The objective of this model is to calculate the convective
and radiant heat transfer from water baseboard heaters to the
people and the surfaces within a zone so that surface heat
balances can take into account the radiant heat transfer to
the surfaces and thus enhance the accuracy of thermal comfort
predictions within the space. The radiant heat gains are
distributed to the surfaces by fractions defined by user
input.
The name of the schedule (ref: Schedule) that denotes
whether the hot water baseboard heater unit can run during a
given time period. A schedule value equal to 0 denotes that
the unit must be off for that time period. A value greater
than 0 denotes that the unit is available to operate during
that time period. If this field is left blank, the schedule
has a value of 1 for all time periods.
This field is the rated average water temperature for the
baseboard heater which is published in the manufacturer’s
literature in degree Celsius. It typically ranges from 65.56°C
to 115.36°C in the I = B = R rating document while the lowest
allowable temperature is 32.22°C. The default value is
87.78°C. If the user does not enter this field, the default
value is assumed.
This field is the rated standard water flow rate in kg/s
which is published as part of the manufacturer’s literature.
It is used by the manufacturers when determining the rated
capacity (see next field). The default value is 0.063kg/s. If
it is blank or zero, the default values is assumed.
Enter the method used to determine the heating design
capacity or the method for scalable sizing. Input allowed is
either HeatingDesignCapacity,
CapacityPerFloorArea, and
FractionOfAutosizedHeatingCapacity. If this input
field is left blank or zero, then autosizing is assumed.
HeatingDesignCapacity means user specifies the
magnitude of heating capacity or the program calculates the
design heating capacity if autosize is specified.
CapacityPerFloorArea means the program calculates the
design heating capacity from user specified heating capacity
per floor area and floor area of the zone served by the
radiant baseboard unit.
FractionOfAutosizedHeatingCapacity means the program
calculates the design heating capacity from user specified
fraction and the auto-sized design heating capacity. The
default method is HeatingDesignCapacity.
This field is the radiant-convective water baseboard rated
capacity in watts at a rated water mass flow rate (see input
field Rated Mass Flow Rate). Almost all publications from
manufacturers indicate it as W/m (Btuh per linear foot). The
user thus must multiply it by the active length of the unit.
The active length is available in the literature.
Manufacturers are required to publish the difference between
active and total length of the unit (I = B = R rating for
boilers baseboard radiation, 2009).If it is blank or zero,
autosizing is assumed. Design day sizing run must be specified
for autosizing.
Field:
Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the rated heating capacity per unit floor area of
radiant-convective water baseboard unit in m3/s-m2. This field
is required field when the Heating Design Capacity Method is
CapacityPerFloorArea. The program calculates the
heating capacity from floor area of the zone served by the
radiant baseboard unit and the heating capacity per unit floor
area value specified by the user. This field may be left
blank.
Field:
Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized
heating capacity of radiant-convective water baseboard. This
input field is required when the Heating Design Capacity
Method is FractionOfAutosizedHeatingCapacity. The
program calculates the heating capacity from the design
autosized heating capacity and user specified fraction. Design
day sizing run must be specified. This field may be left
blank. Default value is 1.0.
This field is the control tolerance for the unit heating
output. The unit is controlled by matching the unit output to
the zone demand. For hot water baseboards, the model must be
numerically inverted to obtain a specified output. The
convergence tolerance is the error tolerance used to terminate
the numerical inversion procedure. Basically this is the
fraction:
This field specifies what fraction of the power input to
the baseboard heater is actually transferred to the space as
radiant heat. The fraction should be between 0 and 1. This is
the portion of the total power that is modeled as radiation.
The portion that is radiant heat transfer from the baseboard
heater is distributed to people and specific surfaces using
the remaining fields. Note that the sum of the fractions in
the remaining fields (people and surfaces) must equal 1.0 so
that all the radiant power is distributed properly. For more
information on the specification of this parameter, please see
the Engineering Reference for EnergyPlus.
Field:
Fraction of Radiant Energy Incident on People[LINK]
This field specifies the fraction of radiant portion of
heat transfer to the zone from the baseboard heater that is
incident directly on people within the space. This has an
impact on the predicted thermal comfort of the zone occupants.
Note that although this energy is “radiant” it is actually
modeled in the zone heat balance as convective energy (like an
internal gain). The basic assumption here is that most radiant
energy falling on people will most likely be rereleased to the
zone air by convection. This is a simplification of reality,
but it maintains the overall energy balance.
Field
Set: Surface Name, Fraction of Radiant Energy to Surface[LINK]
The following two items are repeated up to a maximum of 20
surface/fraction pairs. At least one surface/fraction pair
must appear in an input file. In other words, at least one
surface must be identified as a recipient of radiant energy
from the baseboard heater.
This field is the name of the first surface to which
radiant heat transfer from the baseboard heater is
distributed. Used in conjunction with the next field, it helps
to define the distribution of the radiant energy on the
surfaces within the zone. Note that up to 20 pairs of surface
names and corresponding fractions may be entered for a single
radiant heater system.
Field:
Fraction of Radiant Energy to Surface <x>[LINK]
This field is paired with the preceding surface name
(previous field) to define the fraction of radiant heat
transfer leaving the baseboard heater that is incident on a
particular surface. Users should take into account the
directionality of baseboard heaters and their location when
defining the value for this input field.
Note on Fraction of Radiant Energy Incident on
People
and to Surfaces
The radiant energy from the baseboard heater is defined by
the total energy input to the baseboard heater from the water
loop times the fraction radiant field shown above. This
radiant energy is distributed to surfaces and people using the
surface and fraction pairs and the fraction to people input by
the user. These fractions to people and surfaces must add up
to 1.0. In other words, in an input file, the following
relation should be maintained by the user input:
An example IDF for the water baseboard is shown below.
ZoneHVAC:Baseboard:RadiantConvective:Water,
SPACE2-1 Baseboard, !- Baseboard Name
ReheatCoilAvailSched, !- Availability Schedule Name
SPACE2-1 Zone Coil Water In Node, !- Inlet\_Node
SPACE2-1 Zone Coil Water Out Node, !- Outlet\_Node
76.67, !- Average Water Temperature {C}
0.063, !- Standard Water Mass Flow Rate {Kg/s}
HeatingDesignCapacity, !- Heating Design Capacity Method
3000.0, !- Heating Design Capacity{ W }
, !- Heating Design Capacity Per Floor Area{ W / m2 }
, !- Fraction of Autosized Heating Design Capacity{ -}
0.0013, !- Max Water Volumetric Flow Rate {m3/s}
0.001, !- Convergence Tolerance
0.3, !- Fraction radiant
0.3, !- Fraction of radiant energy incident on people
C2-1, !- Surface 1 Name
0.1, !- Fraction of radiant energy from heater distributed to surface 1
F2-1, !- Surface 2 Name
0.2, !- Fraction of radiant energy from heater distributed to surface 2
SB21, !- surface 3 Name
0.1, !- fraction of radiant energy from heater distributed to surface 3
SB23, !- surface 4 Name
0.1, !- fraction of radiant energy from heater distributed to surface 4
SB25, !- surface 5 Name
0.1, !- fraction of radiant energy from heater distributed to surface 5
WR-1, !- surface 6 Name
0.1; !- fraction of radiant energy from heater distributed to surface 6
This is the actual convective heat addition rate of the
baseboard to the zone in Watts. This value includes the heat
convected to the zone air from the baseboard unit, the heat
radiated to people in the zone from the baseboard unit, and
the additional convection from surfaces within the zone that
have been heated by radiation from the baseboard unit. This
value will be different from (and almost always less than) the
next field.
This is the actual, total convective energy transferred
directly and indirectly from the baseboard to the zone it is
serving in Joules. Direct convective heat transfer includes
the convective portion of the baseboard unit. Indirect
convective heat transfer includes heat radiated to people that
is then convected to the zone air and heat that is radiated to
the surfaces and then convected to the zone air.
The objective of this model is to calculate the convective
and radiant heat transfer from steam baseboard heaters to the
people and the surfaces within a zone so that surface heat
balances can take into account the radiant heat transfer to
the surfaces and thus enhance the accuracy of thermal comfort
predictions within the space. The radiant heat gains are
distributed to the surfaces by fractions defined by the user.
Users are requested to provide degree of sub cooling to
estimate the outlet conditions of the condensate.
The name of the schedule (ref: Schedule) that denotes
whether the steam baseboard heater unit can run during a given
time period. A schedule value equal to 0 denotes that the unit
must be off for that time period. A value greater than 0
denotes that the unit is available to operate during that time
period. If this field is left blank, the schedule has a value
of 1 for all time periods.
Enter the method used to determine the heating design
capacity for scalable sizing. Input allowed is either
HeatingDesignCapacity, CapacityPerFloorArea,
and FractionOfAutosizedHeatingCapacity. If this input
field is left blank or zero, then autosizing is assumed.
HeatingDesignCapacity means user specifies the
magnitude of maximum heating capacity or the program
calculates the maximum design heating capacity if autosize is
specified. CapacityPerFloorArea means the program
calculates the design heating capacity from user specified
heating capacity per floor area and floor area of the zone
served by the radiant baseboard unit.
FractionOfAutosizedHeatingCapacity means the program
calculates the design heating capacity from user specified
fraction and the auto-sized design heating capacity. The
default method is HeatingDesignCapacity.
This field is for the a radiant/convective steam baseboard
unit heating capacity in watts. This field can be autosized by
EnergyPlus. When the Heating Design Capacity Method is
HeatingDesignCapacity and this input is blank,
autosizing is assumed. Design day sizing run must be
specified.
Field:
Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2
of radiant/convective steam baseboard. This field is required
field when the Heating Design Capacity Method is
CapacityPerFloorArea. The program calculates the
heating capacity from floor area of the zone served by the
steam baseboard unit and the heating capacity per unit floor
area value specified by the user. This field may be left
blank.
Field:
Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized
heating capacity of a radiant/convective steam baseboard unit.
This input field is required when the Heating Design Capacity
Method is FractionOfAutosizedHeatingCapacity. The
program calculates the heating capacity from the design
autosized heat capacity and user specified fraction. Design
day sizing run must be specified. This field may be left
blank. Default value is 1.0.
This field is the temperature drop of the condensate in the
coil of the baseboard heater. The steam condensates in the
coil and changes the phase to the water, giving up the latent
heat of steam to the air in the steam to air heat exchanger.
The condensate due to the phase change then cools by certain
degree in the coil, so that this amount of heat is added to
the zone. The minimum value is 1.0° Celsius and default is
5.0° Celsius.
This field is the maximum steam volumetric flow rate in
m\(^{3}\)/s through the steam
baseboard heater. The steam volumetric flow rate is
calculated at 100C and 101325 Pa. It can be autosized by
EnergyPlus.
This field is the control tolerance for the unit heating
output. The unit is controlled by matching the unit output to
the zone demand. For steam baseboards, the model must be
numerically inverted to obtain a specified output. The
convergence tolerance is the error tolerance used to terminate
the numerical inversion procedure. Basically this is the
fraction:
This field specifies what fraction of the power input to
the baseboard heater is actually transferred to the space as
radiant heat. The fraction should be between 0 and 1. This is
the portion of the total power that is modeled as radiation.
The portion that is radiant heat transfer from the baseboard
heater is distributed to people and specific surfaces using
the remaining fields. Note that the sum of the fractions in
the remaining fields (people and surfaces) must equal 1.0 so
that all the radiant power is distributed properly.
Field:
Fraction of Radiant Energy Incident on People[LINK]
This field specifies the fraction of radiant portion of
heat transfer to the zone from the baseboard heater that is
incident directly on people within the space. This has an
impact on the predicted thermal comfort of the zone occupants.
Note that although this energy is “radiant” it is actually
modeled in the zone heat balance as convective energy (like an
internal gain). The basic assumption here is that most radiant
energy falling on people will most likely be rereleased to the
zone air by convection. This is a simplification of reality,
but it maintains the overall energy balance.
Field
Set: Surface Name, Fraction of Radiant Energy to Surface[LINK]
The following two items are repeated up to a maximum of 20
surface/fraction pairs. At least one surface/fraction pair
must appear in an input file. In other words, at least one
surface must be identified as a recipient of radiant energy
from the baseboard heater.
This field is the name of the first surface to which
radiant heat transfer from the baseboard heater is
distributed. Used in conjunction with the next field, it helps
to define the distribution of the radiant energy on the
surfaces within the zone. Note that up to 20 pairs of surface
names and corresponding fractions may be entered for a single
radiant heater system.
Field:
Fraction of Radiant Energy to Surface <x>[LINK]
This field is paired with the preceding surface name
(previous field) to define the fraction of radiant heat
transfer leaving the baseboard heater that is incident on a
particular surface. Users should take into account the
directionality of baseboard heaters and their location when
defining the value for this input field.
Note
on Fraction of Radiant Energy Incident on People and to
Surfaces[LINK]
The radiant energy from the baseboard heater is defined by
the total energy input to the baseboard heater from the steam
loop times the fraction radiant field shown above. This
radiant energy is distributed to surfaces and people using the
surface and fraction pairs and the fraction to people input by
the user. These fractions to people and surfaces must add up
to 1.0. In other words, in an input file, the following
relation should be maintained by the user input:
An example IDF for the steam baseboard is shown below.
ZoneHVAC:Baseboard:RadiantConvective:Steam,
Zone1Baseboard, !- Baseboard name
FanAndCoilAvailSched, !- On/off schedule
Steam Inlet Node, !- Steam inlet node
Steam Outlet Node, !- Steam outlet node
HeatingDesignCapacity,!- Heating Design Capacity Method
autosize, !- Heating Design Capacity{ W }
, !- Heating Design Capacity Per Floor Area{ W / m2 }
, !- Fraction of Autosized Heating Design Capacity{ -}
5.0, !- Degree of sub cooling in the coil {C}
autosize, !- Maximum steam volumetric flow rate {m3/s}
0.001, !- Tolerance
0.3, !- Fraction radiant
0.3, !- Fraction of radiant energy that is incident directly on people
OuterWall, !- Surface 1 Name
0.4, !- Fraction of radiant energy from heater distributed to surface 1
Ceiling, !- Surface 2 Name
0.1, !- Fraction of radiant energy from heater distributed to surface 2
InnerWall, !- Surface 3 Name
0.1, !- Fraction of radiant energy from heater distributed to surface 3
Floor, !- Surface 4 Name
0.1; !- Fraction of radiant energy from heater distributed to surface 4
This is the actual convective heat addition rate of the
baseboard to the zone in Watts. This value includes the heat
convected to the zone air from the baseboard unit, the heat
radiated to people in the zone from the baseboard unit, and
the additional convection from surfaces within the zone that
have been heated by radiation from the baseboard unit. This
value will be different from (and almost always less than) the
next field.
This is the actual, total convective energy transferred
directly and indirectly from the baseboard to the zone it is
serving in Joules. Direct convective heat transfer includes
the convective portion of the baseboard unit. Indirect
convective heat transfer includes heat radiated to people that
is then convected to the zone air and heat that is radiated to
the surfaces and then convected to the zone air.
The electric baseboard heater is a component in the zone
equipment simulation. Heat from this device is radiated to
people and surfaces and also convected to the surrounding air.
The electric baseboard model includes the impact of the
radiant heat addition to people and surfaces so that the
thermal comfort and surface heat balances are impacted. The
component is controlled to meet any remaining zone load not
met by other equipment baseboard operates to meet the
remaining zone load and the total electric consumption is
calculated by dividing by the efficiency of the baseboard.
The name of the schedule (ref: Schedule) that denotes
whether the electric baseboard heater unit can run during a
given time period. A schedule value greater than 0 (usually 1
is used) indicates that the unit can be on during the time
period. A value less than or equal to 0 (usually 0 is used)
denotes that the unit will be off for the time period. If this
field is blank, the schedule has values of 1 for all time
periods.
Enter the method used to determine the heating design
capacity for scalable sizing. Input allowed is either
HeatingDesignCapacity, CapacityPerFloorArea,
and FractionOfAutosizedHeatingCapacity. If this input
field is left blank or zero, then autosizing is assumed.
HeatingDesignCapacity means user specifies the
magnitude of maximum or nominal heating capacity or the
program calculates the maximum or nominal design heating
capacity if autosize is specified.
CapacityPerFloorArea means the program calculates the
design heating capacity from user specified heating capacity
per floor area and floor area of the zone served by the
radiant baseboard unit.
FractionOfAutosizedHeatingCapacity means the program
calculates the design heating capacity from user specified
fraction and the auto-sized design heating capacity. The
default method is HeatingDesignCapacity.
This field is for the radiant-convective electric baseboard
unit nominal heating capacity in watts. This field can be
autosized by EnergyPlus. This input field is autosizable. When
the Heating Design Capacity Method is
HeatingDesignCapacity and this input is blank,
autosizing is assumed. Design day sizing run must be
specified.
Field:
Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2
of radiant/convective electric baseboard. This field is
required field when the Heating Design Capacity Method is
CapacityPerFloorArea. The program calculates the
heating capacity from floor area of the zone served by the
radiant baseboard unit and the heating capacity per unit floor
area value specified by the user. This field may be left
blank.
Field:
Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized
heating capacity for radiant/convective electric baseboard.
This input field is required when the Heating Design Capacity
Method is FractionOfAutosizedHeatingCapacity. The
program calculates the heating capacity from the design
autosized heat capacity and user specified fraction. Design
day sizing run must be specified. This field may be left
blank. Default value is 1.0.
This is the overall electrical efficiency of the electric
baseboard unit. The zone load met by this unit is divided by
the electrical efficiency to obtain the total electric energy
used.
This field specifies what fraction of the power input to
the baseboard heater is actually transferred to the space as
radiant heat. The fraction should be between 0 and 1. This is
the portion of the total power that is modeled as radiation.
The portion that is radiant heat transfer from the baseboard
heater is distributed to people and specific surfaces using
the remaining fields. Note that the sum of the fractions in
the remaining fields (people and surfaces) must equal 1.0 so
that all the radiant power is distributed properly.
Field:
Fraction of Radiant Energy Incident on People[LINK]
This field specifies the fraction of the radiant portion of
heat transfer to the zone from the baseboard heater that is
incident directly on people within the space. This has an
impact on the predicted thermal comfort of the zone occupants.
Note that although this energy is “radiant” it is actually
modeled in the zone heat balance as a convective energy (like
an internal gain). The basic assumption here is that radiant
energy falling on people will most likely be rereleased to the
zone air by convection. This is a simplification of reality,
but it maintains the overall energy balance.
Field
Set: Surface Name, Fraction of Radiant Energy to Surface[LINK]
The following two items are repeated up to a maximum of 20
surface/fraction pairs. At least one surface/fraction pair
must appear in an input file. In other words, at least one
surface must be identified as a recipient of radiant energy
from the baseboard heater.
This field is the name of the first surface to which
radiant heat transfer from the baseboard heater is
distributed. Used in conjunction with the next field, it helps
to define the distribution of the radiant energy on the
surfaces within the zone. Note that up to 20 pairs of surface
names and corresponding fractions may be entered for a single
radiant heater system.
Field
Set: Fraction of Radiant Energy to Surface <x>[LINK]
This field is paired with the preceding surface name
(previous field) to define the fraction of radiant heat
transfer leaving the baseboard heater that is incident on a
particular surface. Users should take into account the
directionality of baseboard heaters and their location when
defining the value for this input field.
Note
on Fraction of Radiant Energy Incident on People and to
Surfaces[LINK]
The radiant energy from the baseboard heater is defined by
the total energy input to the baseboard heater times the
fraction radiant field shown above. This radiant energy is
distributed to surfaces and people using the surface and
fraction pairs and the fraction to people input by the user.
These fractions to people and surfaces must add up to 1.0. In
other words, in an input file, the following relation should
be maintained by the user input:
Below is an example input for an Electric Baseboard
Heater.
ZoneHVAC:Baseboard:RadiantConvective:Electric,
Baseboard 1, !- Name
BB Schedule, !- Availability Schedule Name
HeatingDesignCapacity, !- Heating Design Capacity Method
5000, !- Heating Design Capacity{ W }
, !- Heating Design Capacity Per Floor Area{ W / m2 }
, !- Fraction of Autosized Heating Design Capacity{ -}
0.97, !- Efficiency of the baseboard
0.3, !- Fraction radiant
0.3, !- Fraction of radiant energy that is incident directly on people
EastWall, !- Surface 1 name
0.3, !- Fraction of radiant energy from heater distributed to surface 1
WestWall, !- Surface 2 name
0.1, !- Fraction of radiant energy from heater distributed to surface 2
NorthWall, !- Surface 3 name
0.1, !- Fraction of radiant energy from heater distributed to surface 3
SouthWall, !- Surface 4 name
0.1, !- Fraction of radiant energy from heater distributed to surface 4
Ceiling, !- Surface 5 name
0.1; !- Fraction of radiant energy from heater distributed to surface 5
This is the actual convective heat addition rate of the
baseboard to the zone in Watts. This value includes the heat
convected to the zone air from the baseboard unit, the heat
radiated to people in the zone from the baseboard unit, and
the additional convection from surfaces within the zone that
have been heated by radiation from the baseboard unit. This
value will be different from (and almost always less than) the
next field.
This is the actual convective energy transferred directly
and indirectly from the baseboard heater to the zone it is
serving in Joules. Direct convective heat transfer includes
the convective portion of the baseboard unit. Indirect
convective heat transfer includes heat radiated to people that
is then convected to the zone air and heat that is radiated to
the surfaces and then convected to the zone air.
The radiant/convective cooling panel is a component of zone
equipment. Chilled water is supplied by the plant and
circulated through the panel. Through radiation and convective
heat transfer, the panel absorbs energy contained within the
zone to provide cooling. Control of the panel is achieved
using the methodology used for low temperature radiant
systems—a piecewise linear control profile that varies the
flow rate to the panel based on a control parameter defined by
the user. This is different than being controlled to meet any
remaining load like the air-based systems. However, due to the
radiant nature of these devices, it is not possible to control
precisely on a zone air-based load since this will result in
overcooling at the next time step. Despite this, in addition
to the piecewise linear controls that have been used with low
temperature radiant systems in the past, two new controls will
be added for this simple model: one that varies convective
output of the system to meet the remaining zone load and one
that varies the total convective output of the system to meet
the remaining zone load. In these two zone load control types,
the user must enter the typical zone thermostat object to
replace the setpoint and throttling range input in this
object. In this component, control is accomplished by
throttling the chilled water flow to the device. Capacity
rating information is required as input and is used to
calculate a UA value of the unit. The unit is connected to a
chilled water loop (demand side) with an inlet and outlet
node. The input data dictionary definition of the unit is as
follows.
The name of the schedule (ref: Schedule) that denotes
whether the radiant cooling panel can run during a given hour.
A schedule value greater than 0 (usually 1 is used) indicates
that the unit can be on during the hour. A value less than or
equal to 0 (usually 0 is used) denotes that the unit must be
off for the hour.
This field is the inlet temperature to the panel under
conditions used to rate the capacity of the panel. This value
along with the other rated conditions is used to calculate the
overall heat transfer coefficient (U-Value) that will be used
to characterize the heat transfer between the water being
circulated through the panel and the air in the zone. The
default value is 5°C (44°F).
This field is the combined space temperature (air and
surface) that the panel is exposed to during the rating
process to obtain a rated capacity. This value along with the
other rated conditions is used to calculate the overall heat
transfer coefficient (U-Value) that will be used to
characterize the heat transfer between the water being
circulated through the panel and the air in the zone. The
default value is 24°C (75.2°F).
This field is the rated standard water flow rate in kg/s
that was used to obtain the design cooling capacity under
rated temperature conditions. This value along with the rated
space and water inlet temperatures as well as the cooling
capacity (whether autosized or entered by the user) is used to
calculate the overall heat transfer coefficient (U-Value) that
will be used to characterize the heat transfer between the
water being circulated through the panel and the air in the
space. Users should note that if this value is too low in
comparison to the cooling design capacity that the program
will produce an error message and the user must adjust one of
these two parameters or the rated temperature values. The
default value is 0.063kg/s (1 gpm). If it is blank or zero,
the default value is assumed.
Enter the method used to determine the heating design
capacity for scalable sizing. Input allowed is either
CoolingDesignCapacity, CapacityPerFloorArea,
and FractionOfAutosizedCoolingCapacity. If this input
field is left blank or zero, then autosizing is assumed.
CoolingDesignCapacity means the user specifies the
magnitude of maximum or nominal cooling capacity or the
program calculates the maximum or nominal design cooling
capacity if autosize is specified.
CapacityPerFloorArea means the program calculates the
design cooling capacity from the user specified cooling
capacity per floor area and floor area of the zone served by
the cooling panel unit.
FractionOfAutosizedCoolingCapacity means the program
calculates the design cooling capacity from user specified
fraction and the auto-sized design cooling capacity. The
default method is CoolingDesignCapacity.
This field is for the cooling panel unit nominal cooling
capacity in watts at the rated flow rate of water through the
unit (see Rated Water Mass Flow Rate field above). This field
can be autosized by EnergyPlus. When the Cooling Design
Capacity Method is CoolingDesignCapacity and this
input is blank, autosizing is assumed. Design day sizing run
must be specified.
Field:
Cooling Design Capacity Per Floor Area[LINK]
Enter the cooling capacity per unit floor area in W/m2 for
the cooling panel unit. This field is a required field when
the Cooling Design Capacity Method is
CapacityPerFloorArea. The program calculates the
cooling capacity from floor area of the zone served by the
cooling panel unit and the cooling capacity per unit floor
area value specified by the user. This field may be left
blank.
Field:
Fraction of Autosized Cooling Design Capacity[LINK]
Enter the cooling capacity as a fraction of the autosized
cooling capacity for the cooling panel. This input field is
required when the Cooling Design Capacity Method is
FractionOfAutosizedCoolingCapacity. The program
calculates the cooling capacity from the design autosized
cooling capacity and the user specified fraction. Design day
sizing run must be specified. This field may be left blank.
Default value is 1.0.
This field specifies two different types of control
categories: temperature or zone load. For one of the
temperature based controls, this field along with the
throttling range and setpoint schedules determines how the
user wishes to control the radiant cooling panel. The
temperature denoted in the setpoint schedule can refer to one
of five different temperatures: the zone mean air temperature,
the zone mean radiant temperature, the zone operative
temperature, the outdoor dry-bulb temperature, or the outdoor
wet-bulb temperature. The current field controls the choice of
temperature. For controls that are based more on zone load,
the user can make one of two choices based on whether the zone
load is met by only the convective output of the unit or the
total output of the unit. These zone load controls will not
perform as precisely as air-based systems. The convective zone
load control will come close to meeting the current setpoint
temperature (defined by the typical zone thermostat input by
the user) since the convective output of the unit will be set
to match the remaining zone load. However, in the long run,
this will likely overcool the space since radiant energy is
being absorbed by surfaces and this will impact the zone
conditions at later time steps. The total zone load control
will likely undercool the space in the short term since the
total output (radiant and convective) of the unit will be set
to meet the remaining zone load. However, this will not fully
impact the zone air temperature immediately since some of the
energy is being absorbed from surfaces rather than the zone
air. The user must select from the following options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
OutdoorDryBulbTemperature
OutdoorWetBulbTemperature
ZoneConvectiveLoad
ZoneTotalLoad
Operative temperature for radiant system controls is the
average of Mean Air Temperature and Mean Radiant Temperature.
If the user does not select a control type, MeanAirTemperature
control is assumed by EnergyPlus. See the throttling range and
control temperature schedule fields below for more
information.
This field specifies the range of temperature in degrees
Celsuis over which the radiant cooling panel throttles from
zero flow rate up to the maximum defined by the maximum
chilled water flow rate field described above. The throttling
range parameter is used in conjunction with the control
temperature to define the response of the system to various
zone conditions. The cooling control temperature schedule
specifies the “setpoint” temperature where the flow rate to
the system is at half of the maximum flow rate. For example,
if the cooling control temperature setpoint is currently 25 C
and the cooling throttling range is 2 C, the water flow rate
to the radiant system will be zero when the controlling
temperature (MAT, MRT, Operative Temperature, ODB, or OWB; see
control type field above) is at or below 24 C and the maximum
flow rate when the controlling temperature is at or above 26
C. This represents a throttling range of 2 C around the
setpoint of 25 C. In between 24 C and 26 C, the flow rate to
the radiant system is varied linearly. Note that this field is
ignored when the control type is either ZoneLoadConvective or
ZoneLoadTotal. For the two zone load controls, the user must
use a typical zone thermostat and the system output will be
dependent on the remaining zone load.
Field:
Cooling Control Temperature Schedule Name[LINK]
This field specifies the cooling setpoint or control
temperature for the radiant cooling panel in degrees Celsius.
Used in conjunction with the previous field (cooling control
throttling range), it will define whether or not the system is
running and the current flow rate. Water flow rate to the
system is varied linearly around the setpoint temperature
based on the throttling range and the maximum cooling flow
rate parameters (see above). It should be noted that this
control schedule will allow different setpoint temperatures
throughout the year for cooling. The control of the radiant
cooling panel is based solely on the cooling control
throttling range listed above, the cooling control temperature
schedule, and the control temperature type listed above. The
radiant cooling panel will not use any zone thermostat that
might be used by other systems serving the zone in which this
radiant cooling panel resides. Note that this field is ignored
when the control type is either ZoneLoadConvective or
ZoneLoadTotal. For the two zone load controls, the user must
use a typical zone thermostat and the system output will be
dependent on the remaining zone load.
Since radiant cooling panels provide a cold surface in what
could be a humid zone, there is the possibility that
condensation will occur on the surface of the panel. This is
due to the fact that the surface temperature may drop below
the dew-point temperature of the space. When this occurs,
condensation on the surface will occur. Since there is no
direct calculation of the surface temperature of the radiant
cooling panel, the condensation check will be made at the
inlet water temperature to the panel. Since the user can
utilize the next parameter to adjust the differential between
the dewpoint temperature and the inlet water temperature, this
will allow some flexibility in controlling when the panel will
shutdown to avoid condensation. There are three options for
handling potential condensation: Off, SimpleOff, and
VariableOff. This parameter is optional and will default to
SimpleOff.
Off - EnergyPlus will not do anything other than
produce a warning message when condensation is predicted to
occur. The program will simply continue on; no moisture will
be removed from the zone air and there will be no adjustment
of the surface temperature as a result of the
condensation.
SimpleOff - the program will predict cases where
condensation will occur and shut-off the radiant system to
avoid this situation. With this option, the user also has the
option to adjust when the system will shut down. This is
specified with the next parameter (field: Condensation
Differential Parameter).
VariableOff - the program will attempt to reduce the
inlet temperature to the panel by locally recirculating some
of the water leaving the panel and mixing it with water from
the overall demand side flow. This also means that some of the
demand side water will bypass the panel. In reality, this
would require a pump to achieve such mixing and recirculation,
but due to the simple nature of this model, no pump definition
will be required. Like the SimpleOff option, the VariableOff
option uses the condensation dewpoint offset parameter to
adjust when the system will try to adjust for the possibility
of condensation.
This optional parameter is only valid with the SimpleOff
and VariableOff condensation handling algorithm (see previous
input parameter). It establishes the difference between the
calculated dew-point temperature of the space and the allowed
inlet water temperature to the radiant cooling panel before
the system shuts down in degrees Celsius. This parameter can
be any positive, negative, or zero value. When this parameter
is zero, the radiant system will shut down or recirculate
water (depending on whether SimpleOff or VariableOff is used)
when the inlet temperature drops to the dew-point temperature
or below. When this parameter is positive, the radiant system
will shut down or recirculate water when the inlet water
temperature is the number of degrees Celsius above the
dew-point temperature. This allows some extra safety to avoid
condensation. When this parameter is negative, the radiant
system will shut down or recirculate water when the inlet
water temperature is the number of degrees Celsius below the
dew-point temperature. This strategy allows the user to
simulate a situation where small amounts of condensation are
tolerable or the resistance of the panel from the water loop
to the panel surface is being taken into account as
condensation would likely happen at the panel surface. The
default value for this parameter is 1°C.
This field gives the user an opportunity to characterize
the zone temperature as a function of the zone mean radiant
temperature and the mean air temperature. The performance of
the unit is proportional to the difference between the water
inlet temperature and the zone temperature where the zone
temperature is found using a weighted average of zone mean
radiant temperature and mean air temperature. The weighting
factor is this parameter and it is multiplied by the zone mean
radiant temperature. The remainder of the zone temperature
calculation is made up of the zone mean air temperature. This
parameter can be difficult to quantify as the fraction radiant
can vary with zone conditions. However, by definition, a
radiant system like this radiant cooling panel must exchange
at least 50
Field:
Fraction of Radiant Energy Incident on People[LINK]
This field allows the user to direct some of the radiant
energy to be absorbed from people rather than surfaces within
the space. This would have a direct impact on thermal comfort
and would depend on the location of the people with respect to
the radiant cooling panel. All energy absorbed by the panel
would have a cooling effect on people and is subtracted from
the total radiant energy absorbed by the panel defined by the
previous term.
