IDF Editor is an optional component of the EnergyPlus
installation. For users who want a simple way of creating or
editing EnergyPlus input data files (IDF), IDF Editor provides
this service. The IDF Editor does not check inputs for
validity, although some numeric fields are highlighted if out
of range and some text fields are highlighted if they contain
an invalid reference. For instructions and rules that must be
followed when creating an IDF file the user should refer to
the Input/Output
Reference document.
IDF Editor should be located in the
EnergyPlus\PreProcessor\IDFEditor directory where you
installed EnergyPlus. By double clicking on the IDF Editor
icon you will get a screen similar to the one shown above. IDF
Editor works in conjunction with the current EnergyPlus Input
Data Directory (IDD) file that resides in the directory where
EnergyPlus is installed. Another way to start the IDF Editor
is from EP-Launch. Multiple IDF files can be opened at
once.
Creating a new input data file or selecting an existing
input data file can be accomplished either through use of the
File menu on the menu bar at the top of the screen or through
use of the New File icon button or Open File icon button on
the tool bar.
The classes that can be used to make up an IDF file have
been organized into groups as shown in the ‘Class List’
portion of the screen. A class is made up of a group of
objects. Select a class from the list by clicking on and
highlighting the class. The field to the left of the selected
class in the ‘Class List’ will either contain [——] to indicate
that this class has no objects in the IDF file or it will
contain a number like [0003] to indicate the number of times
the object currently appears in the IDF file. For example, for
the BuildingSurface:Detailed
class selected in the screen above under the Thermal Zone
Description/Geometry group, there are 40 objects in the IDF
file. The details for these 40 objects or any new object that
is defined are displayed in columns within the grid. Each
object is made up of fields and can be used to further define
the object. Any units attached to each field are shown in the
second column. You may need to scroll down the ‘field’ list or
maximize the application to see all of the fields. Likewise,
you may need to scroll to the right of the main grid to see
other objects.
Options under the view menu can change how you use the
Class List. To display only classes that contain objects
select the “show classes with objects only” option on the
“View” menu. You can also toggle this feature on and off with
CTRL+L. If the file is empty and has no objects, this toggle
does not impact the display.
The “Show Quick Select Dropdowns” view menu option adds two
new input fields to the main screen. The input fields can be
used to go quickly to different classes in the main list of
classes. By typing in the top input field, the group that
starts with those letters are displayed. After selecting one
and pressing the tab button, classes in that group are shown
and by typing the first few letters, you can easily select a
specific class. Pressing tab again displays that class and it
objects. This method allows for quick selection of classes if
you remember the group name and class name.
By clicking and highlighting a value within an object,
several things happen:
Any user comments from the IDF file will be displayed
in the ‘Comments from IDF’ portion of the screen
Any notes contained in the IDD for this input field
will be displayed in the ‘Explanation of Keyword’ portion of
the screen
The value can be edited. Depending on the field, a drop
down list may display the default value, maximum and minimum,
or other keywords that can be used with the field.
Numeric fields that can be autosized will include
“autosize” as a selection in the drop down list.
Some numeric fields have a maximum and/or minimum value
specified in the IDD. If the value entered is outside this
range, the cell will be highlighted in pale orange.
For values that are names of nodes, a new dialog box
titled “Edit or Select Node Name” can be shown when the small
button is pressed that is on the right side in each node name
cell as described in the next section.
The following dialog box is displayed when the small button
is pressed that is on the right side of cells used for node
names. Double clicking on cells containing node names can also
make the dialog box appear.
Edit or Select Node Name Dialog
Box
To enter a new node name, type it in the “Node Name” field
near the top of the dialog. To select a name of a node that is
already being used in the file, choose a node name from the
list shown on the left of the dialog box and labeled “Other
Node Names.” When a node name is selected from the list on the
left side of the dialog box, the box near the bottom left
shown as “Where Selected Other Node Name Appears in File” will
display the name of the class, name of the object and name of
the field for each other location in the file that node name
is currently be used.
