the table output corresponding to independent
variables 1 and 2.
Line 1: The first number specified is the number of
independent variables followed by the number of variables for
each independent variable.
- Independent Variable Values:
Line 1: the n values for the first independent variable as
specified in the header.
Line 2: the n values for the second independent variable as
specified in the header if the number of independent variables
is greater than 1. This line is not required if the number of
independent variables is less than 2.
Line 3: the n values for the third independent variable as
specified in the header if the number of independent variables
is greater than 2. This line is not required if the number of
independent variables is less than 3.
Line 4: the n values for the fourth independent variable as
specified in the header if the number of independent variables
is greater than 3. This line is not required if the number of
independent variables is less than 4.
Line 5: the n values for the fifth independent variable as
specified in the header if the number of independent variables
is greater than 4. This line is not required if the number of
independent variables is less than 5.
Line 1: the values of the 3rd through nth
independent variables
Line 2 - m (where m-1 equals the number of variables for
the second independent variable): the tabular data
corresponding to the 1st independent variable (the
number of inputs on this line equals the number of values for
1st independent variable), the mth values for the
2nd independent variable and corresponding to the
values for the 3rd - nth independent variables (see
Line 1 above for Tabular Data).
Three examples are provided here as this can be difficult
to describe in text. This example assumes that the table data
are listed in ascending order from lowest to highest.
- One Independent Variable:
- Header:
1, 5, (1 independent variable with 5 values for the single
independent variable)
- Independent Variable Values:
70, 72, 74, 76, 78, (the five values for the single
independent variable, these values are always listed in
ascending order)
0.1, 0.3, 0.5, 0.7, 0.9; (the table values associated with
the independent variable values listed previously - Note:
these values may be read in ascending or descending order
based on the input in the X1 Sort Order field above). Example:
If X1 Sort Order is ascending, 0.1 corresponds to the value of
70 for the first independent variable. If X1 Sort Order is
descending, then 0.1 corresponds to the value of 78 for the
first independent variable. The use of ascending order
provides a direct correlation to inputs for the Independent
Variable Values group above.
- Two Independent Variables:
- Header:
2, 5, 6, (2 independent variables with 5 and 6 values for
the 1st and 2nd independent variables,
respectively)
- Independent Variable Values:
70, 72, 74, 76, 78, (the five values for the 1st
independent variable, these values are always listed in
ascending order)
32, 45, 68, 81, 94, 107, (the six values for the 2nd
independent variable, these values are always listed in
ascending order)
0.1, 0.3, 0.5, 0.7, 0.9, (the first five table values
associated with each value of the 1st independent
variable and the first value (32) of the second independent
variable listed previously - Note: these values may be listed
in ascending or descending order based on the input in the X1
Sort Order field above. Each of these rows may also be listed
in ascending or descending order based on the input in the X2
Sort Order field above).
0.2, 0.4, 0.6, 0.8, 1.0, (the second five table values
associated with each value of the 1st independent
variable and the second value (45) of the second independent
variable listed previously).
0.3, 0.5, 0.7, 0.9, 1.1, (the third five table values
associated with each value of the 1st independent
variable and the third value (68) of the second independent
variable listed previously).
0.4, 0.6, 0.8, 1.0, 1.2, (the fourth five table values
associated with each value of the 1st independent
variable and the fourth value (81) of the second independent
variable listed previously).
0.5, 0.7, 0.9, 1.1, 1.3, (the fifth five table values
associated with each value of the 1st independent
variable and the fifth value (94) of the second independent
variable listed previously).
0.6, 0.8, 1.0, 1.2, 1.4; (the sixth five table values
associated with each value of the 1st independent
variable and the sixth value (107) of the second independent
variable listed previously).
- Three Independent Variables:
- Header:
3, 5, 6, 2, (3 independent variables with 5, 6 and 2 values
for the 1st , 2nd, and 3rd
independent variables)
- Independent Variable Values:
70, 72, 74, 76, 78, (the five values for the 1st
independent variable, these values are always listed in
ascending order)
32, 45, 68, 81, 94, 107, (the six values for the 2nd
independent variable, these values are always listed in
ascending order)
15.5, 45.5, (the two values for the 3rd
independent variable, these values are always listed in
ascending order)
15.5, (the first value for the 3rd independent
variable - values for the 4th and 5th
independent variable are also listed on this line if they are
used)
0.1, 0.3, 0.5, 0.7, 0.9, (the table values associated with
each value of the 1st independent variable, the
first value (32) of the second independent variable, and the
first value (15.5) of the 3rd independent
variable). Note: these values may be listed in ascending or
descending order based on the input in the X1 Sort Order field
above).
0.2, 0.4, 0.6, 0.8, 1.0, (the table values associated with
each value of the 1st independent variable, the
second value (45) of the second independent variable, and the
first value (15.5) of the 3rd independent
variable).
0.3, 0.5, 0.7, 0.9, 1.1, (the table values associated with
each value of the 1st independent variable, the
third value (68) of the second independent variable, and the
first value (15.5) of the 3rd independent
variable).
0.4, 0.6, 0.8, 1.0, 1.2, (the table values associated with
each value of the 1st independent variable, the
fourth value (81) of the second independent variable, and the
first value (15.5) of the 3rd independent
variable).
0.5, 0.7, 0.9, 1.1, 1.3, (the table values associated with
each value of the 1st independent variable, the
fifth value (94) of the second independent variable, and the
first value (15.5) of the 3rd independent
variable).
0.6, 0.8, 1.0, 1.2, 1.4. (the table values associated with
each value of the 1st independent variable, the
sixth value (107) of the second independent variable, and the
first value (15.5) of the 3rd independent
variable).
