Zone Air Mass Flow
Conservation[LINK]
The zone air mass flow conservation object, ZoneAirMassFlowConservation,
activates zone air mass flow balance calculations. This
feature is available only for controlled zones
(ZoneVAC:EquipmentConnections) which also have either a zone
mixing or infiltration object. The user may specify that zone
mixing, infiltration, or both can be overridden to balance the
zone air mass flows. The following rules apply:
- If there are no zone mixing flows to adjacent zones, then
the zone air mass flow is balanced by setting the Zone Mixing
objects mass flow rate to zero.
- If there are no zone exhaust fans defined and there are no
zone mixing objects specified, then a zone in an air loop is
always balanced.
- Infiltration mass flow is included in the zone air mass
flow balance depending upon one of three options: none (all
infiltration is assumed to be self-balanced), all zones, or
only zones that serve as a source zone for zone mixing
objects.
- The base infiltration mass flow rate (calculated based on
user inputs) may be controlled one of two ways for zone air
mass flow balance purposes: adjust the base infiltration up or
down as needed to balance the zone air mass flow, or assume
the base infiltration rate is self-balanced and add
infiltration if needed to balance the zone air mass flow.
- Optional user inputs can override the default return air
flow rate.
The zone air mass flow conservation equation always
includes: supply air flow rates, return air flow rates, and
zone exhaust fan flow rates. Zone
mixing and infiltration object flow rates may be included
depending upon the selected options. A particular zone can be
a source zone, receiving zone, or both depending on the number
of ZoneMixing
objects specified for that zone.
Return Air Flow
Rate Calculations[LINK]
The return air flow rate is calculated one of two ways.
The default calculation is:
\[{\dot m_{R}} =
ReturnFlowSchedule*MAX\left( {0.0,\,{{\dot m}_S} + {{\dot
m}_{XR}} - {{\dot m}_{EX}} - {{\dot m}_{XS}}}
\right)\]
If one or more Zone
Return Air Flow Rate Basis Nodes are specified in the ZoneHVAC:EquipmentConnections
object, then the base return flow rate is:
\[{\dot m_{R}} =
ReturnFlowSchedule*\sum\nolimits_j {{{\dot
m}_{BasisNode,j}}}\]
where,
\({\dot m_{R}}\) = zone
return air mass flow rate, (kg/s)
\({\dot m_{Basis
Node,j}}\) = zone return air flow basis node mass flow
rate, (kg/s)
\({\dot m_{EX}}\) = zone
exhaust air mass flow rate from exhaust fans, (kg/s)
\({\dot m_{XR}}\) = zone
mixing mass flow rate as a receiving zone, (kg/s)
\({\dot m_{XS}}\) = zone
mixing mass flow rate as a source zone, (kg/s)
\({\dot m_S}\) = zone
supply air mass flow rate, (kg/s)
ReturnFlowSchedule = optional Zone
Return Air Flow Rate Fraction Schedule value
Zone Mixing Flow
Rate Calculations[LINK]
Figure 8 illustrates the zone mass flow components for an
air loop system providing conditioned air to the two zones
connected with a zone mixing object. Since Zone
1 is a source zone only, infiltration object is defined for
zone 1 only. The zone mixing object air flow rate depends on
the user specified values and the zone air mass flow balance
requirements. When required the zone mixing object flow rate
is adjusted from the user specified value for balancing
purpose.

Figure 8. Illustration of zone air mass flow balance
components
An individual zone may be a source zone for multiple
receiving zones, and the same source zone may receive mixing
flows from multiple adjacent zones in an air loop. The source
and receiving mass flow rates of ZoneMixing
objects are calculated from user defined mixing flow rates at
the first HVAC iteration for each time step and adjusted in
subsequent iterations to balance the zone air mass flow. The
source zone mixing mass flow rate is calculated by tracking
the mass flow rates of ZoneMixing
objects connected to a zone and is given by:
\[{\dot m_{XS}} =
\sum\nolimits_j {{{\dot m}_{XS,j}}}\]
Determine the zone return air mass flow rate as shown
above, then adjust the zone mixing mass flow rates based on
the current zone return air mass flow rate:
\[{\dot m_{XR,\,new}} = {\dot
m_R} + {\dot m_{EX}} + {\dot m_{XS}} - {\dot m_S}\]
This updated receiving zone mixing air mass flow rate is
distributed to the mixing objects connected to the current
zone proportional to user specified design flow rate. A single
zone may be connected to more than one adjacent zone using
multiple ZoneMixing
objects. Thus, the mixing flow rate of each contributing
mixing objects defined in the current zone is updated as
follows:
\[{\dot m_{XR,\,new,j}} = \left(
{{{\dot m}_{XR,jDesign}}/{{\dot m}_{XR,Design}}} \right) \cdot
{\dot m_{XR,\,new}}\]
Infiltration Flow
Rate Adjustments[LINK]
There are three options for the treatement of infiltration
in the zone air mass balance: None, AddInfiltrationFlow, and
AdjustInfiltrationFlow. There are also two options to specify
which zones are included in the infiltration adjustments:
AllZones or MixingSourceZonesOnly.
