Group – Detailed
Ground Heat Transfer[LINK]
Detailed Ground Heat
Transfer[LINK]
The following objects may be included in an EnergyPlus
input IDF file but are handled by the Slab preprocessor:
GroundHeatTransfer:Slab:Materials
GroundHeatTransfer:Slab:MatlProps
GroundHeatTransfer:Slab:BoundConds
GroundHeatTransfer:Slab:BldgProps
GroundHeatTransfer:Slab:Insulation
GroundHeatTransfer:Slab:EquivalentSlab
GroundHeatTransfer:Slab:AutoGrid
GroundHeatTransfer:Slab:ManualGrid
GroundHeatTransfer:Slab:XFACE
GroundHeatTransfer:Slab:YFACE
GroundHeatTransfer:Slab:ZFACE
The following objects may be included in an EnergyPlus
input IDF file but are handled by the Basement
preprocessor:
GroundHeatTransfer:Basement:SimParameters
GroundHeatTransfer:Basement:MatlProps
GroundHeatTransfer:Basement:Insulation
GroundHeatTransfer:Basement:SurfaceProps
GroundHeatTransfer:Basement:BldgData
GroundHeatTransfer:Basement:Interior
GroundHeatTransfer:Basement:ComBldg
GroundHeatTransfer:Basement:EquivSlab
GroundHeatTransfer:Basement:EquivAutoGrid
GroundHeatTransfer:Basement:AutoGrid
GroundHeatTransfer:Basement:ManualGrid
GroundHeatTransfer:Basement:XFACE
GroundHeatTransfer:Basement:YFACE
GroundHeatTransfer:Basement:ZFACE
The documentation both the Slab and Basement objects appear
in the AuxiliaryPrograms document under the “Ground Heat
Transfer in EnergyPlus” heading.
The only object described in this section is the control
object which activates the use of the preprocessor.
GroundHeatTransfer:Control[LINK]
The GroundHeatTransfer:Control
object determines if the Slab and Basement preprocessors are
going to be executed. When a Slab or Basement run is performed
the results are saved in files with extensions .SLAB or .BSMT
so that they do not need to be rerun if no input changes are
made to the GroundHeatTransfer:Slab or
GroundHeatTransfer:Basement objects.
This alpha field is the name of the GroundHeatTransfer:Control
object. It is used as an identifier.
Field: Run Basement
Preprocessor[LINK]
The field can either be Yes or No and defaults to No. It is
used to control whether the Basement preprocessor program is
executed. If it has been previously executed the results are
stored in the .BSMT file and do not necessary need to be run
again unless the GroundHeatTransfer:Basement objects have
changed.
Field: Run Slab
Preprocessor[LINK]
The field can either be Yes or No and defaults to No. It is
used to control whether the Slab preprocessor program is
executed. If it has been previously executed the results are
stored in the .SLAB file and do not necessary need to be run
again unless the GroundHeatTransfer:Slab objects have
changed.
Group – Detailed Ground Heat Transfer[LINK]
Detailed Ground Heat Transfer[LINK]
The following objects may be included in an EnergyPlus input IDF file but are handled by the Slab preprocessor:
GroundHeatTransfer:Slab:Materials
GroundHeatTransfer:Slab:MatlProps
GroundHeatTransfer:Slab:BoundConds
GroundHeatTransfer:Slab:BldgProps
GroundHeatTransfer:Slab:Insulation
GroundHeatTransfer:Slab:EquivalentSlab
GroundHeatTransfer:Slab:AutoGrid
GroundHeatTransfer:Slab:ManualGrid
GroundHeatTransfer:Slab:XFACE
GroundHeatTransfer:Slab:YFACE
GroundHeatTransfer:Slab:ZFACE
The following objects may be included in an EnergyPlus input IDF file but are handled by the Basement preprocessor:
GroundHeatTransfer:Basement:SimParameters
GroundHeatTransfer:Basement:MatlProps
GroundHeatTransfer:Basement:Insulation
GroundHeatTransfer:Basement:SurfaceProps
GroundHeatTransfer:Basement:BldgData
GroundHeatTransfer:Basement:Interior
GroundHeatTransfer:Basement:ComBldg
GroundHeatTransfer:Basement:EquivSlab
GroundHeatTransfer:Basement:EquivAutoGrid
GroundHeatTransfer:Basement:AutoGrid
GroundHeatTransfer:Basement:ManualGrid
GroundHeatTransfer:Basement:XFACE
GroundHeatTransfer:Basement:YFACE
GroundHeatTransfer:Basement:ZFACE
The documentation both the Slab and Basement objects appear in the AuxiliaryPrograms document under the “Ground Heat Transfer in EnergyPlus” heading.
The only object described in this section is the control object which activates the use of the preprocessor.
GroundHeatTransfer:Control[LINK]
The GroundHeatTransfer:Control object determines if the Slab and Basement preprocessors are going to be executed. When a Slab or Basement run is performed the results are saved in files with extensions .SLAB or .BSMT so that they do not need to be rerun if no input changes are made to the GroundHeatTransfer:Slab or GroundHeatTransfer:Basement objects.
Inputs[LINK]
Field: Name[LINK]
This alpha field is the name of the GroundHeatTransfer:Control object. It is used as an identifier.
Field: Run Basement Preprocessor[LINK]
The field can either be Yes or No and defaults to No. It is used to control whether the Basement preprocessor program is executed. If it has been previously executed the results are stored in the .BSMT file and do not necessary need to be run again unless the GroundHeatTransfer:Basement objects have changed.
Field: Run Slab Preprocessor[LINK]
The field can either be Yes or No and defaults to No. It is used to control whether the Slab preprocessor program is executed. If it has been previously executed the results are stored in the .SLAB file and do not necessary need to be run again unless the GroundHeatTransfer:Slab objects have changed.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.