45.5, (the second value for the 3rd independent
variable - values for the 4th and 5th
independent variable are also listed on this line if they are
used)
1.1, 1.3, 1.5, 1.7, 1.9, (the table values associated with
each value of the 1st independent variable, the
first value (32) of the second independent variable, and the
second value (45.5) of the 3rd independent
variable).
1.2, 1.4, 1.6, 1.8, 2.0, (the table values associated with
each value of the 1st independent variable, the
second value (45) of the second independent variable, and the
second value (45.5) of the 3rd independent
variable).
1.3, 1.5, 1.7, 1.9, 2.1, (the table values associated with
each value of the 1st independent variable, the
third value (68) of the second independent variable, and the
second value (45.5) of the 3rd independent
variable).
1.4, 1.6, 1.8, 2.0, 2.2, (the table values associated with
each value of the 1st independent variable, the
fourth value (81) of the second independent variable, and the
second value (45.5) of the 3rd independent
variable).
1.5, 1.7, 1.9, 2.1, 2.3, (the table values associated with
each value of the 1st independent variable, the
fifth value (94) of the second independent variable, and the
second value (45.5) of the 3rd independent
variable).
1.6, 1.8, 2.0, 2.2, 2.4. (the table values associated with
each value of the 1st independent variable, the
sixth value (107) of the second independent variable, and the
second value (45.5) of the 3rd independent
variable).
Note: The following fields define the tabular data as
described in the previous examples. These field values depend
on the number and quantity of independent variables used in
the table. The tabular data can be entered in the following
fields or entered using an external file. These fields are
echoed to the eio file as a check when the output diganostics
flag DisplayAdvancedVariables is used (ref. Output:Diagnostics,
DisplayAdvancedVariables). The normalization value is not
included in the echoed values.
Field:
Field #1 (NumberOfIndependentVariables)[LINK]
The number of independent variables used in the lookup
table. This number (n) can range from 1 to 5. The number
entered here will define the following n fields as the number
of values for these n independent variables. This is the first
number in the external file as shown in the previous
examples.
Field:
Field #2 (NumberOfValuesForIndependentVariable1)[LINK]
The number of values for the first independent variable.
This is the second number in the tabular data and resides on
the same line as Field #1.
Field: Field
#3 (DeterminedByPreviousFields)[LINK]
The value specified in this field is dependent on the
number entered in Field #1. If a 1 is entered in Field #1,
this field represents the first value of the single
independent variable. The number of values entered in Field
#3-#n will be equal to the number entered in Field #2. Values
entered in fields #3-#n are always entered in increasing value
(ascending order). If a number greater than 1 is entered in
Field #1, this field represents the number of values for the
second independent variable.
Field: Field #4[LINK]
The value specified in this field is dependent on the
number entered in Field #1. If a 1 is entered in Field #1,
this field represents the second value of the single
independent variable. The number of values entered in Field
#3-#n will be equal to the number entered in Field #2. Values
entered in fields #3-#n are always entered in increasing value
(ascending order). If a 2 is entered in Field #1, this field
represents the first value of the first independent variable.
If a number greater than 2 is entered in Field #1, this field
represents the number of values for the third independent
variable.
Following is an example input for a Table:MultiVariableLookup
object:
Table:MultiVariableLookup,
HPACCoolCapFT, !- Name
LagrangeinterpolationLinearExtrapolation, !- Interpolation Method
3, !- Number of Interpolation Points
BiQuadratic, !- Interpolation Type
SingleLineIndependentVariableWithMatrix, !- Table Data Format
, !- External File Name
ASCENDING, !- X1 Sort Order
ASCENDING, !- X2 Sort Order
24999.9597049817, !- Normalization reference
12.77778, !- Minimum Value of X1,
23.88889, !- Maximum Value of X1,
18.0, !- Minimum Value of X2,
46.11111, !- Maximum Value of X2,
, !- Minimum Value of X3
, !- Maximum Value of X3
, !- Minimum Value of X4
, !- Maximum Value of X4
, !- Minimum Value of X5
, !- Maximum Value of X5
, !- Minimum Table Output
, !- Maximum Table Output
Temperature, !- Input Unit Type for X1
Temperature, !- Input Unit Type for X2
, !- Input Unit Type for X3
, !- Input Unit Type for X4
, !- Input Unit Type for X5
Dimensionless, !- Output Unit Type
2, 6, 7,
12.77778, 15, 18, 19.44448943, 21, 23.88889,
18, 24, 30, 35, 36, 41, 46.11111,
24421.69383, 25997.3589, 28392.31868, 29655.22876, 31094.97495, 33988.3473,
22779.73113, 24352.1562, 26742.74198, 28003.546, 29441.02425, 32330.1846,
21147.21662, 22716.4017, 25102.61348, 26361.31143, 27796.52175, 30681.4701,
19794.00525, 21360.49033, 23743.0571, 25000, 26433.32038, 29314.75872,
19524.15032, 21090.0954, 23471.93318, 24728.52506, 26161.46745, 29042.2038,
18178.81244, 19742.05753, 22120.2503, 23375.08713, 24806.13958, 27683.36592,
16810.36004, 18370.84513, 20745.3119, 21998.35468, 23427.47518, 26301.11353;
Lookup Table Outputs[LINK]
The current value of the lookup table. Performance curves
and tables use the same output variable. This value is
averaged over the time step being reported. Inactive or unused
performance curves will show a value of -999 (e.g., equipment
is off, a specific performance curve is not required for this
aspect of the equipment model at this time step, etc.). This
value means that the performance curve was not called during
the simulation and, therefore, not evaluated. This inactive
state value is only set at the beginning of each environment.
When averaging over long periods of time, this inactive state
value may skew results. In this case, use a detaled reporting
frequency (ref. Output:Variable
object) to view results at each HVAC time step.
The current value of the nth independent variable passed to
the performance curve. The order of the independent variables
is in the same order as the model equation represented by this
performance curve object. This value is averaged over the time
step being reported.
