Reporting Options[LINK]
There are many report variables in EnergyPlus. The ones
available for a specific simulation are listed in the report
data dictionary (rdd) file. These report variables may be
generated automatically if the following is included in the
input file.
Output:VariableDictionary,Regular; !- Key Field
When the object above is included in an input file, the rdd
file is available for review AFTER the simulation has
completed. If this object is not included in the input file,
the user may still use report variables, but must select them
based on the objects included in the simulation. The Input
Output Reference document describes all report variables
available for each EnergyPlus object.
There are two flavors to output variables: ZONE or HVAC.
ZONE does not mean that it is a zone variable - rather, it is
produced at the Zone
Time Step (the same timestep that you specify in the Timestep
object. HVAC type variables, likewise, are produced at the
HVAC timestep (which can differ from the zone timestep
frequency based on the ConvergenceLimits
object).
There are several choices on format with this object. You
can specify “Regular” as the key field and the rdd will show
all report variables along with the variable description as
shown below.
HVAC,Average,Boiler Heating Output Rate [W]HVAC,Sum,Boiler Heating Output Energy [J]HVAC,Average,Boiler Gas Consumption Rate [W]HVAC,Sum,Boiler Gas Consumption [J]HVAC,Average,Boiler Water Inlet Temp [C]HVAC,Average,Boiler Water Outlet Temp [C]HVAC,Average,Boiler Water Mass Flow Rate [kg/s]HVAC,Average,Boiler Parasitic Electric Consumption Rate [W]HVAC,Sum,Boiler Parasitic Electric Consumption [J]HVAC,Average,Boiler Part-Load Ratio []
As an alternative, the key field “IDF” may also be
used.
Output:VariableDictionary,
IDF; !- Key Field
With this option the rdd will format the report variable so
that they may be copied directly into the input file using a
text editor.
Output:Variable,*,Boiler Heating Output Rate,hourly; !- HVAC Average [W]Output:Variable,*,Boiler Heating Output Energy,hourly; !- HVAC Sum [J]Output:Variable,*,Boiler Gas Consumption Rate,hourly; !- HVAC Average [W]Output:Variable,*,Boiler Gas Consumption,hourly; !- HVAC Sum [J]Output:Variable,*,Boiler Water Inlet Temp,hourly; !- HVAC Average [C]Output:Variable,*,Boiler Water Outlet Temp,hourly; !- HVAC Average [C]Output:Variable,*,Boiler Water Mass Flow Rate,hourly; !- HVAC Average [kg/s]Output:Variable,*,Boiler Parasitic Electric Consumption Rate,hourly; !- HVAC Average [W]Output:Variable,*,Boiler Parasitic Electric Consumption,hourly; !- HVAC Sum [J]Output:Variable,*,Boiler Part-Load Ratio,hourly; !- HVAC Average ]
A different version of the output variable object is shown
below.
Output:Variable,
*, !- Key Value
Boiler Heating Output Rate, !- Variable Name
hourly, !- Reporting Frequency
MyReportVarSchedule; !- Schedule Name
Schedule:Compact,
MyReportVarSchedule, !- Name
On/Off, !- Schedule Type Limits Name
Through: 1/20, !- Field 1
For: AllDays, !- Field 2
Until: 24:00, 0.0, !- Field 4
Through: 12/31, !- Field 5
For: AllDays, !- Field 6
Until: 24:00, 1.0; !- Field 8
ScheduleTypeLimits,
On/Off, !- Name
0:1, !- Range
DISCRETE; !- Numeric Type
This allows several options for reporting. First the key
value may be an asterisk (*) where all report variables of
this type are reported (for all boilers). Or the key value
could be specified such that only a single output will be
generated. For example if the key value was specified as “My
Boiler” and a boiler object with the name My Boiler was
included in the input, only the Boiler Heating Output Rate for
this specific boiler will be in the output file (.csv). The
reporting output for all other boilers in the simulation will
not be included in the csv file.
The reporting frequency is also another option and may be
one of several choices (e.g., Timestep,
Hourly, Daily, Monthly, RunPeriod,
Environment, Annual or Detailed).
The detailed reporting frequency reports the data for every
simulation time step (HVAC variable time steps). This choice
is useful for detailed troubleshooting and reporting. The
other choices average or sum the data over the selected
interval. Timestep
refers to the zone Timestep/Number of Timesteps in hour value
and reports the data at regular intervals. Using RunPeriod,
Environment, or Annual will have the same affect on the
reporting frequency and refer to the length of the simulaiton
as specified in the RunPeriod
object.
Timestep,
4; !- Number of Timesteps per Hour
RunPeriod,
1, !- Begin Month
1, !- Begin Day of Month
12, !- End Month
31, !- End Day of Month
Tuesday, !- Day of Week for Start Day
Yes, !- Use Weather File Holidays and Special Days
Yes, !- Use Weather File Daylight Saving Period
No, !- Apply Weekend Holiday Rule
Yes, !- Use Weather File Rain Indicators
Yes; !- Use Weather File Snow Indicator
A schedule may also be used to turn on or off report
variable at selected intervals.
Table reports and meters are also available as reporting
options. See the Input Output and Engineering Reference
manuals for further details.
Reporting Options[LINK]
There are many report variables in EnergyPlus. The ones available for a specific simulation are listed in the report data dictionary (rdd) file. These report variables may be generated automatically if the following is included in the input file.
When the object above is included in an input file, the rdd file is available for review AFTER the simulation has completed. If this object is not included in the input file, the user may still use report variables, but must select them based on the objects included in the simulation. The Input Output Reference document describes all report variables available for each EnergyPlus object.
There are two flavors to output variables: ZONE or HVAC. ZONE does not mean that it is a zone variable - rather, it is produced at the Zone Time Step (the same timestep that you specify in the Timestep object. HVAC type variables, likewise, are produced at the HVAC timestep (which can differ from the zone timestep frequency based on the ConvergenceLimits object).
There are several choices on format with this object. You can specify “Regular” as the key field and the rdd will show all report variables along with the variable description as shown below.
As an alternative, the key field “IDF” may also be used.
With this option the rdd will format the report variable so that they may be copied directly into the input file using a text editor.
A different version of the output variable object is shown below.
This allows several options for reporting. First the key value may be an asterisk (*) where all report variables of this type are reported (for all boilers). Or the key value could be specified such that only a single output will be generated. For example if the key value was specified as “My Boiler” and a boiler object with the name My Boiler was included in the input, only the Boiler Heating Output Rate for this specific boiler will be in the output file (.csv). The reporting output for all other boilers in the simulation will not be included in the csv file.
The reporting frequency is also another option and may be one of several choices (e.g., Timestep, Hourly, Daily, Monthly, RunPeriod, Environment, Annual or Detailed).
The detailed reporting frequency reports the data for every simulation time step (HVAC variable time steps). This choice is useful for detailed troubleshooting and reporting. The other choices average or sum the data over the selected interval. Timestep refers to the zone Timestep/Number of Timesteps in hour value and reports the data at regular intervals. Using RunPeriod, Environment, or Annual will have the same affect on the reporting frequency and refer to the length of the simulaiton as specified in the RunPeriod object.
A schedule may also be used to turn on or off report variable at selected intervals.
Table reports and meters are also available as reporting options. See the Input Output and Engineering Reference manuals for further details.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.