The input object “SurfaceProperty:ExteriorNaturalVentedCavity”
allows modeling a special case for the outside boundary
conditions of heat transfer surfaces with a multi-skin
exterior that is opaque. From the thermal envelope’s point of
view, the presence of a vented cavity on the outside of the
surface modifies the conditions experienced by the underlying
heat transfer surfaces. This exterior cavity acts as a
radiation and convection baffle situated between the exterior
environment and the outside face of the underlying heat
transfer surface. The actual outer surface is referred to as
the “baffle”. The modeling here assumes that the heat
capacity in the outer baffle can be neglected since it is much
lower than the underlying mass surface. This object is used
with the BuildingSurface:Detailed
object where the heat transfer surfaces are referred to as the
underlying surfaces. The constructions and materials for the
heat transfer surfaces should reflect the construction of just
the underlying surface. The SurfaceProperty:ExteriorNaturalVentedCavity
object is used to describe the detached layer, or baffle, and
the characteristics of the cavity and openings for natural
ventilation. This model uses the SurfaceProperty:OtherSideConditionsModel
object to pass boundary conditions to the heat transfer
modeling for the underlying surfaces.
The baffle is assumed to be sufficiently thin and
high-conductivity so that it can be modeled using a single
temperature (for both sides and along its area). This
temperature \({T_{s,baff}}\)
is determined by formulating a heat balance on a control
volume that just encapsulates the baffle surface. The baffle
is assumed to completely cover the underlying surface such
that it is opaque to shortwave and longwave radiation. This
assumption means that even though the baffle will have some
open area for ventilation, no solar energy passes through
these openings. The heat balance is diagrammed in the
following figure.
\(q''_{\alpha
sol}\) is absorbed direct and diffuse solar (short
wavelength) radiation heat flux.
\(q''_{LWR,Env}\)
is net long wavelength (thermal) radiation flux exchange with
the air and surroundings.
\(q''_{conv,Env}\)
= surface convection flux exchange with outside air.
\(q''_{LWR,cav}\)
is net long wavelength (thermal) radiation flux exchange with
the outside face of the underlying surface(s).
\(q''_{conv,cav}\)
= surface convection flux exchange with cavity air.
\({q''_{source}}\)
is a source/sink term that accounts for energy exported out of
the control volume when the baffle is a hybrid device such as
a photovoltaic panel.
All terms are positive for net flux to the baffle. Each of
these heat balance components is introduced briefly below.
\(q''_{\alpha
sol}\) is calculated using procedures presented
elsewhere in this manual and includes both direct and diffuse
incident solar radiation absorbed by the surface face. This
is influenced by location, surface facing angle and tilt,
shading surfaces, surface face material properties, weather
conditions, etc. The baffle blocks all shortwave radiation
from reaching the underlying surface.
\({q''_{LWR,Env}}\) is a
standard radiation exchange formulation between the surface,
the sky, the ground, and the atmosphere. The radiation heat
flux is calculated from the surface absorptivity, surface
temperature, sky, air, and ground temperatures, and sky and
ground view factors. Radiation is modeled using linearized
coefficients. The baffle blocks all longwave radiation.
\(q''_{conv,env}\)
is modeled using the classical formulation: \(q''_{conv} = h_{co}(T_{air} -
T_{o})\) where h\(_{co}\), is the convection
coefficient. The h\(_{co}\)
is treated in the same way as an outside face with
ExteriorEnvironment conditions. In addition, when it is
raining outside, we assume the baffle gets wet and model the
enhanced surface heat transfer using a large value for \({h_{co}}\) .
\({q''_{LWR,cav}}\) is a
standard radiation exchange formulation between the baffle
surface and the underlying heat transfer surface located
across the cavity. Radiation is modeled using linearized
coefficients.
\(q''_{conv,cav}\)
is modeled using the classical formulation: \(q''_{conv} = h_{cp}(T_{air} -
T_{o})\) where h\(_{cp}\), is the convection
coefficient. The value for h\(_{cp}\) is obtained from
correlations used for window gaps from ISO (2003) standard
15099.
Substituting models into Equation [eq:BaffleSurfaceCVHeatBalance]
and solving for \({T_{s,baff}}\) yields the
following equation:
The cavity is the volume of air located between
the baffle and the underlying heat transfer surface. The
cavity air is modeled as well-mixed. The uniform temperature
of the cavity air, \({T_{a,cav}}\) , is determined by
formulating a heat balance on a control volume of air as
diagrammed below.
