Group – Air Path[LINK]
AirLoopHVAC:SupplyPath,
AirLoopHVAC:ReturnPath[LINK]
The zone supply and return air paths are used to describe
the configuration of the flow path that the supply air takes
in moving from the main air handler to the zone terminal units
and that the return air takes on leaving the zones and
returning to the central return air duct. The air paths
consist of a group of components AirLoopHVAC:ZoneSplitters and
AirLoopHVAC:SupplyPlenums for the supply path and
AirLoopHVAC:ReturnPlenums and AirLoopHVAC:ZoneMixers for the
return path. The connectivity of the paths is established by
the components node connections. There are no branches defined
in the zone air path constructs.
For a typical single duct air system there will be one AirLoopHVAC:SupplyPath
and one AirLoopHVAC:ReturnPath.
A typical dual duct system would have 2
AirLoopHVAC:SupplyPaths one for the hot air and one for the
cold air and 1 AirLoopHVAC:ReturnPath.
The AirLoopHVAC:SupplyPlenum
component provides the capability to have supply air
distributed to the conditioned zones through one or more
plenum zones such as would occur in an underfloor air
distribution system (UFAD). The AirLoopHVAC:ReturnPlenum
component allows the program to model return air plenums. Of
course plenums are always optional. The simplest AirLoopHVAC:SupplyPath
would consist of only an AirLoopHVAC:ZoneSplitter;
similarly the simplest return air path consists of a single AirLoopHVAC:ZoneMixer.
A UFAD system supply air path might consist of a single AirLoopHVAC:ZoneSplitter
connecting to multiple AirLoopHVAC:SupplyPlenums which in turn
could each supply one or more conditioned zones. A system with
return plenums would have an AirLoopHVAC:ReturnPath
in which the conditioned zones connect to the return plenum
inlets and the return plenum s outlets connect to a single AirLoopHVAC:ZoneMixer.
Both the zone supply and return plenums are solved in the
heat balance as thermal zones which couple through heat
conduction with adjacent zones. Since they are solved as
thermal zones the solution scheme involves the zone
predictor-corrector technique which will lag the temperature
at the system timestep in every zone. See Summary of
Predictor-Corrector Procedure in the EnergyPlus Engineering
Reference.
Below are the descriptions of the zone supply and return
path statements. Note that each statement type has an
identifying name, a single inlet/outlet node name, and a list
of component type/name pairs. For a single zone being served
by an air loop, the inlet to its air distribution unit and the
zone return air outlet can be the zone equipment inlet and
outlet nodes directly, thus eliminating the need to specify an
AirLoopHVAC:SupplyPath
and an AirLoopHVAC:ReturnPath.
AirLoopHVAC:SupplyPath[LINK]
The AirLoopHVAC:SupplyPath
lists one or more AirLoopHVAC:ZoneSplitter
and AirLoopHVAC:SupplyPlenum
components comprising the path. The components are listed in
flow order: upstream to downstream and may be in series,
parallel, or both. Connectivity is established by means of the
individual component inlet and outlet nodes.
Unique name to identify the supply air path..
Field: Supply
Air Path Inlet Node Name[LINK]
The name of an inlet node for the zone equipment half of
the air loop. This should be one of the nodes named in the AirLoopHVAC
field: Demand Side Inlet Node Names.
Field Set Component
Type and Name[LINK]
The remaining fields are sets of two repeated times: a
component type and a name. These pairs of fields define the
components on the supply air path.
Field: Component
<#> Object Type[LINK]
Start of the component list for the AirLoopHVAC:SupplyPath.
This field should contain either AirLoopHVAC:SupplyPlenum
or AirLoopHVAC:ZoneSplitter.
Field: Component <#>
Name[LINK]
Unique name of the AirLoopHVAC:SupplyPlenum
or AirLoopHVAC:ZoneSplitter
component.
