The water pump is quite simply the component that drives
the flow in plant and condenser loops. How it reacts depends
on several different conditions. In total, there are three
different decision variables, two of which are defined by user
input. These three deciding factors are whether the pump is
constant or variable speed, whether the pump operation is
continuous or intermittent, and whether or not there is a load
on the loop. The pump is simulated first on the supply side
loop after the demand side loop has determined what the demand
on the loop will be. For further reference look at sections
Pump Control for Plant and Condenser Loops, Plant/Condenser
Supply Side, and Plant/Condenser Demand Side in the Plant Flow
Resolver of this document.
Boiler/chiller should be variable flow, regardless of
whether pump is intermittent or continuous (runs at the
minimum if demand is less than minimum, this includes
zero.)
Pump may be intermittent or continuous as long as the
bypass can handle the entire pump volume when the boiler is
not operating
Multiple branches add more complexity, but it is nothing
more than continuity. If the pump is putting out flow then it
has to have a branch to flow down whether it is a chiller or a
bypass. It can be safer to add the bypass for a simulation. If
the active machines require the flow the bypass will be dry.
If performing a pressure simulation, and the flow goes through
a machine which is off, the pressure drop will be accounted
for, but no heat transfer through the machine will be
calculated.
If the user designates a pump that is operating
continuously, the pump will run regardless of whether or not
there is a load. This may have the net effect of adding heat
to the loop if no equipment is turned on. If the pump operates
intermittently, the pump will run at its capacity if a load is
sensed and will shut off if there is no load on the loop. If
the pump is scheduled, the schedule modifies the Rated
Volumetric Flow Rate of the pump on a time basis. The default
is that the pump is ON and runs according to its other
operational requirements.
Shown below is pseudo code for the calculation of the total
efficiency of the pump and the actual pumping efficiency when
the motor efficiency is accounted for either variable or
constant volume pumps.
! Total Efficiency % = Rated Volume Flow Rate *
Rated Pump Head / Rated Power Use
There is an option when performing plant/condenser loop
simulations to account for dynamically changing loop pressure
drop. For the current implementation, the loop pressure drop
is calculated based on pressure drop data on each branch of
the loop, then this total pressure drop is set as the pump
pressure head. There is no pump curve implemented yet, so it
is assumed that the pump can always handle this pressure
value. This is a first approximation to actually having the
pump ride a curve, and this initial implementation allows the
user to enter minimal data, and yet get a more dynamic output
for pump power, which is calculated based on current pressure
drop and flow rate. The equation for pump power is now:
Without the pressure simulation, the pump power is based on
the rated value entered with the pump object. For further
information, see the input-output reference for Branch
objects, and PlantLoop/CondenserLoop objects; as well as the
Plant/Condenser loop section of this engineering
reference.
A variable speed pump (object name: Pump:VariableSpeed) is
defined with maximum and minimum flow rates that are the
physical limits of the device. The pump will operate and
select a flow somewhere between the minimum and maximum
limits. In the case where the pump is running, the pump will
try to meet the flow request made by demand side
components.
All of the pump rules and efficiency and power calculations
are applicable from the introduction in the pump group
section. The main difference between the the variable volume
pump and the constant volume pump is the Part Load Performance
Curve.The fraction of full load power is determined by the
cubic equation:
where C\(_{1}\),C\(_{2}\),C\(_{3}\),and C\(_{4}\) are Coefficients 1 – 4 and
PLR is the Part Load Ratio. In the pseudo code below, the
FracFullLoadPower modifies the NomPowerUse for the total pump
“Power” and shows the “ShaftPower” and the
“PumpHeattoFluid”.
Pressure-based
Flow for Variable Speed Pumps[LINK]
With the introduction of pressure simulations in plant
loops, the variable speed pump object now has the capability
to model a more realistic variable speed operation. There are
two operation modes which are introduced: differential
pressure control is a widely used VFD control method while
most VFDs also have a manual control mode in which the user
determines the input frequency of the electric motor. The mode
can be selected as ‘ManualControl’ or
‘PressureSetpointControl’ in the VFD Control Type input in Pump:VariableSpeed
objects.