Cavity Air Heat Balance [fig:cavity-air-heat-balance]
The heat balance on the cavity air control volume is:
\({\dot m_{vent}}\) is
the air mass flow from natural forces [kg/s]
Modeling natural ventilation air exchanges in a general way
is challenging. Simplistic engineering models are used to
model \({\dot m_{vent}}\)
resulting from natural buoyancy and wind forces. Reasoning
that the configuration is similar to single-side natural
ventilation, we elect to use correlations for natural
ventilation presented as equations (29) and (30) in Chapter 26
of ASHRAE Handbook of Fundamentals (2001).
\(\rho\) is the density
of air [kg/m\(^{3}\)],
and
\(\rlap{--} \dot{V}_{tot} =
\rlap{--} \dot{V}_{wind} + \rlap{--}
\dot{V}_{thermal}\) is the total volumetric flow rate
of air ventilating in and out of the cavity.
\({{\rm{\rlap{--} \dot
V}}_{{\rm{thermal}}}} = {C_D}{A_{in}}\sqrt {2g\Delta
{H_{NPL}}\left( {{T_{amb}} - {T_{a,cav}}}
\right)/{T_{amb}}}\) (if \(T_{amb} > T_{a,cav}\) and
baffle is vertical)
\({C_v}\) is the
effectiveness of the openings that depends on opening geometry
and the orientation with respect to the wind. ASHRAE HoF
(2001) indicates values ranging from 0.25 to 0.6. This value
is available for user input.
\({C_D}\) is the
discharge coefficient for the opening and depends on opening
geometry. This value is available for user input.
Mass continuity arguments lead to modeling the area of the
openings as one half of the total area of the openings, so we
have:
\[{A_{in}} =
\frac{{A\,}}{2}\]
\(g\) is the
gravitational constant taken as 9.81 [m/s\(^{2}\)].
\(\Delta {H_{NPL}}\) is
the height from midpoint of lower opening to the Neutral
Pressure Level. This is value is available for user
input.
If the cavity is horizontal and \(T_{amb} > T_{a,cav}\) then
\({{\rm{\rlap{--} \dot
V}}_{{\rm{thermal}}}}{\rm{ = 0}}\) because this is a
stable situation.
The exterior baffle and cavity are applied to the outside
of a heat transfer surface. This surface is modeled using the
usual EnergyPlus methods for handling heat capacity and
transients – typically the CTF method. These native
EnergyPlus heat balance routines are used to calculate \({T_{so}}\) . The exterior baffle
and cavity system is coupled to the underlying surface using
the SurfaceProperty:OtherSideConditionsModel
mechanism. The exterior naturally vented cavity model
provides values for \({h_{r,cav}}\), \({T_{s,baff}}\), \({h_{c,cav}}\), and \({T_{a,cav}}\) for use with the
heat balance model calculations for the outside face of the
underlying surface (described elsewhere in this manual).
The exterior vented cavity model uses standard EnergyPlus
surfaces in order to take advantage of the detailed solar and
shading calculations. Solar radiation incident on the surface
includes beam and diffuse radiation, as well as radiation
reflected from the ground and adjacent surfaces. Shading of
the collector by other surfaces, such as nearby buildings or
trees, is also taken into account.
The outdoor wind speed affects terms used in modeling. The
wind speed in the weather file is assumed to be measured at a
meteorological station located in an open field at a height of
10 m. To adjust for different terrain at the building site
and differences in the height of building surfaces, the local
wind speed is calculated for each surface.
The wind speed is modified from the measured meteorological
wind speed by the equation (ASHRAE 2001):
where z is the height of the centroid of the system, z\(_{met}\) is the height of the
standard meteorological wind speed measurement, and a and
\(\delta\) are
terrain-dependent coefficients. \(\delta\) is the boundary layer
thickness for the given terrain type. The values of a and
\(\delta\) are shown in the
following table:
Terrain-Dependent Coefficients (ASHRAE 2001).
Terrain
Description
Exponent, a
Layer Thickness, \(\delta\) (m)
1
Flat, open country
0.14
270
2
Rough, wooded country
0.22
370
3
Towns and cities
0.33
460
4
Ocean
0.10
210
5
Urban, industrial, forest
0.22
370
The exterior vented cavity can be defined such that it has
multiple underlying heat transfer surfaces. The centroid
heights for each surface are area-weighted to determine the
average height for use in the local wind calculation.
Exterior cavity modeling requires calculating up to three
different coefficients for surface convection heat transfer.
