A steam system uses the vapor phase of water to supply
enthalpy or kinetic energy through the piping network. In
case of EnergyPlus, the steam system is designed to provide
energy solely for the building heating requirements. Hot
steam from the boiler or steam generator in buildings can be
used to heat a conditioned space with suitable heat transfer
equipment such as fan-coils units, unit-heaters, radiators and
convectors or steam can also heat water through shell and tube
heat exchangers, and hot water can be supplied to the terminal
units to provide the zone heating requirements.
The advantages that steam system offer over hot water or
other heating systems are:
Steam flows through the system unaided by external
energy source such as pumps; pressure difference moves steam
across the system.
Steam, because of its low-density, can be used in
high-rise buildings where water systems create excessive
pressure.
Terminal units such as heating coils can be added or
removed without making any changes to the system.
Steam components can be repaired or replaced by closing
the steam supply without the difficulties associated with
draining and refilling like in the water systems.
Steam is pressure-temperature dependent, therefore the
system temperature can be controlled by varying either steam
pressure or temperature.
Steam can be distributed through out the system without
any change in temperature.
In view of the advantages mentioned, the steam systems are
suitable for applications where heat is required for process
and comfort heating such as in industrial plants, hospitals,
restaurants, dry cleaning plants laundries and commercial
buildings. They are also suitable in places where the heating
medium has to travel great distances such as in facilities
with scattered building locations or where the building height
would result in excessive pressure in a water system, or
locations where the load changes occur intermittently. Thus
steam system is an essential and necessary development step
for EnergyPlus.
From EnergyPlus simulation point of view, the advantage
associated with a steam system is that steam can be
distributed through out the system without change in
temperature. This means that the boiler outlet temperature
can simply be set equal to the heating coil inlet temperature
for a steam system.
Another simulation-based advantage associated with the
steam system is Steam Quality, which does not change from
boiler outlet to coil inlet. Actual building steam systems
are equipped with condensate drains through out the system,
these drains remove, almost immediately any condensate that is
formed during steam transportation, thereby maintaining the
steam quality at constant value of 1.0 through out the
high-pressure steam side.
The HVAC steam system implementation includes simulation
models for two phase steam equipment like steam boiler, steam
to air heating coils, steam pipes and condensate pumps, which
can be connected to the generic loop framework.
To replicate the working of an actual building steam system
in a satisfactory manner with simulation, it was necessary to
make certain assumptions. These assumptions help simplify the
loop complexity and increase usability. The effects of the
assumptions made are described in detail below.
The following figure describes the Temperature Entropy Ts
diagram based on which the steam system operates in
EnergyPlus. The steam side of the loop operates on constant
saturation pressure of steam: PSteam, the waterside of the
loop operates at atmospheric pressure Patm.
Schematic of Temperature –
Entropy Diagram for Steam loop [fig:schematic-of-temperature-entropy-diagram-for]
It should be noted that the figure is simply a schematic
and not a scaled representation of the process on a Mollier
Chart. For the following descriptions, please refer to the
schematic figure above.
Process 1–2 on the Ts diagram, represents condensation
of steam in the coil at constant pressure; this is where the
steam gives up latent heat to the zone.
Process 2–3 represents the subcooling of condensed
steam at higher pressure, this subcooling takes place inside
the steam coil, just before the steam trap. The delta
temperature represented by 2-3 is the degree of subcooling in
the steam coil, and is a user input to the steam coil. This
subcool generally accounts for 1 to 2% of the total heat
transfer in the steam coil.
Process 3–4’ represents the isenthalpic expansion of
water from high-pressure steam side to atmospheric pressure
across the steam trap. As steam gives up its latent heat at
the steam coil the condensate that forms in the steam coil
still exists at higher pressure. This condensate is
discharged to a lower pressure across the steam trap, this
condensate contains more heat than necessary to maintain the
liquid phase at the lower pressure, this excess heat causes
some of the condensate to vaporize or flash to steam at lower
pressure at some quality. The amount of water that flashes to
steam can be calculated by the following equation
Where h4’ is Enthalpy of liquid at steam pressure just
before condensate is supposed to leave the coil. Enthalpy at
Point 3 is equal to enthalpy at point 4’, since it is an
isenthalpic process, and hfg is the latent enthalpy of the
fluid at atmospheric pressure.
For example, water at 102\(^{\circ}\)C and 120 Kpa flashes
to steam at 100\(^{\circ}\)C
and atmospheric pressure, with quality equal to 0.003. This
results in loss of some latent capacity of steam and is one of
the terms contributing to loop loss in steam system.
Process 4’- 4 represents the condensation of the
flashed steam, which has exited from steam trap into the
condensate drain. Condensation occurs at atmospheric pressure
Patm, there is loss in latent capacity due to this unavoidable
process, only condensate can be returned back to the boiler in
a steam system.
Process 4-5 represents the loop sub cooling at
atmospheric pressure; this is the sub cooling of the
condensate that takes place during condensate return to the
boiler because the return loop is not insulated, loop sub
cooling is of the order of 20\(^{\circ}\)C to 30\(^{\circ}\)C. This is a
user-defined input in every steam coil, because the
variability in location of steam coils in a building will
result in different condensate return temperatures for each of
the coils.
Process 5-6 represents the temperature and pressure
rise in condensate due to pump heat addition. The pumping
process generates heat, which is added to the condensate. The
condensate is pumped back to the boiler at higher
pressure.
Process 6-2 represents the sensible heat addition by
the boiler to the return condensate.
Process 2-1 represents the latent enthalpy of steam,
added by the boiler to the water to convert it to steam at
saturation pressure.
Point 3, which is outlet of the coil and Point 5,
which is inlet of the pump are specified directly by the user,
subsequently the loop losses in EnergyPlus are directly summed
up as the enthalpy difference between point 3 and 5, which is
calculated by fluid property routines in EnergyPlus. This
helps to maintain flexibility and at the same time helps
negate the intermediate points calculation in the
system.
Aspects of the steam loop such as quality of steam, steam
pressure, and steam generation which play an important role in
EnergyPlus simulation are described in following sections.
The steam loop in EnergyPlus is pressure driven and it is
assumed to operate at constant pressure on the gaseous-steam
part, while the condensate return loop is assumed to operate
at atmospheric pressure. The steam loop essentially operates
at saturation pressure corresponding to the steam temperature;
the steam boiler serves to maintain the loop temperature. The
boiler model determines the amount of energy required to
generate the required amount of steam.
Factors such as friction in pipes, which tend to cause
small amount of pressure drop in steam loop are neglected in
the model. It is assumed that the steam pipes are fairly well
insulated to prevent heat loss and subsequent condensation of
steam in the pipes. In actual systems small quantities of
steam, which condenses due to heat loss during transportation
is removed immediately from the system by steam drains. This
helps eliminate water hammer, degradation of steam quality and
heat transfer capability.
Building
steam heating systems avoid supplying superheated steam
because superheat damages the building HVAC equipment.
Superheated steam is generated only if there is a cogeneration
power system in building such as steam turbine, which requires
superheated steam. The purpose of having superheated steam is
redundant for building steam heating systems because the
amount of energy carried by the same is negligible compared to
the latent heat. A simple enthalpy calculation, based on each
unit of steam mass flow rate (1 kg/s), has been provided in
this section to describe the negligible effect of
superheat..
Case 1: Loop Operating at Saturation Conditions (no
superheat), calculating enthalpy of saturated steam at boiler
outlet temperature.
The energy difference between the superheated state and the
saturated state as calculated in the following equation. A
5\(^{\circ}\)C superheat
provides only a 0.2608% increase in heat transfer. The
advantage of this additional increase in heat transfer is
negligible, especially when considering the economic aspect of
sizing a bigger heat exchanger to accommodate additional
superheat transfer. The detrimental effects of superheated
steam on the building HVAC system also come into effect once
superheat is used.