In manual VFD control mode the specified schedule will
determine the current pump rotational speed throughout the
simulation. This RPM value will be used to scale the pump
curve which is entered by the user in non-dimensional form.
Once the pump curve has been fixed then the successive
substitution method will use this curve with the system curve
to resolve the operating point. VFD manual control mode is
implemented in EnergyPlus with the use of the RPM schedule
input.
Differential pressure based control will maintain the
differential pressure within the specified range. The pressure
drop corresponding to the mass flow request will be calculated
using the effective pressure constant of the system. This
pressure drop will be checked against the pressure set point
range. If the pressure drop is within the user specified
range, then the mass flow rate will be checked against mass
flow rates of operating points corresponding to maximum and
minimum rotational speeds. Maximum and minimum differential
pressure and rotational speeds are schedule inputs and can be
entered as constant schedule.
The operation of a constant speed pump (object name:
Pump:ConstantSpeed) is fairly straightforward. The user
designates a maximum flow rate and when this pumpo operates it
will run at that capacity. The main difference between the
constant speed pump and the variable speed pump is that the
fraction of full load power is always = 1. In the pseudo code
below, the FracFullLoadPower is = 1.0, therefore the Power is
always the full power.
Pressure-based
Flow for Constant Speed Pumps[LINK]
The constant speed pump can flow can also be overridden
dynamically based on a response to the plant loop pressure
drop. In “single-loop-pump” simulations (no branch pumps, no
common pipe), the user can enter a dimensionless pump curve on
the Pump:ConstantSpeed
(see I/O ref) object which represents the single speed
pressure-flow relationship of the pump. In the process of
determining the operating flow rate for the pump, the pump
will check to see if a valid pressure simulation is being
performed. If it is, a flow will be prescribed based on a
resolution between system pressure characteristics and the
pump pressure curve. This will cause the pump flow to be
“unpredictable,” meaning that it will not always be a
constant, expected value, which is basically what the constant
speed pump gives you without the pressure simulation. There is
more detail on the pressure based simulation in the
Plant/Condenser loop sections of this documentation.
Due to the fact that a pump is a mechanical device that
acts on the fluid it is circulating, it causes the fluid to
increase in temperature. The EnergyPlus model assumes that all
pressure increase caused by the pump will eventually be lost
due to friction, and that friction will be added as heat to
the fluid. Since the plant and condenser loops are not yet
true pressure-based models, EnergyPlus assumes that all of the
heat resulting from the pump itself and from friction
throughout the loop. Therefore, as of version 7, the pump heat
is added to the plant loop interface by injecting the heat
into the mixed tanks used to model loop thermal
capacitance(previously it was added at the outlet node of the
pump). The amount of heat added to the fluid is calculated
using the following two equations:
where the pump motor efficiency is defined by the user
input and the FracMotorLossToFluid is the amount of heat
generated by the pump motor that is added to the fluid loop
(as opposed to being lost to the environment where the pump is
located). FracMotorLossToFluid is also a user input.
Note that the shaft power relates to the increase in head
through the pump. Since all of this head is lost through the
piping network due to frictional heat, this represents a heat
gain by the fluid throughout the network. For simplicity, this
heat is added along with the heat resulting from the pump
motor. The difference between the pump power and the shaft
power is the inefficiency of the pump—or the amount of energy
input into the pump that the motor converts to heat rather
than mechanical energy. Some of this heat is added to the
fluid being pumped. These two terms are shown in the
PumpHeatToFluid equation shown above. Since EnergyPlus Version
7, this heat is added to the loop capacitance tank(s) rather
than at the pump’s outlet and so the outlet temperatue is
equal to the inlet temperaure.