The Other Node Names list on the left side of the dialog
box may contain a very long list of node names depending on
the complexity of the HVAC system. To help with this, four
options are available just above the list titled All, Recent,
Containing, and Class or Field. The All option shows all node
names used in the file while the other options are used to
narrow the list down to only certain node names. The Recent
option shows only node names that have recently been edited.
The Containing option shows a list on the right side of the
dialog box called “Filter by Contents” which shows all of the
various words used as part of node names. These words can be
selected and the Other Node Names list will only show node
names that contain those words. By selecting words from this
list, the list of Other Node Names can be shortened very
quickly. The last option, Class or Field, shows a hierarchical
list on the right side titled Filter by Object or Field
containing the list of classes and fields that can have node
names. By selecting an object or a field, the Other Node Names
list on the right shows only node names that are present in
the selected object or field. This is another way of quickly
shortening the list of Other Node Names so that the
appropriate node name can be selected.
Finally, the Containing Text field just above the OK button
can be typed in. Whatever you type limits the Other Node Names
list to just those characters. The more typed, the shorter the
list becomes. This is another method of quickly finding the
node name used in other parts of the file. The Containing Text
field is usually used with the All option but can be used with
the other display options as well.
To delete an object, first click on any value for the
object and then click on the “Del Obj” button. To add a new
object, click on the “New Obj” button and a new object column
with fields set to blanks, zeros, or default values will be
added to the far right of the grid. The “Dup Obj” button is
similar to “New Obj”, but copies the values of the fields of
the currently selected object. Copying and pasting an object
or groups of objects is also possible using the “Copy Obj” and
“Paste Obj” buttons. These allow objects to be copied between
files are also good for copying from files in the DataSets
subdirectory. (Also see the Edit menu to perform these
functions.)
The File menu can be used for creating or selecting input
files just like the buttons on the IDF Editor screen (see the
Creating or Selecting an Input File section above).
In addition, the File menu is used to save a file or exit the
IDF Editor. More than one file can be opened at a time.
The “File”, “Save Options” screen is shown below.
IDF Editor Save Options
Screen.
The save options allow the order of the objects in the file
to be sorted by type of object or to keep the original order
of the objects (for an existing file). The placement of new
objects when the original order is specified can be either at
the top or bottom of the file.
In addition, the Save Options also allow certain objects to
be written to the file using a specific format that some users
prefer.
The settings for the save options are kept for each file
saved from the IDF Editor.
The “Set as Default” option allows you to keep the save
options intact for files that have not been saved yet with a
version of IDF Editor that has this capability.
The Help that is available from the Save Options screen is
reproduced below:
The save options are related to the layout of the IDF
file after it is saved. These options are not important if you
never edit the IDF file with a text editor.
The sorted order of saving objects is the traditional
way the IDF Editor sorts objects within files. Each type of
object is presented in groups in the order they appear in the
Energy+.IDD. The other options preserve the original order of
the objects from the file but each object will be still be
reformatted. By preserving the order, the objects are not
rearranged so you can group them using a text editor and they
will stay in that order. New objects are placed either near
the top of the file or near the bottom of the file so that
they can be easily found when using a text editor.
You can also choose to specially format some objects.
This affects how individual fields in objects are arranged
when saved. Selecting this option will format the following
objects on a single line: Report, Report Meter, Report
Variable, Version,Timestep
in Hour, Inside Convection Algorithm, Outside Convection
Algorithm, Solution Algorithm, Shadowing Calculations, Ground
Reflectances, and GroundTemperatures:Deep. In addition, Schedule:Compact
objects will be formatted to have two field for some lines.
With this option, objects with geometric vertices are
formatted to have the X, Y, and Z values on the same line.
Those objects include: Surface:HeatTransfer,
Surface:HeatTransfer:Sub, Surface:Shading:Detached:Fixed,
Surface:Shading:Detached:Building and
Surface:Shading:Attached.
These options are saved for each file. If a file has
not been saved with IDF Editor yet, the default is used but if
a file does not specify the default values for these can also
be set by using the set as default option. The saved file
keeps these options by using the !-option line with
SortedOrder, OriginalOrderTop, OriginalOrderBottom, and
UseSpecialFormat.”
