Engineering Reference — EnergyPlus 9.3

<< Prev | Table of Contents | Object Index | Next >>

System Design Loads and Air Flow Rates[LINK]

Overview[LINK]

The purpose of the system design calculation is to estimate design heating and cooling loads and air flow rates for each air loop in the simulation problem. The calculation sequence for system level design loads and air flow rates resembles the calculation sequence for zone loads and air flow rates. There is an update subroutine UpdateSysSizing called at the beginning, during, and end of a loop in the Sizing Manager over all the design days. The major difference is that this calculation is done at the zone time-step only. There is no idealized component calculation triggered at the system time-step as in the zone calculation. The system design calculation operates at the zone time step using the design environment weather data and the data stored in the zone sizing arrays. The results of the system design calculation are stored in the system sizing arrays described below.

System Design Data Arrays[LINK]

The system design data arrays are:

SysSizInput(i) stores the input data from the Sizing:System objects.

SysSizing(i,j) stores the results of the system design calculations for all systems and all design days. The index i is for air loops, j for design days.

CalcSysSizing(i) stores the results of the system design calculations for the peak heating and cooling cases for each air loop. The index i is for the air loops.

FinalSysSizing(i) corresponds to CalcSysSizing but includes the effect of the user specified sizing factor or user specified system design flow rate.

The data stored in SysSizing, CalcSysSizing and FinalSysSizing includes the following data items.

System Sizing Data
Name Description
All the data from SysSizInput
CoinCoolMassFlow coincident peak cooling mass flow rate [kg/s]
CoinHeatMassFlow coincident peak heating mass flow rate [kg/s]
NonCoinCoolMassFlow noncoincident peak cooling mass flow rate [kg/s]
NonCoinHeatMassFlow noncoincident peak heating mass flow rate [kg/s]
DesMainVolFlow design main supply duct volume flow [m\(^{3}\)/s]
DesHeatVolFlow design heat supply duct volume flow [m\(^{3}\)/s]
DesCoolVolFlow design cool supply duct volume flow [m\(^{3}\)/s]
SensCoolCap design sensible cooling capacity [W]
TotCoolCap design total cooling capacity [W]
HeatCap design heating capacity [W]
PreheatCap design preheat capacity [W]
MixTempAtCoolPeak mixed air temperature at the time of the cooling peak [C]
MixHumRatAtCoolPeak mixed air humidity ratio at the time of the cooling peak [kg water/kg dry air]
RetTempAtCoolPeak return air temperature at the time of the cooling peak [C]
RetHumRatAtCoolPeak return air humidity ratio at the time of the cooling peak [kg water/kg dry air]
OutTempAtCoolPeak outside air temperature at the time of the cooling peak [C]
OutHumRatAtCoolPeak outside air humidity ratio at the time of the cooling peak [kg water/kg dry air]
HeatMixTemp design mixed air temperature for heating [C]
HeatMixHumRat design mixed air humidity ratio for heating [kg water/kg dry air]
HeatRetTemp design return air temperature for heating [C]
HeatRetHumRat design return air humidity ratio for heating [kg water/kg dry air]
HeatOutTemp design outside air temperature for heating [C]
HeatOutHumRat design outside air humidity ratio for heating [kg water/kg dry air]
HeatFlowSeq(i) daily sequence of system heating air mass flow rate (zone time step) [kg/s]
CoolFlowSeq(i) daily sequence of system cooling air mass flow rate (zone time step) [kg/s]
SumZoneCoolLoadSeq(I) daily sequence of zones’ summed cooling load (zone time step) [W]
CoolZoneAvgTempSeq(I) daily sequence of zones flow weighted average temperature (zone time step) [W]
SensCoolCapSeq(I) daily sequence of system sensible cooling capacity (zone time step) [W]
TotCoolCapSeq(I) daily sequence of system total cooling capacity (zone time step) [W]
HeatCapSeq(i) daily sequence of system heating capacity (zone time step) [W]
PreHeatCapSeq(i) daily sequence of system preheat capacity (zone time step) [W]
SysCoolRetTempSeq(i) daily sequence of system cooling return temperatures (zone time step) [C]
SysCoolRetHumRatSeq(I) daily sequence of system cooling return humidity ratios (zone time step) [kg water/kg dry air]
SysHeatRetTempSeq(i) daily sequence of system heating return temperatures (zone time step) [C]
SysHeatRetHumRatSeq(I) daily sequence of system heating return humidity ratios (zone time step) [kg water/kg dry air]
SysCoolOutTempSeq daily sequence of system cooling outside temperatures (zone time step) [C]
SysCoolOutHumRatSeq daily sequence of system cooling outside humidity ratios (zone time step) [kg water/kg dry air]
SysHeatOutTempSeq daily sequence of system heating outside temperatures (zone time step) [C]
SysHeatOutHumRatSeq daily sequence of system heating outside humidity ratios (zone time step) [kg water/kg dry air]

