The ##def command allows a block of input
text to be defined and given a name. The block of text can
then be inserted anywhere in the EnergyPlus input stream by
simply referencing the name of the block. (This process is
called macro expansion.) The block can have parameters (also
called arguments) that can be given different values each time
the block is referenced.
The syntax of the ##def command is as
follows:
unique name
| zero or more arguments macro text
| | |
| | |
##def macro-name [ arg1 arg2,arg3 ...] text line 1
|_ | | | |_ | _| |
| | | | | | | |
| | | | | | |
zero one zero_| space(s) one
or or or or comma or
more more more more
spaces spaces spaces spaces
Example: Define a schedule macro with name “All_Const”:
**##def** All_Const[x]
** ** Fraction, WeekON, 1,1, 12,31;
WEEKSCHEDULE, WeekON,
DayON,DayON,DayON,
DayON,DayON,DayON,
DayON,DayON,DayON,
DayON,DayON,DayON;
DAYSCHEDULE, DayON, Fraction,
x,x,x,x,x,x,x,x,x,x,x,x,
x,x,x,x,x,x,x,x,x,x,x,x ;
**##enddef**
Then, in the EnergyPlus input stream (file in.imf), when we
write :
SCHEDULE, Constant At 0.8, All_Const[0.8]
the result (file out.idf) is equivalent to:
SCHEDULE, Constant At 0.8,
Fraction, WeekON, 1,1, 12,31;
WEEKSCHEDULE, WeekON,
DayON,DayON,DayON,
DayON,DayON,DayON,
DayON,DayON,DayON,
DayON,DayON,DayON;
DAYSCHEDULE, DayON, Fraction,
0.8,0.8,0.8,0.8,0.8,0.8,0.8,0.8,0.8,0.8,0.8,0.8,
0.8,0.8,0.8,0.8,0.8,0.8,0.8,0.8,0.8,0.8,0.8,0.8 ;
Macro definitions may have one or more arguments; the
maximum number of arguments is 32. When a macro with arguments
is referenced, its arguments must be given values. When a
macro has no arguments, the brackets are still required both
for macro definition and reference.
Caution: Square brackets [ ] have been used in some
versions of EnergyPlus inputs as comment/units fields. These
will be expanded if left in the IDF and sent to EPMacro.
Macro names must be unique (except see
##set1 below); i.e., when a macro name is
defined it cannot be defined again. Macro names are limited to
40 characters.
To summarize, commands you use to define macros are the
following:
##def macro-name
[arg1,..,argn ]
macro-text
Defines a macro with the name macro-name and arguments
“arg1” through “argn”. “Macro-text” is one or more
lines of text. If there are no arguments, the syntax is
##def macro-name macro-text.
##enddef
Indicates the end of the macro definition initiated by
##def.
##def1 macro-name
[arg1,..,argn ]
macro-text
This is the same as ##def but there is
only one line of text so that the terminating command
##enddef is not required.
##set1 macro-name macro-text
Like ##def1 but has no arguments and
macro-text is evaluated before storing. “Macro-text is
evaluated” means that if macro-text contains other macros,
these macros will be expanded, and the expanded text becomes
the macro-text defined by ##set1.
Example:
**\#\#def1** xx 123
**\#\#set1** yy xx[]
is equivalent to: ##set1 yy 123
##set1 can also be used to redefine
macro-name.
##set1 x 0 . . .
##set1 x #eval[ x[]+1
]
(see Arithmetic Operations for description of the
#eval macro.)
Arithmetic Operations[LINK]
The built-in macro called #eval[ ] can be
used to perform arithmetic, literal, and logical operations.
It can be abbreviated to # [ ].
#eval[ X OP Y ] or #[ X OP Y ]
gives the result X OP Y. The allowed values for X, OP, and
Y, and the corresponding result, are shown in the following
table.
| X* |
OP ** |
Y |
Result |
| number |
+ (plus) |
number |
number |
| number |
- (minus) |
number |
number |
| number |
* (times) |
number |
number |
| number |
/ (divided by) |
number |
number |
| number |
min |
number |
number |
| number |
max |
number |
number |
| number |
mod |
number |
number |
| number |
** (power) |
number |
number |
| SIN |
OF |
number (degrees) |
number |
| COS |
OF |
number (degrees) |
number |
| TAN |
OF |
number (degrees) |
number |
| SQRT |
OF |
number |
number |
| ABS |
OF |
number |
number |
| ASIN |
OF |
number |
number (degrees) |
| ACOS |
OF |
number |
number (degrees) |
| ATAN |
OF |
number |
number |
| INT |
OF |
number |
number |
| LOG10 |
OF |
number |
number |
| LOG |
OF |
number |
number |
| literal1 |
// (concatenate) |
literal2 |
literal “literal1literal2” |
| literal1 |
/// (concatenate) |
literal2 |
literal “literal1 literal2” |
| literal |
EQS (=) |
literal |
logical (true or false) case
sensitive |
| literal |
NES (\(\neq\)) |
literal |
logical (true or false) case
sensitive |
| literal |
EQSU (=) |
literal |
logical (true or false) not case
sensitive |
| literal |
NESU (\(\neq\)) |
literal |
logical (true or false) not case
sensitive |
| logical |
AND |
logical |
logical (true or false) |
| logical |
OR |
logical |
logical (true or false) |
|
NOT |
logical |
logical (true or false) |
| number |
EQ (=) |
number |
logical (true or false) |
| number |
NE (\(\neq\)) |
number |
logical (true or false) |
| number |
GT (>) |
number |
logical (true or false) |
| number |
GE (\(\geq\)) |
number |
logical (true or false) |
| number |
LT (<) |
number |
logical (true or false) |
| number |
LE (\(\leq\)) |
number |
logical (true or false) |
| * Upper or lower case is allowed
for SIN, COS, etc. |
|
|
|
| ** Upper or lower case is
allowed for OF, EQS, etc. |
|
|
|
Example
#eval[** 1 + 2 **] when expanded becomes
3.