The boiler operation is assumed capable to generate steam
at quality equal to1.0 every time. This is a reasonable
assumption, since in practice the variability in generated
steam quality would only occur if the boiler operation were
not properly controlled.
The steam loop is assumed to have perfect transport
mechanism. There is no transportation losses due to friction
and heat transfer with surroundings. This assumption helps
maintain the quality of steam through out the system constant
value of either 0 or 1.
Steam enters the coils at boiler outlet conditions. Steam
coils are designed with steam traps, which only allow
condensed steam to leave the coil; hence the steam always
condenses and leaves the coil at quality of 0.0.
With the above simplifying assumption enables the
EnergyPlus steam loop to be solved without problems.
Steam traps are essential part of the steam system; they
are indirect flow controllers of the loop. Purpose of steam
trap is to allow only condensate out of the coil from
higher-pressure steam to lower atmospheric pressure condensate
return line. Points 3-4’, in schematic Figure [fig:schematic-of-temperature-entropy-diagram-for],
represent this process across the steam trap on the Ts
diagram. The expansion process across the steam trap is
assumed to be isenthalpic. There is possibility of flashing
of high-pressure condensate across the trap because of
pressure drop, resulting in generation of steam at lower
pressure, this steam generated at lower pressure subsequently
condenses in the return piping, and heat is lost to the
atmosphere. This heat lost is a part of the steam loop
losses.
Steam traps are modeled in the EnergyPlus steam coil by
assigning the condensate outlet from the coil a quality of 0.0
and sub cooling the condensate at lower pressure.
Although condensate from the steam coil contains valuable
heat, attempting to utilize this heat by holding the
condensate in the coil reduces the heat transfer area. It
causes operational problems because it retains air, which
further reduces heat transfer and non-condensable gases such
as carbon dioxide, which cause slow corrosion of the steam
coil. Steam moves rapidly in mains and supply piping so when
condensate accumulates to the point where the steam can push a
slug of it, serious damage can occur from the resulting water
hammer, hence the condensate should be immediately removed
from the steam coil. This is achieved with steam traps.
Hence an ideal steam trap should remove all condensate,
air, and non-condensable gases that might be in the system,
with little or no loss of steam.
Subcooling of condensate in condensate return piping and
flash steam condensing across the steam trap constitute the
unavoidable loop losses in the EnergyPlus simulation steam
system. These losses can be inferred from Figure [fig:schematic-of-temperature-entropy-diagram-for]
and are summed up by calculating enthalpy difference between
points 3 and 5 on the schematic Ts diagram.
Unavoidable losses in the EnergyPlus steam loop occur due
to pressure drop across the steam trap, which causes flashing
of steam and loss in some percentage of latent heat of steam,
process 3-4’ and 4’-4 on the Ts diagram in Figure [fig:schematic-of-temperature-entropy-diagram-for].
The condensate is pumped backed to the boiler through return
pipe network, which is not insulated. Sub cooling of the
condensate occurs in the return network, represented by
process 4-5 on the Ts diagram in Figure [fig:schematic-of-temperature-entropy-diagram-for].
This loop sub cool contributes to significant percentage of
loop losses.
In practical systems the return pipeline to the boiler is
not insulated despite the condensate containing some valuable
heat, however due to low mass flow rate of steam, this amount
is negligible and only recovered if separate heat recovery
systems are used by coupling them to the loop. The condensate
is occasionally collected in a receiver and then pumped back
to the boiler. EnergyPlus simulation mimics practical systems
by assumed that the return pipeline is not insulated and
accounts for this by calculating loop losses.
The loop losses are calculated in the steam coil simulation
model rather that the steam pipe simulation, because the
condensate sub cool in the return loop is a direct function of
the location of the steam coil in the building. In building
energy software like EnergyPlus the user would have a fair
idea about location of steam coils rather than the location of
condensate return piping.
The steam to air heat exchanger (Coil:Heating:Steam input
object) is the terminal equipment in the steam loop on the
demand side that satisfies the heating requirements of the
various zones. The steam-to-air heat exchanger simulation
model in EnergyPlus calculates the mass flow rate of steam
desired to meet the heating demand.
A heating coil can be used either as a zone coil or a coil
in the air loop depending on the user and application. The
steam coil simulation model is designed to take these two
locations into consideration. An air-loop steam heating coil
is temperature controlled and the zone coil is zone load
controlled. This relatively simple and straightforward
concept of coil control is preferred over the iterative method
to determine mass flow rates using various numeric
techniques. The assumptions made in the coil model are
described in the section below.
This model accounts for the latent heat transfer and
sensible cooling of water; the question of superheat is
eliminated because steam is assumed to be saturation
conditions. Steam enters the coil at quality equal to 1.0, at
saturation temperature and leaves the coil with desired degree
of sub cooling. The user inputs the desired degree of
subcooling, which determines the condensate outlet condition
from the coil.
EnergyPlus heat balance methods determine the amount of
heating required in the zone to maintain the zone at the
desired conditions. Based on this value of heating load, the
zone coil determines the mass flow rate of steam required
since the heating coil load is the control variable in a zone
coil. The following equation describes this calculation to
determine steam mass flow rate required for the desired
heating capacity. The steam latent heat of vaporization,
h\(_{fg}\) and the
condensate heat capacity, C\(_{p,w}\) are evaluated at the
steam coil inlet node temperature and standard barometric
pressure of 101325.0 Pa.
In case of the air loop-heating coil, the load on the coil
is calculated within the coil simulation routine. The air
loop coil is setpoint controlled and heats the air to maintain
the air stream at the desired setpoint, the setpoint is a user
input, generally in the range of 12\(^{\circ}\)C to 16\(^{\circ}\)C. The following
equation describes the air loop coil load.
Each of the zone coils and air loop coils are simulated
independently and the steam mass flow rates for each is added
over every time step of simulation. This value of total mass
flow rate is reported to the boiler, which in turns supplies
this required amount of steam.
The control of the steam to air coil is a complex issue.
The loop splitter-splits total steam flow from the boiler and
delivers the required amount of steam to each of the coils
connected to the loop through the steam pipe network. In
cases where the system is undersized, the coils demand more
mass flow rate of steam than the boiler can generate. The
splitter in this case cannot provide all the coils with
requested steam mass flow. Subsequently the coils are starved
of steam and the zone temperatures fall. In some cases the
user might schedule off the coil, they should then not
operate. These issues need to be taken care of in the
implementation of the steam coil simulation model. The
control algorithm for the steam coil operation under various
situations is best explained with the help of pseudo-code
using standard IF THEN ELSE blocks.
Check for operational conditions only then continue
simulation further. The operational conditions are the inlet
mass flow rates of steam and air to the coil, the user
schedule to the coil and heating load on the coil. The coil
is simulated only if these conditions are met.
If the heating demand from the zone-heating coil is greater
than coil capacity, then the heating coil is undersized, and
the coil can only deliver its maximum heating capacity to the
zone. In this case the heating demand on the coil is set
equal to this lower value of maximum heating capacity. If the
above is not true then the simulation ignores this statement
and proceeds to the next one.
The following equation calculates the steam mass flow rate
required by the coil. This flow rate is required to meet the
heating requirements for the zone. This value of mass flow is
requested from the splitter outlet.
If the calculated value of steam mass flow with the
previous equation is greater than the maximum inlet steam flow
that the splitter can provide to the coil at that time step.
Then the requested coil flow rate is set equal to the inlet
steam flow rate. This is the maximum amount of steam that can
be supplied to the coil at this moment. The coil can provide
heating capacity equal to this limited amount of steam. If
the requested flow rate is less that what the splitter can
provide then the program ignores the logic of the IF Loop
Below
The following equations calculate the outlet
condensate-water and outlet air temperatures to the zone based
on the amount of heating capacity provided by the coil.