Field
Set: Surface Name, Fraction of Radiant Energy to Surface[LINK]
The following two items are repeated for an unlimited
number of surface/fraction pairs. At least one
surface/fraction pair must appear in an input file. In other
words, at least one surface must be identified as a recipient
of radiant energy from the baseboard heater.
The radiant energy from the cooling panel is defined by the
total energy input to the cooling panel from the chilled water
loop times the fraction radiant field shown above. This
radiant energy is distributed to surfaces and people using the
surface and fraction pairs and the fraction to people input by
the user. These fractions to people and surfaces must add up
to 1.0. In other words, in an input file, the following
relation should be maintained by the user input:
The radiant energy absorbed by the radiant cooling panel
can be specified to be received from particular surfaces
within the space. The next series of pairs of inputs (surface
name and fraction of radiant energy) specify where this
radiant energy is coming from. In essense, the fraction
radiant terms for each surface are similar to a view factor.
These pairs can be repeated for up to 100 surfaces giving the
user plenty of flexibility to have the radiant cooling panel
interact with many potential surfaces. This first parameter in
the pair is the name of the surface defined by user input
elsewhere in the input file. Note that the surface must reside
in the same zone as all of the other surfaces in the following
list (that is, all surfaces listed must be in the same
zone).
Field
Set: Fraction of Radiant Energy to Surface <x>[LINK]
In combination with the previous field, this defines what
fraction of the radiant energy being absorbed by the radiant
cooling panel comes from the surface named by the previous
field. These pairs of surface names and fractions of radiant
energy from the surface can be repeated up to 100 times in the
input for a particular radiant cooling panel. Note that the
sum of all of the radiant energy fractions plus the radiant
fraction from people must add up to unity just like in the
radiant-convective baseboard models. Note that there is a
small possibility that a particular surface listed in these
pairs is actually lower than the temperature of the panel.
This probably will not happen unless there is another cooling
surface within the zone. In reality, absorbing net radiant
energy from a colder surface would violate the Second Law of
Thermodynamics. However, in keeping with the simple nature of
this model, EnergyPlus will monitor the inlet water
temperature to the panel and produce a warning message if this
temperature is lower than any of the surface temperature of
the surfaces with which this system is interacting.
An example input for the radiant cooling panel is shown
below.
ZoneHVAC:CoolingPanel:RadiantConvective:Water,
Radiant Cooling Panel 1, !- Name
RCP Schedule 1, !- Availability schedule
RCP Water Inlet Node, !- Water Inlet node name
RCP Water Outlet Node, !- Water Outlet node name
5.0, !- Rated Water Inlet Temperature {C}
24.0, !- Rated Space Temperature {C}
0.063, !- Rated Water Mass Flow Rate {kg/s}
5000.0, !- Rated cooling capacity {W}
0.1, !- Maximum water flow rate {m3/s}
MeanAirTemperature, !- Temperature Control Type
1.0, !- Cooling Control Throttling Range
RCP Temp Schedule, !- Cooling Control Temperature Schedule Name
SimpleOff, !- Condensation Control Type
1.0, !- Condensation Control Dewpoint Offset
0.65, !- Fraction Radiant
0.2, !- Fraction of Radiant Energy Incident on People
Zone 1 Floor, !- Surface 1 Name
0.5, !- Fraction of Radiant Energy to Surface 1
Zone 1 West Wall, !- Surface 2 Name
0.25, !- Fraction of Radiant Energy to Surface 2
Zone 1 South Wall, !- Surface 3 Name
0.25; !- Fraction of Radiant Energy to Surface 3
HVAC, Average, Cooling Panel Total System Cooling Rate
[W]
HVAC, Average, Cooling Panel Total Cooling Rate
[W]
This field is the total rate of cooling achieved by the
radiant cooling panel on the zone in Watts. This is the impact
of the cooling panel on the space and is the actual impact the
system has on the zone. It includes the convective heat
transfer rate as well as the decreased convection from zone
surfaces as a result of the operation of the unit and the
radiant absorbed by people.
This variable is the total rate of cooling achieved by the
radiant cooling panel on the zone in Watts. This value
includes the sum of both the convective and the radiant energy
absorbed by the panel.
This field reports the rate at which radiant heat is
removed from people and the surfaces of the zone being served
by the radiant cooling panel in Watts.
Cooling
Panel Total System Cooling Energy [J][LINK]
This field is the total cooling achieved by the radiant
cooling panel on the zone in Joules over the timestep being
reported. This is the impact of the cooling panel on the space
and is the actual impact the system has on the zone. It
includes the convective heat transfer rate as well as the
decreased convection from zone surfaces as a result of the
operation of the unit and the radiant absorbed by people.
This field reports the amount of radiant heat removal from
people and the surfaces of the zone being served by the
radiant cooling panel in Joules over the timestep being
reported.
This meter report variable is the sum of the total heat
removal being accomplished by all radiant cooling panels in
the HVAC systems in the simulation.
This field reports the water mass flow rate at the inlet
node of the radiant cooling panel. The water mass flow rate at
the inlet and outlet node of the radiant cooling panel is the
same value.
The hot water baseboard heater is a component of zone
equipment. The component is controlled to meet any remaining
zone load not met by other equipment in the zone that have
higher heating priority. The control is accomplished by
throttling the hot water flow. Input resembles that for the
simple heating coil: there is an availability schedule, an
overall UA, and a maximum hot water mass flow rate. The unit
is connected to a hot water loop (demand side) with an inlet
and outlet node. Finally, there is the convergence tolerance,
which is the tolerance on how closely the baseboard outlet
will meet the zone load. Of course, this tolerance is relative
to the zone load.
The name of the schedule (ref: Schedule) that denotes
whether the hot water baseboard heater unit can run during a
given time period. A schedule value greater than 0 (usually 1
is used) indicates that the unit can be on during the time
period. A value less than or equal to 0 (usually 0 is used)
denotes that the unit must be off for the time period. If this
field is blank, the schedule has values of 1 for all time
periods.
Enter the method used to determine the heating design
capacity for scalable sizing. Input allowed is either
HeatingDesignCapacity, CapacityPerFloorArea,
and FractionOfAutosizedHeatingCapacity. If this input
field is left blank or zero, then autosizing is assumed.
HeatingDesignCapacity means user specifies the
magnitude of maximum or nominal heating capacity or the
program calculates the maximum or nominal design heating
capacity if autosize is specified.
CapacityPerFloorArea means the program calculates the
design heating capacity from user specified heating capacity
per floor area and floor area of the zone served by the hot
water baseboard heater.
FractionOfAutosizedHeatingCapacity means the program
calculates the design heating capacity from user specified
fraction and the auto-sized design heating capacity. The
default method is HeatingDesignCapacity.
This field is for the hot water baseboard heater design
heating capacity in watts. This field can be autosized by
EnergyPlus. This input field is autosizable. When the Heating
Design Capacity Method is HeatingDesignCapacity and
this input is blank, autosizing is assumed. Design day sizing
run must be specified id autosize is specified.
Field:
Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2
of hot water baseboard heater. This field is required field
when the Heating Design Capacity Method is
CapacityPerFloorArea. The program calculates the
heating capacity from floor area of the zone served by hot
water baseboard heater and the heating capacity per unit floor
area value specified by the user. This field may be left
blank.
Field:
Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized
heating capacity for the hot water baseboard heater. This
input field is required when the Heating Design Capacity
Method is FractionOfAutosizedHeatingCapacity. The
program calculates the heating capacity from the design
autosized heat capacity and user specified fraction. Design
day sizing run must be specified. This field may be left
blank. Default value is 1.0.
The overall heat transfer coefficient for the baseboard
heater in watts per degree Celsius at design conditions. The
U-Factor Times Area Value (UA) is used in an NTU -
effectiveness calculation. An estimate of the UA can be
obtained from:
\[q = UA \times ({T_{water,avg}}
- {T_{air,avg}})\]
where q is the heat transferred from water to the air in
watts; T\(_{water,\\ avg}\)
is the average water temperature in degrees C; and T\(_{air,\\ avg}\) is the average
air temperature in degrees C. Or the LMTD temperature
difference can be used.
The control tolerance for the unit heating output. The unit
is controlled by matching the unit output to the zone demand.
For hot water baseboards, the model must be numerically
inverted to obtain a specified output. The convergence
tolerance is the error tolerance used to terminate the
numerical inversion procedure. Basically this is the
fraction:
The electric baseboard heater is a component in the zone
equipment simulation. The component is controlled to meet any
remaining zone load not met by other equipment in the zone
that have higher heating priority. The control is accomplished
by taking the remaining zone load and dividing by the
efficiency of the baseboard.
The name of the schedule (ref: Schedule) that denotes
whether the electric baseboard heater unit can run during a
given time period. A schedule value greater than 0 (usually 1
is used) indicates that the unit can be on during the time
period. A value less than or equal to 0 (usually 0 is used)
denotes that the unit must be off for the time period. If this
field is blank, the schedule has values of 1 for all time
periods.
Enter the method used to determine the heating design
capacity or enter the method for scalable sizing of heating
capacity of electric baseboard unit. Input allowed is either
HeatingDesignCapacity, CapacityPerFloorArea,
and FractionOfAutosizedHeatingCapacity. If this input
field is left blank or zero, then autosizing is assumed.
HeatingDesignCapacity means user specifies the
magnitude of maximum or nominal heating capacity or the
program calculates the maximum or nominal design heating
capacity if autosize is specified.
CapacityPerFloorArea means the program calculates the
design heating capacity from user specified heating capacity
per floor area and floor area of the zone served by the
electric convective baseboard unit.
FractionOfAutosizedHeatingCapacity means the program
calculates the design heating capacity from user specified
fraction and the auto-sized design heating capacity. The
default method is HeatingDesignCapacity.
This field is for the convective electric baseboard nominal
heating capacity in watts. This field can be autosized by
EnergyPlus. This input field is autosizable. Design day sizing
run must be specified. This input field may be left blank.
Field:
Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2
of electric convective baseboard unit. This field is required
field when the Heating Design Capacity Method is
CapacityPerFloorArea. The program calculates the
heating capacity from floor area of the zone served by the
electric convective baseboard unit and the heating capacity
per unit floor area value specified by the user. This field
may be left blank.
Field:
Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized
heating capacity for convective electric baseboard unit. This
input field is required when the Heating Design Capacity
Method is FractionOfAutosizedHeatingCapacity. The
program calculates the heating capacity from the design
autosized heating capacity and user specified fraction. Design
day sizing must be specified. This field may be left blank.
Default value is 1.0.
This is the overall electrical efficiency of the electric
baseboard. The zone load met by this unit is divided by the
electrical efficiency to obtain the total electric energy
used.
An example IDF for the electric convective baseboard is
shown below.
ZoneHVAC:Baseboard:Convective:Electric,
Zone1Baseboard, !- Baseboard Name
FanAndCoilAvailSched, !- Availability Schedule Name
HeatingDesignCapacity, !- Heating Design Capacity Method
5000, !- Heating Design Capacity{ W }
, !- Heating Design Capacity Per Floor Area{ W / m2 }
, !- Fraction of Autosized Heating Design Capacity{ -}
0.97; !- Efficiency of the BaseBoard
This low temperature radiant system (hydronic) is a
component of zone equipment that is intended to model any
“radiant system” where water is used to supply/remove energy
to/from a building surface (wall, ceiling, or floor). The
component is controlled to meet any remaining zone load not
met by other equipment in the zone that have higher priority.
The control is accomplished by throttling the hot or chilled
water flow to the unit. Note that this system will only
control based on the radiant system controls defined by this
input syntax and not via a zone thermostat such as is used for
forced air systems. Note also that because this unit does not
require a thermostat that in cases where no other systems are
serving the zone in which this system resides that it will use
the heating equipment priority to determine which system will
run first. If the radiant system is serving a zone with
forced air equipment, the radiant system will follow the
priority order established by the zone thermostat but will
still base its response on the controls defined by the user
for the radiant system.
This model covers a wide range of low temperature radiant
systems: heating and/or cooling, panel or embedded pipes, etc.
It is not intended to simulate high temperature electric or
gas radiant heaters. Those devices will be handled by a
separate model and different input syntax. Low temperature
radiant systems that use electric resistance heating should
also be defined using separate input syntax (ref:
ZoneHVAC:LowTemperatureRadiant:Electric).
This field is an unique user assigned name for an instance
of a hydronic low temperature radiant system. Any reference to
this unit by another object will use this name.
This field is the name of the schedule (ref: Schedule) that
denotes whether the hydronic low temperature radiant system
can run during a given time period. A schedule value less than
or equal to 0 (usually 0 is used) denotes that the unit must
be off for that time period. A value greater than 0 (usually 1
is used) denotes that the unit is available to operate during
that time period. If this field is left blank, the schedule
has a value of 1 for all time periods.
This field is the name of the zone (Ref: Zone) in which the
hydronic low temperature radiant system is principally located
and intended to affect. A system that is between two zones
will still act upon each zone; however, the zone name
referenced here should be the zone that controls the radiant
system response.
Field:
Surface Name or Radiant Surface Group Name[LINK]
This field is the name of the surface (Ref:
BuildingSurface) or surface list (Ref:
ZoneHVAC:LowTemperatureRadiant:SurfaceGroup) in which the
hydronic tubing is embedded/contained. This specification
attaches the source or sink from the radiant system to a
particular surface and the contribution of the system to the
heat balances of that surface. If this field is a surface
list, then the source or sink is attached to all of the
surfaces in the list with the radiant system surface group
defining the breakdown of how flow rate is split between the
various surfaces. Base surfaces (e.g.,
BuildingSurface:Detailed), door surfaces and internal mass are
valid. Window
surfaces are not valid surface types for embedded radiant
systems.
This field is the inside diameter of the tubes through
which water is circulated for the system being defined by this
statement. The inside diameter should be recorded in meters
and is used to determine the convective heat transfer from the
water to the inside surface of the hydronic tubing.
This field is the total length of pipe embedded in the
surface named above in the surface name field. The length of
the tube should be entered in meters and is used to determine
the effectiveness of heat transfer from the fluid being
circulated through the tubes and the tube/surface. Longer
tubing lengths result in more heat will be transferred to/from
the radiant surface to the circulating fluid. Note that if the
user elects to autosize this field that a standard zone
thermostat such as would be used for a forced air system must
be defined as autosizing calculations are based on the zone
thermostat value and not on the radiant system control values.
In addition, when the user opts to autosize this calculation,
the tube spacing from the construction of each surface
associated with this system is used along with each individual
surface area to make an approximation of the tubing
length.
This field specifies along with the throttling range and
setpoint schedules how the user wishes to control the hydronic
radiant system. The temperature denoted in the setpoint
schedule can refer to one of five different temperatures: the
zone mean air temperature, the zone mean radiant temperature,
the zone operative temperature, the outdoor dry-bulb
temperature, or the outdoor wet-bulb temperature. The choice
of temperature is controlled by the current field—temperature
control type. The user must select from the following
options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
OutdoorDryBulbTemperature
OutdoorWetBulbTemperature
Operative temperature for radiant system controls is the
average of Mean Air Temperature and Mean Radiant Temperature.
If the user does not select a control type,
MeanAirTemperature control is assumed by
EnergyPlus. See the throttling range and control temperature
schedule fields below for more information.
Enter the method used to determine the heating design
capacity for scalable sizing. Input allowed is either
HeatingDesignCapacity, CapacityPerFloorArea,
and FractionOfAutosizedHeatingCapacity. If this input
field is left blank or zero, then autosizing is assumed.
HeatingDesignCapacity means user specifies the
magnitude of maximum or nominal heating capacity or the
program calculates the design heating capacity if autosize is
specified. CapacityPerFloorArea means the program
calculates the design heating capacity from user specified
heating capacity per floor area and floor area of the zone
served by the low temperature radiant variable flow unit.
FractionOfAutosizedHeatingCapacity means the program
calculates the design heating capacity from user specified
fraction and the auto-sized design heating capacity. The
default method is HeatingDesignCapacity.
This field is for the low temperature radiant variable flow
unit design heating capacity in watts. This field can be
autosized by EnergyPlus. This input field is autosizable. When
the Heating Design Capacity Method is
HeatingDesignCapacity and this input is blank,
autosizing is assumed. Design day sizing run must be specified
if autosized.
Field:
Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2
of low temperature radiant variable flow unit. This field is
required field when the Heating Design Capacity Method is
CapacityPerFloorArea. The program calculates the
heating capacity from floor area of the zone served by the low
temperature radiant variable flow unit and the heating
capacity per unit floor area value specified by the user. This
field may be left blank.
Field:
Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized
heating capacity for low temperature radiant variable flow
unit. This input field is required when the Heating Design
Capacity Method is
FractionOfAutosizedHeatingCapacity. The program
calculates the heating capacity from the design autosized heat
capacity and user specified fraction. Design day sizing run
must be specified. This field may be left blank. Default value
is 1.0.
This field is the maximum flow rate of hot water through
the radiant system in m\(^{3}\)/sec. The controls for the
radiant system will vary the flow rate of hot water through
the surface using zero flow and the maximum flow rate
specified in this field as the lower and upper bounds,
respectively. Note that if the user elects to autosize this
field that a standard zone thermostat such as would be used
for a forced air system must be defined as autosizing
calculations are based on the zone thermostat value and not on
the radiant system control values.
This field contains the name of the hot water inlet node to
the radiant system. Note that this node name must also show up
in the branch description when defining the plant demand side
network in a manner identical to defining a heating coil.
This field contains the name of the hot water oulet node to
the radiant system. Note that this node name must also show up
in the branch description when defining the plant demand side
network in a manner identical to defining a heating coil.
This field specifies the range of temperature in degrees
Celsuis over which the radiant system throttles from zero flow
rate up to the maximum defined by the maximum hot water flow
rate field described above. The throttling range parameter is
used in conjunction with the control temperature to define the
response of the system to various zone conditions. The heating
control temperature schedule specifies the “setpoint”
temperature where the flow rate to the system is at half of
the maximum flow rate. For example, if the heating control
temperature setpoint is currently 15°C and the heating
throttling range is 2°C, the water flow rate to the radiant
system will be zero when the controlling temperature (MAT,
MRT, Operative Temperature, ODB, or OWB; see control type
field above) is at or above 16°C and the maximum flow rate
when the controlling temperature is at or below 14°C. This
represents a throttling range of 2°C around the setpoint of
15°C. In between 14°C and 16°C, the flow rate to the radiant
system is varied linearly.
Field:
Heating Control Temperature Schedule Name[LINK]
This field specifies the heating setpoint or control
temperature for the radiant system in degrees Celsius. Used in
conjunction with the previous field (heating control
throttling range), it will define whether or not the system is
running and the current flow rate. Water flow rate to the
system is varied linearly around the setpoint temperature
based on the throttling range and the maximum heating flow
rate parameters (see above). It should be noted that this
control schedule will allow different setpoint temperatures
throughout the year for heating. The control of the radiant
system is based solely on the heating control temperature
schedule, the cooling control temperature schedule (see
below), and the control temperature type listed above. The
radiant system will not use any zone thermostat that might be
used by other systems serving the zone in which the radiant
system resides.
Enter the method used to determine the cooling design
capacity for scalable sizing. Input allowed is either
CoolingDesignCapacity, CapacityPerFloorArea,
and FractionOfAutosizedCoolingCapacity. If this input
field is left blank or zero, then autosizing is assumed.
CoolingDesignCapacity means user specifies the design
cooling capacity or the program calculates the design cooling
capacity if autosize is specified.
CapacityPerFloorArea means the program calculates the
design cooling capacity from user specified heating capacity
per floor area and floor area of the zone served by the low
temperature radiant variable flow unit.
FractionOfAutosizedCoolingCapacity means the program
calculates the design cooling capacity from user specified
fraction and the auto-sized design cooling capacity. The
default method is CoolingDesignCapacity.
This field is for the low temperature radiant variable flow
unit design cooling capacity in watts. This field can be
autosized by EnergyPlus. This input field is autosizable. When
the Cooling Design Capacity Method is
CoolingDesignCapacity and this input is blank,
autosizing is assumed. Design day sizing run must be specified
if autosized.
Field:
Cooling Design Capacity Per Floor Area {W/m2}[LINK]
Enter the cooling capacity per unit floor area in m3/s-m2
of low temperature radiant variable flow unit. This field is
required field when the Cooling Design Capacity Method is
CapacityPerFloorArea. The program calculates the
cooling capacity from floor area of the zone served by the low
temperature radiant variable flow unit and the cooling
capacity per unit floor area value specified by the user. This
field may be left blank.
Field:
Fraction of Autosized Cooling Design Capacity[LINK]
Enter the cooling capacity as a fraction of the autosized
cooling capacity for low temperature radiant variable flow
unit. This input field is required when the Cooling Design
Capacity Method is
FractionOfAutosizedCoolingCapacity. The program
calculates the cooling capacity from the design autosized
cooling capacity and user specified fraction. Design day
sizing run must be specified. This field may be left blank.
Default value is 1.0.
This field is the maximum flow rate of cold water through
the radiant system in m\(^{3}\)/sec. The controls for the
radiant system will vary the flow rate of cold water through
the surface using zero flow and the maximum flow rate
specified in this field as the lower and upper bounds,
respectively. Note that this field is optional and not
required for a heating only system. Note also that if the user
elects to autosize this field that a standard zone thermostat
such as would be used for a forced air system must be defined
as autosizing calculations are based on the zone thermostat
value and not on the radiant system control values.
This field contains the name of the cold water inlet node
to the radiant system. Note that this node name must also show
up in the branch description when defining the plant demand
side network in a manner identical to defining a cooling coil.
As with the maximum cold water flow rate, this field is
optional and not required for a heating only system.
This field contains the name of the cold water oulet node
to the radiant system. Note that this node name must also show
up in the branch description when defining the plant demand
side network in a manner identical to defining a cooling coil.
As with the maximum cold water flow rate, this field is
optional and not required for a heating only system.
This field specifies the range of temperature in degrees
Celsuis over which the radiant system throttles from zero flow
rate up to the maximum defined by the maximum cold water flow
rate field described above. The throttling range parameter is
used in conjunction with the control temperature to define the
response of the system to various zone conditions. The cooling
control temperature schedule specifies the “setpoint”
temperature where the flow rate to the system is at half of
the maximum flow rate. For example, if the cooling control
temperature setpoint is currently 25°C and the cooling
throttling range is 2°C, the water flow rate to the radiant
system will be zero when the controlling temperature (MAT,
MRT, Operative Temperature, ODB, or OWB; see control type
field above) is at or below 24°C and the maximum flow rate
when the controlling temperature is at or above 26°C. This
represents a throttling range of 2°C around the setpoint of
25°C. In between 24°C and 26°C, the flow rate to the radiant
system is varied linearly.
Field:
Cooling Control Temperature Schedule Name[LINK]
This field specifies the cooling setpoint or control
temperature for the radiant system in degrees Celsius. Used in
conjunction with the previous field (cooling control
throttling range), it will define whether or not the system is
running and the current flow rate. Water flow rate to the
system is varied linearly around the setpoint temperature
based on the throttling range and the maximum cooling flow
rate parameters (see above). It should be noted that this
control schedule will allow different setpoint temperatures
throughout the year for cooling. The control of the radiant
system is based solely on the heating control temperature
schedule listed above, the cooling control temperature
schedule, and the control temperature type listed above. The
radiant system will not use any zone thermostat that might be
used by other systems serving the zone in which the radiant
system resides.
When radiant systems do cooling, there is the possibility
that condensation will occur on the surface that is being
cooled. This is due to the fact that the surface temperature
may drop below the dew-point temperature of the space. When
this happens, condensation on the surface will occur. There
are three options for handling this situation: Off, SimpleOff,
and VariableOff. This parameter is optional and will default
to SimpleOff.
Off - EnergyPlus will not do anything other than
produce a warning message when condensation is predicted to
occur. The program will simply continue on, no moisture will
be removed from the zone air, and there will be no adjustment
of the surface temperature as a result of the
condensation.
SimpleOff - the program will predict cases where
condensation will occur and shut-off the radiant system to
avoid this situation. With this option, the users also have
the opportunity to adjust when the system will shut down. This
is specified with the next parameter (field: Condensation
Control Dewpoint Offset).
VariableOff - the program will determine whether
condensation is predicted for the flow rate determined by the
unit control scheme. If condensation is predicted, the unit
makes one attempt to reduce the flow rate using linear
interpolation between the controlled flow rate and a zero flow
rate to achieve a surface temperature that would match the
dew-point temperature modified by the condensation control
dew-point offset (field: Condensation Control Dewpoint
Offset). For example, if the controlled flow rate results in a
surface temperature of 10°C, a zero flow rate results in a
surface temperature of 12°C, and the modified condensation
dew-point temperature is 11°C, then the reduced flow rate
would be half of the controlled flow rate. If this reduced
flow approximation does not result in condensation, then this
reduced flow is used for the unit. If the reduced flow
approximation still results in condensation, then the unit is
turned off to avoid excessive iterations.
This optional parameter is only valid with the SimpleOff
and VariableOff condensation handling algorithm (see previous
input parameter). It establishes the difference between the
calculated dew-point temperature of the space and the allowed
surface temperature to which the surface can drop before the
radiant system shuts down (SimpleOff) or reduces its flow rate
(VariableOff) to avoid condensation in degrees Celsius. This
parameter can be any positive, negative, or zero value. When
this parameter is zero, the radiant system will shut down or
reduce the flow rate when the surface temperature drops to the
dew-point temperature or below. When this parameter is
positive, the radiant system will shut down or reduce the flow
rate when the surface is the number of degrees Celsius above
the dew-point temperature. This allows some extra safety to
avoid condensation. When this parameter is negative, the
radiant system will shut down or reduce the flow rate when the
surface temperature is the number of degrees Celsius below the
dew-point temperature. While not recommended, this strategy
allows the user to simulate a situation where small amounts of
condensation are tolerable. The default value for this
parameter is 1°C.
This optional input allows the user to choose between
modeling each surface in the radiant system as a single
hydronic circuit or to allow the program to divide the surface
into multiple parallel hydronic circuits based on the next
input field Circuit Length. To model as a single
circuit choose OnePerSurface. To model as multiple
circuits choose CalculateFromCircuitLength. It is
recommended that CalculateFromCircuitLength be
chosen. The default is OnePerSurface for backward
compatibility with older versions of EnergyPlus.
The length in meters of each parallel hydronic circuit in a
surface. Used when the previous input field is set to
CalculateFromCircuitLength. The default is 106.7
meters (350 feet), which is the maximum circuit length allowed
in Title 24.
An example IDF with a hydronic low temperature radiant
system is shown below.
ZoneHVAC:LowTemperatureRadiant:VariableFlow,
SPACE1-1 Zone Radiant Floor, !- Name
RADIANTSYSAVAILSCHED, !- Availability Schedule Name
SPACE1-1, !- Zone Name
C1-1, !- Surface Name or Radiant Surface Group Name
0.013, !- Hydronic Tubing Inside Diameter {m}
autosize, !- Hydronic Tubing Length {m}
OperativeTemperature, !- Temperature Control Type
HeatingDesignCapacity, !- Heating Design Capacity Method
autosize, !- Heating Design Capacity{ W }
, !- Heating Design Capacity Per Floor Area{ W / m2 }
, !- Fraction of Autosized Heating Design Capacity{ -}
0.0004, !- Maximum Hot Water Flow {m3/s}
SPACE1-1 Zone Radiant Water Inlet Node, !- Heating Water Inlet Node Name
SPACE1-1 Zone Radiant Water Outlet Node, !- Heating Water Outlet Node Name
2.0, !- Heating Control Throttling Range {deltaC}
RADIANT HEATING SETPOINTS, !- Heating Control Temperature Schedule Name
CoolingDesignCapacity, !- Cooling Design Capacity Method
autosize, !- Cooling Design Capacity{ W }
, !- Cooling Design Capacity Per Floor Area{ W / m2 }
, !- Fraction of Autosized Cooling Design Capacity{ -}
autosize, !- Maximum Cold Water Flow {m3/s}
SPACE1-1 Cooling Water Inlet Node, !- Cooling Water Inlet Node Name
SPACE1-1 Cooling Water Outlet Node, !- Cooling Water Outlet Node Name
2.0, !- Cooling Control Throttling Range {deltaC}
RADIANT COOLING SETPOINTS, !- Cooling Control Temperature Schedule Name
Off, !- Condensation Control Type
1.0, !- Condensation Control Dewpoint Offset
CalculateFromCircuitLength, !- Number of Circuits
106.7; !- Circuit Length
This field reports the heating input rate to the low
temperature radiant system in Watts. This is the heat source
to the surface that is defined as the radiant system. The
heating rate is determined by the zone conditions and the
control scheme defined in the user input.
This field reports the heating input to the low temperature
radiant system in Joules. This is the heat source to the
surface that is defined as the radiant system. The heating
rate is determined by the zone conditions, the control scheme
defined in the user input, and the timestep.
This field reports the cooling input rate to the low
temperature radiant system in Watts. This is the heat sink to
the surface that is defined as the radiant system. The cooling
rate is determined by the zone conditions and the control
scheme defined in the user input.
This field reports the cooling input to the low temperature
radiant system in Joules. This is the heat sink to the surface
that is defined as the radiant system. The cooling rate is
determined by the zone conditions, the control scheme defined
in the user input, and the timestep.
Zone
Radiant HVAC Mass Flow Rate Rate [kg/s][LINK]
This field reports the mass flow rate of water through the
low temperature radiant system in kilograms per second.
This field reports the temperature of water leaving the low
temperature radiant system in Celsius.
Zone
Radiant HVAC Moisture Condensation Time[s][LINK]
This field reports the amount of time when condensation is
occurring. When using the Off condensation control, this
simply reports the amount of time when condensation occurs.
When using the SimpleOff condensation control, this indicates
the amount of time when the system has been shut off because
of the potential danger of condensation.
This low temperature radiant system (hydronic) is a
component of zone equipment that is intended to model any
“radiant system” where water is used to supply/remove energy
to/from a building surface (wall, ceiling, or floor). The
component is controlled via control schedules as described in
the syntax below and does not require a zone thermostat. Note
that because this unit does not require a thermostat that in
cases where no other systems are serving the zone in which
this system resides that it will use the heating equipment
priority to determine which system will run first. If the
radiant system is serving a zone with forced air equipment,
the radiant system will follow the priority order established
by the zone thermostat but will still base its response on the
controls defined by the user for the radiant system.
The constant flow system differs from the hydronic system
describe above in what it controls. The hydronic system varies
the flow rate through the radiant system based on some control
temperature. The constant flow system keeps flow rate constant
via a local circulation pump and varies the water temperature
that is sent to the radiant system. This is accomplished with
a mixing valve that is controlled by a sensor. This model
covers a wide range of low temperature radiant systems:
heating and/or cooling, panel or embedded pipes, etc. It is
not intended to simulate high temperature electric or gas
radiant heaters. Those devices will be handled by a separate
model and different input syntax. Low temperature radiant
systems that use electric resistance heating should also be
defined using separate input syntax (ref:
ZoneHVAC:LowTemperatureRadiant:Electric). Low temperature
radiant systems that vary the flow rate through the radiant
system should also be defined using separate input syntax
(ref: ZoneHVAC:LowTemperatureRadiant:VariableFlow)
One of the other differences between this model and the
variable flow hydronic radiant system is that the constant
flow radiant system has a built-in local secondary loop. It
will recirculate flow coming out of the system and mix this
with flow from the loop to arrive at the desired inlet
temperature to the radiant system (note that this model has
the temperature sensor AFTER the pump to insure proper inlet
temperature to the radiant system). The local loop also
contains a pump which is assumed to be upstream of the radiant
system and after the mixing valve. So, the local loop can have
some recirculation. The flow from the main loop may also
bypass the radiant system if more than enough flow is
available and the main loop is also a constant flow
system.
This field is an unique user assigned name for an instance
of a constant flow low temperature radiant system. Any
reference to this unit by another object will use this
name.
This field is the name of the schedule (ref: Schedule) that
denotes whether the constant flow low temperature radiant
system can run during a given time period. A schedule value
less than or equal to 0 (usually 0 is used) denotes that the
unit must be off for that time period. A value greater than 0
(usually 1 is used) denotes that the unit is available to
operate during that time period. If this field is left blank,
the schedule has a value of 1 for all time periods.
This field is the name of the zone (Ref: Zone) in which the
constant flow low temperature radiant system is principally
located and intended to affect. A system that is between two
zones will still act upon each zone; however, the zone name
referenced here should be the zone that controls the radiant
system response.
