ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air
Quality, contains provisions that allow building ventilation
systems to vary the amount of outdoor ventilation air
delivered to occupied zones based on feedback from sensors
that monitor various indoor air contaminants (ASHRAE 2007).
Although not a contaminant of concern in most buildings,
carbon dioxide (CO\(_{2}\))
levels can be monitored as an indicator of building occupancy
and the associated human bioeffluent concentration. Demand
controlled ventilation (DCV) is being increasingly used to
modulate outdoor ventilation air based on real-time occupancy
(Emmerich and Persily 1997, Schell et al. 1998, Schell and
Int-Hout 2001). Modulating the outdoor ventilation air while
maintaining proper indoor air quality has the potential for
large energy savings compared to constant rate ventilation
systems that are typically designed to provide outdoor
ventilation air based on maximum anticipated occupancy.
EnergyPlus can model DCV by the ventilation rate procedure
(VRP) defined in ASHRAE Standard 62.1-2007/2010 for single and
multiple path systems, and the indoor air quality procedure
(IAQP) defined in Standard 62. The VRP first calculates the
breathing-zone outdoor air flow rate based on two components –
the zone occupant component and the zone floor area component,
then it calculates the zone supply outdoor air flow rate
considering the zone air distribution effectiveness and
secondary recirculation (for mult-path systems only), and
finally calculates the system outdoor air flow rate
considering the zone diversity and system ventilation
efficiency. The user must include the following five objects
in their input data file in order to model DCV (using VRP or
IAQP):
DesignSpecification:ZoneAirDistribution
to describe air distribution effectiveness and secondary
recirculation (for multi-path ventilation systems) for each
zone
The outdoor air system (AirLoopHVAC:OutdoorAirSystem) is a
subsystem of an AirLoopHVAC
which handles the mixed air portion of the primary air system:
the system relief air, the outside air inlet, and any
components and controllers associated with the system relief
air and outside air streams. The inputs for this object are
fully described in the EnergyPlus Input Output Reference.
Determining the outdoor air ventilation rate and introducing
this ventilation via the mixed air box are accomplished by the
mechanical ventilation and outdoor air controller objects.
The VRP currently requires outdoor air ventilation rates to
be determined based on the floor area of each occupied zone
plus the number of people in each zone. The number of people
varies based on the setting of the DCV flag in the Controller:MechanicalVentilation
object. For using occupancy at every time step, the DCV flag
must be set to ‘Yes’. The outdoor air ventilation rate can
then be reset dynamically as operating conditions change
(e.g., variations in occupancy). The Controller:MechanicalVentilation
object simplifies the procedure for calculating these outdoor
air ventilation requirements and resetting them based on
varying occupancy levels. This is particularly useful for
large air distribution systems that serve a number of
different zone types with varying occupancy levels.
The IAQP (ASHRAE 2007) is a design procedure in which
outdoor air intake and other system design parameters are
based on an analysis of contaminant sources, and contaminant
concentration targets. Although carbon dioxide is not
considered as an indoor contaminant but is considered as an
indicator of indoor air quality in buildings, EnergyPlus uses
IAQP to control carbon dioxide. In addition, a generic
contaminant may be introduced. The current IAQP in EnergyPlus
allows credit to be taken for controls that can be reliably
demonstrated to result in indoor carbon dioxide and generic
contaminant concentrations equal to or lower that those
achieved using the VRP. The IAQP may also be used where the
design is intended to attain specific target carbon dioxide
and generic contaminant levels.
\({V_{bz,i}}\) = the
breathing-zone outdoor air flow, m³/s
\({R_{p,i}}\) = the
ventilation rate per person, m³/s-person
\({P_i}\) = the number
of occupants for the zone
\({R_{a,i}}\) = the
ventilation rate per floor area, m³/s-m²
\({A_i}\) = the floor
area of the zone, m²
\({SchedFrac_i}\) = the
Outdoor Air Schedule value for the zone, if specified in the
corresponding DesignSpecification:OutdoorAir
object (defaults to 1.0)
\(i\) = the index of
the zone or zone list
Next, the i-th zone outdoor air flow is calculated:
\[{V_{oz,i}} =
{V_{bz,i}}/{E_i}\]
Where:
\({V_{oz,i}}\) = the zone
outdoor air flow, m³/s
\({E_i}\) = the zone air
distribution effectiveness, see following figure for ASHRAE
recommended values.