HVAC,Average,Performance Curve Output Value []
HVAC,Average,Performance Curve Input Variable 1 Value []
HVAC,Average,Performance Curve Input Variable 2 Value []
HVAC,Average,Performance Curve Input Variable 3 Value []
HVAC,Average,Performance Curve Input Variable 4 Value []
HVAC,Average,Performance Curve Input Variable 5 Value []
Group - Performance Tables[LINK]
This group of objects consists of tabular data which are used to characterize the performance of HVAC equipment. The use of performance tables eliminate the need to perform a regression analysis to calculate the performance curve equation coefficients. Two performance tables are available to represent any performance curve having one or two independent variables. The tabular data is entered as data pairs and represent each independent variable followed by the table output at that condition. When using these two performance table objects, a regression analysis may be performed during the simulation to create the associated performance curve. The regression analysis is performed when the user requests to evaluate the curve to the limits specified (see Interpolation Method input field). The performance curve that is created is used throughout the simulation and is also written to the eio file when the user sets the diagnostics output flag DisplayAdvancedVariables (ref. Output:Diagnostics, DisplayAdvancedVariables) This performance curve object may be directly used in future input files. The following descriptions define the input requirements for the performance table objects.
Table:OneIndependentVariable[LINK]
Input for the data table consists of a table name, the curve type, the interpolation method, and the data pairs representing the polynomial equation. Optional inputs for minimum and maximum values for the independent variable and curve minimum and maximum may be used to limit the output of the table when evaluating the regression curve (e.g., limit extrapolation). The existing performance curves represented by this table object are:
\[Linear\,\,Curve:\,\,\,Output = {C_1} + {C_2}x\]
\[Quadratic\,\,Curve:\,\,\,Output = {C_1} + {C_2}x + {C_3}{x^2}\]
\[Cubic\,\,Curve:\,\,\,Output = {C_1} + {C_2}x + {C_3}{x^2} + {C_4}{x^3}\]
\[Quartic\,\,Curve:\,\,\,Output = {C_1} + {C_2}x + {C_3}{x^2} + {C_4}{x^3} + {C_5}{x^4}\]
\[Exponent\,\,Curve:\,\,\,Output = {C_1} + {C_2}{x^{{C_3}}}\]
Inputs[LINK]
Field: Name[LINK]
A unique user assigned name for an instance of a performance table. When a table is used, it is referenced by this name. The name of this table object may be used anywhere a valid performance curve object is allowed.
Field: Curve Type[LINK]
The form of the polynomial equation used to represent the tabular data. Choices are Linear, Quadratic, Cubic, Quartic and Exponent. This field is used to determine if this table object is representative of the type of performance table (curve) allowed for a particular application (i.e., if this type of polynomial is allowed to be used as the curve type for other objects). This input infers the polynomial order (or degree). This input also specifies the number of interpolation points if the next field, Interpolation Method is set to LagrangeInterpolationLinearExtrapolation. The number of interpolation points for Linear, Quadratic, Cubic, Quartic, and Exponent are set at 2, 3, 4, 5, and 4, respectively.
Field: Interpolation Method[LINK]
The method used to evaluate the tabular data. Choices are LinearInterpolationOfTable, LagrangeInterpolationLinearExtrapolation and EvaluateCurveToLimits. When LinearInterpolationOfTable is selected, the tabular data is interpolated within the limits of the data set and the following fields are used only within the boundary of the table limits (i.e., are only used to limit interpolation). Extrapolation of the data set is not allowed. When LagrangeInterpolationLinearExtrapolation is selected, a polynomial interpolation routine is used within the table boundaries along with linear extrapolation. Given the valid one independent variable equations above, the polynomial order is up to 5th order. When EvaluateCurveToLimits is selected, the coefficients (i.e., C in the equations above) of the polynomial equation are calculated and used to determine the table output within the limits specified in the following fields. If these fields are not entered, the limits of the tabular data are used. The minimum number of data pairs required for this choice are 2, 3, 4, 5, and 4 data pairs for linear, quadratic, cubic, quartic, and exponent curves, respectively. If insufficient data is provided, the regression analysis is not performed and the simulation reverts to interpolating the tabular data. The performance curve is written to the eio file when the output diagnotics flag DisplayAdvancedVariables is used (ref. Output:Diagnostics, DisplayAdvancedVariables).
Field: Minimum Value of X[LINK]
The minimum allowable value of X. Values of X less than the minimum will be replaced by the minimum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Maximum Value of X[LINK]
The maximum allowable value of X. Values of X greater than the maximum will be replaced by the maximum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Minimum Table Output[LINK]
The minimum allowable value of the table output. Values less than the minimum will be replaced by the minimum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Maximum Table Output[LINK]
The maximum allowable value of the table output. Values greater than the maximum will be replaced by the maximum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Input Unit Type for X1[LINK]
This field is used to indicate the kind of units that may be associated with the x values. It is used by IDF Editor to display the appropriate SI and IP units for the Minimum Value of X and Maximum Value of X. The unit conversion is not applied to the coefficients. The available options are shown below. If none of these options are appropriate, select Dimensionless which will have no unit conversion.
Field: Output Unit Type[LINK]
This field is used to indicate the kind of units that may be associated with the output values. It is used by IDF Editor to display the appropriate SI and IP units for the Minimum Curve Output and Maximum Curve Output. The unit conversion is not applied to the coefficients. The available options are shown below. If none of these options are appropriate, select Dimensionless which will have no unit conversion.
Field: Normalization Reference[LINK]
The normalization point for the data set. This field provides a method for automatically normalizing a set of data. Equipment performance data is typically normalized based on a specific operating condition. Both the output values and minimum/maximum curve limits are normalized. This normalization can be performed simply by entering the data at the reference point. If this field is left blank or a 1 is entered, the data set is assumed to be in the correct format.