Field:
Surface Name or Radiant Surface Group Name[LINK]
This field is the name of the surface (Ref:
BuildingSurface:Detailed) or surface list (Ref:
ZoneHVAC:LowTemperatureRadiant:SurfaceGroup) in which the
hydronic tubing is embedded/contained. This specification
attaches the source or sink from the radiant system to a
particular surface and the contribution of the system to the
heat balances of that surface. If this field is a surface
list, then the source or sink is attached to all of the
surfaces in the list with the radiant system surface group
defining the breakdown of how flow rate is split between the
various surfaces. Base surfaces (e.g.,
BuildingSurface:Detailed), door surfaces and internal mass are
valid. Window
surfaces are not valid surface types for embedded radiant
systems.
This field is the inside diameter of the tubes through
which water is circulated for the system being defined by this
statement. The inside diameter should be recorded in meters
and is used to determine the convective heat transfer from the
water to the inside surface of the hydronic tubing.
This field is the total length of pipe embedded in the
surface named above in the surface name field. The length of
the tube should be entered in meters and is used to determine
the effectiveness of heat transfer from the fluid being
circulated through the tubes and the tube/surface. Longer
tubing lengths result in more heat being transferred to/from
the radiant surface to the circulating fluid. Note that if the
user elects to autosize this field that a standard zone
thermostat such as would be used for a forced air system must
be defined as autosizing calculations are based on the zone
thermostat value and not on the radiant system control values.
In addition, when the user opts to autosize this calculation,
the tube spacing from the construction of each surface
associated with this system is used along with each individual
surface area to make an approximation of the tubing
length.
This field specifies along with setpoint (control) and
water schedules how the user wishes to control the constant
flow radiant system. The temperature denoted in the setpoint
schedule can refer to one of five different temperatures: the
zone mean air temperature, the zone mean radiant temperature,
the zone operative temperature, the outdoor dry-bulb
temperature, or the outdoor wet-bulb temperature. The choice
of temperature is controlled by the current field—temperature
control type. The user must select from the following
options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
OutdoorDryBulbTemperature
OutdoorWetBulbTemperature
Operative temperature for radiant system controls is the
average of Mean Air Temperature and Mean Radiant Temperature.
If the user does not select a control type,
MeanAirTemperature control is assumed by
EnergyPlus. See the throttling range and control temperature
schedule fields below for more information.
This field is the maximum flow rate of water through the
radiant system in m\(^{3}\)/sec. This flow rate is
held constant by the local component pump, but the user has
the option of varying this flow rate via a schedule (see next
input field). The constant flow system will accept this flow
rate and control the inlet temperature based on the control
and water temperature schedules defined below. This field is
autosizable.
This field modifies the maximum flow rate of water through
the radiant system in m\(^{3}\)/sec. This input is
“optional”. If the user does not enter a schedule, the flow
rate through the radiant system is assumed to be constant
during all hours that it is operating based on the value
entered in the previous input field. Note that the values for
this schedule must be between zero and one. The values in this
schedule are multipliers on the previous field – Rated Flow
Rate.
This field contains the name of the hot water inlet node to
the radiant system. Note that this node name must also show up
in the branch description when defining the plant demand side
network in a manner identical to defining a heating coil.
This field contains the name of the hot water outlet node
to the radiant system. Note that this node name must also show
up in the branch description when defining the plant demand
side network in a manner identical to defining a heating
coil.
Field:
Heating High Water Temperature Schedule Name[LINK]
This field specifies the high water temperature in degrees
Celsius for the temperature control of a constant flow radiant
heating system. Water and control temperatures for heating
work together to provide a linear function that determines the
water temperature sent to the radiant system. The current
control temperature (see Temperature Control Type above) is
compared to the high and low control temperatures at the
current time. If the control temperature is above the high
temperature, then the system will be turned off and the water
mass flow rate will be zero. If the control temperature is
below the low temperature, then the inlet water temperature is
set to the high water temperature. If the control temperature
is between the high and low value, then the inlet water
temperature is linearly interpolated between the low and high
water temperature values. For more information and a graph of
how the water and control schedules affect the system
operation, please consult the Engineering Reference
document.
Field:
Heating Low Water Temperature Schedule Name[LINK]
This field specifies the low water temperature in degrees
Celsius for the temperature control of a constant flow heating
radiant system. For more information on its interpretation,
see Heating High Water Temperature Schedule above.
Field:
Heating High Control Temperature Schedule Name[LINK]
This field specifies the high control temperature in
degrees Celsius for the temperature control of a constant flow
heating radiant system. For more information on its
interpretation, see Heating High Water Temperature Schedule
above.
Field:
Heating Low Control Temperature Schedule Name[LINK]
This field specifies the low control temperature in degrees
Celsius for the temperature control of a constant flow heating
radiant system. For more information on its interpretation,
see Heating High Water Temperature Schedule above.
This field contains the name of the cold water inlet node
to the radiant system. Note that this node name must also show
up in the branch description when defining the plant demand
side network in a manner identical to defining a cooling coil.
As with the maximum cold water flow rate, this field is
optional and not required for a heating only system.
This field contains the name of the cold water outlet node
to the radiant system. Note that this node name must also show
up in the branch description when defining the plant demand
side network in a manner identical to defining a cooling coil.
As with the maximum cold water flow rate, this field is
optional and not required for a heating only system.
Field:
Cooling High Water Temperature Schedule Name[LINK]
This field specifies the high water temperature in degrees
Celsius for the temperature control of a constant flow radiant
cooling system. Water and control temperatures for heating
work together to provide a linear function that determines the
water temperature sent to the radiant system. The current
control temperature (see Temperature Control Type above) is
compared to the high and low control temperatures at the
current time. If the control temperature is above the high
temperature, then the inlet water temperature is set to the
low water temperature. If the control temperature is below the
low temperature, then system will be turned off and the water
mass flow rate will be zero. If the control temperature is
between the high and low value, then the inlet water
temperature is linearly interpolated between the low and high
water temperature values. For more information and a graph of
how the water and control schedules affect the system
operation, please consult the Engineering Reference
document.
Field:
Cooling Low Water Temperature Schedule Name[LINK]
This field specifies the low water temperature in degrees
Celsius for the temperature control of a constant flow cooling
radiant system. For more information on its interpretation,
see Cooling High Water Temperature Schedule above.
Field:
Cooling High Control Temperature Schedule Name[LINK]
This field specifies the high control temperature in
degrees Celsius for the temperature control of a constant flow
cooling radiant system. For more information on its
interpretation, see Cooling High Water Temperature Schedule
above.
Field:
Cooling Low Control Temperature Schedule Name[LINK]
This field specifies the low control temperature in degrees
Celsius for the temperature control of a constant flow cooling
radiant system. For more information on its interpretation,
see Cooling High Water Temperature Schedule above.
When radiant systems do cooling, there is the possibility
that condensation will occur on the surface that is being
cooled. This is due to the fact that the surface temperature
may drop below the dew-point temperature of the space. When
this happens, condensation on the surface will occur. There
are three options for handling this situation: Off, SimpleOff,
and VariableOff. This parameter is optional and will default
to SimpleOff.
Off - EnergyPlus will not do anything other than
produce a warning message when condensation is predicted to
occur. The program will simply continue on; no moisture will
be removed from the zone air and there will be no adjustment
of the surface temperature as a result of the
condensation.
SimpleOff - the program will predict cases where
condensation will occur and shut-off the radiant system to
avoid this situation. With this option, the users also have
the opportunity to adjust when the system will shut down. This
is specified with the next parameter (field: Condensation
Control Dewpoint Offset).
VariableOff - the program will determine whether
condensation is predicted for the flow rate determined by the
unit control scheme. If condensation is predicted, the unit
makes one attempt to avoid condensation by increasing the
water inlet temperature to the system to match the dew-point
temperature modified by the condensation control dew-point
offset (field: Condensation Control Dewpoint Offset). For
example, if a surface in the space is predicted to be 15°C and
the modified condensation dew-point temperature is 17°C, then
the inlet water temperature to the unit is reset to 17°C and
the system is simulated again with this new inlet water
temperature. If this increased inlet water temperature does
not result in condensation, then the simulation continues
using this operating condition for the system. If the
increased inlet water temperature still results in
condensation, then the unit is turned off to avoid excessive
iterations.
This optional parameter is only valid with the SimpleOff
and VariableOff condensation handling algorithm (see previous
input parameter). It establishes the difference between the
calculated dew-point temperature of the space and the allowed
surface temperature to which the surface can drop before the
radiant system shuts down (SimpleOff) or tries to adjust the
inlet water temperature (VariableOff) in degrees Celsius. This
parameter can be any positive, negative, or zero value. When
this parameter is zero, the radiant system will shut down or
adjust the inlet water temperature when the surface
temperature drops to the dew-point temperature or below. When
this parameter is positive, the radiant system will shut down
or increase the inlet water temperature when the surface is
the number of degrees Celsius above the dew-point temperature.
This allows some extra safety to avoid condensation. When this
parameter is negative, the radiant system will shut down or
increase the inlet water temperature when the surface
temperature is the number of degrees Celsius below the
dew-point temperature. While not recommended, this strategy
allows the user to simulate a situation where small amounts of
condensation are tolerable. The default value for this
parameter is 1°C.
This optional input allows the user to choose between
modeling each surface in the radiant system as a single
hydronic circuit or to allow the program to divide the surface
into multiple parallel hydronic circuits based on the next
input field Circuit Length. To model as a single
circuit choose OnePerSurface. To model as multiple
circuits choose CalculateFromCircuitLength. It is
recommended that CalculateFromCircuitLength be
chosen. The default is OnePerSurface for backward
compatibility with older versions of EnergyPlus.
The length in meters of each parallel hydronic circuit in a
surface. Used when the previous input field is set to
CalculateFromCircuitLength. The default is 106.7
meters (350 feet), which is the maximum circuit length allowed
in Title 24.
An example IDF with a constant flow low temperature radiant
system is shown below.
ZoneHVAC:LowTemperatureRadiant:ConstantFlow,
Resistive Zone Radiant Floor, !- name of CONSTANT FLOW low temperature radiant system
RadiantSysAvailSched, !- availability schedule
Resistive Zone, !- Zone name
Zn001:Flr001, !- Surface name or group
0.012, !- Hydronic tubing inside diameter {m}
400.0, !- Hydronic tubing length {m}
MeanAirTemperature, !- temperature control type
0.0004, !- maximum water volumetric flow rate {m3/s}
, !-schedule for flow rate (optional, non-existent means constant)
30000, !-Rated Pump Head in Pa
50, !-Rated Power Consumption in W
0.87, !-Motor Efficiency
0.1, !-Fraction of Motor Inefficiencies to Fluid Stream
Resistive Zone Radiant Water Inlet Node, !- heating water inlet node
Resistive Zone Radiant Water Outlet Node, !- heating water outlet node
RadHeatHighWaterTemp, !-high water temperature schedule
RadHeatLowWaterTemp, !-low water temperature schedule
RadHeatHighControlTemp, !-high control temperature schedule
RadHeatLowControlTemp, !-low control temperature schedule
Zone 1 Cooling Water Inlet Node, !- cooling water inlet node
Zone 1 Cooling Water Outlet Node, !- cooling water outlet node
RadCoolHighWaterTemp, !-cooling high water temperature schedule
RadCoolLowWaterTemp, !-cooling low water temperature schedule
RadCoolHighControlTemp, !- cooling high control temperature schedule
RadCoolLowControlTemp, !- cooling low control temperature schedule
SimpleOff, !- condensation control type
0.5, !- condensation control dewpoint offset
CalculateFromCircuitLength, !- Number of Circuits
106.7; !- Circuit Length
This field reports the heating input rate to the low
temperature radiant system in Watts. This is the heat source
to the surface that is defined as the radiant system. The
heating rate is determined by the zone conditions and the
control scheme defined in the user input.
This field reports the heating input to the low temperature
radiant system in Joules. This is the heat source to the
surface that is defined as the radiant system. The heating
rate is determined by the zone conditions, the control scheme
defined in the user input, and the timestep.
This field reports the cooling input rate to the low
temperature radiant system in Watts. This is the heat sink to
the surface that is defined as the radiant system. The cooling
rate is determined by the zone conditions and the control
scheme defined in the user input.
This field reports the cooling input to the low temperature
radiant system in Joules. This is the heat sink to the surface
that is defined as the radiant system. The cooling rate is
determined by the zone conditions, the control scheme defined
in the user input, and the timestep.
This field reports the mass flow rate of water through the
low temperature radiant system in kilograms per second. This
should be identical to the pump flow rate for the system.
Zone
Radiant HVAC Injection Mass Flow Rate [kg/s][LINK]
This field reports the mass flow rate of water that is
injected into the radiant system from the main loop. A valve
will control the injection and recirculation mass flow rates
(see next field) to match the temperature controls specified
by the user and dictated by the current simulation
conditions.
Zone
Radiant HVAC Recirculation Mass Flow Rate [kg/s][LINK]
This field reports the mass flow rate of water that is
recirculated from the radiant system outlet and mixed with the
injection flow from the main loop. A valve will control the
injection and recirculation mass flow rates (see next field)
to match the temperature controls specified by the user and
dictated by the current simulation conditions.
This field reports the temperature of water entering the
low temperature radiant system in Celsius. This may differ
from the inlet node temperature for the component since this
component has its own local secondary loop.
This field reports the temperature of water leaving the low
temperature radiant system in Celsius. This may differ from
the outlet node temperature for the component since this
component has its own local secondary loop.
Zone
Radiant HVAC Pump Inlet Temperature [C][LINK]
This field reports the temperature of water entering the
low temperature radiant system pump in Celsius. This may
differ from the inlet node temperature for the component since
this component has its own local secondary loop. It is assumed
that the pump is upstream of the radiant system.
This field reports the electric power consumption for the
pump which supplies flow to the constant flow radiant system
in Joules.
Zone
Radiant HVAC Pump Mass Flow Rate [kg/s][LINK]
This field reports the mass flow rate of water through the
low temperature radiant system pump in kilograms per second.
This should be identical to the flow rate for the system.
Zone
Radiant HVAC Pump Fluid Heat Gain Rate [W][LINK]
This field reports the rate at which heat is added to the
fluid stream as it passes through the pump in Watts. This heat
is reflected in the radiant system inlet temperature which
will be different from the pump inlet temperature if this
field has a non-zero value.
Zone
Radiant HVAC Pump Fluid Heat Gain Energy [J][LINK]
This field reports the amount of heat energy added to the
fluid stream as it passes through the pump in Joules. This
heat is reflected in the radiant system inlet temperature
which will be different from the pump inlet temperature if
this field has a non-zero value.
Zone
Radiant HVAC Moisture Condensation Time [s][LINK]
This field reports the amount of time when condensation is
occurring. When using the Off condensation control, this
simply reports the amount of time when condensation occurs.
When using the SimpleOff condensation control, this indicates
the amount of time when the system has been shut off because
of the potential danger of condensation.
Zone
Radiant HVAC Cooling Fluid Heat Transfer Energy [J][LINK]
The heat transfer energy for the cooling fluid connection,
in Joules.
Zone
Radiant HVAC Heating Fluid Heat Transfer Energy [J][LINK]
The heat transfer energy for the heating fluid connection,
in Joules.
This low temperature radiant system (electric) is a
component of zone equipment that is intended to model any
“radiant system” where electric resistance heating is used to
supply energy (heat) to a building surface (wall, ceiling, or
floor). The component is controlled by the radiant system
controls that are defined in the syntax below and this control
does not require the use of a zone thermostat unless the unit
is being autosized. Note also that because this unit does not
require a thermostat that in cases where no other systems are
serving the zone in which this system resides that it will use
the heating equipment priority to determine which system will
run first. If the radiant system is serving a zone with forced
air equipment, the radiant system will follow the priority
order established by the zone thermostat but will still base
its response on the controls defined by the user for the
radiant system.
The control is accomplished by varying the electrical power
supplied to the unit. This model covers either a radiant panel
system or wires embedded in entire walls, floors, or ceilings.
It is not intended to simulate high temperature electric or
gas radiant heaters. Those devices will be handled by a
separate model (ref: ZoneHVAC:HighTemperatureRadiant) and
different input syntax. Low temperature radiant systems that
use water flowing through tubes to provide heat to the system
should also be defined using separate input syntax (ref: ZoneHVAC:LowTemperatureRadiant:VariableFlow
or ConstantFlow).
This field is an unique user assigned name for an instance
of an electric low temperature radiant system. Any reference
to this unit by another object will use this name.
This field is the name of the schedule (ref: Schedule) that
denotes whether the electric low temperature radiant system
can operate during a given time period. A schedule value less
than or equal to 0 (usually 0 is used) denotes that the unit
must be off for that time period. A value greater than 0
(usually 1 is used) denotes that the unit is available to
operate during that time period. If this field is left blank,
the schedule has a value of 1 for all time periods.
This field is the name of the zone (Ref: Zone) in which the
electric low temperature radiant system is principally located
and intended to affect. A system that is between two zones
will still act upon each zone; however, the zone name
referenced here should be the zone that controls the radiant
system response.
Field:
Surface Name or Radiant Surface Group Name[LINK]
This field is the name of the surface (Ref:
BuildingSurface) or surface list (Ref:
ZoneHVAC:LowTemperatureRadiant:SurfaceGroup) in which the
heating element is embedded/contained. This specification
attaches the source or sink from the radiant system to a
particular surface and the contribution of the system to the
heat balances of that surface. If this field is a surface
list, then the source or sink is attached to all of the
surfaces in the list with the radiant system surface group
defining the breakdown of how energy flow is split between the
various surfaces. Base surfaces (e.g., BuildingSurface:Detailed,Wall:Detailed,RoofCeiling:Detailed,
etc.), door surfaces and internal mass are valid. Window
surfaces are not valid surface types for embedded radiant
systems.
Enter the method used to determine the maximum electrical
power (heating design capacity ) or enter the method for
scalable sizing the maximum electrical power of low
temperature radiant electric unit. Input allowed is either
HeatingDesignCapacity, CapacityPerFloorArea,
and FractionOfAutosizedHeatingCapacity. If this input
field is left blank or zero, then autosizing is assumed.
HeatingDesignCapacity means user specifies the
magnitude of maximum or nominal heating capacity or the
program calculates the maximum or nominal design heating
capacity if autosize is specified.
CapacityPerFloorArea means the program calculates the
design heating capacity from user specified heating capacity
per floor area and floor area of the zone served by the low
temperature radiant electric unit.
FractionOfAutosizedHeatingCapacity means the program
calculates the design heating capacity from user specified
fraction and the auto-sized design heating capacity. The
default method is HeatingDesignCapacity.
This field is for the maximum amount of electric energy
rate (electric power) converted into heat in low temperature
radiant electric unit in watts. This input field is
autosizable. The controls for the radiant system will vary the
amount of power supplied to the surface between zero input and
the maximum power specified in this field as the lower and
upper bounds, respectively. Note that if the user elects to
autosize this field that a standard zone thermostat such as
would be used for a forced air system must be defined as
autosizing calculations are based on the zone thermostat value
and not on the low temperature radiant electric unit control
values. The default input for this input field is
autosize.
Field:
Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2
of low temperature radiant electric system. This field is
required field when the Heating Design Capacity Method is
CapacityPerFloorArea. The program calculates the
heating capacity from floor area of the zone served by the low
temperature radiant electric unit and the heating capacity per
unit floor area value specified by the user. This field may be
left blank.
Field:
Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized
heating capacity of low temperature radiant electric unit.
This input field is required when the Heating Design Capacity
Method is FractionOfAutosizedHeatingCapacity. The
program calculates the heating capacity from the design
autosized heating capacity and user specified fraction. Design
day sizing must be specified. This field may be left blank.
The default value is 1.0.
This field specifies along with the throttling range and
setpoint schedules how the user wishes to control the low
temperature electric radiant system. The temperature denoted
in the setpoint schedule can refer to one of three different
temperatures: the zone mean air temperature, the zone mean
radiant temperature, the zone operative temperature, the
outdoor dry-bulb temperature, or the outdoor wet-bulb
temperature. The choice of temperature is controlled by the
current field—temperature control type. The user must select
from the following options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
OutdoorDryBulbTemperature
OutdoorWetBulbTemperature
Operative temperature for radiant system controls is the
average of Mean Air Temperature and Mean Radiant Temperature.
If the user does not select a control type,
MeanAirTemperature control is assumed by
EnergyPlus. See the throttling range and control temperature
schedule fields below for more information.
This field specifies the range of temperature in degrees
Celsuis over which the radiant system throttles from zero heat
input via the electric resistance wires up to the maximum
defined by the maximum electrical power field described above.
The throttling range parameter is used in conjunction with the
control temperature (see below) to define the response of the
system to various zone conditions. The heating control
temperature schedule specifies the “setpoint” temperature
where the power input to the system is at half of the maximum
power input. For example, if the heating control temperature
setpoint is currently 15°C and the heating throttling range is
2°C, the electrical power supplied to the radiant system will
be zero when the controlling temperature (MAT, MRT, Operative
Temperature, ODB, or OWB; see control type field above) is at
or above 16°C and the maximum power input when the controlling
temperature is at or below 14°C. This represents a throttling
range of 2°C around the setpoint of 15°C. In between 14°C and
16°C, the power input to the radiant system is varied
linearly. The minimum throttling range is 0.5°C.
Field:
Heating Setpoint Temperature Schedule Name[LINK]
This field specifies the heating setpoint or control
temperature for the radiant system in degrees Celsius. Used in
conjunction with the previous field (heating throttling
range), it will define whether or not the system is running
and the current power input to the radiant surface. Power
input to the system is varied linearly around the setpoint
temperature based on the throttling range and the maximum
electrical power parameters (see above). It should be noted
that this control schedule will allow different setpoint
temperatures throughout the year for heating. In addition,
this schedule may be different that the thermostatic control
schedule defined for overall operation of components serving
the zone in which the radiant system is located. The
thermostatic control determines whether or not there is a
heating or cooling load in the space and thus whether the
systems should be operating. This field simply controls the
flow rate to the radiant system.
An example IDF with an electric low temperature radiant
system is shown below.
ZoneHVAC:LowTemperatureRadiant:Electric,
Zone 2 Radiant Floor, !- Name
RadiantPanelAvailSched , !- Availability Schedule Name
EAST ZONE , !- Zone name (name of zone system is serving)
Zn002:Flr001 , !- Surface Name or Radiant Surface Group Name
HeatingDesignCapacity, !- Heating Design Capacity Method
10000, !- Heating Design Capacity{ W }
, !- Heating Design Capacity Per Floor Area{ W/m2 }
, !- Fraction of Autosized Heating Design Capacity{ - }
MeanAirTemperature, !- Temperature Control Type (control on mean air temperature)
2.0 , !- Heating Throttling Range { deltaC }
Radiant Heating Setpoints ; !- Heating Setpoint Temperature Schedule Name
This field reports the rate at which electric energy is
“burned” in the low temperature radiant system in Watts. This
is the heat source to the surface that is defined as the
radiant system. The heating rate is determined by the zone
conditions and the control scheme defined in the user
input.
This field reports the amount of electric energy “burned”
in the low temperature radiant system in Joules. This is the
heat source to the surface that is defined as the radiant
system. The heating rate is determined by the zone conditions,
the control scheme defined in the user input, and the
timestep.
A low temperature radiant system (hydronic or electric) may
consist of multiple active surfaces that serve to condition
the space. Surfaces that act serially can be specified as
multiple radiant systems using the standard radiant system
input described above. However, if the multiple surfaces act
in parallel, the Radiant System Surface Group input line is
used to specify which surfaces are acting in a coordinated
fashion and how energy flow is split between the surfaces.
This list of surfaces (the name it is assigned) replaces the
name of a single surface in the radiant system input described
above. Note that all of the surfaces within a single list must
be a part of the same zone and that the zone of these surfaces
must also match the zone the radiant system is attempting to
condition.
This field is an unique user assigned name for the list of
surfaces that are acting in coordination with one another. Any
reference to this list by a radiant system will use this
name.
Field
Set: Surface Name, Flow Fraction to Surface[LINK]
The pairs of Surface Name, Flow Fraction to Surface are
used in several objects. There can be up to 10 specified. The
object is extensible so more can be added.
This field is the name of a surface in the zone being
conditioned by the radiant system. Base surfaces (e.g.,
BuildingSurface:Detailed), door surfaces and internal mass are
valid. Window
surfaces are not valid surface types for embedded radiant
systems.
This field is the fraction of the total radiant system flow
rate that is being sent to this particular surface. Note that
the Surface Name/Surface Flow Fraction pair can be repeated up
to 10 times. Flow rate fractions must sum to unity, otherwise
the program will not accept the input as valid.
An example IDF with an electric low temperature radiant
system is shown below.
ZoneHVAC:LowTemperatureRadiant:SurfaceGroup,
Zone 1 Radiant Surfaces, !- name of surface list
Zn001:Flr001, !- Surface name 1
0.75, !- Flow fraction for surface 1
Zn001:Roof001, !- Surface name 2
0.25; !- Flow fraction for surface 2
The high temperature radiant system (gas-fired or electric)
is a component of zone equipment that is intended to model any
“high temperature” or “high intensity” radiant system where
electric resistance or gas-fired combustion heating is used to
supply energy (heat) to a building occupants directly as well
as the building surfaces (wall, ceiling, or floor). The
component is controlled by the radiant system controls defined
in the syntax below and this control does not require the use
of a zone thermostat unless the unit is being autosized. Note
also that because this unit does not require a thermostat that
in cases where no other systems are serving the zone in which
this system resides that it will use the heating equipment
priority to determine which system will run first. If the
radiant system is serving a zone with forced air equipment,
the radiant system will follow the priority order established
by the zone thermostat but will still base its response on the
controls defined by the user for the radiant system.
The control is accomplished by varying the electrical power
supplied to or gas consumed by the unit. It is not intended to
simulate low temperature electric or hydronic radiant systems.
Those devices will be handled by a separate model and
different input syntax (ref: the low temperature systems
described elsewhere).
This field is an unique user assigned name for an instance
of the high temperature radiant system. Any reference to this
unit by another object will use this name.
This field is the name of the schedule (ref: Schedule) that
denotes whether the high temperature radiant system can
operate during a given time period. A schedule value less than
or equal to 0 (usually 0 is used) denotes that the unit must
be off for that time period. A value greater than 0 (usually 1
is used) denotes that the unit is available to operate during
that time period. If this field is left blank, the schedule
has a value of 1 for all time periods.
Enter the method used to determine the maximum electrical
power (heating design capacity ) or enter the method for
scalable sizing the maximum electrical power of high
temperature radiant system unit. Input allowed is either
HeatingDesignCapacity, CapacityPerFloorArea,
and FractionOfAutosizedHeatingCapacity. If this input
field is left blank or zero, then autosizing is assumed.
HeatingDesignCapacity means user specifies the
magnitude of maximum or nominal heating capacity or the
program calculates the maximum or nominal design heating
capacity if autosize is specified.
CapacityPerFloorArea means the program calculates the
design heating capacity from user specified heating capacity
per floor area and floor area of the zone served by the high
temperature radiant electric unit.
FractionOfAutosizedHeatingCapacity means the program
calculates the design heating capacity from user specified
fraction and the auto-sized design heating capacity. The
default method is HeatingDesignCapacity.
This field is for the maximum amount of electric energy
rate (electric power) converted into heat in high temperature
radiant electric unit in watts. This input field is
autosizable. The controls for the radiant system will vary the
amount of power supplied to the surface between zero input and
the maximum power specified in this field as the lower and
upper bounds, respectively. Note that if the user elects to
autosize this field that a standard zone thermostat such as
would be used for a forced air system must be defined as
autosizing calculations are based on the zone thermostat value
and not on the radiant system control values. The default
input for this field is autosize.
Field:
Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2
of high temperature radiant electric unit. This field is
required field when the Heating Design Capacity Method is
CapacityPerFloorArea. The program calculates the
heating capacity from floor area of the zone served by the
high temperature radiant electric unit and the heating
capacity per unit floor area value specified by the user. This
field may be left blank.
Field:
Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized
heating capacity for high temperature radiant electric unit.
This input field is required when the Heating Design Capacity
Method is FractionOfAutosizedHeatingCapacity. The
program calculates the heating capacity from the design
autosized heating capacity and user specified fraction. Design
day sizing run must be specified. This field may be left
blank. The default value is 1.0.
This field denotes the type of high temperature radiant
heater: gas or electric. The user must specify this by
inputting either the keyword “NaturalGas” or
“Electricity” for this field.
This field is the combustion efficiency for a gas high
temperature radiant heater. This value should be greater than
0 and less than or equal to 1. It is intended to take into
account any potential inefficiencies in the combustion process
inside the radiant heater. The heater gas consumption is the
ratio of heater output over the combustion efficiency. This
parameter has no meaning for an electric high temperature
radiant heater and is ignored when the previous field is equal
to “Electric”.
Field:
Fraction of Input Converted to Radiant Energy[LINK]
This field specifies what fraction of the power input to
the high temperature radiant heater is actually radiant heat
transfer. The fraction should be between 0 and 1. In
conjunction with the next two parameters, it defines the
breakdown of how the power input to the heater is distributed
to the rest of the zone. The sum of these fractions must be
less than or equal to 1. If the fractions are less than one,
the remaining energy is added to the zone as convective heat
transfer. The radiant heat transfer from the heat is
distributed to people and surfaces using the distribution
fractions listed below.
Field:
Fraction of Input Converted to Latent Energy[LINK]
This field specifies the fraction of the power input to the
high temperature radiant heater that is converted to a latent
heat gain within the space. This may be appropriate when a
combustion process produces moisture that is transferred into
the space. The latent heat addition from a high temperature
radiant heater is handled as any other latent heat gain within
the space, affecting the moisture balance on the zone air.
This field specifies the fraction of power input to the
high temperature radiant heater that is “lost”. This energy is
a loss term, and this fraction of the input power has no
effect on the zone heat balances.
This field specifies along with the throttling range and
setpoint schedules how the user wishes to control the high
temperature radiant system. The temperature denoted in the
setpoint schedule can refer to one of three different
temperatures: a mean air temperature, a mean radiant
temperature, or an operative temperature. The choice of
temperature is controlled by the current field—temperature
control type. The user must select from the following
options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
MeanAirTemperatureSetpoint
MeanRadiantTemperatureSetpoint
OperativeTemperatureSetpoint
If the user does not select a control type,
OperativeTemperature control is assumed by EnergyPlus. For the
setpoint control strategies (those ending in Setpoint above),
EnergyPlus will attempt to find the correct heater output to
meet the heating setpoint temperature (see below) through
iteration and interpolation. This will more closely match the
operation of an actual thermostat, but it will require
significantly longer execution times. For more information on
the standard piecewise linear control algorithm used by the
Mean Air Temperature, Mean Radiant Temperature, and Operative
Temperature control types (the “non-Setpoint” controls), see
the throttling range and control temperature schedule fields
below for more information.
This field specifies the range of temperature in degrees
Celsuis over which the radiant system throttles from zero heat
input via the electric resistance wires up to the maximum
defined by the maximum electrical power field described above.
The throttling range parameter is used in conjunction with the
control temperature (see below) to define the response of the
system to various zone conditions. The heating control
temperature schedule specifies the “setpoint” temperature
where the power input to the system is at half of the maximum
power input. For example, if the heating control temperature
setpoint is currently 15°C and the heating throttling range is
2°C, the electrical power supplied to the radiant system will
be zero when the controlling temperature (Mean Air
Temperature, Mean Radiant Temperature, and Operative
Temperature; see control type field above) is at or above 16°C
and the maximum power input when the controlling temperature
is at or below 14°C. This represents a throttling range of 2°C
around the setpoint of 15°C. In between 14°C and 16°C, the
power input to the radiant system is varied linearly.
Field:
Heating Setpoint Temperature Schedule Name[LINK]
This field specifies the heating setpoint or control
temperature for the radiant system in degrees Celsius. Used in
conjunction with the previous field (heating throttling
range), it will define whether or not the system is running
and the current power input to the radiant surface. Power
input to the system is varied linearly around the setpoint
temperature based on the throttling range and the maximum
electrical power parameters (see above). It should be noted
that this control schedule will allow different setpoint
temperatures throughout the year for heating. In addition,
this schedule may be different that the thermostatic control
schedule defined for overall operation of components serving
the zone in which the radiant system is located. The
thermostatic control determines whether or not there is a
heating or cooling load in the space and thus whether the
systems should be operating. This field simply controls the
flow rate to the radiant system.
Field:
Fraction of Radiant Energy Incident on People[LINK]
This field specifies the fraction of radiant heat transfer
to the zone from the radiant heater that is incident directly
on people within the space. This has an impact on the
predicted thermal comfort of the zone occupants. Note that
since the thermal comfort models only use the results of the
zone heat balances this energy is accounted for within the
heat balance as convective energy, directly affecting the zone
air heat balance. The basic assumption here is that most
radiant energy falling on people will most likely be convected
to the surroundings. This is a simplification of reality, but
it maintains the overall energy balance.