If a zone is excluded from infiltration adjustments, then
the base infiltration rate specified by the Infiltration:*
object(s) in the zone is assumed to be self-balanced, and
infiltration is not included in the mass flow calculations for
that zone.
If a zone is included in the infiltration adjustment, the
infiltration air mass flow rate required to balance the zone
is determined as follows:
\[{\dot m_{Inf-required}} =
MAX\left( {0.0,\,{{\dot m}_{XS}} + {{\dot m}_{EX}} + {{\dot
m}_{R}} - {{\dot m}_S}} \right)\]
This infiltration air mass flow rate calculated is either
added to the base infiltration air flow, which is calculated
from user inputs, or overrides the base infiltration air flow
depending on user choice. For AddInfiltrationFlow, the
zoneinfiltration flow rate is:
\[{\dot m_{Inf}} = {\dot
m_{Inf-base}} + {\dot m_{Inf-required}}\]
For AdjustInfiltrationFlow, the zone infiltration flow rate
is:
\[{\dot m_{Inf}} = {\dot
m_{Inf-required}}\]
where,
\({\dot m_{Inf}}\) = zone
infiltration mass flow rate, (kg/s)
\({\dot m_{Inf-base}}\) =
base zone infiltration mass flow rate calculated from
Infiltration:* objects, (kg/s)
\({\dot
m_{Inf-required}}\) = required zone infiltration mass
flow rate to balance the zone, (kg/s)
There is an additional constraint to the return air mass
flow rate calculation. The sum of the return air mass flow
rates of zones in air loop must satisfy the air loop return
air mass flow balance. The above four sets of equations are
iterated for each zone in an air loop until the convergence
criterion is satisfied or until the maximum iteration limit is
exceeded.
The mass conservation calculations are performed in routine
CalcZoneMassBalance in the ZoneEquipmentManager module. The
latest ZoneMixing
and Infiltration object flow rates are communicated back to
the zone air heat balance terms. This is done by re-simulating
the simple flow objects as zone equipment during each HVAC
iteration. This requires calling the routine CalcAirFlowSimple
in SimZoneEquipment routine as zone equipment. Both of these
routines are also in the ZoneEquipmentManager module.
Zone
Mass Conservation Convergence
The zone mass conservation calculation convergence
criterion is based on the absolute difference of the zone
mixing objects mass flow rates between successive iteration.
If the difference is above tolerance limits of 0.00001 then
the HVAC Air loop is simulated again.
Zone Air Mass Flow Conservation[LINK]
Overiew[LINK]
The zone air mass flow conservation object, ZoneAirMassFlowConservation, activates zone air mass flow balance calculations. This feature is available only for controlled zones (ZoneVAC:EquipmentConnections) which also have either a zone mixing or infiltration object. The user may specify that zone mixing, infiltration, or both can be overridden to balance the zone air mass flows. The following rules apply:
The zone air mass flow conservation equation always includes: supply air flow rates, return air flow rates, and zone exhaust fan flow rates. Zone mixing and infiltration object flow rates may be included depending upon the selected options. A particular zone can be a source zone, receiving zone, or both depending on the number of ZoneMixing objects specified for that zone.
Return Air Flow Rate Calculations[LINK]
The return air flow rate is calculated one of two ways.
The default calculation is:
\[{\dot m_{R}} = ReturnFlowSchedule*MAX\left( {0.0,\,{{\dot m}_S} + {{\dot m}_{XR}} - {{\dot m}_{EX}} - {{\dot m}_{XS}}} \right)\]
If one or more Zone Return Air Flow Rate Basis Nodes are specified in the ZoneHVAC:EquipmentConnections object, then the base return flow rate is:
\[{\dot m_{R}} = ReturnFlowSchedule*\sum\nolimits_j {{{\dot m}_{BasisNode,j}}}\]
where,
\({\dot m_{R}}\) = zone return air mass flow rate, (kg/s)
\({\dot m_{Basis Node,j}}\) = zone return air flow basis node mass flow rate, (kg/s)
\({\dot m_{EX}}\) = zone exhaust air mass flow rate from exhaust fans, (kg/s)
\({\dot m_{XR}}\) = zone mixing mass flow rate as a receiving zone, (kg/s)
\({\dot m_{XS}}\) = zone mixing mass flow rate as a source zone, (kg/s)
\({\dot m_S}\) = zone supply air mass flow rate, (kg/s)
ReturnFlowSchedule = optional Zone Return Air Flow Rate Fraction Schedule value
Zone Mixing Flow Rate Calculations[LINK]
Figure 8 illustrates the zone mass flow components for an air loop system providing conditioned air to the two zones connected with a zone mixing object. Since Zone 1 is a source zone only, infiltration object is defined for zone 1 only. The zone mixing object air flow rate depends on the user specified values and the zone air mass flow balance requirements. When required the zone mixing object flow rate is adjusted from the user specified value for balancing purpose.