Zone Air Distribution
Effectiveness Typical Values (Source: ASHRAE Standard
62.1-2010)
Calculation
of system minimum outdoor air flow[LINK]
For single zone systems, the system outdoor air flow,
\[{V_{ot}} =
{V_{oz}}\]
For 100% outdoor air multi-zone systems, the system outdoor
air flow,
\({X_s}\) = the
uncorrected system outdoor air fraction
\[{X_s} =
{V_{ou}}/{V_{ps}}\]
\({V_{ps}}\) = the system
supply air flow, m³/s
\({Z_{d,i}}\) = the zone
outdoor air fraction
\[{Z_{d,i}} =
{V_{oz,i}}/{V_{dz,i}}\]
\({V_{dz,i}}\) = the
zone supply air flow, m³/s
\({E_v}\) = the system
ventilation efficiency, determined as the minimum of the zone
ventilation efficiency among all ventilation zones served by
the air handler.
Ev = minimum (Evz)
Evz = the zone ventilation efficiency, determined
differently for single-path and multi-path systems.
For single-path systems,
Evz = 1+ Xs– Z\(_{d,i}\)
For multi-path systems,
Evz =(Fa+ Xs·Fb– Z\(_{d,i}\)·Ep·Fc)/Fa
where system air fractions Fa, Fb, and
Fcare determined as follows
Fa = Ep+(1 – Ep) ·Er
Fb = Ep
Fc = 1 –(1 – Ez) · (1 – Er) · (1 –
Ep)
Ep = the zone primary air fraction. For dual-fan
dual-duct systems, the zone primary air is the air from the
cold duct.
Ep = Vpz/Vdz,i
Er = the zone secondary recirculation
fraction
Single-path systems are special cases of multi-path systems
where Er = 0, Ep = 1, Fa = Fb
=Fc = 1.0
The zone secondary recirculation fraction Er is determined
by the designer based on system configuration. For plenum
return systems with secondary recirculation (e.g., fan-powered
VAV with plenum return) Er is usually less than 1.0, although
values may range from 0.1 to 1.2 depending upon the location
of the ventilation zone relative to other zones and the air
handler. For ducted return systems with secondary
recirculation (e.g., fan-powered VAV with ducted return), Er
is typically 0.0, while for those with system-level
recirculation (e.g, dual-fan dual-duct systems with ducted
return) Er is typically 1.0. For other system types, Er is
typically 0.75.
The program then calculates the minimum outdoor air flow
fraction based on the information provided in the object Controller:MechanicalVentilation
and the maximum branch air flow rate as follows:
MechVentOutsideAirMinFrac = outdoor air minimum fraction
based on all zones specified in the Controller:MechanicalVentilation
object
Controller:OutdoorAir
controls the amount of outdoor ventilation air introduced via
the mixed air box based on several user inputs. The user can
define the minimum outdoor air flow rate as a percentage of
the system’s supply air flow rate (e.g., for a variable-air
volume system) or a fixed minimum outdoor air flow rate (not
as a percentage but a fixed value) (field MinimumLimit). DCV,
using the Controller:MechanicalVentilation
object in conjunction with the Controller:OutdoorAir
object, allows a third option for setting the minimum outdoor
air flow. Economizer operation can also be specified to
increase the outdoor air flow above the minimum flow rate to
provide free cooling when conditions permit
(Controller:OutdoorAir, field Economizer Control Type).
EnergyPlus uses the largest outdoor air flow rate
calculated by the various methods described above when
modeling system performance (as long this rate doesn’t exceed
the maximum flow rate specified for the main air loop branch
or for the outdoor air controller itself).
The method used to calculate the outdoor ventilation air
flow rate for each system simulation time step is described in
more detail below. The figure below schematically illustrates
air flow paths used in the calculation of outdoor air flow
rate.
Demand Control Ventilation –
Air Flow Paths
The minimum outdoor air flow rate is first calculated based
on the minimum outdoor air flow rate and the minimum outdoor
air schedule value as defined by the user inputs for the
object Controller:OutdoorAir:
\({\mathop m\limits^
\bullet_{_{\min OA}}}\) = minimum outdoor air
flow rate for this time step, kg/s
\({\mathop V\limits^
\bullet_{_{\min OA}}}\) = minimum outdoor air
flow rate defined in Controller:OutdoorAir,
m\(^{3}\)/s
MinOAScheduleValue = minimum outdoor air schedule
value defined by the schedule identified in Controller:OutdoorAir
RhoStd = standard air density (1.204
kg/m\(^{3}\)) adjusted for
the local barometric pressure (standard barometric pressure
corrected for altitude, ASHRAE 1997 HOF pg. 6.1).
The outdoor air minimum fraction is then calculated as the
ratio of the minimum outdoor air flow rate calculated above to
the maximum air flow rate defined in the Branch
statement for the main air loop (converted to mass flow
rate).