AirLoopHVAC:ReturnPath[LINK]
The AirLoopHVAC:ReturnPath
lists one or more AirLoopHVAC:ZoneMixer
and AirLoopHVAC:ReturnPlenum
components comprising the path. The components are listed in
flow order: upstream to downstream and may be in series,
parallel, or both. Connectivity is established by means of the
individual component inlet and outlet nodes. At this time
there can only be 1 AirLoopHVAC:ZoneMixer
in an AirLoopHVAC:ReturnPath.
Unique name to identify the return air path.
Field: Return
Air Path Outlet Node Name[LINK]
The name of the node that is the outlet to the air loop
from the AirLoopHVAC:ReturnPath.
This should be the same node named in the AirLoopHVAC
field: Demand Side Outlet Node Name.
Field Set
Component Type and Name[LINK]
The remaining fields are sets of two repeated times: a
component type and a name. These pairs of fields define the
components on the return air path.
Field: Component
<#> Object Type[LINK]
Start of the component list for the AirLoopHVAC:ReturnPath.
This field should contain either AirLoopHVAC:ReturnPlenum
or AirLoopHVAC:ZoneMixer.
Field: Component <#>
Name[LINK]
Unique name of the AirLoopHVAC:ReturnPlenum
or AirLoopHVAC:ZoneMixer.
Example inputs are shown below
AirLoopHVAC:SupplyPath,
SupplyAirPath 1, !- Name
Zone Equip In Node, !- Supply Air Path Inlet Node Name
AirLoopHVAC:SupplyPlenum, !- Component 1 Object Type
Supply-Plenum-1, !- Component 1 Name
AirLoopHVAC:ZoneSplitter, !- Component 2 Object Type
Zone Supply Air Splitter 1; !- Component 2 Name
AirLoopHVAC:ReturnPath,
ReturnAirPath1, !- Name
PLENUM-1 Out Node, !- Return Air Path Outlet Node Name
Zone Return Plenum, !- Component 1 Object Type
Return-Plenum-1; !- Component 1 Name
AirLoopHVAC:ReturnPlenum[LINK]
The simple building shown in the figure below consists of a
controlled zone and a return plenum zone that is used for the
return air. This simple configuration contains a ground floor
controlled zone with a window and a return plenum zone which
handles the roof load. The return air plenum is a special type
of component since there is both a heat balance connection and
building description and a system airflow connection that
transfers the airflow directly from the controlled zone to the
return plenum zone in the system air simulation. The input
described in this section is mainly just for the system
airflow connections in the HVAC algorithms. In addition the
return plenum zone must be fully input as a zone object for
the heat balance calculation. The zone description needs to
contain the wall descriptions - the interzone ceiling and
floor, and for this simple case the roof. All the other
attributes of a zone that can be specified in the building
description can be used with a return plenum zone if
necessary: scheduled loads, windows, etc.

Figure 130. Illustration of Zone
Return Plenum
After all the building zone attributes are specified, the
AirLoopHVAC:ReturnPlenum
object is specified and included as one of the named
components in an AirLoopHVAC:ReturnPath.
A unique identifying name identifying the AirLoopHVAC:ReturnPlenum
system component.
Field: Zone Name[LINK]
The zone name specified in the heat balance portion of the
input. This piece of input connects the zone return plenum
system component to the heat balance data structure.
Field: Zone Node Name[LINK]
The name of the zone node. The zone node name connects the
heat balance data structure to the system airflow data
structure through this node. This node name is defined by the
user in the field Zone
Air Node Name in the ZoneHVAC:EquipmentConnections
object for the zone named in the previous field.
Field: Outlet Node Name[LINK]
The name of the return plenum outlet node. For the zone
return plenum there is only one outlet node that can be
specified.
Field:
Induced Air Outlet Node or NodeList Name[LINK]
The name of an induced air outlet node or the name of a NodeList
of such nodes. These nodes are to be used as the secondary
inlet air nodes of powered induction terminal units (See
AirTerminal:SingleDuct:SeriesPIU:Reheat
and AirTerminal:SingleDuct:ParallelPIU:Reheat).
