The Version
object allows you to enter the proper version that your IDF
was created for. This is checked against the current version
of EnergyPlus and a Severe error issued (non-terminating) if
it does not match the current version string. Note that
versions are often significant and there is no guarantee that
the older file will run in the newer versions of the program.
See IDF Version
Updater (Auxiliary Programs Document) for methods of changing
the older files to newer versions.
The Timestep
object specifies the “basic” timestep for the simulation. The
value entered here is usually known as the ZoneTimestep.
This is used in the Zone
Heat Balance Model calculation as the driving timestep for
heat transfer and load calculations. The value entered here is
the number of timesteps to use within an hour. Longer length
timesteps have lower values for Number of Timesteps per Hour.
For example a value of 6 entered here directs the program to
use a zone timestep of 10 minutes and a value of 60 means a 1
minute timestep. The user’s choice for Number of Timesteps per
Hour must be evenly divisible into 60; the allowable choices
are 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, and 60.
The choice made for this field has important implications
for modeling accuracy and the overall time it takes to run a
simulation. Here are some considerations when choosing a
value:
The solution technique used in EnergyPlus has been
designed to be stable with zone timesteps of up to sixty
minutes (Number Timesteps in Hour = 1). However, 60 minutes is
considered a “long” timestep and it should only be used in
rare occasions where there is no HVAC system, accuracy is not
a concern, and short run times are critical. Such long
timesteps are not recommended to use because simulation
results are more accurate for shorter timesteps, of say 10
minutes or less (Number of Timesteps per Hour of 6 or more).
Shorter zone timesteps improve the numerical solution of the
Zone
Heat Balance Model because they improve how models for surface
temperature and zone air temperature are coupled together.
Longer timesteps introduce more lag and lead to more a
dampened dynamic response.
Simulation run time increases with shorter timesteps or
larger values for Number of Timesteps per Hour. The effect
varies with the nature of the model. The user can test out
different values on their particular model to understand the
implications for his or her particular case. Sometimes large
models with multizone HVAC and Plant systems execute nearly as
fast with 15 minute timesteps as with 60 minute timesteps
because fewer iterations are required in the system modeling
since the prior timestep’s results are close to the final
outcome of next timestep.
The weather data files usually have 60-minute (or
hourly) data. However, it does not follow that this should be
used as the basis for choosing the zone timestep
because:
EnergyPlus carefully interpolates the weather data
between data points for use at shorter timesteps. This is
discussed in a later section: Weather Data Hourly
Interpolation
Many aspects of a model have time scales that differ
from the that of the weather data. A goal of the modeling is
to predict how the building will respond to the weather.
However, the building’s response is not governed by
the time scale that the weather data are available at, but
rather the time scales of the dynamic performance of the
thermal envelope as well as things like schedules for internal
gains, thermostats, and equipment availability.
If the model will include calculating the cost of
electricity, then the user should be aware that many electric
utility tariffs base charges on demand windows of a specified
length of time. If the choice of Number of Timesteps per Hour
is not consistent with the demand window, then unexpected
results may be obtained. For reasonable prediction of the
maximum rates for electricity use for in calculating demand
charges, the length of the zone timestep needs to be
consistent with the tariff’s demand window. The following
table lists what values are consistent with various demand
windows.
Demand Window
Applicable Number of Timesteps
per Hour
QuarterHour
4, 12, 20, or 60
HalfHour
2, 4, 6, 10, 12, 20, 30, or
60
FullHour, Day, Week
Any
There is also second type of timestep inside EnergyPlus
that is known as the System Timestep.
This is a variable-length timestep that governs the driving
timestep for HVAC and Plant system modeling. The user cannot
directly control the system timestep (except by use of the ConvergenceLimits
object). When the HVAC portion of the simulation begins its
solution for the current zone timestep, it uses the zone
timestep as its maximum length but then can reduce the
timestep, as necessary, to improve the solution. The technical
details of the approach are explained in the Engineering
Documentation under “Integrated Solution Manager”.
Users can see the system timestep used if they select the
“detailed” frequency option on an HVAC output variable
(e.g. Zone Air Temperature). To contrast, the “Zone” variables
will only be reported on the zone timestep (e.g. Zone Mean Air
Temperature).
And, the IDF example:
Timestep, 6; !- Suggested default for most system simulations
Suggested defaults are 4 for non-HVAC simulations, 6 for
simulations with HVAC, 20 is the minimum for
ConductionFiniteDifference and HeatAndMoistureFiniteElement
simulations. Green roof (ref: Material:RoofVegetation) also
may require more timesteps.
Note that hourly data (such as outdoor conditions expressed
by Design Days or Weather data) are interpolated to the ZoneTimestep.
This is discussed in a later section: Weather Data Hourly
Interpolation
This item is an “advanced” feature that should be used only
with caution. It is specifically included to assist some users
“speed up” calculations while not overly compromising
accuracy. The user must judge for him/herself whether the
reduced run time is useful.
Usually the minimum system timestep is allowed to vary from
the zone timestep (as maximum) to a minimum timestep of 1
minute during certain system calculations. This might be when
the system turns on or off, for example. Entering 0 in this
field sets the minimum system timestep to be the same as the
zone timestep. Otherwise the units of the field are minutes.
It’s probably a good idea to have any minimum entered be a
divisor of the zone timestep.
The HVAC Manager will iterate to a solution or up to a set
number of iterations. If not “converged”, then a warning error
appears:
SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at CHICAGO IL USA TMY2-94846 WMO# = 725300, 10/07 14:06 - 14:08
In order to reduce time used in simulating your building,
you may choose to enter a lesser number than the default of 20
for the maximum number of iterations to be used. Or, you may
wish to enter a bigger number for certain buildings. To get
more information printed with a “max iteration” message, you
need to enter a “Output:Diagnostics, DisplayExtraWarnings;”
command (which may also generate other warnings than just this
one).
The plant system modeling includes a solver that iterates
within a single HVAC manager iteration. This input field and
the next one provide some control over how the plant solver
iterates. This field sets a minimum threshold for plant
iterations. The default for this field is the value “2” which
indicates that a minimum of two full plant model interations
will be performed every time plant is called by the HVAC
manager. For faster performance with simple plant systems,
this input field could be set to the value “1”. For
complicated plant systems that present difficulties to solve,
this value may need to be set higher to ensure accuracy but at
the expense of speed. Complicated plant systems include those
with several interconnected loops, sizing miss-matches such
that plant components are starved of flow compared to their
desired flow, heat recovery systems, and thermal load
following onsite generators.
The plant system solver iterates within a single HVAC
manager iteration. This input field and the previous one
provide some control over how the plant model iterates. This
field sets a maximum limit for plant interations. The default
for this field is the value “8” which indicates that the plant
solver will exit after having completed eight full iterations.
This value can be raised for better accuracy with complex
plants or lowered for faster speed with simple plants. The
output variable called “Plant Solver Sub Iteration Count”
(typically reported at the “detailed” frequency) is useful for
understanding how many plant solver iterations are actually
being used during a particular simulation. The lower limit of
the value for this field is “2.”
Use in an IDF:
ConvergenceLimits,
0, !- Minimum System Timestep (0 = same as zone timestep)
25, !- Maximum HVAC Iterations
3, !- Minimum Plant Iterations
9; !- Maximum Plant Iterations
The Building
object describes parameters that are used during the
simulation of the building. There are necessary correlations
between the entries for this object and some entries in the Site:WeatherStation
and Site:HeightVariation
objects, specifically the Terrain field.
The Building
North Axis is specified relative to true
North. Buildings frequently do not line up with true
north. For convenience, one may enter surfaces in a “regular”
coordinate system and then shift them via the use of the North
Axis. The value is specified in degrees from “true north”
(clockwise is positive).
The figure below shows how the building north axis can be
rotated to correspond with one of the major axes of an actual
building. The relevance of this field is described more
completely under “GlobalGeometryRules”; in particular, the
value of “North Axis” is ignored if a coordinate
system other than “relative” is used.
The site’s terrain affects how the wind hits the building –
as does the building height. In addition, the external
conduction method usually has its own parameters for the
calculation. Please see the Engineering Documentation,
External Conduction section for particulars. The legal values
for this field are shown in the following table.
The following two fields along with the minimum and maximum
number of warmup days (also in this object) define the user
specified criteria for when EnergyPlus will “converge” at each
environment (each sizing period or run period set as Yes in
the SimulationControl
object). EnergyPlus “runs” the first day of the environment
(starting with a set of hard-coded initial conditions:
temperatures are initialized to 23C and zone humidity ratios
are initialized to the outdoor humidity ratio) until the
loads/temperature convergence tolerance values are satisfied
(next two fields) or until it reaches “maximum number of
warmup days”. Note that setting the convergence tolerance
values too loose will cause the program to be satisfied too
early and you may not get the results you expect from the
actual simulation.
This value represents the number at which the loads values
must agree before “convergence” is reached. Loads tolerance
value is a fraction of the load.
Field:
Temperature Convergence Tolerance Value[LINK]
This value represents the number at which the zone
temperatures must agree (from previous iteration) before
“convergence” is reached. (Units for this field is delta
C).
Convergence of the simultaneous heat balance/HVAC solution
is reached when either the loads or temperature criterion is
satisfied.
All tolerances have units so the temperature tolerance is
in degrees C (or degrees K) and the loads tolerance is in
Watts. Both tolerances work the same way, just one looks at
temperatures and one looks at heating and cooling loads. After
the second warm-up day, the program compares the maximum
temperature experienced in a space with the maximum
temperature from the previous day. If those two temperatures
are within the tolerance, then it has passed the first warm-up
check.
It does a similar comparison with lowest temperatures
experience within all the zones. If the current simulation day
and the previous day values are within the tolerance, then it
has passed the second warm-up check. Similar things are done
with the loads tolerance and the maximum heating and cooling
loads that are experienced within the spaces. Those are
compared individually to the values for the previous day. If
they are both in tolerance, then the simulation has passed the
third and fourth warm-up check. The simulation stays in the
warm-up period until ALL FOUR checks have been passed. See
Engineering Reference and Output Details document for further
explanation and outputs.
Please note–other “convergence tolerance” inputs are
required for certain HVAC equipment (unit ventilator, unit
heater, window AC, etc.). The purpose and units of these
parameters are different from “load convergence tolerance” and
“temperature convergence tolerance” in the BUILDING
object.
Setting this value determines how EnergyPlus treats beam
solar radiation and reflectances from exterior surfaces that
strike the building and, ultimately, enter the zone. There are
five choices: MinimalShadowing,
FullExterior and
FullInteriorAndExterior, FullExteriorWithReflections,
FullInteriorAndExteriorWithReflections.
MinimalShadowing
In this case, there is no exterior shadowing except from
window and door reveals. All beam solar radiation entering the
zone is assumed to fall on the floor, where it is absorbed
according to the floor’s solar absorptance. Any reflected by
the floor is added to the transmitted diffuse radiation, which
is assumed to be uniformly distributed on all interior
surfaces. If no floor is present in the zone, the incident
beam solar radiation is absorbed on all interior surfaces
according to their absorptances. The zone heat balance is then
applied at each surface and on the zone’s air with the
absorbed radiation being treated as a flux on the surface.
FullExterior,
FullExteriorWithReflections
In this case, shadow patterns on exterior surfaces caused
by detached shading, wings, overhangs, and exterior surfaces
of all zones are computed. As for MinimalShadowing, shadowing
by window and door reveals is also calculated. Beam solar
radiation entering the zone is treated as for MinimalShadowing
– All beam solar radiation entering the zone is assumed to
fall on the floor, where it is absorbed according to the
floor’s solar absorptance. Any reflected by the floor is added
to the transmitted diffuse radiation, which is assumed to be
uniformly distributed on all interior surfaces. If no floor is
present in the zone, the incident beam solar radiation is
absorbed on all interior surfaces according to their
absorptances. The zone heat balance is then applied at each
surface and on the zone’s air with the absorbed radiation
being treated as a flux on the surface.