Check for operational conditions and continue simulation
further. The operational conditions are the inlet mass flow
rates of steam and air to the coil, the user schedule to the
coil and delta temp exists between the setpoint and air inlet
temperature. The coil is simulated only if these conditions
are met.
The logic loop for temperature-controlled coil begins
here. In case the heating load on the coil is negative, which
might occur if the setpoint is below the air inlet
temperature, the coil operation needs to be shut off.
If air loop coil load is greater than maximum coil load
calculated at maximum steam mass flow rate, in such case the
coil is undersized, the coil can only deliver to the air loop
its maximum heating capacity. Setting the air loop coil load
equal to maximum load on coil. If this is not the case then
the program ignores this ELSE IF block and proceeds to the
next one.
If the heating coil is under sized then it can only provide
its maximum heating capacity, in this case the air temperature
will be below the setpoint, and is calculated based on this
maximum allowed value of heat transfer. Calculating the air
and water outlet temperatures.
A check is introduced to determine if this requested mass
flow rate is greater than what the splitter outlet can provide
to the coil at that particular time step of simulation. In
this case the requested value of steam mass flow is greater
that what the splitter can provide to that coil, subsequently
set the requested coil flow rate equal to the inlet steam flow
rate, delivered to the coil by the splitter. This is the
maximum amount of steam that can be supplied to the coil at
this moment. If the requested flow rate is less that what the
splitter can provide then the program ignores the logic of the
IF Loop.
If the above two IF ELSE block are not true, then the coil
is perfectly sized, the splitter can provide the required mass
flow rate to the coil, and the setpoint temperature can be
maintained as desired.
\[ELSE\]
The ideal case where the coils can meet the required
setpoint temperature. Setting the outlet air temperature to
the setpoint, calculating the water outlet temperature and the
required steam mass flow rate.
\(END\,\,IF\) End IF
statement, for the air coil heating loop.
\(END\,\,IF\) End
IF statement for the operating condition loop
\(END\,\,IF\) End IF
statement for the Temperature Setpoint Controlled Coil
The steam coil model encapsulates the above described
control logic along with the other necessary simulation code
for reading the user inputs and the code for reporting the
simulation results.
The two main types of coil control discussed above are
followed by common simulation code in the coil model. This
code calculates the loop losses occurring due to flashing of
steam across the steam trap, isenthalpic expansion occurring
across the steam trap due to pressure difference, and loss
occurring due to condensate sub cooling returning back to the
boiler. The above-mentioned two processes are explained in
Figure [fig:schematic-of-temperature-entropy-diagram-for]
as process 3-4’ and 4-5.
The loop loss calculation is included in the steam coil
simulation model, because the degree of subcooling in the
return piping for the condensate is solely a function of the
coil location. In practical applications a coil, which is
further away from boiler would return back condensate at much
lower temperatures compared to coil, which is closer to
boiler. Hence for user ease it makes perfect sense to include
this input into the coil and calculate the pump inlet
conditions in the steam coil simulation model itself.
The loop losses in the EnergyPlus steam system is
calculated by determining the enthalpy difference between
point 3 and 5. The simulation code that determines the loop
loss is common to both the coil models, this helps determine
the condensate pump inlet conditions.
The following equation is used to calculate condensate
enthalpy at coil outlet, point 3 in Figure [fig:schematic-of-temperature-entropy-diagram-for].
Point 2 represents condensed steam; enthalpy at this point is
calculated directly by EnergyPlus property routines.
Point 4 is at atmospheric pressure, enthalpy at this is
calculated directly by EnergyPlus property routines. It is
saturation enthalpy of steam at quality equal to 0.0 and
saturation temperature at atmospheric pressure.
Point 5 is inlet to the pump; enthalpy at this point is
calculated with the following equation The delta temperature
represents the degree of loop subcooling occurring during
condensate return back to the pump.
The total loop loss would be a summation of the individual
losses occurring for each of the steam coils, this is the
unavoidable loss in current steam system.
A simple schematic describing the coil framework, inlet and
outlet conditions to the coil and the flow rate resolution is
shown in Figure [fig:schematic-of-steam-coil-connection-to].
Five zone coils and one air loop coil are described in the
picture, Qzone is calculated by EnergyPlus heat balance and it
is the input to the zone coils, while in air loop coil the Qal
is calculated within the simulation model
Schematic of Steam Coil
Connection to the Steam Loop [fig:schematic-of-steam-coil-connection-to]
As depicted in the figure above the steam condenses on
entering the coils, sub cools by the specified amount and
leaves the heat exchanger as water. The steam in the heat
exchanger at any moment has to condense eventually since steam
trap at the outlet to coil permits only water to leave the
coil. Steam traps being an essential part of the loop are
modeled by controlling the coil outlet condition at quality
equal to 0.0. Subsequently the amount of heat transferred to
air is a direct function of latent heat and the degree of sub
cooling desired by the user.
The steam coils works on two basic assumptions, firstly,
it’s assumed that perfect latent heat transfer takes place
over every time step, secondly, the user specified degree of
subcooling occurs in the coil. Steam coils always use steam
traps- purpose of which is to only let water out of the coil,
hence the modeler knows with certainty the outlet dryness
faction of steam coil is at quality equal to 0.0, because
water leaves coil. Hence the heat transfer is equal to latent
heat of steam, which is independent of UA value of coil when
averaged over time step of EnergyPlus simulation.
In practice there is 1% to 2% sub cooling of the outlet
water stream, the user with desired degree of subcool input
accounts for this, subsequently UA calculation for the coil
model become superfluous and is neglected in the EnergyPlus
model.
Ideally for sub-cooling UA would play an important role,
however sub cooling in steam coil constitutes negligible
amount of heat transfer, hence this model avoids the UA
calculation. This is a very reasonable assumption since
sensible heat transfer is barely 1% to 2% of the total heat
transfer in steam coils, simply due to large latent heat
capacity of coil. NOTE in his thesis he gives a little example
here which is probably not necessary for the Docs.
The steam loop operates at a pressure differential over the
gaseous and liquid part of the loop; subsequently a condensate
pump is required to pump the condensed steam back to the
boiler at the required pressure. Two main reasons for
condensed steam to be returned to the boiler is energy savings
in reheating water since the water is at high temperature,
secondly the water is treated by chemicals to prevent
corrosion in the pipes and equipment. This is an expensive
process and therefore it’s economical to reuse the chemically
treated water.
The pump model designed in EnergyPlus is a variable speed
condensate pump. Condensation of steam produces water, this
takes place at variable rate hence the return water flow rate
would be variable but constant when averaged over a time
step. Condensate pumps operate intermittently; the pump will
run at its capacity if a load/flow rate is sensed and will
shut off if there is no load on the loop.
The condensate pump essentially operates between maximum
and minimum flow rates, which are the physical limits of the
device. The pump is designed to meet the flow request made by
demand side components, which are the coils in case of steam
system.
The main difference between the variable volume pump and
the constant volume pump is the Part Load Performance Curve.
The fraction of full load power is determined by the third
order equation, which follows:
In preceding equation, PLR stands for part load ratio while
C1 to C4 are pump- part load coefficients. The following five
equations describe the pump operation and calculation of pump
output variables such as total power, shaft power and pump
heat to fluid etc.
Using the previous equation the pump volume flow rate is
determined; the user enters the value of the maximum and
minimum volume flow rate.
The pump part load ratio is a function of the pump volume
flow rate at any instance determined by the loop and the pump
nominal volume flow rate, which is a user input. The
following equation calculates the Part Load Ratio (PLR).
\[PLR = \,\frac{{\dot
V}}{{{{\dot V}_{nom}}}}\]
The pump power is calculated as described in following
equation. Pump power is a product of fractional full load
power and pump nominal power use. Fractional full load power
is calculated in a preceding equation while pump nominal power
is a user input to the model.
\[P = {P_{Frac}} \times
{P_{Nom}}\]
The shaft power is simply the product of the pump power and
motor efficiency, this is required to calculate the heat
generated and delivered to the fluid being pumped. The
following equation is used to calculate pump shaft power.