Data Pairs[LINK]
The following inputs describe the data set. Data pairs are entered as X and Output pairs where X is the independent variable (i.e., x in the equation above) and Output is the dependent variable (i.e., Output in the equation above). Any number of data pairs may be entered, however, a minimum number of data pairs must be entered and depends on the polynomial equation. Linear (1st order), Quadratic (2nd order), Cubic (3rd order), Quartic (4th order), and Exponent (nth order) polynomials require a minimum of 2, 3, 4, 5, and 4 data pairs, respectively. This minimum requirement is for performing a regression analysis, not interpolating the tabular data. If a regression analysis is not performed (i.e., only table interpolation is used), these minimum requirements are not enforced. If a regression analysis is performed and these minimum requirements are not met, the simulation will revert to table interpolation. These fields may be repeated as many times as necessary to define the tabular data.
Field: X Value #n[LINK]
The value of the independent variable n (i.e., independent variable values for data 1 to number of data pairs).
Field: Output Value #n[LINK]
The value of the dependent variable n (i.e., dependent variable values for data 1 to number of data pairs).
Following is an example input for a Table:OneIndependentVariable object:
Outputs[LINK]
Performance Curve Output Value [][LINK]
The current value of the performance table. Performance curves and tables use the same output variable. This value is averaged over the time step being reported. Inactive or unused performance curves will show a value of -999 (e.g., equipment is off, a specific performance curve is not required for this aspect of the equipment model at this time step, etc.). This value means that the performance curve was not called during the simulation and, therefore, not evaluated. This inactive state value is only set at the beginning of each environment. When averaging over long periods of time, this inactive state value may skew results. In this case, use a detaled reporting frequency (ref. Output:Variable object) to view results at each HVAC time step.
Performance Curve Input Variable 1 Value [][LINK]
The current value of the independent variable passed to the performance curve. This value is averaged over the time step being reported.
Table:TwoIndependentVariables[LINK]
Input for the data table consists of a table name, the curve type, the interpolation method, and the data pairs representing the polynomial equation. Optional inputs for minimum and maximum values for the independent variable, and curve minimum and maximum may be used to limit the output of the table (e.g., limit extrapolation) when evaluating the regression curve instead of the tabular data. The polynomial equations currently represented by this table object are:
\[BiQuadratic\,\,Curve:\,\,\,\,Output = {C_1} + {C_2}x + {C_3}{x^2} + {C_4}y + {C_5}{y^2} + {C_6}xy\]
\[QuadraticLinear\,\,Curve:\,\,\,\,Output = {C_1} + {C_2}x + {C_3}{x^2} + {C_4}y + {C_5}xy + {C_6}{x^2}y\]
Inputs[LINK]
Field: Name[LINK]
A unique user assigned name for an instance of a performance table. When a table is used, it is referenced by this name. The name of this table object may be used anywhere a valid performance curve object is allowed.
Field: Curve Type[LINK]
The form of the polynomial equation represented by the entered data. The only valid choices are BiQuadratic and QuadraticLinear. This field is used to determine if this table object is representative of the type of performance table (curve) allowed for a particular equipment model (i.e., if this type of polynomial is allowed to be used as the curve type for specific input fields). A minimum of 6 data pairs are required when selecting EvaluateCurveToLimits in the following field. This input also specifies the number of interpolation points if the next field, Interpolation Method is set to LagrangeInterpolationLinearExtrapolation. The number of interpolation points for BiQuadratic and QuadraticLinear are set at 6.
Field: Interpolation Method[LINK]
The method used to evaluate the tabular data. Choices are LinearInterpolationOfTable, LagrangeInterpolationLinearExtrapolation, and EvaluateCurveToLimits. When LinearInterpolationOfTable is selected, the data entered is evaluated within the limits of the data set and the following fields are used only within the boundary of the table limits (i.e., are only used to limit interpolation). A complete data set is required. For each X variable, entries must include all Y variables and associated curve output (i.e., a complete table, no gaps or missing data). Extrapolation of the data set is not allowed. When LagrangeInterpolationLinearExtrapolation is selected, a polynomial interpolation routine is used within the table boundaries along with linear extrapolation. Given the valid equations above, the polynomial order is fixed at 2 which infers that 3 data points will be used for interpolation. When EvaluateCurveToLimits is selected, the coefficients (i.e., C in the equations above) of the polynomial equation are calculated and used to determine the table output within the limits specified in the following fields (or the tabular data, whichever provide the larger range). If the following fields are not entered, the limits of the data set are used. A complete table is not required when using this method, however, a minimum number of data is required to perform the regression analysis. The minimum number of data pairs required for this choice is 6 data pairs for both bi-quadratic and quadratic-linear curve types. If insufficient data is provided, the simulation reverts to interpolating the tabular data. The performance curve is written to the eio file when the output diagnotics flag DisplayAdvancedVariables is used (ref. Output:Diagnostics, DisplayAdvancedVariables).
Field: Minimum Value of X[LINK]
The minimum allowable value of X. Values of X less than the minimum will be replaced by the minimum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Maximum Value of X[LINK]
The maximum allowable value of X. Values of X greater than the maximum will be replaced by the maximum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Minimum Value of Y[LINK]
The minimum allowable value of Y. Values of Y less than the minimum will be replaced by the minimum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Maximum Value of Y[LINK]
The maximum allowable value of Y. Values of Y greater than the maximum will be replaced by the maximum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Minimum Table Output[LINK]
The minimum allowable value of the table output. Values less than the minimum will be replaced by the minimum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Maximum Table Output[LINK]
The maximum allowable value of the table output. Values greater than the maximum will be replaced by the maximum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Input Unit Type for X[LINK]
This field is used to indicate the kind of units that may be associated with the X values. It is used by IDF Editor to display the appropriate SI and IP units for the Minimum Value of X and Maximum Value of X. The unit conversion is not applied to the coefficients. The available options are shown below. If none of these options are appropriate, select Dimensionless which will have no unit conversion.