This is the same as FullExterior except that instead of
assuming all transmitted beam solar falls on the floor the
program calculates the amount of beam radiation falling on
each surface in the zone, including floor, walls and windows,
by projecting the sun’s rays through the exterior windows,
taking into account the effect of exterior shadowing surfaces
and window shading devices.
If this option is used, you should be sure that the
surfaces of the zone totally enclose a space. This can be
determined by viewing the eplusout.dxf file
with a program like AutoDesk’s Volo View Express. You should
also be sure that the zone is convex.
Examples of convex and non-convex zones are shown in Figure.
The most common non-convex zone is an L-shaped zone. (A formal
definition of convex is that any straight line passing through
the zone intercepts at most two surfaces.) If the zone’s
surfaces do not enclose a space or if the zone is not convex
you should use Solar Distribution =
FullExterior instead of
FullInteriorAndExterior.
If you use FullInteriorAndExterior the
program will also calculate how much beam radiation falling on
the inside of an exterior window (from other windows in the
zone) is absorbed by the window, how much is reflected back
into the zone, and how much is transmitted to the outside. In
this calculation the effect of a shading device, if present,
is accounted for.
Illustration of Convex and
Non-convex Zones
Reflection calculations
Note: Using the reflection calculations can be very
time-consuming. Even error-prone. As a possible alleviation,
you can use the Output:Diagnostics,DoNotMirrorDetachedShading;
in many cases to get past a fatal error.
If using reflections, the program calculates beam and sky
solar radiation that is reflected from exterior surfaces and
then strikes the building. These reflecting surfaces fall into
three categories:
These surfaces can have diffuse and/or specular
(beam-to-beam) reflectance values that are specified with the
ShadingProperty:Reflectance
object which specifies those parameters. They have a default
value of .2 for both visible and diffuse reflection.
2) Exterior building surfaces. In this
case one section of the building reflects solar radiation onto
another section (and vice-versa). See Figure.
The building surfaces are assumed to be diffusely
reflecting if they are opaque (walls, for example) and
specularly reflecting if they are windows or glass doors. The
reflectance values for opaque surfaces are calculated by the
program from the Solar Absorptance and Visible Absorptance
values of the outer material layer of the surface’s
construction (ref: Material
object properties). The reflectance values for windows and
glass doors are calculated by the program from the reflectance
properties of the individual glass layers that make up
surface’s construction assuming no shading device is present
and taking into account inter-reflections among the layers
(ref: Window
Properties).
3) The ground surface. Reflection from the
ground is calculated even if reflections option is not used;l
but then the ground plane is considered unobstructed, i.e.,
the shadowing of the ground by the building itself or by
obstructions such as neighboring buildings is ignored.
Shadowing by the building itself or neighboring buildings is
taken into account when the “with reflections” option is used
but then the “view factor to ground” is NOT used. This is
shown in Figure.
Solar reflection from shadowing
surfaces. Solid arrows are beam solar radiation; dashed arrows
are diffuse solar radiation. (a) Diffuse reflection of beam
solar radiation from the top of an overhang. (b) Diffuse
reflection of sky solar radiation from the top of an overhang.
(c) Beam-to-beam (specular) reflection from the façade of an
adjacent highly-glazed building represented by a vertical
shadowing surface.
Solar reflection from building
surfaces onto other building surfaces. In this example beam
solar reflects from a vertical section of the building onto a
roof section. The reflection from the window is specular. The
reflection from the wall is diffuse.
Shadowing from building affects
beam solar reflection from the ground. Beam-to-diffuse
reflection from the ground onto the building occurs only for
sunlit areas, A and C, not from shaded area, B.
This field specifies the number of “warmup” days that might
be used in the simulation before “convergence” is achieved.
The default number, 25, is usually more than sufficient for
this task; however, some complex buildings (with complex
constructions) may require more days. If you enter less than
25 as a maximum, that is the number of maximum warmup days
that will be used. An error message will occur when the
simulation “runs” out of days and has not converged:
CheckWarmupConvergence: Loads Initialization, Zone = "MAIN ZONE" did not converge after 30 warmup days.
See Warmup Convergence Information in .eio file for details
..Environment(SizingPeriod) = "DENVER CENTENNIAL GOLDEN N ANN CLG 1% CONDNS DB = >MWB"
..Max Temp Comparison = 2.06E-002 vs Temperature Convergence Tolerance = 0.50 – Pass Convergence
..Min Temp Comparison = 5.95E-003 vs Temperature Convergence Tolerance = 0.50 – Pass Convergence
..Max Cool Load Comparison = 9.5082E-002 vs Loads Convergence Tolerance = 5.00E-002 – Fail Convergence
As noted in the message, there will be more information in
the .eio file. (Refer to Output Details document as well for
examples.)
You may be able to increase the Maximum Number of Warmup
Days and get convergence, but some anomalous buildings may
still not converge. Simulation proceeds for x warmup days
until “convergence” is reached (see the discussion under the
Temperature Convergence Tolerance Value field in this object,
just above).
This field specifies the minimum number of “warmup” days
before EnergyPlus will check if it has achieved convergence
and can thus start simulating the particular environment
(design day, annual run) in question. Research into the
minimum number of warmup days indicates that 6 warmup days is
generally enough on the minimum end of the spectrum to avoid
false predictions of convergence and thus to produce enough
temperature and flux history to start EnergyPlus simulation.
This was based on a study that used the benchmark reference
buildings. It also was observed that convergence performance
improved when the number of warmup days increased. As a
result, the default value for the minimum warmup days has been
set to 6. Users should decrease this number only if they have
knowledge that a specific file converges more quickly than 6
days. Users may wish to increase the value in certain
situations when, based on the output variables described in
the Output Details document, it is determined that EnergyPlus
has not converged. While this parameter should be less than
the previous parameter, a value greater than the value entered
in the field “Maximum Number of Warmup Days” above may be used
when users wish to increase warmup days more than the previous
field. In this particular case, the previous field will be
automatically reset to the value entered in this field and
EnergyPlus will run exactly the number of warmup days
specified in this field.
An example from an IDF:
Building,
PSI HOUSE DORM AND OFFICES, !- Name
36.87000, !- North Axis {deg}
Suburbs, !- Terrain
0.04, !- Loads Convergence Tolerance Value
0.4000000, !- Temperature Convergence Tolerance Value {deltaC}
FullInteriorAndExterior, !- Solar Distribution
40, !- Maximum Number of Warmup Days
6; !- Minimum Number of Warmup Days
This input object is used control the choice of models used
for surface convection at the inside face of all the heat
transfer surfaces in the model. This object sets the selection
for convection correlations in a global way. The Zone
Inside Convection Algorithm input field in the Zone
object may be used to selectively override this value on a
zone-by-zone basis. Further, individual surfaces can refine
the choice by each surface or surface lists – see object SurfaceProperty:ConvectionCoefficients
and object SurfaceProperty:ConvectionCoefficients:MultipleSurface.
The model specified in this field is the default algorithm
for the inside face all the surfaces.. The key choices are
Simple, TARP,
CeilingDiffuser, and
AdaptiveConvectionAlgorithm.
The Simple model applies constant heat
transfer coefficients depending on the surface
orientation.
The TARP model correlates the heat
transfer coefficient to the temperature difference for various
orientations. This model is based on flat plate
experiments.
The CeilingDiffuser model is a mixed and
forced convection model for ceiling diffuser configurations.
The model correlates the heat transfer coefficient to the air
change rate for ceilings, walls and floors. These correlations
are based on experiments performed in an isothermal room with
a cold ceiling jet. To avoid discontinuities in surface heat
transfer rate calculations, all of correlations have been
extrapolated beyond the lower limit of the data set (3 ACH) to
a natural convection limit that is applied during the hours
when the system is off.
The AdaptiveConvectionAlgorithm model is
an dynamic algorithm that organizes a large number of
different convection models and automatically selects the one
that best applies. The adaptive convection algorithm can also
be customized using the SurfaceConvectionAlgorithm:Inside:AdaptiveModelSelections
input object. These models are explained in detail in the
EnergyPlus Engineering Reference Document.
Various exterior convection models may be selected for
global use. The optional Zone
Outside Convection Algorithm input field in the Zone
object may be used to selectively override this value on a
zone-by-zone basis. Further, individual surfaces can refine
the choice by each surface or surface lists – see object SurfaceProperty:ConvectionCoefficients
and object SurfaceProperty:ConvectionCoefficients:MultipleSurface.
The available key choices are
SimpleCombined, TARP,
MoWiTT, DOE-2, and
AdaptiveConvectionAlgorithm.
The Simple convection model applies heat
transfer coefficients depending on the roughness and
windspeed. This is a combined heat transfer coefficient that
includes radiation to sky, ground, and air. The correlation is
based on Figure,
Page 25.1 (Thermal and Water Vapor Transmission Data), 2001
ASHRAE Handbook of Fundamentals. Note that if
Simple is chosen here or in the Zone
field and a SurfaceProperty:ConvectionCoefficients
object attempts to override the calculation with a different
choice, the action will still be one of combined calculation.
To change this, you must select one of the other methods for
the global default.
All other convection models apply heat transfer
coefficients depending on the roughness, windspeed, and
terrain of the building’s location. These are convection
only heat transfer coefficients; radiation heat transfer
coefficients are calculated automatically by the program.
The TARP algorithm was developed for the
TARP software and combines natural and wind-driven convection
correlations from laboratory measurements on flat plates.
The DOE-2 and MoWiTT were
derived from field measurements. DOE-2 uses a correlation from
measurements by Klems and Yazdanian for rough surfaces. MoWitt
uses a correlation from measurements by Klems and Yazdanian
for smooth surfaces and, therefore, is most appropriate for
windows (see SurfaceProperty:ConvectionCoefficients:MultipleSurface
for how to apply to only windows).
The AdaptiveConvectionAlgorithm model is
an dynamic algorithm that organizes a large number of
different convection models and automatically selects the one
that best applies. The adaptive convection algorithm can also
be customized using the SurfaceConvectionAlgorithm:Outside:AdaptiveModelSelections
input object. All algorithms are described more fully in the
Engineering Reference.
The default is DOE-2.
Note that when the surface is wet (i.e. it is raining and
the surface is exposed to wind) then the convection
coefficient appears as a very large number (1000) and the
surface is exposed to the Outdoor Wet-bulb Temperature rather
than the Outdoor Dry-bulb Temperature.
The HeatBalanceAlgorithm
object provides a way to select what type of heat and moisture
transfer algorithm will be used for calculating the
performance of the building’s surface assemblies. This input
controls the overall algorithm used for all the surfaces
unless one or more of the
SurfaceProperty:HeatTransferAlgorithm:* objects are used to
alter the selection for particular surfaces.
Four values are allowed to select which solution will be
used.
The ConductionTransferFunction
selection is a sensible heat only solution and does not take
into account moisture storage or diffusion in the construction
elements.
The
MoisturePenetrationDepthConductionTransferFunction
selection is a sensible heat diffusion and an inside surface
moisture storage algorithm that also needs additional moisture
material property information. Sometimes, this is referred to
as the Effective Moisture Penetration Depth or EMPD. See the
moisture material property object for additional information
and description of outputs:
Advanced/Research usage:The
ConductionFiniteDifference selection is a
sensible heat only solution and does not take into account
moisture storage or diffusion in the construction elements.