If the user input includes naming a Zone
that surrounds the pump, then the pump becomes a source of
internal heat gain to that zone. The amount of heat
transmitted to the surrounding zone is simply the difference
between power input and the rate of heat transferred to the
fluid. The user can also input a fraction, \({f_{rad}}\), that controls the
overall split between thermal radiation and sensible
convection. The pump’s sensible zone gains are determined
using the following equations:
The input objects HeaderedPumps:ConstantSpeed
and HeaderedPumps:VariableSpeed
provide models for headered pumps that consist of two or more
pumps connected in parallel. The headered pump is simulated as
a single component, and it is specified as an integer number
of a specific pump. The flow rate provided by the headered
pump is determined by the number of pumps in operation and the
flow rate of the individual pump. The total flow rate is
calculated as
The simulation starts by turning ON all pumps in the group.
The pumps are then turned OFF one at a time until the flow
provided is less than the flow requested. Finally the last
pump is turned back ON to meet the remaining flow
(FlowDifference) requested. The flow rate of the last pump
depends on the pump bank type. For constant speed headered
pumps, the last pump runs at the nominal flow rate, thereby
giving a final headered pump flow which is equal to or greater
than the flow requested. In a variable speed headered pump the
last pump runs at part load so that the flow provided matches
the flow requested. The power of the headered pump is then
calculated as
The input object Pump:VariableSpeed:Condensate
provides a model for steam condensate pumps, see the
discussion for steam loops, reference: Condensate Pump.
Pumps[LINK]
The water pump is quite simply the component that drives the flow in plant and condenser loops. How it reacts depends on several different conditions. In total, there are three different decision variables, two of which are defined by user input. These three deciding factors are whether the pump is constant or variable speed, whether the pump operation is continuous or intermittent, and whether or not there is a load on the loop. The pump is simulated first on the supply side loop after the demand side loop has determined what the demand on the loop will be. For further reference look at sections Pump Control for Plant and Condenser Loops, Plant/Condenser Supply Side, and Plant/Condenser Demand Side in the Plant Flow Resolver of this document.
Summary of Pump Rules[LINK]
Pumps in Plant Loop can be on the supply side or demand side
A Pump, if present, in the demand side of plant loop must be the first component of the inlet branch.
Pumps in Condenser loop must be on supply side
Pumps can operate as constant or variable flow.
Pumps can run continuously or intermittently.
Single boiler/chiller with NO bypass, use Pump:ConstantSpeed
Boiler/chiller should be constant flow
Pump should be intermittent
Single boiler/chiller with NO bypass, Pump:VariableSpeed
Single boiler/chiller with bypass, Pump:ConstantSpeed
Boiler/chiller can be constant or variable flow
Pump may be intermittent or continuous as long as the bypass can handle the entire pump volume when the boiler is not operating
Multiple branches add more complexity, but it is nothing more than continuity. If the pump is putting out flow then it has to have a branch to flow down whether it is a chiller or a bypass. It can be safer to add the bypass for a simulation. If the active machines require the flow the bypass will be dry. If performing a pressure simulation, and the flow goes through a machine which is off, the pressure drop will be accounted for, but no heat transfer through the machine will be calculated.
If the user designates a pump that is operating continuously, the pump will run regardless of whether or not there is a load. This may have the net effect of adding heat to the loop if no equipment is turned on. If the pump operates intermittently, the pump will run at its capacity if a load is sensed and will shut off if there is no load on the loop. If the pump is scheduled, the schedule modifies the Rated Volumetric Flow Rate of the pump on a time basis. The default is that the pump is ON and runs according to its other operational requirements.
Shown below is pseudo code for the calculation of the total efficiency of the pump and the actual pumping efficiency when the motor efficiency is accounted for either variable or constant volume pumps.
