Using EnergyPlus for Compliance — EnergyPlus 9.0

<< Prev | Table of Contents | Object Index | Next >>

Tabular Summary Reports[LINK]

Several predefined reports are available from the Output Table:Predefined object including the following.

  • Annual Building Utility Performance Summary

  • Input Verification and Results Summary

  • Demand End Use Components Summary

  • Source Energy End Use Components Summary

  • Climatic Data Summary

  • Equipment Summary

  • Envelope Summary

  • Surface Shadowing Summary

  • Shading Summary

  • Lighting Summary

  • HVAC Sizing Summary

  • System Summary

  • Component Sizing Summary

  • Outside Air Summary

  • Object Count Summary

In addition, specifying “All Summary” will enable all the reports in this category (more than are shown here).

Annual Building Utility Performance Summary[LINK]

First and foremost, the Annual Building Utility Performance Summary gives a good overview of the energy use by category:

Report: AnnualBuildingUtilityPerformanceSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

Values gathered over 8760.00 hours

Site and Source Energy

p1.5inp1.5inp1.5inp1.5in   & Total Energy [GJ] & Energy Per Total Building Area [MJ/m2] & Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy & 180.73 & 194.92 & 194.92
Net Site Energy & 180.73 & 194.92 & 194.92
Total Source Energy & 1141.64 & 1231.28 & 1231.28
Net Source Energy & 1141.64 & 1231.28 & 1231.28

Source to Site Energy Conversion Factors

  Source= > Site Conversion Factor
Electricity 0.293
Natural Gas 0.010
District Cooling 0.098
District Heating 0.033
Steam 0.250
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050

Building Area

  Area [m2]
Total Building Area 927.20
Net Conditioned Building Area 927.20
Unconditioned Building Area 0.00

End Uses

p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in   & Electricity [GJ] & Natural Gas [GJ] & Other Fuel [GJ] & District Cooling [GJ] & District Heating [GJ] & Water [m3]
Heating & 0.00 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00
Cooling & 16.56 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 81.24 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 47.70 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 6.59 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 0.48 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
  &   &   &   &   &   &  
Total End Uses & 152.57 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00

Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

p0.75inp0.75inp0.75inp0.75inp0.75inp0.75inp0.75inp0.75in   & Subcategory & Electricity [GJ] & Natural Gas [GJ] & Other Fuel [GJ] & District Cooling [GJ] & District Heating [GJ] & Water [m3]
Heating & Boiler & 0.00 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00
  & Boiler Parasitic & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Cooling & General & 16.56 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & GeneralLights & 81.24 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & General & 47.70 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & General & 6.59 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & General & 0.48 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00

Normalized Metrics

Utility Use Per Conditioned Floor Area

p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in   & Electricity Intensity [MJ/m2] & Natural Gas Intensity [MJ/m2] & Other Fuel Intensity [MJ/m2] & District Cooling Intensity [MJ/m2] & District Heating Intensity [MJ/m2] & Water Intensity [m3/m2]
Lighting & 87.62 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
HVAC & 25.49 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Other & 51.44 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Total & 164.55 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00

Utility Use Per Total Floor Area

p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in   & Electricity Intensity [MJ/m2] & Natural Gas Intensity [MJ/m2] & Other Fuel Intensity [MJ/m2] & District Cooling Intensity [MJ/m2] & District Heating Intensity [MJ/m2] & Water Intensity [m3/m2]
Lighting & 87.62 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
HVAC & 25.49 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Other & 51.44 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Total & 164.55 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00

Electric Loads Satisfied

p2.9inp1.5inp1.59in   & Electricity [GJ] & Percent Electricity [%]
Fuel-Fired Power Generation & 0.00 & 0.00
High Temperature Geothermal* & 0.00 & 0.00
Photovoltaic Power & 0.00 & 0.00
Wind Power* & 0.00 & 0.00
Net Decrease in On-Site Storage & 0.00 & 0.00
Total On-Site Electric Sources & 0.00 & 0.00
  &   &  
Electricity Coming From Utility & 152.57 & 100.00
Surplus Electricity Going To Utility & 0.00 & 0.00
Net Electricity From Utility & 152.57 & 100.00
  &   &  
Total On-Site and Utility Electric Sources & 152.57 & 100.00
Total Electricity End Uses & 152.57 & 100.00

On-Site Thermal Sources

  Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  

Water Source Summary

p3.0inp1.5inp1.5in   & Water [m3] & Percent Water [%]
Rainwater Collection & 0.00 & -
Condensate Collection & 0.00 & -
Groundwater Well & 0.00 & -
Total On Site Water Sources & 0.00 & -
- & - & -
Initial Storage & 0.00 & -
Final Storage & 0.00 & -
Change in Storage & 0.00 & -
- & - & -
Water Supplied by Utility & 0.00 & -
- & - & -
Total On Site, Change in Storage, and Utility Water Sources & 0.00 & -
Total Water End Uses & 0.00 & -

