Branches, Connectors,
and Nodes[LINK]
In EnergyPlus, the HVAC system and plant form a network
(technically, a graph). The individual pieces of equipment –
the fans, coils, chillers, etc. – are connected together by
air ducts and fluid pipes. In EnergyPlus nomenclature, the air
and fluid circuits are called loops. Specifying how an
individual system and plant are connected is done in the
EnergyPlus input (IDF) file. The overall structure of the
network is defined with Branch
and Connector objects. The detail is filled with components
and their inlet and outlet nodes. A Branch
consists of one or more components arranged sequentially along
a pipe or duct. A Connector specifies how three or more
branches are connected through a Splitter or Mixer. Nodes
connect components along a branch: the outlet node of one
component is the inlet node of the next downstream component.
The nodes represent conditions at a point on a loop. Each
component has one or more inlet and outlet nodes, depending on
how many loops it interacts with. A fan, for instance, has one
inlet node and one outlet node, since it interacts with a
single air loop. A water coil will have 2 inlet and 2 outlet
nodes, since it interacts with an air and a fluid loop. Figure shows a diagram of
an EnergyPlus HVAC input.
As an illustration of how such a network is built up on the
IDF, here is the section of the IDF that describes the supply
fan, splitter, and heating and cooling coil section of the
dual duct air system.
BranchList,
Dual Duct
Air Loop Branches, !- Name
Air Loop Main Branch, !- Branch
1 Name
Heating Coil Air Sys Branch, !- Branch
2 Name
Cooling Coil Air Sys Branch; !- Branch
3 Name
ConnectorList,
Dual Duct
Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
DualDuctAirSplitter; !- Connector 1 Name
NodeList,
Zone
Equipment Inlet Node List, !- Name
Main Hot Air Inlet, !- Node 1 Name
Main Cold Air Inlet; !- Node 2 Name
NodeList,
Air Loop Outlet Node List, !- Name
Heating Coil Outlet Node,!- Node 1 Name
Cooling Coil Outlet Node;!- Node 2 Name
Branch,
Air Loop Main Branch, !- Name
autosize, !- Maximum Flow Rate
{m3/s}
Fan:ConstantVolume, !- Component 1 Object Type
Supply Fan 1, !- Component 1 Name
Supply Fan Inlet Node, !- Component 1 Inlet Node
Name
Supply Fan Outlet Node, !- Component 1 Outlet Node
Name
PASSIVE; !- Component 1 Branch
Control Type
Branch,
Heating Coil Air Sys Branch, !- Name
autosize, !- Maximum Flow Rate
{m3/s}
Coil:Heating:Water, !- Component 1 Object Type
Main Heating Coil, !- Component 1 Name
Heating Coil Inlet Node, !- Component 1 Inlet Node
Name
Heating Coil Outlet Node,!- Component 1 Outlet Node
Name
ACTIVE; !- Component 1 Branch
Control Type
Branch,
Cooling Coil Air Sys Branch, !- Name
autosize, !- Maximum Flow Rate
{m3/s}
Coil:Cooling:Water, !- Component 1 Object Type
Simple Cooling Coil, !- Component 1 Name
Cooling Coil Inlet Node, !- Component 1 Inlet Node
Name
Cooling Coil Outlet Node,!- Component 1 Outlet Node
Name
ACTIVE; !- Component 1 Branch
Control Type
Connector:Splitter,
DualDuctAirSplitter, !- Name
Air Loop Main Branch, !- Inlet Branch
Name
Heating Coil Air Sys Branch, !- Outlet Branch
1 Name
Cooling Coil Air Sys Branch; !- Outlet Branch
2 Name
Fan:ConstantVolume,
Supply Fan 1, !- Name
FanAndCoilAvailSched, !- Availability Schedule
Name
0.7, !- Fan Efficiency
600.0, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate
