Built-In Functions[LINK]
Several useful, built-in functions are available for use in
Erl programs. You cannot configure these; they are internal to
the language processor inside EnergyPlus. They provide access
to a subset of general service routines that are useful inside
the main EnergyPlus program or are intrinsic functions
available in the underlying Fortran language. The “@”
character is used to signal to the language processor that the
following character string defines a built-in function that is
used to assign a result to an Erl variable. The characters
appended to the “@” operator must be one of the predefined
names listed in Table, Table,
Table,
or Table.
The syntax of the function call will vary depending on the
arguments required by the function, but the general structure
is:
SET <variable> = @<function name>
<argument1> <argument2> …
<argumentN>
Where “argument” can be either an Erl variable or a numeric
constant.
For example, the following two statements can be used to
set the value of an Erl variable called mySupplyRH to have
percent relative humidity.
SET mySupplyRH = @RhFnTdbWPb mySupplyDryblub
mySupplyHumRat mySupplyPress
SET mySupplyRH = mySupplyRH * 100
Built-in Math Functions[LINK]
Table
lists the built-in functions for common mathematical
functions. The numerical model for these functions is provided
by the underlying Fortran language and the compiler.
Built-in Math Functions for Erl
| Function Name |
Description |
Number of Arguments |
| @Round |
Decreases precision of real
number argument to nearest whole number, remains a real
number. |
1 |
| @Mod |
Returns remainder after dividing
the first argument by the second. |
2 |
| @Sin |
Sine, returns sine of angle
given in radians. |
1 |
| @Cos |
Cosine, returns cosine of angle
given in radians. |
1 |
| @ArcSin |
Arcsine, returns angle in
radians from sine of angle. |
1 |
| @ArcCos |
ArcCosine, returns angle in
radians from cosine of angle. |
1 |
| @DegToRad |
Degrees to radians, returns
radians from degrees. |
1 |
| @RadToDeg |
Radians to degrees, returns
degrees from radians. |
1 |
| @Exp |
Exponential, e , returns
result. |
1 |
| @Ln |
Natural log, log (x), returns
result. |
1 |
| @Max |
Maximum, returns largest value
of two arguments. |
2 |
| @Min |
Minimum, returns smallest value
of two arguments. |
2 |
| @Abs |
Absolute value, returns positive
magnitude of argument. |
1 |
| @RandomUniform |
Pseudo-Random Number Generator,
returns random number with uniform probability distribution
across the range of values passed as the arguments, inclusive.
Argument 1 is the lower limit. Argument 2 is the upper
limit. |
2 |
| @RandomNormal |
Pseudo-Random Number Generator,
returns random number with normal (Gaussian) probability
distribution as a function of the mean, standard deviation,
and limits. Argument 1 is the mean. Argument 2 is the standard
deviation. Argument 3 is the lower limit. Argument 4 is the
upper limit. |
4 |
| @SeedRandom |
Random Seed, controls the seed
used in the random number generator for calls to @RandomUniform and @RandomNormal. Use is
optional and provided for repeatable series of random numbers.
The argument is rounded to the nearest whole number and then
used to set the size and values of the seed for the number
generator. |
1 |
Built-In
Simulation Management Functions[LINK]
Built-in EnergyPlus Simulation Management Functions
for Erl
| Function Name |
Description |
Number of Arguments |
| @FatalHaltEp |
Throws fatal error with time of
occurrence and stops execution of current model. Argument
passes a number that can be used as an error code. |
1 |
| @SevereWarnEp |
Throws severe error with time of
occurrence and continues execution. Argument passes a number
that can be used as an error code. |
1 |
| @WarnEp |
Throws warning error and
continues execution. Argument passes a number that can be used
as an error code. |
1 |
Built-in Trend
Variable Functions[LINK]
For control algorithms, you often need to be able put a
sensor reading into some historical context. The trend
variables are provided in Erl as a way to log the time history
of data to use in control decisions. To use the trend
variables in Erl programs, their values must be extracted and
placed into normal Erl variables. Setting up an Erl variable
as a trend variable requires an EnergyManagementSystem:TrendVariable
input object. The access functions listed in Table
are used to obtain data from a trend variable during the
execution of an Erl program. These functions act on trend
variables and return values into the user’s Erl variables for
subsequent use in calculations. Each trend function takes the
name of the trend variable and an index that identifies how
far back in time the function should be applied. Trend
variable names are also Erl variables but with special
pointers to another data structure with the time series data
storage. The trend logs have a first-in, first-out storage
array where only the most recent data are retained. Each
element in the history corresponds to the result for that
value over a zone timestep. The time difference between trend
log items is the zone timestep in hours, so that the slope
returned by @TrendDirection is in
per-hour units.