Comfort and Setpoint Not Met Summary

p4.5inp1.5in   & Facility [Hours]
Time Set Point Not Met During Occupied Heating & 0.00
Time Set Point Not Met During Occupied Cooling & 213.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 & 72.50

Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Input Verification Summary[LINK]

The input verification summary gives a good overview of the facility being simulated:

Report: InputVerificationandResultsSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

General

p2.25inp3.74in   & Value
Program Version and Build & EnergyPlus 4.0.0.017, 9/17/2009 5:30 PM
Weather & Climate Zone 6 CA USA WYEC2-C-00006 WMO#=722970
Latitude [deg] & 33.90
Longitude [deg] & -118.5
Elevation [m] & 30.00
Time Zone & -8.0
North Axis Angle [deg] & 30.00
Rotation for Appendix G [deg] & 0.00
Hours Simulated [hrs] & 8760.00

ENVELOPE

Window-Wall Ratio

p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in   & Total & North (315 to 45 deg) & East (45 to 135 deg) & South (135 to 225 deg) & West (225 to 315 deg)
Gross Wall Area [m2] & 274.20 & 91.50 & 45.60 & 91.50 & 45.60
Window Opening Area [m2] & 60.90 & 20.85 & 9.12 & 21.81 & 9.12
Window-Wall Ratio [%] & 22.21 & 22.79 & 20.00 & 23.84 & 20.00

Skylight-Roof Ratio

  Total
Gross Roof Area [m2] 463.60
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00

PERFORMANCE

Zone Summary

p0.7inp0.4inp0.5inp0.5inp0.4inp0.5inp0.5inp0.5inp0.5inp0.5in   & Area [m2] & Conditioned (Y/N) & Volume [m3] & Multipliers & Gross Wall Area [m2] & Window Glass Area [m2] & Lighting [W/m2] & People [m2] per person & Plug and Process [W/m2]
PLENUM-1 & 463.60 & Yes & 283.20 & 1.00 & 54.84 & 0.00 & 0.0000 &   & 0.0000
SPACE1-1 & 99.16 & Yes & 239.25 & 1.00 & 73.20 & 21.81 & 15.9742 & 9.01 & 10.6495
SPACE2-1 & 42.73 & Yes & 103.31 & 1.00 & 36.48 & 9.12 & 16.0056 & 8.55 & 10.6704
SPACE3-1 & 96.48 & Yes & 239.25 & 1.00 & 73.20 & 20.85 & 16.4179 & 8.77 & 10.9453
SPACE4-1 & 42.73 & Yes & 103.31 & 1.00 & 36.48 & 9.12 & 16.0056 & 8.55 & 10.6704
SPACE5-1 & 182.49 & Yes & 447.68 & 1.00 & 0.00 & 0.00 & 16.2420 & 9.12 & 10.8280
Total & 927.20 &   & 1416.00 &   & 274.20 & 60.90 & 8.0889 & 17.83 & 5.3926
Conditioned Total & 927.20 &   & 1416.00 &   & 274.20 & 60.90 & 8.0889 & 17.83 & 5.3926
Unconditioned Total & 0.00 &   & 0.00 &   & 0.00 & 0.00 &   &   &  

Source Energy End Use Components Summary[LINK]

The source energy end use components summary gives a good overview of the source energy consumption broken down by end uses for the facility being simulated:

Report: SourceEnergyEndUseComponentsSummary

For: Entire Facility

Timestamp: 2011-10-07 20:53:43

Values gathered over 8760.00 hours

Source Energy End Use Components Summary

p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [GJ] & Source Natural Gas [GJ] & Source Other Fuel [GJ] & Source District Cooling [GJ] & Source District Heating [GJ]
Heating & 0.00 & 140.03 & 0.00 & 0.00 & 0.00
Cooling & 167.65 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 569.39 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 325.49 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 55.72 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 7.57 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1125.82 & 140.03 & 0.00 & 0.00 & 0.00

Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [MJ/m2] & Source Natural Gas [MJ/m2] & Source Other Fuel [MJ/m2] & Source District Cooling [MJ/m2] & Source District Heating [MJ/m2]
Heating & 0.00 & 151.02 & 0.00 & 0.00 & 0.00
Cooling & 180.82 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 614.09 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 351.05 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 60.10 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 8.16 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1214.22 & 151.02 & 0.00 & 0.00 & 0.00

Source Energy End Use Components Per Total Floor Area

p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [MJ/m2] & Source Natural Gas [MJ/m2] & Source Other Fuel [MJ/m2] & Source District Cooling [MJ/m2] & Source District Heating [MJ/m2]
Heating & 0.00 & 151.02 & 0.00 & 0.00 & 0.00
Cooling & 180.82 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 614.09 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 351.05 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 60.10 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 8.16 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1214.22 & 151.02 & 0.00 & 0.00 & 0.00

Other Summary Reports[LINK]

The Climatic Data Summary, Envelope Summary and Equipment Summary reports might be quite important to some reporting or presentation.