Field: Inlet <#> Node
Name[LINK]
The name of a plenum inlet node. There is no limit to the
number of inlet nodes, and there may be no duplicate inlet
node names. (Note that some EnergyPlus editing tools may allow
only 500 inlet node names, but this may be increased by
extending the object in the Energy+.idd file.)
An IDF example of a zone return plenum component
specification:
AirLoopHVAC:ReturnPlenum,
Return-Plenum-1, !- Name
PLENUM-1, !- Zone Name
PLENUM-1 Node, !- Zone Node Name
PLENUM-1 Out Node, !- Outlet Node Name
PLENUM-1 Induced Air Nodes, !- Induced Air Outlet Node or NodeList Name
SPACE1-1 Out Node, !- Inlet 1 Node Name
SPACE2-1 Out Node, !- Inlet 2 Node Name
SPACE3-1 Out Node, !- Inlet 3 Node Name
SPACE4-1 Out Node, !- Inlet 4 Node Name
SPACE5-1 Out Node; !- Inlet 5 Node Name
NodeList,
PLENUM-1 Induced Air Nodes, !- Name
SPACE1-1 ATU Sec Node, !- Node 1 Name
SPACE2-1 ATU Sec Node, !- Node 2 Name
SPACE3-1 ATU Sec Node, !- Node 3 Name
SPACE4-1 ATU Sec Node; !- Node 4 Name
Below is an example of the AirLoopHVAC:ReturnPath
for the simple case shown above.
AirLoopHVAC:ReturnPath,
ReturnAirPath1, !- Name
PLENUM-1 Out Node, !- Return Air Path Outlet Node Name
AirLoopHVAC:ReturnPlenum,!- Component 1 Object Type
Return-Plenum-1; !- Component 1 Name
AirLoopHVAC:SupplyPlenum[LINK]
The building shown in the figure below consists of three
controlled zones served by an AirLoopHVAC:SupplyPlenum
beneath the floor.

Figure 131. Illustration of AirLoopHVAC:SupplyPlenum
The AirLoopHVAC:SupplyPlenum
has a heat balance connection and building description, and a
system airflow connection which transfers the airflow from the
supply plenum zone to the controlled zones in the system
simulation. The input described in this section is mainly just
for the system airflow connections in the HVAC algorithms. In
addition the supply plenum zone must be fully input in the
building zone description. The supply plenum zone description
needs to contain the wall descriptions, the interzone ceiling
and floor, and the ground connection. All the other attributes
of a zone that can be specified in the building description
can be utilized with a supply plenum zone if necessary,
i.e. scheduled loads, windows, etc.
After all the building zone attributes are specified, the
AirLoopHVAC:SupplyPlenum
object is specified and included as one of the named
components in an AirLoopHVAC:SupplyPath.
A unique identifying name identifying the AirLoopHVAC:SupplyPlenum
system component.
Field: Zone Name[LINK]
The zone name specified in the heat balance portion of the
input. This piece of input connects the AirLoopHVAC:SupplyPlenum
system component to the heat balance data structure.
Field: Zone Node Name[LINK]
The name of the zone node. The zone node name connects the
heat balance data structure to the system airflow data
structure through this node. This node name is defined by the
user in the field Zone
Air Node Name in the ZoneHVAC:EquipmentConnections
object for the zone named in the previous field.
Field: Inlet Node Name[LINK]
The name of the inlet node to the supply plenum. The AirLoopHVAC:SupplyPlenum
component can send air to many outlets, but there is only one
inlet.
Field: Outlet <#> Node
Name[LINK]
The name of a plenum outlet node. There is no limit to the
number of outlet nodes, and there may be no duplicate outlet
node names. (Note that some EnergyPlus editing tools may allow
only 500 outlet node names, but this may be increased by
extending the object in the Energy+.idd file.)