Built-in Functions for Trend Variables in Erl
| Function Name |
Description |
Number of Arguments |
| @TrendValue |
Returns history value for a
particular number of timesteps into the past. Dereferences
data stored in trend into another Erl variable. Takes trend
variable name and the specific timestep into the past to
return. |
2 |
| @TrendAverage |
Returns historical average
(mean) for values in trend variable. Takes trend variable name
and number of steps into the past to analyze |
2 |
| @TrendMax |
Returns historical maximum for
values in trend variable. Takes trend variable name and number
of steps into the past to analyze. |
2 |
| @TrendMin |
Returns historical minimum for
values in trend variable within the index. Takes trend
variable name and number of steps into the past to
analyze. |
2 |
| @TrendDirection |
Returns slope of a linear least
squares fit of trend data within the index. Positive if trend
is increasing, negative if decreasing. Takes trend variable
name and number of steps into the past to analyze. |
2 |
| @TrendSum |
Returns sum of elements stored
in trend. Takes trend variable name and number of steps into
the past to analyze. |
2 |
The trend functions all take as their second argument an
array index. This number should be considered an integer for
locating an array position. (It will be rounded down to the
nearest integer using Fortran’s FLOOR intrinsic.) This index
argument tells the trend functions how far back in time they
should reach into the history log when they evaluate the
function call. This enables you to compare long- and
short-range trends.
Built-in
Psychrometric Functions[LINK]
Building
modeling often involves calculations related to moist air. A
comprehensive set of built-in functions is available for
psychrometric calculations. Table
lists the functions available for use in Erl programs that are
related to moist air properties and some physical properties
related to water. More discussion of the psychrometric
functions is provided in the section “Pyschrometric services”
in the Module Developer Guide.
Built-in Psychrometric Functions for Erl
| Function Name |
Arguments |
Description |
Units |
| @RhoAirFnPbTdbW |
Result |
Density of moist air |
kg/m < sup > 3 < /sup
> |
| Input 1 |
Barometric pressure |
Pa |
|
| Input 2 |
Drybulb temperature |
°C |
|
| Input 3 |
Humidity ratio |
kgWater/kgDryAir |
|
| @CpAirFnWTdb |
Result |
Heat capacity of moist air |
J/kg-°C |
| Input 1 |
Humidity ratio |
kgWater/kgDryAir |
|
| Input 2 |
Drybulb temperature |
°C |
|
@HfgAirFnWTdb’ & Result
& Heat of vaporization for vapor & J/kg
Input 1 & Humidity ratio & kgWater/kgDryAir
Input 2 & Drybulb temperature & °C
@HgAirFnWTdb & Result
& Enthalpy of the gas &
Input 1 & Humidity ratio & kgWater/kgDryAir
Input 2 & Drybulb temperature & °C
@TdpFnTdbTwbPb & Result
& Dew-point temperature & °C
Input 1 & Drybulb temperature & °C
Input 2 & Wetbulb temperature & °C
Input 3 & Barometric pressure & Pa
@TdpFnWPb
& Result & Dew-point temperature & °C
Input 1 & Humidity ratio & kgWater/kgDryAir
Input 2 & Barometric pressure & Pa
@HFnTdbW
& Result & Enthalpy of moist air & J/kg
Input 1 & Drybulb temperature & °C
Input 2 & Humidity ratio & kgWater/kgDryAir
@HFnTdbRhPb & Result &
Enthalpy of moist air & J/kg
Input 1 & Drybulb temperature & °C
Input 2 & Relative humidity & Fraction (0.0 ..
1)
Input 3 & Barometric pressure & Pa
@TdbFnHW
& Result & Drybulb temperature & °C
Input 1 & Enthalpy of moist air & J/kg
Input 2 & Humidity ratio & kgWater/kgDryAir
@RhovFnTdbRh & Result
& Vapor density in air & kg/m < sup > 3 <
/sup >
Input 1 & Drybulb temperature & °C
Input 2 & Relative humidity & Fraction (0.0 ..
