Surface Heat Balance With Moveable Insulation[LINK]
Basic Heat Balance Cases[LINK]
A heat balance must exist at the outside surface-air interface. The incoming conductive, convective, and radiative fluxes must sum up to zero:
Conductive+Convective+Radiative=0
In contrast to the internal surface heat balance that treats all surfaces simultaneously, the external thermal balance for each surface is performed independent of all other surfaces. This implies that there is no direct interaction between the individual surfaces.
TARP includes four possible representations for the basic outside surface heat balance. The first two depend on which of the optimal surface conductance algorithms the user selects. The simple outside surface conductance that includes both the convective and thermal interchange between the surface and the environment in a single coefficient, is represented by the thermal network in Figure. Equation can also be expressed as:
[KOPt+Y0⋅TIt−X0⋅TOt]+[HO⋅(Ta−TOt)]+QSO=0
This can be solved for the outside surface temperature.
TOt=[KOPt+QSO+Y0⋅TIt+HO⋅TaX0+HO]
The detailed outside surface conductance model considers convection and radiant interchange with the sky and with the ground as separate factors. Its use in the outside thermal balance is shown in Figure.In this case, equation can be expanded to give
[KOPt+Y0⋅TIt−X0⋅TOt]+[HA⋅(Ta−TOt)+HS⋅(Ts−TOt)+HG⋅(Tg−TOt)]+QSO=0
This can be solved for the outside surface temperature:
TOt=[KOPt+QSO+Y0⋅TIt+HA⋅Ta+HS⋅Ts+HG⋅TgX0+HA+HS+HG]
The third and fourth representations occur when the outside surface has been covered with movable insulation. The insulation has a conductance of UM. The thermal network in Figure represents this case.The insulation must be mass-less because it is not generally possible to perform a correct thermal balance at the juncture of two surfaces each modeled by CTF.
The equation for the thermal balance between the surface and the insulation is
[KOPt+Y0⋅TIt−X0⋅TOt+UM⋅(TM−TOt)]+QSO=0
Which can be rewritten to solve for TO :
TOt=[KOPt+QSO+Y0⋅TIt+UM⋅TMX0+UM]
Depending on whether or not the detailed or simple algorithm for surface conductance is being used, there are two expressions for TM, the outside temperature of the insulation. For the simple conductance:
TM=[QSM+UM⋅TOt+HO⋅TaUM+HO]
For the detailed conductance:
TOt=[QSM+UM⋅TOt+HA⋅Ta+HS⋅Ts+HG⋅TgUM+HA+HS+HG]
In this case the values of HA, HS and HG must be found by using an estimated value of TM in place of TO.
Heat Balance Cases[LINK]
TOt and TIt are related through the Y0CTF. However TIt is also unknown. While it is possible to combine the outside and the inside surface heat balances to compute TOt and TIt simultaneously, TARP uses a simpler procedure where TOt is based on a previous value of TI. When Y0 is small, as occurs in well insulated or very massive surfaces, TIt can be replaced by TIt−1 (which is known for the previous hour’s heat balance) without significantly effecting the value of TOt When Y0 is large, TO and TI can so strongly be coupled that separate outside and inside heat balances do not work because the environment and zone temperatures have negligible influence on the heat balances. The TARP uses the inside surface heat balance to couple TOt with TZ and TR. These two temperatures are less strongly influenced by TO and allow a reasonable heat balance. On the first heat balance iteration, TZ and TR are the values at time t-1. The user may optionally require that TOt be recomputed with every iteration of TIt. In this case TZ and TR have values from the previous iteration and a true simultaneous solution is achieved. In most conventional constructions, recomputing TOt does not significantly change the computed zone loads and temperatures. The inside surface heat balance is given by