An IDF example of an AirLoopHVAC:SupplyPlenum
component specification:
AirLoopHVAC:SupplyPlenum,
Supply Plenum 1, ! Name
SUPPLY PLENUM ZONE, ! Zone Name
Supply Plenum 1 Zone Node, ! Zone Node Name
Zone Equipment Inlet Node, ! Inlet Node Name
Supply Plenum 1 Outlet Node; ! Outlet 1 Node Name
Below is an example of the AirLoopHVAC:SupplyPath
for the building shown above.
AirLoopHVAC:SupplyPath,
TermReheatSupplyPath, ! Name
Zone Equipment Inlet Node, ! Supply Air Path Inlet Node Name
AirLoopHVAC:SupplyPlenum, ! Component 1 Object Type
Supply Plenum 1, ! Component 1 Name
AirLoopHVAC:ZoneSplitter, ! Component 2 Object Type
Zone Supply Air Splitter; ! Component 2 Name
AirLoopHVAC:ZoneSplitter[LINK]
The AirLoopHVAC:ZoneSplitter
is a component that splits airflow from a single inlet to
multiple outlets. This component must be referenced in an AirLoopHVAC:SupplyPath
object. The input contains only node connection
information.
Unique name for this zone splitter.
Field: Inlet Node Name[LINK]
The name of the single inlet node going into the
splitter.
Field: Outlet <#> Node
Name[LINK]
The name of a splitter outlet node. There is no limit to
the number of outlet nodes, and there may be no duplicate
outlet node names. (Note that some EnergyPlus editing tools
may allow only 500 outlet node names, but this may be
increased by extending the object in the Energy+.idd
file.)
An example is shown below.
AirLoopHVAC:ZoneSplitter,
Zone Supply Air Splitter, ! Name
Zone Equipment Inlet Node, ! Inlet Node Name
Zone 1 Damper Inlet Node, ! Outlet 1 Node Name
Zone 2 Damper Inlet Node, ! Outlet 2 Node Name
Zone 3 Damper Inlet Node; ! Outlet 3 Node Name
AirLoopHVAC:ZoneMixer[LINK]
The AirLoopHVAC:ZoneMixer
takes the air from multiple inlets and mixes the streams
together to be sent out of a single outlet node. This is a
simple process of summing flows and averaging the air
properties. This compoment may be part of an air loop return
path or part of an induction terminal unit. When used as a
return air mixer, this component must be listed in an AirLoopHVAC:ReturnPath
object, and the inlets may be zone return air nodes or AirLoopHVAC:ReturnPlenum
outlet nodes. When used in an induction terminal unit (ref. AirTerminal:SingleDuct:SeriesPIU:Reheat,
AirTerminal:SingleDuct:ParallelPIU:Reheat,
and AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction),
one inlet node is the supply (primary) air inlet from the
central air handler, and the second inlet node is the induced
(secondary) air inlet. These node names should match
equivalent node names in the terminal unit.
Unique name for this zone mixer.
Field: Outlet Node Name[LINK]
The name of the single outlet node leaving the mixer.
Field: Inlet <#> Node
Name[LINK]
The name of a mixer inlet node. There is no limit to the
number of inlet nodes, and there may be no duplicate inlet
node names. (Note that some EnergyPlus editing tools may allow
only 500 inlet node names, but this may be increased by
extending the object in the Energy+.idd file.)
An input example is shown below.