These coefficients are defined in the classic way by:
First, \({h_{co}}\) is
the convection coefficient for the baffle surface facing the
outdoors. It is modeled in exactly the same way as elsewhere
in EnergyPlus and will depend on the user setting for Outside
Convection Algorithm – Outside Surface Heat Balance entry
elsewhere in this document.
Second, \({h_{c,cav}}\)
is the convection coefficient for baffle surfaces facing the
cavity. This coefficient is applied to both the baffle and
the underlying surface. The convection coefficient is modeled
in the same way used in EnergyPlus to model air gaps in
windows. These correlations vary by Rayleigh number and
surface tilt and are based on the work of various research
including Hollands et. al., Elsherbiny et. al., Wright, and
Arnold. The formulations are documented in ISO (2003)
standard 15099. The routines were adapted from Subroutine
NusseltNumber in WindowManager.f90 (by F. Winkelmann), which
itself was derived from Window5 subroutine “nusselt”.
Exterior vented cavity modeling requires calculating up to
four different linearized coefficients for radiation heat
transfer. Whereas radiation calculations usually use
temperature raised to the fourth power, this greatly
complicates solving heat balance equations for a single
temperature. Linearized radiation coefficients have the same
units and are used in the same manner as surface convection
coefficients and introduce very little error for the
temperature levels involved.
The radiation coefficient, \({h_{r,cav}}\) , is used to model
thermal radiation between the collector surface and the
outside face of the underlying heat transfer surface. We
assume a view factor of unity. It is calculated using:
\({\sigma_{SB}}\) is the
Stefan-Boltzmann constant,
\({e_{baff}}\) is the
longwave thermal emittance of the baffle, and
\({e_{so}}\) is the
longwave thermal emittance of the underlying heat transfer
surface.
The three other coefficients, \({h_{r,atm}}\) , \({h_{r,sky}}\) , and \({h_{r,gnd}}\) are used elsewhere
in EnergyPlus for the outside face surface heat balance and
are calculated in the same manner as Equation [eq:HrcavEquation].
[This is accomplished by calling subroutine
InitExteriorConvectionCoeffs in the file
HeatBalanceConvectionCoeffs.f90. ]
ASHRAE HOF 2001. 2001 ASHRAE Fundamentals Handbook.
American Society of Heating Refrigeration and Air-Conditioning
Engineers. Altanta GA.
ISO. 2003. ISO 15099:2003. Thermal performance of windows,
doors, and shading devices – Detailed calculations.
International Organization for Standardization.
Exterior Naturally Vented Cavity[LINK]
The input object “SurfaceProperty:ExteriorNaturalVentedCavity” allows modeling a special case for the outside boundary conditions of heat transfer surfaces with a multi-skin exterior that is opaque. From the thermal envelope’s point of view, the presence of a vented cavity on the outside of the surface modifies the conditions experienced by the underlying heat transfer surfaces. This exterior cavity acts as a radiation and convection baffle situated between the exterior environment and the outside face of the underlying heat transfer surface. The actual outer surface is referred to as the “baffle”. The modeling here assumes that the heat capacity in the outer baffle can be neglected since it is much lower than the underlying mass surface. This object is used with the BuildingSurface:Detailed object where the heat transfer surfaces are referred to as the underlying surfaces. The constructions and materials for the heat transfer surfaces should reflect the construction of just the underlying surface. The SurfaceProperty:ExteriorNaturalVentedCavity object is used to describe the detached layer, or baffle, and the characteristics of the cavity and openings for natural ventilation. This model uses the SurfaceProperty:OtherSideConditionsModel object to pass boundary conditions to the heat transfer modeling for the underlying surfaces.
Baffle Heat Balance[LINK]
The baffle is assumed to be sufficiently thin and high-conductivity so that it can be modeled using a single temperature (for both sides and along its area). This temperature \({T_{s,baff}}\) is determined by formulating a heat balance on a control volume that just encapsulates the baffle surface. The baffle is assumed to completely cover the underlying surface such that it is opaque to shortwave and longwave radiation. This assumption means that even though the baffle will have some open area for ventilation, no solar energy passes through these openings. The heat balance is diagrammed in the following figure.
The heat balance on the baffle surface’s control volume is:
\[{q''_{\alpha sol}} + {q''_{LWR,Env}} + {q''_{conv,Env}} + {q''_{LWR,cav}} + {q''_{conv,cav}} + {q''_{source}} = 0 \label{eq:BaffleSurfaceCVHeatBalance}\]
where:
\(q''_{\alpha sol}\) is absorbed direct and diffuse solar (short wavelength) radiation heat flux.
