Solar
Radiation Reflected from Exterior Surfaces[LINK]
EnergyPlus has an option to calculate beam and sky solar
radiation that is reflected from exterior surfaces and then
strikes the building. This calculation occurs if
“withReflections” is used on the SolarDistribution option in
the Building
object. For zones with detailed daylighting, these reflections
are also considered in the daylight illuminance
calculations.1
The reflecting surfaces fall into three categories:
These surfaces can have diffuse and/or specular
(beam-to-beam) reflectance values that are specified with the
ShadingProperty:Reflectance
object.
Exterior building surfaces. In this
case one section of the building reflects solar radiation onto
another section (and vice-versa). See Figure.
Opaque building surfaces (walls, for example) are assumed
to be diffusely reflecting. Windows and glass doors are
assumed to be specularly reflecting. The reflectance values
for opaque surfaces are calculated by the program from the
Solar Absorptance and Visible Absorptance values of the outer
material layer of the surface’s construction. The reflectance
values for windows and glass doors are calculated by the
program from the reflectance properties of the individual
glass layers that make up surface’s construction assuming no
shading device is present and taking into account
inter-reflections among the layers.
The ground surface. Beam solar and sky
solar reflection from the ground is calculated even if
“withReflections” is not used (the default). But in this case
the ground plane is considered unobstructed, i.e., the
shadowing of the ground by the building itself or by
obstructions such as neighboring buildings is ignored. This
shadowing is taken into account only if “WithReflections” is
used in the Solar Distribution field (in “Building” input
object) (Figure).
In this case the user-input value of ground view factor is not
used.
Examples of solar reflection
from shadowing surfaces in the Shading series of input
objects. Solid arrows are beam solar radiation; dashed arrows
are diffuse solar radiation. (a) Diffuse reflection of beam
solar radiation from the top of an overhang. (b) Diffuse
reflection of sky solar radiation from the top of an overhang.
(c) Beam-to-beam (specular) reflection from the façade of an
adjacent highly-glazed building represented by a vertical
shadowing surface.
Solar reflection from building
surfaces onto other building surfaces. In this example beam
solar reflects from a vertical section of the building onto a
roof section. The reflection from the window is specular. The
reflection from the wall is diffuse.
Shadowing by the building
itself affects beam solar reflection from the ground.
Beam-to-diffuse reflection from the ground onto the building
occurs only for sunlit areas, A and C, not for shaded area, B.
Shadowing by the building also affects sky solar reflection
from ground (not shown).
A different method from that described here is
used for calculating reflections from daylighting shelves (see
“Daylighting Shelves”).↩︎
Solar Radiation Reflected from Exterior Surfaces[LINK]
EnergyPlus has an option to calculate beam and sky solar radiation that is reflected from exterior surfaces and then strikes the building. This calculation occurs if “withReflections” is used on the SolarDistribution option in the Building object. For zones with detailed daylighting, these reflections are also considered in the daylight illuminance calculations.1
The reflecting surfaces fall into three categories:
Shadowing surfaces. These are surfaces like overhangs or neighboring buildings entered with objects Shading:Site:Detailed, Shading:Building:Detailed, or Shading:Zone:Detailed Examples are shown in Figure.
These surfaces can have diffuse and/or specular (beam-to-beam) reflectance values that are specified with the ShadingProperty:Reflectance object.
Exterior building surfaces. In this case one section of the building reflects solar radiation onto another section (and vice-versa). See Figure.
Opaque building surfaces (walls, for example) are assumed to be diffusely reflecting. Windows and glass doors are assumed to be specularly reflecting. The reflectance values for opaque surfaces are calculated by the program from the Solar Absorptance and Visible Absorptance values of the outer material layer of the surface’s construction. The reflectance values for windows and glass doors are calculated by the program from the reflectance properties of the individual glass layers that make up surface’s construction assuming no shading device is present and taking into account inter-reflections among the layers.
The ground surface. Beam solar and sky solar reflection from the ground is calculated even if “withReflections” is not used (the default). But in this case the ground plane is considered unobstructed, i.e., the shadowing of the ground by the building itself or by obstructions such as neighboring buildings is ignored. This shadowing is taken into account only if “WithReflections” is used in the Solar Distribution field (in “Building” input object) (Figure). In this case the user-input value of ground view factor is not used.
A different method from that described here is used for calculating reflections from daylighting shelves (see “Daylighting Shelves”).↩︎
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.