Full line comments which begin with “!” are preserved
by IDF Editor and become associated with the object
immediately followin the comment line(s).
Endline comments which begin with “!” are preserved by
IDF Editor and are placed immediately before the object they
are found in.
Endline comment which being with “!-” are automatic
comments which IDF Editor will overwrite with the field name
and units. User-provided text which follows “!-” will be lost.
User comments should be added above the pertinent object using
“!” to begin the line.
Also on the File menu is the Open DataSet menu and submenu.
This allows you to open any input file that appears in the
DataSet subdirectory and copy objects from them into another
file. This is required because EnergyPlus does not read the
DataSet files, it is up to you to include objects from
them.
The Edit Menu offers options to create a new object,
duplicate an object, and delete an object as well as finding
and searching. The object options are the same operations as
can be accomplished by using the ‘New Obj’, ‘Dup Obj’ and ‘Del
Obj’ buttons (see the Working with Objects section
above). In addition, the “Next Row after Enter” option can be
toggled. When this option is on, the selection moves down one
row after pressing Enter. The copy and paste object commands
allow a single object to be copied within a file or between
files. The pasted object appears as the last object in the
class. This capability makes it easier to utilize the data in
the DataSets directory.
The Find Class menu item brings up the following dialog box
used to search through the Class List:
Find Class Dialog
Box
The Find Class dialog can be used to find class names
quickly and can be activated by the CTRL-F keyboard
combination. The Find Previous Class (CTRL-T) and Find Next
Class (CTRL-G) can continue the searching process for the next
and previous times that the searched text is found in the
Class List. If you find this option useful you may also want
to try the Show Quick Select Dropdowns option under the View
menu which also speeds up searching through the Class
List.
The Search and Replace menu item or CTRL-H activates the
following dialog box:
Search and Replace Diaglog
Box
The Search and Replace dialog box can be used to find and
change each instance of text being searched with some
replacement text. The Search and Replace dialog is used to
search and replace values of fields rather than classes like
the Find Class dialog. To use the Search and Replace dialog,
enter the text being searched in the Find What field and press
the Find button. After the Find button is pressed, the list
shows the places in the file that the text appears. For each
time the text is found, the entire field value is shown
followed by the class name, name of the object, and the name
of the field in parentheses. Each item in the list can be
selected using the check box to the left. The All and None
buttons will select all or none of the items found. After the
locations are selected that need to be replaced, you should
enter the text in the Replace With field. When the Replace
Selected button is pressed the value in each of locations that
were checked will be replaced with the Replace with text.
The dialog will usually open with the Find What field
filled with the value of the currently selected cell. If the
current cell has just been changed, the Find What and the
Replace With fields will contain the before and after values
of the change in the current cell. This makes it easy to
change other instances in the file to be consistent with the
changes just made. If renaming objects, the recommended
approach is to rename the object and select the cell again and
open the Search and Replace dialog. This will show other
places in the file that use that object name that also may
need to be changed.
The View menu offers options for units and column widths.
The Narrow/Medium/Wide Column options set the standard column
width for items in the object grid. Individual columns can
also be resized by dragging the column separator. The
displayed value is rounded and/or expressed in scientific
notation to fit within the column width.
EnergyPlus input files are always in SI units. However,
selecting “Inch-Pound” (IP) units in the View menu displays
and edits values in IP units in the IDF editor. The IP unit
will be displayed in the units column of the object grid. Some
SI units convert to multiple IP units. For example, W becomes
Btu/hr for heating and cooling capacity but remains as W for
lighting and electrical equipment.
All conversion factors used in the IDF editor are
documented in a block of comments near the top of the
Energy+.IDD file.
Schedules, fluid properties and curves now support IP
unit conversions. For curves, the minimum and maximum values
are converted but the coefficients are not.
To display only classes that contain objects select the
“show classes with objects only” option on the “View” menu.
You can also toggle this feature on and off with CTRL+L. If
the file is empty and has no objects, this toggle does not
impact the display.