\(q''_{LWR,Env}\) is net long wavelength (thermal) radiation flux exchange with the air and surroundings.
\(q''_{conv,Env}\) = surface convection flux exchange with outside air.
\(q''_{LWR,cav}\) is net long wavelength (thermal) radiation flux exchange with the outside face of the underlying surface(s).
\(q''_{conv,cav}\) = surface convection flux exchange with cavity air.
\({q''_{source}}\) is a source/sink term that accounts for energy exported out of the control volume when the baffle is a hybrid device such as a photovoltaic panel.
All terms are positive for net flux to the baffle. Each of these heat balance components is introduced briefly below.
External SW Radiation[LINK]
\(q''_{\alpha sol}\) is calculated using procedures presented elsewhere in this manual and includes both direct and diffuse incident solar radiation absorbed by the surface face. This is influenced by location, surface facing angle and tilt, shading surfaces, surface face material properties, weather conditions, etc. The baffle blocks all shortwave radiation from reaching the underlying surface.
External LW Radiation[LINK]
\({q''_{LWR,Env}}\) is a standard radiation exchange formulation between the surface, the sky, the ground, and the atmosphere. The radiation heat flux is calculated from the surface absorptivity, surface temperature, sky, air, and ground temperatures, and sky and ground view factors. Radiation is modeled using linearized coefficients. The baffle blocks all longwave radiation.
External Convection[LINK]
\(q''_{conv,env}\) is modeled using the classical formulation: \(q''_{conv} = h_{co}(T_{air} - T_{o})\) where h\(_{co}\), is the convection coefficient. The h\(_{co}\) is treated in the same way as an outside face with ExteriorEnvironment conditions. In addition, when it is raining outside, we assume the baffle gets wet and model the enhanced surface heat transfer using a large value for \({h_{co}}\) .
Cavity LW Radiation[LINK]
\({q''_{LWR,cav}}\) is a standard radiation exchange formulation between the baffle surface and the underlying heat transfer surface located across the cavity. Radiation is modeled using linearized coefficients.
Cavity Convection[LINK]
\(q''_{conv,cav}\) is modeled using the classical formulation: \(q''_{conv} = h_{cp}(T_{air} - T_{o})\) where h\(_{cp}\), is the convection coefficient. The value for h\(_{cp}\) is obtained from correlations used for window gaps from ISO (2003) standard 15099.
Substituting models into Equation [eq:BaffleSurfaceCVHeatBalance] and solving for \({T_{s,baff}}\) yields the following equation:
\[{T_{s,baff}} = \frac{{\left( {{I_s}\alpha + {h_{co}}{T_{amb}} + {h_{r,atm}}{T_{amb}} + {h_{r,sky}}{T_{sky}} + {h_{r,gnd}}{T_{amb}} + {h_{r,cav}}{T_{so}} + {h_{c,cav}}{T_{a,cav}} + {{q''}_{source}}} \right)}}{{\left( {{h_{co}} + {h_{r,air}} + {h_{r,sky}} + {h_{r,gnd}} + {h_{r,cav}} + {h_{c,cav}}} \right)}}\]
where,
\({I_s}\) is the incident solar radiation of all types [W/m\(^{2}\)],
\(\alpha\) is the solar absorptivity of the baffle [dimensionless],
\({h_{r,atm}}\) is the linearized radiation coefficient for the surrounding atmosphere [W/m\(^{2}\)·K],
\({T_{amb}}\) is the outdoor drybulb from the weather data, also assumed for ground surface [ºC],
\({h_{r,sky}}\) is the linearized radiation coefficient for the sky [W/m\(^{2}\)·K],
\({T_{sky}}\) is the effective sky temperature [ºC],
\({h_{r,gnd}}\) is the linearized radiation coefficient for the ground [W/m\(^{2}\)·K],
\({h_{r,cav}}\) is the linearized radiation coefficient for the underlying surface [W/m\(^{2}\)·K],
\({T_{so}}\) is the temperature of the outside face of the underlying heat transfer surface [ºC],
\({h_{co}}\) is the convection coefficient for the outdoor environment [W/m\(^{2}\)·K],
\({h_{c,cav}}\) is the convection coefficient for the surfaces facing the plenum [W/m\(^{2}\)·K], and
\({T_{a,cav}}\) is the drybulb temperature for air in the cavity [ºC].