{m3/s}
0.9, !- Motor Efficiency
1.0, !- Motor In Airstream
Fraction
Supply Fan Inlet Node, !- Fan Inlet Node Name
Supply Fan Outlet Node; !- Fan Outlet Node Name
Coil:Cooling:Water,
Simple Cooling Coil, !- Name
CoolingCoilAvailSched, !- Availability Schedule
Name
autosize, !- Design Water Flow Rate
{m3/s}
autosize, !- Design Air Flow Rate
{m3/s}
autosize, !- Design Inlet Water Temperature
{C}
autosize, !- Design Inlet Air Temperature
{C}
autosize, !- Design Outlet Air Temperature
{C}
autosize, !- Design Inlet Air Humidity Ratio
{kg-H2O/kg-air}
autosize, !- Design Outlet Air Humidity Ratio
{kg-H2O/kg-air}
Cooling Coil Water Inlet Node, !- Water Inlet Node
Name
Cooling Coil Water Outlet Node, !- Water Outlet Node
Name
Cooling Coil Inlet Node, !- Air Inlet Node Name
Cooling Coil Outlet Node,!- Air Outlet Node Name
SimpleAnalysis, !- Type of Analysis
CrossFlow; !- Heat Exchanger
Configuration
AirLoopHVAC:ZoneSplitter,
ZoneColdAirSupplySplitter, !- Name
Main Cold Air Inlet, !- Inlet Node Name
Zone
1 Dual Duct
Cold Inlet, !- Outlet 1 Node Name
Zone
2 Dual Duct
Cold Inlet, !- Outlet 2 Node Name
Zone
3 Dual Duct
Cold Inlet; !- Outlet 3 Node Name
AirLoopHVAC:ZoneSplitter,
ZoneHotAirSupplySplitter,!- Name
Main Hot Air Inlet, !- Inlet Node Name
Zone
1 Dual Duct
Hot Inlet, !- Outlet 1 Node Name
Zone
2 Dual Duct
Hot Inlet, !- Outlet 2 Node Name
Zone
3 Dual Duct
Hot Inlet; !- Outlet 3 Node Name
AirLoopHVAC:ZoneMixer,
ZoneReturnAirMixer, !- Name
Return Air Mixer Outlet, !- Outlet Node Name
Zone
1 Outlet Node, !- Inlet 1 Node Name
Zone
2 Outlet Node, !- Inlet 2 Node Name
Zone
3 Outlet Node; !- Inlet 3 Node Name
Coil:Heating:Water,
Main Heating Coil, !- Name
FanAndCoilAvailSched, !- Availability Schedule
Name
autosize, !- U-Factor Times Area Value
{W/K}
autosize, !- Maximum Water Flow Rate
{m3/s}
Heating Coil Water Inlet,!- Water Inlet Node Name
Heating Coil Water Outlet, !- Water Outlet Node
Name
Heating Coil Inlet Node, !- Air Inlet Node Name
Heating Coil Outlet Node,!- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance
Input Method
autosize, !- Nominal Capacity {W}
82.2, !- Design Inlet Water
Temperature {C}
16.6, !- Design Inlet Air
Temperature {C}
71.1, !- Design Outlet Water
Temperature {C}
32.2; !- Design Outlet Air
Temperature {C}
Controller:WaterCoil,
Main Cooling Coil Controller, !- Name
Temperature, !- Control Variable
Reverse, !- Action
FLOW, !- Actuator Variable
Cooling Coil Outlet Node,!- Sensor Node Name
Cooling Coil Water Inlet Node, !- Actuator Node
Name
0.001, !- Controller Convergence Tolerance
{deltaC}
autosize, !- Maximum Actuated Flow
{m3/s}
0.0; !- Minimum Actuated Flow
{m3/s}
Controller:WaterCoil,
Main Heating Coil Controller, !- Name
Temperature, !- Control Variable
Normal, !- Action
FLOW, !- Actuator Variable
Heating Coil Outlet Node,!- Sensor Node Name
Heating Coil Water Inlet,!- Actuator Node Name
0.01, !- Controller Convergence Tolerance
{deltaC}
autosize, !- Maximum Actuated Flow
{m3/s}
0.0; !- Minimum Actuated Flow
{m3/s}
Obviously, the creation of such a system/plant network
description is best handled by a graphical user interface
(GUI). However, for testing purposes a developer may have to
create the input for a component by hand and insert it into an
existing IDF. Then the developer must be careful to choose
unique names for the branches and nodes and make sure the
entire network makes physical sense.