The “Show Quick Select Dropdowns” option, which can also be
turned on and off with CTRL-Q, displays two dropdown lists
above the class list that can be quickly used to select
classes. The first list displays the possible groups. Once
those are selected, the second list contains only the classes
within that group. This option may be used to quickly access
classes while avoiding scrolling through the long class list.
In addition these pull down menus may be used with the
keyboard to select groups and class names based on the first
few letters of the names.
The figure below shows the “Layout Options” also accessible
under the View menu.
IDF Editor Layout Options
Screen.
This option allows for different arrangements of the layout
for the main screen of the IDF Editor. Select one of the four
layouts available.
The “Show Quick Select Dropdowns” view menu option adds two
new input fields to the main screen. The input fields can be
used to go quickly to different classes in the main list of
classes.
The “Validity Check” function has replaced and expanded
upon the old “Check Out-of-Range” function. It can also be
started by using CTRL-R. The “Validity Check” function
performs three kinds of validity checks and displays the
results as shown in the dialog box below:
Validity Check Dialog
Box
The list displays the values and locations for objects with
values that are either above the maximum or below the minimum
values. This allows you to check your input for out-of-range
values prior to running EnergyPlus. It also displays fields
that contain invalid references. An invalid reference is when
a name is used that should be the name of object but no object
exists that uses that name. For example, if a Construction
object references a layer named IN20 but no Material
(or Material:NoMass,
etc.) object is named IN20. When viewing the class that
contains invalid references, those references are shown with a
different background color similar to numbers that are out of
range. The “Validity Check” dialog also shows when an entry
for a field is not one of the possible lists of choices. The
Goto button allows you to jump directly to the selected
identified problems. The Perform Validity Check When Saving
File can be turned on and off and automatically performs the
check whenever the file is saved.
Remember to save any changes made before you create or edit
another input file.
No “Run EnergyPlus” button is available. Save your IDF file
and use EP-Launch to execute an EnergyPlus run.
You cannot edit comments in the ‘Comments from IDF’ section
of the screen.
The use of point “.” or comma “,” as the decimal symbol is
controlled by the windows system settings. This setting is
found in the Control Panel, Regional Options, Number tab,
Decimal Symbol field. IDF Editor will use the current decimal
symbol to signify the start of the fractional portion of the
number and will ignore other symbols. The idf file is always
written using point “.” as the decimal symbol.
IDFEditor[LINK]
IDF Editor is an optional component of the EnergyPlus installation. For users who want a simple way of creating or editing EnergyPlus input data files (IDF), IDF Editor provides this service. The IDF Editor does not check inputs for validity, although some numeric fields are highlighted if out of range and some text fields are highlighted if they contain an invalid reference. For instructions and rules that must be followed when creating an IDF file the user should refer to the Input/Output Reference document.
Start IDF Editor[LINK]
IDF Editor should be located in the EnergyPlus\PreProcessor\IDFEditor directory where you installed EnergyPlus. By double clicking on the IDF Editor icon you will get a screen similar to the one shown above. IDF Editor works in conjunction with the current EnergyPlus Input Data Directory (IDD) file that resides in the directory where EnergyPlus is installed. Another way to start the IDF Editor is from EP-Launch. Multiple IDF files can be opened at once.
Creating or Selecting an Input Data File[LINK]
Creating a new input data file or selecting an existing input data file can be accomplished either through use of the File menu on the menu bar at the top of the screen or through use of the New File icon button or Open File icon button on the tool bar.
Class List and Objects[LINK]
The classes that can be used to make up an IDF file have been organized into groups as shown in the ‘Class List’ portion of the screen. A class is made up of a group of objects. Select a class from the list by clicking on and highlighting the class. The field to the left of the selected class in the ‘Class List’ will either contain [——] to indicate that this class has no objects in the IDF file or it will contain a number like [0003] to indicate the number of times the object currently appears in the IDF file. For example, for the BuildingSurface:Detailed class selected in the screen above under the Thermal Zone Description/Geometry group, there are 40 objects in the IDF file. The details for these 40 objects or any new object that is defined are displayed in columns within the grid. Each object is made up of fields and can be used to further define the object. Any units attached to each field are shown in the second column. You may need to scroll down the ‘field’ list or maximize the application to see all of the fields. Likewise, you may need to scroll to the right of the main grid to see other objects.
