EnergyPlus models follow fundamental heat balance
principles very closely in almost all aspects of the program.
However, the simulation of building surface constructions has
relied on a conduction transfer function (CTF) transformation
carried over from BLAST. This has all the usual restrictions
of a transformation-based solution: constant properties, fixed
values of some parameters, and do not produce results for the
interior of the surface. As the energy analysis field moves
toward simulating more advanced constructions, such as phase
change materials (PCM), it becomes necessary to step back from
transformations to more fundamental forms. Accordingly, a
conduction finite difference (CondFD) solution algorithm has
been incorporated into EnergyPlus. This does not replace the
CTF solution algorithm, but complements it for cases where the
user needs to simulate phase change materials or variable
thermal conductivity. It is also possible to use the finite
difference algorithm for zone time steps as short as one
minute.
EnergyPlus includes two different options for the specific
scheme or formulation used for the finite difference model.
The first scheme is referred to as Crank-Nicholson and was the
formulation used in EnergyPlus prior to version 7. As of
version 7 a second scheme was added and is referred to as
fully implicit. The selection between the two can be made by
the user with the HeatBalanceSettings:ConductionFiniteDifference
input object. Once selected, the same scheme is used
throughout the simulation. Although the two different schemes
differ in their fundamental heat transfer equations, they
share nearly all the same supporting models for material
properties, data storage, solution schemes, and spatial
discretization algorithms.
The Crank-Nicholson scheme is semi-implicit and based on an
Adams-Moulton solution approach. It is considered second-order
in time. The algorithm uses an implicit finite difference
scheme coupled with an enthalpy-temperature function to
account for phase change energy accurately. The implicit
formulation for an internal node is shown in the equation
below.
\(\Delta\)x = finite
difference layer thickness (always less than construction
layer thickness)
C\(_{p}\) = specific heat
of material
k\(_{w}\) = thermal
conductivity for interface between i node and i+1 node
k\(_{E}\) = thermal
conductivity for interface between i node and i-1 node
\(\rho\) = density of
material
Then, this equation is accompanied by a second equation
that relates enthalpy and temperature.
\[{h_i} = HTF\left( {{T_i}}
\right)\]
where HTF is an enthalpy-temperature function that uses
user input data.
The fully implicit scheme is also based on an Adams-Moulton
solution approach. It is considered first order in time. The
model equation for this scheme is show in the following
equation.
For both schemes, EnergyPlus uses the following four types
of nodes, as shown in the figure below (1) interior surface
nodes, (2) interior nodes, (3) material interface nodes and
(4) external surface nodes. The grid for each material is
established by specifying a half node for each edge of a
material and equal size nodes for the rest of the material.
Equations such as [eq:InternalNodeImplicitEquation]
are formed for all nodes in a construction. The formulation of
all node types is basically the same.
Node depiction for Conduction
Finite Difference Model [fig:node-depiction-for-conduction-finite]
In the CondFD model, surface discretization depends on the
thermal diffusivity of the material (\(\alpha\)) and time step (\(\Delta\)t) selected, as shown in
the equation below. The default value of 3 for the space
discretization constant, C, is basically the inverse
of the Fourier Number:
\[Fo = \frac{\alpha \Delta
t}{\Delta x^2}\]
and is based on the stability requirement for the explicit
mode that requires values higher than 2, or a Fourier number
lower than 0.5. However, CondFD uses implicit schemes that do
not have the same stability requirements as the explicit mode.
Thus, the default 3 was originally set rather arbitrary. As
of version 7, the value of this constant can be controlled by
the user with the input field called Space Discretization
Constant in the HeatBalanceSettings:ConductionFiniteDifference
input object. The discretization method allows CondFD to
assign different node spacing or grid size to different
material layers in a wall or roof, as building walls and roofs
typically consist of several layers of different materials
having different thermal properties.
The actual integer number of nodes for each layer is then
calculated by rounding off the result from dividing the length
of the material layer by the result of the equation above.