The model assumes that all heat generated and lost ends up
in the fluid to the loop, this assumption is necessary since
EnergyPlus operates on a closed loop. The following equation
is used to calculate the pump heat to the fluid, which raises
the condensate temperature. The pump motor efficiency is
defined by the user input and the fractional motor loss to
fluid is the amount of heat generated by the pump motor that
is added to the fluid loop (as opposed to being lost to the
environment where the pump is located). FracMotorLossToFluid
is also a user input
The shaft power relates to the increase in head through the
pump to the loop operating pressure. The head lost through
the piping network due to frictional heat, represents the heat
gain by the fluid throughout the network. . For model
simplicity, this heat is added along with the heat resulting
from the pump motor. The difference between the pump power
and the shaft power is the inefficiency of the pump, or the
amount of energy input into the pump that the motor converts
to heat rather than mechanical energy. Some of this heat is
added to the fluid being pumped. These two above-mentioned
terms are used in the PumpHeatToFluid equation for calculating
P\(_{H}\) shown above.
A simple energy balance over the pump based on the pump
inlet conditions and flow rate is used to calculate the pump
outlet temperature. The condensate outlet temperature from
the pump is slightly higher than inlet due to the heat
dissipation to the fluid steam during pumping action. This is
calculated in the following equation. The pump water outlet
temperature is the boiler inlet temperature.
Pump control is an important part of the steam loop.
Existing control structure from EnergyPlus has been utilized
to operate the condensate pump. The pump is simulated first
on the supply side of the loop after the demand side loop has
determined what the demand on the loop will be.
A simple schematic describing the flow across the pump is
shown in the following figure
Schematic of Condensate Pump in
Steam Loop [fig:schematic-of-condensate-pump-in-steam-loop]
Due to the fact that a pump is a mechanical device that
acts on the fluid it is circulating, it causes the fluid
temperature rise. The EnergyPlus model assumes that all
pressure increase caused by the pump will eventually be lost
due to friction, and that friction will be added as heat to
the fluid. Although the plant and condenser loops in steam
systems are simple pressure-based models, a simplifying
assumption has be made in EnergyPlus to assume the heat
resulting from the pump itself and from friction throughout
the loop is added at the fluid being pumped. In case of
steam, this assumption is easily justified because the volume
flow rate of water is very small in the loop.
The steam pipe essentially serves as “energy carrier” and
transfers the node conditions from one point of the pipe to
another. It’s simply a node inlet to node outlet connection,
transferring values from inlet to outlet. The pipe forms an
important part of the framework connecting various equipments
from the supply to demand side and inlet and outlets of the
equipments.
The steam pipe supports two additional properties, which
are pressure and quality, unlike its water counterpart. Pipe
simulation model in EnergyPlus is hardwired to water as a
fluid type; this necessitated the development of similar model
supporting pressure and quality for the steam system.
The piping network in the developed steam system is assumed
to perfectly distribute steam, return the condensate, and
remove air and non-condensable gases. It is also assumed that
the pipes are sized to distribute steam not only at full load
but also at partial loads and excess loads that can occur
during system warm up.
The steam pipe is perfect and there is no losses occurring
in transportation. This assumption was necessitated since if
pipe losses were accounted for, the loss would have to be
distributed into the zone, which would be a very complex issue
in itself, since in EnergyPlus the pipes are unaware of their
locations and simply serve as connectors.
Steam Systems and Component Models[LINK]
A steam system uses the vapor phase of water to supply enthalpy or kinetic energy through the piping network. In case of EnergyPlus, the steam system is designed to provide energy solely for the building heating requirements. Hot steam from the boiler or steam generator in buildings can be used to heat a conditioned space with suitable heat transfer equipment such as fan-coils units, unit-heaters, radiators and convectors or steam can also heat water through shell and tube heat exchangers, and hot water can be supplied to the terminal units to provide the zone heating requirements.
The advantages that steam system offer over hot water or other heating systems are:
Steam flows through the system unaided by external energy source such as pumps; pressure difference moves steam across the system.
Steam, because of its low-density, can be used in high-rise buildings where water systems create excessive pressure.
Terminal units such as heating coils can be added or removed without making any changes to the system.
Steam components can be repaired or replaced by closing the steam supply without the difficulties associated with draining and refilling like in the water systems.
Steam is pressure-temperature dependent, therefore the system temperature can be controlled by varying either steam pressure or temperature.
Steam can be distributed through out the system without any change in temperature.
In view of the advantages mentioned, the steam systems are suitable for applications where heat is required for process and comfort heating such as in industrial plants, hospitals, restaurants, dry cleaning plants laundries and commercial buildings. They are also suitable in places where the heating medium has to travel great distances such as in facilities with scattered building locations or where the building height would result in excessive pressure in a water system, or locations where the load changes occur intermittently. Thus steam system is an essential and necessary development step for EnergyPlus.
From EnergyPlus simulation point of view, the advantage associated with a steam system is that steam can be distributed through out the system without change in temperature. This means that the boiler outlet temperature can simply be set equal to the heating coil inlet temperature for a steam system.
Another simulation-based advantage associated with the steam system is Steam Quality, which does not change from boiler outlet to coil inlet. Actual building steam systems are equipped with condensate drains through out the system, these drains remove, almost immediately any condensate that is formed during steam transportation, thereby maintaining the steam quality at constant value of 1.0 through out the high-pressure steam side.
The HVAC steam system implementation includes simulation models for two phase steam equipment like steam boiler, steam to air heating coils, steam pipes and condensate pumps, which can be connected to the generic loop framework.
Steam Loop Assumptions[LINK]
To replicate the working of an actual building steam system in a satisfactory manner with simulation, it was necessary to make certain assumptions. These assumptions help simplify the loop complexity and increase usability. The effects of the assumptions made are described in detail below.
The following figure describes the Temperature Entropy Ts diagram based on which the steam system operates in EnergyPlus. The steam side of the loop operates on constant saturation pressure of steam: PSteam, the waterside of the loop operates at atmospheric pressure Patm.
It should be noted that the figure is simply a schematic and not a scaled representation of the process on a Mollier Chart. For the following descriptions, please refer to the schematic figure above.
Process 1–2 on the Ts diagram, represents condensation of steam in the coil at constant pressure; this is where the steam gives up latent heat to the zone.
Process 2–3 represents the subcooling of condensed steam at higher pressure, this subcooling takes place inside the steam coil, just before the steam trap. The delta temperature represented by 2-3 is the degree of subcooling in the steam coil, and is a user input to the steam coil. This subcool generally accounts for 1 to 2% of the total heat transfer in the steam coil.
Process 3–4’ represents the isenthalpic expansion of water from high-pressure steam side to atmospheric pressure across the steam trap. As steam gives up its latent heat at the steam coil the condensate that forms in the steam coil still exists at higher pressure. This condensate is discharged to a lower pressure across the steam trap, this condensate contains more heat than necessary to maintain the liquid phase at the lower pressure, this excess heat causes some of the condensate to vaporize or flash to steam at lower pressure at some quality. The amount of water that flashes to steam can be calculated by the following equation
\[\% Flash\,\,Steam\,\, = \frac{{{h_{4'}} - \,{h_4}}}{{{h_{fg}}}}\,\, \times \,\,\,100\]
Where h4’ is Enthalpy of liquid at steam pressure just before condensate is supposed to leave the coil. Enthalpy at Point 3 is equal to enthalpy at point 4’, since it is an isenthalpic process, and hfg is the latent enthalpy of the fluid at atmospheric pressure.
For example, water at 102\(^{\circ}\)C and 120 Kpa flashes to steam at 100\(^{\circ}\)C and atmospheric pressure, with quality equal to 0.003. This results in loss of some latent capacity of steam and is one of the terms contributing to loop loss in steam system.