Report: ClimaticDataSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

SizingPeriod:DesignDay

p1.2inp0.7inp0.7inp0.7inp0.7inp0.7inp0.7in   & Maximum Dry Bulb [C] & Daily Temperature Range [C] & Humidity Value & Humidity Type & Wind Speed [m/s] & Wind Direction
LOS_ANGELES_CA_USA HEATING 99% CONDITIONS & 7.40 & 0.00 & 7.40 & 0 & 2.80 & 70.00
LOS_ANGELES_CA_USA COOLING 1% CONDITIONS DB= > MWB & 27.00 & 6.10 & 17.60 & 0 & 4.40 & 250.00

Weather Statistics File

p2.15inp3.84in   & Value
Reference & CZ06RV2
Site:Location & Climate Zone 6 CA USA
Latitude & N 33° 54’
Longitude & W 118° 30’
Time Zone & GMT -8.0 Hours
Elevation & 30m above sea level
Standard Pressure at Elevation & 100965Pa
Data Source & WYEC2-C-00006
WMO Station & 722970
Design Conditions & Climate Design Data 2005 ASHRAE Handbook
Heating Design Temperature 99.6% (C) & 4.9
Heating Design Temperature 99% (C) & 6.2
Cooling Design Temperature 0.4% (C) & 33.1
Cooling Design Temperature 1% (C) & 30.9
Cooling Design Temperature 2% (C) & 29.2
Maximum Dry Bulb Temperature (C) & 31.7°
Maximum Dry Bulb Occurs on & Sep 24
Minimum Dry Bulb Temperature (C) & 3.5°
Minimum Dry Bulb Occurs on & Jan 8
Maximum Dew Point Temperature (C) & 20.9
Maximum Dew Point Occurs on & Jun 20
Minimum Dew Point Temperature (C) & -21.7
Minimum Dew Point Occurs on & Dec 27
Heating Degree-Days (base 10°C) & 2
Cooling Degree-Days (base 18°C) & 216
Köppen Classification & Csb
Köppen Description & Mediterranean climate (dry warm summer, mild winter, lat. 30-45°N)
Köppen Recommendation &  
ASHRAE Climate Zone & 3C
ASHRAE Description & Warm-Marine

Report: EnvelopeSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

Opaque Exterior

p0.66inp0.66inp0.6inp0.6inp0.6inp0.6inp0.6inp0.6inp0.6in   & Construction & Reflectance & U-Factor with Film [W/m2-K] & U-Factor no Film [W/m2-K] & Gross Area [m2] & Azimuth [deg] & Tilt [deg] & Cardinal Direction
WALL-1PF & WALL-1 & 0.22 & 0.384 & 0.408 & 18.30 & 210.00 & 90.00 & S
WALL-1PR & WALL-1 & 0.22 & 0.384 & 0.408 & 9.12 & 120.00 & 90.00 & E
WALL-1PB & WALL-1 & 0.22 & 0.384 & 0.408 & 18.30 & 30.00 & 90.00 & N
WALL-1PL & WALL-1 & 0.22 & 0.384 & 0.408 & 9.12 & 300.00 & 90.00 & W
TOP-1 & ROOF-1 & 0.35 & 0.268 & 0.282 & 463.60 & 210.00 & 0.00 &  
FRONT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 73.20 & 210.00 & 90.00 & S
F1-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 99.16 & 30.00 & 180.00 &  
RIGHT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 36.48 & 120.00 & 90.00 & E
F2-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 42.73 & 300.00 & 180.00 &  
BACK-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 73.20 & 30.00 & 90.00 & N
F3-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 96.48 & 74.22 & 180.00 &  
LEFT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 36.48 & 300.00 & 90.00 & W
F4-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 42.73 & 120.00 & 180.00 &  
F5-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 182.49 & 30.00 & 180.00 &  