\({\mathop m\limits^
\bullet_{\max branch}}\) = Max branch air volume
flow rate times RhoStd, kg/s
The program then calculates the minimum outdoor air flow
fraction (MechVentOutsideAirMinFrac) according to the
VRP based on the information provided in the object Controller:MechanicalVentilation
and the maximum branch air flow rate.
The algorithm then uses the larger of these outdoor air
minimum fractions in subsequent calculations, and also makes
sure that the resulting fraction is between 0 and 1.
The algorithm goes on to determine if economizer operation
is possible based on the user inputs and the current
conditions of the outdoor air and return air. If conditions
permit economizer operation, the outdoor air flow fraction is
increased beyond the minimum fraction to meet the mixed air
setpoint temperature (setpoint temperature assigned to the
node defined in field “Control_Node” of
Controller:OutdoorAir).
If a fixed minimum outdoor air flow rate is specified
(field Minimum Limit Type in Controller:OutdoorAir) for a
continuous air flow system, the program makes sure that the
outdoor air mass flow rate is greater than or equal to the
minimum outdoor air flow rate specified by the user.
The outdoor air mass flow rate should also be less than or
equal to the maximum outdoor air flow rate specified by the
user, and the outdoor air flow rate is reset if necessary.
\({\dot m_{OA,z,i}}\) =
outdoor air mass flow rate for the ith zone as calculated
according to section Carbon Dioxide Prediction located
elsewhere in this document.
\({SchedFrac_i}\) = the
Outdoor Air Schedule value for the zone, if specified in the
corresponding DesignSpecification:OutdoorAir
object (defaults to 1.0)
The control has two choices:
ProportionalControlBasedonOccupancySchedule and
ProportionalControlBasedonDesignOccupancy. The difference is
occupancy level. The former uses real time occupancy, while
the latter uses design occupancy level. Like Ventilation Rate
Procedure and the Indoor Air Quality Procedure, the following
three objects must be included in the input data file in order
to model CO\(_{2}\)-based DCV
with Proportional Control:
4) The target indoor CO\(_{2}\) concentration at \({V_{ot - min}}\) is either a
user input in the object ZoneControl:ContaminantController
or equal to the outdoor CO\(_{2}\) concentration. The default
is outdoor CO\(_{2}\)
concentration.
\[{C_{s - min,i}} =
{C_o}\]
When the indoor CO\(_{2}\)
concentration equals \({C_{s -
design,i}}\) , \({V_{ot}}\) should equal \({V_{ot - design,i}}\) . When the
indoor CO\(_{2}\)
concentration equals \({C_{s -
min,i}}\) , \({V_{ot}}\) should equal \({V_{ot - min,i}}\) . When the
indoor CO\(_{2}\)
concentration is between \({C_{s -
min,i}}\) and \({C_{s -
design,i}}\) , a controller should adjust outdoor air
intake flow \({V_{ot}}\)
proportionally between \({V_{ot -
min,i}}\) and \({V_{ot -
design,i}}\) :
\({R_{p,i}}\) = Required
outdoor air flow rate per person, (m\(^{3}\)/s)/person
\({R_{a,i}}\) = Required
outdoor air flow rate per unit area, (m\(^{3}\)/s)/m\(^{2}\)
\({P_{z,i}}\) = Design
zone population, number of people
\({SchedFrac_i}\) = the
Outdoor Air Schedule value for the zone, if specified in the
corresponding DesignSpecification:OutdoorAir
object (defaults to 1.0)
When ProportionalControlBasedonDesignOccupancy is
specified, number of people = design occupancy * current
schedule value. When ProportionalControlBasedonDesignOccupancy
is specified, number of people = design occupancy.
\({E_i}\) = The zone air
distribution effectiveness
\(N\) = CO\(_{2}\) generation rate, (m\(^{3}\)/s)/person (Specified in
the People
object)
\({C_o}\) = CO\(_{2}\) concentration in the
outdoor air, ppm
\({C_{s - design,i}}\) =
CO\(_{2}\) concentration in
the space for the design conditions, ppm
\({C_{s - min,i}}\) =
Minimum CO\(_{2}\)
concentration in the space, ppm
\({C_{s - actual,i}}\) =
Actual CO\(_{2}\)
concentration in the space, ppm
\({V_{ot - design,i}}\)
= Required intake of outdoor air flow rate at \({C_{s - design}}\) , (m\(^{3}\)/s)
\({V_{ot - min,i}}\) =
Required intake of outdoor air flow rate at \({C_{s - min}}\) , (m\(^{3}\)/s)
\({V_{ot,i}}\) =
Required intake of outdoor air flow rate at \({C_{s - actual}}\) , (m\(^{3}\)/s)
Except \({C_{s - min,i}}\)
above, all other variables are already available in
EnergyPlus (See Eng. Reference for “Ventilation Rate
Procedure” above for further details). \({C_{s - min}}\) can be specified
in the ZoneControl:ContaminantController
object as a schedule. If \({C_{s -
min}}\) is not specified in the ZoneControl:ContaminantController
object, then outdoor air CO2 concentration will be used as the
minimum. In order for “ProportionalControl” to be active, the
following conditions must be met, otherwise default
“VentilationProcedure” will be modeled and a warning will be
issued during runtime:
1) “Carbon Dioxide Control Availability Schedule Name”
input field in the ZoneControl:ContaminantController
object must be greater than zero.