AirLoopHVAC:ZoneMixer,
Zone Return Air Mixer, ! Name
Return Air Mixer Outlet Node, ! Outlet Node Name
Zone 1 Outlet Node, ! Inlet 1 Node Name
Zone 2 Outlet Node, ! Inlet 2 Node Name
Zone 3 Outlet Node; ! Inlet 3 Node Name
Group – Air Path[LINK]
AirLoopHVAC:SupplyPath, AirLoopHVAC:ReturnPath[LINK]
The zone supply and return air paths are used to describe the configuration of the flow path that the supply air takes in moving from the main air handler to the zone terminal units and that the return air takes on leaving the zones and returning to the central return air duct. The air paths consist of a group of components AirLoopHVAC:ZoneSplitters and AirLoopHVAC:SupplyPlenums for the supply path and AirLoopHVAC:ReturnPlenums and AirLoopHVAC:ZoneMixers for the return path. The connectivity of the paths is established by the components node connections. There are no branches defined in the zone air path constructs.
For a typical single duct air system there will be one AirLoopHVAC:SupplyPath and one AirLoopHVAC:ReturnPath. A typical dual duct system would have 2 AirLoopHVAC:SupplyPaths one for the hot air and one for the cold air and 1 AirLoopHVAC:ReturnPath.
The AirLoopHVAC:SupplyPlenum component provides the capability to have supply air distributed to the conditioned zones through one or more plenum zones such as would occur in an underfloor air distribution system (UFAD). The AirLoopHVAC:ReturnPlenum component allows the program to model return air plenums. Of course plenums are always optional. The simplest AirLoopHVAC:SupplyPath would consist of only an AirLoopHVAC:ZoneSplitter; similarly the simplest return air path consists of a single AirLoopHVAC:ZoneMixer. A UFAD system supply air path might consist of a single AirLoopHVAC:ZoneSplitter connecting to multiple AirLoopHVAC:SupplyPlenums which in turn could each supply one or more conditioned zones. A system with return plenums would have an AirLoopHVAC:ReturnPath in which the conditioned zones connect to the return plenum inlets and the return plenum s outlets connect to a single AirLoopHVAC:ZoneMixer.
Both the zone supply and return plenums are solved in the heat balance as thermal zones which couple through heat conduction with adjacent zones. Since they are solved as thermal zones the solution scheme involves the zone predictor-corrector technique which will lag the temperature at the system timestep in every zone. See Summary of Predictor-Corrector Procedure in the EnergyPlus Engineering Reference.
Below are the descriptions of the zone supply and return path statements. Note that each statement type has an identifying name, a single inlet/outlet node name, and a list of component type/name pairs. For a single zone being served by an air loop, the inlet to its air distribution unit and the zone return air outlet can be the zone equipment inlet and outlet nodes directly, thus eliminating the need to specify an AirLoopHVAC:SupplyPath and an AirLoopHVAC:ReturnPath.
AirLoopHVAC:SupplyPath[LINK]
The AirLoopHVAC:SupplyPath lists one or more AirLoopHVAC:ZoneSplitter and AirLoopHVAC:SupplyPlenum components comprising the path. The components are listed in flow order: upstream to downstream and may be in series, parallel, or both. Connectivity is established by means of the individual component inlet and outlet nodes.
Inputs[LINK]
Field: Name[LINK]
Unique name to identify the supply air path..
Field: Supply Air Path Inlet Node Name[LINK]
The name of an inlet node for the zone equipment half of the air loop. This should be one of the nodes named in the AirLoopHVAC field: Demand Side Inlet Node Names.
Field Set Component Type and Name[LINK]
The remaining fields are sets of two repeated times: a component type and a name. These pairs of fields define the components on the supply air path.
Field: Component <#> Object Type[LINK]
Start of the component list for the AirLoopHVAC:SupplyPath. This field should contain either AirLoopHVAC:SupplyPlenum or AirLoopHVAC:ZoneSplitter.
Field: Component <#> Name[LINK]
Unique name of the AirLoopHVAC:SupplyPlenum or AirLoopHVAC:ZoneSplitter component.
AirLoopHVAC:ReturnPath[LINK]
The AirLoopHVAC:ReturnPath lists one or more AirLoopHVAC:ZoneMixer and AirLoopHVAC:ReturnPlenum components comprising the path. The components are listed in flow order: upstream to downstream and may be in series, parallel, or both. Connectivity is established by means of the individual component inlet and outlet nodes. At this time there can only be 1 AirLoopHVAC:ZoneMixer in an AirLoopHVAC:ReturnPath.