TIt=[KIPt+QSI+HC⋅TZ+HR⋅TR+Y0⋅TOZ0+HC+HR]
The surface heat balances can be combined in eight ways according to conditions for calculations of the outside surface temperature
F1=[Y0Z0+HI+HR]
F2=[UMUM+HO]
F3=[UMUM+HA+HS+HG]
Case1: Y0 small, simple conductance, no movable insulation:[LINK]
From Equation
TOt=[KOPt+QSO+Y0⋅TIt−1+HO⋅TaX0+HO]
Case2: Y0 not small, simple conductance, no movable insulation:[LINK]
From Equations and
TOt=[KOPt+QSO+HO⋅Ta+F1⋅(KIPt+QSI+HI⋅TZ+HR⋅TR)X0+HO−F1⋅Y0]
Case3: Y0 small, detailed conductance, no movable insulation:[LINK]
From Equation
TOt=[KOPt+QSO+Y0⋅TIt−1+HA⋅Ta+HS⋅Ts+HG⋅TgX0+HA+HS+HG]
Case4: Y0 not small, detailed conductance, no movable insulation:[LINK]
From Equations and
TOt=[KOPt+QSO+HA⋅Ta+HS⋅Ts+HG⋅Tg+F1⋅(KIPt+QSI+HI⋅TZ+HR⋅TR)X0+HA+HS+HG−F1⋅Y0]
Case5: Y0 small, simple conductance, with movable insulation:[LINK]
From Equations and TOt=[KOPt+QSO+HA⋅Ta+HS⋅Ts+HG⋅Tg+F1⋅(KIPtQS1+HI⋅TZ+HR⋅TR)X0+HA+HS+HG−F1⋅Y0]
Case6: Y0 not small, simple conductance, with movable insulation:[LINK]
From Equations , and
TOt=[KOPt+QSO+F2⋅(QSM+HO⋅Ta)+F1⋅(KIPt+QSI+HI⋅TZ+HR⋅TR)X0+UM−F2⋅UM−F1⋅Y0]
Case7: Y0 small, detailed conductance, with movable insulation:[LINK]
From Equations and
TOt=[KOPt+QSO+Y0⋅TIt−1+F3(QSM+HA⋅Ta+HS⋅Ts+HG⋅Tg)X0+UM−F3⋅UM]
Case8: Y0 not small, detailed conductance, with movable insulation:[LINK]
From Equations , and
TOt=[KOPt+QSO+F1⋅(KIPt+QSI+HI⋅TZ+HR⋅TR)+F3(QSM+HA⋅Ta+HS⋅Ts+HG⋅Tg)X0+UM−F3⋅UM−F1⋅Y0]
Fortran Algorithm Examples[LINK]
Case5: Y0 small, simple conductance, with movable insulation:[LINK]
From Equation
! Outside heat balance case: Movable insulation, slow conduction, simple convection
F2 = DBLE(HmovInsul) / ( DBLE(HmovInsul) + DBLE(HExtSurf(SurfNum)) )
TH(SurfNum,1,1) = (-CTFConstOutPart(SurfNum) &
+DBLE(QRadSWOutAbs(SurfNum) ) &
+Construct(ConstrNum)\%CTFCross(0)*TempSurfIn(SurfNum) &
+F2* ( DBLE(QRadSWOutMvIns(SurfNum)) &
+ DBLE(HExtSurf(SurfNum))* DBLE(TempExt) ) ) &
/( Construct(ConstrNum)\%CTFOutside(0) + DBLE(HmovInsul) &
- F2* DBLE(HMovInsul))
Case6: Y0 not small, simple conductance, with movable insulation:[LINK]
From Equation
! Outside heat balance case: Movable insulation, quick conduction, simple convection
F2 = DBLE(HmovInsul) / ( DBLE(HmovInsul) + DBLE(HExtSurf(SurfNum)) )
TH(SurfNum,1,1) = (-CTFConstOutPart(SurfNum) &
DBLE(QRadSWOutAbs(SurfNum)) &
+F2*( DBLE(QRadSWOutMvIns(SurfNum)) &
+DBLE(HExtSurf(SurfNum))* DBLE(TempExt) ) &
+F1*( CTFConstInPart(SurfNum) &
+ DBLE(QRadSWInAbs(SurfNum)) &
+ DBLE(QRadThermInAbs(SurfNum)) &
+ DBLE(HConvIn(SurfNum))*MAT(ZoneNum) &
+ DBLE(NetLWRadToSurf(SurfNum)) ) ) &
/( Construct(ConstrNum)\%CTFOutside(0) + DBLE(HmovInsul) &
-F2* DBLE(HMovInsul )- F1*Construct(ConstrNum)\%CTFCross(0) )
Case7: Y0 small, detailed conductance, with movable insulation:[LINK]
From Equation
! Outside heat balance case: Movable insulation, slow conduction, detailed convection
F2 = DBLE(HMovInsul)/ ( DBLE(HMovInsul) + DBLE(HExtSurf(SurfNum)) &
+DBLE(HSky) + DBLE(HGround) )