After this, Δx is recalculated by dividing the length of the
material by the number of nodes. A full node is equal to two
half nodes. Lower values for the Space Discretization Constant
yield more nodes, with higher values yield fewer nodes.
Because the solution is implicit, a Gauss-Seidell iteration
scheme is used to update to the new node temperatures in the
construction and under-relaxation is used for increased
stability. The Gauss-Seidell iteration loop is the inner-most
solver and is called for each surface. It is limited to 30
iterations but will exit early when the sum of all the node
temperatures changes between the last call and the current
call, normalized by the sum of the temperature values, is
below 0.000001C. This convergence criteria is typically met
after 3 iterations, except when PCMs are simulated as it takes
an average of 2-3 more iterations when PCM are changing phase.
If the number if iterations needed to met convergence criteria
start to increase, an automatic internal relaxation factor
stabilities the solution and in most cases keep the number of
iterations less than 10.
EnergyPlus also uses a separate, outer iteration loop
across all the different inside surface heat balances so that
internal long-wave radiation exchange can be properly solved.
For CTF formulations, this iteration is controlled by a
maximum allowable temperature difference of 0.002C for inside
face surface temperatures from one iteration to the next (or a
limit of 100 iterations). CondFD uses the same default value
for allowable temperature difference as CTF. However, this
parameter was found to often need to be smaller for stability
and so the inside surface heat balance manager uses a separate
allowable maximum temperature difference when modeling
CondFD. The user can control the value of the relaxation
factor by using the input field called Inside Face Surface
Temperature Convergence Criteria in the HeatBalanceSettings:ConductionFiniteDifference
input object. In addition, if the program detects that there
is instability by watching for excessive numbers of iterations
in this outer loop and may decrease the relaxation factor.
Users can also output the number of iterations inside of
CondFD loop for each surface and the outer internal heat
balance loop for each zone with “CondFD Inner Solver Loop
Iterations” and “Heat Balance Inside Surfaces Calculation
Iterations” respectively.
Because of the iteration scheme used for CondFD, the node
enthalpies get updated each iteration, and then they are used
to develop a variable Cp if a phase change material is being
simulated. This is done by including a third equation for
Cp.
For inputs with MaterialProperty:PhaseChange,
the specific heat is calculated from the tabulated input data
of temperature/enthalpy pairs:
For inputs with MaterialProperty:PhaseChangeHysteresis,
the specific heat is not only dependent on the current state,
but also the previous state, as it captures the hysteresis
physics present between the melting and freezing
processes.
The hysteresis model also has inputs for solid and liquid
state values for thermal conductivity and density. Within the
transition region of the hysteresis model the average of the
two is used. If the dynamic nature of these parameters is not
known, the user may enter the same value for both states and
that static value will be used throughout.
The actual formulation of the hysteresis model is captured
in Figure [fig:PCMHysteresis].
The inputs that led to those curves were as follows:
All temperature “difference” inputs were set to 1.0 as
this is an example only. Using smaller or larger temperature
differences would shrink or expand the freezing or melting
regions accordingly.
The total latent heat transferred during the phase
transition process is set to 25000 J/kg
The peak freezing temperature is set to 23 degrees
Celsius, where the freezing curve transition is
centered.
The peak melting temperature is set to 27 degrees
Celsius, where the melting curve transition is
centered.
Hysteresis PCM Model
Curves
The iteration scheme assures that the correct enthalpy, and
therefore the correct Cp is used in each time step, and the
enthalpy of the material is accounted for accurately. Of
course, if the material is regular, the user input constant Cp
is used.
