As the simulation starts, each module gets called and gets
the values from the input file. These are usually referred to
as GetInput routines. They add another error check on the
inputs that cannot be fully described by the IDD limits plus
they are privy to interactions that their object may have to
another object.
Site:GroundTemperature:BuildingSurface: Some values fall outside the range of 15-25C.
These values may be inappropriate. Please consult the Input Output Reference for more details.
Ground temperatures can have a significant influence on
buildings. Values outside the range indicated may give you
inaccurate simulation temperatures. Consult the Input Output
Reference for more details.
GetSurfaceData: CAUTION -- Interzone surfaces are usually in different zones
Surface = WALLMASS, Zone = ZONE1
Surface = iz-WALLMASS, Zone = ZONE1
Conventionally, interzone surfaces separate two zones.
However, some advanced users may create them in the same zone
for certain heat transfer efficiencies. This warning message
alerts you in case that was not your intention.
Weather file location will be used rather than entered Location object.
..Location object = ATLANTA
..Weather File Location = Tampa International Ap FL USA TMY3 WMO# = 722110
..due to location differences, Latitude difference = [5.68] degrees, Longitude difference = [1.89] degrees.
..Time Zone difference = [0.0] hour(s), Elevation difference = [98.10] percent, [309.00] meters.
You have “attached” a weather file that contains different
location information than your Site:Location
object. The program is warning you of this condition.
GetPollutionFactorInput: Requested reporting for Carbon Equivalent Pollution, but insufficient information is entered.
Both “FuelFactors”
and “EnvironmentalImpactFactors”
must be entered or the displayed carbon pollution will all be
zero.
You have requested reporting for Carbon Equivalent
Pollution (output variables) but you have not entered the
required FuelFactor and EnvironmentalImpactFactor objects that
are necessary to trigger these outputs properly.
BuildingSurface:Detailed = "SURF:xyz", Sun Exposure = "SUNEXPOSED".
..This surface is not exposed to External Environment. Sun exposure has no effect.
The surface has been entered with SunExposed but it is not
an exterior/outdoor surface.
GetSurfaceData: InterZone Surface Areas do not match as expected and might not satisfy conservation of energy:
Area = 1.4E-002 in Surface = 319767, Zone = 2PAV_CONDIC_LOJA_D
Area = 67.0 in Surface = 6C0708, Zone = 3PAV_CONDIC_TEATRO_G
Interzone surface areas usually should be matching between
the two zones.
GetSurfaceData: InterZone Surface Azimuths do not match as expected.
Azimuth = 270.0, Tilt = 90.0, in Surface = 319767, Zone = 2PAV_CONDIC_LOJA_D
Azimuth = 180.0, Tilt = 90.0, in Surface = 6C0708, Zone = 3PAV_CONDIC_TEATRO_G
..surface class of base surface = Wall
Interzone surfaces should be opposite each other –
therefore when Azimuth/Facing do not differ by 180 degrees, a
warning is shown. Likewise, Tilt angles should be checked
here.
GetVertices: Floor is upside down! Tilt angle = [0.0], should be near 180, Surface = "ROOM302-FLOOR", in Zone = "ROOM302".
Automatic fix is attempted.
GetVertices: Roof is upside down! Tilt angle = [180.0], should be near 0, Surface = "ROOM302-CEILING", in Zone = "ROOM302".
Automatic fix is attempted.
In both of these messages, it has been detected that the
outward surface normal for the surfaces is not as expected.
With not as expected angles, the sun will not be received on
these surfaces (typically), so it is something to correct. The
program attempts to fix these – usually caused by entering the
vertices backwards (i.e. clockwise when should have been
counter-clockwise or vice versa).
GetInternalHeatGains: Zone = "02AO_FCU04_AN" occupant density is extremely high.
Occupant Density = [14] person/m2.
Occupant Density = [7.000E-002] m2/person. Problems in Temperature Out of Bounds may result.
The Get Internal Heat Gains routine does some checks as far
as Design Level (and maximum schedule * Design Level) and
compares to density values. Extremely high gains, especially
when no exit for the air (i.e. infiltration, ventilation) can
often result in Temperature Out of Bounds errors (see below in
Simulation messages) and these can be fatal.
GetVertices: Distance between two vertices < .01, possibly coincident. for Surface = 1%PIANOINTERRATO:UFFICI_WALL_3_0_1, in Zone = 1%PIANOINTERRATO:UFFICI
Vertex [2] = (-53.99,5.86,0.50)
Vertex [1] = (-53.99,5.86,0.51)
Dropping Vertex [2].
The distance between two vertices is very small (.01 meter
~ .4 inches). This distance is too small for shading
calculations and the vertex is dropped.
CheckConvexity: Surface = "ZN001:ROOF001" is non-convex.
Shown when DisplayExtraWarnings is on and a surface is not
a convex shape. By itself, this is only a warning but see the
severe in the next section when it has impact on the
calculations.