Field: Input Unit Type for Y[LINK]
This field is used to indicate the kind of units that may be associated with the Y values. It is used by IDF Editor to display the appropriate SI and IP units for the Minimum Value of Y and Maximum Value of Y. The unit conversion is not applied to the coefficients. The available options are shown below. If none of these options are appropriate, select Dimensionless which will have no unit conversion.
Field: Output Unit Type[LINK]
This field is used to indicate the kind of units that may be associated with the output values. It is used by IDF Editor to display the appropriate SI and IP units for the Minimum Curve Output and Maximum Curve Output. The unit conversion is not applied to the coefficients. The available options are shown below. If none of these options are appropriate, select Dimensionless which will have no unit conversion.
Field: Normalization Reference[LINK]
The normalization point for the data set. This field provides a method for automatically normalizing a set of data. Equipment performance data is typically normalized based on a specific operating condition. Both the output values and minimum/maximum curve limits are normalized as applicable. This normalization can be performed simply by entering the data at the reference point. If this field is left blank or a 1 is entered, the data set is assumed to be in the correct format.
Data Pairs[LINK]
The following inputs describe the data set. Data pairs are entered as X, Y and Output pairs where X and Y are the independent variables (i.e., x and y in the equations above) and Output is the dependent variable (i.e., Output in the equation above). Any number of data pairs may be entered, however, a minimum number of data pairs must be entered and depends on the polynomial equation. BiQuadratic and QuadraticLinear (2nd order with 2 independent variables) require a minimum of 6 data pairs. This minimum requirement is for performing a regression analysis, not interpolating the tabular data. If a regression analysis is not performed (i.e., only table interpolation is used), these minimum requirements are not enforced. If a regression analysis is performed and these minimum requirements are not met, the simulation will revert to table interpolation. These fields may be repeated as many times as necessary to define the tabular data.
Field: X Value #n[LINK]
The value of the first independent variable n (i.e., first independent variable values for data pair 1 to number of data pairs).
Field: Y Value #n[LINK]
The value of the second independent variable n (i.e., second independent variable values for data pair 1 to number of data pairs).
Field: Output Value #n[LINK]
The value of the dependent variable n (i.e., dependent variable values for data pair 1 to number of data pairs).
Following is an example input for a Table:TwoIndependentVariable object:
Outputs[LINK]
Performance Curve Output Value [][LINK]
The current value of the performance table. Performance curves and tables use the same output variable. This value is averaged over the time step being reported. Inactive or unused performance curves will show a value of -999 (e.g., equipment is off, a specific performance curve is not required for this aspect of the equipment model at this time step, etc.). This value means that the performance curve was not called during the simulation and, therefore, not evaluated. This inactive state value is only set at the beginning of each environment. When averaging over long periods of time, this inactive state value may skew results. In this case, use a detaled reporting frequency (ref. Output:Variable object) to view results at each HVAC time step.
Performance Curve Input Variable 1 Value [][LINK]
Performance Curve Input Variable 2 Value [][LINK]
The current value of the first and second independent variable passed to the performance curve. The order of the independent variables is in the same order as the model equation represented by this performance curve object. This value is averaged over the time step being reported.
Lookup Tables[LINK]
Lookup tables are useful for determining the results of a nth order polynomial without the need to calculate the polynomial coefficients. The Lagrange method for interpolation is currently the only method available for polynomial interpolation. LinearInterpolationOfTable and EvaluateCurveToLimits may also be used. The multi-variable lookup table can represent from 1 to 5 independent variables and can interpolate these independent variables up to a 4th order polynomial. The polynomial order is assumed to be the number of interpolation points (n) minus 1. Polynomial interpolation of tabular data takes place when the values of the independent variables are within the upper table boundary and at least n data points are available when approaching the lower table boundary for any independent variable. When any independent variable value is outside the table limits, linear extrapolation is used to predict the table result and is based on the two nearest data points in the table for that particular independent variable.
Table:MultiVariableLookup[LINK]
Input for the multi-variable data table consists of a table name, the interpolation method, the number of points to be used for interpolation, an optional external file name, and, if an external file name is not entered, the tabular data. Optional inputs for minimum and maximum values for the independent variable, and curve minimum and maximum may be used to limit the output of the table (e.g., limit extrapolation).
Inputs[LINK]
Field: Name[LINK]
A unique user assigned name for an instance of a lookup table. When a table is used, it is referenced by this name. The name of this table object may be used anywhere a valid performance curve object is allowed.
Field: Curve Type[LINK]
The order of the polynomial used to represent the tabular data. Choices are Linear, Quadratic, Cubic, Quartic, BiQuadratic, QaudraticLinear, BuCibic. This field is used to determine if this table object is representative of the type of performance table (curve) allowed for a particular application (i.e., if this type of polynomial is allowed to be used as the curve type for other objects). This input also infers the polynomial order (or degree).