For non-hysteresis finite difference calculations, the
algorithm also has a provision for including a temperature
coefficient to modify the thermal conductivity. The thermal
conductivity is obtained from:
\[k = {k_o} + {k_1}\left( {{T_i}
- 20} \right)\]
where:
k\(_{o}\) is the 20°C
value of thermal conductivity (normal idf input)
k\(_{1}\) is the change in
conductivity per degree temperature difference from 20°C
As of Version
7, the CondFD implementation was changed to evaluate the
thermal conductivity at the interface between nodes, as shown
below. In this case, EnergyPlus uses a linear interpolation
between nodal points.
These additional property information values are put into
the input file as explained in the Input/Output Reference
Document, but it consists simply of a value for k1 and set of
enthalpy temperature pairs that describe the enthalpy of the
phase change material in straight line segments with respect
to temperature.
A graph showing the effect of a large PCM on the outside
surface of a zone is shown below. The phase change temperature
was 30°C, and the flat temperature response during the phase
change is obvious. This example was run with a zone time step
of one minute to show that such small time steps can be done
with the finite difference solution technique. It is more
efficient to set the zone time step shorter than those used
for the CTF solution algorithm. It should be set to 20 time
steps per hour or greater, and can range up to 60. The finite
difference algorithm actually works better with shorter zone
time steps. The computation time has a minimum at a zone time
step around two minutes (30 time steps/hr), and increases for
shorter or longer zone time steps.
Effects of Large PCM on Outside
Zone Surface [fig:effects-of-large-pcm-on-outside-zone-surface]
Finite
Difference Node Arrangement in Surfaces[LINK]
The Conduction Finite Difference algorithm determines the
number of nodes in each layer of the surface based on the
Fourier stability criteria. The node thicknesses are normally
selected so that the time step is near the explicit solution
limit in spite of the fact that the solution is implicit. For
very thin, high conductivity layers, a minimum of two nodes is
used. This means two half thickness nodes with the node
temperatures representing the inner and outer faces of the
layer. All thicker layers also have two half thickness nodes
at their inner and outer faces. These nodes produce layer
interface temperatures.
The ConductionFiniteDifferenceSimplified capability was
removed as of Version
7.2.
The Conduction Finite Difference algorithm has also been
given the capability to use an expanded thermal conductivity
function. This function, explained in the input/output
document, is similar to the temperature enthalpy function. It
consists of pairs of temperature and thermal conductivity
values that form a linear segmented function. It is
established with the MaterialProperty:VariableThermalConductivity
object.
The Conduction Finite Difference algorithm can output the
heat flux at each node and the heat capacitance of each
half-node. During the CondFD solution iterations, the heat
capacitance of each half node (CondFD Surface Heat Capacitance
Node < n >) is stored:
For nodes which are at the inside or outside face of the
surface, there is only one half-node.
After the CondFD node temperatures have been solved for a
given timestep, the heat fluxes (CondFD Surface Heat Flux Node
< i > ) are calculated beginning with the inside face of
the surface.
HeatCap1\(_{i}\) = heat
capacitance associated with a given outer half-node
HeatCap2\(_{i}\) = heat
capacitance associated with a given inner half-node
QDreport\(_{i}\) = CondFD
Surface Heat Flux Node < i > QSource\(_{i}\) = internal source heat
flux at node i Q\(_{inside}\)
= Surface Inside Face Conduction Heat Transfer Rate per Area
[W/m\(^{2}\)]
N = total number of nodes in a surface including the
surface inside face node. Note that the variable
TotNodes used in the source code is actually N-1. The
surface inside face node is referenced as
TotNodes+1.
Pedersen C.O., Enthalpy Formulation of conduction heat
transfer problems involving latent heat, Simulation, Vol 18,
No. 2, February 1972
Versteeg, H. and Malalasekra, W. 1996. An introduction to
computational fluid dynamic: the finite volume method
approach. Prentice Hall.
Tabares-Velasco, P.C. and Griffith, B. 2012. Diagnostic
Test Cases for Verifying Surface Heat Transfer Algorithms and
Boundary Conditions in Building
Energy Simulation Programs, Journal of Building
Performance Simulation, doi:10.1080/19401493.2011.595501
Tabares-Velasco, P.C., Christensen, C. and Bianchi, M.