Fenestration

p0.6inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5in   & Construction & Area of One Opening [m2] & Area of Openings [m2] & U-Factor [W/m2-K] & SHGC & Visible Transmittance & Shade Control & Parent Surface & Azimuth [deg] & Cardinal Direction
WF-1 & DBL CLR 3MM/13MM AIR & 16.56 & 16.56 & 2.720 & 0.764 & 0.812 & No & FRONT-1 & 210.00 & S
DF-1 & SGL GREY 3MM & 5.25 & 5.25 & 5.894 & 0.716 & 0.611 & No & FRONT-1 & 210.00 & S
WR-1 & DBL CLR 3MM/13MM AIR & 9.12 & 9.12 & 2.720 & 0.764 & 0.812 & No & RIGHT-1 & 120.00 & E
WB-1 & DBL CLR 3MM/13MM AIR & 16.44 & 16.44 & 2.720 & 0.764 & 0.812 & No & BACK-1 & 30.00 & N
DB-1 & SGL GREY 3MM & 4.41 & 4.41 & 5.894 & 0.716 & 0.611 & No & BACK-1 & 30.00 & N
WL-1 & DBL CLR 3MM/13MM AIR & 9.12 & 9.12 & 2.720 & 0.764 & 0.812 & No & LEFT-1 & 300.00 & W
Total or Average &   &   & 60.90 & 3.22 & 0.756 & 0.780 &   &   &   &  
North Total or Average &   &   & 20.85 & 3.39 & 0.754 & 0.769 &   &   &   &  
Non-North Total or Average &   &   & 40.05 & 3.14 & 0.757 & 0.785 &   &   &   &  


Report: ShadingSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

Sunlit Fraction

Ma rch 21 9am Ma rch 21 noon Ma rch 21 3pm Ju ne 21 9am Ju ne 21 noon Ju ne 21 3pm De cember 21 9am De cember 21 noon De cember 21 3pm
WF-1 0.00 0.00 0.26 0.00 0.00 0.00 0.00 0.30 0.74
DF-1 0.75 0.13 0.59 0.00 0.00 0.35 0.92 0.62 0.94
WR-1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WB-1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DB-1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WL-1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00

Window Control

  Name Type Shaded Construction Control Glare Control
None          

Report: LightingSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

Interior Lighting

Zo ne Li ghting Power Density [W/m2] Zo ne Area [m2] To tal Power [W] En d Use Subcategory Sc hedule Name Av erage Hours/Week [hr] Re turn Air Fraction Co nditioned (Y/N)
SPACE1-1 LIGHTS 1 SPACE1-1 15.9742 99.16 1584.00 GeneralLights LIGHTS-1 0.00 0.2000 Y
SPACE2-1 LIGHTS 1 SPACE2-1 16.0056 42.73 684.00 GeneralLights LIGHTS-1 0.00 0.2000 Y
SPACE3-1 LIGHTS 1 SPACE3-1 16.4179 96.48 1584.00 GeneralLights LIGHTS-1 0.00 0.2000 Y
SPACE4-1 LIGHTS 1 SPACE4-1 16.0056 42.73 684.00 GeneralLights LIGHTS-1 0.00 0.2000 Y
SPACE5-1 LIGHTS 1 SPACE5-1 16.2420 182.49 2964.00 GeneralLights LIGHTS-1 0.00 0.2000 Y
Interior Lighting Total   16.1777 463.60 7500.00          

Daylighting

  Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            

Exterior Lighting

  Total Watts Astronomical Clock/Schedule Schedule Name Average Annual Hours/Week
Exterior Lighting Total 0.00      

Report: EquipmentSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

Central Plant

Ty pe No minal Capacity [W] No minal Efficiency [W/W]
CENTRAL CHILLER Chiller:Electric 25311.64 3.20
CENTRAL BOILER Boiler:HotWater 56191.29 0.80

Cooling Coils

Ty pe No minal Total Capacity [W] No minal Sensible Capacity [W] No minal Latent Capacity [W] No minal Sensible Heat Ratio No minal Efficiency [W/W]
MAIN COOLING COIL 1 Coil:Cooling:Water 28159.12 19476.53 8682.60 0.69 -

Heating Coils

  Type Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPACE1-1 ZONE COIL Coil:Heating:Water 10384.85 -
SPACE2-1 ZONE COIL Coil:Heating:Water 8470.48 -
SPACE3-1 ZONE COIL Coil:Heating:Water 10477.88 -
SPACE4-1 ZONE COIL Coil:Heating:Water 11334.29 -
SPACE5-1 ZONE COIL Coil:Heating:Water 11391.33 -
MAIN HEATING COIL 1 Coil:Heating:Water 4061.83 -

Fans

Ty pe To tal Efficiency [W/W] De lta Pressure [pa] Ma x Flow Rate [m3/s] Ra ted Power [W] Mo tor Heat In Air Fraction En d Use
SUPPLY FAN 1 Fan:VariableVolume 0.70 600.00 1.28 1099.23 1.00 General

Pumps

Ty pe Co ntrol He ad [pa] Po wer [W] Mo tor Efficiency [W/W]
HW CIRC PUMP Pump:VariableSpeed INTERMITTENT 179352.00 312.23 0.90
CW CIRC PUMP Pump:VariableSpeed INTERMITTENT 179352.00 231.95 0.90

Service Water Heating

  Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
None