Field
Set: Surface Name, Fraction of radiant energy to Surface[LINK]
The pairs of Surface Name, Fraction of Radiant Energy to
Surface are used in several objects. There can be up to 20
specified.
This field is the name of the first surface to which
radiant heat transfer from the high temperature radiant heater
is distributed. Used in conjunction with the next field, it
helps to define the distribution of the radiant energy on the
surfaces within the zone. Note that up to 20 pairs of surface
names and corresponding fractions may be entered for a single
radiant heater system.
Field:
Fraction of Radiant Energy to Surface <x>[LINK]
This field is paired with the preceding surface name
(previous field) to define the fraction of radiant heat
transfer leaving the high temperature radiant system that is
incident on a particular surface. Users should take into
account the directionality of high temperature radiant heaters
and their location when defining the value for this input
field. Note that the sum of all fractions plus the fraction of
radiant energy incident on people must add up to 1 so that all
radiant energy is taken into account and none of it is
“lost”.
An example IDF with a high temperature radiant system is
shown below.
ZoneHVAC:HighTemperatureRadiant, Zone 2 Radiant Heater,
RadiantPanelAvailSched , !- Availability schedule
EAST ZONE , !- Zone name (name of zone system is serving)
10000, !- Heating Design Capacity{ W }
, !- Heating Design Capacity Per Floor Area{ W / m2 }
, !- Fraction of Autosized Heating Design Capacity{ -}
Gas, !- type of heater (either gas or electric)
0.8, !- combustion efficiency (ignored for electric radiant heaters)
0.80, !- fraction radiant
0.00, !- fraction latent
0.00, !- fraction lost
OperativeTemperature, !- temperature control type (controls on operative temperature)
2.0 , !- heating throttling range (in C)
Radiant Heating Setpoints, !- heating setpoint temperatures
0.04, !- fraction of radiant energy that is incident directly on people
Zn002:Flr001, 0.80, !- fraction of radiant energy that is incident on the surface indicated
Zn002:Wall001, 0.04, !- fraction of radiant energy that is incident on the surface indicated
Zn002:Wall002, 0.04, !- fraction of radiant energy that is incident on the surface indicated
Zn002:Wall003, 0.04, !- fraction of radiant energy that is incident on the surface indicated
Zn002:Wall004, 0.04; !- fraction of radiant energy that is incident on the surface indicated
This field reports the rate at which energy is transferred
from the high temperature radiant system to the zone in Watts.
This rate is determined by the zone conditions and the control
scheme defined in the user input. Note that this amount takes
into account any combustion inefficiency and thus could be
different that the gas consumption rate in a high temperature
gas radiant system.
This field reports the amount of energy transferred from
the high temperature gas radiant system to the zone in Joules.
This amount is determined by the zone conditions, the control
scheme defined in the user input, and the timestep. Note that
this amount takes into account any combustion inefficiency and
thus could be different that the gas consumption in a high
temperature gas radiant system.
This field reports the rate at which gas is “burned” in a
high temperature gas radiant system in Watts. This rate is
determined by the zone conditions and the control scheme
defined in the user input.
This field reports the amount of gas “burned” in a high
temperature gas radiant system in Joules. This amount is
determined by the zone conditions, the control scheme defined
in the user input, and the timestep.
This field reports the rate at which electric energy is
“burned” in a high temperature electric radiant system in
Watts. This rate is determined by the zone conditions and the
control scheme defined in the user input.
This field reports the amount of electric energy “burned”
in a high temperature electric radiant system in Joules. This
amount is determined by the zone conditions, the control
scheme defined in the user input, and the timestep.
Ventilated slab systems in general use outdoor air to
“precool” slabs with colder nighttime air. This method of
precooling the thermal mass of a space can be very effective
when nighttime temperatures are low and the mass of the system
is high enough to provide a significant amount of cooling
potential during the day to counteract internal heat gains
within a zone. Nearly all ventilated slabs are simple systems
such as that shown in the right side of Figure.
The fan is shown in a blow through position, but the model
will allow either a blow or draw through configuration.
This field is a unique user assigned name for an instance
of a ventilated slab system. Any reference to this unit by
another object will use this name. Other objects that use this
ventilated slab system will reference it by this name.
This field is the name of the schedule (ref: Schedule) that
denotes whether the ventilated slab system can run during a
given time period. A schedule value less than or equal to 0
(usually 0 is used) denotes that the unit must be off for that
time period. A value greater than 0 (usually 1 is used)
denotes that the unit is available to operate during that time
period. If this field is left blank, the schedule has a value
of 1 for all time periods.
This field is the name of the zone (Ref: Zone) in which the
ventilated slab system is principally located and intended to
affect. A system that is between two zones will still act upon
each zone; however, the zone name referenced here should be
the zone that controls the system response.
Field:
Surface Name or Radiant Surface Group Name[LINK]
This field is the name of the surface (Ref: Surface) or
surface list (Ref: ZoneHVAC:VentilatedSlab:SlabGroup) in which
the hollow cores are embedded/contained. This specification
attaches the source or sinks from the radiant system to a
particular surface and the contribution of the system to the
heat balances of that surface. If this field is a surface
list, then the source or sink is attached to all of the
surfaces in the list with the radiant system surface group
defining the breakdown of how flow rate is split between the
various surfaces. Only base surfaces (Walls, Roofs, Floors)
are valid. Window/Door surfaces and Internal Mass are not
valid surface types for embedded radiant systems.
This field allows the user to enter the maximum volumetric
flow rate of air through the ventilated slab system in m\(^{3}\)/sec. This parameter
should be some real number greater than zero.
This field allows the user to control how outdoor air is
used in the ventilated slab system. The ventilated slab
system described by this syntax has its own outdoor air
handler. The three options for outdoor air control are
“VariablePercent”,
“FixedTemperature” and
“FixedAmount”. Those keywords are the only
allowed choices for this parameter. In general, the variable
percent control will attempt to vary the amount of outdoor air
between some minimum and maximum schedules of fractions (see
next two fields) to best meet the current heating or cooling
load. The fixed temperature control will vary the amount of
outdoor air between the minimum schedule (fraction of maximum,
see next field) and 100% available outdoor air to come as
close as possible to a desired mixed air temperature (see two
fields down) that can be scheduled. The fixed amount control
will fix the outdoor air flow rate as minimum outdoor air flow
rate and schedule specified by the user and automatically set
the maximum and minimum outside flow rate to be equal by
ignoring the maximum outdoor air flow rate. More information
on the controls and operation of the ventilated slab are given
in the section above (preceding the IDF description).
This field allows the user to enter the minimum volumetric
flow rate of outdoor air (in m\(^{3}\)/sec) that will be brought
in to the ventilated slab. The actual minimum outdoor air flow
rate will be this number multiplied by the schedule value from
the minimum outdoor air schedule. If “FixedAmount” type is
selected as the outdoor air control strategy, the outdoor air
flow rate will be fixed at the value of this field and the
ventilated slab will automatically set the maximum and minimum
outside flow rate to be equal by ignoring the maximum outdoor
air flow rate.
This field contains a schedule name (ref: Schedule) that
should contain values for the minimum outdoor air used by the
ventilated slab system for IAQ or other reasons. Note that if
the ventilated slab is scheduled off or if there is no load
sensed in the zone that the system will not operate even to
achieve the minimum air fraction. However, if the system is
operating, it will always bring in at least this fraction of
the minimum air flow rate (see minimum air flow rate field
above). If “FixedAmount” type is selected as the outdoor air
control strategy, the actual outdoor air flow rate will be
this number multiplied by the minimum outdoor air flow rate in
the field above. The ventilated slab will automatically set
the maximum and minimum outdoor air schedule to be equal by
ignoring the maximum outdoor air schedule.
This field allows the user to enter the maximum volumetric
flow rate of outdoor air that can be brought into the
ventilated slab in m\(^{3}\)/sec. This parameter
should be some real number greater than zero. Note that the
value for this parameter may be less than the maximum air flow
rate of the ventilated slab and this may affect the maximum
fraction of outdoor air within the control strategy defined
above. This parameter is an absolute maximum and will
supercede any scheduled fraction of the ventilated slab
maximum airflow rate. If “FixedAmount” type is selected as the
outdoor air control strategy, this field will be ignored and
be automatically set to be equal to the minimum outdoor air
flow rate specified in the field above.
Field:
Maximum Outdoor Air Fraction or Temperature Schedule Name[LINK]
This field can have one of two meanings depending the type
of control selected in the outdoor air control type parameter
above. If “VariablePercent” or “FixedAmount” was selected,
then this field is a schedule name (ref: Schedule)
corresponding to a maximum air fraction schedule. Furthermore,
if “FixedAmount” type is selected as the outdoor air control
strategy, this field will be ignored and be automatically set
to be equal to the minimum outdoor air fraction specified in
the field below. Note that this is a fraction of the maximum
airflow rate field (see parameter above) for the ventilated
slab. If “FixedTemperature” control was selected, then this
field is still a schedule name (ref: Schedule), but it
corresponds to a schedule of mixed air temperatures that the
outdoor air control will try to attain.
This field allows the user to control how the air is
circulated using the ventilated slab system. The options for
system configuration are
SlabOnly
SlabAndZone
SeriesSlabs
In the SlabOnly, the ventilation air is
sent to the slab only and does not enter the zone. In the
SlabAndZone, the air first enters the slab
and then is delivered to the zone before returning to the
system. With the SeriesSlabs option, the user
specifies a list of slabs (ZoneHVAC:VentilatedSlab:SlabGroup).
This list determines the order of slabs through which the air
passes. In this option, air is not delivered to any zone.
This field is the inside diameter of the cores through
which air is circulated for the system being defined by this
statement. The inside diameter should be recorded in meters
and is used to determine the convective heat transfer from the
circulated air to the inside surface of the ventilated
slab.
This field is the length of core embedded in the surface
named above in the surface name field. In other words, this
should be the distance that air travels as it through the
slab. The length of the hollow core in the slab should be
entered in meters and is used to determine the effectiveness
of heat transfer from the air being circulated through the
cores and the core inside surface. Longer core lengths result
in more heat transferred to/from the radiant surface to the
circulating fluid.
This field specifies along with the throttling range and
setpoint schedules how the user wishes to control the
ventilated slab system. The temperature denoted in the set
temperature schedule can refer to one of seven different
temperatures: the zone mean air temperature, the zone mean
radiant temperature, the zone operative temperature, the
surface temperature of the ventilated slab, the outdoor
dry-bulb temperature, the outdoor wet-bulb temperature, or the
dewpoint temperature of zone mean air temperature. The choice
of temperature is controlled by the current field—temperature
control type. The user must select from the following
options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
OutdoorDryBulbTemperature
OutdoorWetBulbTemperature
SurfaceTemperature
ZoneAirDewPointTemperature
If the user does not select a control type,
MeanAirTemperature control is assumed by
EnergyPlus. See the control temperature schedule fields below
for more information.
Field:
Heating High Air Temperature Schedule Name[LINK]
This field specifies the high air temperature in degrees
Celsius for the temperature control of a ventilated slab
system. Air and control temperatures for heating work together
to provide a linear function that determines the air
temperature sent to the ventilated slab. The current control
temperature (see Temperature Control Type above) is compared
to the high and low control temperatures at the current
time. If the control temperature is above the high
temperature, then the inlet air temperature is set to the low
air temperature. If the control temperature is below the low
temperature, then the inlet air temperature is set to the high
air temperature. If the control temperature is between the
high and low value, then the inlet air temperature is linearly
interpolated between the low and high air temperature
values.
Field:
Heating Low Air Temperature Schedule Name[LINK]
This field specifies the low air temperature in degrees
Celsius for the temperature control of a ventilated slab. For
more information on its interpretation, see Heating High Air
Temperature Schedule above.
Field:
Heating High Control Temperature Schedule Name[LINK]
This field specifies the high control temperature in
degrees Celsius for the temperature control of a ventilated
slab. For more information on its interpretation, see Heating
High Air Temperature Schedule above.
Field:
Heating Low Control Temperature Schedule Name[LINK]
This field specifies the low control temperature in degrees
Celsius for the temperature control of a ventilated slab. For
more information on its interpretation, see Heating High Air
Temperature Schedule above.
Field:
Cooling High Air Temperature Schedule Name[LINK]
This field specifies the high air temperature in degrees
Celsius for the temperature control of a ventilated slab
system. Air and control temperatures for cooling work together
to provide a linear function that determines the air
temperature sent to the ventilated slab system. The current
control temperature (see Temperature Control Type above) is
compared to the high and low control temperatures at the
current time. If the control temperature is above the high
temperature, then the inlet air temperature is set to the low
air temperature. If the control temperature is below the low
temperature, then the inlet air temperature is set to the high
air temperature. If the control temperature is between the
high and low value, then the inlet air temperature is linearly
interpolated between the low and high air temperature
values.
Field:
Cooling Low Air Temperature Schedule Name[LINK]
This field specifies the low air temperature in degrees
Celsius for the temperature control of a constant flow cooling
radiant system. For more information on its interpretation,
see Cooling High Air Temperature Schedule above.
Field:
Cooling High Control Temperature Schedule Name[LINK]
This field specifies the high control temperature in
degrees Celsius for the temperature control of a constant flow
cooling radiant system. For more information on its
interpretation, see Cooling High Air Temperature Schedule
above.
Field:
Cooling Low Control Temperature Schedule Name[LINK]
This field specifies the low control temperature in degrees
Celsius for the temperature control of a ventilated slab
system. For more information on its interpretation, see
Cooling High Air Temperature Schedule above.
This field is a node name used to identify the node that
serves as the zone return air inlet to the ventilated slab
system. This node is one of the inlets to the outdoor air
mixer which is implicit in the ventilated slab system model.
For “SlabAndZone” configuration, the Return Air Node will
typically be the same node as a zone exhaust node. For
“SlabOnly” or “SeriesSlabs” configuration, this node name is
required but will have zero flow.
This field is a node name used to identify the node that
serves as the inlet of the ventilated slab or series of slabs,
after the outdoor air mixer, fan, and optional coils.
This field is a node name used to identify the node that
serves as the outlet from the ventilated slab system to the
zone when using the “SlabAndZone” configuration. It is the
node exiting the slab section of the system. This node will
typically be the same node as a zone inlet node. In the case
of “SlabOnly” or “SeriesSlabs” configuration, this field will
be ignored and it should be left BLANK.
This field is a node name used to identify the node
associated with fresh outdoor air brought into the ventilated
slab system outdoor air mixer. This node should also be
specified in an OutdoorAir:Node
or OutdoorAir:NodeList
object.
This field is a node name used to identify the node
associated with the “mixed” air of the ventilated slab. These
conditions are post-“mixing box” since they are the conditions
of the fraction of return air combined with the outdoor air.
Since this is a simple system, this can also be viewed as the
conditions of the air being sent to the coils.
This field is the name of a fan (ref: Fan:SystemModel
or Fan:ConstantVolume) that is part of the ventilated slab
system. This name links the ventilated slab to particular fan
data entered elsewhere in the input data file. A fan name is
required since it is the prime mover of air in the ventilated
slab system.
This field allows the user to specify the coil operating
options as one of the following options:
None
Heating
Cooling
HeatingAndCooling
If None is selected, the ventilated slab
does not have any coils, and any other input will be ignored.
If either Heating or Cooling
is selected, only a heating or cooling coil, respectively, is
present. Thus, only four more inputs will be expected. If
HeatingAndCooling is selected, both heating
and cooling coil input must be entered, and the ventilated
slab will have both a heating and a cooling coil.
This field is the name of the heating coil that is part of
the ventilated slab system. It is assumed that there is
always some sort of heating coil associated with a ventilated
slab system. This name links the ventilated slab to
particular heating coil data entered elsewhere in the input
data file.
This field corresponds to the water inlet node to the
heating coil for a water coil. The water inlet node controls
how a water heating coil operates. This field is ignored/not
needed for gas and electric heating coils.
This field is the name of the cooling coil (ref: Coil:Cooling:Water,Coil:Cooling:Water:DetailedGeometry,
CoilSystem:Cooling:Water:HeatExchangerAssisted) that is part
of the ventilated slab system. This name links the ventilated
slab system to particular cooling coil data entered elsewhere
in the input data file. If no cooling coil is present, the
previous field may be followed by a semi-colon and the
remaining parameters in this statement may be ignored.
This field is the name of the cooling coil that is part of
the ventilated slab system. It is assumed that there is
always some sort of cooling coil associated with a ventilated
slab system. This name links the ventilated slab to
particular cooling coil data entered elsewhere in the input
data file.
This field corresponds to the water inlet node to the
cooling coil. The water inlet node controls how a water
cooling coil operates and is required for the ventilated slab
system that has a cooling coil associated with it to function
properly.
This optional input field is the name of an AvailabilityManagerAssignmentList
object. An Availability Manager Assignment List is a list of
Availability Managers giving both Availability Manager type
and name. The availability managers in the list apply to this
ventilated slab object’s fan. If the ventilated slab is
available (per the Availability Schedule Name input field
above) and this input field has a valid availability manager
assignment list name, then the availability managers in the
list determine when and if the fan of this ventilated slab
object should be on or off.
This optional input field is the name of a DesignSpecification:ZoneHVAC:Sizing
object. The name must correspond to unique name of a DesignSpecification:ZoneHVAC:Sizing
object. A Design Sepcification Zone
HVAC Sizing object defines scalable sizing methods for sizing
input fields such as Maximum Air Flow Rate in this Ventilated
Slab zone HVAC object. The scaled Maximum Air Flow Rate in
turn is used to size cooling and heating capacity of the
coils.
An example IDF with a ventilated slab is shown below.
ZoneHVAC:VentilatedSlab,
Zone4VentSlab, !- Name
VentSlabAvailability, !- Availability Schedule Name
SPACE4-1, !- Zone Name
F4-1, !- Surface Name or Radiant Surface Group Name
0.84, !- Maximum Air Flow Rate {m3/s}
VariablePercent, !- Outdoor Air Control Type
0.168, !- Minimum Outdoor Air Flow Rate {m3/s}
U2MinOASched, !- Minimum Outdoor Air Schedule Name
0.84, !- Maximum Outdoor Air Flow Rate {m3/s}
VentSlabMaxOA, !- Maximum Outdoor Air Fraction or Temperature Schedule Name
SlabAndZone, !- System Configuration Type
0.050, !- Hollow Core Inside Diameter {m}
15.0, !- Hollow Core Length {m}
50.0, !- Number of Cores
MeanRadiantTemperature, !- Temperature Control Type
VentSlabHotHighAir, !- Heating High Air Temperature Schedule Name
VentSlabHotLowAir, !- Heating Low Air Temperature Schedule Name
VentSlabHotHighControl, !- Heating High Control Temperature Schedule Name
VentSlabHotLowControl, !- Heating Low Control Temperature Schedule Name
VentSlabCoolHighAir, !- Cooling High Air Temperature Schedule Name
VentSlabCoolLowAir, !- Cooling Low Air Temperature Schedule Name
VentSlabCoolHighControl, !- Cooling High Control Temperature Schedule Name
VentSlabCoolLowControl, !- Cooling Low Control Temperature Schedule Name
Zone4VentSlabReturnAirNode, !- Return Air Node Name
Zone4VentslabSlabInNode, !- Slab In Node Name
Zone4Inlets, !-Zone Supply Air Node Name
Zone4VentSlabOAInNode, !- Outdoor Air Node Name
Zone4VentSlabExhNode, !- Relief Air Node Name
Zone4VentSlabOAMixerOutletNode, !-Outdoor Air Mixer Outlet Node Name
Zone4VentSlabFanOutletNode, !- Fan Outlet Node Name
Zone4VentSlabFan, !- Fan Name
HeatingAndCooling, !- Coil Option Type
Coil:Heating:Electric, !- Heating Coil Object Type
Zone4VentSlabHeatingCoil,!- Heating Coil Name
, !- Hot Water or Steam Inlet Node Name
Coil:Cooling:Water, !- Cooling Coil Object Type
Zone4VentSlabCoolingCoil,!- Cooling Coil Name
Zone4VentSlabChWInletNode; !- Cold Water Inlet Node Name
HVAC,Sum,Zone Ventilated Slab Coil Latent Cooling
Energy [J]
HVAC,Average, Zone
Ventilated Slab Air Mass Flow Rate [kg/s]
HVAC,Average, Zone
Ventilated Slab Fan Electric Power [W]
HVAC,Sum,Zone Ventilated Slab Fan Electric Energy
[J]
HVAC,Average,Zone Ventilated Slab Inlet Air Temperature
[C]
HVAC,Average,Zone Ventilated Slab Outlet Air
Temperature [C]
HVAC,Average,Zone Ventilated Slab Zone
Inlet Air Temperature [C]
HVAC,Average,Zone Ventilated Slab Return Air
Temperature [C]
HVAC,Average,Zone Ventilated Slab Fan Outlet Air
Temperature [C]
HVAC,Average,Zone Ventilated Slab Fan Availability
Status []
Zone
Ventilated Slab Radiant Heating Rate [W][LINK]
This field reports the radiant heating input rate of the
ventilated slab system to the zone it is serving in Watts.
This is determined by outlet and zone air conditions and the
mass flow rate through the ventilated slab system.
Zone
Ventilated Slab Radiant Heating Energy [J][LINK]
This field is the heating radiant input of the ventilated
slab system to the zone it is serving in Joules over the
timestep being reported. This is determined by outlet and
zone air conditions, the mass flow rate through the ventilated
slab system, and the timestep.
Zone
Ventilated Slab Radiant Cooling Rate [W][LINK]
This field reports the radiant cooling input rate to the
ventilated slab system in Watts. This is the heat sink to the
surface that is defined as the ventilated slab system. The
cooling rate is determined by the zone conditions and the
control scheme defined in the user input.
Zone
Ventilated Slab Radiant Cooling Energy [J][LINK]
This field reports the radiant cooling input to the
ventilated slab system in Joules. This is the heat sink to the
surface that is defined as the radiant system. The cooling
rate is determined by the zone conditions, the control scheme
defined in the user input, and the timestep.
This field reports the heating input rate of the heating
coil of ventilated slab system the zone it is serving in
Watts. This is determined by return air and zone air
conditions and the mass flow rate through the ventilation slab
system.
Zone
Ventilated Slab Coil Heating Energy [J][LINK]
This field is the heating output of the heating coil of the
ventilated slab system the zone it is serving in Joules over
the timestep being reported. This is determined by return air
and zone air conditions, the mass flow rate through the
ventilation slab system, and the timestep.
Zone
Ventilated Slab Coil Total Cooling Rate [W][LINK]
This field reports the total cooling (sensible plus latent)
output rate of the cooling coil of the ventilated slab system
to the zone it is serving in Watts. This is determined by
outlet and zone air conditions and the mass flow rate through
the ventilation slab system.
Zone
Ventilated Slab Coil Total Cooling Energy [J][LINK]
This field is the total cooling (sensible plus latent)
output of the cooling coil of the ventilated slab system to
the zone it is serving in Joules over the timestep being
reported. This is determined by outlet and zone air
conditions, the mass flow rate through the ventilation slab
system, and the timestep.
Zone
Ventilated Slab Coil Sensible Cooling Rate [W][LINK]
This field reports the sensible cooling output rate of the
cooling coil of the ventilated slab system to the zone it is
serving in Watts. This is determined by outlet and zone air
conditions and the mass flow rate through the ventilation slab
system.
Zone
Ventilated Slab Coil Sensible Cooling Energy [J][LINK]
This field is the sensible cooling output of the cooling
coli of the ventilated slab system to the zone it is serving
in Joules over the timestep being reported. This is
determined by outlet and zone air conditions, the mass flow
rate through the ventilation slab system, and the
timestep.
Zone
Ventilated Slab Coil Latent Cooling Rate [W][LINK]
This field reports the latent cooling output rate of the
cooling coil of the ventilated slab system to the zone it is
serving in Watts. This is determined by outlet and zone air
conditions and the mass flow rate through the ventilation slab
system.
Zone
Ventilated Slab Coil Latent Cooling Energy [J][LINK]
This field is the latent cooling output of the cooling coli
of the ventilated slab system to the zone it is serving in
Joules over the timestep being reported. This is determined
by outlet and zone air conditions, the mass flow rate through
the ventilation slab system, and the timestep.
Zone
Ventilated Slab Air Mass Flow Rate [kg/s][LINK]
This field reports the mass flow rate of air through the
ventilated slab system in kilograms per second.
This field reports the electric power consumption rate of
the fan of the ventilated slab system in Watts.
Zone
Ventilated Slab Fan Electric Energy [J][LINK]
This field reports the electric power consumed by the fan
of the ventilated slab system over the timestep in Joules.
Zone
Ventilated Slab Inlet Air Temperature [C][LINK]
This field reports the temperature of air entering the
ventilated slab system in Celsius.
Zone
Ventilated Slab Outlet Air Temperature [C][LINK]
This field reports the temperature of air leaving the
ventilated slab system in Celsius.
Zone
Ventilated Slab Zone Inlet Air Temperature [C][LINK]
This field reports the temperature of air entering the zone
in Celsius.
Zone
Ventilated Slab Return Air Temperature [C][LINK]
This field reports the temperature of air leaving the zone
in Celsius. When system does not circulate air to
zone(“SlabOnly” Configuration), the slab outlet temperature
and return air temperature will be the same.
Zone
Ventilated Slab Fan Outlet Air Temperature [C][LINK]
This field reports the fan outlet air temperature for the
ventilated slab system in Celsius.
Zone
Ventilated Slab Fan Availability Status [][LINK]
This is the availability status of the ventilated slab fan.
This status flag is a result of the calculations made by the
Availability Manager(s) listed in an AvailabilityManagerAssignmentList
object and/or calculations made by Hybrid Ventilation Manager
object. The AvailabilityManagerAssignmentList
is an optional input in the ventilated slab object. When a
single availability manager is used in an Availability Manager
Assignment List, this is also the availability status reported
by the specific availability manager (Ref.
AvailabilityManager:* Outputs). For multiple availability
managers in an Availability Manager Assignment List along with
Hybrid Ventilation Manager, rules to determine fan
availability status are described in the section ‘Group –
System Availability Managers’. The control status outputs are
represented using integers 0 through 3. These integers
represent NoAction (0), ForceOff (1), CycleOn (2), and
CycleOnZoneFansOnly (3). Since the status output is averaged,
the output result may not correspond to the values described
here when output variable frequencies other than detailed are
used. Use the “detailed” reporting frequency (Ref. Output:Variable
object) to view the availability status at each simulation
timestep.
A ventilated slab system may consist of multiple active
slabs that are serving to condition the zone. Slabs that act
serially can be specified as multiple radiant systems using
the standard ventilated slab input described above. This list
of surfaces (the name it is assigned) replcaces the name of a
single surface in the ventilated slab system input described
above.
Field :
Name of Ventilated Slab Surface Group[LINK]
This field is a unique user assigned name for the list of
surfaces that are acting in coordination with one another. Any
reference to this list by a ventilated slab system will use
this name.
This field is the name of a surface in the zone being
conditioned by the ventilated slab system. Only base surfaces
like walls, floors and roofs are valid. Door/Window Surface
and Internal Mass are not valid surface types for the
ventilated slab system.
This field is the inside diameter of the cores through
which air is circulated for the surface being defined by this
statement. The inside diameter should be recorded in meters
and is used to determine the convective heat transfer from the
circulated air to the inside surface of the ventilated
slab.
This field is the length of core embedded in the surface
named above in the surface name field. In other words, this
should be the distance that air travels as it through the
slab. The length of the hollow core in the surface should be
entered in meters and is used to determine the effectiveness
of heat transfer from the air being circulated through the
cores and the core inside surface. Longer core lengths result
in more heat transferred to/from the radiant surface to the
circulating fluid.
This field is a node name (character string) used to
identify the node that serves as the inlet (air side) to the
surface. In EnergyPlus, nodes represent points between
components or at various points in the loops. While a node
name may be referenced more than once in an input data file,
each node must have a unique name.
This field is a node name (character string) used to
identify the node that serves as the outlet (air side) of the
surface. In EnergyPlus, nodes represent points between
components or at various points in the loops. While a node
name may be referenced more than once in an input data file,
each node must have a unique name.
An Example IDF with a ventilated slab system is shown
below
ZoneHVAC:VentilatedSlab:SlabGroup,
Z125, !- Name
SPACE1-1, !- Zone 1 Name
C1-1, !- Surface 1 Name
0.05, !- Core Diameter for Surface 1
30, !- Core Length for Surface 1
20, !- Core Numbers for Surface 1
Z1VentslabIn, !- Slab In Node Name for Surface 1
Z1VentSlabout, !- Slab Outlet Node Name for Surface 1
SPACE2-1, !- Zone 2 Name
C2-1, !- Surface 2 Name
0.05, !- Core Diameter for Surface 2
15, !- Core Length for Surface 2
20, !- Core Numbers for Surface 2
Z2VentSlabIn, !- Slab In Node Name for Surface 2
Z2VentSlabOut, !- Slab Outlet Node Name for Surface 2
SPACE5-1, !- Zone 3 Name
C5-1, !- Surface 3 Name
0.05, !- Core Diameter for Surface 3
30, !- Core Length for Surface 3
20, !- Core Numbers for Surface 3
Z5VentSlabIn, !- Slab In Node Name for Surface 3
Z5VentSlabOut; !- Slab Outlet Node Name for Surface 3
Group – Radiative / Convective Units[LINK]
This section describes the radiative/convective zone equipment units. The following units are included in this section:
ZoneHVAC:Baseboard:Convective:Electric
ZoneHVAC:Baseboard:RadiantConvective:Water
ZoneHVAC:Baseboard:RadiantConvective:Steam
ZoneHVAC:Baseboard:RadiantConvective:Electric
ZoneHVAC:CoolingPanel:RadiantConvective:Water
ZoneHVAC:Baseboard:Convective:Water
ZoneHVAC:HighTemperatureRadiant
ZoneHVAC:LowTemperatureRadiant:ConstantFlow
ZoneHVAC:LowTemperatureRadiant:Electric
ZoneHVAC:LowTemperatureRadiant:VariableFlow
ZoneHVAC:Baseboard:RadiantConvective:Water[LINK]
The objective of this model is to calculate the convective and radiant heat transfer from water baseboard heaters to the people and the surfaces within a zone so that surface heat balances can take into account the radiant heat transfer to the surfaces and thus enhance the accuracy of thermal comfort predictions within the space. The radiant heat gains are distributed to the surfaces by fractions defined by user input.
Inputs[LINK]
Field: Name[LINK]
A unique user assigned name for an instance of a hot water baseboard heater unit. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
The name of the schedule (ref: Schedule) that denotes whether the hot water baseboard heater unit can run during a given time period. A schedule value equal to 0 denotes that the unit must be off for that time period. A value greater than 0 denotes that the unit is available to operate during that time period. If this field is left blank, the schedule has a value of 1 for all time periods.
Field: Inlet Node Name[LINK]
This field is the name of the hot water inlet node for the baseboard heater.
Field: Outlet Node Name[LINK]
This field is the name of the hot water outlet node for the baseboard heater.
Field: Rated AverageWaterTemperature[LINK]
This field is the rated average water temperature for the baseboard heater which is published in the manufacturer’s literature in degree Celsius. It typically ranges from 65.56°C to 115.36°C in the I = B = R rating document while the lowest allowable temperature is 32.22°C. The default value is 87.78°C. If the user does not enter this field, the default value is assumed.
Field: Rated Water Mass Flow Rate[LINK]
This field is the rated standard water flow rate in kg/s which is published as part of the manufacturer’s literature. It is used by the manufacturers when determining the rated capacity (see next field). The default value is 0.063kg/s. If it is blank or zero, the default values is assumed.
Field: Heating Design Capacity Method[LINK]
Enter the method used to determine the heating design capacity or the method for scalable sizing. Input allowed is either HeatingDesignCapacity, CapacityPerFloorArea, and FractionOfAutosizedHeatingCapacity. If this input field is left blank or zero, then autosizing is assumed. HeatingDesignCapacity means user specifies the magnitude of heating capacity or the program calculates the design heating capacity if autosize is specified. CapacityPerFloorArea means the program calculates the design heating capacity from user specified heating capacity per floor area and floor area of the zone served by the radiant baseboard unit. FractionOfAutosizedHeatingCapacity means the program calculates the design heating capacity from user specified fraction and the auto-sized design heating capacity. The default method is HeatingDesignCapacity.
Field: Heating Design Capacity {W}[LINK]
This field is the radiant-convective water baseboard rated capacity in watts at a rated water mass flow rate (see input field Rated Mass Flow Rate). Almost all publications from manufacturers indicate it as W/m (Btuh per linear foot). The user thus must multiply it by the active length of the unit. The active length is available in the literature. Manufacturers are required to publish the difference between active and total length of the unit (I = B = R rating for boilers baseboard radiation, 2009).If it is blank or zero, autosizing is assumed. Design day sizing run must be specified for autosizing.