2012. Verification and Validation of EnergyPlus Phase Change
Material
Model for Opaque Wall Assemblies, Building
and Environment 54: 186-196.
Conduction Finite Difference Solution Algorithm[LINK]
Basic Finite Difference Solution Approach[LINK]
EnergyPlus models follow fundamental heat balance principles very closely in almost all aspects of the program. However, the simulation of building surface constructions has relied on a conduction transfer function (CTF) transformation carried over from BLAST. This has all the usual restrictions of a transformation-based solution: constant properties, fixed values of some parameters, and do not produce results for the interior of the surface. As the energy analysis field moves toward simulating more advanced constructions, such as phase change materials (PCM), it becomes necessary to step back from transformations to more fundamental forms. Accordingly, a conduction finite difference (CondFD) solution algorithm has been incorporated into EnergyPlus. This does not replace the CTF solution algorithm, but complements it for cases where the user needs to simulate phase change materials or variable thermal conductivity. It is also possible to use the finite difference algorithm for zone time steps as short as one minute.
EnergyPlus includes two different options for the specific scheme or formulation used for the finite difference model. The first scheme is referred to as Crank-Nicholson and was the formulation used in EnergyPlus prior to version 7. As of version 7 a second scheme was added and is referred to as fully implicit. The selection between the two can be made by the user with the HeatBalanceSettings:ConductionFiniteDifference input object. Once selected, the same scheme is used throughout the simulation. Although the two different schemes differ in their fundamental heat transfer equations, they share nearly all the same supporting models for material properties, data storage, solution schemes, and spatial discretization algorithms.
The Crank-Nicholson scheme is semi-implicit and based on an Adams-Moulton solution approach. It is considered second-order in time. The algorithm uses an implicit finite difference scheme coupled with an enthalpy-temperature function to account for phase change energy accurately. The implicit formulation for an internal node is shown in the equation below.
\[C_p \rho \Delta x \frac{T_i^{j+1}-T_i^j}{\Delta t} = \frac{1}{2}\left(k_W\frac{T_{i+1}^{j+1}-T_{i}^{j+1}}{\Delta x} + k_E\frac{T_{i-1}^{j+1}-T_{i}^{j+1}}{\Delta x} + k_W\frac{T_{i+1}^{j}-T_{i}^{j}}{\Delta x} + k_E\frac{T_{i-1}^{j}-T_{i}^{j}}{\Delta x}\right) \label{eq:InternalNodeImplicitEquation}\]
Where:
T = node temperature
Subscripts:
i = node being modeled
i+1 = adjacent node to interior of construction
i-1 = adjacent node to exterior of construction
j+1 = new time step
j = previous time step
\(\Delta\)t = calculation time step
\(\Delta\)x = finite difference layer thickness (always less than construction layer thickness)
C\(_{p}\) = specific heat of material
k\(_{w}\) = thermal conductivity for interface between i node and i+1 node
k\(_{E}\) = thermal conductivity for interface between i node and i-1 node
\(\rho\) = density of material
Then, this equation is accompanied by a second equation that relates enthalpy and temperature.
\[{h_i} = HTF\left( {{T_i}} \right)\]
where HTF is an enthalpy-temperature function that uses user input data.
The fully implicit scheme is also based on an Adams-Moulton solution approach. It is considered first order in time. The model equation for this scheme is show in the following equation.
\[{C_p}\rho {\rm{\Delta x}}\frac{{T_i^{j + 1} - T_i^j}}{{{\rm{\Delta }}t}} = \left( {{k_W}\frac{{\left( {T_{i + 1}^{j + 1} - T_i^{j + 1}} \right)}}{{{\rm{\Delta x}}}} + {k_E}\frac{{\left( {T_{i - 1}^{j + 1} - T_i^{j + 1}} \right)}}{{{\rm{\Delta x}}}}} \right)\]
For both schemes, EnergyPlus uses the following four types of nodes, as shown in the figure below (1) interior surface nodes, (2) interior nodes, (3) material interface nodes and (4) external surface nodes. The grid for each material is established by specifying a half node for each edge of a material and equal size nodes for the rest of the material. Equations such as [eq:InternalNodeImplicitEquation] are formed for all nodes in a construction. The formulation of all node types is basically the same.