2) CO2 gain from people in the zone must be greater than
zero.
3) “Outdoor air flow per person” and “Outdoor air flow
per zone floor area” in the corresponding
“DesignSpecification:OutdoorAir” object must be greater than
zero.
ASHRAE. 2007. ANSI/ASHRAE Standard 62.1-2007,
Ventilation for acceptable indoor air quality. Atlanta:
American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc.
ASHRAE. 2010. ANSI/ASHRAE Standard 62.1-2010,
Ventilation for acceptable indoor air quality. Atlanta:
American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc.
Emmerich, S.J. and A.K. Persily. 1997. Literature review on
CO\(_{2}\)-based
demand-controlled ventilation. ASHRAE Transactions
103(2):229-243.
Schell, M.B., S.C. Turner, R.O. Shim. 1998. Application of
CO\(_{2}\)-based demand
controlled ventilation using ASHRAE Standard 62-1989.
ASHRAE Transactions 104(2):1213-1225.
Schell, M. and D. Int-Hout. 2001. Demand control
ventilation using CO\(_{2}\).
ASHRAE Journal, February.
Demand Controlled Ventilation[LINK]
ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air Quality, contains provisions that allow building ventilation systems to vary the amount of outdoor ventilation air delivered to occupied zones based on feedback from sensors that monitor various indoor air contaminants (ASHRAE 2007). Although not a contaminant of concern in most buildings, carbon dioxide (CO\(_{2}\)) levels can be monitored as an indicator of building occupancy and the associated human bioeffluent concentration. Demand controlled ventilation (DCV) is being increasingly used to modulate outdoor ventilation air based on real-time occupancy (Emmerich and Persily 1997, Schell et al. 1998, Schell and Int-Hout 2001). Modulating the outdoor ventilation air while maintaining proper indoor air quality has the potential for large energy savings compared to constant rate ventilation systems that are typically designed to provide outdoor ventilation air based on maximum anticipated occupancy.
EnergyPlus can model DCV by the ventilation rate procedure (VRP) defined in ASHRAE Standard 62.1-2007/2010 for single and multiple path systems, and the indoor air quality procedure (IAQP) defined in Standard 62. The VRP first calculates the breathing-zone outdoor air flow rate based on two components – the zone occupant component and the zone floor area component, then it calculates the zone supply outdoor air flow rate considering the zone air distribution effectiveness and secondary recirculation (for mult-path systems only), and finally calculates the system outdoor air flow rate considering the zone diversity and system ventilation efficiency. The user must include the following five objects in their input data file in order to model DCV (using VRP or IAQP):
AirLoopHVAC:OutdoorAirSystem to simulate the mixed air box of the air loop
Controller:MechanicalVentilation with the DCV flag set to ‘Yes’ to determine the minimum outdoor air flow rate to be provided by the mixed air box
Controller:OutdoorAir to control the outside air flow rate introduced via the mixed air box
DesignSpecification:OutdoorAir to describe the outdoor air requirements for each zone
DesignSpecification:ZoneAirDistribution to describe air distribution effectiveness and secondary recirculation (for multi-path ventilation systems) for each zone
The outdoor air system (AirLoopHVAC:OutdoorAirSystem) is a subsystem of an AirLoopHVAC which handles the mixed air portion of the primary air system: the system relief air, the outside air inlet, and any components and controllers associated with the system relief air and outside air streams. The inputs for this object are fully described in the EnergyPlus Input Output Reference. Determining the outdoor air ventilation rate and introducing this ventilation via the mixed air box are accomplished by the mechanical ventilation and outdoor air controller objects.
The VRP currently requires outdoor air ventilation rates to be determined based on the floor area of each occupied zone plus the number of people in each zone. The number of people varies based on the setting of the DCV flag in the Controller:MechanicalVentilation object. For using occupancy at every time step, the DCV flag must be set to ‘Yes’. The outdoor air ventilation rate can then be reset dynamically as operating conditions change (e.g., variations in occupancy). The Controller:MechanicalVentilation object simplifies the procedure for calculating these outdoor air ventilation requirements and resetting them based on varying occupancy levels. This is particularly useful for large air distribution systems that serve a number of different zone types with varying occupancy levels.