Options under the view menu can change how you use the Class List. To display only classes that contain objects select the “show classes with objects only” option on the “View” menu. You can also toggle this feature on and off with CTRL+L. If the file is empty and has no objects, this toggle does not impact the display.
The “Show Quick Select Dropdowns” view menu option adds two new input fields to the main screen. The input fields can be used to go quickly to different classes in the main list of classes. By typing in the top input field, the group that starts with those letters are displayed. After selecting one and pressing the tab button, classes in that group are shown and by typing the first few letters, you can easily select a specific class. Pressing tab again displays that class and it objects. This method allows for quick selection of classes if you remember the group name and class name.
Changing Values[LINK]
By clicking and highlighting a value within an object, several things happen:
Any user comments from the IDF file will be displayed in the ‘Comments from IDF’ portion of the screen
Any notes contained in the IDD for this input field will be displayed in the ‘Explanation of Keyword’ portion of the screen
The value can be edited. Depending on the field, a drop down list may display the default value, maximum and minimum, or other keywords that can be used with the field.
Numeric fields that can be autosized will include “autosize” as a selection in the drop down list.
Some numeric fields have a maximum and/or minimum value specified in the IDD. If the value entered is outside this range, the cell will be highlighted in pale orange.
For values that are names of nodes, a new dialog box titled “Edit or Select Node Name” can be shown when the small button is pressed that is on the right side in each node name cell as described in the next section.
Edit or Select Node Names Dialog[LINK]
The following dialog box is displayed when the small button is pressed that is on the right side of cells used for node names. Double clicking on cells containing node names can also make the dialog box appear.
To enter a new node name, type it in the “Node Name” field near the top of the dialog. To select a name of a node that is already being used in the file, choose a node name from the list shown on the left of the dialog box and labeled “Other Node Names.” When a node name is selected from the list on the left side of the dialog box, the box near the bottom left shown as “Where Selected Other Node Name Appears in File” will display the name of the class, name of the object and name of the field for each other location in the file that node name is currently be used.
The Other Node Names list on the left side of the dialog box may contain a very long list of node names depending on the complexity of the HVAC system. To help with this, four options are available just above the list titled All, Recent, Containing, and Class or Field. The All option shows all node names used in the file while the other options are used to narrow the list down to only certain node names. The Recent option shows only node names that have recently been edited. The Containing option shows a list on the right side of the dialog box called “Filter by Contents” which shows all of the various words used as part of node names. These words can be selected and the Other Node Names list will only show node names that contain those words. By selecting words from this list, the list of Other Node Names can be shortened very quickly. The last option, Class or Field, shows a hierarchical list on the right side titled Filter by Object or Field containing the list of classes and fields that can have node names. By selecting an object or a field, the Other Node Names list on the right shows only node names that are present in the selected object or field. This is another way of quickly shortening the list of Other Node Names so that the appropriate node name can be selected.
Finally, the Containing Text field just above the OK button can be typed in. Whatever you type limits the Other Node Names list to just those characters. The more typed, the shorter the list becomes. This is another method of quickly finding the node name used in other parts of the file. The Containing Text field is usually used with the All option but can be used with the other display options as well.
Working with Objects[LINK]
To delete an object, first click on any value for the object and then click on the “Del Obj” button. To add a new object, click on the “New Obj” button and a new object column with fields set to blanks, zeros, or default values will be added to the far right of the grid. The “Dup Obj” button is similar to “New Obj”, but copies the values of the fields of the currently selected object. Copying and pasting an object or groups of objects is also possible using the “Copy Obj” and “Paste Obj” buttons. These allow objects to be copied between files are also good for copying from files in the DataSets subdirectory. (Also see the Edit menu to perform these functions.)
File Menu[LINK]
The File menu can be used for creating or selecting input files just like the buttons on the IDF Editor screen (see the Creating or Selecting an Input File section above). In addition, the File menu is used to save a file or exit the IDF Editor. More than one file can be opened at a time.
The “File”, “Save Options” screen is shown below.