In the CondFD model, surface discretization depends on the thermal diffusivity of the material (\(\alpha\)) and time step (\(\Delta\)t) selected, as shown in the equation below. The default value of 3 for the space discretization constant, C, is basically the inverse of the Fourier Number:
\[Fo = \frac{\alpha \Delta t}{\Delta x^2}\]
and is based on the stability requirement for the explicit mode that requires values higher than 2, or a Fourier number lower than 0.5. However, CondFD uses implicit schemes that do not have the same stability requirements as the explicit mode. Thus, the default 3 was originally set rather arbitrary. As of version 7, the value of this constant can be controlled by the user with the input field called Space Discretization Constant in the HeatBalanceSettings:ConductionFiniteDifference input object. The discretization method allows CondFD to assign different node spacing or grid size to different material layers in a wall or roof, as building walls and roofs typically consist of several layers of different materials having different thermal properties.
\[{\rm{\Delta x}} = \sqrt {{\rm{C\alpha \Delta t}}}\]
The actual integer number of nodes for each layer is then calculated by rounding off the result from dividing the length of the material layer by the result of the equation above. After this, Δx is recalculated by dividing the length of the material by the number of nodes. A full node is equal to two half nodes. Lower values for the Space Discretization Constant yield more nodes, with higher values yield fewer nodes.
Because the solution is implicit, a Gauss-Seidell iteration scheme is used to update to the new node temperatures in the construction and under-relaxation is used for increased stability. The Gauss-Seidell iteration loop is the inner-most solver and is called for each surface. It is limited to 30 iterations but will exit early when the sum of all the node temperatures changes between the last call and the current call, normalized by the sum of the temperature values, is below 0.000001C. This convergence criteria is typically met after 3 iterations, except when PCMs are simulated as it takes an average of 2-3 more iterations when PCM are changing phase. If the number if iterations needed to met convergence criteria start to increase, an automatic internal relaxation factor stabilities the solution and in most cases keep the number of iterations less than 10.
EnergyPlus also uses a separate, outer iteration loop across all the different inside surface heat balances so that internal long-wave radiation exchange can be properly solved. For CTF formulations, this iteration is controlled by a maximum allowable temperature difference of 0.002C for inside face surface temperatures from one iteration to the next (or a limit of 100 iterations). CondFD uses the same default value for allowable temperature difference as CTF. However, this parameter was found to often need to be smaller for stability and so the inside surface heat balance manager uses a separate allowable maximum temperature difference when modeling CondFD. The user can control the value of the relaxation factor by using the input field called Inside Face Surface Temperature Convergence Criteria in the HeatBalanceSettings:ConductionFiniteDifference input object. In addition, if the program detects that there is instability by watching for excessive numbers of iterations in this outer loop and may decrease the relaxation factor. Users can also output the number of iterations inside of CondFD loop for each surface and the outer internal heat balance loop for each zone with “CondFD Inner Solver Loop Iterations” and “Heat Balance Inside Surfaces Calculation Iterations” respectively.
\[{T_{i,new}} = {T_{i,old}} + \left( {{T_{i,new}} - {T_{i,old}}} \right)*Relax\]
Because of the iteration scheme used for CondFD, the node enthalpies get updated each iteration, and then they are used to develop a variable Cp if a phase change material is being simulated. This is done by including a third equation for Cp.