TH(SurfNum,1,1) = (-CTFConstOutPart(SurfNum) &
+DBLE(QRadSWOutAbs(SurfNum)) &
+Construct(ConstrNum)\%CTFCross(0)*TempSurfIn(SurfNum) &
+F2*( DBLE(QRadSWOutMvIns(SurfNum)) &
+DBLE(HExtSurf(SurfNum))*DBLE(TempExt) &
+DBLE(HSky)*DBLE(SkyTemp) &
+DBLE(HGround)*DBLE(OutDryBulbTemp) ) ) &
/( Construct(ConstrNum)\%CTFOutside(0) &
+DBLE(HMovInsul) - F2*DBLE(HMovInsul) )
Case8: Y0 not small, detailed conductance, with movable insulation:[LINK]
From Equation
! Outside heat balance case: Movable insulation, quick conduction, detailed convection
F2 = DBLE(HMovInsul)/ ( DBLE(HMovInsul) + DBLE(HExtSurf(SurfNum)) &
+DBLE(HSky) + DBLE(HGround) )
TH(SurfNum,1,1) = (-CTFConstOutPart(SurfNum) &
+DBLE(QRadSWOutAbs(SurfNum)) &
+F1*( CTFConstInPart(SurfNum) &
+DBLE(QRadSWInAbs(SurfNum)) &
+DBLE(QRadThermInAbs(SurfNum)) &
+DBLE(HConvIn(SurfNum))*MAT(ZoneNum) &
+DBLE(NetLWRadToSurf(SurfNum)) ) &
+F2*( DBLE(QRadSWOutMvIns(SurfNum)) &
+DBLE(HExtSurf(SurfNum))*DBLE(TempExt) &
+DBLE(HSky)*DBLE(SkyTemp) &
+DBLE(HGround)*DBLE(OutDryBulbTemp) ) &
/( Construct(ConstrNum)\%CTFOutside(0) &
+DBLE(HMovInsul) - F2*DBLE(HMovInsul) &
-F1*Construct(ConstrNum)\%CTFCross(0) )
Fortran Variable Descriptions[LINK]
Fortran Variables and Descriptions
TH(SurfNum,1,1) |
Temperature History(SurfNum,Hist Term,In/Out), where: Hist Term (1 = Current Time, 2-MaxCTFTerms = previous times), In/Out (1 = Outside, 2 = Inside) |
TO |
C |
Temperature of outside of surface I at time t |
Construct(ConstrNum) % CTFCross(0) |
Cross or Y term of the CTF equation |
Y0 |
W/m K |
Cross CTF term |
Construct(ConstrNum) % CTFInside(0) |
Inside or Z terms of the CTF equation |
Z0 |
W/m K |
Inside CTF term |
Construct(ConstrNum) % CTFOutside(0) |
Outside or X terms of the CTF equation |
X0 |
W/m K |
Outside CTF term |
CTFConstInPart(SurfNum) |
Constant inside portion of the CTF calculation |
KIP |
W/m |
Portion of inward conductive flux based on previous temperature and flux history terms |
CTFConstOutPart(SurfNum) |
Constant Outside portion of the CTF calculation |
KOP |
W/m |
Portion of outward conductive flux based on previous temperature and flux history terms |
F1, F2, F3 |
Intermediate calculation variables |
F1, F2, F3 |
|
Radiation interchange factor between surfaces |
GroundTemp |
Ground surface temperature |
T |
C |
Temperature of ground at the surface exposed to the outside environment |
HConvIn(SurfNum) |
Inside convection coefficient |
HI |
W/m K |
Inside convection coefficient |
HExtSurf(SurfNum) |
Outside Convection Coefficient |
HO, HA |
W/m K |
Overall outside surface conductance |
HGround |
Radiant exchange (linearized) coefficient |
HG |
W/m K |
Radiative conductance (outside surface to ground temperature |
HmovInsul |
Conductance or “h” value of movable insulation |
UM |
W/m K |
Conductance of Movable insulation |
HSky |
Radiant exchange (linearized) coefficient |
HS |
W/m K |
Radiative conductance (outside surface to sky radiant temperature |
MAT(ZoneNum) |
Zone temperature |
TZ |
C |
Temperature of zone air |
NetLWRadToSurf(SurfNum) |
Net interior longwave radiation to a surface from other surfaces |
HR*TR |
W/m |
Net surface to surface radiant exchange |
QRadSWInAbs(SurfNum) |
Short-wave radiation absorbed on inside of opaque surface |
QSI |
W/m |
Short wave radiant flux absorbed at inside of surface |
QRadSWOutAbs(SurfNum) |
Short wave radiation absorbed on outside opaque surface |