The IAQP (ASHRAE 2007) is a design procedure in which outdoor air intake and other system design parameters are based on an analysis of contaminant sources, and contaminant concentration targets. Although carbon dioxide is not considered as an indoor contaminant but is considered as an indicator of indoor air quality in buildings, EnergyPlus uses IAQP to control carbon dioxide. In addition, a generic contaminant may be introduced. The current IAQP in EnergyPlus allows credit to be taken for controls that can be reliably demonstrated to result in indoor carbon dioxide and generic contaminant concentrations equal to or lower that those achieved using the VRP. The IAQP may also be used where the design is intended to attain specific target carbon dioxide and generic contaminant levels.
Ventilation Rate Procedure[LINK]
Calculation of zone minimum outdoor air flow[LINK]
For the i-th zone, first the breathing-zone outdoor air flow is calculated:
\[{V_{bz,i}} = {R_{p,i}} \times {P_i} + {R_{a,i}} \times {A_i} \times {SchedFrac_i}\]
Where:
\({V_{bz,i}}\) = the breathing-zone outdoor air flow, m³/s
\({R_{p,i}}\) = the ventilation rate per person, m³/s-person
\({P_i}\) = the number of occupants for the zone
\({R_{a,i}}\) = the ventilation rate per floor area, m³/s-m²
\({A_i}\) = the floor area of the zone, m²
\({SchedFrac_i}\) = the Outdoor Air Schedule value for the zone, if specified in the corresponding DesignSpecification:OutdoorAir object (defaults to 1.0)
\(i\) = the index of the zone or zone list
Next, the i-th zone outdoor air flow is calculated:
\[{V_{oz,i}} = {V_{bz,i}}/{E_i}\]
Where:
\({V_{oz,i}}\) = the zone outdoor air flow, m³/s
\({E_i}\) = the zone air distribution effectiveness, see following figure for ASHRAE recommended values.
Calculation of system minimum outdoor air flow[LINK]
For single zone systems, the system outdoor air flow,
\[{V_{ot}} = {V_{oz}}\]
For 100% outdoor air multi-zone systems, the system outdoor air flow,
\[{V_{ot}} = \mathop \sum \limits_{i = 1}^{allzones} {V_{oz,i}}\]
For non 100% outdoor air multi-zone systems, the system outdoor air flow,
\[{V_{ot}} = {V_{ou}}/{E_v}\]
Where:
\({V_{ou}}\) the uncorrected system outdoor air flow, m³/s
\[{V_{ou}} = \mathop \sum \limits_{i = 1}^{allzones} ({R_{p,i}} \times {P_i} \times {SchedFrac_i}) + \mathop \sum \limits_{i = 1}^{allzones} ({R_{a,i}} \times {A_i} \times {SchedFrac_i})\]
\({X_s}\) = the uncorrected system outdoor air fraction
\[{X_s} = {V_{ou}}/{V_{ps}}\]
\({V_{ps}}\) = the system supply air flow, m³/s
\({Z_{d,i}}\) = the zone outdoor air fraction
\[{Z_{d,i}} = {V_{oz,i}}/{V_{dz,i}}\]
\({V_{dz,i}}\) = the zone supply air flow, m³/s
\({E_v}\) = the system ventilation efficiency, determined as the minimum of the zone ventilation efficiency among all ventilation zones served by the air handler.
Ev = minimum (Evz)
Evz = the zone ventilation efficiency, determined differently for single-path and multi-path systems.
For single-path systems,
Evz = 1+ Xs– Z\(_{d,i}\)
For multi-path systems,
Evz = (Fa+ Xs·Fb– Z\(_{d,i}\)·Ep·Fc)/Fa
where system air fractions Fa, Fb, and Fcare determined as follows
Fa = Ep+ (1 – Ep) ·Er
Fb = Ep
Fc = 1 – (1 – Ez) · (1 – Er) · (1 – Ep)
Ep = the zone primary air fraction. For dual-fan dual-duct systems, the zone primary air is the air from the cold duct.