This solution technique uses a 1-D finite difference solution
in the construction elements. Outputs for the surfaces are
described with the material property objects. The Conduction
Finite Difference (aka CondFD) property objects are:
Advanced/Research usage: The
CombinedHeatAndMoistureFiniteElement is a
coupled heat and moisture transfer and storage solution. The
solution technique uses a one dimensional finite difference
solution in the construction elements and requires further
material properties described in the Heat and Moisture
Transfer material properties objects. Outputs from the
algorithm are described with these objects. The Heat and
Moisture Transfer property objects are:
This field is a bit “advanced”. It should only be used when
the simulation fails AND you cannot determine a cause for the
failure. That is, you receive an error similar to:
** Severe ** Temperature out of bounds (202.91) for surface = Wall1
** ~~~ ** in Zone = Zone01
** ~~~ ** Occurrence info = NEW YORK CITY NY SUMMER, 07/21 16:00 - 16:01
** ~~~ ** A temperature out of bounds problem can be caused by several things. The user
** ~~~ ** should check the weather environment, the level of internal gains with respect
** ~~~ ** to the zone, and the thermal properties of their materials among other things.
** ~~~ ** A common cause is a building with no thermal mass -- all materials with
** ~~~ ** Regular-R definitions.
And, after careful perusal, you cannot find a solution as
suggested in the error description. You may then want to enter
a higher number than the default for this field.
Field:
Minimum Surface Convection Heat Transfer Coefficient
Value[LINK]
This optional field is used to set an overall minimum for
the value of the coefficient for surface convection heat
transfer (Hc) in W/m2-K. A minimum is necessary for numerical
robustness because some correlations for Hc can result in zero
values and create numerical problems. This field can be used
to support specialized validation testing to suppress
convection heat transfer and to investigate the implications
of different minimum Hc values. The default is 0.1.
Field:
Maximum Surface Convection Heat Transfer Coefficient
Value[LINK]
This optional field is used to set an overall maximum for
the value of the coefficient for surface convection heat
transfer (Hc) in W/m2-K. High Hc values are used in EnergyPlus
to approximate fixed surface temperature boundary conditions.
This field can be used to alter the accepted range of
user-defined Hc values.
This object is used to control the behavior of the
Conduction Finite Difference algorithm for surface heat
transfer. The settings are global and affect how the model
behaves for all the surfaces.
This field determines the solution scheme used by the
Conduction Finite Difference model. There are two options
CrankNicholsonSecondOrder and FullyImplicitFirstOrder. The
CrankNicholsonSecondOrder scheme is second order in time and
may be faster. But it can be unstable over time when boundary
conditions change abruptly and severely. The
FullyImplicitFirstOrder scheme is first order in time and is
more stable over time. But it may be slower. The default is
FullyImplicitFirstOrder when ConductionFiniteDifference is
selected as the Heat Balance Algorithm.
This field controls how the model determines spatial
discretization, or the count of nodes across each material
layer in the construction. The model calculates the nominal
distance associated with a node, \(\Delta x\), using
\[\Delta x = \sqrt {C\alpha
\Delta t}\]
Where
\(\alpha\) is the thermal
diffusivity of the material layer, in m\(^{2}\)/s
\(\Delta t\) is the length
of the timestep in seconds.
C is a constant set by this field.
The default is 3. Typical values are from 1 to 3. Lower
values for this constant lead to more nodes and finer-grained
space discretization.
The finite difference solver includes under-relaxation for
improved stability for interactions with the other surfaces.
This input field can optionally be used to modify the starting
value for the relaxation factor. Larger numbers may solve
faster, while smaller numbers may be more stable. The default
is 1.0. If the program detects numerical instability, it may
reduce the value entered here to something lower and more
stable.
Field:
Inside Face Surface Temperature Convergence Criteria[LINK]
The surface heat balance model at the inside face has a
numerical solver that uses a convergence parameter for a
maximum allowable differences in surface temperature. This
field can optionally be used to modify this convergence
criteria. The default value is 0.002 and was selected for
stability. Lower values may further increase stability at the
expense of longer runtimes, while higher values may decrease
runtimes but lead to possible instabilities. The units are in
degrees Celsius.
An example IDF object follows.
HeatBalanceSettings:ConductionFiniteDifference,
FullyImplicitFirstOrder, !- Difference Scheme
3.0, !- Space Discretization Constant
1.0, !- Relaxation Factor
0.002; !- Inside Face Surface Temperature Convergence Criteria
The ZoneAirHeatBalanceAlgorithm
object provides a way to select what type of solution
algorithm will be used to calculate zone air temperatures and
humidity ratios. This object is an optional object. If the
default algorithm is used, this object is not required in an
input file.
Three choices are allowed to select which solution
algorithm will be used. The
ThirdOrderBackwardDifference selection is the
default selection and uses the third order finite difference
approximation to solve the zone air energy and moisture
balance equations. The AnalyticalSolution
selection uses the integration approach to solve the zone air
energy and moisture balance equations. The
EulerMethod selection uses the first order
finite backward difference approximation to solve the zone air
energy and moisture balance equations.
The ZoneAirContaminantBalance
object provides a way to select which contaminant type will be
simulated. Although carbon dioxide is not considered as an
indoor contaminant but it is used as an indicator of indoor
air quality in buildings. From modeling point of view
EnergyPlus treats carbon dioxide as a type of contaminant. In
addition to carbon dioxide, a generic contaminant type model
was also added. This object is optional, only required in the
input data file if the user wishes to model contaminant
concentration levels as part of their simulation.
Input is Yes or No. The default is No. If Yes, simulation
of carbon dioxide concentration levels will be performed. If
No, simulation of carbon dioxide concentration levels will not
be performed.
This field specifies the name of a schedule that contains
outdoor air carbon dioxide level values in units of ppm. One
source of monthly average CO\(_{2}\) levels in the atmosphere
is available at NOAA’s
website or via ftp.
Input is Yes or No. The default is No. If Yes, simulation
of generic contaminant concentration levels will be performed.
If No, simulation of generic contaminant concentration levels
will not be performed.
This output variable represents the carbon dioxide
concentration level in parts per million (ppm) for each zone.
This is calculated and reported from the Correct step in the
Zone
Air Contaminant Predictor-Corrector module.
Zone
Air CO2 Internal Gain Volume Flow Rate [m3/s][LINK]
This is the rate of carbon dioxide added to a zone from all
types of sources or sinks, in m\(^{3}\)/s.
The following output variable is available when Generic
Contaminant Concentration = Yes.
HVAC,Average,Zone Generic Air Contaminant Generation Volume
Flow Rate [m3/s]
HVAC,Average,Zone Air Generic Air Contaminant Concentration
[ppm]
Zone
Air Generic Air Contaminant Concentration [ppm][LINK]
This output variable represents the generic contaminant
concentration level in parts per million (ppm) for each zone.
This is calculated and reported from the Correct step in the
Zone
Air Contaminant Predictor-Corrector module.
Zone
Generic Air Contaminant Generation Volume Flow Rate
[m3/s][LINK]
This is the rate of generic air contaminant added (or
subtracted) to a zone from all types of sources or sinks.
This object is used to control some details of EnergyPlus’s
solar, shadowing and daylighting models. There are two basic
methods available for the calculations. In order to speed up
the calculations, shadowing calculations (sun position, etc.)
for the default method are performed over a period of days.
Note that this value may be very important for determining the
amount of sun entering your building and by inference the
amount of cooling or heating load needed for maintaining the
building. Though termed “shadowing” calculations, it in affect
determines the sun position for a particular day in a weather
file period simulation. (Each design day will use the date of
the design day object). Even though weather file data contains
the amount of solar radiation, the internal calculation of sun
position will govern how that affects various parts of the
building. By default, the calculations are done for every 20
days throughout a weather run period; an average solar
position is chosen and the solar factors (such as sunlit areas
of surfaces) remain the same for that number of days. When
more integrated calculations are needed for controlling
dynamic windows or shades, a second method is available where
solar calculations are performed at each zone timestep.
This field is used to control how the solar, shading, and
daylighting models are calculated with respect to the time of
calculations during the simulation. The default and fastest
method is selected using the keyword
AverageOverDaysInFrequency. A more detailed and slower method
can be selected using the keyword TimestepFrequency. The
TimestepFrequency method must be used for modeling dynamic
fenestration and shading surfaces.
This numeric field will cause the shadowing calculations to
be done periodically using the number in the field as the
number of days in each period. This field is only used if the
default method AverageOverDaysInFrequency is used in the
previous field. Using this field will allow you to synchronize
the shadowing calculations with changes in shading devices.
Using the default of 20 days in each period is the average
number of days between significant changes in solar position
angles. For these shadowing calculations, an “average” (over
the time period) of solar angles, position, equation of time
are also used.
Field:
Maximum Figures in Shadow Overlap Calculations[LINK]
This numeric field will allow you to increase the number of
figures in shadow overlaps. Due to the shadowing algorithm,
the number of shadows in a figure may grow quite large even
with fairly reasonable looking structures. Of course, the
inclusion of more allowed figures will increase calculation
time. Likewise, too few figures may not result in as accurate
calculations as you desire.
This is an advanced feature. Prior to V7, the internal
polygon clipping method was a special case of the
Weiler-Atherton method. Now, two options are available:
SutherlandHodgman (default) and
ConvexWeilerAtherton. Theoretically,
Sutherland-Hodgman is a simpler algorithm but it works well in
cases where receiving surfaces (of shadows) are non-convex.
The Weiler-Atherton implementation is only accurate where both
casting and receiving surfaces are convex. Warnings/severe
errors are displayed when necessary. More details on polygon
clipping are contained in the Engineering Reference.
Two choices are available here: SimpleSkyDiffuseModeling
and DetailedSkyDiffuseModeling.
SimpleSkyDiffuseModeling (default) performs a
one-time calculation for sky diffuse properties. This has
implications if you have shadowing surfaces with changing
transmittance (i.e. not all opaque or not all transparent)
during the year. The program checks to see if this might be
the case and automatically selects
DetailedSkyDiffuseModeling if the shading
transmittance varies. Even if the transmittance doesn’t vary
and the option for detailed modeling is used, that option is
retained (though it will increase execution time) because you
may be using EMS to vary the transmittance. When the detailed
modeling is done, there will be a warning posted if the
Calculation Frequency (above) is > 1.
In general (and you should also read the previous field
description), if shadowing surfaces are used with the
transmittance property, the user should be careful to
synchronize this calculation with the scheduled occurrence of
the transmittance (if any) (or use 1, which will be the most
accurate but will cause more time in the calculations).
This field applies to the method called
“AverageOverDaysInFrequency.” When the method called
“DetailedTimestepIntegration” is used the diffuse sky modeling
always uses DetailedSkyDiffuseModeling.
Examples of this object in IDF: (note this object must be
unique in an IDF)
Note that the use of “1” in the examples is NOT the same as
using DetailedTimestepIntegration – “1” causes daily
calculation of the sun position variables but does not change
the shadowing calculations more frequently than daily.
Sometimes, messages only confuse users – especially new
users. Likewise, sometimes certain output variables exist for
only a certain condition but some take them at face
value/name. Some features may be very important but under
certain instances cause problems. Thus, we have added the
diagnostic output object to be able to turn
on or off certain messages, variables, and features depending
on conditions.
Both fields of the Output:Diagnostics
command can accept all the applicable keys. More than one
object may be entered.
DisplayAllWarnings – use this to get all
warnings (except the developer warnings
“DisplayZoneAirHeatBalanceOffBalance”). This key sets all
other display warning values to on.
DisplayExtraWarnings – use this to get all
extra warnings. An example of an extra warning is when a user
enters a ceiling height or volume with the Zone
object and EnergyPlus calculates something significantly
different based on the entered zone geometry.
DisplayUnusedSchedules – use this to have
the unused schedules (by name) listed at the end of the
simulation.
DisplayUnusedObjects – use this to have
unused (orphan) objects (by name) listed at the end of the
simulation.
DisplayAdvancedReportVariables – use this
to be able to use certain advanced output variables where the
name may be misleading and you need to understand the concepts
or reasons for use. If you put in this field, then you will be
able to report on these features. They are noted in the
descriptions of objects or output variables.
DisplayZoneAirHeatBalanceOffBalance – this
is a developer diagnostic which you can turn on, if you
desire.
DoNotMirrorDetachedShading – use this to
turn off the automatic mirroring of detached shading surfaces.
These surfaces are automatically mirrored so that the user
does not need to worry about facing direction of the surface
and the shading surface will shade the building as
appropriate.
DoNotMirrorAttachedShading – use this to
turn off the automatic mirroring of attached shading surfaces.