! Total Efficiency % = Rated Volume Flow Rate * Rated Pump Head / Rated Power Use
TotalEffic = PumpEquip(PumpNum)%NomVolFlowRate * &
PumpEquip(PumpNum)%NomPumpHead / &
PumpEquip(PumpNum)%NomPowerUse
! Calculated Pump Efficiency % = Total Efficiency % / Motor Efficiency %
PumpEquip(PumpNum)%PumpEffic = TotalEffic /
PumpEquip(PumpNum)%MotorEffic
Dynamic Pump Pressure Head[LINK]
There is an option when performing plant/condenser loop simulations to account for dynamically changing loop pressure drop. For the current implementation, the loop pressure drop is calculated based on pressure drop data on each branch of the loop, then this total pressure drop is set as the pump pressure head. There is no pump curve implemented yet, so it is assumed that the pump can always handle this pressure value. This is a first approximation to actually having the pump ride a curve, and this initial implementation allows the user to enter minimal data, and yet get a more dynamic output for pump power, which is calculated based on current pressure drop and flow rate. The equation for pump power is now:
\[Pump~Electric~Power = Pump~Volume~Flow~Rate*\frac{{Pump~Head}}{{Total~Efficiency}}\]
Without the pressure simulation, the pump power is based on the rated value entered with the pump object. For further information, see the input-output reference for Branch objects, and PlantLoop/CondenserLoop objects; as well as the Plant/Condenser loop section of this engineering reference.
Variable Speed Pump[LINK]
A variable speed pump (object name: Pump:VariableSpeed) is defined with maximum and minimum flow rates that are the physical limits of the device. The pump will operate and select a flow somewhere between the minimum and maximum limits. In the case where the pump is running, the pump will try to meet the flow request made by demand side components.
All of the pump rules and efficiency and power calculations are applicable from the introduction in the pump group section. The main difference between the the variable volume pump and the constant volume pump is the Part Load Performance Curve.The fraction of full load power is determined by the cubic equation:
\[FractionFullLoadPower = {C_1} + {C_2}PLR + {C_3}PL{R^2} + {C_4}PL{R^3}\]
where C\(_{1}\),C\(_{2}\),C\(_{3}\),and C\(_{4}\) are Coefficients 1 – 4 and PLR is the Part Load Ratio. In the pseudo code below, the FracFullLoadPower modifies the NomPowerUse for the total pump “Power” and shows the “ShaftPower” and the “PumpHeattoFluid”.
VolFlowRate = PumpMassFlowRate / LoopDensity
PartLoadRatio = VolFlowRate / PumpEquip(PumpNum)%NomVolFlowRate
FracFullLoadPower = PumpEquip(PumpNum)%PartLoadCoef(1) &
+ PumpEquip(PumpNum)%PartLoadCoef(2) * PartLoadRatio &
+ PumpEquip(PumpNum)%PartLoadCoef(3) * PartLoadRatio**2 &
+ PumpEquip(PumpNum)%PartLoadCoef(4) * PartLoadRatio**3
Power = FracFullLoadPower * PumpEquip(PumpNum)%NomPowerUse
ShaftPower = Power * PumpEquip(PumpNum)%MotorEffic
! This adds the pump heat based on User input for the pump
! We assume that all of the heat ends up in the fluid eventually since this is a closed loop
! PumpHeattoFluid = ShaftPower*(1-PumpEquip(PumpNum)%PumpEffic)
PumpHeattoFluid = ShaftPower + (Power - ShaftPower) &
*PumpEquip(PumpNum)%FracMotorLossToFluid
Node(OutletNode)%Temp = Node(InletNode)%Temp &
+ PumpHeattoFluid/(PumpMassFlowRate * LoopCp)
PumpEquip(PumpNum)%Power = Power
Pressure-based Flow for Variable Speed Pumps[LINK]
With the introduction of pressure simulations in plant loops, the variable speed pump object now has the capability to model a more realistic variable speed operation. There are two operation modes which are introduced: differential pressure control is a widely used VFD control method while most VFDs also have a manual control mode in which the user determines the input frequency of the electric motor. The mode can be selected as ‘ManualControl’ or ‘PressureSetpointControl’ in the VFD Control Type input in Pump:VariableSpeed objects.