Field: Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the rated heating capacity per unit floor area of radiant-convective water baseboard unit in m3/s-m2. This field is required field when the Heating Design Capacity Method is CapacityPerFloorArea. The program calculates the heating capacity from floor area of the zone served by the radiant baseboard unit and the heating capacity per unit floor area value specified by the user. This field may be left blank.
Field: Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized heating capacity of radiant-convective water baseboard. This input field is required when the Heating Design Capacity Method is FractionOfAutosizedHeatingCapacity. The program calculates the heating capacity from the design autosized heating capacity and user specified fraction. Design day sizing run must be specified. This field may be left blank. Default value is 1.0.
Field: Maximum Water Flow Rate[LINK]
This field is the maximum water volumetric flow rate in m\(^{3}\)/sec. It can be autosized by EnergyPlus.
Field: Convergence Tolerance[LINK]
This field is the control tolerance for the unit heating output. The unit is controlled by matching the unit output to the zone demand. For hot water baseboards, the model must be numerically inverted to obtain a specified output. The convergence tolerance is the error tolerance used to terminate the numerical inversion procedure. Basically this is the fraction:
\[\frac{{\left| {({Q_{bb,out}} - {Q_{ZoneLoad}})} \right|}}{{{Q_{ZoneLoad}}}} \le Convergence{\kern 1pt} Tolerance\]
The default is 0.001.
Field: Fraction Radiant[LINK]
This field specifies what fraction of the power input to the baseboard heater is actually transferred to the space as radiant heat. The fraction should be between 0 and 1. This is the portion of the total power that is modeled as radiation. The portion that is radiant heat transfer from the baseboard heater is distributed to people and specific surfaces using the remaining fields. Note that the sum of the fractions in the remaining fields (people and surfaces) must equal 1.0 so that all the radiant power is distributed properly. For more information on the specification of this parameter, please see the Engineering Reference for EnergyPlus.
Field: Fraction of Radiant Energy Incident on People[LINK]
This field specifies the fraction of radiant portion of heat transfer to the zone from the baseboard heater that is incident directly on people within the space. This has an impact on the predicted thermal comfort of the zone occupants. Note that although this energy is “radiant” it is actually modeled in the zone heat balance as convective energy (like an internal gain). The basic assumption here is that most radiant energy falling on people will most likely be rereleased to the zone air by convection. This is a simplification of reality, but it maintains the overall energy balance.
Field Set: Surface Name, Fraction of Radiant Energy to Surface[LINK]
The following two items are repeated up to a maximum of 20 surface/fraction pairs. At least one surface/fraction pair must appear in an input file. In other words, at least one surface must be identified as a recipient of radiant energy from the baseboard heater.
Field: Surface <x> Name[LINK]
This field is the name of the first surface to which radiant heat transfer from the baseboard heater is distributed. Used in conjunction with the next field, it helps to define the distribution of the radiant energy on the surfaces within the zone. Note that up to 20 pairs of surface names and corresponding fractions may be entered for a single radiant heater system.
Field: Fraction of Radiant Energy to Surface <x>[LINK]
This field is paired with the preceding surface name (previous field) to define the fraction of radiant heat transfer leaving the baseboard heater that is incident on a particular surface. Users should take into account the directionality of baseboard heaters and their location when defining the value for this input field.
Note on Fraction of Radiant Energy Incident on People and to Surfaces
The radiant energy from the baseboard heater is defined by the total energy input to the baseboard heater from the water loop times the fraction radiant field shown above. This radiant energy is distributed to surfaces and people using the surface and fraction pairs and the fraction to people input by the user. These fractions to people and surfaces must add up to 1.0. In other words, in an input file, the following relation should be maintained by the user input:
\[FractionIndicentOnPeople + \sum {FractionToSurfaces = 1}\]
An example IDF for the water baseboard is shown below.
Outputs[LINK]
HVAC,Average,Baseboard Total Heating Rate [W]
HVAC,Average,Baseboard Convective Heating Rate [W]
HVAC,Average,Baseboard Radiant Heating Rate [W]
HVAC,Sum,Baseboard Total Heating Energy [J]
HVAC,Sum,Baseboard Total Heating Energy [J]
HVAC,Sum,Baseboard Convective Heating Energy [J]
HVAC,Sum,Baseboard Radiant Heating Energy [J]
HVAC,Meter,Baseboard:EnergyTransfer [J]
Baseboard Total Heating Rate [W][LINK]
This is the actual convective heat addition rate of the baseboard to the zone in Watts. This value includes the heat convected to the zone air from the baseboard unit, the heat radiated to people in the zone from the baseboard unit, and the additional convection from surfaces within the zone that have been heated by radiation from the baseboard unit. This value will be different from (and almost always less than) the next field.
Baseboard Convective Heating Rate [W][LINK]
This field reports the rate at which convective heat addition is transferred from the baseboard to the zone in Watts.
Baseboard Radiant Heating Rate [W][LINK]
This field reports the rate at which radiant heat addition is transferred from the baseboard to the people and the surfaces within the zone in Watts.
Baseboard Total Heating Energy [J][LINK]
This is the actual, total convective energy transferred directly and indirectly from the baseboard to the zone it is serving in Joules. Direct convective heat transfer includes the convective portion of the baseboard unit. Indirect convective heat transfer includes heat radiated to people that is then convected to the zone air and heat that is radiated to the surfaces and then convected to the zone air.
Baseboard Convective Heating Energy [J][LINK]
This field reports the amount of convective energy transferred from the baseboard directly to the zone air in Joules.
Baseboard Radiant Heating Energy [J][LINK]
This field reports the amount of radiant energy transferred from the baseboard to the zone in Joules.
Baseboard Hot Water Mass Flow Rate [kg/s][LINK]
This field reports the water mass flow rate at the inlet node of a baseboard unit.
Baseboard Air Mass Flow Rate [kg/s][LINK]
This field reports the air mass flow rate at the inlet node of a baseboard unit.
Baseboard Water Inlet Temperature [C][LINK]
This field reports the water temperatures at the inlet node of a baseboard unit.
Baseboard Water Outlet Temperature [C][LINK]
This field reports the water temperatures at the outlet node of a baseboard unit.
Baseboard Air Inlet Temperature [C][LINK]
This field reports the air temperatures at the inlet node of a baseboard unit.
Baseboard Air Outlet Temperature [C][LINK]
This field reports the air temperatures at the outlet node of a baseboard unit.
ZoneHVAC:Baseboard:RadiantConvective:Steam[LINK]
The objective of this model is to calculate the convective and radiant heat transfer from steam baseboard heaters to the people and the surfaces within a zone so that surface heat balances can take into account the radiant heat transfer to the surfaces and thus enhance the accuracy of thermal comfort predictions within the space. The radiant heat gains are distributed to the surfaces by fractions defined by the user. Users are requested to provide degree of sub cooling to estimate the outlet conditions of the condensate.
Inputs[LINK]
Field: Name[LINK]
A unique user assigned name for an instance of a steam baseboard heater unit. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
The name of the schedule (ref: Schedule) that denotes whether the steam baseboard heater unit can run during a given time period. A schedule value equal to 0 denotes that the unit must be off for that time period. A value greater than 0 denotes that the unit is available to operate during that time period. If this field is left blank, the schedule has a value of 1 for all time periods.
Field: Inlet Node Name[LINK]
This field is the name of the steam inlet node for the baseboard heater.
Field: Outlet Node Name[LINK]
This field is the name of the steam outlet node for the baseboard heater.
Field: Heating Design Capacity Method[LINK]
Enter the method used to determine the heating design capacity for scalable sizing. Input allowed is either HeatingDesignCapacity, CapacityPerFloorArea, and FractionOfAutosizedHeatingCapacity. If this input field is left blank or zero, then autosizing is assumed. HeatingDesignCapacity means user specifies the magnitude of maximum heating capacity or the program calculates the maximum design heating capacity if autosize is specified. CapacityPerFloorArea means the program calculates the design heating capacity from user specified heating capacity per floor area and floor area of the zone served by the radiant baseboard unit. FractionOfAutosizedHeatingCapacity means the program calculates the design heating capacity from user specified fraction and the auto-sized design heating capacity. The default method is HeatingDesignCapacity.
Field: Heating Design Capacity {W}[LINK]
This field is for the a radiant/convective steam baseboard unit heating capacity in watts. This field can be autosized by EnergyPlus. When the Heating Design Capacity Method is HeatingDesignCapacity and this input is blank, autosizing is assumed. Design day sizing run must be specified.
Field: Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2 of radiant/convective steam baseboard. This field is required field when the Heating Design Capacity Method is CapacityPerFloorArea. The program calculates the heating capacity from floor area of the zone served by the steam baseboard unit and the heating capacity per unit floor area value specified by the user. This field may be left blank.
Field: Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized heating capacity of a radiant/convective steam baseboard unit. This input field is required when the Heating Design Capacity Method is FractionOfAutosizedHeatingCapacity. The program calculates the heating capacity from the design autosized heat capacity and user specified fraction. Design day sizing run must be specified. This field may be left blank. Default value is 1.0.
Field: Degree of SubCooling[LINK]
This field is the temperature drop of the condensate in the coil of the baseboard heater. The steam condensates in the coil and changes the phase to the water, giving up the latent heat of steam to the air in the steam to air heat exchanger. The condensate due to the phase change then cools by certain degree in the coil, so that this amount of heat is added to the zone. The minimum value is 1.0° Celsius and default is 5.0° Celsius.
Field: Maximum Steam Flow Rate[LINK]
This field is the maximum steam volumetric flow rate in m\(^{3}\)/s through the steam baseboard heater. The steam volumetric flow rate is calculated at 100C and 101325 Pa. It can be autosized by EnergyPlus.
Field: Convergence Tolerance[LINK]
This field is the control tolerance for the unit heating output. The unit is controlled by matching the unit output to the zone demand. For steam baseboards, the model must be numerically inverted to obtain a specified output. The convergence tolerance is the error tolerance used to terminate the numerical inversion procedure. Basically this is the fraction:
\[\frac{{\left| {({Q_{bb,out}} - {Q_{ZoneLoad}})} \right|}}{{{Q_{ZoneLoad}}}} \le Convergence{\kern 1pt} Tolerance\]
The default is 0.001.
Field: Fraction Radiant[LINK]
This field specifies what fraction of the power input to the baseboard heater is actually transferred to the space as radiant heat. The fraction should be between 0 and 1. This is the portion of the total power that is modeled as radiation. The portion that is radiant heat transfer from the baseboard heater is distributed to people and specific surfaces using the remaining fields. Note that the sum of the fractions in the remaining fields (people and surfaces) must equal 1.0 so that all the radiant power is distributed properly.
Field: Fraction of Radiant Energy Incident on People[LINK]
This field specifies the fraction of radiant portion of heat transfer to the zone from the baseboard heater that is incident directly on people within the space. This has an impact on the predicted thermal comfort of the zone occupants. Note that although this energy is “radiant” it is actually modeled in the zone heat balance as convective energy (like an internal gain). The basic assumption here is that most radiant energy falling on people will most likely be rereleased to the zone air by convection. This is a simplification of reality, but it maintains the overall energy balance.
Field Set: Surface Name, Fraction of Radiant Energy to Surface[LINK]
The following two items are repeated up to a maximum of 20 surface/fraction pairs. At least one surface/fraction pair must appear in an input file. In other words, at least one surface must be identified as a recipient of radiant energy from the baseboard heater.
Field: Surface <x> Name[LINK]
This field is the name of the first surface to which radiant heat transfer from the baseboard heater is distributed. Used in conjunction with the next field, it helps to define the distribution of the radiant energy on the surfaces within the zone. Note that up to 20 pairs of surface names and corresponding fractions may be entered for a single radiant heater system.
Field: Fraction of Radiant Energy to Surface <x>[LINK]
This field is paired with the preceding surface name (previous field) to define the fraction of radiant heat transfer leaving the baseboard heater that is incident on a particular surface. Users should take into account the directionality of baseboard heaters and their location when defining the value for this input field.
Note on Fraction of Radiant Energy Incident on People and to Surfaces[LINK]
The radiant energy from the baseboard heater is defined by the total energy input to the baseboard heater from the steam loop times the fraction radiant field shown above. This radiant energy is distributed to surfaces and people using the surface and fraction pairs and the fraction to people input by the user. These fractions to people and surfaces must add up to 1.0. In other words, in an input file, the following relation should be maintained by the user input:
\[FractionIndicentOnPeople + \sum {FractionToSurfaces = 1}\]
An example IDF for the steam baseboard is shown below.
Outputs[LINK]
HVAC,Average,Baseboard Total Heating Rate [W]
HVAC,Average,Baseboard Convective Heating Rate [W]
HVAC,Average,Baseboard Radiant Heating Rate [W]
HVAC,Sum,Baseboard Total Heating Energy [J]
HVAC,Sum,Baseboard Convective Heating Energy [J]
HVAC,Sum,Baseboard Radiant Heating Energy [J]
HVAC,Meter,Baseboard:EnergyTransfer [J]
HVAC,Average,Baseboard Steam Mass Flow Rate [kg/s]
HVAC,Average,Baseboard Steam Inlet temperature [C]
HVAC,Average,Baseboard Steam Outlet temperature [C]
Baseboard Total Heating Rate [W][LINK]
This is the actual convective heat addition rate of the baseboard to the zone in Watts. This value includes the heat convected to the zone air from the baseboard unit, the heat radiated to people in the zone from the baseboard unit, and the additional convection from surfaces within the zone that have been heated by radiation from the baseboard unit. This value will be different from (and almost always less than) the next field.
Baseboard Convective Heating Rate [W][LINK]
This field reports the rate at which convective heat addition is transferred from the baseboard to the zone in Watts.
Baseboard Radiant Heating Rate [W][LINK]
This field reports the rate at which radiant heat addition is transferred from the baseboard to the people and the surfaces within the zone in Watts.
Baseboard Total Heating Energy [J][LINK]
This is the actual, total convective energy transferred directly and indirectly from the baseboard to the zone it is serving in Joules. Direct convective heat transfer includes the convective portion of the baseboard unit. Indirect convective heat transfer includes heat radiated to people that is then convected to the zone air and heat that is radiated to the surfaces and then convected to the zone air.
Baseboard Convective Heating Energy [J][LINK]
This field reports the amount of convective energy transferred from the baseboard directly to the zone air in Joules.
Baseboard Radiant Heating Energy [J][LINK]
This field reports the amount of radiant energy transferred from the baseboard to the zone in Joules.
Baseboard Steam Energy [J][LINK]
Baseboard Steam Rate [W][LINK]
These are the total heat addition energy and rate of steam used by the baseboard to heat the zone it is serving in Joules and Watts.
Baseboard Steam Mass Flow Rate [kg/s][LINK]
This field reports the steam mass flow rate at the inlet node of a baseboard unit.
Baseboard Steam Inlet Temperature [C][LINK]
This field reports the steam temperatures at the inlet node of a baseboard unit.
Baseboard Steam Outlet Temperature [C][LINK]
This field reports the steam temperatures at the outlet node of a baseboard unit.
ZoneHVAC:Baseboard:RadiantConvective:Electric[LINK]
The electric baseboard heater is a component in the zone equipment simulation. Heat from this device is radiated to people and surfaces and also convected to the surrounding air. The electric baseboard model includes the impact of the radiant heat addition to people and surfaces so that the thermal comfort and surface heat balances are impacted. The component is controlled to meet any remaining zone load not met by other equipment baseboard operates to meet the remaining zone load and the total electric consumption is calculated by dividing by the efficiency of the baseboard.
Inputs[LINK]
Field: Name[LINK]
A unique user assigned name for an instance of an electric baseboard heater unit. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
The name of the schedule (ref: Schedule) that denotes whether the electric baseboard heater unit can run during a given time period. A schedule value greater than 0 (usually 1 is used) indicates that the unit can be on during the time period. A value less than or equal to 0 (usually 0 is used) denotes that the unit will be off for the time period. If this field is blank, the schedule has values of 1 for all time periods.
Field: Heating Design Capacity Method[LINK]
Enter the method used to determine the heating design capacity for scalable sizing. Input allowed is either HeatingDesignCapacity, CapacityPerFloorArea, and FractionOfAutosizedHeatingCapacity. If this input field is left blank or zero, then autosizing is assumed. HeatingDesignCapacity means user specifies the magnitude of maximum or nominal heating capacity or the program calculates the maximum or nominal design heating capacity if autosize is specified. CapacityPerFloorArea means the program calculates the design heating capacity from user specified heating capacity per floor area and floor area of the zone served by the radiant baseboard unit. FractionOfAutosizedHeatingCapacity means the program calculates the design heating capacity from user specified fraction and the auto-sized design heating capacity. The default method is HeatingDesignCapacity.
Field: Heating Design Capacity {W}[LINK]
This field is for the radiant-convective electric baseboard unit nominal heating capacity in watts. This field can be autosized by EnergyPlus. This input field is autosizable. When the Heating Design Capacity Method is HeatingDesignCapacity and this input is blank, autosizing is assumed. Design day sizing run must be specified.
Field: Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2 of radiant/convective electric baseboard. This field is required field when the Heating Design Capacity Method is CapacityPerFloorArea. The program calculates the heating capacity from floor area of the zone served by the radiant baseboard unit and the heating capacity per unit floor area value specified by the user. This field may be left blank.
Field: Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized heating capacity for radiant/convective electric baseboard. This input field is required when the Heating Design Capacity Method is FractionOfAutosizedHeatingCapacity. The program calculates the heating capacity from the design autosized heat capacity and user specified fraction. Design day sizing run must be specified. This field may be left blank. Default value is 1.0.
Field: Efficiency[LINK]
This is the overall electrical efficiency of the electric baseboard unit. The zone load met by this unit is divided by the electrical efficiency to obtain the total electric energy used.
Field: Fraction Radiant[LINK]
This field specifies what fraction of the power input to the baseboard heater is actually transferred to the space as radiant heat. The fraction should be between 0 and 1. This is the portion of the total power that is modeled as radiation. The portion that is radiant heat transfer from the baseboard heater is distributed to people and specific surfaces using the remaining fields. Note that the sum of the fractions in the remaining fields (people and surfaces) must equal 1.0 so that all the radiant power is distributed properly.
Field: Fraction of Radiant Energy Incident on People[LINK]
This field specifies the fraction of the radiant portion of heat transfer to the zone from the baseboard heater that is incident directly on people within the space. This has an impact on the predicted thermal comfort of the zone occupants. Note that although this energy is “radiant” it is actually modeled in the zone heat balance as a convective energy (like an internal gain). The basic assumption here is that radiant energy falling on people will most likely be rereleased to the zone air by convection. This is a simplification of reality, but it maintains the overall energy balance.
Field Set: Surface Name, Fraction of Radiant Energy to Surface[LINK]
The following two items are repeated up to a maximum of 20 surface/fraction pairs. At least one surface/fraction pair must appear in an input file. In other words, at least one surface must be identified as a recipient of radiant energy from the baseboard heater.
Field Set: Surface <x> Name[LINK]
This field is the name of the first surface to which radiant heat transfer from the baseboard heater is distributed. Used in conjunction with the next field, it helps to define the distribution of the radiant energy on the surfaces within the zone. Note that up to 20 pairs of surface names and corresponding fractions may be entered for a single radiant heater system.
Field Set: Fraction of Radiant Energy to Surface <x>[LINK]
This field is paired with the preceding surface name (previous field) to define the fraction of radiant heat transfer leaving the baseboard heater that is incident on a particular surface. Users should take into account the directionality of baseboard heaters and their location when defining the value for this input field.
Note on Fraction of Radiant Energy Incident on People and to Surfaces[LINK]
The radiant energy from the baseboard heater is defined by the total energy input to the baseboard heater times the fraction radiant field shown above. This radiant energy is distributed to surfaces and people using the surface and fraction pairs and the fraction to people input by the user. These fractions to people and surfaces must add up to 1.0. In other words, in an input file, the following relation should be maintained by the user input:
\[FractionIndicentOnPeople + \sum {FractionToSurfaces = 1}\]
Below is an example input for an Electric Baseboard Heater.
Outputs[LINK]
HVAC,Average,Baseboard Total Heating Rate [W]
HVAC,Average,Baseboard Radiant Heating Rate [W]
HVAC,Average,Baseboard Convective Heating Rate [W]
HVAC,Average,Baseboard Electric Power[W]
HVAC,Sum,Baseboard Total Heating Energy [J]
HVAC,Sum,Baseboard Radiant Heating Energy [J]
HVAC,Sum,Baseboard Convective Heating Energy [J]
HVAC,Sum,Baseboard Electric Energy [J]
HVAC,Meter,Baseboard:EnergyTransfer [J]
HVAC,Meter,Heating:Electricity[J]
Baseboard Total Heating Rate [W][LINK]
This is the actual convective heat addition rate of the baseboard to the zone in Watts. This value includes the heat convected to the zone air from the baseboard unit, the heat radiated to people in the zone from the baseboard unit, and the additional convection from surfaces within the zone that have been heated by radiation from the baseboard unit. This value will be different from (and almost always less than) the next field.
Baseboard Radiant Heating Rate [W][LINK]
This field reports the rate at which radiant heat addition is transferred from the baseboard to the people and the surfaces within the zone in Watts.
Baseboard Convective Heating Rate [W][LINK]
This field reports the rate at which convective heat addition is transferred from the baseboard to the zone in Watts.
Baseboard Electric Energy [J][LINK]
This is the electric energy used by the baseboard in Joules.
Baseboard Electric Power [J][LINK]
This is the electric power required by the baseboard to heat the zone it is serving in Watts
Baseboard Total Heating Energy [J][LINK]
This is the actual convective energy transferred directly and indirectly from the baseboard heater to the zone it is serving in Joules. Direct convective heat transfer includes the convective portion of the baseboard unit. Indirect convective heat transfer includes heat radiated to people that is then convected to the zone air and heat that is radiated to the surfaces and then convected to the zone air.
Baseboard Radiant Heating Energy [J][LINK]
This field reports the amount of radiant energy transferred from the baseboard to the zone in Joules.
Baseboard Convective Heating Energy [J][LINK]
This field reports the amount of convective energy transferred from the baseboard directly to the zone air in Joules.
ZoneHVAC:CoolingPanel:RadiantConvective:Water[LINK]
The radiant/convective cooling panel is a component of zone equipment. Chilled water is supplied by the plant and circulated through the panel. Through radiation and convective heat transfer, the panel absorbs energy contained within the zone to provide cooling. Control of the panel is achieved using the methodology used for low temperature radiant systems—a piecewise linear control profile that varies the flow rate to the panel based on a control parameter defined by the user. This is different than being controlled to meet any remaining load like the air-based systems. However, due to the radiant nature of these devices, it is not possible to control precisely on a zone air-based load since this will result in overcooling at the next time step. Despite this, in addition to the piecewise linear controls that have been used with low temperature radiant systems in the past, two new controls will be added for this simple model: one that varies convective output of the system to meet the remaining zone load and one that varies the total convective output of the system to meet the remaining zone load. In these two zone load control types, the user must enter the typical zone thermostat object to replace the setpoint and throttling range input in this object. In this component, control is accomplished by throttling the chilled water flow to the device. Capacity rating information is required as input and is used to calculate a UA value of the unit. The unit is connected to a chilled water loop (demand side) with an inlet and outlet node. The input data dictionary definition of the unit is as follows.
Inputs[LINK]
Field: Name[LINK]
A unique user assigned name for an instance of radiant cooling panel. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
The name of the schedule (ref: Schedule) that denotes whether the radiant cooling panel can run during a given hour. A schedule value greater than 0 (usually 1 is used) indicates that the unit can be on during the hour. A value less than or equal to 0 (usually 0 is used) denotes that the unit must be off for the hour.
Field: Inlet Node Name[LINK]
The name of the water inlet node for the radiant cooling panel.
Field: Outlet Node Name[LINK]
The name of the water outlet node for the radiant cooling panel.
Field: Rated Inlet Water Temperature[LINK]
This field is the inlet temperature to the panel under conditions used to rate the capacity of the panel. This value along with the other rated conditions is used to calculate the overall heat transfer coefficient (U-Value) that will be used to characterize the heat transfer between the water being circulated through the panel and the air in the zone. The default value is 5°C (44°F).
Field: Rated Space Temperature[LINK]
This field is the combined space temperature (air and surface) that the panel is exposed to during the rating process to obtain a rated capacity. This value along with the other rated conditions is used to calculate the overall heat transfer coefficient (U-Value) that will be used to characterize the heat transfer between the water being circulated through the panel and the air in the zone. The default value is 24°C (75.2°F).
Field: Rated Water Mass Flow Rate[LINK]
This field is the rated standard water flow rate in kg/s that was used to obtain the design cooling capacity under rated temperature conditions. This value along with the rated space and water inlet temperatures as well as the cooling capacity (whether autosized or entered by the user) is used to calculate the overall heat transfer coefficient (U-Value) that will be used to characterize the heat transfer between the water being circulated through the panel and the air in the space. Users should note that if this value is too low in comparison to the cooling design capacity that the program will produce an error message and the user must adjust one of these two parameters or the rated temperature values. The default value is 0.063kg/s (1 gpm). If it is blank or zero, the default value is assumed.
Field: Cooling Design Capacity Method[LINK]
Enter the method used to determine the heating design capacity for scalable sizing. Input allowed is either CoolingDesignCapacity, CapacityPerFloorArea, and FractionOfAutosizedCoolingCapacity. If this input field is left blank or zero, then autosizing is assumed. CoolingDesignCapacity means the user specifies the magnitude of maximum or nominal cooling capacity or the program calculates the maximum or nominal design cooling capacity if autosize is specified. CapacityPerFloorArea means the program calculates the design cooling capacity from the user specified cooling capacity per floor area and floor area of the zone served by the cooling panel unit. FractionOfAutosizedCoolingCapacity means the program calculates the design cooling capacity from user specified fraction and the auto-sized design cooling capacity. The default method is CoolingDesignCapacity.
Field: Cooling Design Capacity[LINK]
This field is for the cooling panel unit nominal cooling capacity in watts at the rated flow rate of water through the unit (see Rated Water Mass Flow Rate field above). This field can be autosized by EnergyPlus. When the Cooling Design Capacity Method is CoolingDesignCapacity and this input is blank, autosizing is assumed. Design day sizing run must be specified.
Field: Cooling Design Capacity Per Floor Area[LINK]
Enter the cooling capacity per unit floor area in W/m2 for the cooling panel unit. This field is a required field when the Cooling Design Capacity Method is CapacityPerFloorArea. The program calculates the cooling capacity from floor area of the zone served by the cooling panel unit and the cooling capacity per unit floor area value specified by the user. This field may be left blank.
Field: Fraction of Autosized Cooling Design Capacity[LINK]
Enter the cooling capacity as a fraction of the autosized cooling capacity for the cooling panel. This input field is required when the Cooling Design Capacity Method is FractionOfAutosizedCoolingCapacity. The program calculates the cooling capacity from the design autosized cooling capacity and the user specified fraction. Design day sizing run must be specified. This field may be left blank. Default value is 1.0.
Field: Maximum Chilled Water Flow Rate[LINK]
The maximum chilled water volumetric flow rate in m3/sec. This field can also be autosized.
Field: Control Type[LINK]
This field specifies two different types of control categories: temperature or zone load. For one of the temperature based controls, this field along with the throttling range and setpoint schedules determines how the user wishes to control the radiant cooling panel. The temperature denoted in the setpoint schedule can refer to one of five different temperatures: the zone mean air temperature, the zone mean radiant temperature, the zone operative temperature, the outdoor dry-bulb temperature, or the outdoor wet-bulb temperature. The current field controls the choice of temperature. For controls that are based more on zone load, the user can make one of two choices based on whether the zone load is met by only the convective output of the unit or the total output of the unit. These zone load controls will not perform as precisely as air-based systems. The convective zone load control will come close to meeting the current setpoint temperature (defined by the typical zone thermostat input by the user) since the convective output of the unit will be set to match the remaining zone load. However, in the long run, this will likely overcool the space since radiant energy is being absorbed by surfaces and this will impact the zone conditions at later time steps. The total zone load control will likely undercool the space in the short term since the total output (radiant and convective) of the unit will be set to meet the remaining zone load. However, this will not fully impact the zone air temperature immediately since some of the energy is being absorbed from surfaces rather than the zone air. The user must select from the following options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
OutdoorDryBulbTemperature
OutdoorWetBulbTemperature
ZoneConvectiveLoad
ZoneTotalLoad
Operative temperature for radiant system controls is the average of Mean Air Temperature and Mean Radiant Temperature. If the user does not select a control type, MeanAirTemperature control is assumed by EnergyPlus. See the throttling range and control temperature schedule fields below for more information.
Field: Cooling Control Throttling Range[LINK]
This field specifies the range of temperature in degrees Celsuis over which the radiant cooling panel throttles from zero flow rate up to the maximum defined by the maximum chilled water flow rate field described above. The throttling range parameter is used in conjunction with the control temperature to define the response of the system to various zone conditions. The cooling control temperature schedule specifies the “setpoint” temperature where the flow rate to the system is at half of the maximum flow rate. For example, if the cooling control temperature setpoint is currently 25 C and the cooling throttling range is 2 C, the water flow rate to the radiant system will be zero when the controlling temperature (MAT, MRT, Operative Temperature, ODB, or OWB; see control type field above) is at or below 24 C and the maximum flow rate when the controlling temperature is at or above 26 C. This represents a throttling range of 2 C around the setpoint of 25 C. In between 24 C and 26 C, the flow rate to the radiant system is varied linearly. Note that this field is ignored when the control type is either ZoneLoadConvective or ZoneLoadTotal. For the two zone load controls, the user must use a typical zone thermostat and the system output will be dependent on the remaining zone load.
Field: Cooling Control Temperature Schedule Name[LINK]
This field specifies the cooling setpoint or control temperature for the radiant cooling panel in degrees Celsius. Used in conjunction with the previous field (cooling control throttling range), it will define whether or not the system is running and the current flow rate. Water flow rate to the system is varied linearly around the setpoint temperature based on the throttling range and the maximum cooling flow rate parameters (see above). It should be noted that this control schedule will allow different setpoint temperatures throughout the year for cooling. The control of the radiant cooling panel is based solely on the cooling control throttling range listed above, the cooling control temperature schedule, and the control temperature type listed above. The radiant cooling panel will not use any zone thermostat that might be used by other systems serving the zone in which this radiant cooling panel resides. Note that this field is ignored when the control type is either ZoneLoadConvective or ZoneLoadTotal. For the two zone load controls, the user must use a typical zone thermostat and the system output will be dependent on the remaining zone load.
Field: Condensation Control Type[LINK]
Since radiant cooling panels provide a cold surface in what could be a humid zone, there is the possibility that condensation will occur on the surface of the panel. This is due to the fact that the surface temperature may drop below the dew-point temperature of the space. When this occurs, condensation on the surface will occur. Since there is no direct calculation of the surface temperature of the radiant cooling panel, the condensation check will be made at the inlet water temperature to the panel. Since the user can utilize the next parameter to adjust the differential between the dewpoint temperature and the inlet water temperature, this will allow some flexibility in controlling when the panel will shutdown to avoid condensation. There are three options for handling potential condensation: Off, SimpleOff, and VariableOff. This parameter is optional and will default to SimpleOff.
Off - EnergyPlus will not do anything other than produce a warning message when condensation is predicted to occur. The program will simply continue on; no moisture will be removed from the zone air and there will be no adjustment of the surface temperature as a result of the condensation.
SimpleOff - the program will predict cases where condensation will occur and shut-off the radiant system to avoid this situation. With this option, the user also has the option to adjust when the system will shut down. This is specified with the next parameter (field: Condensation Differential Parameter).
VariableOff - the program will attempt to reduce the inlet temperature to the panel by locally recirculating some of the water leaving the panel and mixing it with water from the overall demand side flow. This also means that some of the demand side water will bypass the panel. In reality, this would require a pump to achieve such mixing and recirculation, but due to the simple nature of this model, no pump definition will be required. Like the SimpleOff option, the VariableOff option uses the condensation dewpoint offset parameter to adjust when the system will try to adjust for the possibility of condensation.
Field: Condensation Control Dewpoint Offset[LINK]
This optional parameter is only valid with the SimpleOff and VariableOff condensation handling algorithm (see previous input parameter). It establishes the difference between the calculated dew-point temperature of the space and the allowed inlet water temperature to the radiant cooling panel before the system shuts down in degrees Celsius. This parameter can be any positive, negative, or zero value. When this parameter is zero, the radiant system will shut down or recirculate water (depending on whether SimpleOff or VariableOff is used) when the inlet temperature drops to the dew-point temperature or below. When this parameter is positive, the radiant system will shut down or recirculate water when the inlet water temperature is the number of degrees Celsius above the dew-point temperature. This allows some extra safety to avoid condensation. When this parameter is negative, the radiant system will shut down or recirculate water when the inlet water temperature is the number of degrees Celsius below the dew-point temperature. This strategy allows the user to simulate a situation where small amounts of condensation are tolerable or the resistance of the panel from the water loop to the panel surface is being taken into account as condensation would likely happen at the panel surface. The default value for this parameter is 1°C.