These surfaces are automatically mirrored so that the user
does not need to worry about facing direction of the surface
and the shading surface will shade the building as
appropriate. Attached shading surfaces include Shading:Overhang,Shading:Overhang:Projection,Shading:Fin,Shading:Fin:Projection,
and Shading:Zone:Detailed.
DisplayWeatherMissingDataWarnings – use
this to turn on the missing data warnings from the read of the
weather file.
ReportDuringWarmup – use this to allow
reporting during warmup days. This can show you exactly how
your facility is converging (or not) during the initial
“warmup” days of the simulation. Generally, only developers or
expert simulation users would need this kind of detail.
ReportDetailedWarmupConvergence – use this
to produce detailed reporting (essentially each warmup day for
each zone) for warmup convergence.
ReportDuringHVACSizingSimulation – use
this to allow controlling reporting to SQLite database during
sizing period simulations done for HVAC Sizing Simulation. The
regular reporting is done in the usual way. This can show
details of how advanced sizing adjustments were determined by
documenting how the systems operated when doing the
intermediate sizing periods. Depending on the number of
iterations performed for HVAC Sizing Simulation, there will be
a number of sets of results with each set containing all the
Sizing Periods.
There may be times when a particular input file requires
additional debugging. The Output:DebuggingData
object may be used to report all available node data (e.g.,
temperature, mass flow rate, set point, pressure, etc.). The
debug data is reported to the DBG text file. The debug file
first reports the node number and name, and then all available
node information for each zone time step (Ref. Timestep).
The 2 fields of the Output:DebuggingData
object can accept either a 1 (turn on) or any other value
(turn off). Only one object may be entered.
This field allows the debug data to be reported during the
warmup period. When a value of 1 is entered the data is
reported at all times, even during warmup. Any other value
(usually 0) disables “reporting at all time” and debug data is
only reported for each environment (RunPeriod or
SizingPeriod:DesignDay).
The Output:PreprocessorMessage
object can be used by preprocessor programs to EnergyPlus for
passing certain conditions/errors that might not be detected
by scripts executing the EnergyPlus system of programs. This
allows EnergyPlus to intercept problems and terminate
gracefully rather than the user having to track down the exact
conditions.
There is no reason for a user to enter an Output:PreprocessorMessage
object but you should encourage interface developers to use
this feature. More than one Output:PreprocessorMessage
objects may be entered. Of course, no preprocessor message
objects are necessary if there is no error information to be
passed.
The preprocessor name (e.g. EPMacro, ExpandObjects) is
entered here. Case is retained so that messages from
EnergyPlus look very similar to what a preprocessor would
produce.
This is the error severity. If Fatal, EnergyPlus will
terminate after showing all preprocessor messages.
Fields:
Message Line 1 through Message Line 10[LINK]
Each line is limited to 100 characters and an appropriate
message can be composed.
An IDF Example:
Output:PreprocessorMessage,
No Preprocessor Used, !- preprocessor name
Information, !- error severity
Illustrative Message, !- message line 1
No problems for processing; !- message line 2
And would appear in output:
Preprocessor = "No Preprocessor Used" has the following Information messages:
Illustrative Message
No problems for processing
This object is an advanced feature that can be used to
control the effective storage capacity of the zone.
Capacitance multipliers of 1.0 indicate the capacitance is
that of the (moist) air in the volume of the specified zone.
This multiplier can be increased if the zone air capacitance
needs to be increased for stability of the simulation or to
allow modeling higher or lower levels of damping of behavior
over time. The multipliers are applied to the base value
corresponding to the total capacitance for the zone’s volume
of air at current zone (moist) conditions.
This field is used to alter the effective heat capacitance
of the zone air volume. This affects the transient
calculations of zone air temperature. Values greater than 1.0
have the effect of smoothing or damping the rate of change in
the temperature of zone air from timestep to timestep. Note
that sensible heat capacity can also be modeled using internal
mass surfaces.
This field is used to alter the effective moisture
capacitance of the zone air volume. This affects the transient
calculations of zone air humidity ratio. Values greater than
1.0 have the effect of smoothing, or damping, the rate of
change in the water content of zone air from timestep to
timestep.
This field is used to alter the effective carbon dioxide
capacitance of the zone air volume. This affects the transient
calculations of zone air carbon dioxide concentration. Values
greater than 1.0 have the effect of smoothing or damping the
rate of change in the carbon dioxide level of zone air from
timestep to timestep.
This field is used to alter the effective generic
contaminant capacitance of the zone air volume. This affects
the transient calculations of zone air generic
contaminantconcentration. Values greater than 1.0 have the
effect of smoothing or damping the rate of change in the
generic contaminantlevel of zone air from timestep to
timestep.
This field is the name of the thermal zone (ref: Zone) and
attaches a particular zone capacitance multiplier to a thermal
zone or set of thermal zones in the building. When the ZoneList
option is used then capacity multiplier is applied to each of
the zones in the zone list.
The input for SimulationControl
allows the user to specify what kind of calculations a given
EnergyPlus simulation will perform. For instance the user may
want to perform one or more of the sizing calculations but not
proceed to an annual weather file simulation. Or the user
might have all flow rates and equipment sizes already
specified and desire an annual weather without any preceding
sizing calculations. Sizing runs, even for large projects, are
quickly run – they do not add much to the overall simulation
time. The SimulationControl
input allows all permutations of run selection by means of 5
yes/no inputs.
Only one SimulationControl object is permitted for each
EnergyPlus input file. While a SimulationControl is needed to
trigger sizing calculations, it is optional for other runs
(design days, run periods). The actions will still be shown in
the eplusout.eio file (see Output Details and Examples
Document).
Input is Yes or No. The default is No. Zone Sizing (see Sizing:Zone
object) performs a special calculation, using a theoretical
ideal zonal system, and determines the zone design heating and
cooling flow rates and loads, saving the results in the zone
sizing arrays.
Input is Yes or No. The default is No. System Sizing (see
Sizing:System
object) also performs a special calculation that, to
oversimplify, sums up the results of the zone sizing
calculation and saves the results in the system sizing arrays
for reporting on component size requirements. Thus, in order
to perform the system sizing calculations, the zone sizing
arrays need to be filled and hence the zone sizing
calculations must be performed in the same run. (This
requirement is enforced by the program).
Input is Yes or No. The default is No. Unlike Zone
and System Sizing, Plant Sizing does not use the Zone
or System sizing arrays. Plant Sizing uses the Sizing:Plant
object fields and data on the maximum component flow rates.
The data on component (such as coil) flow rates is saved and
made available to the Plant code whether or not component
autosizing is performed and whether or not zone sizing and/or
system sizing is performed. Therefore, you can specify Plant
Sizing without also specifying to do Zone
Sizing or System Sizing calculations.
Input is Yes or No. The default is Yes. Yes implies that
the simulation will be run on all the included SizingPeriod
objects (i.e., SizingPeriod:DesignDay,SizingPeriod:WeatherFileDays,
and SizingPeriod:WeatherFileConditionType). Note that each
SizingPeriod object constitutes an “environment” and warmup
convergence (see earlier topic under the Building
object) will occur for each.
Field:
Run Simulation for Weather File Run Periods[LINK]
Input is Yes or No. The default is Yes. Yes implies the
simulation will be run on all the included RunPeriod
objects. Note that each RunPeriod
object constitutes an “environment” and warmup convergence
(see earlier topic under the Building
object) will occur for each.
Field:
Do HVAC Sizing Simulation for Sizing Periods[LINK]
This field is optional. It can be used to enable certain
advanced sizing calculations that rely on simulating the
sizing periods to collect information. This is currently only
applicable when sizing plant loops using the sizing option
called Coincident.
Field:
Maximum Number of HVAC Sizing Simulation Passes[LINK]
This field is optional and is only used if the previous
field is set to Yes. The HVAC Sizing Simulation approach can
use iteration to improve sizing calculations. Each iteration
is a Sizing Pass. This field is used to manually place an
upper limit the number of passes that the sizing algorithms
can use.
An IDF example:
SimulationControl,
No, !- Do Zone Sizing Calculation
No, !- Do System Sizing Calculation
No, !- Do Plant Sizing Calculation
Yes, !- Run Simulation for Sizing Periods
Yes, !- Run Simulation for Weather File Run Periods
No, !- Do HVAC Sizing Simulation for Sizing Periods
2; !- Maximum Number of HVAC Sizing Simulation Passes
A custom meter allows the user to group variables or meters
onto a virtual meter that can be used just like a normal meter
created by EnergyPlus. For consistency, the items being
grouped must all be similar. A Meter:Custom
cannot reference another Meter:Custom.
A fuel type should be specified for the meter. All
assignments to this meter will be checked to assure that the
same fuel type is used. Additionally, this may be used in
other objects (such as the Demand Limiting). Valid choices for
this field are:
Electricity
NaturalGas
PropaneGas
FuelOil#1
FuelOil#2
Coal
Diesel
Gasoline
Water
Generic
OtherFuel1
OtherFuel2
Fuel types are generally self-explanatory. Generic is
included for convenience when a custom meter is defined that
doesn’t quite fit the “fuel” categories. See the examples
below.
The rest of the object is filled with parameters of the key
name/output variable or meter names. When a meter name is
used, the key name field is left blank.
A key name field is used when the following field specifies
an output variable. If the field is left blank, then all the
output variables in the following field are assigned to the
meter.
This field must be a valid output variable name or a valid
meter name. If a Meter:Custom
references another Meter:Custom
it will generate a warning and not product any output.
The decrement custom meter is very similar to the custom
meter specification but additionally allows a predefined meter
to be used as the “source” meter and the remaining items
subtract from that predefined meter.
A fuel type should be specified for the meter. All
assignments to this meter will be checked to assure that the
same fuel type is used. Additionally, this may be used in
other objects (such as the Demand Limiting). Valid choices for
this field are:
This name specifies the meter that will be used as the main
source for the decrement custom meter. The remainder of the
fields are subtracted from the value of this meter to create
the meter value named above. The Source Meter is not changed
in any way by including this custom meter.
The rest of the object is filled with parameters of the key
name/output variable or meter names. When a meter name is
used, the key name field is left blank.
A key name field is used when the following field specifies
an output variable. If the field is left blank, then all the
output variables in the following field are assigned to the
meter.
This field must be a valid output variable name or a valid
meter name. Additionally, it must be contained on the Source
Meter. Note that, if an error occurs, only the Variable in
error will show – confusing things if what was entered was a
meter name.
Details of the Meter:Custom/Meter:CustomDecrement are shown
on the Meter Details file.
In the following examples, the custom meters are set up to
illustrate the capabilities of custom meters. Custom meter
“MyGeneralLights” duplicates the
InteriorLights:Electricity meter. Custom meter
“MyBuildingElectric” duplicates the
Electricity:Building meter (by specifying that meter). Custom
Meter (Decrement) “MyBuildingOther” uses the
Electricity:Building meter as the source meter and subtracts
out the values for MyGeneralLights (aka
InteriorLights:Electricity). The resultant value for the
MyBuildingOther meter should be equal to the value for the
meters Electricity:Building – InteriorLights:Electricity.
Meter:Custom,
MyGeneralLights, !- Name
Electricity, !- Fuel Type
SPACE1-1, !- Key Name 1
Lights Electric Energy, !- Output Variable or Meter Name 1
SPACE2-1, !- Key Name 2
Lights Electric Energy, !- Output Variable or Meter Name 2
SPACE3-1, !- Key Name 3
Lights Electric Energy, !- Output Variable or Meter Name 3
SPACE4-1, !- Key Name 4
Lights Electric Energy, !- Output Variable or Meter Name 4
SPACE5-1, !- Key Name 5
Lights Electric Energy; !- Output Variable or Meter Name 5
Meter:Custom,
MyBuildingElectric, !- Name
Electricity, !- Fuel Type
, !- Key Name #1
Electricity:Building; !- Output Variable or Meter Name #1
Meter:CustomDecrement,
MyBuildingOther, !- Name
Electricity, !- Fuel Type
Electricity:Building, !- Source Meter Name
, !- Key Name #1
MyGeneralLights; !- Output Variable or Meter Name #1
For an example of “generic” fuel type, one might put the Building
Infiltration Heat Loss & Heat Gain on a set of custom
meters:
Meter:Custom,
Building Infiltration Heat Loss, !- Name
Generic, !- Fuel Type
*, !- Key Name 1
Zone Infiltration Total Heat Loss Energy; !- Output Variable Name 1
Meter:Custom,
Building Infiltration Heat Gain, !- Name
Generic, !- Fuel Type
*, !- Key Name 1
Zone Infiltration Total Heat Gain Energy; !- Output Variable Name 1
One can then report these values the same way one reports
other standard meters.