In manual VFD control mode the specified schedule will determine the current pump rotational speed throughout the simulation. This RPM value will be used to scale the pump curve which is entered by the user in non-dimensional form. Once the pump curve has been fixed then the successive substitution method will use this curve with the system curve to resolve the operating point. VFD manual control mode is implemented in EnergyPlus with the use of the RPM schedule input.
Differential pressure based control will maintain the differential pressure within the specified range. The pressure drop corresponding to the mass flow request will be calculated using the effective pressure constant of the system. This pressure drop will be checked against the pressure set point range. If the pressure drop is within the user specified range, then the mass flow rate will be checked against mass flow rates of operating points corresponding to maximum and minimum rotational speeds. Maximum and minimum differential pressure and rotational speeds are schedule inputs and can be entered as constant schedule.
The allowable mass flow rate range for the Differential pressure control is explained in the Figure [fig:allowable-mass-flow-rate-range-for].
Constant Speed Pump[LINK]
The operation of a constant speed pump (object name: Pump:ConstantSpeed) is fairly straightforward. The user designates a maximum flow rate and when this pumpo operates it will run at that capacity. The main difference between the constant speed pump and the variable speed pump is that the fraction of full load power is always = 1. In the pseudo code below, the FracFullLoadPower is = 1.0, therefore the Power is always the full power.
VolFlowRate = PumpMassFlowRate / LoopDensity
PartLoadRatio = VolFlowRate / PumpEquip(PumpNum)%NomVolFlowRate
FracFullLoadPower = 1.0
Power = FracFullLoadPower * PumpEquip(PumpNum)%NomPowerUse
ShaftPower = Power * PumpEquip(PumpNum)%MotorEffic
! This adds the pump heat based on User input for the pump
! We assume that all of the heat ends up in the fluid eventually since this is a closed loop
! PumpHeattoFluid = ShaftPower*(1-PumpEquip(PumpNum)%PumpEffic) &
PumpHeattoFluid = ShaftPower + (Power - ShaftPower) &
* PumpEquip(PumpNum)%FracMotorLossToFluid
Node(OutletNode)%Temp = Node(InletNode)%Temp &
+ PumpHeattoFluid/(PumpMassFlowRate * LoopCp)
PumpEquip(PumpNum)%Power = Power
Pressure-based Flow for Constant Speed Pumps[LINK]
The constant speed pump can flow can also be overridden dynamically based on a response to the plant loop pressure drop. In “single-loop-pump” simulations (no branch pumps, no common pipe), the user can enter a dimensionless pump curve on the Pump:ConstantSpeed (see I/O ref) object which represents the single speed pressure-flow relationship of the pump. In the process of determining the operating flow rate for the pump, the pump will check to see if a valid pressure simulation is being performed. If it is, a flow will be prescribed based on a resolution between system pressure characteristics and the pump pressure curve. This will cause the pump flow to be “unpredictable,” meaning that it will not always be a constant, expected value, which is basically what the constant speed pump gives you without the pressure simulation. There is more detail on the pressure based simulation in the Plant/Condenser loop sections of this documentation.
Pump Heat Addition to the Loop[LINK]
Due to the fact that a pump is a mechanical device that acts on the fluid it is circulating, it causes the fluid to increase in temperature. The EnergyPlus model assumes that all pressure increase caused by the pump will eventually be lost due to friction, and that friction will be added as heat to the fluid. Since the plant and condenser loops are not yet true pressure-based models, EnergyPlus assumes that all of the heat resulting from the pump itself and from friction throughout the loop. Therefore, as of version 7, the pump heat is added to the plant loop interface by injecting the heat into the mixed tanks used to model loop thermal capacitance(previously it was added at the outlet node of the pump). The amount of heat added to the fluid is calculated using the following two equations:
\[ShaftPower = PumpPower * PumpMotorEfficiency\]
\[PumpHeatToFluid = ShaftPower + \left( {PumpPower - ShaftPower} \right) * FracMotorLossToFluid\]
where the pump motor efficiency is defined by the user input and the FracMotorLossToFluid is the amount of heat generated by the pump motor that is added to the fluid loop (as opposed to being lost to the environment where the pump is located). FracMotorLossToFluid is also a user input.