Field: Fraction Radiant[LINK]
This field gives the user an opportunity to characterize the zone temperature as a function of the zone mean radiant temperature and the mean air temperature. The performance of the unit is proportional to the difference between the water inlet temperature and the zone temperature where the zone temperature is found using a weighted average of zone mean radiant temperature and mean air temperature. The weighting factor is this parameter and it is multiplied by the zone mean radiant temperature. The remainder of the zone temperature calculation is made up of the zone mean air temperature. This parameter can be difficult to quantify as the fraction radiant can vary with zone conditions. However, by definition, a radiant system like this radiant cooling panel must exchange at least 50
Field: Fraction of Radiant Energy Incident on People[LINK]
This field allows the user to direct some of the radiant energy to be absorbed from people rather than surfaces within the space. This would have a direct impact on thermal comfort and would depend on the location of the people with respect to the radiant cooling panel. All energy absorbed by the panel would have a cooling effect on people and is subtracted from the total radiant energy absorbed by the panel defined by the previous term.
Field Set: Surface Name, Fraction of Radiant Energy to Surface[LINK]
The following two items are repeated for an unlimited number of surface/fraction pairs. At least one surface/fraction pair must appear in an input file. In other words, at least one surface must be identified as a recipient of radiant energy from the baseboard heater.
The radiant energy from the cooling panel is defined by the total energy input to the cooling panel from the chilled water loop times the fraction radiant field shown above. This radiant energy is distributed to surfaces and people using the surface and fraction pairs and the fraction to people input by the user. These fractions to people and surfaces must add up to 1.0. In other words, in an input file, the following relation should be maintained by the user input:
\[FractionIndicentOnPeople + \sum {FractionToSurfaces = 1}\]
Field Set: Surface <x> Name[LINK]
The radiant energy absorbed by the radiant cooling panel can be specified to be received from particular surfaces within the space. The next series of pairs of inputs (surface name and fraction of radiant energy) specify where this radiant energy is coming from. In essense, the fraction radiant terms for each surface are similar to a view factor. These pairs can be repeated for up to 100 surfaces giving the user plenty of flexibility to have the radiant cooling panel interact with many potential surfaces. This first parameter in the pair is the name of the surface defined by user input elsewhere in the input file. Note that the surface must reside in the same zone as all of the other surfaces in the following list (that is, all surfaces listed must be in the same zone).
Field Set: Fraction of Radiant Energy to Surface <x>[LINK]
In combination with the previous field, this defines what fraction of the radiant energy being absorbed by the radiant cooling panel comes from the surface named by the previous field. These pairs of surface names and fractions of radiant energy from the surface can be repeated up to 100 times in the input for a particular radiant cooling panel. Note that the sum of all of the radiant energy fractions plus the radiant fraction from people must add up to unity just like in the radiant-convective baseboard models. Note that there is a small possibility that a particular surface listed in these pairs is actually lower than the temperature of the panel. This probably will not happen unless there is another cooling surface within the zone. In reality, absorbing net radiant energy from a colder surface would violate the Second Law of Thermodynamics. However, in keeping with the simple nature of this model, EnergyPlus will monitor the inlet water temperature to the panel and produce a warning message if this temperature is lower than any of the surface temperature of the surfaces with which this system is interacting.
An example input for the radiant cooling panel is shown below.
HVAC, Average, Cooling Panel Total System Cooling Rate [W]
HVAC, Average, Cooling Panel Total Cooling Rate [W]
HVAC, Average, Cooling Panel Convective Cooling Rate [W]
HVAC, Average, Cooling Panel Radiant Cooling Rate [W]
HVAC, Sum, Cooling Panel Total System Cooling Energy [J]
HVAC, Sum, Cooling Panel Total Cooling Energy [J]
HVAC, Sum, Cooling Panel Convective Cooling Energy [J]
HVAC, Sum, Cooling Panel Radiant Cooling Energy [J]
HVAC, Meter, CoolingPanel:EnergyTransfer [J]
HVAC, Average, Cooling Panel Water Mass Flow Rate [kg/s]
HVAC, Average, Cooling Panel Water Inlet Temperature [C]
Cooling Panel Total System Cooling Rate [W][LINK]
This field is the total rate of cooling achieved by the radiant cooling panel on the zone in Watts. This is the impact of the cooling panel on the space and is the actual impact the system has on the zone. It includes the convective heat transfer rate as well as the decreased convection from zone surfaces as a result of the operation of the unit and the radiant absorbed by people.
Cooling Panel Total Cooling Rate [W][LINK]
This variable is the total rate of cooling achieved by the radiant cooling panel on the zone in Watts. This value includes the sum of both the convective and the radiant energy absorbed by the panel.
Cooling Panel Convective Cooling Rate [W][LINK]
This field reports the rate at which convective heat is removed by the radiant cooling panel from the zone in Watts.
Cooling Panel Radiant Cooling Rate [W][LINK]
This field reports the rate at which radiant heat is removed from people and the surfaces of the zone being served by the radiant cooling panel in Watts.
Cooling Panel Total System Cooling Energy [J][LINK]
This field is the total cooling achieved by the radiant cooling panel on the zone in Joules over the timestep being reported. This is the impact of the cooling panel on the space and is the actual impact the system has on the zone. It includes the convective heat transfer rate as well as the decreased convection from zone surfaces as a result of the operation of the unit and the radiant absorbed by people.
Cooling Panel Total Cooling Energy [J][LINK]
This field reports the total heat removal from the zone by the radiant cooling panel in Joules over the timestep being reported.
Cooling Panel Convective Cooling Energy [J][LINK]
This field reports the convective heat removal from the zone by the radiant cooling panel in Joules over the timestep being reported.
Cooling Panel Radiant Cooling Energy [J][LINK]
This field reports the amount of radiant heat removal from people and the surfaces of the zone being served by the radiant cooling panel in Joules over the timestep being reported.
CoolingPanel:EnergyTransfer [J][LINK]
This meter report variable is the sum of the total heat removal being accomplished by all radiant cooling panels in the HVAC systems in the simulation.
Cooling Panel Water Mass Flow Rate [kg/s][LINK]
This field reports the water mass flow rate at the inlet node of the radiant cooling panel. The water mass flow rate at the inlet and outlet node of the radiant cooling panel is the same value.
Cooling Panel Water Inlet Temperature [C][LINK]
This field reports the water temperature at the inlet node of the radiant cooling panel.
Cooling Panel Water Outlet Temperature [C][LINK]
This field reports the water temperature at the outlet node of the radiant cooling panel.
ZoneHVAC:Baseboard:Convective:Water[LINK]
The hot water baseboard heater is a component of zone equipment. The component is controlled to meet any remaining zone load not met by other equipment in the zone that have higher heating priority. The control is accomplished by throttling the hot water flow. Input resembles that for the simple heating coil: there is an availability schedule, an overall UA, and a maximum hot water mass flow rate. The unit is connected to a hot water loop (demand side) with an inlet and outlet node. Finally, there is the convergence tolerance, which is the tolerance on how closely the baseboard outlet will meet the zone load. Of course, this tolerance is relative to the zone load.
Inputs[LINK]
Field: Name[LINK]
A unique user assigned name for an instance of a hot water baseboard heater unit. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
The name of the schedule (ref: Schedule) that denotes whether the hot water baseboard heater unit can run during a given time period. A schedule value greater than 0 (usually 1 is used) indicates that the unit can be on during the time period. A value less than or equal to 0 (usually 0 is used) denotes that the unit must be off for the time period. If this field is blank, the schedule has values of 1 for all time periods.
Field: Inlet Node Name[LINK]
The name of the hot water inlet node for the baseboard heater.
Field: Outlet Node Name[LINK]
The name of the hot water outlet node for the baseboard heater.
Field: Heating Design Capacity Method[LINK]
Enter the method used to determine the heating design capacity for scalable sizing. Input allowed is either HeatingDesignCapacity, CapacityPerFloorArea, and FractionOfAutosizedHeatingCapacity. If this input field is left blank or zero, then autosizing is assumed. HeatingDesignCapacity means user specifies the magnitude of maximum or nominal heating capacity or the program calculates the maximum or nominal design heating capacity if autosize is specified. CapacityPerFloorArea means the program calculates the design heating capacity from user specified heating capacity per floor area and floor area of the zone served by the hot water baseboard heater. FractionOfAutosizedHeatingCapacity means the program calculates the design heating capacity from user specified fraction and the auto-sized design heating capacity. The default method is HeatingDesignCapacity.
Field: Heating Design Capacity {W}[LINK]
This field is for the hot water baseboard heater design heating capacity in watts. This field can be autosized by EnergyPlus. This input field is autosizable. When the Heating Design Capacity Method is HeatingDesignCapacity and this input is blank, autosizing is assumed. Design day sizing run must be specified id autosize is specified.
Field: Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2 of hot water baseboard heater. This field is required field when the Heating Design Capacity Method is CapacityPerFloorArea. The program calculates the heating capacity from floor area of the zone served by hot water baseboard heater and the heating capacity per unit floor area value specified by the user. This field may be left blank.
Field: Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized heating capacity for the hot water baseboard heater. This input field is required when the Heating Design Capacity Method is FractionOfAutosizedHeatingCapacity. The program calculates the heating capacity from the design autosized heat capacity and user specified fraction. Design day sizing run must be specified. This field may be left blank. Default value is 1.0.
Field: U-Factor Times Area Value[LINK]
The overall heat transfer coefficient for the baseboard heater in watts per degree Celsius at design conditions. The U-Factor Times Area Value (UA) is used in an NTU - effectiveness calculation. An estimate of the UA can be obtained from:
\[q = UA \times ({T_{water,avg}} - {T_{air,avg}})\]
where q is the heat transferred from water to the air in watts; T\(_{water,\\ avg}\) is the average water temperature in degrees C; and T\(_{air,\\ avg}\) is the average air temperature in degrees C. Or the LMTD temperature difference can be used.
Field: Maximum Water Flow Rate[LINK]
The maximum hot water volumetric flow rate in m\(^{3}\)/sec.
Field Convergence Tolerance[LINK]
The control tolerance for the unit heating output. The unit is controlled by matching the unit output to the zone demand. For hot water baseboards, the model must be numerically inverted to obtain a specified output. The convergence tolerance is the error tolerance used to terminate the numerical inversion procedure. Basically this is the fraction:
\[\frac{{\left| {({Q_{bb,out}} - {Q_{ZoneLoad}})} \right|}}{{{Q_{ZoneLoad}}}} \le Convergence{\kern 1pt} Tolerance\]
The default is 0.001.
An example IDF for the hot water convective baseboard is shown below.
Outputs[LINK]
HVAC,Average,Baseboard Total Heating Rate [W]
HVAC,Sum,Baseboard Total Heating Energy [J]
HVAC,Sum,Baseboard Hot Water Energy [J]
HVAC,Average,Baseboard Hot Water Mass Flow Rate [kg/s]
HVAC,Average,Baseboard Air Mass Flow Rate [kg/s]
HVAC,Average,Baseboard Air Inlet Temperature [C]
HVAC,Average,Baseboard Air Outlet Temperature [C]
HVAC,Average,Baseboard Water Inlet Temperature [C]
HVAC,Average,Baseboard Water Outlet Temperature [C]
Baseboard Total Heating Rate [W][LINK]
This is the heat addition rate of the convective baseboard to the zone it is serving in Watts.
Baseboard Total Heating Energy [J][LINK]
This is the heat addition of the convective baseboard to the zone it is serving in Joules over the timestep being reported.
Baseboard Hot Water Energy [J][LINK]
This is the energy in the hot water used by the baseboard to heat the zone, in Joules.
Baseboard Hot Water Mass Flow Rate [kg/s][LINK]
This field reports the water mass flow rate at the inlet node of a baseboard unit.
Baseboard Air Mass Flow Rate [kg/s][LINK]
This field reports the air mass flow rate at the inlet node of a baseboard unit.
Baseboard Water Inlet Temperature [C][LINK]
This field reports the water temperatures at the inlet node of a baseboard unit.
Baseboard Water Outlet Temperature [C][LINK]
This field reports the water temperatures at the outlet node of a baseboard unit.
Baseboard Air Inlet Temperature [C][LINK]
This field reports the air temperatures at the inlet node of a baseboard unit.
Baseboard Air Outlet Temperature [C][LINK]
This field reports the air temperatures at the outlet node of a baseboard unit.
ZoneHVAC:Baseboard:Convective:Electric[LINK]
The electric baseboard heater is a component in the zone equipment simulation. The component is controlled to meet any remaining zone load not met by other equipment in the zone that have higher heating priority. The control is accomplished by taking the remaining zone load and dividing by the efficiency of the baseboard.
Inputs[LINK]
Field: Name[LINK]
A unique user assigned name for an instance of a electric baseboard heater unit. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
The name of the schedule (ref: Schedule) that denotes whether the electric baseboard heater unit can run during a given time period. A schedule value greater than 0 (usually 1 is used) indicates that the unit can be on during the time period. A value less than or equal to 0 (usually 0 is used) denotes that the unit must be off for the time period. If this field is blank, the schedule has values of 1 for all time periods.
Field: Heating Design Capacity Method[LINK]
Enter the method used to determine the heating design capacity or enter the method for scalable sizing of heating capacity of electric baseboard unit. Input allowed is either HeatingDesignCapacity, CapacityPerFloorArea, and FractionOfAutosizedHeatingCapacity. If this input field is left blank or zero, then autosizing is assumed. HeatingDesignCapacity means user specifies the magnitude of maximum or nominal heating capacity or the program calculates the maximum or nominal design heating capacity if autosize is specified. CapacityPerFloorArea means the program calculates the design heating capacity from user specified heating capacity per floor area and floor area of the zone served by the electric convective baseboard unit. FractionOfAutosizedHeatingCapacity means the program calculates the design heating capacity from user specified fraction and the auto-sized design heating capacity. The default method is HeatingDesignCapacity.
Field: Heating Design Capacity {W}[LINK]
This field is for the convective electric baseboard nominal heating capacity in watts. This field can be autosized by EnergyPlus. This input field is autosizable. Design day sizing run must be specified. This input field may be left blank.
Field: Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2 of electric convective baseboard unit. This field is required field when the Heating Design Capacity Method is CapacityPerFloorArea. The program calculates the heating capacity from floor area of the zone served by the electric convective baseboard unit and the heating capacity per unit floor area value specified by the user. This field may be left blank.
Field: Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized heating capacity for convective electric baseboard unit. This input field is required when the Heating Design Capacity Method is FractionOfAutosizedHeatingCapacity. The program calculates the heating capacity from the design autosized heating capacity and user specified fraction. Design day sizing must be specified. This field may be left blank. Default value is 1.0.
Field: Efficiency[LINK]
This is the overall electrical efficiency of the electric baseboard. The zone load met by this unit is divided by the electrical efficiency to obtain the total electric energy used.
An example IDF for the electric convective baseboard is shown below.
Outputs[LINK]
HVAC,Average,Baseboard Total Heating Rate [W]
HVAC,Sum,Baseboard Total Heating Energy [J]
HVAC,Meter,Baseboard:EnergyTransfer [J]
HVAC,Sum,Baseboard Electric Energy [J]
HVAC,Average,Baseboard Electric Power[W]
HVAC,Meter,Heating:Electricity[J]
Baseboard Total Heating Rate [W][LINK]
This is the heat addition rate of the electric convective baseboard to the zone it is serving in Watts.
Baseboard Total Heating Energy [J][LINK]
This is the heat addition of the convective baseboard to the zone it is serving in Joules over the timestep being reported.
Baseboard Electric Energy [J][LINK]
This is the total electric consumption of the baseboard for the zone it is serving in Joules over the timestep being reported.
Baseboard Electric Power [W][LINK]
This is the electric power required by the baseboard to the zone it is serving in Watts.
ZoneHVAC:LowTemperatureRadiant:VariableFlow[LINK]
This low temperature radiant system (hydronic) is a component of zone equipment that is intended to model any “radiant system” where water is used to supply/remove energy to/from a building surface (wall, ceiling, or floor). The component is controlled to meet any remaining zone load not met by other equipment in the zone that have higher priority. The control is accomplished by throttling the hot or chilled water flow to the unit. Note that this system will only control based on the radiant system controls defined by this input syntax and not via a zone thermostat such as is used for forced air systems. Note also that because this unit does not require a thermostat that in cases where no other systems are serving the zone in which this system resides that it will use the heating equipment priority to determine which system will run first. If the radiant system is serving a zone with forced air equipment, the radiant system will follow the priority order established by the zone thermostat but will still base its response on the controls defined by the user for the radiant system.
This model covers a wide range of low temperature radiant systems: heating and/or cooling, panel or embedded pipes, etc. It is not intended to simulate high temperature electric or gas radiant heaters. Those devices will be handled by a separate model and different input syntax. Low temperature radiant systems that use electric resistance heating should also be defined using separate input syntax (ref: ZoneHVAC:LowTemperatureRadiant:Electric).
Inputs[LINK]
Field: Name[LINK]
This field is an unique user assigned name for an instance of a hydronic low temperature radiant system. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that denotes whether the hydronic low temperature radiant system can run during a given time period. A schedule value less than or equal to 0 (usually 0 is used) denotes that the unit must be off for that time period. A value greater than 0 (usually 1 is used) denotes that the unit is available to operate during that time period. If this field is left blank, the schedule has a value of 1 for all time periods.
Field: Zone Name[LINK]
This field is the name of the zone (Ref: Zone) in which the hydronic low temperature radiant system is principally located and intended to affect. A system that is between two zones will still act upon each zone; however, the zone name referenced here should be the zone that controls the radiant system response.
Field: Surface Name or Radiant Surface Group Name[LINK]
This field is the name of the surface (Ref: BuildingSurface) or surface list (Ref: ZoneHVAC:LowTemperatureRadiant:SurfaceGroup) in which the hydronic tubing is embedded/contained. This specification attaches the source or sink from the radiant system to a particular surface and the contribution of the system to the heat balances of that surface. If this field is a surface list, then the source or sink is attached to all of the surfaces in the list with the radiant system surface group defining the breakdown of how flow rate is split between the various surfaces. Base surfaces (e.g., BuildingSurface:Detailed), door surfaces and internal mass are valid. Window surfaces are not valid surface types for embedded radiant systems.
Field: Hydronic Tubing Inside Diameter[LINK]
This field is the inside diameter of the tubes through which water is circulated for the system being defined by this statement. The inside diameter should be recorded in meters and is used to determine the convective heat transfer from the water to the inside surface of the hydronic tubing.
Field: Hydronic Tubing Length[LINK]
This field is the total length of pipe embedded in the surface named above in the surface name field. The length of the tube should be entered in meters and is used to determine the effectiveness of heat transfer from the fluid being circulated through the tubes and the tube/surface. Longer tubing lengths result in more heat will be transferred to/from the radiant surface to the circulating fluid. Note that if the user elects to autosize this field that a standard zone thermostat such as would be used for a forced air system must be defined as autosizing calculations are based on the zone thermostat value and not on the radiant system control values. In addition, when the user opts to autosize this calculation, the tube spacing from the construction of each surface associated with this system is used along with each individual surface area to make an approximation of the tubing length.
Field: Temperature Control Type[LINK]
This field specifies along with the throttling range and setpoint schedules how the user wishes to control the hydronic radiant system. The temperature denoted in the setpoint schedule can refer to one of five different temperatures: the zone mean air temperature, the zone mean radiant temperature, the zone operative temperature, the outdoor dry-bulb temperature, or the outdoor wet-bulb temperature. The choice of temperature is controlled by the current field—temperature control type. The user must select from the following options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
OutdoorDryBulbTemperature
OutdoorWetBulbTemperature
Operative temperature for radiant system controls is the average of Mean Air Temperature and Mean Radiant Temperature. If the user does not select a control type, MeanAirTemperature control is assumed by EnergyPlus. See the throttling range and control temperature schedule fields below for more information.
Field: Heating Design Capacity Method[LINK]
Enter the method used to determine the heating design capacity for scalable sizing. Input allowed is either HeatingDesignCapacity, CapacityPerFloorArea, and FractionOfAutosizedHeatingCapacity. If this input field is left blank or zero, then autosizing is assumed. HeatingDesignCapacity means user specifies the magnitude of maximum or nominal heating capacity or the program calculates the design heating capacity if autosize is specified. CapacityPerFloorArea means the program calculates the design heating capacity from user specified heating capacity per floor area and floor area of the zone served by the low temperature radiant variable flow unit. FractionOfAutosizedHeatingCapacity means the program calculates the design heating capacity from user specified fraction and the auto-sized design heating capacity. The default method is HeatingDesignCapacity.
Field: Heating Design Capacity {W}[LINK]
This field is for the low temperature radiant variable flow unit design heating capacity in watts. This field can be autosized by EnergyPlus. This input field is autosizable. When the Heating Design Capacity Method is HeatingDesignCapacity and this input is blank, autosizing is assumed. Design day sizing run must be specified if autosized.
Field: Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2 of low temperature radiant variable flow unit. This field is required field when the Heating Design Capacity Method is CapacityPerFloorArea. The program calculates the heating capacity from floor area of the zone served by the low temperature radiant variable flow unit and the heating capacity per unit floor area value specified by the user. This field may be left blank.
Field: Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized heating capacity for low temperature radiant variable flow unit. This input field is required when the Heating Design Capacity Method is FractionOfAutosizedHeatingCapacity. The program calculates the heating capacity from the design autosized heat capacity and user specified fraction. Design day sizing run must be specified. This field may be left blank. Default value is 1.0.
Field: Maximum Hot Water Flow[LINK]
This field is the maximum flow rate of hot water through the radiant system in m\(^{3}\)/sec. The controls for the radiant system will vary the flow rate of hot water through the surface using zero flow and the maximum flow rate specified in this field as the lower and upper bounds, respectively. Note that if the user elects to autosize this field that a standard zone thermostat such as would be used for a forced air system must be defined as autosizing calculations are based on the zone thermostat value and not on the radiant system control values.
Field: Heating Water Inlet Node Name[LINK]
This field contains the name of the hot water inlet node to the radiant system. Note that this node name must also show up in the branch description when defining the plant demand side network in a manner identical to defining a heating coil.
Field: Heating Water Outlet Node Name[LINK]
This field contains the name of the hot water oulet node to the radiant system. Note that this node name must also show up in the branch description when defining the plant demand side network in a manner identical to defining a heating coil.
Field: Heating Control Throttling Range[LINK]
This field specifies the range of temperature in degrees Celsuis over which the radiant system throttles from zero flow rate up to the maximum defined by the maximum hot water flow rate field described above. The throttling range parameter is used in conjunction with the control temperature to define the response of the system to various zone conditions. The heating control temperature schedule specifies the “setpoint” temperature where the flow rate to the system is at half of the maximum flow rate. For example, if the heating control temperature setpoint is currently 15°C and the heating throttling range is 2°C, the water flow rate to the radiant system will be zero when the controlling temperature (MAT, MRT, Operative Temperature, ODB, or OWB; see control type field above) is at or above 16°C and the maximum flow rate when the controlling temperature is at or below 14°C. This represents a throttling range of 2°C around the setpoint of 15°C. In between 14°C and 16°C, the flow rate to the radiant system is varied linearly.
Field: Heating Control Temperature Schedule Name[LINK]
This field specifies the heating setpoint or control temperature for the radiant system in degrees Celsius. Used in conjunction with the previous field (heating control throttling range), it will define whether or not the system is running and the current flow rate. Water flow rate to the system is varied linearly around the setpoint temperature based on the throttling range and the maximum heating flow rate parameters (see above). It should be noted that this control schedule will allow different setpoint temperatures throughout the year for heating. The control of the radiant system is based solely on the heating control temperature schedule, the cooling control temperature schedule (see below), and the control temperature type listed above. The radiant system will not use any zone thermostat that might be used by other systems serving the zone in which the radiant system resides.
Field: Cooling Design Capacity Method[LINK]
Enter the method used to determine the cooling design capacity for scalable sizing. Input allowed is either CoolingDesignCapacity, CapacityPerFloorArea, and FractionOfAutosizedCoolingCapacity. If this input field is left blank or zero, then autosizing is assumed. CoolingDesignCapacity means user specifies the design cooling capacity or the program calculates the design cooling capacity if autosize is specified. CapacityPerFloorArea means the program calculates the design cooling capacity from user specified heating capacity per floor area and floor area of the zone served by the low temperature radiant variable flow unit. FractionOfAutosizedCoolingCapacity means the program calculates the design cooling capacity from user specified fraction and the auto-sized design cooling capacity. The default method is CoolingDesignCapacity.
Field: Cooling Design Capacity {W}[LINK]
This field is for the low temperature radiant variable flow unit design cooling capacity in watts. This field can be autosized by EnergyPlus. This input field is autosizable. When the Cooling Design Capacity Method is CoolingDesignCapacity and this input is blank, autosizing is assumed. Design day sizing run must be specified if autosized.
Field: Cooling Design Capacity Per Floor Area {W/m2}[LINK]
Enter the cooling capacity per unit floor area in m3/s-m2 of low temperature radiant variable flow unit. This field is required field when the Cooling Design Capacity Method is CapacityPerFloorArea. The program calculates the cooling capacity from floor area of the zone served by the low temperature radiant variable flow unit and the cooling capacity per unit floor area value specified by the user. This field may be left blank.
Field: Fraction of Autosized Cooling Design Capacity[LINK]
Enter the cooling capacity as a fraction of the autosized cooling capacity for low temperature radiant variable flow unit. This input field is required when the Cooling Design Capacity Method is FractionOfAutosizedCoolingCapacity. The program calculates the cooling capacity from the design autosized cooling capacity and user specified fraction. Design day sizing run must be specified. This field may be left blank. Default value is 1.0.
Field: Maximum Cold Water Flow[LINK]
This field is the maximum flow rate of cold water through the radiant system in m\(^{3}\)/sec. The controls for the radiant system will vary the flow rate of cold water through the surface using zero flow and the maximum flow rate specified in this field as the lower and upper bounds, respectively. Note that this field is optional and not required for a heating only system. Note also that if the user elects to autosize this field that a standard zone thermostat such as would be used for a forced air system must be defined as autosizing calculations are based on the zone thermostat value and not on the radiant system control values.
Field: Cooling Water Inlet Node Name[LINK]
This field contains the name of the cold water inlet node to the radiant system. Note that this node name must also show up in the branch description when defining the plant demand side network in a manner identical to defining a cooling coil. As with the maximum cold water flow rate, this field is optional and not required for a heating only system.
Field: Cooling Water Outlet Node Name[LINK]
This field contains the name of the cold water oulet node to the radiant system. Note that this node name must also show up in the branch description when defining the plant demand side network in a manner identical to defining a cooling coil. As with the maximum cold water flow rate, this field is optional and not required for a heating only system.
Field: Cooling Control Throttling Range[LINK]
This field specifies the range of temperature in degrees Celsuis over which the radiant system throttles from zero flow rate up to the maximum defined by the maximum cold water flow rate field described above. The throttling range parameter is used in conjunction with the control temperature to define the response of the system to various zone conditions. The cooling control temperature schedule specifies the “setpoint” temperature where the flow rate to the system is at half of the maximum flow rate. For example, if the cooling control temperature setpoint is currently 25°C and the cooling throttling range is 2°C, the water flow rate to the radiant system will be zero when the controlling temperature (MAT, MRT, Operative Temperature, ODB, or OWB; see control type field above) is at or below 24°C and the maximum flow rate when the controlling temperature is at or above 26°C. This represents a throttling range of 2°C around the setpoint of 25°C. In between 24°C and 26°C, the flow rate to the radiant system is varied linearly.
Field: Cooling Control Temperature Schedule Name[LINK]
This field specifies the cooling setpoint or control temperature for the radiant system in degrees Celsius. Used in conjunction with the previous field (cooling control throttling range), it will define whether or not the system is running and the current flow rate. Water flow rate to the system is varied linearly around the setpoint temperature based on the throttling range and the maximum cooling flow rate parameters (see above). It should be noted that this control schedule will allow different setpoint temperatures throughout the year for cooling. The control of the radiant system is based solely on the heating control temperature schedule listed above, the cooling control temperature schedule, and the control temperature type listed above. The radiant system will not use any zone thermostat that might be used by other systems serving the zone in which the radiant system resides.
Field: Condensation Control Type[LINK]
When radiant systems do cooling, there is the possibility that condensation will occur on the surface that is being cooled. This is due to the fact that the surface temperature may drop below the dew-point temperature of the space. When this happens, condensation on the surface will occur. There are three options for handling this situation: Off, SimpleOff, and VariableOff. This parameter is optional and will default to SimpleOff.
Off - EnergyPlus will not do anything other than produce a warning message when condensation is predicted to occur. The program will simply continue on, no moisture will be removed from the zone air, and there will be no adjustment of the surface temperature as a result of the condensation.
SimpleOff - the program will predict cases where condensation will occur and shut-off the radiant system to avoid this situation. With this option, the users also have the opportunity to adjust when the system will shut down. This is specified with the next parameter (field: Condensation Control Dewpoint Offset).
VariableOff - the program will determine whether condensation is predicted for the flow rate determined by the unit control scheme. If condensation is predicted, the unit makes one attempt to reduce the flow rate using linear interpolation between the controlled flow rate and a zero flow rate to achieve a surface temperature that would match the dew-point temperature modified by the condensation control dew-point offset (field: Condensation Control Dewpoint Offset). For example, if the controlled flow rate results in a surface temperature of 10°C, a zero flow rate results in a surface temperature of 12°C, and the modified condensation dew-point temperature is 11°C, then the reduced flow rate would be half of the controlled flow rate. If this reduced flow approximation does not result in condensation, then this reduced flow is used for the unit. If the reduced flow approximation still results in condensation, then the unit is turned off to avoid excessive iterations.
Field: Condensation Control Dewpoint Offset[LINK]
This optional parameter is only valid with the SimpleOff and VariableOff condensation handling algorithm (see previous input parameter). It establishes the difference between the calculated dew-point temperature of the space and the allowed surface temperature to which the surface can drop before the radiant system shuts down (SimpleOff) or reduces its flow rate (VariableOff) to avoid condensation in degrees Celsius. This parameter can be any positive, negative, or zero value. When this parameter is zero, the radiant system will shut down or reduce the flow rate when the surface temperature drops to the dew-point temperature or below. When this parameter is positive, the radiant system will shut down or reduce the flow rate when the surface is the number of degrees Celsius above the dew-point temperature. This allows some extra safety to avoid condensation. When this parameter is negative, the radiant system will shut down or reduce the flow rate when the surface temperature is the number of degrees Celsius below the dew-point temperature. While not recommended, this strategy allows the user to simulate a situation where small amounts of condensation are tolerable. The default value for this parameter is 1°C.
Field: Number of Circuits[LINK]
This optional input allows the user to choose between modeling each surface in the radiant system as a single hydronic circuit or to allow the program to divide the surface into multiple parallel hydronic circuits based on the next input field Circuit Length. To model as a single circuit choose OnePerSurface. To model as multiple circuits choose CalculateFromCircuitLength. It is recommended that CalculateFromCircuitLength be chosen. The default is OnePerSurface for backward compatibility with older versions of EnergyPlus.
Field: Circuit Length[LINK]
The length in meters of each parallel hydronic circuit in a surface. Used when the previous input field is set to CalculateFromCircuitLength. The default is 106.7 meters (350 feet), which is the maximum circuit length allowed in Title 24.
An example IDF with a hydronic low temperature radiant system is shown below.
Outputs[LINK]
HVAC,Average,Zone Radiant HVAC Heating Rate [W]
HVAC,Sum,Zone Radiant HVAC Heating Energy [J]
HVAC,Average,Zone Radiant HVAC Cooling Rate [W]
HVAC,Sum,Zone Radiant HVAC Cooling Energy [J]
HVAC,Average,Zone Radiant HVAC Mass Flow Rate [kg/s]
HVAC,Average,Zone Radiant HVAC Inlet Temperature [C]
HVAC,Average,Zone Radiant HVAC Outlet Temperature [C]
HVAC,Sum,Zone Radiant HVAC Moisture Condensation Time[s]
HVAC,Sum,Zone Radiant HVAC Heating Fluid Energy [J]
HVAC,Sum,Zone Radiant HVAC Cooling Fluid Energy [J]
Zone Radiant HVAC Heating Rate [W][LINK]
This field reports the heating input rate to the low temperature radiant system in Watts. This is the heat source to the surface that is defined as the radiant system. The heating rate is determined by the zone conditions and the control scheme defined in the user input.
Zone Radiant HVAC Heating Energy [J][LINK]
This field reports the heating input to the low temperature radiant system in Joules. This is the heat source to the surface that is defined as the radiant system. The heating rate is determined by the zone conditions, the control scheme defined in the user input, and the timestep.