Group – Simulation Parameters[LINK]
This group of objects influences the simulation in various ways.
Version[LINK]
Inputs[LINK]
Field: Version Identifier[LINK]
The Version object allows you to enter the proper version that your IDF was created for. This is checked against the current version of EnergyPlus and a Severe error issued (non-terminating) if it does not match the current version string. Note that versions are often significant and there is no guarantee that the older file will run in the newer versions of the program. See IDF Version Updater (Auxiliary Programs Document) for methods of changing the older files to newer versions.
Timestep[LINK]
Inputs[LINK]
Field: Number of Timesteps per Hour[LINK]
The Timestep object specifies the “basic” timestep for the simulation. The value entered here is usually known as the Zone Timestep. This is used in the Zone Heat Balance Model calculation as the driving timestep for heat transfer and load calculations. The value entered here is the number of timesteps to use within an hour. Longer length timesteps have lower values for Number of Timesteps per Hour. For example a value of 6 entered here directs the program to use a zone timestep of 10 minutes and a value of 60 means a 1 minute timestep. The user’s choice for Number of Timesteps per Hour must be evenly divisible into 60; the allowable choices are 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, and 60.
The choice made for this field has important implications for modeling accuracy and the overall time it takes to run a simulation. Here are some considerations when choosing a value:
The solution technique used in EnergyPlus has been designed to be stable with zone timesteps of up to sixty minutes (Number Timesteps in Hour = 1). However, 60 minutes is considered a “long” timestep and it should only be used in rare occasions where there is no HVAC system, accuracy is not a concern, and short run times are critical. Such long timesteps are not recommended to use because simulation results are more accurate for shorter timesteps, of say 10 minutes or less (Number of Timesteps per Hour of 6 or more). Shorter zone timesteps improve the numerical solution of the Zone Heat Balance Model because they improve how models for surface temperature and zone air temperature are coupled together. Longer timesteps introduce more lag and lead to more a dampened dynamic response.
Simulation run time increases with shorter timesteps or larger values for Number of Timesteps per Hour. The effect varies with the nature of the model. The user can test out different values on their particular model to understand the implications for his or her particular case. Sometimes large models with multizone HVAC and Plant systems execute nearly as fast with 15 minute timesteps as with 60 minute timesteps because fewer iterations are required in the system modeling since the prior timestep’s results are close to the final outcome of next timestep.
The weather data files usually have 60-minute (or hourly) data. However, it does not follow that this should be used as the basis for choosing the zone timestep because:
EnergyPlus carefully interpolates the weather data between data points for use at shorter timesteps. This is discussed in a later section: Weather Data Hourly Interpolation
Many aspects of a model have time scales that differ from the that of the weather data. A goal of the modeling is to predict how the building will respond to the weather. However, the building’s response is not governed by the time scale that the weather data are available at, but rather the time scales of the dynamic performance of the thermal envelope as well as things like schedules for internal gains, thermostats, and equipment availability.
If the model will include calculating the cost of electricity, then the user should be aware that many electric utility tariffs base charges on demand windows of a specified length of time. If the choice of Number of Timesteps per Hour is not consistent with the demand window, then unexpected results may be obtained. For reasonable prediction of the maximum rates for electricity use for in calculating demand charges, the length of the zone timestep needs to be consistent with the tariff’s demand window. The following table lists what values are consistent with various demand windows.
There is also second type of timestep inside EnergyPlus that is known as the System Timestep. This is a variable-length timestep that governs the driving timestep for HVAC and Plant system modeling. The user cannot directly control the system timestep (except by use of the ConvergenceLimits object). When the HVAC portion of the simulation begins its solution for the current zone timestep, it uses the zone timestep as its maximum length but then can reduce the timestep, as necessary, to improve the solution. The technical details of the approach are explained in the Engineering Documentation under “Integrated Solution Manager”.
Users can see the system timestep used if they select the “detailed” frequency option on an HVAC output variable (e.g. Zone Air Temperature). To contrast, the “Zone” variables will only be reported on the zone timestep (e.g. Zone Mean Air Temperature).
And, the IDF example:
Suggested defaults are 4 for non-HVAC simulations, 6 for simulations with HVAC, 20 is the minimum for ConductionFiniteDifference and HeatAndMoistureFiniteElement simulations. Green roof (ref: Material:RoofVegetation) also may require more timesteps.
Note that hourly data (such as outdoor conditions expressed by Design Days or Weather data) are interpolated to the Zone Timestep. This is discussed in a later section: Weather Data Hourly Interpolation
ConvergenceLimits[LINK]
This item is an “advanced” feature that should be used only with caution. It is specifically included to assist some users “speed up” calculations while not overly compromising accuracy. The user must judge for him/herself whether the reduced run time is useful.
Inputs[LINK]
Field: Minimum System Timestep[LINK]
Usually the minimum system timestep is allowed to vary from the zone timestep (as maximum) to a minimum timestep of 1 minute during certain system calculations. This might be when the system turns on or off, for example. Entering 0 in this field sets the minimum system timestep to be the same as the zone timestep. Otherwise the units of the field are minutes. It’s probably a good idea to have any minimum entered be a divisor of the zone timestep.
Field: Maximum HVAC Iterations[LINK]
The HVAC Manager will iterate to a solution or up to a set number of iterations. If not “converged”, then a warning error appears:
In order to reduce time used in simulating your building, you may choose to enter a lesser number than the default of 20 for the maximum number of iterations to be used. Or, you may wish to enter a bigger number for certain buildings. To get more information printed with a “max iteration” message, you need to enter a “Output:Diagnostics, DisplayExtraWarnings;” command (which may also generate other warnings than just this one).
Field: Minimum Plant Iterations[LINK]
The plant system modeling includes a solver that iterates within a single HVAC manager iteration. This input field and the next one provide some control over how the plant solver iterates. This field sets a minimum threshold for plant iterations. The default for this field is the value “2” which indicates that a minimum of two full plant model interations will be performed every time plant is called by the HVAC manager. For faster performance with simple plant systems, this input field could be set to the value “1”. For complicated plant systems that present difficulties to solve, this value may need to be set higher to ensure accuracy but at the expense of speed. Complicated plant systems include those with several interconnected loops, sizing miss-matches such that plant components are starved of flow compared to their desired flow, heat recovery systems, and thermal load following onsite generators.
Field: Maximum Plant Iterations[LINK]
The plant system solver iterates within a single HVAC manager iteration. This input field and the previous one provide some control over how the plant model iterates. This field sets a maximum limit for plant interations. The default for this field is the value “8” which indicates that the plant solver will exit after having completed eight full iterations. This value can be raised for better accuracy with complex plants or lowered for faster speed with simple plants. The output variable called “Plant Solver Sub Iteration Count” (typically reported at the “detailed” frequency) is useful for understanding how many plant solver iterations are actually being used during a particular simulation. The lower limit of the value for this field is “2.”
Use in an IDF:
Building[LINK]
The Building object describes parameters that are used during the simulation of the building. There are necessary correlations between the entries for this object and some entries in the Site:WeatherStation and Site:HeightVariation objects, specifically the Terrain field.
Inputs[LINK]
Field: Building Name[LINK]
Building name is specified for output convenience.
Field: North Axis[LINK]
The Building North Axis is specified relative to true North. Buildings frequently do not line up with true north. For convenience, one may enter surfaces in a “regular” coordinate system and then shift them via the use of the North Axis. The value is specified in degrees from “true north” (clockwise is positive).
The figure below shows how the building north axis can be rotated to correspond with one of the major axes of an actual building. The relevance of this field is described more completely under “GlobalGeometryRules”; in particular, the value of “North Axis” is ignored if a coordinate system other than “relative” is used.
Field: Terrain[LINK]
The site’s terrain affects how the wind hits the building – as does the building height. In addition, the external conduction method usually has its own parameters for the calculation. Please see the Engineering Documentation, External Conduction section for particulars. The legal values for this field are shown in the following table.
Warmup Convergence[LINK]
The following two fields along with the minimum and maximum number of warmup days (also in this object) define the user specified criteria for when EnergyPlus will “converge” at each environment (each sizing period or run period set as Yes in the SimulationControl object). EnergyPlus “runs” the first day of the environment (starting with a set of hard-coded initial conditions: temperatures are initialized to 23C and zone humidity ratios are initialized to the outdoor humidity ratio) until the loads/temperature convergence tolerance values are satisfied (next two fields) or until it reaches “maximum number of warmup days”. Note that setting the convergence tolerance values too loose will cause the program to be satisfied too early and you may not get the results you expect from the actual simulation.
Field: Loads Convergence Tolerance Value[LINK]
This value represents the number at which the loads values must agree before “convergence” is reached. Loads tolerance value is a fraction of the load.
Field: Temperature Convergence Tolerance Value[LINK]
This value represents the number at which the zone temperatures must agree (from previous iteration) before “convergence” is reached. (Units for this field is delta C).
Convergence of the simultaneous heat balance/HVAC solution is reached when either the loads or temperature criterion is satisfied.
All tolerances have units so the temperature tolerance is in degrees C (or degrees K) and the loads tolerance is in Watts. Both tolerances work the same way, just one looks at temperatures and one looks at heating and cooling loads. After the second warm-up day, the program compares the maximum temperature experienced in a space with the maximum temperature from the previous day. If those two temperatures are within the tolerance, then it has passed the first warm-up check.
It does a similar comparison with lowest temperatures experience within all the zones. If the current simulation day and the previous day values are within the tolerance, then it has passed the second warm-up check. Similar things are done with the loads tolerance and the maximum heating and cooling loads that are experienced within the spaces. Those are compared individually to the values for the previous day. If they are both in tolerance, then the simulation has passed the third and fourth warm-up check. The simulation stays in the warm-up period until ALL FOUR checks have been passed. See Engineering Reference and Output Details document for further explanation and outputs.
Please note–other “convergence tolerance” inputs are required for certain HVAC equipment (unit ventilator, unit heater, window AC, etc.). The purpose and units of these parameters are different from “load convergence tolerance” and “temperature convergence tolerance” in the BUILDING object.
Field: Solar Distribution[LINK]
Setting this value determines how EnergyPlus treats beam solar radiation and reflectances from exterior surfaces that strike the building and, ultimately, enter the zone. There are five choices: MinimalShadowing, FullExterior and FullInteriorAndExterior, FullExteriorWithReflections, FullInteriorAndExteriorWithReflections.
MinimalShadowing
In this case, there is no exterior shadowing except from window and door reveals. All beam solar radiation entering the zone is assumed to fall on the floor, where it is absorbed according to the floor’s solar absorptance. Any reflected by the floor is added to the transmitted diffuse radiation, which is assumed to be uniformly distributed on all interior surfaces. If no floor is present in the zone, the incident beam solar radiation is absorbed on all interior surfaces according to their absorptances. The zone heat balance is then applied at each surface and on the zone’s air with the absorbed radiation being treated as a flux on the surface.