The save options allow the order of the objects in the file to be sorted by type of object or to keep the original order of the objects (for an existing file). The placement of new objects when the original order is specified can be either at the top or bottom of the file.
In addition, the Save Options also allow certain objects to be written to the file using a specific format that some users prefer.
The settings for the save options are kept for each file saved from the IDF Editor.
The “Set as Default” option allows you to keep the save options intact for files that have not been saved yet with a version of IDF Editor that has this capability.
The Help that is available from the Save Options screen is reproduced below:
The save options are related to the layout of the IDF file after it is saved. These options are not important if you never edit the IDF file with a text editor.
The sorted order of saving objects is the traditional way the IDF Editor sorts objects within files. Each type of object is presented in groups in the order they appear in the Energy+.IDD. The other options preserve the original order of the objects from the file but each object will be still be reformatted. By preserving the order, the objects are not rearranged so you can group them using a text editor and they will stay in that order. New objects are placed either near the top of the file or near the bottom of the file so that they can be easily found when using a text editor.
You can also choose to specially format some objects. This affects how individual fields in objects are arranged when saved. Selecting this option will format the following objects on a single line: Report, Report Meter, Report Variable, Version, Timestep in Hour, Inside Convection Algorithm, Outside Convection Algorithm, Solution Algorithm, Shadowing Calculations, Ground Reflectances, and GroundTemperatures:Deep. In addition, Schedule:Compact objects will be formatted to have two field for some lines. With this option, objects with geometric vertices are formatted to have the X, Y, and Z values on the same line. Those objects include: Surface:HeatTransfer, Surface:HeatTransfer:Sub, Surface:Shading:Detached:Fixed, Surface:Shading:Detached:Building and Surface:Shading:Attached.
These options are saved for each file. If a file has not been saved with IDF Editor yet, the default is used but if a file does not specify the default values for these can also be set by using the set as default option. The saved file keeps these options by using the !-option line with SortedOrder, OriginalOrderTop, OriginalOrderBottom, and UseSpecialFormat.”
Full line comments which begin with “!” are preserved by IDF Editor and become associated with the object immediately followin the comment line(s).
Endline comments which begin with “!” are preserved by IDF Editor and are placed immediately before the object they are found in.
Endline comment which being with “!-” are automatic comments which IDF Editor will overwrite with the field name and units. User-provided text which follows “!-” will be lost. User comments should be added above the pertinent object using “!” to begin the line.
Also on the File menu is the Open DataSet menu and submenu. This allows you to open any input file that appears in the DataSet subdirectory and copy objects from them into another file. This is required because EnergyPlus does not read the DataSet files, it is up to you to include objects from them.
Edit Menu[LINK]
The Edit Menu offers options to create a new object, duplicate an object, and delete an object as well as finding and searching. The object options are the same operations as can be accomplished by using the ‘New Obj’, ‘Dup Obj’ and ‘Del Obj’ buttons (see the Working with Objects section above). In addition, the “Next Row after Enter” option can be toggled. When this option is on, the selection moves down one row after pressing Enter. The copy and paste object commands allow a single object to be copied within a file or between files. The pasted object appears as the last object in the class. This capability makes it easier to utilize the data in the DataSets directory.
The Find Class menu item brings up the following dialog box used to search through the Class List:
The Find Class dialog can be used to find class names quickly and can be activated by the CTRL-F keyboard combination. The Find Previous Class (CTRL-T) and Find Next Class (CTRL-G) can continue the searching process for the next and previous times that the searched text is found in the Class List. If you find this option useful you may also want to try the Show Quick Select Dropdowns option under the View menu which also speeds up searching through the Class List.
The Search and Replace menu item or CTRL-H activates the following dialog box:
The Search and Replace dialog box can be used to find and change each instance of text being searched with some replacement text. The Search and Replace dialog is used to search and replace values of fields rather than classes like the Find Class dialog. To use the Search and Replace dialog, enter the text being searched in the Find What field and press the Find button. After the Find button is pressed, the list shows the places in the file that the text appears. For each time the text is found, the entire field value is shown followed by the class name, name of the object, and the name of the field in parentheses. Each item in the list can be selected using the check box to the left. The All and None buttons will select all or none of the items found. After the locations are selected that need to be replaced, you should enter the text in the Replace With field. When the Replace Selected button is pressed the value in each of locations that were checked will be replaced with the Replace with text.