Inputs[LINK]
Field: Name[LINK]
Unique name to identify the return air path.
Field: Return Air Path Outlet Node Name[LINK]
The name of the node that is the outlet to the air loop from the AirLoopHVAC:ReturnPath. This should be the same node named in the AirLoopHVAC field: Demand Side Outlet Node Name.
Field Set Component Type and Name[LINK]
The remaining fields are sets of two repeated times: a component type and a name. These pairs of fields define the components on the return air path.
Field: Component <#> Object Type[LINK]
Start of the component list for the AirLoopHVAC:ReturnPath. This field should contain either AirLoopHVAC:ReturnPlenum or AirLoopHVAC:ZoneMixer.
Field: Component <#> Name[LINK]
Unique name of the AirLoopHVAC:ReturnPlenum or AirLoopHVAC:ZoneMixer.
Example inputs are shown below
AirLoopHVAC:ReturnPlenum[LINK]
The simple building shown in the figure below consists of a controlled zone and a return plenum zone that is used for the return air. This simple configuration contains a ground floor controlled zone with a window and a return plenum zone which handles the roof load. The return air plenum is a special type of component since there is both a heat balance connection and building description and a system airflow connection that transfers the airflow directly from the controlled zone to the return plenum zone in the system air simulation. The input described in this section is mainly just for the system airflow connections in the HVAC algorithms. In addition the return plenum zone must be fully input as a zone object for the heat balance calculation. The zone description needs to contain the wall descriptions - the interzone ceiling and floor, and for this simple case the roof. All the other attributes of a zone that can be specified in the building description can be used with a return plenum zone if necessary: scheduled loads, windows, etc.
Figure 130. Illustration of Zone Return Plenum
After all the building zone attributes are specified, the AirLoopHVAC:ReturnPlenum object is specified and included as one of the named components in an AirLoopHVAC:ReturnPath.
Inputs[LINK]
Field: Name[LINK]
A unique identifying name identifying the AirLoopHVAC:ReturnPlenum system component.
Field: Zone Name[LINK]
The zone name specified in the heat balance portion of the input. This piece of input connects the zone return plenum system component to the heat balance data structure.
Field: Zone Node Name[LINK]
The name of the zone node. The zone node name connects the heat balance data structure to the system airflow data structure through this node. This node name is defined by the user in the field Zone Air Node Name in the ZoneHVAC:EquipmentConnections object for the zone named in the previous field.
Field: Outlet Node Name[LINK]
The name of the return plenum outlet node. For the zone return plenum there is only one outlet node that can be specified.
Field: Induced Air Outlet Node or NodeList Name[LINK]
The name of an induced air outlet node or the name of a NodeList of such nodes. These nodes are to be used as the secondary inlet air nodes of powered induction terminal units (See AirTerminal:SingleDuct:SeriesPIU:Reheat and AirTerminal:SingleDuct:ParallelPIU:Reheat).
Field: Inlet <#> Node Name[LINK]
The name of a plenum inlet node. There is no limit to the number of inlet nodes, and there may be no duplicate inlet node names. (Note that some EnergyPlus editing tools may allow only 500 inlet node names, but this may be increased by extending the object in the Energy+.idd file.)
An IDF example of a zone return plenum component specification:
Below is an example of the AirLoopHVAC:ReturnPath for the simple case shown above.
AirLoopHVAC:SupplyPlenum[LINK]
The building shown in the figure below consists of three controlled zones served by an AirLoopHVAC:SupplyPlenum beneath the floor.