FullExterior, FullExteriorWithReflections
In this case, shadow patterns on exterior surfaces caused by detached shading, wings, overhangs, and exterior surfaces of all zones are computed. As for MinimalShadowing, shadowing by window and door reveals is also calculated. Beam solar radiation entering the zone is treated as for MinimalShadowing – All beam solar radiation entering the zone is assumed to fall on the floor, where it is absorbed according to the floor’s solar absorptance. Any reflected by the floor is added to the transmitted diffuse radiation, which is assumed to be uniformly distributed on all interior surfaces. If no floor is present in the zone, the incident beam solar radiation is absorbed on all interior surfaces according to their absorptances. The zone heat balance is then applied at each surface and on the zone’s air with the absorbed radiation being treated as a flux on the surface.
FullInteriorAndExterior, FullInteriorAndExteriorWithReflections
This is the same as FullExterior except that instead of assuming all transmitted beam solar falls on the floor the program calculates the amount of beam radiation falling on each surface in the zone, including floor, walls and windows, by projecting the sun’s rays through the exterior windows, taking into account the effect of exterior shadowing surfaces and window shading devices.
If this option is used, you should be sure that the surfaces of the zone totally enclose a space. This can be determined by viewing the eplusout.dxf file with a program like AutoDesk’s Volo View Express. You should also be sure that the zone is convex. Examples of convex and non-convex zones are shown in Figure. The most common non-convex zone is an L-shaped zone. (A formal definition of convex is that any straight line passing through the zone intercepts at most two surfaces.) If the zone’s surfaces do not enclose a space or if the zone is not convex you should use Solar Distribution = FullExterior instead of FullInteriorAndExterior.
If you use FullInteriorAndExterior the program will also calculate how much beam radiation falling on the inside of an exterior window (from other windows in the zone) is absorbed by the window, how much is reflected back into the zone, and how much is transmitted to the outside. In this calculation the effect of a shading device, if present, is accounted for.
Reflection calculations
Note: Using the reflection calculations can be very time-consuming. Even error-prone. As a possible alleviation, you can use the Output:Diagnostics,DoNotMirrorDetachedShading; in many cases to get past a fatal error.
If using reflections, the program calculates beam and sky solar radiation that is reflected from exterior surfaces and then strikes the building. These reflecting surfaces fall into three categories:
1) Shadowing surfaces. These are surfaces like overhangs or neighboring buildings entered with Shading:Site, Shading:Building, Shading:Site:Detailed, Shading:Building:Detailed, Shading:Overhang, Shading:Overhang:Projection, Shading:Fin, Shading:Fin:Projection or Shading:Zone:Detailed objects. See Figure.
These surfaces can have diffuse and/or specular (beam-to-beam) reflectance values that are specified with the ShadingProperty:Reflectance object which specifies those parameters. They have a default value of .2 for both visible and diffuse reflection.
2) Exterior building surfaces. In this case one section of the building reflects solar radiation onto another section (and vice-versa). See Figure.
The building surfaces are assumed to be diffusely reflecting if they are opaque (walls, for example) and specularly reflecting if they are windows or glass doors. The reflectance values for opaque surfaces are calculated by the program from the Solar Absorptance and Visible Absorptance values of the outer material layer of the surface’s construction (ref: Material object properties). The reflectance values for windows and glass doors are calculated by the program from the reflectance properties of the individual glass layers that make up surface’s construction assuming no shading device is present and taking into account inter-reflections among the layers (ref: Window Properties).
3) The ground surface. Reflection from the ground is calculated even if reflections option is not used;l but then the ground plane is considered unobstructed, i.e., the shadowing of the ground by the building itself or by obstructions such as neighboring buildings is ignored. Shadowing by the building itself or neighboring buildings is taken into account when the “with reflections” option is used but then the “view factor to ground” is NOT used. This is shown in Figure.
Field: Maximum Number of Warmup Days[LINK]
This field specifies the number of “warmup” days that might be used in the simulation before “convergence” is achieved. The default number, 25, is usually more than sufficient for this task; however, some complex buildings (with complex constructions) may require more days. If you enter less than 25 as a maximum, that is the number of maximum warmup days that will be used. An error message will occur when the simulation “runs” out of days and has not converged:
As noted in the message, there will be more information in the .eio file. (Refer to Output Details document as well for examples.)
You may be able to increase the Maximum Number of Warmup Days and get convergence, but some anomalous buildings may still not converge. Simulation proceeds for x warmup days until “convergence” is reached (see the discussion under the Temperature Convergence Tolerance Value field in this object, just above).
Field: Minimum Number of Warmup Days[LINK]
This field specifies the minimum number of “warmup” days before EnergyPlus will check if it has achieved convergence and can thus start simulating the particular environment (design day, annual run) in question. Research into the minimum number of warmup days indicates that 6 warmup days is generally enough on the minimum end of the spectrum to avoid false predictions of convergence and thus to produce enough temperature and flux history to start EnergyPlus simulation. This was based on a study that used the benchmark reference buildings. It also was observed that convergence performance improved when the number of warmup days increased. As a result, the default value for the minimum warmup days has been set to 6. Users should decrease this number only if they have knowledge that a specific file converges more quickly than 6 days. Users may wish to increase the value in certain situations when, based on the output variables described in the Output Details document, it is determined that EnergyPlus has not converged. While this parameter should be less than the previous parameter, a value greater than the value entered in the field “Maximum Number of Warmup Days” above may be used when users wish to increase warmup days more than the previous field. In this particular case, the previous field will be automatically reset to the value entered in this field and EnergyPlus will run exactly the number of warmup days specified in this field.
An example from an IDF:
SurfaceConvectionAlgorithm:Inside[LINK]
This input object is used control the choice of models used for surface convection at the inside face of all the heat transfer surfaces in the model. This object sets the selection for convection correlations in a global way. The Zone Inside Convection Algorithm input field in the Zone object may be used to selectively override this value on a zone-by-zone basis. Further, individual surfaces can refine the choice by each surface or surface lists – see object SurfaceProperty:ConvectionCoefficients and object SurfaceProperty:ConvectionCoefficients:MultipleSurface.
Inputs[LINK]
Field: Algorithm[LINK]
The model specified in this field is the default algorithm for the inside face all the surfaces.. The key choices are Simple, TARP, CeilingDiffuser, and AdaptiveConvectionAlgorithm.
The Simple model applies constant heat transfer coefficients depending on the surface orientation.
The TARP model correlates the heat transfer coefficient to the temperature difference for various orientations. This model is based on flat plate experiments.
The CeilingDiffuser model is a mixed and forced convection model for ceiling diffuser configurations. The model correlates the heat transfer coefficient to the air change rate for ceilings, walls and floors. These correlations are based on experiments performed in an isothermal room with a cold ceiling jet. To avoid discontinuities in surface heat transfer rate calculations, all of correlations have been extrapolated beyond the lower limit of the data set (3 ACH) to a natural convection limit that is applied during the hours when the system is off.
The AdaptiveConvectionAlgorithm model is an dynamic algorithm that organizes a large number of different convection models and automatically selects the one that best applies. The adaptive convection algorithm can also be customized using the SurfaceConvectionAlgorithm:Inside:AdaptiveModelSelections input object. These models are explained in detail in the EnergyPlus Engineering Reference Document.
The default is TARP.
IDF Example:
SurfaceConvectionAlgorithm:Outside[LINK]
Various exterior convection models may be selected for global use. The optional Zone Outside Convection Algorithm input field in the Zone object may be used to selectively override this value on a zone-by-zone basis. Further, individual surfaces can refine the choice by each surface or surface lists – see object SurfaceProperty:ConvectionCoefficients and object SurfaceProperty:ConvectionCoefficients:MultipleSurface.
Inputs[LINK]
Field: Algorithm[LINK]
The available key choices are SimpleCombined, TARP, MoWiTT, DOE-2, and AdaptiveConvectionAlgorithm.
The Simple convection model applies heat transfer coefficients depending on the roughness and windspeed. This is a combined heat transfer coefficient that includes radiation to sky, ground, and air. The correlation is based on Figure, Page 25.1 (Thermal and Water Vapor Transmission Data), 2001 ASHRAE Handbook of Fundamentals. Note that if Simple is chosen here or in the Zone field and a SurfaceProperty:ConvectionCoefficients object attempts to override the calculation with a different choice, the action will still be one of combined calculation. To change this, you must select one of the other methods for the global default.
All other convection models apply heat transfer coefficients depending on the roughness, windspeed, and terrain of the building’s location. These are convection only heat transfer coefficients; radiation heat transfer coefficients are calculated automatically by the program.
The TARP algorithm was developed for the TARP software and combines natural and wind-driven convection correlations from laboratory measurements on flat plates.
The DOE-2 and MoWiTT were derived from field measurements. DOE-2 uses a correlation from measurements by Klems and Yazdanian for rough surfaces. MoWitt uses a correlation from measurements by Klems and Yazdanian for smooth surfaces and, therefore, is most appropriate for windows (see SurfaceProperty:ConvectionCoefficients:MultipleSurface for how to apply to only windows).
The AdaptiveConvectionAlgorithm model is an dynamic algorithm that organizes a large number of different convection models and automatically selects the one that best applies. The adaptive convection algorithm can also be customized using the SurfaceConvectionAlgorithm:Outside:AdaptiveModelSelections input object. All algorithms are described more fully in the Engineering Reference.
The default is DOE-2.
Note that when the surface is wet (i.e. it is raining and the surface is exposed to wind) then the convection coefficient appears as a very large number (1000) and the surface is exposed to the Outdoor Wet-bulb Temperature rather than the Outdoor Dry-bulb Temperature.
IDF Example:
HeatBalanceAlgorithm[LINK]
The HeatBalanceAlgorithm object provides a way to select what type of heat and moisture transfer algorithm will be used for calculating the performance of the building’s surface assemblies. This input controls the overall algorithm used for all the surfaces unless one or more of the SurfaceProperty:HeatTransferAlgorithm:* objects are used to alter the selection for particular surfaces.
Inputs[LINK]
Field: Algorithm[LINK]
Four values are allowed to select which solution will be used.
The ConductionTransferFunction selection is a sensible heat only solution and does not take into account moisture storage or diffusion in the construction elements.
The MoisturePenetrationDepthConductionTransferFunction selection is a sensible heat diffusion and an inside surface moisture storage algorithm that also needs additional moisture material property information. Sometimes, this is referred to as the Effective Moisture Penetration Depth or EMPD. See the moisture material property object for additional information and description of outputs:
MaterialProperty:MoisturePenetrationDepth:Settings
Advanced/Research usage:The ConductionFiniteDifference selection is a sensible heat only solution and does not take into account moisture storage or diffusion in the construction elements. This solution technique uses a 1-D finite difference solution in the construction elements. Outputs for the surfaces are described with the material property objects. The Conduction Finite Difference (aka CondFD) property objects are:
MaterialProperty:PhaseChange
MaterialProperty:VariableThermalConductivity
Advanced/Research usage: The CombinedHeatAndMoistureFiniteElement is a coupled heat and moisture transfer and storage solution. The solution technique uses a one dimensional finite difference solution in the construction elements and requires further material properties described in the Heat and Moisture Transfer material properties objects. Outputs from the algorithm are described with these objects. The Heat and Moisture Transfer property objects are:
MaterialProperty:HeatAndMoistureTransfer:Settings
MaterialProperty:HeatAndMoistureTransfer:SorptionIsotherm
MaterialProperty:HeatAndMoistureTransfer:Suction
MaterialProperty:HeatAndMoistureTransfer:Redistribution
MaterialProperty:HeatAndMoistureTransfer:Diffusion
MaterialProperty:HeatAndMoistureTransfer:ThermalConductivity
Field: Surface Temperature Upper Limit[LINK]
This field is a bit “advanced”. It should only be used when the simulation fails AND you cannot determine a cause for the failure. That is, you receive an error similar to:
And, after careful perusal, you cannot find a solution as suggested in the error description. You may then want to enter a higher number than the default for this field.
Field: Minimum Surface Convection Heat Transfer Coefficient Value[LINK]
This optional field is used to set an overall minimum for the value of the coefficient for surface convection heat transfer (Hc) in W/m2-K. A minimum is necessary for numerical robustness because some correlations for Hc can result in zero values and create numerical problems. This field can be used to support specialized validation testing to suppress convection heat transfer and to investigate the implications of different minimum Hc values. The default is 0.1.