Ep = Vpz/Vdz,i
Er = the zone secondary recirculation fraction
Single-path systems are special cases of multi-path systems where Er = 0, Ep = 1, Fa = Fb = Fc = 1.0
The zone secondary recirculation fraction Er is determined by the designer based on system configuration. For plenum return systems with secondary recirculation (e.g., fan-powered VAV with plenum return) Er is usually less than 1.0, although values may range from 0.1 to 1.2 depending upon the location of the ventilation zone relative to other zones and the air handler. For ducted return systems with secondary recirculation (e.g., fan-powered VAV with ducted return), Er is typically 0.0, while for those with system-level recirculation (e.g, dual-fan dual-duct systems with ducted return) Er is typically 1.0. For other system types, Er is typically 0.75.
The program then calculates the minimum outdoor air flow fraction based on the information provided in the object Controller:MechanicalVentilation and the maximum branch air flow rate as follows:
MechVentOutsideAirMinFrac = \({V_{ot}}\) RhoStd / \(\dot m{_{maxbranch}}\) here:
MechVentOutsideAirMinFrac = outdoor air minimum fraction based on all zones specified in the Controller:MechanicalVentilation object
Controller:OutdoorAir controls the amount of outdoor ventilation air introduced via the mixed air box based on several user inputs. The user can define the minimum outdoor air flow rate as a percentage of the system’s supply air flow rate (e.g., for a variable-air volume system) or a fixed minimum outdoor air flow rate (not as a percentage but a fixed value) (field MinimumLimit). DCV, using the Controller:MechanicalVentilation object in conjunction with the Controller:OutdoorAir object, allows a third option for setting the minimum outdoor air flow. Economizer operation can also be specified to increase the outdoor air flow above the minimum flow rate to provide free cooling when conditions permit (Controller:OutdoorAir, field Economizer Control Type).
EnergyPlus uses the largest outdoor air flow rate calculated by the various methods described above when modeling system performance (as long this rate doesn’t exceed the maximum flow rate specified for the main air loop branch or for the outdoor air controller itself).
The method used to calculate the outdoor ventilation air flow rate for each system simulation time step is described in more detail below. The figure below schematically illustrates air flow paths used in the calculation of outdoor air flow rate.
The minimum outdoor air flow rate is first calculated based on the minimum outdoor air flow rate and the minimum outdoor air schedule value as defined by the user inputs for the object Controller:OutdoorAir:
\[\dot{m}_{minOA} = \dot{V}_{minOA} \cdot MinOAScheduleValue \cdot RhoStd\]
where:
\({\mathop m\limits^ \bullet_{_{\min OA}}}\) = minimum outdoor air flow rate for this time step, kg/s
\({\mathop V\limits^ \bullet_{_{\min OA}}}\) = minimum outdoor air flow rate defined in Controller:OutdoorAir, m\(^{3}\)/s
MinOAScheduleValue = minimum outdoor air schedule value defined by the schedule identified in Controller:OutdoorAir
RhoStd = standard air density (1.204 kg/m\(^{3}\)) adjusted for the local barometric pressure (standard barometric pressure corrected for altitude, ASHRAE 1997 HOF pg. 6.1).
The outdoor air minimum fraction is then calculated as the ratio of the minimum outdoor air flow rate calculated above to the maximum air flow rate defined in the Branch statement for the main air loop (converted to mass flow rate).
\[OutAirMinFrac = \frac{\dot{m}_{minOA}}{\dot{m}_{max,branch}}\]
where:
\({\mathop m\limits^ \bullet_{\max branch}}\) = Max branch air volume flow rate times RhoStd, kg/s
The program then calculates the minimum outdoor air flow fraction (MechVentOutsideAirMinFrac) according to the VRP based on the information provided in the object Controller:MechanicalVentilation and the maximum branch air flow rate.
The algorithm then uses the larger of these outdoor air minimum fractions in subsequent calculations, and also makes sure that the resulting fraction is between 0 and 1.
\[OutAirMinFrac = \,\,MAX\left( {OutAirMinFrac,MechVentOutsideAirMinFrac} \right)\]
\[OutAirMinFrac = \,\,MIN\left( {MAX\left( {OutAirMinFrac,0.0} \right),\,1.0} \right)\]
The algorithm goes on to determine if economizer operation is possible based on the user inputs and the current conditions of the outdoor air and return air. If conditions permit economizer operation, the outdoor air flow fraction is increased beyond the minimum fraction to meet the mixed air setpoint temperature (setpoint temperature assigned to the node defined in field “Control_Node” of Controller:OutdoorAir).
\[OAFrac = \,MAX\,(OutAirMinFrac,\,EconomizerOAFrac)\]
The mass flow rate of outdoor air is then calculated based on the outdoor air fraction determined above and the mixed (supply) air mass flow rate:
\[{\dot m_{OA}} = OAFrac * {\dot m_{MixedAir}}\]
where:
\({\dot m_{OA}}\) = mass flow rate of outdoor air, kg/s
\(OAFrac\) = fraction of outdoor air in the mixed (supply) air stream
\({\mathop m\limits^ \bullet_{MixedAir}}\) = mass flow rate of the mixture of return air and outdoor ventilation air, kg/s
The algorithm checks to make sure the calculated outdoor air mass flow rate is greater than or equal to the air flow rate being exhausted.