Zone Radiant HVAC Cooling Rate [W][LINK]
This field reports the cooling input rate to the low temperature radiant system in Watts. This is the heat sink to the surface that is defined as the radiant system. The cooling rate is determined by the zone conditions and the control scheme defined in the user input.
Zone Radiant HVAC Cooling Energy [J][LINK]
This field reports the cooling input to the low temperature radiant system in Joules. This is the heat sink to the surface that is defined as the radiant system. The cooling rate is determined by the zone conditions, the control scheme defined in the user input, and the timestep.
Zone Radiant HVAC Mass Flow Rate Rate [kg/s][LINK]
This field reports the mass flow rate of water through the low temperature radiant system in kilograms per second.
Zone Radiant HVAC Inlet Temperature [C][LINK]
This field reports the temperature of water entering the low temperature radiant system in Celsius.
Zone Radiant HVAC Outlet Temperature [C][LINK]
This field reports the temperature of water leaving the low temperature radiant system in Celsius.
Zone Radiant HVAC Moisture Condensation Time[s][LINK]
This field reports the amount of time when condensation is occurring. When using the Off condensation control, this simply reports the amount of time when condensation occurs. When using the SimpleOff condensation control, this indicates the amount of time when the system has been shut off because of the potential danger of condensation.
Zone Radiant HVAC Heating Fluid Energy [J][LINK]
This is the demand placed on the hot fluid plant loop connection serving the low temperature radiant system, in Joules.
Zone Radiant HVAC Cooling Fluid Energy [J][LINK]
This is the demand placed on the cooling fluid plant loop connection serving the low temperature radiant system, in Joules.
ZoneHVAC:LowTemperatureRadiant:ConstantFlow[LINK]
This low temperature radiant system (hydronic) is a component of zone equipment that is intended to model any “radiant system” where water is used to supply/remove energy to/from a building surface (wall, ceiling, or floor). The component is controlled via control schedules as described in the syntax below and does not require a zone thermostat. Note that because this unit does not require a thermostat that in cases where no other systems are serving the zone in which this system resides that it will use the heating equipment priority to determine which system will run first. If the radiant system is serving a zone with forced air equipment, the radiant system will follow the priority order established by the zone thermostat but will still base its response on the controls defined by the user for the radiant system.
The constant flow system differs from the hydronic system describe above in what it controls. The hydronic system varies the flow rate through the radiant system based on some control temperature. The constant flow system keeps flow rate constant via a local circulation pump and varies the water temperature that is sent to the radiant system. This is accomplished with a mixing valve that is controlled by a sensor. This model covers a wide range of low temperature radiant systems: heating and/or cooling, panel or embedded pipes, etc. It is not intended to simulate high temperature electric or gas radiant heaters. Those devices will be handled by a separate model and different input syntax. Low temperature radiant systems that use electric resistance heating should also be defined using separate input syntax (ref: ZoneHVAC:LowTemperatureRadiant:Electric). Low temperature radiant systems that vary the flow rate through the radiant system should also be defined using separate input syntax (ref: ZoneHVAC:LowTemperatureRadiant:VariableFlow)
One of the other differences between this model and the variable flow hydronic radiant system is that the constant flow radiant system has a built-in local secondary loop. It will recirculate flow coming out of the system and mix this with flow from the loop to arrive at the desired inlet temperature to the radiant system (note that this model has the temperature sensor AFTER the pump to insure proper inlet temperature to the radiant system). The local loop also contains a pump which is assumed to be upstream of the radiant system and after the mixing valve. So, the local loop can have some recirculation. The flow from the main loop may also bypass the radiant system if more than enough flow is available and the main loop is also a constant flow system.
Inputs[LINK]
Field: Name[LINK]
This field is an unique user assigned name for an instance of a constant flow low temperature radiant system. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that denotes whether the constant flow low temperature radiant system can run during a given time period. A schedule value less than or equal to 0 (usually 0 is used) denotes that the unit must be off for that time period. A value greater than 0 (usually 1 is used) denotes that the unit is available to operate during that time period. If this field is left blank, the schedule has a value of 1 for all time periods.
Field: Zone Name[LINK]
This field is the name of the zone (Ref: Zone) in which the constant flow low temperature radiant system is principally located and intended to affect. A system that is between two zones will still act upon each zone; however, the zone name referenced here should be the zone that controls the radiant system response.
Field: Surface Name or Radiant Surface Group Name[LINK]
This field is the name of the surface (Ref: BuildingSurface:Detailed) or surface list (Ref: ZoneHVAC:LowTemperatureRadiant:SurfaceGroup) in which the hydronic tubing is embedded/contained. This specification attaches the source or sink from the radiant system to a particular surface and the contribution of the system to the heat balances of that surface. If this field is a surface list, then the source or sink is attached to all of the surfaces in the list with the radiant system surface group defining the breakdown of how flow rate is split between the various surfaces. Base surfaces (e.g., BuildingSurface:Detailed), door surfaces and internal mass are valid. Window surfaces are not valid surface types for embedded radiant systems.
Field: Hydronic Tubing Inside Diameter[LINK]
This field is the inside diameter of the tubes through which water is circulated for the system being defined by this statement. The inside diameter should be recorded in meters and is used to determine the convective heat transfer from the water to the inside surface of the hydronic tubing.
Field: Hydronic Tubing Length[LINK]
This field is the total length of pipe embedded in the surface named above in the surface name field. The length of the tube should be entered in meters and is used to determine the effectiveness of heat transfer from the fluid being circulated through the tubes and the tube/surface. Longer tubing lengths result in more heat being transferred to/from the radiant surface to the circulating fluid. Note that if the user elects to autosize this field that a standard zone thermostat such as would be used for a forced air system must be defined as autosizing calculations are based on the zone thermostat value and not on the radiant system control values. In addition, when the user opts to autosize this calculation, the tube spacing from the construction of each surface associated with this system is used along with each individual surface area to make an approximation of the tubing length.
Field: Temperature Control Type[LINK]
This field specifies along with setpoint (control) and water schedules how the user wishes to control the constant flow radiant system. The temperature denoted in the setpoint schedule can refer to one of five different temperatures: the zone mean air temperature, the zone mean radiant temperature, the zone operative temperature, the outdoor dry-bulb temperature, or the outdoor wet-bulb temperature. The choice of temperature is controlled by the current field—temperature control type. The user must select from the following options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
OutdoorDryBulbTemperature
OutdoorWetBulbTemperature
Operative temperature for radiant system controls is the average of Mean Air Temperature and Mean Radiant Temperature. If the user does not select a control type, MeanAirTemperature control is assumed by EnergyPlus. See the throttling range and control temperature schedule fields below for more information.
Field: Rated Flow Rate[LINK]
This field is the maximum flow rate of water through the radiant system in m\(^{3}\)/sec. This flow rate is held constant by the local component pump, but the user has the option of varying this flow rate via a schedule (see next input field). The constant flow system will accept this flow rate and control the inlet temperature based on the control and water temperature schedules defined below. This field is autosizable.
Field: Pump Flow Rate Schedule Name[LINK]
This field modifies the maximum flow rate of water through the radiant system in m\(^{3}\)/sec. This input is “optional”. If the user does not enter a schedule, the flow rate through the radiant system is assumed to be constant during all hours that it is operating based on the value entered in the previous input field. Note that the values for this schedule must be between zero and one. The values in this schedule are multipliers on the previous field – Rated Flow Rate.
Field: Rated Pump Head[LINK]
This numeric field contains the pump’s rated head in Pascals.
Field: Rated Power Consumption[LINK]
This numeric field contains the pump’s rated power consumption in Watts.
Field: Motor Efficiency[LINK]
This numeric field contains the pump’s efficiency in decimal form (0 = 0%, 1 = 100%).
Field: Fraction of Motor Inefficiencies to Fluid Stream[LINK]
This numeric field contains the pump’s fraction of power loss to the fluid.
Field: Heating Water Inlet Node Name[LINK]
This field contains the name of the hot water inlet node to the radiant system. Note that this node name must also show up in the branch description when defining the plant demand side network in a manner identical to defining a heating coil.
Field: Heating Water Outlet Node Name[LINK]
This field contains the name of the hot water outlet node to the radiant system. Note that this node name must also show up in the branch description when defining the plant demand side network in a manner identical to defining a heating coil.
Field: Heating High Water Temperature Schedule Name[LINK]
This field specifies the high water temperature in degrees Celsius for the temperature control of a constant flow radiant heating system. Water and control temperatures for heating work together to provide a linear function that determines the water temperature sent to the radiant system. The current control temperature (see Temperature Control Type above) is compared to the high and low control temperatures at the current time. If the control temperature is above the high temperature, then the system will be turned off and the water mass flow rate will be zero. If the control temperature is below the low temperature, then the inlet water temperature is set to the high water temperature. If the control temperature is between the high and low value, then the inlet water temperature is linearly interpolated between the low and high water temperature values. For more information and a graph of how the water and control schedules affect the system operation, please consult the Engineering Reference document.
Field: Heating Low Water Temperature Schedule Name[LINK]
This field specifies the low water temperature in degrees Celsius for the temperature control of a constant flow heating radiant system. For more information on its interpretation, see Heating High Water Temperature Schedule above.
Field: Heating High Control Temperature Schedule Name[LINK]
This field specifies the high control temperature in degrees Celsius for the temperature control of a constant flow heating radiant system. For more information on its interpretation, see Heating High Water Temperature Schedule above.
Field: Heating Low Control Temperature Schedule Name[LINK]
This field specifies the low control temperature in degrees Celsius for the temperature control of a constant flow heating radiant system. For more information on its interpretation, see Heating High Water Temperature Schedule above.
Field: Cooling Water Inlet Node Name[LINK]
This field contains the name of the cold water inlet node to the radiant system. Note that this node name must also show up in the branch description when defining the plant demand side network in a manner identical to defining a cooling coil. As with the maximum cold water flow rate, this field is optional and not required for a heating only system.
Field: Cooling Water Outlet Node Name[LINK]
This field contains the name of the cold water outlet node to the radiant system. Note that this node name must also show up in the branch description when defining the plant demand side network in a manner identical to defining a cooling coil. As with the maximum cold water flow rate, this field is optional and not required for a heating only system.
Field: Cooling High Water Temperature Schedule Name[LINK]
This field specifies the high water temperature in degrees Celsius for the temperature control of a constant flow radiant cooling system. Water and control temperatures for heating work together to provide a linear function that determines the water temperature sent to the radiant system. The current control temperature (see Temperature Control Type above) is compared to the high and low control temperatures at the current time. If the control temperature is above the high temperature, then the inlet water temperature is set to the low water temperature. If the control temperature is below the low temperature, then system will be turned off and the water mass flow rate will be zero. If the control temperature is between the high and low value, then the inlet water temperature is linearly interpolated between the low and high water temperature values. For more information and a graph of how the water and control schedules affect the system operation, please consult the Engineering Reference document.
Field: Cooling Low Water Temperature Schedule Name[LINK]
This field specifies the low water temperature in degrees Celsius for the temperature control of a constant flow cooling radiant system. For more information on its interpretation, see Cooling High Water Temperature Schedule above.
Field: Cooling High Control Temperature Schedule Name[LINK]
This field specifies the high control temperature in degrees Celsius for the temperature control of a constant flow cooling radiant system. For more information on its interpretation, see Cooling High Water Temperature Schedule above.
Field: Cooling Low Control Temperature Schedule Name[LINK]
This field specifies the low control temperature in degrees Celsius for the temperature control of a constant flow cooling radiant system. For more information on its interpretation, see Cooling High Water Temperature Schedule above.
Field: Condensation Control Type[LINK]
When radiant systems do cooling, there is the possibility that condensation will occur on the surface that is being cooled. This is due to the fact that the surface temperature may drop below the dew-point temperature of the space. When this happens, condensation on the surface will occur. There are three options for handling this situation: Off, SimpleOff, and VariableOff. This parameter is optional and will default to SimpleOff.
Off - EnergyPlus will not do anything other than produce a warning message when condensation is predicted to occur. The program will simply continue on; no moisture will be removed from the zone air and there will be no adjustment of the surface temperature as a result of the condensation.
SimpleOff - the program will predict cases where condensation will occur and shut-off the radiant system to avoid this situation. With this option, the users also have the opportunity to adjust when the system will shut down. This is specified with the next parameter (field: Condensation Control Dewpoint Offset).
VariableOff - the program will determine whether condensation is predicted for the flow rate determined by the unit control scheme. If condensation is predicted, the unit makes one attempt to avoid condensation by increasing the water inlet temperature to the system to match the dew-point temperature modified by the condensation control dew-point offset (field: Condensation Control Dewpoint Offset). For example, if a surface in the space is predicted to be 15°C and the modified condensation dew-point temperature is 17°C, then the inlet water temperature to the unit is reset to 17°C and the system is simulated again with this new inlet water temperature. If this increased inlet water temperature does not result in condensation, then the simulation continues using this operating condition for the system. If the increased inlet water temperature still results in condensation, then the unit is turned off to avoid excessive iterations.
Field: Condensation Control Dewpoint Offset[LINK]
This optional parameter is only valid with the SimpleOff and VariableOff condensation handling algorithm (see previous input parameter). It establishes the difference between the calculated dew-point temperature of the space and the allowed surface temperature to which the surface can drop before the radiant system shuts down (SimpleOff) or tries to adjust the inlet water temperature (VariableOff) in degrees Celsius. This parameter can be any positive, negative, or zero value. When this parameter is zero, the radiant system will shut down or adjust the inlet water temperature when the surface temperature drops to the dew-point temperature or below. When this parameter is positive, the radiant system will shut down or increase the inlet water temperature when the surface is the number of degrees Celsius above the dew-point temperature. This allows some extra safety to avoid condensation. When this parameter is negative, the radiant system will shut down or increase the inlet water temperature when the surface temperature is the number of degrees Celsius below the dew-point temperature. While not recommended, this strategy allows the user to simulate a situation where small amounts of condensation are tolerable. The default value for this parameter is 1°C.
Field: Number of Circuits[LINK]
This optional input allows the user to choose between modeling each surface in the radiant system as a single hydronic circuit or to allow the program to divide the surface into multiple parallel hydronic circuits based on the next input field Circuit Length. To model as a single circuit choose OnePerSurface. To model as multiple circuits choose CalculateFromCircuitLength. It is recommended that CalculateFromCircuitLength be chosen. The default is OnePerSurface for backward compatibility with older versions of EnergyPlus.
Field: Circuit Length[LINK]
The length in meters of each parallel hydronic circuit in a surface. Used when the previous input field is set to CalculateFromCircuitLength. The default is 106.7 meters (350 feet), which is the maximum circuit length allowed in Title 24.
An example IDF with a constant flow low temperature radiant system is shown below.
Outputs[LINK]
HVAC,Average,Zone Radiant HVAC Heating Rate [W]
HVAC,Sum,Zone Radiant HVAC Heating Energy [J]
HVAC,Average,Zone Radiant HVAC Cooling Rate [W]
HVAC,Sum,Zone Radiant HVAC Cooling Energy [J]
HVAC,Average,Zone Radiant HVAC Mass Flow Rate [kg/s]
HVAC,Average,Zone Radiant HVAC Injection Mass Flow Rate [kg/s]
HVAC,Average,Zone Radiant HVAC Recirculation Mass Flow Rate [kg/s]
HVAC,Average,Zone Radiant HVAC Inlet Temperature [C]
HVAC,Average,Zone Radiant HVAC Outlet Temperature [C]
HVAC,Average,Zone Radiant HVAC Pump Inlet Temperature [C]
HVAC,Average,Zone Radiant HVAC Pump Electric Power[W]
HVAC,Sum,Zone Radiant HVAC Pump Electric Energy [J]
HVAC,Average,Zone Radiant HVAC Pump Mass Flow Rate [kg/s]
HVAC,Average,Zone Radiant HVAC Pump Fluid Heat Gain Rate [W]
HVAC,Sum,Zone Radiant HVAC Pump Fluid Heat Gain Energy [J]
HVAC,Sum,Zone Radiant HVAC Moisture Condensation Time [s]
HVAC,Sum,Zone Radiant HVAC Cooling Fluid Heat Transfer Energy [J]
HVAC,Sum,Zone Radiant HVAC Heating Fluid Heat Transfer Energy [J]
Zone Radiant HVAC Heating Rate [W][LINK]
This field reports the heating input rate to the low temperature radiant system in Watts. This is the heat source to the surface that is defined as the radiant system. The heating rate is determined by the zone conditions and the control scheme defined in the user input.
Zone Radiant HVAC Heating Energy [J][LINK]
This field reports the heating input to the low temperature radiant system in Joules. This is the heat source to the surface that is defined as the radiant system. The heating rate is determined by the zone conditions, the control scheme defined in the user input, and the timestep.
Zone Radiant HVAC Cooling Rate [W][LINK]
This field reports the cooling input rate to the low temperature radiant system in Watts. This is the heat sink to the surface that is defined as the radiant system. The cooling rate is determined by the zone conditions and the control scheme defined in the user input.
Zone Radiant HVAC Cooling Energy [J][LINK]
This field reports the cooling input to the low temperature radiant system in Joules. This is the heat sink to the surface that is defined as the radiant system. The cooling rate is determined by the zone conditions, the control scheme defined in the user input, and the timestep.
Zone Radiant HVAC Mass Flow Rate [kg/s][LINK]
This field reports the mass flow rate of water through the low temperature radiant system in kilograms per second. This should be identical to the pump flow rate for the system.
Zone Radiant HVAC Injection Mass Flow Rate [kg/s][LINK]
This field reports the mass flow rate of water that is injected into the radiant system from the main loop. A valve will control the injection and recirculation mass flow rates (see next field) to match the temperature controls specified by the user and dictated by the current simulation conditions.
Zone Radiant HVAC Recirculation Mass Flow Rate [kg/s][LINK]
This field reports the mass flow rate of water that is recirculated from the radiant system outlet and mixed with the injection flow from the main loop. A valve will control the injection and recirculation mass flow rates (see next field) to match the temperature controls specified by the user and dictated by the current simulation conditions.
Zone Radiant HVAC Inlet Temperature [C][LINK]
This field reports the temperature of water entering the low temperature radiant system in Celsius. This may differ from the inlet node temperature for the component since this component has its own local secondary loop.
Zone Radiant HVAC Outlet Temperature [C][LINK]
This field reports the temperature of water leaving the low temperature radiant system in Celsius. This may differ from the outlet node temperature for the component since this component has its own local secondary loop.
Zone Radiant HVAC Pump Inlet Temperature [C][LINK]
This field reports the temperature of water entering the low temperature radiant system pump in Celsius. This may differ from the inlet node temperature for the component since this component has its own local secondary loop. It is assumed that the pump is upstream of the radiant system.
Zone Radiant HVAC Pump Electric Power [W][LINK]
This field reports the rate of electric power consumption for the pump which supplies flow to the constant flow radiant system in Watts.
Zone Radiant HVAC Pump Electric Energy [J][LINK]
This field reports the electric power consumption for the pump which supplies flow to the constant flow radiant system in Joules.
Zone Radiant HVAC Pump Mass Flow Rate [kg/s][LINK]
This field reports the mass flow rate of water through the low temperature radiant system pump in kilograms per second. This should be identical to the flow rate for the system.
Zone Radiant HVAC Pump Fluid Heat Gain Rate [W][LINK]
This field reports the rate at which heat is added to the fluid stream as it passes through the pump in Watts. This heat is reflected in the radiant system inlet temperature which will be different from the pump inlet temperature if this field has a non-zero value.
Zone Radiant HVAC Pump Fluid Heat Gain Energy [J][LINK]
This field reports the amount of heat energy added to the fluid stream as it passes through the pump in Joules. This heat is reflected in the radiant system inlet temperature which will be different from the pump inlet temperature if this field has a non-zero value.
Zone Radiant HVAC Moisture Condensation Time [s][LINK]
This field reports the amount of time when condensation is occurring. When using the Off condensation control, this simply reports the amount of time when condensation occurs. When using the SimpleOff condensation control, this indicates the amount of time when the system has been shut off because of the potential danger of condensation.
Zone Radiant HVAC Cooling Fluid Heat Transfer Energy [J][LINK]
The heat transfer energy for the cooling fluid connection, in Joules.
Zone Radiant HVAC Heating Fluid Heat Transfer Energy [J][LINK]
The heat transfer energy for the heating fluid connection, in Joules.
ZoneHVAC:LowTemperatureRadiant:Electric[LINK]
This low temperature radiant system (electric) is a component of zone equipment that is intended to model any “radiant system” where electric resistance heating is used to supply energy (heat) to a building surface (wall, ceiling, or floor). The component is controlled by the radiant system controls that are defined in the syntax below and this control does not require the use of a zone thermostat unless the unit is being autosized. Note also that because this unit does not require a thermostat that in cases where no other systems are serving the zone in which this system resides that it will use the heating equipment priority to determine which system will run first. If the radiant system is serving a zone with forced air equipment, the radiant system will follow the priority order established by the zone thermostat but will still base its response on the controls defined by the user for the radiant system.
The control is accomplished by varying the electrical power supplied to the unit. This model covers either a radiant panel system or wires embedded in entire walls, floors, or ceilings. It is not intended to simulate high temperature electric or gas radiant heaters. Those devices will be handled by a separate model (ref: ZoneHVAC:HighTemperatureRadiant) and different input syntax. Low temperature radiant systems that use water flowing through tubes to provide heat to the system should also be defined using separate input syntax (ref: ZoneHVAC:LowTemperatureRadiant:VariableFlow or ConstantFlow).
Inputs[LINK]
Field: Name[LINK]
This field is an unique user assigned name for an instance of an electric low temperature radiant system. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that denotes whether the electric low temperature radiant system can operate during a given time period. A schedule value less than or equal to 0 (usually 0 is used) denotes that the unit must be off for that time period. A value greater than 0 (usually 1 is used) denotes that the unit is available to operate during that time period. If this field is left blank, the schedule has a value of 1 for all time periods.
Field: Zone Name[LINK]
This field is the name of the zone (Ref: Zone) in which the electric low temperature radiant system is principally located and intended to affect. A system that is between two zones will still act upon each zone; however, the zone name referenced here should be the zone that controls the radiant system response.
Field: Surface Name or Radiant Surface Group Name[LINK]
This field is the name of the surface (Ref: BuildingSurface) or surface list (Ref: ZoneHVAC:LowTemperatureRadiant:SurfaceGroup) in which the heating element is embedded/contained. This specification attaches the source or sink from the radiant system to a particular surface and the contribution of the system to the heat balances of that surface. If this field is a surface list, then the source or sink is attached to all of the surfaces in the list with the radiant system surface group defining the breakdown of how energy flow is split between the various surfaces. Base surfaces (e.g., BuildingSurface:Detailed, Wall:Detailed, RoofCeiling:Detailed, etc.), door surfaces and internal mass are valid. Window surfaces are not valid surface types for embedded radiant systems.
Field: Heating Design Capacity Method[LINK]
Enter the method used to determine the maximum electrical power (heating design capacity ) or enter the method for scalable sizing the maximum electrical power of low temperature radiant electric unit. Input allowed is either HeatingDesignCapacity, CapacityPerFloorArea, and FractionOfAutosizedHeatingCapacity. If this input field is left blank or zero, then autosizing is assumed. HeatingDesignCapacity means user specifies the magnitude of maximum or nominal heating capacity or the program calculates the maximum or nominal design heating capacity if autosize is specified. CapacityPerFloorArea means the program calculates the design heating capacity from user specified heating capacity per floor area and floor area of the zone served by the low temperature radiant electric unit. FractionOfAutosizedHeatingCapacity means the program calculates the design heating capacity from user specified fraction and the auto-sized design heating capacity. The default method is HeatingDesignCapacity.
Field: Heating Design Capacity {W}[LINK]
This field is for the maximum amount of electric energy rate (electric power) converted into heat in low temperature radiant electric unit in watts. This input field is autosizable. The controls for the radiant system will vary the amount of power supplied to the surface between zero input and the maximum power specified in this field as the lower and upper bounds, respectively. Note that if the user elects to autosize this field that a standard zone thermostat such as would be used for a forced air system must be defined as autosizing calculations are based on the zone thermostat value and not on the low temperature radiant electric unit control values. The default input for this input field is autosize.
Field: Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2 of low temperature radiant electric system. This field is required field when the Heating Design Capacity Method is CapacityPerFloorArea. The program calculates the heating capacity from floor area of the zone served by the low temperature radiant electric unit and the heating capacity per unit floor area value specified by the user. This field may be left blank.
Field: Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized heating capacity of low temperature radiant electric unit. This input field is required when the Heating Design Capacity Method is FractionOfAutosizedHeatingCapacity. The program calculates the heating capacity from the design autosized heating capacity and user specified fraction. Design day sizing must be specified. This field may be left blank. The default value is 1.0.
Field: Temperature Control Type[LINK]
This field specifies along with the throttling range and setpoint schedules how the user wishes to control the low temperature electric radiant system. The temperature denoted in the setpoint schedule can refer to one of three different temperatures: the zone mean air temperature, the zone mean radiant temperature, the zone operative temperature, the outdoor dry-bulb temperature, or the outdoor wet-bulb temperature. The choice of temperature is controlled by the current field—temperature control type. The user must select from the following options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
OutdoorDryBulbTemperature
OutdoorWetBulbTemperature
Operative temperature for radiant system controls is the average of Mean Air Temperature and Mean Radiant Temperature. If the user does not select a control type, MeanAirTemperature control is assumed by EnergyPlus. See the throttling range and control temperature schedule fields below for more information.
Field: Heating Throttling Range[LINK]
This field specifies the range of temperature in degrees Celsuis over which the radiant system throttles from zero heat input via the electric resistance wires up to the maximum defined by the maximum electrical power field described above. The throttling range parameter is used in conjunction with the control temperature (see below) to define the response of the system to various zone conditions. The heating control temperature schedule specifies the “setpoint” temperature where the power input to the system is at half of the maximum power input. For example, if the heating control temperature setpoint is currently 15°C and the heating throttling range is 2°C, the electrical power supplied to the radiant system will be zero when the controlling temperature (MAT, MRT, Operative Temperature, ODB, or OWB; see control type field above) is at or above 16°C and the maximum power input when the controlling temperature is at or below 14°C. This represents a throttling range of 2°C around the setpoint of 15°C. In between 14°C and 16°C, the power input to the radiant system is varied linearly. The minimum throttling range is 0.5°C.
Field: Heating Setpoint Temperature Schedule Name[LINK]
This field specifies the heating setpoint or control temperature for the radiant system in degrees Celsius. Used in conjunction with the previous field (heating throttling range), it will define whether or not the system is running and the current power input to the radiant surface. Power input to the system is varied linearly around the setpoint temperature based on the throttling range and the maximum electrical power parameters (see above). It should be noted that this control schedule will allow different setpoint temperatures throughout the year for heating. In addition, this schedule may be different that the thermostatic control schedule defined for overall operation of components serving the zone in which the radiant system is located. The thermostatic control determines whether or not there is a heating or cooling load in the space and thus whether the systems should be operating. This field simply controls the flow rate to the radiant system.
An example IDF with an electric low temperature radiant system is shown below.
Outputs[LINK]
HVAC,Average, Zone Radiant HVAC Electric Power[W]
HVAC,Sum, Zone Radiant HVAC Electric Energy [J]
HVAC,Sum,Zone Radiant HVAC Heating Energy [J]
HVAC,Average, Zone Radiant HVAC Heating Rate [W]
Zone Radiant HVAC Electric Power [W][LINK]
This field reports the rate at which electric energy is “burned” in the low temperature radiant system in Watts. This is the heat source to the surface that is defined as the radiant system. The heating rate is determined by the zone conditions and the control scheme defined in the user input.
Zone Radiant HVAC Electric Energy [J][LINK]
This field reports the amount of electric energy “burned” in the low temperature radiant system in Joules. This is the heat source to the surface that is defined as the radiant system. The heating rate is determined by the zone conditions, the control scheme defined in the user input, and the timestep.
Zone Radiant HVAC Heating Energy [J][LINK]
Zone Radiant HVAC Heating Rate [W][LINK]
These outputs are the heating provided by the low temperature radiant system to the zone, in Watts or Joules.
ZoneHVAC:LowTemperatureRadiant:SurfaceGroup[LINK]
A low temperature radiant system (hydronic or electric) may consist of multiple active surfaces that serve to condition the space. Surfaces that act serially can be specified as multiple radiant systems using the standard radiant system input described above. However, if the multiple surfaces act in parallel, the Radiant System Surface Group input line is used to specify which surfaces are acting in a coordinated fashion and how energy flow is split between the surfaces. This list of surfaces (the name it is assigned) replaces the name of a single surface in the radiant system input described above. Note that all of the surfaces within a single list must be a part of the same zone and that the zone of these surfaces must also match the zone the radiant system is attempting to condition.
Inputs[LINK]
Field: Name[LINK]
This field is an unique user assigned name for the list of surfaces that are acting in coordination with one another. Any reference to this list by a radiant system will use this name.
Field Set: Surface Name, Flow Fraction to Surface[LINK]
The pairs of Surface Name, Flow Fraction to Surface are used in several objects. There can be up to 10 specified. The object is extensible so more can be added.
Field: Surface <x> Name[LINK]
This field is the name of a surface in the zone being conditioned by the radiant system. Base surfaces (e.g., BuildingSurface:Detailed), door surfaces and internal mass are valid. Window surfaces are not valid surface types for embedded radiant systems.
Field: Flow Fraction for Surface <x>[LINK]
This field is the fraction of the total radiant system flow rate that is being sent to this particular surface. Note that the Surface Name/Surface Flow Fraction pair can be repeated up to 10 times. Flow rate fractions must sum to unity, otherwise the program will not accept the input as valid.
An example IDF with an electric low temperature radiant system is shown below.
ZoneHVAC:HighTemperatureRadiant[LINK]
The high temperature radiant system (gas-fired or electric) is a component of zone equipment that is intended to model any “high temperature” or “high intensity” radiant system where electric resistance or gas-fired combustion heating is used to supply energy (heat) to a building occupants directly as well as the building surfaces (wall, ceiling, or floor). The component is controlled by the radiant system controls defined in the syntax below and this control does not require the use of a zone thermostat unless the unit is being autosized. Note also that because this unit does not require a thermostat that in cases where no other systems are serving the zone in which this system resides that it will use the heating equipment priority to determine which system will run first. If the radiant system is serving a zone with forced air equipment, the radiant system will follow the priority order established by the zone thermostat but will still base its response on the controls defined by the user for the radiant system.
The control is accomplished by varying the electrical power supplied to or gas consumed by the unit. It is not intended to simulate low temperature electric or hydronic radiant systems. Those devices will be handled by a separate model and different input syntax (ref: the low temperature systems described elsewhere).
Inputs[LINK]
Field: Name[LINK]
This field is an unique user assigned name for an instance of the high temperature radiant system. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that denotes whether the high temperature radiant system can operate during a given time period. A schedule value less than or equal to 0 (usually 0 is used) denotes that the unit must be off for that time period. A value greater than 0 (usually 1 is used) denotes that the unit is available to operate during that time period. If this field is left blank, the schedule has a value of 1 for all time periods.
Field: Zone Name[LINK]
This field is the name of the zone (Ref: Zone) in which the high temperature radiant system is principally located and intended to affect.
Field: Heating Design Capacity Method[LINK]
Enter the method used to determine the maximum electrical power (heating design capacity ) or enter the method for scalable sizing the maximum electrical power of high temperature radiant system unit. Input allowed is either HeatingDesignCapacity, CapacityPerFloorArea, and FractionOfAutosizedHeatingCapacity. If this input field is left blank or zero, then autosizing is assumed. HeatingDesignCapacity means user specifies the magnitude of maximum or nominal heating capacity or the program calculates the maximum or nominal design heating capacity if autosize is specified. CapacityPerFloorArea means the program calculates the design heating capacity from user specified heating capacity per floor area and floor area of the zone served by the high temperature radiant electric unit. FractionOfAutosizedHeatingCapacity means the program calculates the design heating capacity from user specified fraction and the auto-sized design heating capacity. The default method is HeatingDesignCapacity.
Field: Heating Design Capacity {W}[LINK]
This field is for the maximum amount of electric energy rate (electric power) converted into heat in high temperature radiant electric unit in watts. This input field is autosizable. The controls for the radiant system will vary the amount of power supplied to the surface between zero input and the maximum power specified in this field as the lower and upper bounds, respectively. Note that if the user elects to autosize this field that a standard zone thermostat such as would be used for a forced air system must be defined as autosizing calculations are based on the zone thermostat value and not on the radiant system control values. The default input for this field is autosize.
Field: Heating Design Capacity Per Floor Area {W/m2}[LINK]
Enter the heating capacity per unit floor area in m3/s-m2 of high temperature radiant electric unit. This field is required field when the Heating Design Capacity Method is CapacityPerFloorArea. The program calculates the heating capacity from floor area of the zone served by the high temperature radiant electric unit and the heating capacity per unit floor area value specified by the user. This field may be left blank.