Field: Maximum Surface Convection Heat Transfer Coefficient Value[LINK]
This optional field is used to set an overall maximum for the value of the coefficient for surface convection heat transfer (Hc) in W/m2-K. High Hc values are used in EnergyPlus to approximate fixed surface temperature boundary conditions. This field can be used to alter the accepted range of user-defined Hc values.
And, a default IDF example
HeatBalanceSettings:ConductionFiniteDifference[LINK]
This object is used to control the behavior of the Conduction Finite Difference algorithm for surface heat transfer. The settings are global and affect how the model behaves for all the surfaces.
Inputs[LINK]
Field: Difference Scheme[LINK]
This field determines the solution scheme used by the Conduction Finite Difference model. There are two options CrankNicholsonSecondOrder and FullyImplicitFirstOrder. The CrankNicholsonSecondOrder scheme is second order in time and may be faster. But it can be unstable over time when boundary conditions change abruptly and severely. The FullyImplicitFirstOrder scheme is first order in time and is more stable over time. But it may be slower. The default is FullyImplicitFirstOrder when ConductionFiniteDifference is selected as the Heat Balance Algorithm.
Field: Space Discretization Constant[LINK]
This field controls how the model determines spatial discretization, or the count of nodes across each material layer in the construction. The model calculates the nominal distance associated with a node, \(\Delta x\), using
\[\Delta x = \sqrt {C\alpha \Delta t}\]
Where
\(\alpha\) is the thermal diffusivity of the material layer, in m\(^{2}\)/s
\(\Delta t\) is the length of the timestep in seconds.
C is a constant set by this field.
The default is 3. Typical values are from 1 to 3. Lower values for this constant lead to more nodes and finer-grained space discretization.
Field: Relaxation Factor[LINK]
The finite difference solver includes under-relaxation for improved stability for interactions with the other surfaces. This input field can optionally be used to modify the starting value for the relaxation factor. Larger numbers may solve faster, while smaller numbers may be more stable. The default is 1.0. If the program detects numerical instability, it may reduce the value entered here to something lower and more stable.
Field: Inside Face Surface Temperature Convergence Criteria[LINK]
The surface heat balance model at the inside face has a numerical solver that uses a convergence parameter for a maximum allowable differences in surface temperature. This field can optionally be used to modify this convergence criteria. The default value is 0.002 and was selected for stability. Lower values may further increase stability at the expense of longer runtimes, while higher values may decrease runtimes but lead to possible instabilities. The units are in degrees Celsius.
An example IDF object follows.
ZoneAirHeatBalanceAlgorithm[LINK]
The ZoneAirHeatBalanceAlgorithm object provides a way to select what type of solution algorithm will be used to calculate zone air temperatures and humidity ratios. This object is an optional object. If the default algorithm is used, this object is not required in an input file.
Inputs[LINK]
Field: Algorithm[LINK]
Three choices are allowed to select which solution algorithm will be used. The ThirdOrderBackwardDifference selection is the default selection and uses the third order finite difference approximation to solve the zone air energy and moisture balance equations. The AnalyticalSolution selection uses the integration approach to solve the zone air energy and moisture balance equations. The EulerMethod selection uses the first order finite backward difference approximation to solve the zone air energy and moisture balance equations.
And, a default IDF example is shown below:
ZoneAirContaminantBalance[LINK]
The ZoneAirContaminantBalance object provides a way to select which contaminant type will be simulated. Although carbon dioxide is not considered as an indoor contaminant but it is used as an indicator of indoor air quality in buildings. From modeling point of view EnergyPlus treats carbon dioxide as a type of contaminant. In addition to carbon dioxide, a generic contaminant type model was also added. This object is optional, only required in the input data file if the user wishes to model contaminant concentration levels as part of their simulation.
Inputs[LINK]
Field: Carbon Dioxide Concentration[LINK]
Input is Yes or No. The default is No. If Yes, simulation of carbon dioxide concentration levels will be performed. If No, simulation of carbon dioxide concentration levels will not be performed.
Field: Outdoor Carbon Dioxide Schedule Name[LINK]
This field specifies the name of a schedule that contains outdoor air carbon dioxide level values in units of ppm. One source of monthly average CO\(_{2}\) levels in the atmosphere is available at NOAA’s website or via ftp.
Field: Generic Contaminant Concentration[LINK]
Input is Yes or No. The default is No. If Yes, simulation of generic contaminant concentration levels will be performed. If No, simulation of generic contaminant concentration levels will not be performed.
Field: Outdoor Generic Contaminant Schedule Name[LINK]
This field specifies the name of a schedule that contains outdoor air generic contaminant level values in units of ppm.
An IDF example:
Outputs[LINK]
The following output variables are available when Carbon Dioxide Concentration = Yes.
Zone Air CO2 Concentration [ppm][LINK]
This output variable represents the carbon dioxide concentration level in parts per million (ppm) for each zone. This is calculated and reported from the Correct step in the Zone Air Contaminant Predictor-Corrector module.
Zone Air CO2 Internal Gain Volume Flow Rate [m3/s][LINK]
This is the rate of carbon dioxide added to a zone from all types of sources or sinks, in m\(^{3}\)/s.
Outputs[LINK]
The following output variable is available when Generic Contaminant Concentration = Yes.
HVAC,Average,Zone Generic Air Contaminant Generation Volume Flow Rate [m3/s]
HVAC,Average,Zone Air Generic Air Contaminant Concentration [ppm]
Zone Air Generic Air Contaminant Concentration [ppm][LINK]
This output variable represents the generic contaminant concentration level in parts per million (ppm) for each zone. This is calculated and reported from the Correct step in the Zone Air Contaminant Predictor-Corrector module.
Zone Generic Air Contaminant Generation Volume Flow Rate [m3/s][LINK]
This is the rate of generic air contaminant added (or subtracted) to a zone from all types of sources or sinks.
ShadowCalculation[LINK]
This object is used to control some details of EnergyPlus’s solar, shadowing and daylighting models. There are two basic methods available for the calculations. In order to speed up the calculations, shadowing calculations (sun position, etc.) for the default method are performed over a period of days. Note that this value may be very important for determining the amount of sun entering your building and by inference the amount of cooling or heating load needed for maintaining the building. Though termed “shadowing” calculations, it in affect determines the sun position for a particular day in a weather file period simulation. (Each design day will use the date of the design day object). Even though weather file data contains the amount of solar radiation, the internal calculation of sun position will govern how that affects various parts of the building. By default, the calculations are done for every 20 days throughout a weather run period; an average solar position is chosen and the solar factors (such as sunlit areas of surfaces) remain the same for that number of days. When more integrated calculations are needed for controlling dynamic windows or shades, a second method is available where solar calculations are performed at each zone timestep.
Inputs[LINK]
Field: Calculation Method[LINK]
This field is used to control how the solar, shading, and daylighting models are calculated with respect to the time of calculations during the simulation. The default and fastest method is selected using the keyword AverageOverDaysInFrequency. A more detailed and slower method can be selected using the keyword TimestepFrequency. The TimestepFrequency method must be used for modeling dynamic fenestration and shading surfaces.
Field: Calculation Frequency[LINK]
This numeric field will cause the shadowing calculations to be done periodically using the number in the field as the number of days in each period. This field is only used if the default method AverageOverDaysInFrequency is used in the previous field. Using this field will allow you to synchronize the shadowing calculations with changes in shading devices. Using the default of 20 days in each period is the average number of days between significant changes in solar position angles. For these shadowing calculations, an “average” (over the time period) of solar angles, position, equation of time are also used.
Field: Maximum Figures in Shadow Overlap Calculations[LINK]
This numeric field will allow you to increase the number of figures in shadow overlaps. Due to the shadowing algorithm, the number of shadows in a figure may grow quite large even with fairly reasonable looking structures. Of course, the inclusion of more allowed figures will increase calculation time. Likewise, too few figures may not result in as accurate calculations as you desire.
Field: Polygon Clipping Algorithm[LINK]
This is an advanced feature. Prior to V7, the internal polygon clipping method was a special case of the Weiler-Atherton method. Now, two options are available: SutherlandHodgman (default) and ConvexWeilerAtherton. Theoretically, Sutherland-Hodgman is a simpler algorithm but it works well in cases where receiving surfaces (of shadows) are non-convex. The Weiler-Atherton implementation is only accurate where both casting and receiving surfaces are convex. Warnings/severe errors are displayed when necessary. More details on polygon clipping are contained in the Engineering Reference.
Field: Sky Diffuse Modeling Algorithm[LINK]
Two choices are available here: SimpleSkyDiffuseModeling and DetailedSkyDiffuseModeling. SimpleSkyDiffuseModeling (default) performs a one-time calculation for sky diffuse properties. This has implications if you have shadowing surfaces with changing transmittance (i.e. not all opaque or not all transparent) during the year. The program checks to see if this might be the case and automatically selects DetailedSkyDiffuseModeling if the shading transmittance varies. Even if the transmittance doesn’t vary and the option for detailed modeling is used, that option is retained (though it will increase execution time) because you may be using EMS to vary the transmittance. When the detailed modeling is done, there will be a warning posted if the Calculation Frequency (above) is > 1.
In general (and you should also read the previous field description), if shadowing surfaces are used with the transmittance property, the user should be careful to synchronize this calculation with the scheduled occurrence of the transmittance (if any) (or use 1, which will be the most accurate but will cause more time in the calculations).
This field applies to the method called “AverageOverDaysInFrequency.” When the method called “DetailedTimestepIntegration” is used the diffuse sky modeling always uses DetailedSkyDiffuseModeling.
Examples of this object in IDF: (note this object must be unique in an IDF)
Note that the use of “1” in the examples is NOT the same as using DetailedTimestepIntegration – “1” causes daily calculation of the sun position variables but does not change the shadowing calculations more frequently than daily.
Output:Diagnostics[LINK]
Sometimes, messages only confuse users – especially new users. Likewise, sometimes certain output variables exist for only a certain condition but some take them at face value/name. Some features may be very important but under certain instances cause problems. Thus, we have added the diagnostic output object to be able to turn on or off certain messages, variables, and features depending on conditions.
Both fields of the Output:Diagnostics command can accept all the applicable keys. More than one object may be entered.
Inputs[LINK]
Field: key1, key2[LINK]
Allowable choices are:
DisplayAllWarnings – use this to get all warnings (except the developer warnings “DisplayZoneAirHeatBalanceOffBalance”). This key sets all other display warning values to on.
DisplayExtraWarnings – use this to get all extra warnings. An example of an extra warning is when a user enters a ceiling height or volume with the Zone object and EnergyPlus calculates something significantly different based on the entered zone geometry.
DisplayUnusedSchedules – use this to have the unused schedules (by name) listed at the end of the simulation.
DisplayUnusedObjects – use this to have unused (orphan) objects (by name) listed at the end of the simulation.
DisplayAdvancedReportVariables – use this to be able to use certain advanced output variables where the name may be misleading and you need to understand the concepts or reasons for use. If you put in this field, then you will be able to report on these features. They are noted in the descriptions of objects or output variables.
DisplayZoneAirHeatBalanceOffBalance – this is a developer diagnostic which you can turn on, if you desire.
DoNotMirrorDetachedShading – use this to turn off the automatic mirroring of detached shading surfaces. These surfaces are automatically mirrored so that the user does not need to worry about facing direction of the surface and the shading surface will shade the building as appropriate.
DoNotMirrorAttachedShading – use this to turn off the automatic mirroring of attached shading surfaces. These surfaces are automatically mirrored so that the user does not need to worry about facing direction of the surface and the shading surface will shade the building as appropriate. Attached shading surfaces include Shading:Overhang, Shading:Overhang:Projection, Shading:Fin, Shading:Fin:Projection, and Shading:Zone:Detailed.
DisplayWeatherMissingDataWarnings – use this to turn on the missing data warnings from the read of the weather file.