Process 4’- 4 represents the condensation of the flashed steam, which has exited from steam trap into the condensate drain. Condensation occurs at atmospheric pressure Patm, there is loss in latent capacity due to this unavoidable process, only condensate can be returned back to the boiler in a steam system.
Process 4-5 represents the loop sub cooling at atmospheric pressure; this is the sub cooling of the condensate that takes place during condensate return to the boiler because the return loop is not insulated, loop sub cooling is of the order of 20\(^{\circ}\)C to 30\(^{\circ}\)C. This is a user-defined input in every steam coil, because the variability in location of steam coils in a building will result in different condensate return temperatures for each of the coils.
Process 5-6 represents the temperature and pressure rise in condensate due to pump heat addition. The pumping process generates heat, which is added to the condensate. The condensate is pumped back to the boiler at higher pressure.
Process 6-2 represents the sensible heat addition by the boiler to the return condensate.
Process 2-1 represents the latent enthalpy of steam, added by the boiler to the water to convert it to steam at saturation pressure.
Point 3, which is outlet of the coil and Point 5, which is inlet of the pump are specified directly by the user, subsequently the loop losses in EnergyPlus are directly summed up as the enthalpy difference between point 3 and 5, which is calculated by fluid property routines in EnergyPlus. This helps to maintain flexibility and at the same time helps negate the intermediate points calculation in the system.
Aspects of the steam loop such as quality of steam, steam pressure, and steam generation which play an important role in EnergyPlus simulation are described in following sections.
Constant Pressure Steam loop[LINK]
The steam loop in EnergyPlus is pressure driven and it is assumed to operate at constant pressure on the gaseous-steam part, while the condensate return loop is assumed to operate at atmospheric pressure. The steam loop essentially operates at saturation pressure corresponding to the steam temperature; the steam boiler serves to maintain the loop temperature. The boiler model determines the amount of energy required to generate the required amount of steam.
Factors such as friction in pipes, which tend to cause small amount of pressure drop in steam loop are neglected in the model. It is assumed that the steam pipes are fairly well insulated to prevent heat loss and subsequent condensation of steam in the pipes. In actual systems small quantities of steam, which condenses due to heat loss during transportation is removed immediately from the system by steam drains. This helps eliminate water hammer, degradation of steam quality and heat transfer capability.
Steam Generation at Saturated Conditions:[LINK]
Building steam heating systems avoid supplying superheated steam because superheat damages the building HVAC equipment. Superheated steam is generated only if there is a cogeneration power system in building such as steam turbine, which requires superheated steam. The purpose of having superheated steam is redundant for building steam heating systems because the amount of energy carried by the same is negligible compared to the latent heat. A simple enthalpy calculation, based on each unit of steam mass flow rate (1 kg/s), has been provided in this section to describe the negligible effect of superheat..
Case 1: Loop Operating at Saturation Conditions (no superheat), calculating enthalpy of saturated steam at boiler outlet temperature.
Boiler Outlet Temperature = 105\(^{\circ}\)C,
\[{h_{Case1:NoSuperheat}} = [{h_f}_{{{105}^ \circ }C}]\]
\[{h_{Case1:NoSuperheat}} = \,\,\,\,2684000\,\,\,\,\,\,J\]
Case 2: Loop operating with Superheated steam, calculating enthalpy of superheated steam for 5\(^{\circ}\)C superheat.
Degree of Superheat = 5\(^{\circ}\)C
Boiler Outlet Temperature = 110\(^{\circ}\)C,
\[{h_{Case2:Superheat}} = [{h_f}_{{{110}^ \circ }C}]\]
\[{h_{Case2:Superheat}} = \,\,\,2691000\,\,\,\,\,\,\,\,J\]
The energy difference between the superheated state and the saturated state as calculated in the following equation. A 5\(^{\circ}\)C superheat provides only a 0.2608% increase in heat transfer. The advantage of this additional increase in heat transfer is negligible, especially when considering the economic aspect of sizing a bigger heat exchanger to accommodate additional superheat transfer. The detrimental effects of superheated steam on the building HVAC system also come into effect once superheat is used.
\[\Delta {Q_{2 - 1}}\,\,\, = \,\,\,\frac{{2691000\, - 2684000}}{{2684000}}\,\, \times 100\,\,\,\, = \,\,0.2608\,\,\,percent\]
Based on the reasoning above the steam loop in EnergyPlus is designed and implemented to operate at saturated conditions.
Steam Quality[LINK]
The boiler operation is assumed capable to generate steam at quality equal to1.0 every time. This is a reasonable assumption, since in practice the variability in generated steam quality would only occur if the boiler operation were not properly controlled.
The steam loop is assumed to have perfect transport mechanism. There is no transportation losses due to friction and heat transfer with surroundings. This assumption helps maintain the quality of steam through out the system constant value of either 0 or 1.
Steam enters the coils at boiler outlet conditions. Steam coils are designed with steam traps, which only allow condensed steam to leave the coil; hence the steam always condenses and leaves the coil at quality of 0.0.
With the above simplifying assumption enables the EnergyPlus steam loop to be solved without problems.
Steam Traps[LINK]
Steam traps are essential part of the steam system; they are indirect flow controllers of the loop. Purpose of steam trap is to allow only condensate out of the coil from higher-pressure steam to lower atmospheric pressure condensate return line. Points 3-4’, in schematic Figure [fig:schematic-of-temperature-entropy-diagram-for], represent this process across the steam trap on the Ts diagram. The expansion process across the steam trap is assumed to be isenthalpic. There is possibility of flashing of high-pressure condensate across the trap because of pressure drop, resulting in generation of steam at lower pressure, this steam generated at lower pressure subsequently condenses in the return piping, and heat is lost to the atmosphere. This heat lost is a part of the steam loop losses.
Steam traps are modeled in the EnergyPlus steam coil by assigning the condensate outlet from the coil a quality of 0.0 and sub cooling the condensate at lower pressure.
Although condensate from the steam coil contains valuable heat, attempting to utilize this heat by holding the condensate in the coil reduces the heat transfer area. It causes operational problems because it retains air, which further reduces heat transfer and non-condensable gases such as carbon dioxide, which cause slow corrosion of the steam coil. Steam moves rapidly in mains and supply piping so when condensate accumulates to the point where the steam can push a slug of it, serious damage can occur from the resulting water hammer, hence the condensate should be immediately removed from the steam coil. This is achieved with steam traps.
Hence an ideal steam trap should remove all condensate, air, and non-condensable gases that might be in the system, with little or no loss of steam.
Loop Losses[LINK]
Subcooling of condensate in condensate return piping and flash steam condensing across the steam trap constitute the unavoidable loop losses in the EnergyPlus simulation steam system. These losses can be inferred from Figure [fig:schematic-of-temperature-entropy-diagram-for] and are summed up by calculating enthalpy difference between points 3 and 5 on the schematic Ts diagram.
Unavoidable losses in the EnergyPlus steam loop occur due to pressure drop across the steam trap, which causes flashing of steam and loss in some percentage of latent heat of steam, process 3-4’ and 4’-4 on the Ts diagram in Figure [fig:schematic-of-temperature-entropy-diagram-for]. The condensate is pumped backed to the boiler through return pipe network, which is not insulated. Sub cooling of the condensate occurs in the return network, represented by process 4-5 on the Ts diagram in Figure [fig:schematic-of-temperature-entropy-diagram-for]. This loop sub cool contributes to significant percentage of loop losses.
In practical systems the return pipeline to the boiler is not insulated despite the condensate containing some valuable heat, however due to low mass flow rate of steam, this amount is negligible and only recovered if separate heat recovery systems are used by coupling them to the loop. The condensate is occasionally collected in a receiver and then pumped back to the boiler. EnergyPlus simulation mimics practical systems by assumed that the return pipeline is not insulated and accounts for this by calculating loop losses.