Field: Interpolation Method[LINK]
The method used to evaluate the lookup table. The choices are LinearInterpolationOfTable, LagrangeInterpolationLinearExtrapolation, and EvaluateCurveToLimits. . When LinearInterpolationOfTable is selected, the data entered is evaluated within the limits of the data set and the minimum/maximum value of x and output inputs are used only within the boundary of the table limits (i.e., are only used to limit interpolation). A complete data set is required. For each X variable, entries must include all Y variables and associated curve output (i.e., a complete table, no gaps or missing data). Extrapolation of the data set is not allowed. When LagrangeInterpolationLinearExtrapolation is selected, the lookup table is evaluated using Lagrange’s form of the interpolating polynomial. The order of the polynomial is inferred to be one less than the input in the Number of Interpolation Points field below. When EvaluateCurveToLimits is selected, the coefficients (i.e., C in the equation above) of the polynomial equation are calculated and used to determine the table output within the limits specified in the following fields (or the tabular data, whichever provide the larger range). If the minimum/maximum fields below are not entered, the limits of the data set are used. A complete table is not required when using this method, however, a minimum number of data is required to perform the regression analysis. The minimum number of data pairs required for this choice is 6 data pairs for both bi-quadratic and quadratic-linear curve types. If insufficient data is provided, the simulation reverts to interpolating the tabular data. The performance curve is written to the eio file when the output diagnotics flag DisplayAdvancedVariables is used (ref. Output:Diagnostics, DisplayAdvancedVariables). A regression analysis may only be performed on lookup tables with one or two independent variables.
Field: Table Data Format[LINK]
The format specifier which determines the method used to read the lookup table. The only valid choice at this time is SingleLineIndependentVariableWithMatrix. When SingleLineIndependentVariableWithMatrix is selected, a free format is used as shown below. The format shown below assumes the output values are in ascending order for both independent variables 1 and 2. Tabular data are entered in 3 groups of data, the header, the independent variable values, and the tabular data matrix. A summary of the external file format is shown below.
Field: Number of Interpolation Points[LINK]
This field specifies the number of data points to be used in the lookup table interpolation. The value specified in this field should be 1 greater than the order (or degree) of the polynomial used for interpolation. For example, if 2 is entered here, the polynomial is assumed to be first order where only 2 data points are required to calculate the table solution. If 3 is entered here, the polynomial is assumed to be second order and 3 data points would be required to calculate the table solution. Linear extrapolation is always used when the independent variable values are near the lower edge or outside the range of the table. The interpolation points selected are always the nearest data point greater than the independent variable with 1 or more values less than the independent variable. For example, if 3 interpolation points are used, the data point greater than the independent variable and 2 data points less than the indpenedent variable are used to determine the table solution. If the independent variable exactly equals a table reference point, that value is used as the table solution.
Field: External File Name[LINK]
The name of an external file that represents the tabular data. This file would include all data after the Output Unit Type field below starting with the number of independent variables and continuing until all input and output values have been entered. The tabular data may use either comma, space or tab delimited format. The field should include a full path with file name, for best results. The field must be <= 100 characters. The file name must not include commas or an exclamation point. A relative path or a simple file name should work with version 7.0 or later when using EP-Launch even though EP-Launch uses temporary directories as part of the execution of EnergyPlus. If using RunEPlus.bat to run EnergyPlus from the command line, a relative path or a simple file name may work if RunEPlus.bat is run from the folder that contains EnergyPlus.exe.
Field: X1 Sort Order[LINK]
The choice field specifies the order of the lookup table data for the 1st independent variable. Valid choices are Increasing or Decreasing. If increasing is selected, then the order of the data is from lowest value of the 1st independent variable to highest. If decreasing is selected, then the order of the data is from highest value of the 1st independent variable to lowest.
Field: X2 Sort Order[LINK]
The choice field specifies the order of the lookup table data for the 2nd independent variable. Valid choices are Increasing or Decreasing. If increasing is selected, then the order of the data is from lowest value of the 2nd independent variable to highest. If decreasing is selected, then the order of the data is from highest value of the 2nd independent variable to lowest.
Field: Minimum Value of X1[LINK]
The minimum allowable value of X1. Values of X1 less than the minimum will be replaced by the minimum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Maximum Value of X1[LINK]
The maximum allowable value of X1. Values of X1 greater than the maximum will be replaced by the maximum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Minimum Value of X2[LINK]
The minimum allowable value of X2. Values of X2 less than the minimum will be replaced by the minimum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit. This field is only used when the number of independent variables is greater than 1.
Field: Maximum Value of X2[LINK]
The maximum allowable value of X2. Values of X2 greater than the maximum will be replaced by the maximum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit. This field is only used when the number of independent variables is greater than 1.
Field: Minimum Value of X3[LINK]
The minimum allowable value of X3. Values of X3 less than the minimum will be replaced by the minimum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit. This field is only used when the number of independent variables is greater than 2.
Field: Maximum Value of X3[LINK]
The maximum allowable value of X3. Values of X3 greater than the maximum will be replaced by the maximum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit. This field is only used when the number of independent variables is greater than 2.
Field: Minimum Value of X4[LINK]
The minimum allowable value of X4. Values of X4 less than the minimum will be replaced by the minimum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit. This field is only used when the number of independent variables is greater than 3.
Field: Maximum Value of X4[LINK]
The maximum allowable value of X4. Values of X4 greater than the maximum will be replaced by the maximum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit. This field is only used when the number of independent variables is greater than 3.
Field: Minimum Value of X5[LINK]
The minimum allowable value of X5. Values of X5 less than the minimum will be replaced by the minimum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit. This field is only used when the number of independent variables is greater than 4.
Field: Maximum Value of X5[LINK]
The maximum allowable value of X5. Values of X5 greater than the maximum will be replaced by the maximum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit. This field is only used when the number of independent variables is greater than 4.
Field: Minimum Curve Output[LINK]
The minimum allowable value of the evaluated curve. Values less than the minimum will be replaced by the minimum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Maximum Curve Output[LINK]
The maximum allowable value of the evaluated curve. Values greater than the maximum will be replaced by the maximum. This field can only limit extrapolation when the Interpolation Method is selected as EvaluateCurveToLimits or LagrangeInterpolationLinearExtrapolation. This filed can be used to limit interpolation using any Interpolation Method. If this field is left blank, the data set determines the limit.