\[{\dot m_{OA}} = MAX\left( {{{\dot m}_{OA}},{{\dot m}_{ExhaustAir}}} \right)\]
If a fixed minimum outdoor air flow rate is specified (field Minimum Limit Type in Controller:OutdoorAir) for a continuous air flow system, the program makes sure that the outdoor air mass flow rate is greater than or equal to the minimum outdoor air flow rate specified by the user.
\[{\dot m_{OA}} = MAX\left( {{{\dot m}_{OA}},{{\dot m}_{\min OA}}} \right)\]
The outdoor air mass flow rate should be less than or equal to the mixed (supply) air flow rate, and the outdoor air flow rate is reset if necessary.
\[{\dot m_{OA}} = MIN\left( {{{\dot m}_{OA}},{{\dot m}_{MixedAir}}} \right)\]
The outdoor air mass flow rate should also be less than or equal to the maximum outdoor air flow rate specified by the user, and the outdoor air flow rate is reset if necessary.
\[{\dot m_{OA}} = MIN\left( {{{\dot m}_{OA}},{{\dot m}_{MaxOA}}} \right)\]
where:
\({\dot m_{MaxOA}}\) = maximum outdoor air mass flow rate, kg/s = maximum outdoor air volume flow rate from Controller:OutdoorAir times RhoStd
Finally, the relief air flow rate is calculated as the difference between the outside and exhaust air mass flow rates.
\[{\dot m_{ReliefAir}} = MAX\left( {{{\dot m}_{OA}} - \,{{\dot m}_{ExhaustAir}}\,,0.0} \right)\]
Indoor Air Quality Procedure[LINK]
Like VRP, the user must include the following three objects in their input data file in order to model CO\(_{2}\)-based DCV with IAQP:
AirLoopHVAC:OutdoorAirSystem to simulate the mixed air box of the air loop
Controller:MechanicalVentilation to determine the minimum outside air flow rate to be provided by the mixed air box
Controller:OutdoorAir to control the outside air flow rate introduced via the mixed air box
The outdoor air mass flow rate provided by the air loop is calculated as below:
\[{\dot m_{OA}} = \sum\limits_i^N {{{\dot m}_{OA,z,i}} \times {SchedFrac_i}}\]
where:
\({\dot m_{OA,z,i}}\) = outdoor air mass flow rate for the ith zone as calculated according to section Carbon Dioxide Prediction located elsewhere in this document.
\({SchedFrac_i}\) = the Outdoor Air Schedule value for the zone, if specified in the corresponding DesignSpecification:OutdoorAir object (defaults to 1.0)
N = number of zones served by the air loop, which is provided in the input for a Controller:MechanicalVentilation object
Proportional Control[LINK]
The control has two choices: ProportionalControlBasedonOccupancySchedule and ProportionalControlBasedonDesignOccupancy. The difference is occupancy level. The former uses real time occupancy, while the latter uses design occupancy level. Like Ventilation Rate Procedure and the Indoor Air Quality Procedure, the following three objects must be included in the input data file in order to model CO\(_{2}\)-based DCV with Proportional Control:
AirLoopHVAC:OutdoorAirSystem to simulate the mixed air box of the air loop
Controller:MechanicalVentilation to determine the minimum outside air flow rate to be provided by the mixed air box
Controller:OutdoorAir to control the outside air flow rate introduced via the mixed air box
For the i-th zone, the outdoor air mass flow rate provided by the air loop is calculated as below:
1) The required intake flow of outdoor air for the design zone population, P\(_{z,i}\)
\[{V_{ot - design,i}} = \frac{{\left( {{R_{p,i}}.{P_{z,i}} \times {SchedFrac_i}} \right) + ({R_{a,i}}.{A_{z,i}} \times {SchedFrac_i})}}{{{E_i}}}\]
2) The required intake flow of outdoor air when the zone is unoccupied i.e. P\(_{z,i}\) = 0
\[{V_{ot - min,i}} = \frac{{({R_{a,i}}.{A_{z,i}} \times {SchedFrac_i})}}{{{E_i}}}\]
3) The target indoor CO\(_{2}\) concentration at \({V_{ot - design,i}}\)
\[{C_{s - design,i}} = {C_o} + \frac{N}{{\left( {{V_{ot - design,i}}/{P_{z,i}}} \right)}}\]
4) The target indoor CO\(_{2}\) concentration at \({V_{ot - min}}\) is either a user input in the object ZoneControl:ContaminantController or equal to the outdoor CO\(_{2}\) concentration. The default is outdoor CO\(_{2}\) concentration.