QSO |
W/m |
Short wave radiant flux absorbed at outside of surface |
QRadSWOutMvIns(SurfNum) |
Short wave radiation absorbed on outside of movable insulation |
QSM |
W/m |
Short wave radiant flux absorbed at surface of movable insulation |
QRadThermInAbs(SurfNum) |
Thermal Radiation absorbed on inside surfaces |
|
W/m |
Longwave radiant flux from internal gains |
SkyTemp |
Sky temperature |
T |
C |
Sky temp |
TempExt |
Exterior surface temperature or exterior air temperature |
TM, T |
C |
Temperature of external surface of movable insulation or outside ambient air temperature |
TempSurfIn(SurfNum) |
Temperature of inside surface for each heat transfer surface |
TI |
C |
Temperature of inside of surface I at time t-1 |
Walton, G.N. 1983. “The Thermal Analysis Research Program Reference Manual Program (TARP)”, National Bureau of Standards (now National Institute of Standards and Technology).
Surface Heat Balance With Moveable Insulation[LINK]
Basic Heat Balance Cases[LINK]
A heat balance must exist at the outside surface-air interface. The incoming conductive, convective, and radiative fluxes must sum up to zero:
Conductive+Convective+Radiative=0
In contrast to the internal surface heat balance that treats all surfaces simultaneously, the external thermal balance for each surface is performed independent of all other surfaces. This implies that there is no direct interaction between the individual surfaces.
TARP includes four possible representations for the basic outside surface heat balance. The first two depend on which of the optimal surface conductance algorithms the user selects. The simple outside surface conductance that includes both the convective and thermal interchange between the surface and the environment in a single coefficient, is represented by the thermal network in Figure. Equation can also be expressed as:
[KOPt+Y0⋅TIt−X0⋅TOt]+[HO⋅(Ta−TOt)]+QSO=0
This can be solved for the outside surface temperature.
TOt=[KOPt+QSO+Y0⋅TIt+HO⋅TaX0+HO]
The detailed outside surface conductance model considers convection and radiant interchange with the sky and with the ground as separate factors. Its use in the outside thermal balance is shown in Figure.In this case, equation can be expanded to give
[KOPt+Y0⋅TIt−X0⋅TOt]+[HA⋅(Ta−TOt)+HS⋅(Ts−TOt)+HG⋅(Tg−TOt)]+QSO=0
This can be solved for the outside surface temperature:
TOt=[KOPt+QSO+Y0⋅TIt+HA⋅Ta+HS⋅Ts+HG⋅TgX0+HA+HS+HG]
The third and fourth representations occur when the outside surface has been covered with movable insulation. The insulation has a conductance of UM. The thermal network in Figure represents this case.The insulation must be mass-less because it is not generally possible to perform a correct thermal balance at the juncture of two surfaces each modeled by CTF.
The equation for the thermal balance between the surface and the insulation is
[KOPt+Y0⋅TIt−X0⋅TOt+UM⋅(TM−TOt)]+QSO=0
Which can be rewritten to solve for TO :
TOt=[KOPt+QSO+Y0⋅TIt+UM⋅TMX0+UM]
Depending on whether or not the detailed or simple algorithm for surface conductance is being used, there are two expressions for TM, the outside temperature of the insulation. For the simple conductance:
TM=[QSM+UM⋅TOt+HO⋅TaUM+HO]
For the detailed conductance:
TOt=[QSM+UM⋅TOt+HA⋅Ta+HS⋅Ts+HG⋅TgUM+HA+HS+HG]
In this case the values of HA, HS and HG must be found by using an estimated value of TM in place of TO.