1)
@RhovFnTdbWPb & Result
& Vapor density in air & kg/m < sup > 3 <
/sup >
Input 1 & Drybulb temperature & °C
Input 2 & Humidity ratio & kgWater/kgDryAir
Input 3 & Barometric pressure & Pa
@RhFnTdbRhov & Result
& Relative humidity & Fraction (0.0 .. 1)
Input 1 & Drybulb temperature & °C
Input 2 & Vapor density in air & kg/m < sup > 3
< /sup >
@RhFnTdbWPb & Result &
Relative humidity & Fraction (0.0 .. 1)
Input 1 & Drybulb temperature & °C
Input 2 & Humidity ratio & kgWater/kgDryAir
Input 3 & Barometric pressure & Pa
@TwbFnTdbWPb & Result
& Wetbulb temperature & °C
Input 1 & Drybulb temperature & °C
Input 2 & Humidity ratio & kgWater/kgDryAir
Input 3 & Barometric pressure & Pa
@VFnTdbWPb & Result &
Specific volume & m < sup > 3 < /sup >
/kg
Input 1 & Drybulb temperature & °C
Input 2 & Humidity ratio & kgWater/kgDryAir
Input 3 & Barometric pressure & Pa
@WFnTdpPb
& Result & Humidity ratio & kgWater/kgDryAir
Input 1 & Dew-point temperature & °C
Input 2 & Barometric pressure & Pa
@WFnTdbH
& Result & Humidity ratio & kgWater/kgDryAir
Input 1 & Drybulb temperature & °C
Input 2 & Enthalpy of moist air & J/kg
@WFnTdbTwbPb & Result
& Humidity ratio & kgWater/kgDryAir
Input 1 & Drybulb temperature & °C
Input 2 & Wetbulb temperature & °C
Input 3 & Barometric pressure & Pa
@WFnTdbRhPb & Result &
Humidity ratio & kgWater/kgDryAir
Input 1 & Drybulb temperature & °C
Input 2 & Relative humidity & Fraction (0.0 ..
1)
Input 3 & Barometric pressure & Pa
@PsatFnTemp & Result &
Saturation pressure & Pa
Input 1 & Drybulb temperature & °C
@TsatFnHPb & Result &
Saturation temperature & °C
Input 1 & Enthalpy of moist air & J/kg
Input 2 & Barometric pressure & Pa
@CpCW &
Result & Heat capacity of water & J/kg
Input 1 & Temperature & °C
@CpHW &
Result & Heat capacity of water & J/kg
Input 1 & Temperature & °C
@RhoH2O
& Result & Density of water & kg/m < sup > 3
< /sup >
Input 1 & Temperature & °C
|
|
|
|
Built-in Curve and
Table Functions[LINK]
EnergyPlus has a number of different generic curve and
table input objects that are used to describe the performance
characteristics for various component models. Table
describes a built-in function called @CurveValue that is available
for reusing those curve and table input objects in your Erl
programs. Although the Erl language could be used to
replicate the functionality, reusing those input objects can
have advantages because the input may have already been
developed for use in traditional component models or the
limiting and interpolation methods are helpful. The @CurveValue
function expects six arguments, although usually only a subset
of them will be used depending on the number of independent
variables involved with the curve or table. Because Erl does
not support passing optional arguments, dummy variables do
need to be included in the function call for all unused
independent variables. For example, the Curve:Biquadratric
object has only x and y independent variables, so input
arguments 4, 5, and 6 will not be used when @CurveValue is
evaluated:
Set MyCurveResult = @CurveValue myCurveIndex X1 Y1
dummy dummy dummy;
Note that although version 8.6 of EnergyPlus introduced
changes to not allow uninitialized variables in expressions,
@CurveValue has an exception to
this for backward compatibility. @CurveValue only issues errors
to the EDD file and does not fatal when called with
uninitialized dummy variables.
The first input argument is always an Erl variable that has
been declared using an EnergyManagementSystem:CurveOrTableIndexVariable
input object. This variable identifies the location of a
specific curve or table in the program’s internal data
structures. It is important that you do not inadvertently
reassign the value held in this variable because it is only
filled once at the beginning of the simulation.
