Summary of
Predictor-Corrector Procedure[LINK]
The predictor-corrector scheme can be summarized as
follows:
- Using equation , an estimate is made of the air system
energy required to balance the equation with the zone air
temperature equal to the setpoint temperature.
- With that quantity as a demand, the air system is
simulated to determine its actual supply capability at the
time of the simulation. This will include a plant simulation
if necessary.
- The actual air system capability is used in equation to
calculate the resulting zone temperature.
Summary of Predictor-Corrector Procedure[LINK]
The predictor-corrector scheme can be summarized as follows:
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.