Cavity Heat Balance[LINK]
The cavity is the volume of air located between the baffle and the underlying heat transfer surface. The cavity air is modeled as well-mixed. The uniform temperature of the cavity air, \({T_{a,cav}}\) , is determined by formulating a heat balance on a control volume of air as diagrammed below.
The heat balance on the cavity air control volume is:
\[{\dot Q_{vent}} + {\dot Q_{co}} + {\dot Q_{c,baff}} = 0 \label{eq:CavityAirCVHeatBalance}\]
where,
\(\dot{Q}_{vent}\) is the net rate of energy added from natural ventilation – where outdoor ambient air exchanges with the cavity air.
\(\dot{Q}_{co}\) is the net rate of energy added by surface convection heat transfer with the underlying surface.
\({\dot Q_{c,baff}}\) is the net rate of energy added by surface convection heat transfer with the collector.
And substituting into Equation [eq:CavityAirCVHeatBalance] yields the following equation:
\[{T_{a,cav}} = \frac{{\left( {{h_{c,cav}}A\,{T_{so}} + {{\dot m}_{vent}}{c_p}{T_{amb}} + {h_{c,cav}}A\,{T_{s,baff}}} \right)}}{{\left( {{h_{c,cav}}A + {{\dot m}_{vent}}{c_p} + {h_{c,cav}}A} \right)}}\]
where,
\({\dot m_{vent}}\) is the air mass flow from natural forces [kg/s]
Modeling natural ventilation air exchanges in a general way is challenging. Simplistic engineering models are used to model \({\dot m_{vent}}\) resulting from natural buoyancy and wind forces. Reasoning that the configuration is similar to single-side natural ventilation, we elect to use correlations for natural ventilation presented as equations (29) and (30) in Chapter 26 of ASHRAE Handbook of Fundamentals (2001).
\[{\dot m_{vent}} = \rho \,{{\rm{\rlap{--} \dot V}}_{{\rm{tot}}}}\]
where,
\(\rho\) is the density of air [kg/m\(^{3}\)], and
\(\rlap{--} \dot{V}_{tot} = \rlap{--} \dot{V}_{wind} + \rlap{--} \dot{V}_{thermal}\) is the total volumetric flow rate of air ventilating in and out of the cavity.
\(\rlap{--} \dot{V}_{wind} = C_{v}A_{in}U_{\infty}\)
\({{\rm{\rlap{--} \dot V}}_{{\rm{thermal}}}} = {C_D}{A_{in}}\sqrt {2g\Delta {H_{NPL}}\left( {{T_{a,cav}} - {T_{amb}}} \right)/{T_{a,cav}}}\) (if \(T_{a,cav} > T_{amb}\) )
\({{\rm{\rlap{--} \dot V}}_{{\rm{thermal}}}} = {C_D}{A_{in}}\sqrt {2g\Delta {H_{NPL}}\left( {{T_{amb}} - {T_{a,cav}}} \right)/{T_{amb}}}\) (if \(T_{amb} > T_{a,cav}\) and baffle is vertical)
\({C_v}\) is the effectiveness of the openings that depends on opening geometry and the orientation with respect to the wind. ASHRAE HoF (2001) indicates values ranging from 0.25 to 0.6. This value is available for user input.
\({C_D}\) is the discharge coefficient for the opening and depends on opening geometry. This value is available for user input.
Mass continuity arguments lead to modeling the area of the openings as one half of the total area of the openings, so we have:
\[{A_{in}} = \frac{{A\,}}{2}\]
\(g\) is the gravitational constant taken as 9.81 [m/s\(^{2}\)].
\(\Delta {H_{NPL}}\) is the height from midpoint of lower opening to the Neutral Pressure Level. This is value is available for user input.
If the cavity is horizontal and \(T_{amb} > T_{a,cav}\) then \({{\rm{\rlap{--} \dot V}}_{{\rm{thermal}}}}{\rm{ = 0}}\) because this is a stable situation.
Underlying Heat Transfer Surface[LINK]
The exterior baffle and cavity are applied to the outside of a heat transfer surface. This surface is modeled using the usual EnergyPlus methods for handling heat capacity and transients – typically the CTF method. These native EnergyPlus heat balance routines are used to calculate \({T_{so}}\) . The exterior baffle and cavity system is coupled to the underlying surface using the SurfaceProperty:OtherSideConditionsModel mechanism. The exterior naturally vented cavity model provides values for \({h_{r,cav}}\), \({T_{s,baff}}\), \({h_{c,cav}}\), and \({T_{a,cav}}\) for use with the heat balance model calculations for the outside face of the underlying surface (described elsewhere in this manual).