Thermal Network for Simple Outside Surface Coefficient
Thermal Network for Detailed Outside Surface Coefficient
Thermal Network for Outside Moveable Insulation
Heat Balance Cases[LINK]
TOt and TIt are related through the Y0CTF. However TIt is also unknown. While it is possible to combine the outside and the inside surface heat balances to compute TOt and TIt simultaneously, TARP uses a simpler procedure where TOt is based on a previous value of TI. When Y0 is small, as occurs in well insulated or very massive surfaces, TIt can be replaced by TIt−1 (which is known for the previous hour’s heat balance) without significantly effecting the value of TOt When Y0 is large, TO and TI can so strongly be coupled that separate outside and inside heat balances do not work because the environment and zone temperatures have negligible influence on the heat balances. The TARP uses the inside surface heat balance to couple TOt with TZ and TR. These two temperatures are less strongly influenced by TO and allow a reasonable heat balance. On the first heat balance iteration, TZ and TR are the values at time t-1. The user may optionally require that TOt be recomputed with every iteration of TIt. In this case TZ and TR have values from the previous iteration and a true simultaneous solution is achieved. In most conventional constructions, recomputing TOt does not significantly change the computed zone loads and temperatures. The inside surface heat balance is given by
TIt=[KIPt+QSI+HC⋅TZ+HR⋅TR+Y0⋅TOZ0+HC+HR]
The surface heat balances can be combined in eight ways according to conditions for calculations of the outside surface temperature
F1=[Y0Z0+HI+HR]
F2=[UMUM+HO]
F3=[UMUM+HA+HS+HG]
Case1: Y0 small, simple conductance, no movable insulation:[LINK]
From Equation
TOt=[KOPt+QSO+Y0⋅TIt−1+HO⋅TaX0+HO]
Case2: Y0 not small, simple conductance, no movable insulation:[LINK]
From Equations and
TOt=[KOPt+QSO+HO⋅Ta+F1⋅(KIPt+QSI+HI⋅TZ+HR⋅TR)X0+HO−F1⋅Y0]
Case3: Y0 small, detailed conductance, no movable insulation:[LINK]
From Equation
TOt=[KOPt+QSO+Y0⋅TIt−1+HA⋅Ta+HS⋅Ts+HG⋅TgX0+HA+HS+HG]
Case4: Y0 not small, detailed conductance, no movable insulation:[LINK]
From Equations and
TOt=[KOPt+QSO+HA⋅Ta+HS⋅Ts+HG⋅Tg+F1⋅(KIPt+QSI+HI⋅TZ+HR⋅TR)X0+HA+HS+HG−F1⋅Y0]
Case5: Y0 small, simple conductance, with movable insulation:[LINK]
From Equations and TOt=[KOPt+QSO+HA⋅Ta+HS⋅Ts+HG⋅Tg+F1⋅(KIPtQS1+HI⋅TZ+HR⋅TR)X0+HA+HS+HG−F1⋅Y0]
Case6: Y0 not small, simple conductance, with movable insulation:[LINK]
From Equations , and
TOt=[KOPt+QSO+F2⋅(QSM+HO⋅Ta)+F1⋅(KIPt+QSI+HI⋅TZ+HR⋅TR)X0+UM−F2⋅UM−F1⋅Y0]
Case7: Y0 small, detailed conductance, with movable insulation:[LINK]
From Equations and
TOt=[KOPt+QSO+Y0⋅TIt−1+F3(QSM+HA⋅Ta+HS⋅Ts+HG⋅Tg)X0+UM−F3⋅UM]
Case8: Y0 not small, detailed conductance, with movable insulation:[LINK]
From Equations , and
TOt=[KOPt+QSO+F1⋅(KIPt+QSI+HI⋅TZ+HR⋅TR)+F3(QSM+HA⋅Ta+HS⋅Ts+HG⋅Tg)X0+UM−F3⋅UM−F1⋅Y0]
Fortran Algorithm Examples[LINK]
Case5: Y0 small, simple conductance, with movable insulation:[LINK]
From Equation
Case6: Y0 not small, simple conductance, with movable insulation:[LINK]
From Equation
Case7: Y0 small, detailed conductance, with movable insulation:[LINK]
From Equation
Case8: Y0 not small, detailed conductance, with movable insulation:[LINK]
From Equation
Fortran Variable Descriptions[LINK]
References[LINK]
Walton, G.N. 1983. “The Thermal Analysis Research Program Reference Manual Program (TARP)”, National Bureau of Standards (now National Institute of Standards and Technology).
Documentation content copyright © 1996-2016 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.