Reading the documentation, I’m wondering if the Cavity
algorithm is usable for other double facade types or only
Trombe wall? In other words, does Cavity implicitly presume
that the inner wall is highly solar absorbent and so generate
specific convection?
The Trombe wall convection algorithm is applicable to just
about any vertical cavity with a high aspect ratio and
relatively narrow width. I’m not sure if a double facade
cavity would meet the aspect ratio requirement. But I do know
the Trombe wall algorithm is not picky about whether the inner
wall is highly absorbant, or about any particular properties
of the walls. Actually the same basic algorithm is used by the
window model to calculate the convection between the two panes
of a window. The full reference is ISO 15099.
Cavity Algorithm Model[LINK]
Reading the documentation, I’m wondering if the Cavity algorithm is usable for other double facade types or only Trombe wall? In other words, does Cavity implicitly presume that the inner wall is highly solar absorbent and so generate specific convection?
The Trombe wall convection algorithm is applicable to just about any vertical cavity with a high aspect ratio and relatively narrow width. I’m not sure if a double facade cavity would meet the aspect ratio requirement. But I do know the Trombe wall algorithm is not picky about whether the inner wall is highly absorbant, or about any particular properties of the walls. Actually the same basic algorithm is used by the window model to calculate the convection between the two panes of a window. The full reference is ISO 15099.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.