Branches, Connectors, and Nodes[LINK]
In EnergyPlus, the HVAC system and plant form a network (technically, a graph). The individual pieces of equipment – the fans, coils, chillers, etc. – are connected together by air ducts and fluid pipes. In EnergyPlus nomenclature, the air and fluid circuits are called loops. Specifying how an individual system and plant are connected is done in the EnergyPlus input (IDF) file. The overall structure of the network is defined with Branch and Connector objects. The detail is filled with components and their inlet and outlet nodes. A Branch consists of one or more components arranged sequentially along a pipe or duct. A Connector specifies how three or more branches are connected through a Splitter or Mixer. Nodes connect components along a branch: the outlet node of one component is the inlet node of the next downstream component. The nodes represent conditions at a point on a loop. Each component has one or more inlet and outlet nodes, depending on how many loops it interacts with. A fan, for instance, has one inlet node and one outlet node, since it interacts with a single air loop. A water coil will have 2 inlet and 2 outlet nodes, since it interacts with an air and a fluid loop. Figure shows a diagram of an EnergyPlus HVAC input.
As an illustration of how such a network is built up on the IDF, here is the section of the IDF that describes the supply fan, splitter, and heating and cooling coil section of the dual duct air system.
BranchList,
Dual Duct Air Loop Branches, !- Name
Air Loop Main Branch, !- Branch 1 Name
Heating Coil Air Sys Branch, !- Branch 2 Name
Cooling Coil Air Sys Branch; !- Branch 3 Name
ConnectorList,
Dual Duct Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
DualDuctAirSplitter; !- Connector 1 Name
NodeList,
Zone Equipment Inlet Node List, !- Name
Main Hot Air Inlet, !- Node 1 Name
Main Cold Air Inlet; !- Node 2 Name
NodeList,
Air Loop Outlet Node List, !- Name
Heating Coil Outlet Node,!- Node 1 Name
Cooling Coil Outlet Node;!- Node 2 Name
Branch,
Air Loop Main Branch, !- Name
autosize, !- Maximum Flow Rate {m3/s}
Fan:ConstantVolume, !- Component 1 Object Type
Supply Fan 1, !- Component 1 Name
Supply Fan Inlet Node, !- Component 1 Inlet Node Name
Supply Fan Outlet Node, !- Component 1 Outlet Node Name
PASSIVE; !- Component 1 Branch Control Type
Branch,
Heating Coil Air Sys Branch, !- Name
autosize, !- Maximum Flow Rate {m3/s}
Coil:Heating:Water, !- Component 1 Object Type
Main Heating Coil, !- Component 1 Name
Heating Coil Inlet Node, !- Component 1 Inlet Node Name
Heating Coil Outlet Node,!- Component 1 Outlet Node Name
ACTIVE; !- Component 1 Branch Control Type
Branch,
Cooling Coil Air Sys Branch, !- Name
autosize, !- Maximum Flow Rate {m3/s}
Coil:Cooling:Water, !- Component 1 Object Type
Simple Cooling Coil, !- Component 1 Name
Cooling Coil Inlet Node, !- Component 1 Inlet Node Name
Cooling Coil Outlet Node,!- Component 1 Outlet Node Name
ACTIVE; !- Component 1 Branch Control Type
Connector:Splitter,
DualDuctAirSplitter, !- Name
Air Loop Main Branch, !- Inlet Branch Name
Heating Coil Air Sys Branch, !- Outlet Branch 1 Name
Cooling Coil Air Sys Branch; !- Outlet Branch 2 Name
Fan:ConstantVolume,
Supply Fan 1, !- Name
FanAndCoilAvailSched, !- Availability Schedule Name
0.7, !- Fan Efficiency
600.0, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.9, !- Motor Efficiency