The loop losses are calculated in the steam coil simulation model rather that the steam pipe simulation, because the condensate sub cool in the return loop is a direct function of the location of the steam coil in the building. In building energy software like EnergyPlus the user would have a fair idea about location of steam coils rather than the location of condensate return piping.
Steam To Air Heat Exchanger[LINK]
Description of Model:[LINK]
The steam to air heat exchanger (Coil:Heating:Steam input object) is the terminal equipment in the steam loop on the demand side that satisfies the heating requirements of the various zones. The steam-to-air heat exchanger simulation model in EnergyPlus calculates the mass flow rate of steam desired to meet the heating demand.
A heating coil can be used either as a zone coil or a coil in the air loop depending on the user and application. The steam coil simulation model is designed to take these two locations into consideration. An air-loop steam heating coil is temperature controlled and the zone coil is zone load controlled. This relatively simple and straightforward concept of coil control is preferred over the iterative method to determine mass flow rates using various numeric techniques. The assumptions made in the coil model are described in the section below.
This model accounts for the latent heat transfer and sensible cooling of water; the question of superheat is eliminated because steam is assumed to be saturation conditions. Steam enters the coil at quality equal to 1.0, at saturation temperature and leaves the coil with desired degree of sub cooling. The user inputs the desired degree of subcooling, which determines the condensate outlet condition from the coil.
EnergyPlus heat balance methods determine the amount of heating required in the zone to maintain the zone at the desired conditions. Based on this value of heating load, the zone coil determines the mass flow rate of steam required since the heating coil load is the control variable in a zone coil. The following equation describes this calculation to determine steam mass flow rate required for the desired heating capacity. The steam latent heat of vaporization, h\(_{fg}\) and the condensate heat capacity, C\(_{p,w}\) are evaluated at the steam coil inlet node temperature and standard barometric pressure of 101325.0 Pa.
\[{\dot m_{zc}}\,\,\,\, = \,\,\,\,\,\frac{{{Q_{zc}}}}{{{h_{fg}} + {c_{p,w}} \times \Delta {T_{sc}}}}\]
In case of the air loop-heating coil, the load on the coil is calculated within the coil simulation routine. The air loop coil is setpoint controlled and heats the air to maintain the air stream at the desired setpoint, the setpoint is a user input, generally in the range of 12\(^{\circ}\)C to 16\(^{\circ}\)C. The following equation describes the air loop coil load.
\[{Q_{al}}\,\, = \,\,{\dot m_a}\,\,\, \times \,\,\,\,\,{c_{p,a}}\,\,\, \times \,\,\,\,\,\left[ {{T_{sp}}\,\,\, - \,\,\,{T_a}} \right]\]
The following equation is used to determine the steam mass flow rate required by the air loop coil to meet the heating requirements.
\[{\dot m_{al}}\,\,\,\, = \,\,\,\,\,\frac{{{Q_{al}}}}{{{h_{fg}} + {c_{p,w}} \times \Delta {T_{sc}}}}\]
Each of the zone coils and air loop coils are simulated independently and the steam mass flow rates for each is added over every time step of simulation. This value of total mass flow rate is reported to the boiler, which in turns supplies this required amount of steam.
The control of the steam to air coil is a complex issue. The loop splitter-splits total steam flow from the boiler and delivers the required amount of steam to each of the coils connected to the loop through the steam pipe network. In cases where the system is undersized, the coils demand more mass flow rate of steam than the boiler can generate. The splitter in this case cannot provide all the coils with requested steam mass flow. Subsequently the coils are starved of steam and the zone temperatures fall. In some cases the user might schedule off the coil, they should then not operate. These issues need to be taken care of in the implementation of the steam coil simulation model. The control algorithm for the steam coil operation under various situations is best explained with the help of pseudo-code using standard IF THEN ELSE blocks.
*********************PSEUDO CODE SECTION STARTS**************************
Steam coil is zone load controlled.[LINK]
\[IF\,\,\,\,\,(Coil\, = LoadControlled)\,\,\,\,\,\,THEN\,\]
Check for operational conditions only then continue simulation further. The operational conditions are the inlet mass flow rates of steam and air to the coil, the user schedule to the coil and heating load on the coil. The coil is simulated only if these conditions are met.
\[IF\,\,\,\left[ {\,({{\dot m}_s}\,\,\, > \,\,\,0)\,\,.and.\,\,\,({{\dot m}_a} > \,\,\,0)\,\,.and.\,\,(Schedule\,\, = \,\,\,ON)\,.and.\,\,\,({Q_{ZC}}\,\, > \,\,0.0)\,} \right]\,\,\,THEN\]
If the heating demand from the zone-heating coil is greater than coil capacity, then the heating coil is undersized, and the coil can only deliver its maximum heating capacity to the zone. In this case the heating demand on the coil is set equal to this lower value of maximum heating capacity. If the above is not true then the simulation ignores this statement and proceeds to the next one.
\[IF\,\,\,\left[ {\,\,\,({Q_{ZC}}\,\, > \,\,{Q_{Z{C_{Max}}}})} \right]\,\,\,\,\,\,THEN\,\,\,\,\,\,\left[ {{Q_{ZC}} = \,\,{Q_{Z{C_{Max}}}}} \right]\]
The following equation calculates the steam mass flow rate required by the coil. This flow rate is required to meet the heating requirements for the zone. This value of mass flow is requested from the splitter outlet.
\[{\dot m_{zc}}\,\,\,\, = \,\,\,\,\,\frac{{{Q_{zc}}}}{{{h_{fg}} + {c_{p,w}} \times \Delta {T_{sc}}}}\]
If the calculated value of steam mass flow with the previous equation is greater than the maximum inlet steam flow that the splitter can provide to the coil at that time step. Then the requested coil flow rate is set equal to the inlet steam flow rate. This is the maximum amount of steam that can be supplied to the coil at this moment. The coil can provide heating capacity equal to this limited amount of steam. If the requested flow rate is less that what the splitter can provide then the program ignores the logic of the IF Loop Below
\[IF\,\,({\dot m_{zc}}\,\, > \,\,{\dot m_{in}})\,\,THEN\,\,(\,\,\,{\dot m_{zc}}\,\, = \,\,{\dot m_{in}})\]
Re-Calculating the coil heating capacity with the lower value of steam mass flow rate.
\[{Q_{ZC}} = {\dot m_{zc}}\,\, \times \,\,({h_{fg}} + {c_{p,w}} \times \Delta {T_{sc}})\]
\[END\,\,IF\]
The following equations calculate the outlet condensate-water and outlet air temperatures to the zone based on the amount of heating capacity provided by the coil.
\[T{w_{out}} = \,\,T{s_{in}}\,\, - \,\,\,\Delta {T_{sc}}\]
\[T{a_{out}}\,\,\, = \,\,T{a_{in}}\,\, + \,\,\,\frac{{{Q_{zc}}}}{{\,{{\dot m}_a}\, \times \,\,\,{c_{p,a}}}}\]
\(ELSE\) Else the coil is not running and in this case set outlets to inlets.
\[{\dot m_s} = 0\,,\,\,\,{\dot m_a} = 0\,,\,\,\,\,\,\,\,\,\,\,\,\,{Q_{zc}} = 0,\,\,\,\,\,\,\,\,\,\,\,\,T{w_{out}} = T{s_{in\,\,,\,\,\,\,}}\,\,\,\,\,\,T{a_{out}} = T{a_{in}}\]
\[END\,\,IF\]
\(END\,\,IF\) End IF for the zone load controlled coil.