\[{C_{s - min,i}} = {C_o}\]
When the indoor CO\(_{2}\) concentration equals \({C_{s - design,i}}\) , \({V_{ot}}\) should equal \({V_{ot - design,i}}\) . When the indoor CO\(_{2}\) concentration equals \({C_{s - min,i}}\) , \({V_{ot}}\) should equal \({V_{ot - min,i}}\) . When the indoor CO\(_{2}\) concentration is between \({C_{s - min,i}}\) and \({C_{s - design,i}}\) , a controller should adjust outdoor air intake flow \({V_{ot}}\) proportionally between \({V_{ot - min,i}}\) and \({V_{ot - design,i}}\) :
\[{V_{ot,i}} = {V_{ot - min,i}} + ({V_{ot - design,i}} - {V_{ot - min,i}})\frac{{({C_{s - actual,i}} - {C_{s - min,i}})}}{{({C_{s - design,i}} - {C_{s - min,i}})}}\]
Where,
\({R_{p,i}}\) = Required outdoor air flow rate per person, (m\(^{3}\)/s)/person
\({R_{a,i}}\) = Required outdoor air flow rate per unit area, (m\(^{3}\)/s)/m\(^{2}\)
\({P_{z,i}}\) = Design zone population, number of people
\({SchedFrac_i}\) = the Outdoor Air Schedule value for the zone, if specified in the corresponding DesignSpecification:OutdoorAir object (defaults to 1.0)
When ProportionalControlBasedonDesignOccupancy is specified, number of people = design occupancy * current schedule value. When ProportionalControlBasedonDesignOccupancy is specified, number of people = design occupancy.
\({A_{z,i}}\) = Zone floor area, m\(^{2}\)
\({E_i}\) = The zone air distribution effectiveness
\(N\) = CO\(_{2}\) generation rate, (m\(^{3}\)/s)/person (Specified in the People object)
\({C_o}\) = CO\(_{2}\) concentration in the outdoor air, ppm
\({C_{s - design,i}}\) = CO\(_{2}\) concentration in the space for the design conditions, ppm
\({C_{s - min,i}}\) = Minimum CO\(_{2}\) concentration in the space, ppm
\({C_{s - actual,i}}\) = Actual CO\(_{2}\) concentration in the space, ppm
\({V_{ot - design,i}}\) = Required intake of outdoor air flow rate at \({C_{s - design}}\) , (m\(^{3}\)/s)
\({V_{ot - min,i}}\) = Required intake of outdoor air flow rate at \({C_{s - min}}\) , (m\(^{3}\)/s)
\({V_{ot,i}}\) = Required intake of outdoor air flow rate at \({C_{s - actual}}\) , (m\(^{3}\)/s)
Except \({C_{s - min,i}}\) above, all other variables are already available in EnergyPlus (See Eng. Reference for “Ventilation Rate Procedure” above for further details). \({C_{s - min}}\) can be specified in the ZoneControl:ContaminantController object as a schedule. If \({C_{s - min}}\) is not specified in the ZoneControl:ContaminantController object, then outdoor air CO2 concentration will be used as the minimum. In order for “ProportionalControl” to be active, the following conditions must be met, otherwise default “VentilationProcedure” will be modeled and a warning will be issued during runtime:
1) “Carbon Dioxide Control Availability Schedule Name” input field in the ZoneControl:ContaminantController object must be greater than zero.
2) CO2 gain from people in the zone must be greater than zero.
3) “Outdoor air flow per person” and “Outdoor air flow per zone floor area” in the corresponding “DesignSpecification:OutdoorAir” object must be greater than zero.
References[LINK]
ASHRAE. 2007. ANSI/ASHRAE Standard 62.1-2007, Ventilation for acceptable indoor air quality. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ASHRAE. 2010. ANSI/ASHRAE Standard 62.1-2010, Ventilation for acceptable indoor air quality. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
Emmerich, S.J. and A.K. Persily. 1997. Literature review on CO\(_{2}\)-based demand-controlled ventilation. ASHRAE Transactions 103(2):229-243.
Schell, M.B., S.C. Turner, R.O. Shim. 1998. Application of CO\(_{2}\)-based demand controlled ventilation using ASHRAE Standard 62-1989. ASHRAE Transactions 104(2):1213-1225.
Schell, M. and D. Int-Hout. 2001. Demand control ventilation using CO\(_{2}\). ASHRAE Journal, February.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.