For inputs with MaterialProperty:PhaseChange, the specific heat is calculated from the tabulated input data of temperature/enthalpy pairs:
\[Cp = \frac{{{h_{i,new}} - {h_{i,old}}}}{{{T_{i,new}} - {T_{i,old}}}}\]
For inputs with MaterialProperty:PhaseChangeHysteresis, the specific heat is not only dependent on the current state, but also the previous state, as it captures the hysteresis physics present between the melting and freezing processes.
\[Cp = f\left(T_{i,new}, T_{i, prev}, PhaseState_{new}, PhaseState_{prev}\right)\]
The hysteresis model also has inputs for solid and liquid state values for thermal conductivity and density. Within the transition region of the hysteresis model the average of the two is used. If the dynamic nature of these parameters is not known, the user may enter the same value for both states and that static value will be used throughout.
The actual formulation of the hysteresis model is captured in Figure [fig:PCMHysteresis]. The inputs that led to those curves were as follows:
All temperature “difference” inputs were set to 1.0 as this is an example only. Using smaller or larger temperature differences would shrink or expand the freezing or melting regions accordingly.
The total latent heat transferred during the phase transition process is set to 25000 J/kg
The peak freezing temperature is set to 23 degrees Celsius, where the freezing curve transition is centered.
The peak melting temperature is set to 27 degrees Celsius, where the melting curve transition is centered.
The iteration scheme assures that the correct enthalpy, and therefore the correct Cp is used in each time step, and the enthalpy of the material is accounted for accurately. Of course, if the material is regular, the user input constant Cp is used.
For non-hysteresis finite difference calculations, the algorithm also has a provision for including a temperature coefficient to modify the thermal conductivity. The thermal conductivity is obtained from:
\[k = {k_o} + {k_1}\left( {{T_i} - 20} \right)\]
where:
k\(_{o}\) is the 20°C value of thermal conductivity (normal idf input)
k\(_{1}\) is the change in conductivity per degree temperature difference from 20°C
As of Version 7, the CondFD implementation was changed to evaluate the thermal conductivity at the interface between nodes, as shown below. In this case, EnergyPlus uses a linear interpolation between nodal points.
\[{C_p}\rho {\rm{\Delta x}}\frac{{T_i^{j + 1} - T_i^j}}{{{\rm{\Delta }}t}} = \frac{1}{2}\left[ {\left( {{k_W}\frac{{\left( {T_{i + 1}^{j + 1} - T_i^{j + 1}} \right)}}{{{\rm{\Delta x}}}} + {k_E}\frac{{\left( {T_{i - 1}^{j + 1} - T_i^{j + 1}} \right)}}{{{\rm{\Delta x}}}}} \right) + \left( {{k_W}\frac{{\left( {T_{i + 1}^j - T_i^j} \right)}}{{{\rm{\Delta x}}}} + {k_E}\frac{{\left( {T_{i - 1}^j - T_i^j} \right)}}{{{\rm{\Delta x}}}}} \right)} \right]\]
Where,
\[{k_W} = \frac{{\left( {k_{i + 1}^{j + 1} + k_i^{j + 1}} \right)}}{2}\]
\[{{\rm{k}}_{\rm{E}}} = \frac{{\left( {{\rm{k}}_{{\rm{i}} - 1}^{{\rm{j}} + 1} + {\rm{k}}_{\rm{i}}^{{\rm{j}} + 1}} \right)}}{2}\]
These additional property information values are put into the input file as explained in the Input/Output Reference Document, but it consists simply of a value for k1 and set of enthalpy temperature pairs that describe the enthalpy of the phase change material in straight line segments with respect to temperature.
A graph showing the effect of a large PCM on the outside surface of a zone is shown below. The phase change temperature was 30°C, and the flat temperature response during the phase change is obvious. This example was run with a zone time step of one minute to show that such small time steps can be done with the finite difference solution technique. It is more efficient to set the zone time step shorter than those used for the CTF solution algorithm. It should be set to 20 time steps per hour or greater, and can range up to 60. The finite difference algorithm actually works better with shorter zone time steps. The computation time has a minimum at a zone time step around two minutes (30 time steps/hr), and increases for shorter or longer zone time steps.