Field: Fraction of Autosized Heating Design Capacity[LINK]
Enter the heating capacity as a fraction of the autosized heating capacity for high temperature radiant electric unit. This input field is required when the Heating Design Capacity Method is FractionOfAutosizedHeatingCapacity. The program calculates the heating capacity from the design autosized heating capacity and user specified fraction. Design day sizing run must be specified. This field may be left blank. The default value is 1.0.
Field: Fuel Type[LINK]
This field denotes the type of high temperature radiant heater: gas or electric. The user must specify this by inputting either the keyword “NaturalGas” or “Electricity” for this field.
Field: Combustion Efficiency[LINK]
This field is the combustion efficiency for a gas high temperature radiant heater. This value should be greater than 0 and less than or equal to 1. It is intended to take into account any potential inefficiencies in the combustion process inside the radiant heater. The heater gas consumption is the ratio of heater output over the combustion efficiency. This parameter has no meaning for an electric high temperature radiant heater and is ignored when the previous field is equal to “Electric”.
Field: Fraction of Input Converted to Radiant Energy[LINK]
This field specifies what fraction of the power input to the high temperature radiant heater is actually radiant heat transfer. The fraction should be between 0 and 1. In conjunction with the next two parameters, it defines the breakdown of how the power input to the heater is distributed to the rest of the zone. The sum of these fractions must be less than or equal to 1. If the fractions are less than one, the remaining energy is added to the zone as convective heat transfer. The radiant heat transfer from the heat is distributed to people and surfaces using the distribution fractions listed below.
Field: Fraction of Input Converted to Latent Energy[LINK]
This field specifies the fraction of the power input to the high temperature radiant heater that is converted to a latent heat gain within the space. This may be appropriate when a combustion process produces moisture that is transferred into the space. The latent heat addition from a high temperature radiant heater is handled as any other latent heat gain within the space, affecting the moisture balance on the zone air.
Field: Fraction of Input that Is Lost[LINK]
This field specifies the fraction of power input to the high temperature radiant heater that is “lost”. This energy is a loss term, and this fraction of the input power has no effect on the zone heat balances.
Field: Temperature control type[LINK]
This field specifies along with the throttling range and setpoint schedules how the user wishes to control the high temperature radiant system. The temperature denoted in the setpoint schedule can refer to one of three different temperatures: a mean air temperature, a mean radiant temperature, or an operative temperature. The choice of temperature is controlled by the current field—temperature control type. The user must select from the following options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
MeanAirTemperatureSetpoint
MeanRadiantTemperatureSetpoint
OperativeTemperatureSetpoint
If the user does not select a control type, OperativeTemperature control is assumed by EnergyPlus. For the setpoint control strategies (those ending in Setpoint above), EnergyPlus will attempt to find the correct heater output to meet the heating setpoint temperature (see below) through iteration and interpolation. This will more closely match the operation of an actual thermostat, but it will require significantly longer execution times. For more information on the standard piecewise linear control algorithm used by the Mean Air Temperature, Mean Radiant Temperature, and Operative Temperature control types (the “non-Setpoint” controls), see the throttling range and control temperature schedule fields below for more information.
Field: Heating Throttling Range[LINK]
This field specifies the range of temperature in degrees Celsuis over which the radiant system throttles from zero heat input via the electric resistance wires up to the maximum defined by the maximum electrical power field described above. The throttling range parameter is used in conjunction with the control temperature (see below) to define the response of the system to various zone conditions. The heating control temperature schedule specifies the “setpoint” temperature where the power input to the system is at half of the maximum power input. For example, if the heating control temperature setpoint is currently 15°C and the heating throttling range is 2°C, the electrical power supplied to the radiant system will be zero when the controlling temperature (Mean Air Temperature, Mean Radiant Temperature, and Operative Temperature; see control type field above) is at or above 16°C and the maximum power input when the controlling temperature is at or below 14°C. This represents a throttling range of 2°C around the setpoint of 15°C. In between 14°C and 16°C, the power input to the radiant system is varied linearly.
Field: Heating Setpoint Temperature Schedule Name[LINK]
This field specifies the heating setpoint or control temperature for the radiant system in degrees Celsius. Used in conjunction with the previous field (heating throttling range), it will define whether or not the system is running and the current power input to the radiant surface. Power input to the system is varied linearly around the setpoint temperature based on the throttling range and the maximum electrical power parameters (see above). It should be noted that this control schedule will allow different setpoint temperatures throughout the year for heating. In addition, this schedule may be different that the thermostatic control schedule defined for overall operation of components serving the zone in which the radiant system is located. The thermostatic control determines whether or not there is a heating or cooling load in the space and thus whether the systems should be operating. This field simply controls the flow rate to the radiant system.
Field: Fraction of Radiant Energy Incident on People[LINK]
This field specifies the fraction of radiant heat transfer to the zone from the radiant heater that is incident directly on people within the space. This has an impact on the predicted thermal comfort of the zone occupants. Note that since the thermal comfort models only use the results of the zone heat balances this energy is accounted for within the heat balance as convective energy, directly affecting the zone air heat balance. The basic assumption here is that most radiant energy falling on people will most likely be convected to the surroundings. This is a simplification of reality, but it maintains the overall energy balance.
Field Set: Surface Name, Fraction of radiant energy to Surface[LINK]
The pairs of Surface Name, Fraction of Radiant Energy to Surface are used in several objects. There can be up to 20 specified.
Field: Surface <x> Name[LINK]
This field is the name of the first surface to which radiant heat transfer from the high temperature radiant heater is distributed. Used in conjunction with the next field, it helps to define the distribution of the radiant energy on the surfaces within the zone. Note that up to 20 pairs of surface names and corresponding fractions may be entered for a single radiant heater system.
Field: Fraction of Radiant Energy to Surface <x>[LINK]
This field is paired with the preceding surface name (previous field) to define the fraction of radiant heat transfer leaving the high temperature radiant system that is incident on a particular surface. Users should take into account the directionality of high temperature radiant heaters and their location when defining the value for this input field. Note that the sum of all fractions plus the fraction of radiant energy incident on people must add up to 1 so that all radiant energy is taken into account and none of it is “lost”.
An example IDF with a high temperature radiant system is shown below.
Outputs[LINK]
HVAC,Average, Zone Radiant HVAC Heating Rate [W]
HVAC,Sum, Zone Radiant HVAC Heating Energy [J]
HVAC,Average, Zone Radiant HVAC Gas Rate [W]
HVAC,Sum, Zone Radiant HVAC Gas Energy [J]
HVAC,Average, Zone Radiant HVAC Electric Power[W]
HVAC,Sum, Zone Radiant HVAC Electric Energy [J]
Zone Radiant HVAC Heating Rate [W][LINK]
This field reports the rate at which energy is transferred from the high temperature radiant system to the zone in Watts. This rate is determined by the zone conditions and the control scheme defined in the user input. Note that this amount takes into account any combustion inefficiency and thus could be different that the gas consumption rate in a high temperature gas radiant system.
Zone Radiant HVAC Heating Energy [J][LINK]
This field reports the amount of energy transferred from the high temperature gas radiant system to the zone in Joules. This amount is determined by the zone conditions, the control scheme defined in the user input, and the timestep. Note that this amount takes into account any combustion inefficiency and thus could be different that the gas consumption in a high temperature gas radiant system.
Zone Radiant HVAC Gas Rate [W][LINK]
This field reports the rate at which gas is “burned” in a high temperature gas radiant system in Watts. This rate is determined by the zone conditions and the control scheme defined in the user input.
Zone Radiant HVAC Gas Energy [J][LINK]
This field reports the amount of gas “burned” in a high temperature gas radiant system in Joules. This amount is determined by the zone conditions, the control scheme defined in the user input, and the timestep.
Zone Radiant HVAC Electric Power[W][LINK]
This field reports the rate at which electric energy is “burned” in a high temperature electric radiant system in Watts. This rate is determined by the zone conditions and the control scheme defined in the user input.
Zone Radiant HVAC Electric Energy [J][LINK]
This field reports the amount of electric energy “burned” in a high temperature electric radiant system in Joules. This amount is determined by the zone conditions, the control scheme defined in the user input, and the timestep.
ZoneHVAC:VentilatedSlab[LINK]
Ventilated slab systems in general use outdoor air to “precool” slabs with colder nighttime air. This method of precooling the thermal mass of a space can be very effective when nighttime temperatures are low and the mass of the system is high enough to provide a significant amount of cooling potential during the day to counteract internal heat gains within a zone. Nearly all ventilated slabs are simple systems such as that shown in the right side of Figure. The fan is shown in a blow through position, but the model will allow either a blow or draw through configuration.
Inputs[LINK]
Field: Name[LINK]
This field is a unique user assigned name for an instance of a ventilated slab system. Any reference to this unit by another object will use this name. Other objects that use this ventilated slab system will reference it by this name.
Field: Availability Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that denotes whether the ventilated slab system can run during a given time period. A schedule value less than or equal to 0 (usually 0 is used) denotes that the unit must be off for that time period. A value greater than 0 (usually 1 is used) denotes that the unit is available to operate during that time period. If this field is left blank, the schedule has a value of 1 for all time periods.
Field: Zone Name[LINK]
This field is the name of the zone (Ref: Zone) in which the ventilated slab system is principally located and intended to affect. A system that is between two zones will still act upon each zone; however, the zone name referenced here should be the zone that controls the system response.
Field: Surface Name or Radiant Surface Group Name[LINK]
This field is the name of the surface (Ref: Surface) or surface list (Ref: ZoneHVAC:VentilatedSlab:SlabGroup) in which the hollow cores are embedded/contained. This specification attaches the source or sinks from the radiant system to a particular surface and the contribution of the system to the heat balances of that surface. If this field is a surface list, then the source or sink is attached to all of the surfaces in the list with the radiant system surface group defining the breakdown of how flow rate is split between the various surfaces. Only base surfaces (Walls, Roofs, Floors) are valid. Window/Door surfaces and Internal Mass are not valid surface types for embedded radiant systems.
Field: Maximum Air Flow Rate[LINK]
This field allows the user to enter the maximum volumetric flow rate of air through the ventilated slab system in m\(^{3}\)/sec. This parameter should be some real number greater than zero.
Field: Outdoor Air Control Type[LINK]
This field allows the user to control how outdoor air is used in the ventilated slab system. The ventilated slab system described by this syntax has its own outdoor air handler. The three options for outdoor air control are “VariablePercent”, “FixedTemperature” and “FixedAmount”. Those keywords are the only allowed choices for this parameter. In general, the variable percent control will attempt to vary the amount of outdoor air between some minimum and maximum schedules of fractions (see next two fields) to best meet the current heating or cooling load. The fixed temperature control will vary the amount of outdoor air between the minimum schedule (fraction of maximum, see next field) and 100% available outdoor air to come as close as possible to a desired mixed air temperature (see two fields down) that can be scheduled. The fixed amount control will fix the outdoor air flow rate as minimum outdoor air flow rate and schedule specified by the user and automatically set the maximum and minimum outside flow rate to be equal by ignoring the maximum outdoor air flow rate. More information on the controls and operation of the ventilated slab are given in the section above (preceding the IDF description).
Field: Minimum Outdoor Air Flow Rate[LINK]
This field allows the user to enter the minimum volumetric flow rate of outdoor air (in m\(^{3}\)/sec) that will be brought in to the ventilated slab. The actual minimum outdoor air flow rate will be this number multiplied by the schedule value from the minimum outdoor air schedule. If “FixedAmount” type is selected as the outdoor air control strategy, the outdoor air flow rate will be fixed at the value of this field and the ventilated slab will automatically set the maximum and minimum outside flow rate to be equal by ignoring the maximum outdoor air flow rate.
Field: Minimum Outdoor Air Schedule Name[LINK]
This field contains a schedule name (ref: Schedule) that should contain values for the minimum outdoor air used by the ventilated slab system for IAQ or other reasons. Note that if the ventilated slab is scheduled off or if there is no load sensed in the zone that the system will not operate even to achieve the minimum air fraction. However, if the system is operating, it will always bring in at least this fraction of the minimum air flow rate (see minimum air flow rate field above). If “FixedAmount” type is selected as the outdoor air control strategy, the actual outdoor air flow rate will be this number multiplied by the minimum outdoor air flow rate in the field above. The ventilated slab will automatically set the maximum and minimum outdoor air schedule to be equal by ignoring the maximum outdoor air schedule.
Field: Maximum Outdoor Air Flow Rate[LINK]
This field allows the user to enter the maximum volumetric flow rate of outdoor air that can be brought into the ventilated slab in m\(^{3}\)/sec. This parameter should be some real number greater than zero. Note that the value for this parameter may be less than the maximum air flow rate of the ventilated slab and this may affect the maximum fraction of outdoor air within the control strategy defined above. This parameter is an absolute maximum and will supercede any scheduled fraction of the ventilated slab maximum airflow rate. If “FixedAmount” type is selected as the outdoor air control strategy, this field will be ignored and be automatically set to be equal to the minimum outdoor air flow rate specified in the field above.
Field: Maximum Outdoor Air Fraction or Temperature Schedule Name[LINK]
This field can have one of two meanings depending the type of control selected in the outdoor air control type parameter above. If “VariablePercent” or “FixedAmount” was selected, then this field is a schedule name (ref: Schedule) corresponding to a maximum air fraction schedule. Furthermore, if “FixedAmount” type is selected as the outdoor air control strategy, this field will be ignored and be automatically set to be equal to the minimum outdoor air fraction specified in the field below. Note that this is a fraction of the maximum airflow rate field (see parameter above) for the ventilated slab. If “FixedTemperature” control was selected, then this field is still a schedule name (ref: Schedule), but it corresponds to a schedule of mixed air temperatures that the outdoor air control will try to attain.
Field: System Configuration Type[LINK]
This field allows the user to control how the air is circulated using the ventilated slab system. The options for system configuration are
SlabOnly
SlabAndZone
SeriesSlabs
In the SlabOnly, the ventilation air is sent to the slab only and does not enter the zone. In the SlabAndZone, the air first enters the slab and then is delivered to the zone before returning to the system. With the SeriesSlabs option, the user specifies a list of slabs (ZoneHVAC:VentilatedSlab:SlabGroup). This list determines the order of slabs through which the air passes. In this option, air is not delivered to any zone.
Field: Hollow Core Inside Diameter[LINK]
This field is the inside diameter of the cores through which air is circulated for the system being defined by this statement. The inside diameter should be recorded in meters and is used to determine the convective heat transfer from the circulated air to the inside surface of the ventilated slab.
Field: Hollow Core Length[LINK]
This field is the length of core embedded in the surface named above in the surface name field. In other words, this should be the distance that air travels as it through the slab. The length of the hollow core in the slab should be entered in meters and is used to determine the effectiveness of heat transfer from the air being circulated through the cores and the core inside surface. Longer core lengths result in more heat transferred to/from the radiant surface to the circulating fluid.
Field: Number of Cores[LINK]
This field allows the user to specify how many cores there are in the ventilated slab. Air flow will be divided equally among the different cores.
Field: Temperature Control Type[LINK]
This field specifies along with the throttling range and setpoint schedules how the user wishes to control the ventilated slab system. The temperature denoted in the set temperature schedule can refer to one of seven different temperatures: the zone mean air temperature, the zone mean radiant temperature, the zone operative temperature, the surface temperature of the ventilated slab, the outdoor dry-bulb temperature, the outdoor wet-bulb temperature, or the dewpoint temperature of zone mean air temperature. The choice of temperature is controlled by the current field—temperature control type. The user must select from the following options:
MeanAirTemperature
MeanRadiantTemperature
OperativeTemperature
OutdoorDryBulbTemperature
OutdoorWetBulbTemperature
SurfaceTemperature
ZoneAirDewPointTemperature
If the user does not select a control type, MeanAirTemperature control is assumed by EnergyPlus. See the control temperature schedule fields below for more information.
Field: Heating High Air Temperature Schedule Name[LINK]
This field specifies the high air temperature in degrees Celsius for the temperature control of a ventilated slab system. Air and control temperatures for heating work together to provide a linear function that determines the air temperature sent to the ventilated slab. The current control temperature (see Temperature Control Type above) is compared to the high and low control temperatures at the current time. If the control temperature is above the high temperature, then the inlet air temperature is set to the low air temperature. If the control temperature is below the low temperature, then the inlet air temperature is set to the high air temperature. If the control temperature is between the high and low value, then the inlet air temperature is linearly interpolated between the low and high air temperature values.
Field: Heating Low Air Temperature Schedule Name[LINK]
This field specifies the low air temperature in degrees Celsius for the temperature control of a ventilated slab. For more information on its interpretation, see Heating High Air Temperature Schedule above.
Field: Heating High Control Temperature Schedule Name[LINK]
This field specifies the high control temperature in degrees Celsius for the temperature control of a ventilated slab. For more information on its interpretation, see Heating High Air Temperature Schedule above.
Field: Heating Low Control Temperature Schedule Name[LINK]
This field specifies the low control temperature in degrees Celsius for the temperature control of a ventilated slab. For more information on its interpretation, see Heating High Air Temperature Schedule above.
Field: Cooling High Air Temperature Schedule Name[LINK]
This field specifies the high air temperature in degrees Celsius for the temperature control of a ventilated slab system. Air and control temperatures for cooling work together to provide a linear function that determines the air temperature sent to the ventilated slab system. The current control temperature (see Temperature Control Type above) is compared to the high and low control temperatures at the current time. If the control temperature is above the high temperature, then the inlet air temperature is set to the low air temperature. If the control temperature is below the low temperature, then the inlet air temperature is set to the high air temperature. If the control temperature is between the high and low value, then the inlet air temperature is linearly interpolated between the low and high air temperature values.
Field: Cooling Low Air Temperature Schedule Name[LINK]
This field specifies the low air temperature in degrees Celsius for the temperature control of a constant flow cooling radiant system. For more information on its interpretation, see Cooling High Air Temperature Schedule above.
Field: Cooling High Control Temperature Schedule Name[LINK]
This field specifies the high control temperature in degrees Celsius for the temperature control of a constant flow cooling radiant system. For more information on its interpretation, see Cooling High Air Temperature Schedule above.
Field: Cooling Low Control Temperature Schedule Name[LINK]
This field specifies the low control temperature in degrees Celsius for the temperature control of a ventilated slab system. For more information on its interpretation, see Cooling High Air Temperature Schedule above.
Field: Return Air Node Name[LINK]
This field is a node name used to identify the node that serves as the zone return air inlet to the ventilated slab system. This node is one of the inlets to the outdoor air mixer which is implicit in the ventilated slab system model. For “SlabAndZone” configuration, the Return Air Node will typically be the same node as a zone exhaust node. For “SlabOnly” or “SeriesSlabs” configuration, this node name is required but will have zero flow.
Field: Slab In Node Name[LINK]
This field is a node name used to identify the node that serves as the inlet of the ventilated slab or series of slabs, after the outdoor air mixer, fan, and optional coils.
Field: Zone Supply Air Node Name[LINK]
This field is a node name used to identify the node that serves as the outlet from the ventilated slab system to the zone when using the “SlabAndZone” configuration. It is the node exiting the slab section of the system. This node will typically be the same node as a zone inlet node. In the case of “SlabOnly” or “SeriesSlabs” configuration, this field will be ignored and it should be left BLANK.
Field: Outdoor Air Node Name[LINK]
This field is a node name used to identify the node associated with fresh outdoor air brought into the ventilated slab system outdoor air mixer. This node should also be specified in an OutdoorAir:Node or OutdoorAir:NodeList object.
Field: Relief Air Node Name[LINK]
This field is a node name used to identify the node associated with air exhausted out of the ventilated slab system to the outdoor environment.
Field: Outdoor Air Mixer Outlet Node Name[LINK]
This field is a node name used to identify the node associated with the “mixed” air of the ventilated slab. These conditions are post-“mixing box” since they are the conditions of the fraction of return air combined with the outdoor air. Since this is a simple system, this can also be viewed as the conditions of the air being sent to the coils.
Field: Fan Outlet Node Name[LINK]
This field is a node name used to identify the node that serves as the air outlet from the fan.
Field: Fan Name[LINK]
This field is the name of a fan (ref: Fan:SystemModel or Fan:ConstantVolume) that is part of the ventilated slab system. This name links the ventilated slab to particular fan data entered elsewhere in the input data file. A fan name is required since it is the prime mover of air in the ventilated slab system.
Field: Coil Option Type[LINK]
This field allows the user to specify the coil operating options as one of the following options:
None
Heating
Cooling
HeatingAndCooling
If None is selected, the ventilated slab does not have any coils, and any other input will be ignored. If either Heating or Cooling is selected, only a heating or cooling coil, respectively, is present. Thus, only four more inputs will be expected. If HeatingAndCooling is selected, both heating and cooling coil input must be entered, and the ventilated slab will have both a heating and a cooling coil.
Field: Heating Coil Object Type[LINK]
This field is the type of coil (ref: Coil:Heating:Water, Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam) that is used for heating in the ventilated slab system. This field must be one of the following keywords: Coil:Heating:Water, Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam. It is used in conjunction with the heating coil name (see next field) to specify the heating coil present within the system.
Field: Heating Coil Name[LINK]
This field is the name of the heating coil that is part of the ventilated slab system. It is assumed that there is always some sort of heating coil associated with a ventilated slab system. This name links the ventilated slab to particular heating coil data entered elsewhere in the input data file.
Field: Hot Water or Steam Inlet Node Name[LINK]
This field corresponds to the water inlet node to the heating coil for a water coil. The water inlet node controls how a water heating coil operates. This field is ignored/not needed for gas and electric heating coils.
Field: Cooling Coil Object Type[LINK]
This field is the name of the cooling coil (ref: Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry, CoilSystem:Cooling:Water:HeatExchangerAssisted) that is part of the ventilated slab system. This name links the ventilated slab system to particular cooling coil data entered elsewhere in the input data file. If no cooling coil is present, the previous field may be followed by a semi-colon and the remaining parameters in this statement may be ignored.
Field: Cooling Coil Name[LINK]
This field is the name of the cooling coil that is part of the ventilated slab system. It is assumed that there is always some sort of cooling coil associated with a ventilated slab system. This name links the ventilated slab to particular cooling coil data entered elsewhere in the input data file.
Field: Cold Water Inlet Node Name[LINK]
This field corresponds to the water inlet node to the cooling coil. The water inlet node controls how a water cooling coil operates and is required for the ventilated slab system that has a cooling coil associated with it to function properly.
Field: Availability Manager List Name[LINK]
This optional input field is the name of an AvailabilityManagerAssignmentList object. An Availability Manager Assignment List is a list of Availability Managers giving both Availability Manager type and name. The availability managers in the list apply to this ventilated slab object’s fan. If the ventilated slab is available (per the Availability Schedule Name input field above) and this input field has a valid availability manager assignment list name, then the availability managers in the list determine when and if the fan of this ventilated slab object should be on or off.
Field: Design Specification ZoneHVAC Sizing Object Name[LINK]
This optional input field is the name of a DesignSpecification:ZoneHVAC:Sizing object. The name must correspond to unique name of a DesignSpecification:ZoneHVAC:Sizing object. A Design Sepcification Zone HVAC Sizing object defines scalable sizing methods for sizing input fields such as Maximum Air Flow Rate in this Ventilated Slab zone HVAC object. The scaled Maximum Air Flow Rate in turn is used to size cooling and heating capacity of the coils.
An example IDF with a ventilated slab is shown below.
Outputs[LINK]
HVAC,Average,Zone Ventilated Slab Radiant Heating Rate [W]
HVAC,Sum,Zone Ventilated Slab Radiant Heating Energy [J]
HVAC,Average,Zone Ventilated Slab Radiant Cooling Rate [W]
HVAC,Sum,Zone Ventilated Slab Radiant Cooling Energy [J]
HVAC,Average,Zone Ventilated Slab Coil Heating Rate [W]
HVAC,Sum,Zone Ventilated Slab Coil Heating Energy [J]
HVAC,Average,Zone Ventilated Slab Coil Total Cooling Rate [W]
HVAC,Sum,Zone Ventilated Slab Coil Total Cooling Energy [J]
HVAC,Average,Zone Ventilated Slab Coil Sensible Cooling Rate [W]
HVAC,Sum,Zone Ventilated Slab Coil Sensible Cooling Energy [J]
HVAC,Average,Zone Ventilated Slab Coil Latent Cooling Rate [W]
HVAC,Sum,Zone Ventilated Slab Coil Latent Cooling Energy [J]
HVAC,Average, Zone Ventilated Slab Air Mass Flow Rate [kg/s]
HVAC,Average, Zone Ventilated Slab Fan Electric Power [W]
HVAC,Sum,Zone Ventilated Slab Fan Electric Energy [J]
HVAC,Average,Zone Ventilated Slab Inlet Air Temperature [C]
HVAC,Average,Zone Ventilated Slab Outlet Air Temperature [C]
HVAC,Average,Zone Ventilated Slab Zone Inlet Air Temperature [C]
HVAC,Average,Zone Ventilated Slab Return Air Temperature [C]
HVAC,Average,Zone Ventilated Slab Fan Outlet Air Temperature [C]
HVAC,Average,Zone Ventilated Slab Fan Availability Status []
Zone Ventilated Slab Radiant Heating Rate [W][LINK]
This field reports the radiant heating input rate of the ventilated slab system to the zone it is serving in Watts. This is determined by outlet and zone air conditions and the mass flow rate through the ventilated slab system.
Zone Ventilated Slab Radiant Heating Energy [J][LINK]
This field is the heating radiant input of the ventilated slab system to the zone it is serving in Joules over the timestep being reported. This is determined by outlet and zone air conditions, the mass flow rate through the ventilated slab system, and the timestep.
Zone Ventilated Slab Radiant Cooling Rate [W][LINK]
This field reports the radiant cooling input rate to the ventilated slab system in Watts. This is the heat sink to the surface that is defined as the ventilated slab system. The cooling rate is determined by the zone conditions and the control scheme defined in the user input.
Zone Ventilated Slab Radiant Cooling Energy [J][LINK]
This field reports the radiant cooling input to the ventilated slab system in Joules. This is the heat sink to the surface that is defined as the radiant system. The cooling rate is determined by the zone conditions, the control scheme defined in the user input, and the timestep.
Zone Ventilated Slab Coil Heating Rate [W][LINK]
This field reports the heating input rate of the heating coil of ventilated slab system the zone it is serving in Watts. This is determined by return air and zone air conditions and the mass flow rate through the ventilation slab system.
Zone Ventilated Slab Coil Heating Energy [J][LINK]
This field is the heating output of the heating coil of the ventilated slab system the zone it is serving in Joules over the timestep being reported. This is determined by return air and zone air conditions, the mass flow rate through the ventilation slab system, and the timestep.
Zone Ventilated Slab Coil Total Cooling Rate [W][LINK]
This field reports the total cooling (sensible plus latent) output rate of the cooling coil of the ventilated slab system to the zone it is serving in Watts. This is determined by outlet and zone air conditions and the mass flow rate through the ventilation slab system.
Zone Ventilated Slab Coil Total Cooling Energy [J][LINK]
This field is the total cooling (sensible plus latent) output of the cooling coil of the ventilated slab system to the zone it is serving in Joules over the timestep being reported. This is determined by outlet and zone air conditions, the mass flow rate through the ventilation slab system, and the timestep.
Zone Ventilated Slab Coil Sensible Cooling Rate [W][LINK]
This field reports the sensible cooling output rate of the cooling coil of the ventilated slab system to the zone it is serving in Watts. This is determined by outlet and zone air conditions and the mass flow rate through the ventilation slab system.
Zone Ventilated Slab Coil Sensible Cooling Energy [J][LINK]
This field is the sensible cooling output of the cooling coli of the ventilated slab system to the zone it is serving in Joules over the timestep being reported. This is determined by outlet and zone air conditions, the mass flow rate through the ventilation slab system, and the timestep.
Zone Ventilated Slab Coil Latent Cooling Rate [W][LINK]
This field reports the latent cooling output rate of the cooling coil of the ventilated slab system to the zone it is serving in Watts. This is determined by outlet and zone air conditions and the mass flow rate through the ventilation slab system.
Zone Ventilated Slab Coil Latent Cooling Energy [J][LINK]
This field is the latent cooling output of the cooling coli of the ventilated slab system to the zone it is serving in Joules over the timestep being reported. This is determined by outlet and zone air conditions, the mass flow rate through the ventilation slab system, and the timestep.
Zone Ventilated Slab Air Mass Flow Rate [kg/s][LINK]
This field reports the mass flow rate of air through the ventilated slab system in kilograms per second.
Zone Ventilated Slab Fan Electric Power [W][LINK]
This field reports the electric power consumption rate of the fan of the ventilated slab system in Watts.
Zone Ventilated Slab Fan Electric Energy [J][LINK]
This field reports the electric power consumed by the fan of the ventilated slab system over the timestep in Joules.
Zone Ventilated Slab Inlet Air Temperature [C][LINK]
This field reports the temperature of air entering the ventilated slab system in Celsius.
Zone Ventilated Slab Outlet Air Temperature [C][LINK]
This field reports the temperature of air leaving the ventilated slab system in Celsius.
Zone Ventilated Slab Zone Inlet Air Temperature [C][LINK]
This field reports the temperature of air entering the zone in Celsius.
Zone Ventilated Slab Return Air Temperature [C][LINK]
This field reports the temperature of air leaving the zone in Celsius. When system does not circulate air to zone(“SlabOnly” Configuration), the slab outlet temperature and return air temperature will be the same.
Zone Ventilated Slab Fan Outlet Air Temperature [C][LINK]
This field reports the fan outlet air temperature for the ventilated slab system in Celsius.
Zone Ventilated Slab Fan Availability Status [][LINK]
This is the availability status of the ventilated slab fan. This status flag is a result of the calculations made by the Availability Manager(s) listed in an AvailabilityManagerAssignmentList object and/or calculations made by Hybrid Ventilation Manager object. The AvailabilityManagerAssignmentList is an optional input in the ventilated slab object. When a single availability manager is used in an Availability Manager Assignment List, this is also the availability status reported by the specific availability manager (Ref. AvailabilityManager:* Outputs). For multiple availability managers in an Availability Manager Assignment List along with Hybrid Ventilation Manager, rules to determine fan availability status are described in the section ‘Group – System Availability Managers’. The control status outputs are represented using integers 0 through 3. These integers represent NoAction (0), ForceOff (1), CycleOn (2), and CycleOnZoneFansOnly (3). Since the status output is averaged, the output result may not correspond to the values described here when output variable frequencies other than detailed are used. Use the “detailed” reporting frequency (Ref. Output:Variable object) to view the availability status at each simulation timestep.
ZoneHVAC:VentilatedSlab:SlabGroup[LINK]
A ventilated slab system may consist of multiple active slabs that are serving to condition the zone. Slabs that act serially can be specified as multiple radiant systems using the standard ventilated slab input described above. This list of surfaces (the name it is assigned) replcaces the name of a single surface in the ventilated slab system input described above.
Inputs[LINK]
Field : Name of Ventilated Slab Surface Group[LINK]
This field is a unique user assigned name for the list of surfaces that are acting in coordination with one another. Any reference to this list by a ventilated slab system will use this name.
Field: Zone Name[LINK]
This field is the name of the zone in which the surface is principally located and intended to affect.
Field: Surface Name[LINK]
This field is the name of a surface in the zone being conditioned by the ventilated slab system. Only base surfaces like walls, floors and roofs are valid. Door/Window Surface and Internal Mass are not valid surface types for the ventilated slab system.
Field: Core Diameter[LINK]
This field is the inside diameter of the cores through which air is circulated for the surface being defined by this statement. The inside diameter should be recorded in meters and is used to determine the convective heat transfer from the circulated air to the inside surface of the ventilated slab.
Field: Core length[LINK]
This field is the length of core embedded in the surface named above in the surface name field. In other words, this should be the distance that air travels as it through the slab. The length of the hollow core in the surface should be entered in meters and is used to determine the effectiveness of heat transfer from the air being circulated through the cores and the core inside surface. Longer core lengths result in more heat transferred to/from the radiant surface to the circulating fluid.
Field: Number of Cores[LINK]
This field allows the user to specify how many cores there are in the ventilated slab. Air flow will be divided equally among the different cores.
Field: Slab Inlet Node Name[LINK]
This field is a node name (character string) used to identify the node that serves as the inlet (air side) to the surface. In EnergyPlus, nodes represent points between components or at various points in the loops. While a node name may be referenced more than once in an input data file, each node must have a unique name.
Field: Slab Outlet Node Name[LINK]
This field is a node name (character string) used to identify the node that serves as the outlet (air side) of the surface. In EnergyPlus, nodes represent points between components or at various points in the loops. While a node name may be referenced more than once in an input data file, each node must have a unique name.
An Example IDF with a ventilated slab system is shown below