Built-in Function for Accessing Curves and
Tables
| Function Name |
Arguments |
Description |
Notes |
| @CurveValue |
Result |
Result from evaluating the curve
or table as a function of the input arguments |
|
| Input 1 |
Index variable that “points” to
a specific curve or table object defined elsewhere in the
IDF. |
This variable needs to be
declared and filled using an
EnergyManagementSystem:CurveOrTableIndexVariable object. |
|
| Input 2 |
First independent variable |
Typically the “X” input value,
always used |
|
| Input 3 |
Second independent variable |
Typically the “Y” value, only
used if curve/table has two or more independent variables |
|
| Input 4 |
Third independent variable |
Typically the “Z” value, only
used if curve/table has three or more independent
variables. |
|
| Input 5 |
Fourth independent variable |
Only used if table has four or
more independent variables |
|
| Input 6 |
Fifth independent variable |
Only used if table has five
independent variables |
|
Built-In Functions[LINK]
Several useful, built-in functions are available for use in Erl programs. You cannot configure these; they are internal to the language processor inside EnergyPlus. They provide access to a subset of general service routines that are useful inside the main EnergyPlus program or are intrinsic functions available in the underlying Fortran language. The “@” character is used to signal to the language processor that the following character string defines a built-in function that is used to assign a result to an Erl variable. The characters appended to the “@” operator must be one of the predefined names listed in Table, Table, Table, or Table. The syntax of the function call will vary depending on the arguments required by the function, but the general structure is:
SET <variable> = @<function name> <argument1> <argument2> … <argumentN>
Where “argument” can be either an Erl variable or a numeric constant.
For example, the following two statements can be used to set the value of an Erl variable called mySupplyRH to have percent relative humidity.
SET mySupplyRH = @RhFnTdbWPb mySupplyDryblub mySupplyHumRat mySupplyPress
SET mySupplyRH = mySupplyRH * 100
Built-in Math Functions[LINK]
Table lists the built-in functions for common mathematical functions. The numerical model for these functions is provided by the underlying Fortran language and the compiler.
Built-In Simulation Management Functions[LINK]
Built-in Trend Variable Functions[LINK]
For control algorithms, you often need to be able put a sensor reading into some historical context. The trend variables are provided in Erl as a way to log the time history of data to use in control decisions. To use the trend variables in Erl programs, their values must be extracted and placed into normal Erl variables. Setting up an Erl variable as a trend variable requires an EnergyManagementSystem:TrendVariable input object. The access functions listed in Table are used to obtain data from a trend variable during the execution of an Erl program. These functions act on trend variables and return values into the user’s Erl variables for subsequent use in calculations. Each trend function takes the name of the trend variable and an index that identifies how far back in time the function should be applied. Trend variable names are also Erl variables but with special pointers to another data structure with the time series data storage. The trend logs have a first-in, first-out storage array where only the most recent data are retained. Each element in the history corresponds to the result for that value over a zone timestep. The time difference between trend log items is the zone timestep in hours, so that the slope returned by @TrendDirection is in per-hour units.
The trend functions all take as their second argument an array index. This number should be considered an integer for locating an array position. (It will be rounded down to the nearest integer using Fortran’s FLOOR intrinsic.) This index argument tells the trend functions how far back in time they should reach into the history log when they evaluate the function call. This enables you to compare long- and short-range trends.
Built-in Psychrometric Functions[LINK]
Building modeling often involves calculations related to moist air. A comprehensive set of built-in functions is available for psychrometric calculations. Table lists the functions available for use in Erl programs that are related to moist air properties and some physical properties related to water. More discussion of the psychrometric functions is provided in the section “Pyschrometric services” in the Module Developer Guide.