Figure 8. Illustration of zone air mass flow balance components
An individual zone may be a source zone for multiple receiving zones, and the same source zone may receive mixing flows from multiple adjacent zones in an air loop. The source and receiving mass flow rates of ZoneMixing objects are calculated from user defined mixing flow rates at the first HVAC iteration for each time step and adjusted in subsequent iterations to balance the zone air mass flow. The source zone mixing mass flow rate is calculated by tracking the mass flow rates of ZoneMixing objects connected to a zone and is given by:
\[{\dot m_{XS}} = \sum\nolimits_j {{{\dot m}_{XS,j}}}\]
Determine the zone return air mass flow rate as shown above, then adjust the zone mixing mass flow rates based on the current zone return air mass flow rate:
\[{\dot m_{XR,\,new}} = {\dot m_R} + {\dot m_{EX}} + {\dot m_{XS}} - {\dot m_S}\]
This updated receiving zone mixing air mass flow rate is distributed to the mixing objects connected to the current zone proportional to user specified design flow rate. A single zone may be connected to more than one adjacent zone using multiple ZoneMixing objects. Thus, the mixing flow rate of each contributing mixing objects defined in the current zone is updated as follows:
\[{\dot m_{XR,\,new,j}} = \left( {{{\dot m}_{XR,jDesign}}/{{\dot m}_{XR,Design}}} \right) \cdot {\dot m_{XR,\,new}}\]
Infiltration Flow Rate Adjustments[LINK]
There are three options for the treatement of infiltration in the zone air mass balance: None, AddInfiltrationFlow, and AdjustInfiltrationFlow. There are also two options to specify which zones are included in the infiltration adjustments: AllZones or MixingSourceZonesOnly.
If a zone is excluded from infiltration adjustments, then the base infiltration rate specified by the Infiltration:* object(s) in the zone is assumed to be self-balanced, and infiltration is not included in the mass flow calculations for that zone.
If a zone is included in the infiltration adjustment, the infiltration air mass flow rate required to balance the zone is determined as follows:
\[{\dot m_{Inf-required}} = MAX\left( {0.0,\,{{\dot m}_{XS}} + {{\dot m}_{EX}} + {{\dot m}_{R}} - {{\dot m}_S}} \right)\]
This infiltration air mass flow rate calculated is either added to the base infiltration air flow, which is calculated from user inputs, or overrides the base infiltration air flow depending on user choice. For AddInfiltrationFlow, the zoneinfiltration flow rate is:
\[{\dot m_{Inf}} = {\dot m_{Inf-base}} + {\dot m_{Inf-required}}\]
For AdjustInfiltrationFlow, the zone infiltration flow rate is:
\[{\dot m_{Inf}} = {\dot m_{Inf-required}}\]
where,
\({\dot m_{Inf}}\) = zone infiltration mass flow rate, (kg/s)
\({\dot m_{Inf-base}}\) = base zone infiltration mass flow rate calculated from Infiltration:* objects, (kg/s)
\({\dot m_{Inf-required}}\) = required zone infiltration mass flow rate to balance the zone, (kg/s)
There is an additional constraint to the return air mass flow rate calculation. The sum of the return air mass flow rates of zones in air loop must satisfy the air loop return air mass flow balance. The above four sets of equations are iterated for each zone in an air loop until the convergence criterion is satisfied or until the maximum iteration limit is exceeded.
The mass conservation calculations are performed in routine CalcZoneMassBalance in the ZoneEquipmentManager module. The latest ZoneMixing and Infiltration object flow rates are communicated back to the zone air heat balance terms. This is done by re-simulating the simple flow objects as zone equipment during each HVAC iteration. This requires calling the routine CalcAirFlowSimple in SimZoneEquipment routine as zone equipment. Both of these routines are also in the ZoneEquipmentManager module.
Zone Mass Conservation Convergence
The zone mass conservation calculation convergence criterion is based on the absolute difference of the zone mixing objects mass flow rates between successive iteration. If the difference is above tolerance limits of 0.00001 then the HVAC Air loop is simulated again.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.