System Design Flow Rate and Load Summation and Adjustment[LINK]

There is no system level subroutine corresponding to SizeZoneEquipment. Instead the system design loads and flow rates are calculated using the zone level results. The zone design flow rates for the zones served by an air loop are summed to obtain the system level design flow rates. These air flows are mixed with the system level design minimum outside air flow rate to obtain system design coil loads. These activities are all performed within the UpdateSysSizing subroutine in the SimAirServingZones module. It is called at the start of each design day (CallIndicator = BeginDay), at the zone time-step (CallIndicator = DuringDay), at the end of the design day (CallIndicator = EndDay) and at the end of the zone design calculation (CallIndicator = EndSysSizingCalc).

There is a logical flag SysSizingCalc corresponding to ZoneSizingCalc. It is used to allow the component routines to distinguish a normal simulation call from a being called during a system sizing calculation.

Note that throughout this section, any reference to a “zone” is equivalent to “air terminal unit”.

BeginDay[LINK]

  1. The environment (in this case, a design day) name is stored in the system sizing data structures.

  2. Loop over the zones cooled by this air loop:

NonCoinCoolMassFlow\(_{sys}\) = \(\Sigma\) DesCoolMassFlow\(_{zone}\)

  1. Loop over the zones heated by this air loop:

NonCoinCoolMassFlow\(_{sys}\) = \(\Sigma\) DesHeatMassFlow\(_{zone}\)

DuringDay[LINK]

  1. Loop over the zones cooled by this air loop:

CoolFlowSeq\(_{sys}\)(i) = \(\Sigma\) CoolFlowSeq \(_{zone}\)(i)

SysCoolRetTemp(i) = \(\Sigma\) (CoolZoneRetTempSeq(i) * CoolFlowSeq\(_{zone}\)(i))/ CoolFlowSeq\(_{sys}\)(i)

SysCoolRetHumRat(i) = \(\Sigma\) (CoolZoneHumRatSeq(i) * CoolFlowSeq\(_{zone}\)(i))/ CoolFlowSeq\(_{sys}\)(i)

FracOA = \(\rho\)\(_{air}\) * DesOutAirVolFlow\(_{sys}\)/ CoolFlowSeq\(_{sys}\)(i)

T\(_{mix}\) = T\(_{outside}\) * FracOA + SysCoolRetTemp(i)(1 - FracOA)

W\(_{mix}\) = W\(_{outside}\) * FracOA + SysCoolRetHumRat (i)(1 - FracOA)

SysCoolOutTempSeq(i) = T\(_{outside}\)

SysCoolOutHumRatSeq(i) = W\(_{outside}\)

Get the current (zone time-step) system cooling capacity:

SysSensCoolCap\(_{cur}\) = C\(_{p,air}\) * CoolFlowSeq\(_{sys}\)(i) *( T\(_{mix}\)-T\(_{sup}\))

SensCoolCapSeq(I) = SysSensCoolCap\(_{cur}\)

If SysSensCoolCap\(_{cur}\) is the maximum for the day so far then save SysSensCoolCap\(_{cur}\) as the design value:

SensCoolCap(i )\(_{sys}\) = SysSensCoolCap\(_{cur}\)

And save the corresponding mixed, return and outside conditions:

CoolMixTemp\(_{sys}\) = T\(_{mix}\)

CoolMixHumRat\(_{sys}\) = W\(_{mix}\)

CoolRetTemp\(_{sys}\) = SysCoolRetTemp(i)

CoolRetHumRat\(_{sys}\) = SysCoolRetHumRat(I)

CoolOutTemp\(_{sys}\) = T\(_{outside}\)

CoolOutHumRat\(_{sys}\) = W\(_{outside}\)

Here \(\rho\)\(_{air}\) is the density of dry air at 20\(^{\circ}\)C and standard elevation corrected pressure, [kg/m\(^{3}\)];

FracOA is the outside air fraction; C\(_{p,air}\) is the specific heat of dry air at 20\(^{\circ}\)C, [J/kg-K]; T\(_{sup}\) is the user specified design cooling supply temperature [C]; T\(_{mix}\) is the current mixed air temperature [C]; W\(_{mix}\) is the current mixed air humidity ratio [kg water / kg dry air]; \(T_{outside}\) is the current outside air temperature [C]; \(W_{outside}\) is the current outside air humidity ratio [kg water / kg dry air].