Input 1 & Humidity ratio & kgWater/kgDryAir
Input 2 & Drybulb temperature & °C
@HgAirFnWTdb & Result & Enthalpy of the gas &
Input 1 & Humidity ratio & kgWater/kgDryAir
Input 2 & Drybulb temperature & °C
@TdpFnTdbTwbPb & Result & Dew-point temperature & °C
Input 1 & Drybulb temperature & °C
Input 2 & Wetbulb temperature & °C
Input 3 & Barometric pressure & Pa
@TdpFnWPb & Result & Dew-point temperature & °C
Input 1 & Humidity ratio & kgWater/kgDryAir
Input 2 & Barometric pressure & Pa
@HFnTdbW & Result & Enthalpy of moist air & J/kg
Input 1 & Drybulb temperature & °C
Input 2 & Humidity ratio & kgWater/kgDryAir
@HFnTdbRhPb & Result & Enthalpy of moist air & J/kg
Input 1 & Drybulb temperature & °C
Input 2 & Relative humidity & Fraction (0.0 .. 1)
Input 3 & Barometric pressure & Pa
@TdbFnHW & Result & Drybulb temperature & °C
Input 1 & Enthalpy of moist air & J/kg
Input 2 & Humidity ratio & kgWater/kgDryAir
@RhovFnTdbRh & Result & Vapor density in air & kg/m < sup > 3 < /sup >
Input 1 & Drybulb temperature & °C
Input 2 & Relative humidity & Fraction (0.0 .. 1)
@RhovFnTdbWPb & Result & Vapor density in air & kg/m < sup > 3 < /sup >
Input 1 & Drybulb temperature & °C
Input 2 & Humidity ratio & kgWater/kgDryAir
Input 3 & Barometric pressure & Pa
@RhFnTdbRhov & Result & Relative humidity & Fraction (0.0 .. 1)
Input 1 & Drybulb temperature & °C
Input 2 & Vapor density in air & kg/m < sup > 3 < /sup >
@RhFnTdbWPb & Result & Relative humidity & Fraction (0.0 .. 1)
Input 1 & Drybulb temperature & °C
Input 2 & Humidity ratio & kgWater/kgDryAir
Input 3 & Barometric pressure & Pa
@TwbFnTdbWPb & Result & Wetbulb temperature & °C
Input 1 & Drybulb temperature & °C
Input 2 & Humidity ratio & kgWater/kgDryAir
Input 3 & Barometric pressure & Pa
@VFnTdbWPb & Result & Specific volume & m < sup > 3 < /sup > /kg
Input 1 & Drybulb temperature & °C
Input 2 & Humidity ratio & kgWater/kgDryAir
Input 3 & Barometric pressure & Pa
@WFnTdpPb & Result & Humidity ratio & kgWater/kgDryAir
Input 1 & Dew-point temperature & °C
Input 2 & Barometric pressure & Pa
@WFnTdbH & Result & Humidity ratio & kgWater/kgDryAir
Input 1 & Drybulb temperature & °C
Input 2 & Enthalpy of moist air & J/kg
@WFnTdbTwbPb & Result & Humidity ratio & kgWater/kgDryAir
Input 1 & Drybulb temperature & °C
Input 2 & Wetbulb temperature & °C
Input 3 & Barometric pressure & Pa
@WFnTdbRhPb & Result & Humidity ratio & kgWater/kgDryAir
Input 1 & Drybulb temperature & °C
Input 2 & Relative humidity & Fraction (0.0 .. 1)
Input 3 & Barometric pressure & Pa
@PsatFnTemp & Result & Saturation pressure & Pa
Input 1 & Drybulb temperature & °C
@TsatFnHPb & Result & Saturation temperature & °C
Input 1 & Enthalpy of moist air & J/kg
Input 2 & Barometric pressure & Pa
@CpCW & Result & Heat capacity of water & J/kg
Input 1 & Temperature & °C
@CpHW & Result & Heat capacity of water & J/kg
Input 1 & Temperature & °C
@RhoH2O & Result & Density of water & kg/m < sup > 3 < /sup >
Input 1 & Temperature & °C
Built-in Curve and Table Functions[LINK]
EnergyPlus has a number of different generic curve and table input objects that are used to describe the performance characteristics for various component models. Table describes a built-in function called @CurveValue that is available for reusing those curve and table input objects in your Erl programs. Although the Erl language could be used to replicate the functionality, reusing those input objects can have advantages because the input may have already been developed for use in traditional component models or the limiting and interpolation methods are helpful. The @CurveValue function expects six arguments, although usually only a subset of them will be used depending on the number of independent variables involved with the curve or table. Because Erl does not support passing optional arguments, dummy variables do need to be included in the function call for all unused independent variables. For example, the Curve:Biquadratric object has only x and y independent variables, so input arguments 4, 5, and 6 will not be used when @CurveValue is evaluated:
Set MyCurveResult = @CurveValue myCurveIndex X1 Y1 dummy dummy dummy;
Note that although version 8.6 of EnergyPlus introduced changes to not allow uninitialized variables in expressions, @CurveValue has an exception to this for backward compatibility. @CurveValue only issues errors to the EDD file and does not fatal when called with uninitialized dummy variables.
The first input argument is always an Erl variable that has been declared using an EnergyManagementSystem:CurveOrTableIndexVariable input object. This variable identifies the location of a specific curve or table in the program’s internal data structures. It is important that you do not inadvertently reassign the value held in this variable because it is only filled once at the beginning of the simulation.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.