Field: Input Unit Type for X1[LINK]
This field is used to indicate the kind of units that may be associated with the X1 values. It is used by IDF Editor to display the appropriate SI and IP units for the Minimum Value of X1 and Maximum Value of X1. The unit conversion is not applied to the coefficients. The available options are shown below. If none of these options are appropriate, select Dimensionless which will have no unit conversion.
Field: Input Unit Type for X2[LINK]
This field is used to indicate the kind of units that may be associated with the X2 values. It is used by IDF Editor to display the appropriate SI and IP units for the Minimum Value of X2 and Maximum Value of X2. The unit conversion is not applied to the coefficients. The available options are shown below. If none of these options are appropriate, select Dimensionless which will have no unit conversion.
Field: Input Unit Type for X3[LINK]
This field is used to indicate the kind of units that may be associated with the X3 values. It is used by IDF Editor to display the appropriate SI and IP units for the Minimum Value of X3 and Maximum Value of X3. The unit conversion is not applied to the coefficients. The available options are shown below. If none of these options are appropriate, select Dimensionless which will have no unit conversion.
Field: Input Unit Type for X4[LINK]
This field is used to indicate the kind of units that may be associated with the X4 values. It is used by IDF Editor to display the appropriate SI and IP units for the Minimum Value of X4 and Maximum Value of X4. The unit conversion is not applied to the coefficients. The available options are shown below. If none of these options are appropriate, select Dimensionless which will have no unit conversion.
Field: Input Unit Type for X5[LINK]
This field is used to indicate the kind of units that may be associated with the X5 values. It is used by IDF Editor to display the appropriate SI and IP units for the Minimum Value of X5 and Maximum Value of X5. The unit conversion is not applied to the coefficients. The available options are shown below. If none of these options are appropriate, select Dimensionless which will have no unit conversion.
Field: Output Unit Type[LINK]
This field is used to indicate the kind of units that may be associated with the output values. It is used by IDF Editor to display the appropriate SI and IP units for the Minimum Curve Output and Maximum Curve Output. The unit conversion is not applied to the coefficients. The available options are shown below. If none of these options are appropriate, select Dimensionless which will have no unit conversion.
Data Input Format[LINK]
The following inputs describe the data set. These values may also be placed in an external file starting with Field #1. If an external file name is entered above, the following fields are not used. Data are entered in a specific order according to the number and quantity of independent variables. The data input format is described here in 3 groups as Header, Independent Variable Values, and the Tabular Data. The header is always the first line in the data set and represents the number of independent varibles followed by the number of values for each independent variable. The independent variable values are listed next and represent the values of each independent variable on a separate line. These values are only listed once at the top of the data set and are listed in ascending order. The number of independent variables, the first number in the header, specifies how many lines, or rows, make up this section of tabular data. The remaining lines are repeated as many times as necessary to completely describe the tabular data. The values of independent variables 3 - n are listed on a single line followed by a matrix of data that represent the table output corresponding to independent variables 1 and 2.
Line 1: The first number specified is the number of independent variables followed by the number of variables for each independent variable.
Line 1: the n values for the first independent variable as specified in the header.
Line 2: the n values for the second independent variable as specified in the header if the number of independent variables is greater than 1. This line is not required if the number of independent variables is less than 2.
Line 3: the n values for the third independent variable as specified in the header if the number of independent variables is greater than 2. This line is not required if the number of independent variables is less than 3.
Line 4: the n values for the fourth independent variable as specified in the header if the number of independent variables is greater than 3. This line is not required if the number of independent variables is less than 4.
Line 5: the n values for the fifth independent variable as specified in the header if the number of independent variables is greater than 4. This line is not required if the number of independent variables is less than 5.
Line 1: the values of the 3rd through nth independent variables
Line 2 - m (where m-1 equals the number of variables for the second independent variable): the tabular data corresponding to the 1st independent variable (the number of inputs on this line equals the number of values for 1st independent variable), the mth values for the 2nd independent variable and corresponding to the values for the 3rd - nth independent variables (see Line 1 above for Tabular Data).
Three examples are provided here as this can be difficult to describe in text. This example assumes that the table data are listed in ascending order from lowest to highest.
1, 5, (1 independent variable with 5 values for the single independent variable)
70, 72, 74, 76, 78, (the five values for the single independent variable, these values are always listed in ascending order)
0.1, 0.3, 0.5, 0.7, 0.9; (the table values associated with the independent variable values listed previously - Note: these values may be read in ascending or descending order based on the input in the X1 Sort Order field above). Example: If X1 Sort Order is ascending, 0.1 corresponds to the value of 70 for the first independent variable. If X1 Sort Order is descending, then 0.1 corresponds to the value of 78 for the first independent variable. The use of ascending order provides a direct correlation to inputs for the Independent Variable Values group above.
2, 5, 6, (2 independent variables with 5 and 6 values for the 1st and 2nd independent variables, respectively)
70, 72, 74, 76, 78, (the five values for the 1st independent variable, these values are always listed in ascending order)
32, 45, 68, 81, 94, 107, (the six values for the 2nd independent variable, these values are always listed in ascending order)
0.1, 0.3, 0.5, 0.7, 0.9, (the first five table values associated with each value of the 1st independent variable and the first value (32) of the second independent variable listed previously - Note: these values may be listed in ascending or descending order based on the input in the X1 Sort Order field above. Each of these rows may also be listed in ascending or descending order based on the input in the X2 Sort Order field above).
0.2, 0.4, 0.6, 0.8, 1.0, (the second five table values associated with each value of the 1st independent variable and the second value (45) of the second independent variable listed previously).
0.3, 0.5, 0.7, 0.9, 1.1, (the third five table values associated with each value of the 1st independent variable and the third value (68) of the second independent variable listed previously).
