Daylight Modeling[LINK]
          Why isn’t my lighting energy being reduced with a daylighting system?
          In order to see changes in the lighting electric power consumption due to daylighting, the Fraction Replaceable in the Lights input object must be set to 1.0. This is documented in the I/O reference, and also a warning is generated in the ERR file.
                    
         
        
Daylight Modeling[LINK]
Why isn’t my lighting energy being reduced with a daylighting system?
In order to see changes in the lighting electric power consumption due to daylighting, the Fraction Replaceable in the Lights input object must be set to 1.0. This is documented in the I/O reference, and also a warning is generated in the ERR file.
Documentation content copyright © 1996-2016 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.