EMS Actuators[LINK]
This section provides details about EMS actuators, the
conduits by which Erl programs control EnergyPlus simulations.
They actuate selected features inside EnergyPlus.
Rather than add a new set of controls and component models
that have EMS awareness, they generally override established
features.
Internal to EnergyPlus are two separate lists of actuators:
those that are available for use, and those that are being
used in the EMS. While implementing the EMS, developers have
added code to control points to make them available for use in
EMS. The actuators available in a given model depend on the
non-EMS-related content of the input file. Similar to how
EnergyPlus reports the available output variables to the RDD
file, a list of available actuators is written to the EDD file
(depending on the settings in Output:EnergyManagementSystem).
Note that the EDD file is ONLY produced if you have set up EMS
/ Erl programs. To use an actuator in EMS, you need to enter
an EnergyManagementSystem:Actuator
input object. The EDD file contains information needed for
this input object; however, it is not available until after
the output has been generated from a previous run. If you do
not see a particular actuator in the EDD output file, it is
not available in EMS for that particular model. There is no
way to create a new actuator (except by modifying EnergyPlus
source code); you can only customize the behavior of current
actuators. If you need an actuator that you suspect could be
provided by the program but is not available, you can use the
regular system(s) for user support to request it be added to
the program. New actuators are added to the program from time
to time so the availability of actuators will grow with each
new release.
Actuators override things inside EnergyPlus whenever the
actuator’s Erl variable is set to a value other than “Null.”
Null is a special built-in variable used to deactivate an
actuator. Once an actuator starts overriding, it will continue
to do so until the actuator’s Erl variable is set to Null. You
should set the actuators to Null whenever you want the EMS to
revert to normal operation.
The rest of this section provides details about specific
actuators.
EMS Actuators[LINK]
This section provides details about EMS actuators, the conduits by which Erl programs control EnergyPlus simulations. They actuate selected features inside EnergyPlus. Rather than add a new set of controls and component models that have EMS awareness, they generally override established features.
Internal to EnergyPlus are two separate lists of actuators: those that are available for use, and those that are being used in the EMS. While implementing the EMS, developers have added code to control points to make them available for use in EMS. The actuators available in a given model depend on the non-EMS-related content of the input file. Similar to how EnergyPlus reports the available output variables to the RDD file, a list of available actuators is written to the EDD file (depending on the settings in Output:EnergyManagementSystem). Note that the EDD file is ONLY produced if you have set up EMS / Erl programs. To use an actuator in EMS, you need to enter an EnergyManagementSystem:Actuator input object. The EDD file contains information needed for this input object; however, it is not available until after the output has been generated from a previous run. If you do not see a particular actuator in the EDD output file, it is not available in EMS for that particular model. There is no way to create a new actuator (except by modifying EnergyPlus source code); you can only customize the behavior of current actuators. If you need an actuator that you suspect could be provided by the program but is not available, you can use the regular system(s) for user support to request it be added to the program. New actuators are added to the program from time to time so the availability of actuators will grow with each new release.
Actuators override things inside EnergyPlus whenever the actuator’s Erl variable is set to a value other than “Null.” Null is a special built-in variable used to deactivate an actuator. Once an actuator starts overriding, it will continue to do so until the actuator’s Erl variable is set to Null. You should set the actuators to Null whenever you want the EMS to revert to normal operation.
The rest of this section provides details about specific actuators.