  1. Loop over the zones heated by this air loop.

HeatFlowSeq\(_{sys}\)(i) = \(\Sigma\) HeatFlowSeq \(_{zone}\)(i)

SysHeatRetTemp(i) = \(\Sigma\) (HeatZoneRetTempSeq(i) * HeatFlowSeq\(_{zone}\)(i))/

HeatFlowSeq\(_{sys}\)(i)

SysHeatRetHumRat(i) = \(\Sigma\) (HeatZoneHumRatSeq(i) * HeatFlowSeq\(_{zone}\)(i))/

HeatFlowSeq\(_{sys}\)(i)

FracOA = r\(_{air}\) * DesOutAirVolFlow\(_{sys}\)/ HeatFlowSeq\(_{sys}\)(i)

T\(_{mix}\) = T\(_{outside}\) * FracOA + SysHeatRetTemp(i)(1 - FracOA)

W\(_{mix}\) = W\(_{outside}\) * FracOA + SysHeatRetHumRat (i)(1 - FracOA)

SysHeatOutTempSeq(i) = T\(_{outside}\)

SysHeatOutHumRatSeq(i) = W\(_{outside}\)

Get the current (zone time-step) system heating capacity:

SysHeatCap\(_{cur}\) = C\(_{p,air}\) * MinFlowRat\(_{sys}\) *HeatFlowSeq\(_{sys}\)(i) *( T\(_{sup}\)-T\(_{mix}\))

HeatCapSeq(I) = SysHeatCap\(_{cur}\)

If SysHeatCap\(_{cur}\) is the maximum for the day so far then save SysHeatCap\(_{cur}\) as the design value:

HeatCap(i )\(_{sys}\) = SysHeatCap\(_{cur}\)

And save the corresponding mixed, return and outside conditions:

HeatMixTemp\(_{sys}\) = T\(_{mix}\)

HeatMixHumRat\(_{sys}\) = W\(_{mix}\)

HeatRetTemp\(_{sys}\) = SysHeatRetTemp(i)

HeatRetHumRat\(_{sys}\) = SysHeatRetHumRat(I)

HeatOutTemp\(_{sys}\) = T\(_{outside}\)

HeatOutHumRat\(_{sys}\) = W\(_{outside}\)

Here MinFlowRat\(_{sys}\) is the user specified minimum supply flow ratio.

EndDay[LINK]

If the user has specified coincident system sizing then:

DesCoolVolFlow\(_{sys}\) = \(\rho\)\(_{air}\) *CoinCoolMassFlow\(_{sys}\)

DesHeatVolFlow\(_{sys}\) = \(\rho\)\(_{air}\) *CoinHeatMassFlow\(_{sys}\)

DesMainVolFlow\(_{sys}\) = Max(DesCoolVolFlow\(_{sys}\), DesHeatVolFlow\(_{sys}\))

If the user has specified noncoincidentsystem sizing then:

DesCoolVolFlow\(_{sys}\) = \(\rho\)\(_{air}\) *NonCoinCoolMassFlow\(_{sys}\)

DesHeatVolFlow\(_{sys}\) = \(\rho\)\(_{air}\) *NonCoinHeatMassFlow\(_{sys}\)

DesMainVolFlow\(_{sys}\) = Max(DesCoolVolFlow\(_{sys}\), DesHeatVolFlow\(_{sys}\))

Based on the outdoor air method selected, the DesCoolVolFlow\(_{sys}\) and DesHeatVolFlow\(_{sys}\) are modified based on the system ventilation effciency calculated based on the maximum outdoor air fraction.

EndSysSizingCalc[LINK]

At this point all the calculations have been done in SysSizing(i,j): we have results for each design day. Now these results need to be processed to find the heating and cooling design quantities for each system over all the design days.

For coincident sizing the task is quite easy.