Steam coil is temperature controlled.[LINK]
\[IF\,\,\,\,\,(Coil\, = TemperatureControlled)\,\,\,\,\,\,THEN\,\]
Check for operational conditions and continue simulation further. The operational conditions are the inlet mass flow rates of steam and air to the coil, the user schedule to the coil and delta temp exists between the setpoint and air inlet temperature. The coil is simulated only if these conditions are met.
\[IF\,\left[ \begin{array}{l}\,({{\dot m}_s}\,\,\, > \,\,\,0)\,\,.\,and.\,({{\dot m}_a} > \,\,\,0)\,\,.and.\,\,(Schedule\,\, = \,\,\,ON)\,.and.\,\\\,\,({T_{SP}} - T{a_{in}})\,\, > \,\,0.0001)\,\end{array} \right]\,THEN\]
Calculate the heating load on the coil using setpoint and inlet air temperatures.
\[{Q_{al}}\,\, = \,\,\,{\dot m_a}\, \times \,\,\,C{p_a}\,\, \times \,\,\,\,[\,\,{T_{sp}}\,\, - \,\,\,{T_a}]\]
The logic loop for temperature-controlled coil begins here. In case the heating load on the coil is negative, which might occur if the setpoint is below the air inlet temperature, the coil operation needs to be shut off.
\[IF\,\,({Q_{al}}\,\,\, < \,\,\,\,0.0)\,\,\,\,THEN\]
Assigning the inlet to outlet and mass flows to zero shuts off the coil operation.
\[{\dot m_s} = 0\,,\,\,\,{\dot m_a} = 0\,,\,\,\,\,\,\,\,\,\,\,\,\,{Q_{al}} = 0,\,\,\,\,\,\,\,\,\,\,\,\,T{w_{out}} = T{s_{in\,\,,\,\,\,\,}}\,\,\,\,\,\,T{a_{out}} = T{a_{in}}\]
If air loop coil load is greater than maximum coil load calculated at maximum steam mass flow rate, in such case the coil is undersized, the coil can only deliver to the air loop its maximum heating capacity. Setting the air loop coil load equal to maximum load on coil. If this is not the case then the program ignores this ELSE IF block and proceeds to the next one.
\[ELSE\,\,\,IF\,\,\,\,\left[ {\,\,\,({Q_{al}}\,\, > \,\,{Q_{a{l_{Max}}}})} \right]\,\,\,\,\,\,THEN\,\,\,\,\,\,\left[ {{Q_{al}} = \,\,{Q_{a{l_{Max}}}}} \right]\]
If the heating coil is under sized then it can only provide its maximum heating capacity, in this case the air temperature will be below the setpoint, and is calculated based on this maximum allowed value of heat transfer. Calculating the air and water outlet temperatures.
\[T{a_{out}}\,\,\, = \,\,T{a_{in}}\,\, + \,\,\,\frac{{{Q_{al}}}}{{\,\,{{\dot m}_a}\, \times \,\,\,{c_{p,a}}}}\]
\[T{w_{out}} = \,\,T{s_{in}}\,\, - \,\,\,\Delta {T_{sc}}\]
Determining the mass flow rate of steam required by the undersized coil. This value of mass flow is requested from the splitter outlet.
\[{\dot m_{al}}\,\,\,\, = \,\,\,\,\,\frac{{{Q_{al}}}}{{{h_{fg}} + {c_{p,w}} \times \Delta {T_{sc}}}}\]
A check is introduced to determine if this requested mass flow rate is greater than what the splitter outlet can provide to the coil at that particular time step of simulation. In this case the requested value of steam mass flow is greater that what the splitter can provide to that coil, subsequently set the requested coil flow rate equal to the inlet steam flow rate, delivered to the coil by the splitter. This is the maximum amount of steam that can be supplied to the coil at this moment. If the requested flow rate is less that what the splitter can provide then the program ignores the logic of the IF Loop.
\[IF\,\,\,({\dot m_{al}}\,\, > \,\,{\dot m_{in}})\,\,THEN\,\,(\,\,\,{\dot m_{al}}\,\, = \,\,{\dot m_{in}})\]
Re-Calculating the coil heating capacity and air outlet temperature with the lower value of steam mass flow rate provided by the splitter.
\[{Q_{al}}\,\,\,\, = \,\,\,\,{\dot m_{al}}({h_{fg}} + {c_{p,w}} \times \Delta {T_{sc}})\]
\[T{a_{out}}\,\,\, = \,\,T{a_{in}}\,\, + \,\,\,\frac{{{Q_{al}}}}{{\,\,{{\dot m}_a}\, \times \,\,\,{c_{p,a}}}}\]
\[End\,\,\,IF\]
If the above two IF ELSE block are not true, then the coil is perfectly sized, the splitter can provide the required mass flow rate to the coil, and the setpoint temperature can be maintained as desired.
\[ELSE\]
The ideal case where the coils can meet the required setpoint temperature. Setting the outlet air temperature to the setpoint, calculating the water outlet temperature and the required steam mass flow rate.
\[T{a_{out}}\,\,\, = \,\,{T_{SP}}\]
\[T{w_{out}} = \,\,T{s_{in}}\,\, - \,\,\,\Delta {T_{sc}}\]
\[{Q_{al}}\,\, = \,\,\,{\dot m_a}\, \times \,\,\,{c_{p,a}}\,\, \times \,\,\,\,[\,\,{T_{sp}}\,\, - \,\,\,{T_a}]\]
\(END\,\,IF\) End IF statement, for the air coil heating loop.
\(END\,\,IF\) End IF statement for the operating condition loop
\(END\,\,IF\) End IF statement for the Temperature Setpoint Controlled Coil
The steam coil model encapsulates the above described control logic along with the other necessary simulation code for reading the user inputs and the code for reporting the simulation results.
*********************PSEUDO CODE SECTION ENDS**************************
The two main types of coil control discussed above are followed by common simulation code in the coil model. This code calculates the loop losses occurring due to flashing of steam across the steam trap, isenthalpic expansion occurring across the steam trap due to pressure difference, and loss occurring due to condensate sub cooling returning back to the boiler. The above-mentioned two processes are explained in Figure [fig:schematic-of-temperature-entropy-diagram-for] as process 3-4’ and 4-5.
The loop loss calculation is included in the steam coil simulation model, because the degree of subcooling in the return piping for the condensate is solely a function of the coil location. In practical applications a coil, which is further away from boiler would return back condensate at much lower temperatures compared to coil, which is closer to boiler. Hence for user ease it makes perfect sense to include this input into the coil and calculate the pump inlet conditions in the steam coil simulation model itself.
The loop losses in the EnergyPlus steam system is calculated by determining the enthalpy difference between point 3 and 5. The simulation code that determines the loop loss is common to both the coil models, this helps determine the condensate pump inlet conditions.
The following equation is used to calculate condensate enthalpy at coil outlet, point 3 in Figure [fig:schematic-of-temperature-entropy-diagram-for]. Point 2 represents condensed steam; enthalpy at this point is calculated directly by EnergyPlus property routines.
\[{h_{f3}} = {h_{f2}} - {c_{p,w}} \times \Delta {T_{SC}}\]
Point 4 is at atmospheric pressure, enthalpy at this is calculated directly by EnergyPlus property routines. It is saturation enthalpy of steam at quality equal to 0.0 and saturation temperature at atmospheric pressure.
Point 5 is inlet to the pump; enthalpy at this point is calculated with the following equation The delta temperature represents the degree of loop subcooling occurring during condensate return back to the pump.
\[{h_{f5}} = {h_{f4}} - {c_{p,w}} \times \Delta {T_{LSC}}\]
Subsequently loop loss for each coil would be enthalpy difference between 3 and 5 and is calculated using the following equation
\[\Delta {Q_{loss}} = {\dot m_s}\,\,\, \times \,\,\,\,({h_{f3}} - {h_{f5}})\]
The total loop loss would be a summation of the individual losses occurring for each of the steam coils, this is the unavoidable loss in current steam system.