The dialog will usually open with the Find What field filled with the value of the currently selected cell. If the current cell has just been changed, the Find What and the Replace With fields will contain the before and after values of the change in the current cell. This makes it easy to change other instances in the file to be consistent with the changes just made. If renaming objects, the recommended approach is to rename the object and select the cell again and open the Search and Replace dialog. This will show other places in the file that use that object name that also may need to be changed.
View Menu[LINK]
The View menu offers options for units and column widths. The Narrow/Medium/Wide Column options set the standard column width for items in the object grid. Individual columns can also be resized by dragging the column separator. The displayed value is rounded and/or expressed in scientific notation to fit within the column width.
EnergyPlus input files are always in SI units. However, selecting “Inch-Pound” (IP) units in the View menu displays and edits values in IP units in the IDF editor. The IP unit will be displayed in the units column of the object grid. Some SI units convert to multiple IP units. For example, W becomes Btu/hr for heating and cooling capacity but remains as W for lighting and electrical equipment.
All conversion factors used in the IDF editor are documented in a block of comments near the top of the Energy+.IDD file.
Schedules, fluid properties and curves now support IP unit conversions. For curves, the minimum and maximum values are converted but the coefficients are not.
To display only classes that contain objects select the “show classes with objects only” option on the “View” menu. You can also toggle this feature on and off with CTRL+L. If the file is empty and has no objects, this toggle does not impact the display.
The “Show Quick Select Dropdowns” option, which can also be turned on and off with CTRL-Q, displays two dropdown lists above the class list that can be quickly used to select classes. The first list displays the possible groups. Once those are selected, the second list contains only the classes within that group. This option may be used to quickly access classes while avoiding scrolling through the long class list. In addition these pull down menus may be used with the keyboard to select groups and class names based on the first few letters of the names.
The figure below shows the “Layout Options” also accessible under the View menu.
This option allows for different arrangements of the layout for the main screen of the IDF Editor. Select one of the four layouts available.
The “Show Quick Select Dropdowns” view menu option adds two new input fields to the main screen. The input fields can be used to go quickly to different classes in the main list of classes.
The “Validity Check” function has replaced and expanded upon the old “Check Out-of-Range” function. It can also be started by using CTRL-R. The “Validity Check” function performs three kinds of validity checks and displays the results as shown in the dialog box below:
The list displays the values and locations for objects with values that are either above the maximum or below the minimum values. This allows you to check your input for out-of-range values prior to running EnergyPlus. It also displays fields that contain invalid references. An invalid reference is when a name is used that should be the name of object but no object exists that uses that name. For example, if a Construction object references a layer named IN20 but no Material (or Material:NoMass, etc.) object is named IN20. When viewing the class that contains invalid references, those references are shown with a different background color similar to numbers that are out of range. The “Validity Check” dialog also shows when an entry for a field is not one of the possible lists of choices. The Goto button allows you to jump directly to the selected identified problems. The Perform Validity Check When Saving File can be turned on and off and automatically performs the check whenever the file is saved.
Help Menu[LINK]
The Help menu offers options to open the EnergyPlus documentation files.
Caveats[LINK]
Remember to save any changes made before you create or edit another input file.
No “Run EnergyPlus” button is available. Save your IDF file and use EP-Launch to execute an EnergyPlus run.
You cannot edit comments in the ‘Comments from IDF’ section of the screen.
The use of point “.” or comma “,” as the decimal symbol is controlled by the windows system settings. This setting is found in the Control Panel, Regional Options, Number tab, Decimal Symbol field. IDF Editor will use the current decimal symbol to signify the start of the fractional portion of the number and will ignore other symbols. The idf file is always written using point “.” as the decimal symbol.
Bugs[LINK]
Please report any bugs to the helpdesk (email to energyplus-support@gard.com) so that we can fix them prior to the next release.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.