Slab Program Output
Files[LINK]
The following output files are created by the Slab program
and saved in the output file path specified in the RunSlab.bat
file:
*_slab.ger - Error file. Input errors are reported
here.
*_slab.out - Summary of inputs, location data, and grid
coordinates
*_slab.gtp - Monthly ground temperatures and EnergyPlus idf
objects
EnergyPlus
idf Objects from Slab Program[LINK]
If the objects are placed in the normal EnergyPlus input
IDF file using the “GroundHeatTransfer:Slab:” prefix, then the
values resulting from the Slab preprocessor will be
automatically included in the simulation at run time. The
surfaces can reference these values using Outside Boundary
Conditions of:
GroundSlabPreprocessorAverage
GroundSlabPreprocessorCore
GroundSlabPreprocessorPerimeter
The objects that support this include:
The slab program is capable of supplying the EnergyPlus idf
objects needed to use the slab program outputs directly by
copying the objects into the EnergyPlus idf file. The file
containing these objects has the extension gtp, and an example
is shown below. It contains the output temperatures and heat
fluxes, and in addition it contains an OtherSideCoefficient
object example as mentioned above, and three compact schedule
objects that can be used to describe the average, core and
perimeter temperatures directly in EnergyPlus. The Name in the
compact schedule corresponds to the
GroundTemperatureScheduleName in the OtherSideCoefficient
object.
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = = = = = = = = = = = = = = = = =
CHECK CONVERGENCE MESSAGE AT END OF THIS FILE!
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = = = = = = = = = = = = = = = = =
Monthly Slab Outside Face Temperatures, C and Heat Fluxes(loss), W/(m^2)
Perimeter Area: 304.00 Core Area: 1296.00
Month TAverage TPerimeter TCore TInside AverageFlux PerimeterFlux CoreFlux
1 17.74 16.41 18.05 18.00 0.88 5.39 -0.17
2 17.49 16.15 17.81 18.00 1.73 6.29 0.66
3 17.45 16.23 17.74 18.00 1.86 6.02 0.88
4 18.96 17.86 19.22 20.00 3.51 7.24 2.64
5 19.22 18.22 19.45 20.00 2.66 6.04 1.86
6 19.28 18.38 19.49 20.00 2.44 5.48 1.73
7 20.83 19.98 21.03 22.00 3.96 6.87 3.28
8 21.12 20.39 21.29 22.00 2.98 5.47 2.40
9 21.18 20.46 21.35 22.00 2.76 5.22 2.19
10 21.17 20.23 21.39 22.00 2.82 6.02 2.08
11 19.64 18.63 19.88 20.00 1.22 4.63 0.42
12 19.36 18.14 19.65 20.00 2.16 6.30 1.19
! OTHER SIDE COEFFICIENT OBJECT EXAMPLE FOR IDF FILE
SurfaceProperty:OtherSideCoefficients,
ExampleOSC, !- OtherSideCoeff Name \*\*\*CHANGE THIS!\*\*\*
0, !- Combined convective/radiative film coefficient
1, !- N2,User selected Constant Temperature {C}
1, !- Coefficient modifying the user selected constant temperature
0, !- Coefficient modifying the external dry bulb temperature
0, !- Coefficient modifying the ground temperature
0, !- Coefficient modifying the wind speed term (s/m)
0, !- Coefficient modifying the zone air temperature
! part of the equation
GroundTempCompactSchedName; !- Name of Schedule for values of const
! temperature. Schedule values replace N2.
! \*\*\*REPLACE WITH CORRECT NAME\*\*\*
Schedule:Compact,
MonthlyAveSurfaceTemp, !Name
Temperature , !- ScheduleType
Through: 1/31,
For:AllDays,
Until:24:00,
17.74 ,
Through: 2/28,
For:AllDays,
Until:24:00,
17.49 ,
Through: 3/31,
For:AllDays,
Until:24:00,
17.45 ,
Through: 4/30,
For:AllDays,
Until:24:00,
18.96 ,
Through: 5/31,
For:AllDays,
Until:24:00,
19.22 ,
Through: 6/30,
For:AllDays,
Until:24:00,
19.28 ,
Through: 7/31,
For:AllDays,
Until:24:00,
20.83 ,
Through: 8/31,
For:AllDays,
Until:24:00,
21.12 ,
Through: 9/30,
For:AllDays,
Until:24:00,
21.18 ,
Through: 10/31,
For:AllDays,
Until:24:00,
21.17 ,
Through: 11/30,
For:AllDays,
Until:24:00,
19.64 ,
Through: 12/31,
For:AllDays,
Until:24:00,
19.36 ;
- compact schedules for
MonthlyPerimeterTemp and MonthlyCoreTemp are included.
Convergence has been gained.
Slab Program Output Files[LINK]
The following output files are created by the Slab program and saved in the output file path specified in the RunSlab.bat file:
*_slab.ger - Error file. Input errors are reported here.
*_slab.out - Summary of inputs, location data, and grid coordinates
*_slab.gtp - Monthly ground temperatures and EnergyPlus idf objects
EnergyPlus idf Objects from Slab Program[LINK]
If the objects are placed in the normal EnergyPlus input IDF file using the “GroundHeatTransfer:Slab:” prefix, then the values resulting from the Slab preprocessor will be automatically included in the simulation at run time. The surfaces can reference these values using Outside Boundary Conditions of:
GroundSlabPreprocessorAverage
GroundSlabPreprocessorCore
GroundSlabPreprocessorPerimeter
The objects that support this include:
BuildingSurface:Detailed
Wall:Detailed
RoofCeiling:Detailed
Floor:Detailed
The slab program is capable of supplying the EnergyPlus idf objects needed to use the slab program outputs directly by copying the objects into the EnergyPlus idf file. The file containing these objects has the extension gtp, and an example is shown below. It contains the output temperatures and heat fluxes, and in addition it contains an OtherSideCoefficient object example as mentioned above, and three compact schedule objects that can be used to describe the average, core and perimeter temperatures directly in EnergyPlus. The Name in the compact schedule corresponds to the GroundTemperatureScheduleName in the OtherSideCoefficient object.
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
CHECK CONVERGENCE MESSAGE AT END OF THIS FILE!
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.