#eval[** 1 +#eval[2 * 3]
**] when expanded becomes 7.
Example
##set1 city[] Washington
DesignDay, #[ city[ ] /// SUMMER ], ! Design Day Name
gives
DesignDay, "Washington SUMMER", ! Design Day Name
The following example illustrates the use of
#eval inside #if
commands:
##if #[** city[ ] EQS Chicago
**]
##if #[#[** city[ ] EQS Chicago ]
and#[** occup[ ] NES low **]** **]**
Notes:
- For logical values:
False = 0 or BLANK,
True = any other character
- A literal must be enclosed inside a pair of double quotes
if it contains BLANKs or reserved characters like [ ] ( )
,
E.g., “abc *def”
Otherwise, the quotes around the literals are optional.
- Literal concatenation operators // and /// produce quoted
literals.
E.g., # [ large /// office ] gives “large office”
Literals are case sensitive. For example, “Chicago”,
“CHICAGO” and “chicago” are distinct.
EQS and NES are case sensitive string comparisons. EQSU
and NESU are case insensitive string comparisons.
Literals are limited to 40 characters.
Defining Blocks of Input[LINK]
The ##def command allows a block of input text to be defined and given a name. The block of text can then be inserted anywhere in the EnergyPlus input stream by simply referencing the name of the block. (This process is called macro expansion.) The block can have parameters (also called arguments) that can be given different values each time the block is referenced.
The syntax of the ##def command is as follows:
Example: Define a schedule macro with name “All_Const”:
Then, in the EnergyPlus input stream (file in.imf), when we write :
the result (file out.idf) is equivalent to:
Macro definitions may have one or more arguments; the maximum number of arguments is 32. When a macro with arguments is referenced, its arguments must be given values. When a macro has no arguments, the brackets are still required both for macro definition and reference.
Caution: Square brackets [ ] have been used in some versions of EnergyPlus inputs as comment/units fields. These will be expanded if left in the IDF and sent to EPMacro.
Macro names must be unique (except see ##set1 below); i.e., when a macro name is defined it cannot be defined again. Macro names are limited to 40 characters.
To summarize, commands you use to define macros are the following:
##def macro-name [arg1,..,argn ] macro-text
Defines a macro with the name macro-name and arguments “arg1” through “argn”. “Macro-text” is one or more lines of text. If there are no arguments, the syntax is ##def macro-name macro-text.
##enddef
Indicates the end of the macro definition initiated by ##def.
##def1 macro-name [arg1,..,argn ] macro-text
This is the same as ##def but there is only one line of text so that the terminating command ##enddef is not required.
##set1 macro-name macro-text
Like ##def1 but has no arguments and macro-text is evaluated before storing. “Macro-text is evaluated” means that if macro-text contains other macros, these macros will be expanded, and the expanded text becomes the macro-text defined by ##set1.
Example:
is equivalent to: ##set1 yy 123
##set1 can also be used to redefine macro-name.
##set1 x 0 . . .
##set1 x #eval[ x[]+1 ]
(see Arithmetic Operations for description of the #eval macro.)
Arithmetic Operations[LINK]
The built-in macro called #eval[ ] can be used to perform arithmetic, literal, and logical operations. It can be abbreviated to # [ ].
#eval[ X OP Y ] or #[ X OP Y ]
gives the result X OP Y. The allowed values for X, OP, and Y, and the corresponding result, are shown in the following table.
Example
#eval[** 1 + 2 **] when expanded becomes 3.
#eval[** 1 +#eval[2 * 3] **] when expanded becomes 7.
Example
##set1 city[] Washington
DesignDay, #[ city[ ] /// SUMMER ], ! Design Day Name
gives
The following example illustrates the use of #eval inside #if commands:
##if #[** city[ ] EQS Chicago **]
##if #[#[** city[ ] EQS Chicago ] and#[** occup[ ] NES low **]** **]**
Notes:
False = 0 or BLANK,
True = any other character
E.g., “abc *def”
Otherwise, the quotes around the literals are optional.
E.g., # [ large /// office ] gives “large office”
Literals are case sensitive. For example, “Chicago”, “CHICAGO” and “chicago” are distinct.
EQS and NES are case sensitive string comparisons. EQSU and NESU are case insensitive string comparisons.
Literals are limited to 40 characters.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.