Note that the shaft power relates to the increase in head through the pump. Since all of this head is lost through the piping network due to frictional heat, this represents a heat gain by the fluid throughout the network. For simplicity, this heat is added along with the heat resulting from the pump motor. The difference between the pump power and the shaft power is the inefficiency of the pump—or the amount of energy input into the pump that the motor converts to heat rather than mechanical energy. Some of this heat is added to the fluid being pumped. These two terms are shown in the PumpHeatToFluid equation shown above. Since EnergyPlus Version 7, this heat is added to the loop capacitance tank(s) rather than at the pump’s outlet and so the outlet temperatue is equal to the inlet temperaure.
Pump Heat Addition to Surrounding Zone[LINK]
If the user input includes naming a Zone that surrounds the pump, then the pump becomes a source of internal heat gain to that zone. The amount of heat transmitted to the surrounding zone is simply the difference between power input and the rate of heat transferred to the fluid. The user can also input a fraction, \({f_{rad}}\), that controls the overall split between thermal radiation and sensible convection. The pump’s sensible zone gains are determined using the following equations:
\[TotalZoneGain = PumpPower - PumpHeatToFluid\]
\[ConvectiveZoneGain = \left( {1 - {f_{rad}}} \right)*TotalZoneGain\]
\[RadiativeZoneGain = {f_{rad}}*TotalZoneGain\]
Headered Pumps[LINK]
The input objects HeaderedPumps:ConstantSpeed and HeaderedPumps:VariableSpeed provide models for headered pumps that consist of two or more pumps connected in parallel. The headered pump is simulated as a single component, and it is specified as an integer number of a specific pump. The flow rate provided by the headered pump is determined by the number of pumps in operation and the flow rate of the individual pump. The total flow rate is calculated as
\[FlowProvided = NumPumpsON*IndividualPumpFlowRate\]
The simulation starts by turning ON all pumps in the group. The pumps are then turned OFF one at a time until the flow provided is less than the flow requested. Finally the last pump is turned back ON to meet the remaining flow (FlowDifference) requested. The flow rate of the last pump depends on the pump bank type. For constant speed headered pumps, the last pump runs at the nominal flow rate, thereby giving a final headered pump flow which is equal to or greater than the flow requested. In a variable speed headered pump the last pump runs at part load so that the flow provided matches the flow requested. The power of the headered pump is then calculated as
\[Power = (P{R_{FL}}{\rm{*N}}{}_{{\rm{FL}}} + {\rm{P}}{{\rm{R}}_{{\rm{PL}}}}{\rm{*}}{{\rm{N}}_{{\rm{PL}}}}{\rm{)*}}{{\rm{P}}_{{\rm{Nom}}}}{\rm{ }}\]
where:
Power is the power consumed by the pump bank
PR\(_{FL}\) is the power ratio at full load (generally equal to 1)
N\(_{FL}\) is the number of pumps running at full load
PR\(_{PL}\) is the power ratio at part load
N\(_{PL}\) is the number of pumps running at part load
P\(_{Nom}\) is the nominal power consumption of individual pumps.
For a constant speed headered pump, N\(_{PL}\) is zero. For a variable speed headered pump, N\(_{PL}\) is equal to one.
Condensate Pumps[LINK]
The input object Pump:VariableSpeed:Condensate provides a model for steam condensate pumps, see the discussion for steam loops, reference: Condensate Pump.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.