Figure 131. Illustration of AirLoopHVAC:SupplyPlenum
The AirLoopHVAC:SupplyPlenum has a heat balance connection and building description, and a system airflow connection which transfers the airflow from the supply plenum zone to the controlled zones in the system simulation. The input described in this section is mainly just for the system airflow connections in the HVAC algorithms. In addition the supply plenum zone must be fully input in the building zone description. The supply plenum zone description needs to contain the wall descriptions, the interzone ceiling and floor, and the ground connection. All the other attributes of a zone that can be specified in the building description can be utilized with a supply plenum zone if necessary, i.e. scheduled loads, windows, etc.
After all the building zone attributes are specified, the AirLoopHVAC:SupplyPlenum object is specified and included as one of the named components in an AirLoopHVAC:SupplyPath.
Inputs[LINK]
Field: Name[LINK]
A unique identifying name identifying the AirLoopHVAC:SupplyPlenum system component.
Field: Zone Name[LINK]
The zone name specified in the heat balance portion of the input. This piece of input connects the AirLoopHVAC:SupplyPlenum system component to the heat balance data structure.
Field: Zone Node Name[LINK]
The name of the zone node. The zone node name connects the heat balance data structure to the system airflow data structure through this node. This node name is defined by the user in the field Zone Air Node Name in the ZoneHVAC:EquipmentConnections object for the zone named in the previous field.
Field: Inlet Node Name[LINK]
The name of the inlet node to the supply plenum. The AirLoopHVAC:SupplyPlenum component can send air to many outlets, but there is only one inlet.
Field: Outlet <#> Node Name[LINK]
The name of a plenum outlet node. There is no limit to the number of outlet nodes, and there may be no duplicate outlet node names. (Note that some EnergyPlus editing tools may allow only 500 outlet node names, but this may be increased by extending the object in the Energy+.idd file.)
An IDF example of an AirLoopHVAC:SupplyPlenum component specification:
Below is an example of the AirLoopHVAC:SupplyPath for the building shown above.
AirLoopHVAC:ZoneSplitter[LINK]
The AirLoopHVAC:ZoneSplitter is a component that splits airflow from a single inlet to multiple outlets. This component must be referenced in an AirLoopHVAC:SupplyPath object. The input contains only node connection information.
Inputs[LINK]
Field: Name[LINK]
Unique name for this zone splitter.
Field: Inlet Node Name[LINK]
The name of the single inlet node going into the splitter.
Field: Outlet <#> Node Name[LINK]
The name of a splitter outlet node. There is no limit to the number of outlet nodes, and there may be no duplicate outlet node names. (Note that some EnergyPlus editing tools may allow only 500 outlet node names, but this may be increased by extending the object in the Energy+.idd file.)
An example is shown below.
AirLoopHVAC:ZoneMixer[LINK]
The AirLoopHVAC:ZoneMixer takes the air from multiple inlets and mixes the streams together to be sent out of a single outlet node. This is a simple process of summing flows and averaging the air properties. This compoment may be part of an air loop return path or part of an induction terminal unit. When used as a return air mixer, this component must be listed in an AirLoopHVAC:ReturnPath object, and the inlets may be zone return air nodes or AirLoopHVAC:ReturnPlenum outlet nodes. When used in an induction terminal unit (ref. AirTerminal:SingleDuct:SeriesPIU:Reheat, AirTerminal:SingleDuct:ParallelPIU:Reheat, and AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction), one inlet node is the supply (primary) air inlet from the central air handler, and the second inlet node is the induced (secondary) air inlet. These node names should match equivalent node names in the terminal unit.
Inputs[LINK]
Field: Name[LINK]
Unique name for this zone mixer.
Field: Outlet Node Name[LINK]
The name of the single outlet node leaving the mixer.
Field: Inlet <#> Node Name[LINK]
The name of a mixer inlet node. There is no limit to the number of inlet nodes, and there may be no duplicate inlet node names. (Note that some EnergyPlus editing tools may allow only 500 inlet node names, but this may be increased by extending the object in the Energy+.idd file.)
An input example is shown below.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.