A simple schematic describing the coil framework, inlet and outlet conditions to the coil and the flow rate resolution is shown in Figure [fig:schematic-of-steam-coil-connection-to]. Five zone coils and one air loop coil are described in the picture, Qzone is calculated by EnergyPlus heat balance and it is the input to the zone coils, while in air loop coil the Qal is calculated within the simulation model
As depicted in the figure above the steam condenses on entering the coils, sub cools by the specified amount and leaves the heat exchanger as water. The steam in the heat exchanger at any moment has to condense eventually since steam trap at the outlet to coil permits only water to leave the coil. Steam traps being an essential part of the loop are modeled by controlling the coil outlet condition at quality equal to 0.0. Subsequently the amount of heat transferred to air is a direct function of latent heat and the degree of sub cooling desired by the user.
Model Assumptions[LINK]
The steam coils works on two basic assumptions, firstly, it’s assumed that perfect latent heat transfer takes place over every time step, secondly, the user specified degree of subcooling occurs in the coil. Steam coils always use steam traps- purpose of which is to only let water out of the coil, hence the modeler knows with certainty the outlet dryness faction of steam coil is at quality equal to 0.0, because water leaves coil. Hence the heat transfer is equal to latent heat of steam, which is independent of UA value of coil when averaged over time step of EnergyPlus simulation.
In practice there is 1% to 2% sub cooling of the outlet water stream, the user with desired degree of subcool input accounts for this, subsequently UA calculation for the coil model become superfluous and is neglected in the EnergyPlus model.
Ideally for sub-cooling UA would play an important role, however sub cooling in steam coil constitutes negligible amount of heat transfer, hence this model avoids the UA calculation. This is a very reasonable assumption since sensible heat transfer is barely 1% to 2% of the total heat transfer in steam coils, simply due to large latent heat capacity of coil. NOTE in his thesis he gives a little example here which is probably not necessary for the Docs.
Condensate Pump[LINK]
The steam loop operates at a pressure differential over the gaseous and liquid part of the loop; subsequently a condensate pump is required to pump the condensed steam back to the boiler at the required pressure. Two main reasons for condensed steam to be returned to the boiler is energy savings in reheating water since the water is at high temperature, secondly the water is treated by chemicals to prevent corrosion in the pipes and equipment. This is an expensive process and therefore it’s economical to reuse the chemically treated water.
Description of Pump Model[LINK]
The pump model designed in EnergyPlus is a variable speed condensate pump. Condensation of steam produces water, this takes place at variable rate hence the return water flow rate would be variable but constant when averaged over a time step. Condensate pumps operate intermittently; the pump will run at its capacity if a load/flow rate is sensed and will shut off if there is no load on the loop.
The condensate pump essentially operates between maximum and minimum flow rates, which are the physical limits of the device. The pump is designed to meet the flow request made by demand side components, which are the coils in case of steam system.
The main difference between the variable volume pump and the constant volume pump is the Part Load Performance Curve. The fraction of full load power is determined by the third order equation, which follows:
\[{P_{Frac}}\,\, = \,\,{C_1} + \,{C_2} \times PLR\,\, + \,\,\,{C_3} \times PL{R^2}\,\, + \,\,{C_4} \times PL{R^3}\]
In preceding equation, PLR stands for part load ratio while C1 to C4 are pump- part load coefficients. The following five equations describe the pump operation and calculation of pump output variables such as total power, shaft power and pump heat to fluid etc.
\[\dot V\,\, = \,\,\frac{{\,\dot m\,}}{{{\rho_w}}}\]
Using the previous equation the pump volume flow rate is determined; the user enters the value of the maximum and minimum volume flow rate.
The pump part load ratio is a function of the pump volume flow rate at any instance determined by the loop and the pump nominal volume flow rate, which is a user input. The following equation calculates the Part Load Ratio (PLR).
\[PLR = \,\frac{{\dot V}}{{{{\dot V}_{nom}}}}\]
The pump power is calculated as described in following equation. Pump power is a product of fractional full load power and pump nominal power use. Fractional full load power is calculated in a preceding equation while pump nominal power is a user input to the model.
\[P = {P_{Frac}} \times {P_{Nom}}\]
The shaft power is simply the product of the pump power and motor efficiency, this is required to calculate the heat generated and delivered to the fluid being pumped. The following equation is used to calculate pump shaft power.
\[{P_S}\,\,\, = P\,\,\,\, \times \,\,\,\,{\eta_m}\]
The model assumes that all heat generated and lost ends up in the fluid to the loop, this assumption is necessary since EnergyPlus operates on a closed loop. The following equation is used to calculate the pump heat to the fluid, which raises the condensate temperature. The pump motor efficiency is defined by the user input and the fractional motor loss to fluid is the amount of heat generated by the pump motor that is added to the fluid loop (as opposed to being lost to the environment where the pump is located). FracMotorLossToFluid is also a user input
\[{P_H} = {P_S}\,\,\, + \,(\,P\,\, - {P_S}) \times {F_{mf}}\]
The shaft power relates to the increase in head through the pump to the loop operating pressure. The head lost through the piping network due to frictional heat, represents the heat gain by the fluid throughout the network. . For model simplicity, this heat is added along with the heat resulting from the pump motor. The difference between the pump power and the shaft power is the inefficiency of the pump, or the amount of energy input into the pump that the motor converts to heat rather than mechanical energy. Some of this heat is added to the fluid being pumped. These two above-mentioned terms are used in the PumpHeatToFluid equation for calculating P\(_{H}\) shown above.
A simple energy balance over the pump based on the pump inlet conditions and flow rate is used to calculate the pump outlet temperature. The condensate outlet temperature from the pump is slightly higher than inlet due to the heat dissipation to the fluid steam during pumping action. This is calculated in the following equation. The pump water outlet temperature is the boiler inlet temperature.
\[{T_{{w_{out}}}} = {T_{{w_{in}}}}\,\,\, + \,\,\,\,\,\frac{{{P_H}}}{{\,\dot m\,\,\, \times \,\,\,\,{c_{p,w}}}}\]
Pump control is an important part of the steam loop. Existing control structure from EnergyPlus has been utilized to operate the condensate pump. The pump is simulated first on the supply side of the loop after the demand side loop has determined what the demand on the loop will be.
A simple schematic describing the flow across the pump is shown in the following figure
Model Assumptions[LINK]
Due to the fact that a pump is a mechanical device that acts on the fluid it is circulating, it causes the fluid temperature rise. The EnergyPlus model assumes that all pressure increase caused by the pump will eventually be lost due to friction, and that friction will be added as heat to the fluid. Although the plant and condenser loops in steam systems are simple pressure-based models, a simplifying assumption has be made in EnergyPlus to assume the heat resulting from the pump itself and from friction throughout the loop is added at the fluid being pumped. In case of steam, this assumption is easily justified because the volume flow rate of water is very small in the loop.
Steam Pipe[LINK]
Description of Model[LINK]
The steam pipe essentially serves as “energy carrier” and transfers the node conditions from one point of the pipe to another. It’s simply a node inlet to node outlet connection, transferring values from inlet to outlet. The pipe forms an important part of the framework connecting various equipments from the supply to demand side and inlet and outlets of the equipments.
The steam pipe supports two additional properties, which are pressure and quality, unlike its water counterpart. Pipe simulation model in EnergyPlus is hardwired to water as a fluid type; this necessitated the development of similar model supporting pressure and quality for the steam system.
Model Assumptions[LINK]
The piping network in the developed steam system is assumed to perfectly distribute steam, return the condensate, and remove air and non-condensable gases. It is also assumed that the pipes are sized to distribute steam not only at full load but also at partial loads and excess loads that can occur during system warm up.
The steam pipe is perfect and there is no losses occurring in transportation. This assumption was necessitated since if pipe losses were accounted for, the loss would have to be distributed into the zone, which would be a very complex issue in itself, since in EnergyPlus the pipes are unaware of their locations and simply serve as connectors.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.