Finite Difference Node Arrangement in Surfaces[LINK]
The Conduction Finite Difference algorithm determines the number of nodes in each layer of the surface based on the Fourier stability criteria. The node thicknesses are normally selected so that the time step is near the explicit solution limit in spite of the fact that the solution is implicit. For very thin, high conductivity layers, a minimum of two nodes is used. This means two half thickness nodes with the node temperatures representing the inner and outer faces of the layer. All thicker layers also have two half thickness nodes at their inner and outer faces. These nodes produce layer interface temperatures.
The ConductionFiniteDifferenceSimplified capability was removed as of Version 7.2.
Conduction Finite Difference Variable Thermal Conductivity[LINK]
The Conduction Finite Difference algorithm has also been given the capability to use an expanded thermal conductivity function. This function, explained in the input/output document, is similar to the temperature enthalpy function. It consists of pairs of temperature and thermal conductivity values that form a linear segmented function. It is established with the MaterialProperty:VariableThermalConductivity object.
Conduction Finite Difference Source Sink Layers[LINK]
The Conduction Finite Difference algorithm can also invoke the source/sink layer capability by using the Construction:InternalSource object.
Conduction Finite Difference Heat Flux Outputs[LINK]
The Conduction Finite Difference algorithm can output the heat flux at each node and the heat capacitance of each half-node. During the CondFD solution iterations, the heat capacitance of each half node (CondFD Surface Heat Capacitance Node < n >) is stored:
\[{HeatCap_{i} = Cp_{i}*\Delta x_{i}*\rho_{i}/2}\]
For nodes which are at the inside or outside face of the surface, there is only one half-node.
After the CondFD node temperatures have been solved for a given timestep, the heat fluxes (CondFD Surface Heat Flux Node < i > ) are calculated beginning with the inside face of the surface.
\[{QDreport_{N} = Q_{inside}}\]
for the remaining nodes
\[\begin{array}{l} QDreport_{i} = QDreport_{i+1}+HeatCap1_{i+1}* \frac{\left(T_{i+1,new}-T_{i+1,old}\right)}{\Delta t}-QSource_{i}+HeatCap2_{i} \\ \quad \quad \quad \quad * \frac{\left(T_{i,new}-T_{i,old}\right)}{\Delta t} \end{array}\]
Where:
HeatCap1\(_{i}\) = heat capacitance associated with a given outer half-node HeatCap2\(_{i}\) = heat capacitance associated with a given inner half-node QDreport\(_{i}\) = CondFD Surface Heat Flux Node < i > QSource\(_{i}\) = internal source heat flux at node i Q\(_{inside}\) = Surface Inside Face Conduction Heat Transfer Rate per Area [W/m\(^{2}\)]
N = total number of nodes in a surface including the surface inside face node. Note that the variable TotNodes used in the source code is actually N-1. The surface inside face node is referenced as TotNodes+1.
References[LINK]
Pedersen C.O., Enthalpy Formulation of conduction heat transfer problems involving latent heat, Simulation, Vol 18, No. 2, February 1972
Versteeg, H. and Malalasekra, W. 1996. An introduction to computational fluid dynamic: the finite volume method approach. Prentice Hall.
Tabares-Velasco, P.C. and Griffith, B. 2012. Diagnostic Test Cases for Verifying Surface Heat Transfer Algorithms and Boundary Conditions in Building Energy Simulation Programs, Journal of Building Performance Simulation, doi:10.1080/19401493.2011.595501
Tabares-Velasco, P.C., Christensen, C. and Bianchi, M. 2012. Verification and Validation of EnergyPlus Phase Change Material Model for Opaque Wall Assemblies, Building and Environment 54: 186-196.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.