0.4, 0.6, 0.8, 1.0, 1.2, (the fourth five table values associated with each value of the 1st independent variable and the fourth value (81) of the second independent variable listed previously).
0.5, 0.7, 0.9, 1.1, 1.3, (the fifth five table values associated with each value of the 1st independent variable and the fifth value (94) of the second independent variable listed previously).
0.6, 0.8, 1.0, 1.2, 1.4; (the sixth five table values associated with each value of the 1st independent variable and the sixth value (107) of the second independent variable listed previously).
3, 5, 6, 2, (3 independent variables with 5, 6 and 2 values for the 1st , 2nd, and 3rd independent variables)
70, 72, 74, 76, 78, (the five values for the 1st independent variable, these values are always listed in ascending order)
32, 45, 68, 81, 94, 107, (the six values for the 2nd independent variable, these values are always listed in ascending order)
15.5, 45.5, (the two values for the 3rd independent variable, these values are always listed in ascending order)
15.5, (the first value for the 3rd independent variable - values for the 4th and 5th independent variable are also listed on this line if they are used)
0.1, 0.3, 0.5, 0.7, 0.9, (the table values associated with each value of the 1st independent variable, the first value (32) of the second independent variable, and the first value (15.5) of the 3rd independent variable). Note: these values may be listed in ascending or descending order based on the input in the X1 Sort Order field above).
0.2, 0.4, 0.6, 0.8, 1.0, (the table values associated with each value of the 1st independent variable, the second value (45) of the second independent variable, and the first value (15.5) of the 3rd independent variable).
0.3, 0.5, 0.7, 0.9, 1.1, (the table values associated with each value of the 1st independent variable, the third value (68) of the second independent variable, and the first value (15.5) of the 3rd independent variable).
0.4, 0.6, 0.8, 1.0, 1.2, (the table values associated with each value of the 1st independent variable, the fourth value (81) of the second independent variable, and the first value (15.5) of the 3rd independent variable).
0.5, 0.7, 0.9, 1.1, 1.3, (the table values associated with each value of the 1st independent variable, the fifth value (94) of the second independent variable, and the first value (15.5) of the 3rd independent variable).
0.6, 0.8, 1.0, 1.2, 1.4. (the table values associated with each value of the 1st independent variable, the sixth value (107) of the second independent variable, and the first value (15.5) of the 3rd independent variable).
45.5, (the second value for the 3rd independent variable - values for the 4th and 5th independent variable are also listed on this line if they are used)
1.1, 1.3, 1.5, 1.7, 1.9, (the table values associated with each value of the 1st independent variable, the first value (32) of the second independent variable, and the second value (45.5) of the 3rd independent variable).
1.2, 1.4, 1.6, 1.8, 2.0, (the table values associated with each value of the 1st independent variable, the second value (45) of the second independent variable, and the second value (45.5) of the 3rd independent variable).
1.3, 1.5, 1.7, 1.9, 2.1, (the table values associated with each value of the 1st independent variable, the third value (68) of the second independent variable, and the second value (45.5) of the 3rd independent variable).
1.4, 1.6, 1.8, 2.0, 2.2, (the table values associated with each value of the 1st independent variable, the fourth value (81) of the second independent variable, and the second value (45.5) of the 3rd independent variable).
1.5, 1.7, 1.9, 2.1, 2.3, (the table values associated with each value of the 1st independent variable, the fifth value (94) of the second independent variable, and the second value (45.5) of the 3rd independent variable).
1.6, 1.8, 2.0, 2.2, 2.4. (the table values associated with each value of the 1st independent variable, the sixth value (107) of the second independent variable, and the second value (45.5) of the 3rd independent variable).
Field: Field #1 (NumberOfIndependentVariables)[LINK]
The number of independent variables used in the lookup table. This number (n) can range from 1 to 5. The number entered here will define the following n fields as the number of values for these n independent variables. This is the first number in the external file as shown in the previous examples.
Field: Field #2 (NumberOfValuesForIndependentVariable1)[LINK]
The number of values for the first independent variable. This is the second number in the tabular data and resides on the same line as Field #1.
Field: Field #3 (DeterminedByPreviousFields)[LINK]
The value specified in this field is dependent on the number entered in Field #1. If a 1 is entered in Field #1, this field represents the first value of the single independent variable. The number of values entered in Field #3-#n will be equal to the number entered in Field #2. Values entered in fields #3-#n are always entered in increasing value (ascending order). If a number greater than 1 is entered in Field #1, this field represents the number of values for the second independent variable.
Field: Field #4[LINK]
The value specified in this field is dependent on the number entered in Field #1. If a 1 is entered in Field #1, this field represents the second value of the single independent variable. The number of values entered in Field #3-#n will be equal to the number entered in Field #2. Values entered in fields #3-#n are always entered in increasing value (ascending order). If a 2 is entered in Field #1, this field represents the first value of the first independent variable. If a number greater than 2 is entered in Field #1, this field represents the number of values for the third independent variable.
Following is an example input for a Table:MultiVariableLookup object:
Lookup Table Outputs[LINK]
Performance Curve Output Value [][LINK]
The current value of the lookup table. Performance curves and tables use the same output variable. This value is averaged over the time step being reported. Inactive or unused performance curves will show a value of -999 (e.g., equipment is off, a specific performance curve is not required for this aspect of the equipment model at this time step, etc.). This value means that the performance curve was not called during the simulation and, therefore, not evaluated. This inactive state value is only set at the beginning of each environment. When averaging over long periods of time, this inactive state value may skew results. In this case, use a detaled reporting frequency (ref. Output:Variable object) to view results at each HVAC time step.
Performance Curve Input Variable 1(-N) Value [][LINK]
The current value of the nth independent variable passed to the performance curve. The order of the independent variables is in the same order as the model equation represented by this performance curve object. This value is averaged over the time step being reported.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.