GetSurfaceData: Some Outward Facing angles of subsurfaces differ significantly from base surface.
...use Output:Diagnostics,DisplayExtraWarnings; to show more details on individual surfaces.
GetSurfaceData: Outward facing angle [95.5] of subsurface = "WL2-1" significantly different than
..facing angle [275.5] of base surface = WEST WALL 2 Tilt = 90.0
..surface class of base surface = Wall
These are two versions of the same message. The first is
shown when DisplayExtraWarnings is not activated. The second
is shown for details on each subsurface that has the error.
The error is usually that the subsurface vertices have been
entered in opposite order (i.e. clockwise vs
counter-clockwise) from the base surface.
This building has no thermal mass which can cause an unstable solution.
Use Material object for all opaque material definitions except very light insulation layers.
You have probably defined all the surfaces in this building
with resistive only constructions (i.e. object
Material:NoMass). An unstable solution can result (including
crashes).
GetVertices: Distance between two vertices < .01, possibly coincident. for Surface = 1%PIANOINTERRATO:UFFICI_WALL_3_0_1, in Zone = 1%PIANOINTERRATO:UFFICI
Vertex [3] = (-44.82,-12.14,0.51)
Vertex [2] = (-44.82,-12.14,0.50)
Cannot Drop Vertex [3].
Number of Surface Sides at minimum.
The distance between two vertices is very small (.01 meter
~ .4 inches). This distance is too small for shading
calculations but the vertex cannot be dropped as that would
bring the surface to less than 3 sides. This surface is
degenerate and should be removed from your input file.
DetermineShadowingCombinations: Surface = "0%VESPAIO:ZONA1\_ROOF\_1\_6\_0" is a receiving surface and is non-convex.
...Shadowing values may be inaccurate. Check .shd report file for more surface shading details
Receiving surfaces which are not convex shapes will not be
calculated correctly with the shadowing routines. You should
view the results carefully.
Severes in this realm usually lead to Fatals.
Preceding conditions lead to termination.
Example Error Messages from Module GetInput routines[LINK]
As the simulation starts, each module gets called and gets the values from the input file. These are usually referred to as GetInput routines. They add another error check on the inputs that cannot be fully described by the IDD limits plus they are privy to interactions that their object may have to another object.
Warning[LINK]
Ground temperatures can have a significant influence on buildings. Values outside the range indicated may give you inaccurate simulation temperatures. Consult the Input Output Reference for more details.
Conventionally, interzone surfaces separate two zones. However, some advanced users may create them in the same zone for certain heat transfer efficiencies. This warning message alerts you in case that was not your intention.
You have “attached” a weather file that contains different location information than your Site:Location object. The program is warning you of this condition.
Both “FuelFactors” and “EnvironmentalImpactFactors” must be entered or the displayed carbon pollution will all be zero.
You have requested reporting for Carbon Equivalent Pollution (output variables) but you have not entered the required FuelFactor and EnvironmentalImpactFactor objects that are necessary to trigger these outputs properly.
The surface has been entered with SunExposed but it is not an exterior/outdoor surface.
Interzone surface areas usually should be matching between the two zones.
Interzone surfaces should be opposite each other – therefore when Azimuth/Facing do not differ by 180 degrees, a warning is shown. Likewise, Tilt angles should be checked here.
In both of these messages, it has been detected that the outward surface normal for the surfaces is not as expected. With not as expected angles, the sun will not be received on these surfaces (typically), so it is something to correct. The program attempts to fix these – usually caused by entering the vertices backwards (i.e. clockwise when should have been counter-clockwise or vice versa).
The Get Internal Heat Gains routine does some checks as far as Design Level (and maximum schedule * Design Level) and compares to density values. Extremely high gains, especially when no exit for the air (i.e. infiltration, ventilation) can often result in Temperature Out of Bounds errors (see below in Simulation messages) and these can be fatal.
The distance between two vertices is very small (.01 meter ~ .4 inches). This distance is too small for shading calculations and the vertex is dropped.
Shown when DisplayExtraWarnings is on and a surface is not a convex shape. By itself, this is only a warning but see the severe in the next section when it has impact on the calculations.
Severe[LINK]
These are two versions of the same message. The first is shown when DisplayExtraWarnings is not activated. The second is shown for details on each subsurface that has the error. The error is usually that the subsurface vertices have been entered in opposite order (i.e. clockwise vs counter-clockwise) from the base surface.
You have probably defined all the surfaces in this building with resistive only constructions (i.e. object Material:NoMass). An unstable solution can result (including crashes).
The distance between two vertices is very small (.01 meter ~ .4 inches). This distance is too small for shading calculations but the vertex cannot be dropped as that would bring the surface to less than 3 sides. This surface is degenerate and should be removed from your input file.
Receiving surfaces which are not convex shapes will not be calculated correctly with the shadowing routines. You should view the results carefully.
Fatal[LINK]
Severes in this realm usually lead to Fatals.
Preceding conditions lead to termination.