Solar and Shading Calculations[LINK]
The exterior vented cavity model uses standard EnergyPlus surfaces in order to take advantage of the detailed solar and shading calculations. Solar radiation incident on the surface includes beam and diffuse radiation, as well as radiation reflected from the ground and adjacent surfaces. Shading of the collector by other surfaces, such as nearby buildings or trees, is also taken into account.
Local Wind Speed Calculations[LINK]
The outdoor wind speed affects terms used in modeling. The wind speed in the weather file is assumed to be measured at a meteorological station located in an open field at a height of 10 m. To adjust for different terrain at the building site and differences in the height of building surfaces, the local wind speed is calculated for each surface.
The wind speed is modified from the measured meteorological wind speed by the equation (ASHRAE 2001):
\[{U_\infty } = {V_{met}}{\left( {\frac{{{\delta_{met}}}}{{{z_{met}}}}} \right)^{{a_{met}}}}{\left( {\frac{z}{\delta }} \right)^a}\]
where z is the height of the centroid of the system, z\(_{met}\) is the height of the standard meteorological wind speed measurement, and a and \(\delta\) are terrain-dependent coefficients. \(\delta\) is the boundary layer thickness for the given terrain type. The values of a and \(\delta\) are shown in the following table:
The exterior vented cavity can be defined such that it has multiple underlying heat transfer surfaces. The centroid heights for each surface are area-weighted to determine the average height for use in the local wind calculation.
Convection Coefficients[LINK]
Exterior cavity modeling requires calculating up to three different coefficients for surface convection heat transfer. These coefficients are defined in the classic way by:
\[{h_c} = \frac{{{T_{air}} - {T_{surf}}}}{{{{q''}_{conv}}}}\]
First, \({h_{co}}\) is the convection coefficient for the baffle surface facing the outdoors. It is modeled in exactly the same way as elsewhere in EnergyPlus and will depend on the user setting for Outside Convection Algorithm – Outside Surface Heat Balance entry elsewhere in this document.
Second, \({h_{c,cav}}\) is the convection coefficient for baffle surfaces facing the cavity. This coefficient is applied to both the baffle and the underlying surface. The convection coefficient is modeled in the same way used in EnergyPlus to model air gaps in windows. These correlations vary by Rayleigh number and surface tilt and are based on the work of various research including Hollands et. al., Elsherbiny et. al., Wright, and Arnold. The formulations are documented in ISO (2003) standard 15099. The routines were adapted from Subroutine NusseltNumber in WindowManager.f90 (by F. Winkelmann), which itself was derived from Window5 subroutine “nusselt”.
Radiation Coefficients[LINK]
Exterior vented cavity modeling requires calculating up to four different linearized coefficients for radiation heat transfer. Whereas radiation calculations usually use temperature raised to the fourth power, this greatly complicates solving heat balance equations for a single temperature. Linearized radiation coefficients have the same units and are used in the same manner as surface convection coefficients and introduce very little error for the temperature levels involved.
The radiation coefficient, \({h_{r,cav}}\) , is used to model thermal radiation between the collector surface and the outside face of the underlying heat transfer surface. We assume a view factor of unity. It is calculated using:
\[{h_{r,cav}} = {\sigma_{SB}}{e_{baff}}{e_{so}}\frac{{\left( {T_{s,baff}^4 - T_{so}^4} \right)}}{{\left( {{T_{s,baff}} - {T_{so}}} \right)}} \label{eq:HrcavEquation}\]
where,
all temperatures are converted to Kelvin,
\({\sigma_{SB}}\) is the Stefan-Boltzmann constant,
\({e_{baff}}\) is the longwave thermal emittance of the baffle, and
\({e_{so}}\) is the longwave thermal emittance of the underlying heat transfer surface.
The three other coefficients, \({h_{r,atm}}\) , \({h_{r,sky}}\) , and \({h_{r,gnd}}\) are used elsewhere in EnergyPlus for the outside face surface heat balance and are calculated in the same manner as Equation [eq:HrcavEquation]. [This is accomplished by calling subroutine InitExteriorConvectionCoeffs in the file HeatBalanceConvectionCoeffs.f90. ]
References[LINK]
ASHRAE HOF 2001. 2001 ASHRAE Fundamentals Handbook. American Society of Heating Refrigeration and Air-Conditioning Engineers. Altanta GA.
ISO. 2003. ISO 15099:2003. Thermal performance of windows, doors, and shading devices – Detailed calculations. International Organization for Standardization.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.