1.0, !- Motor In Airstream Fraction
Supply Fan Inlet Node, !- Fan Inlet Node Name
Supply Fan Outlet Node; !- Fan Outlet Node Name
Coil:Cooling:Water,
Simple Cooling Coil, !- Name
CoolingCoilAvailSched, !- Availability Schedule Name
autosize, !- Design Water Flow Rate {m3/s}
autosize, !- Design Air Flow Rate {m3/s}
autosize, !- Design Inlet Water Temperature {C}
autosize, !- Design Inlet Air Temperature {C}
autosize, !- Design Outlet Air Temperature {C}
autosize, !- Design Inlet Air Humidity Ratio {kg-H2O/kg-air}
autosize, !- Design Outlet Air Humidity Ratio {kg-H2O/kg-air}
Cooling Coil Water Inlet Node, !- Water Inlet Node Name
Cooling Coil Water Outlet Node, !- Water Outlet Node Name
Cooling Coil Inlet Node, !- Air Inlet Node Name
Cooling Coil Outlet Node,!- Air Outlet Node Name
SimpleAnalysis, !- Type of Analysis
CrossFlow; !- Heat Exchanger Configuration
AirLoopHVAC:ZoneSplitter,
ZoneColdAirSupplySplitter, !- Name
Main Cold Air Inlet, !- Inlet Node Name
Zone 1 Dual Duct Cold Inlet, !- Outlet 1 Node Name
Zone 2 Dual Duct Cold Inlet, !- Outlet 2 Node Name
Zone 3 Dual Duct Cold Inlet; !- Outlet 3 Node Name
AirLoopHVAC:ZoneSplitter,
ZoneHotAirSupplySplitter,!- Name
Main Hot Air Inlet, !- Inlet Node Name
Zone 1 Dual Duct Hot Inlet, !- Outlet 1 Node Name
Zone 2 Dual Duct Hot Inlet, !- Outlet 2 Node Name
Zone 3 Dual Duct Hot Inlet; !- Outlet 3 Node Name
AirLoopHVAC:ZoneMixer,
ZoneReturnAirMixer, !- Name
Return Air Mixer Outlet, !- Outlet Node Name
Zone 1 Outlet Node, !- Inlet 1 Node Name
Zone 2 Outlet Node, !- Inlet 2 Node Name
Zone 3 Outlet Node; !- Inlet 3 Node Name
Coil:Heating:Water,
Main Heating Coil, !- Name
FanAndCoilAvailSched, !- Availability Schedule Name
autosize, !- U-Factor Times Area Value {W/K}
autosize, !- Maximum Water Flow Rate {m3/s}
Heating Coil Water Inlet,!- Water Inlet Node Name
Heating Coil Water Outlet, !- Water Outlet Node Name
Heating Coil Inlet Node, !- Air Inlet Node Name
Heating Coil Outlet Node,!- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
autosize, !- Nominal Capacity {W}
82.2, !- Design Inlet Water Temperature {C}
16.6, !- Design Inlet Air Temperature {C}
71.1, !- Design Outlet Water Temperature {C}
32.2; !- Design Outlet Air Temperature {C}
Controller:WaterCoil,
Main Cooling Coil Controller, !- Name
Temperature, !- Control Variable
Reverse, !- Action
FLOW, !- Actuator Variable
Cooling Coil Outlet Node,!- Sensor Node Name
Cooling Coil Water Inlet Node, !- Actuator Node Name
0.001, !- Controller Convergence Tolerance {deltaC}
autosize, !- Maximum Actuated Flow {m3/s}
0.0; !- Minimum Actuated Flow {m3/s}
Controller:WaterCoil,
Main Heating Coil Controller, !- Name
Temperature, !- Control Variable
Normal, !- Action
FLOW, !- Actuator Variable
Heating Coil Outlet Node,!- Sensor Node Name
Heating Coil Water Inlet,!- Actuator Node Name
0.01, !- Controller Convergence Tolerance {deltaC}
autosize, !- Maximum Actuated Flow {m3/s}
0.0; !- Minimum Actuated Flow {m3/s}
Obviously, the creation of such a system/plant network description is best handled by a graphical user interface (GUI). However, for testing purposes a developer may have to create the input for a component by hand and insert it into an existing IDF. Then the developer must be careful to choose unique names for the branches and nodes and make sure the entire network makes physical sense.