ReportDuringWarmup – use this to allow reporting during warmup days. This can show you exactly how your facility is converging (or not) during the initial “warmup” days of the simulation. Generally, only developers or expert simulation users would need this kind of detail.
ReportDetailedWarmupConvergence – use this to produce detailed reporting (essentially each warmup day for each zone) for warmup convergence.
ReportDuringHVACSizingSimulation – use this to allow controlling reporting to SQLite database during sizing period simulations done for HVAC Sizing Simulation. The regular reporting is done in the usual way. This can show details of how advanced sizing adjustments were determined by documenting how the systems operated when doing the intermediate sizing periods. Depending on the number of iterations performed for HVAC Sizing Simulation, there will be a number of sets of results with each set containing all the Sizing Periods.
In IDF use:
Output:DebuggingData[LINK]
There may be times when a particular input file requires additional debugging. The Output:DebuggingData object may be used to report all available node data (e.g., temperature, mass flow rate, set point, pressure, etc.). The debug data is reported to the DBG text file. The debug file first reports the node number and name, and then all available node information for each zone time step (Ref. Timestep).
The 2 fields of the Output:DebuggingData object can accept either a 1 (turn on) or any other value (turn off). Only one object may be entered.
Inputs[LINK]
Field: Report Debugging Data[LINK]
This field turns on debug reporting when a value of 1 is entered. Any other value (usually 0) disables debug reporting.
Field: Report During Warmup[LINK]
This field allows the debug data to be reported during the warmup period. When a value of 1 is entered the data is reported at all times, even during warmup. Any other value (usually 0) disables “reporting at all time” and debug data is only reported for each environment (RunPeriod or SizingPeriod:DesignDay).
In IDF use:
Output:PreprocessorMessage[LINK]
The Output:PreprocessorMessage object can be used by preprocessor programs to EnergyPlus for passing certain conditions/errors that might not be detected by scripts executing the EnergyPlus system of programs. This allows EnergyPlus to intercept problems and terminate gracefully rather than the user having to track down the exact conditions.
There is no reason for a user to enter an Output:PreprocessorMessage object but you should encourage interface developers to use this feature. More than one Output:PreprocessorMessage objects may be entered. Of course, no preprocessor message objects are necessary if there is no error information to be passed.
Inputs[LINK]
Field: Preprocessor Name[LINK]
The preprocessor name (e.g. EPMacro, ExpandObjects) is entered here. Case is retained so that messages from EnergyPlus look very similar to what a preprocessor would produce.
Field: Error Severity[LINK]
This is the error severity. If Fatal, EnergyPlus will terminate after showing all preprocessor messages.
Fields: Message Line 1 through Message Line 10[LINK]
Each line is limited to 100 characters and an appropriate message can be composed.
An IDF Example:
And would appear in output:
ZoneCapacitanceMultiplier:ResearchSpecial[LINK]
This object is an advanced feature that can be used to control the effective storage capacity of the zone. Capacitance multipliers of 1.0 indicate the capacitance is that of the (moist) air in the volume of the specified zone. This multiplier can be increased if the zone air capacitance needs to be increased for stability of the simulation or to allow modeling higher or lower levels of damping of behavior over time. The multipliers are applied to the base value corresponding to the total capacitance for the zone’s volume of air at current zone (moist) conditions.
Inputs[LINK]
Field: Temperature Capacity Multiplier[LINK]
This field is used to alter the effective heat capacitance of the zone air volume. This affects the transient calculations of zone air temperature. Values greater than 1.0 have the effect of smoothing or damping the rate of change in the temperature of zone air from timestep to timestep. Note that sensible heat capacity can also be modeled using internal mass surfaces.
Field: Humidity Capacity Multiplier[LINK]
This field is used to alter the effective moisture capacitance of the zone air volume. This affects the transient calculations of zone air humidity ratio. Values greater than 1.0 have the effect of smoothing, or damping, the rate of change in the water content of zone air from timestep to timestep.
Field: Carbon Dioxide Capacity Multiplier[LINK]
This field is used to alter the effective carbon dioxide capacitance of the zone air volume. This affects the transient calculations of zone air carbon dioxide concentration. Values greater than 1.0 have the effect of smoothing or damping the rate of change in the carbon dioxide level of zone air from timestep to timestep.
Field: Generic Contaminant Capacity Multiplier[LINK]
This field is used to alter the effective generic contaminant capacitance of the zone air volume. This affects the transient calculations of zone air generic contaminantconcentration. Values greater than 1.0 have the effect of smoothing or damping the rate of change in the generic contaminantlevel of zone air from timestep to timestep.
Field: Name[LINK]
The name of the ZoneCapacitanceMultiplier:ResearchSpecial object.
Field: Zone or ZoneList Name[LINK]
This field is the name of the thermal zone (ref: Zone) and attaches a particular zone capacitance multiplier to a thermal zone or set of thermal zones in the building. When the ZoneList option is used then capacity multiplier is applied to each of the zones in the zone list.
SimulationControl[LINK]
The input for SimulationControl allows the user to specify what kind of calculations a given EnergyPlus simulation will perform. For instance the user may want to perform one or more of the sizing calculations but not proceed to an annual weather file simulation. Or the user might have all flow rates and equipment sizes already specified and desire an annual weather without any preceding sizing calculations. Sizing runs, even for large projects, are quickly run – they do not add much to the overall simulation time. The SimulationControl input allows all permutations of run selection by means of 5 yes/no inputs.
Only one SimulationControl object is permitted for each EnergyPlus input file. While a SimulationControl is needed to trigger sizing calculations, it is optional for other runs (design days, run periods). The actions will still be shown in the eplusout.eio file (see Output Details and Examples Document).
Inputs[LINK]
Field: Do Zone Sizing Calculation[LINK]
Input is Yes or No. The default is No. Zone Sizing (see Sizing:Zone object) performs a special calculation, using a theoretical ideal zonal system, and determines the zone design heating and cooling flow rates and loads, saving the results in the zone sizing arrays.
Field: Do System Sizing Calculation[LINK]
Input is Yes or No. The default is No. System Sizing (see Sizing:System object) also performs a special calculation that, to oversimplify, sums up the results of the zone sizing calculation and saves the results in the system sizing arrays for reporting on component size requirements. Thus, in order to perform the system sizing calculations, the zone sizing arrays need to be filled and hence the zone sizing calculations must be performed in the same run. (This requirement is enforced by the program).
Field: Do Plant Sizing Calculation[LINK]
Input is Yes or No. The default is No. Unlike Zone and System Sizing, Plant Sizing does not use the Zone or System sizing arrays. Plant Sizing uses the Sizing:Plant object fields and data on the maximum component flow rates. The data on component (such as coil) flow rates is saved and made available to the Plant code whether or not component autosizing is performed and whether or not zone sizing and/or system sizing is performed. Therefore, you can specify Plant Sizing without also specifying to do Zone Sizing or System Sizing calculations.
Field: Run Simulation for Sizing Periods[LINK]
Input is Yes or No. The default is Yes. Yes implies that the simulation will be run on all the included SizingPeriod objects (i.e., SizingPeriod:DesignDay, SizingPeriod:WeatherFileDays, and SizingPeriod:WeatherFileConditionType). Note that each SizingPeriod object constitutes an “environment” and warmup convergence (see earlier topic under the Building object) will occur for each.
Field: Run Simulation for Weather File Run Periods[LINK]
Input is Yes or No. The default is Yes. Yes implies the simulation will be run on all the included RunPeriod objects. Note that each RunPeriod object constitutes an “environment” and warmup convergence (see earlier topic under the Building object) will occur for each.
Field: Do HVAC Sizing Simulation for Sizing Periods[LINK]
This field is optional. It can be used to enable certain advanced sizing calculations that rely on simulating the sizing periods to collect information. This is currently only applicable when sizing plant loops using the sizing option called Coincident.
Field: Maximum Number of HVAC Sizing Simulation Passes[LINK]
This field is optional and is only used if the previous field is set to Yes. The HVAC Sizing Simulation approach can use iteration to improve sizing calculations. Each iteration is a Sizing Pass. This field is used to manually place an upper limit the number of passes that the sizing algorithms can use.
An IDF example:
Meter:Custom[LINK]
A custom meter allows the user to group variables or meters onto a virtual meter that can be used just like a normal meter created by EnergyPlus. For consistency, the items being grouped must all be similar. A Meter:Custom cannot reference another Meter:Custom.
Inputs[LINK]
Field: Name[LINK]
This is a user defined name for the custom meter. Names for custom meters cannot duplicate internal meter names.
Field: Fuel Type[LINK]
A fuel type should be specified for the meter. All assignments to this meter will be checked to assure that the same fuel type is used. Additionally, this may be used in other objects (such as the Demand Limiting). Valid choices for this field are:
Electricity
NaturalGas
PropaneGas
FuelOil#1
FuelOil#2
Coal
Diesel
Gasoline
Water
Generic
OtherFuel1
OtherFuel2
Fuel types are generally self-explanatory. Generic is included for convenience when a custom meter is defined that doesn’t quite fit the “fuel” categories. See the examples below.
Field: group(s) Key Name-Output Variable/Meter Name[LINK]
The rest of the object is filled with parameters of the key name/output variable or meter names. When a meter name is used, the key name field is left blank.
Field: Key Name #[LINK]
A key name field is used when the following field specifies an output variable. If the field is left blank, then all the output variables in the following field are assigned to the meter.
Field: Output Variable or Meter Name #[LINK]
This field must be a valid output variable name or a valid meter name. If a Meter:Custom references another Meter:Custom it will generate a warning and not product any output.
Meter:CustomDecrement[LINK]
The decrement custom meter is very similar to the custom meter specification but additionally allows a predefined meter to be used as the “source” meter and the remaining items subtract from that predefined meter.
Inputs[LINK]
Field: Name[LINK]
This is a user defined name for the custom meter. Names for custom meters cannot duplicate internal meter names.
Field: Fuel Type[LINK]
A fuel type should be specified for the meter. All assignments to this meter will be checked to assure that the same fuel type is used. Additionally, this may be used in other objects (such as the Demand Limiting). Valid choices for this field are:
Electricity
NaturalGas
PropaneGas
FuelOil#1
FuelOil#2
Coal
Diesel
Gasoline
Water
Generic
OtherFuel1
OtherFuel2
Field: Source Meter Name[LINK]
This name specifies the meter that will be used as the main source for the decrement custom meter. The remainder of the fields are subtracted from the value of this meter to create the meter value named above. The Source Meter is not changed in any way by including this custom meter.
Field: group(s) Key Name-Output Variable/Meter Name[LINK]
The rest of the object is filled with parameters of the key name/output variable or meter names. When a meter name is used, the key name field is left blank.
Field: Key Name #[LINK]
A key name field is used when the following field specifies an output variable. If the field is left blank, then all the output variables in the following field are assigned to the meter.
Field: Output Variable or Meter Name #[LINK]
This field must be a valid output variable name or a valid meter name. Additionally, it must be contained on the Source Meter. Note that, if an error occurs, only the Variable in error will show – confusing things if what was entered was a meter name.
Custom Meter Examples[LINK]
Details of the Meter:Custom/Meter:CustomDecrement are shown on the Meter Details file.
In the following examples, the custom meters are set up to illustrate the capabilities of custom meters. Custom meter “MyGeneralLights” duplicates the InteriorLights:Electricity meter. Custom meter “MyBuildingElectric” duplicates the Electricity:Building meter (by specifying that meter). Custom Meter (Decrement) “MyBuildingOther” uses the Electricity:Building meter as the source meter and subtracts out the values for MyGeneralLights (aka InteriorLights:Electricity). The resultant value for the MyBuildingOther meter should be equal to the value for the meters Electricity:Building – InteriorLights:Electricity.
For an example of “generic” fuel type, one might put the Building Infiltration Heat Loss & Heat Gain on a set of custom meters:
One can then report these values the same way one reports other standard meters.
Simulation Parameter Outputs[LINK]
These appear in the eplusout.eio file. For details of the reporting, please see the Output Details and Examples document.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.