  1. Loop over all of the air loops.
  1. Loop over all of the design days.
  1. If the value of DesCoolVolFlow in SysSizing for the current design day is greater than the value stored in CalcSysSizing, then move DesCoolVolFlow from SysSizing into CalcSysSizing along with CoolDesDay, CoinCoolMassFlow, SensCoolCap, CoolFlowSeq(i), SensCoolCapSeq(i), CoolMixTemp, CoolRetTemp, CoolMixHumRat, CoolRetHumRat, CoolOutTemp, CoolOutHumRat, SysCoolRetTempSeq(i), SysCoolRetHumRatSeq(i), SysCoolOutTempSeq(i) and SysCoolOutHumRatSeq(i).

  2. If the value of DesHeatVolFlow in SysSizing for the current design day is greater than the value stored in CalcSysSizing, then move DesHeatVolFlow from SysSizing into CalcSysSizing along with HeatDesDay, CoinHeatMassFlow, HeatCap, PreHeatCap, HeatFlowSeq(i), HeatCapSeq(i), PreHeatCapSeq(i), HeatMixTemp, HeatRetTemp, HeatMixHumRat, HeatRetHumRat, HeatOutTemp, HeatOutHumRat, SysHeatRetTempSeq(i), SysHeatRetHumRatSeq(i), SysHeatOutTempSeq(i) and SysHeatOutHumRatSeq(i).

At the end of each design day loop the peak cooling and the peak heating data will be stored in CalcSysSizing. At this point we set DesMainVolFlow in CalcSysSizing equal to the maximum of DesCoolVolFlow and DesHeatVolFlow.

For noncoincident sizing the task is harder since we don’t have a single time-step during which all the zone peaks occur. So there is no obvious value for outside air temperature at the peak, return air temperature at the peak and so forth. We must return to the zone sizing data and calculate average values for return and outside conditions.

  1. Loop over all of the zones cooled by this air loop.

In FinalZoneSizing replace the value in DesCoolCoilInTemp with the user specified CoolSupTemp\(_{sys}\). Do the same for DesCoolCoilInHumRat and CoolSupHumRat. This ensures that zone equipment connected to an air loop will use the system design supply air conditions as coil entering conditions.

NonCoinCoolMassFlow\(_{sys}\) = \(\Sigma\) DesCoolMassFlow\(_{zone}\)

SysCoolRetTemp = (ZoneRetTempAtCoolPeak *DesCoolMassFlow\(_{zone}\)) / NonCoinCoolMassFlow\(_{sys}\)

SysCoolRetHumRat = (ZoneHumRatAtCoolPeak * DesCoolMassFlow\(_{zone}\)) /NonCoinCoolMassFlow\(_{sys}\)

SysCoolOutTemp = (T\(_{OA,zone\, peak}\) *DesCoolMassFlow\(_{zone}\)) /NonCoinCoolMassFlow\(_{sys}\)

SysCoolOutHumRat = (W\(_{OA,zone\\ peak}\) *DesCoolMassFlow\(_{zone}\)) /NonCoinCoolMassFlow\(_{sys}\)

At the end of the zone loop calculate mixed air conditions and the system sensible cooling capacity.

FracOA = \(\rho\)\(_{air}\) * DesOutAirVolFlow\(_{sys}\)/ NonCoinCoolMassFlow\(_{sys}\)

T\(_{mix}\) = SysCoolOutTemp * FracOA + SysCoolRetTemp * (1 - FracOA)

W\(_{mix}\) = SysCoolOutHumRat * FracOA + SysCoolRetHumRat *

(1 - FracOA)

SysSensCoolCap = C\(_{p,air}\) * NonCoinCoolMassFlow *( T\(_{mix}\)-T\(_{sup}\))

Then (for noncoincident sizing) the variables calculated in section (ii) are moved into the CalcSysSizing Array.

  1. Loop over all of the zones heated by this air loop.

In FinalZoneSizing replace the value in DesHeatCoilInTemp with the user specified HeatSupTemp\(_{sys}\). Do the same for DesHeatCoilInHumRat and HeatSupHumRat. This ensures that zone equipment connected to an air loop will use the system design supply air conditions as coil entering conditions.

NonCoinHeatMassFlow\(_{sys}\) = \(\Sigma\) DesHeatMassFlow\(_{zone}\)

SysHeatRetTemp = (ZoneRetTempAtHeatPeak *DesHeatMassFlow\(_{zone}\))/ NonCoinHeatMassFlow\(_{sys}\)

SysHeatRetHumRat = (ZoneHumRatAtHeatPeak *DesHeatMassFlow\(_{zone}\))/ NonCoinHeatMassFlow\(_{sys}\)

SysHeatOutTemp = (T\(_{OA,zone\\ peak}\) *DesHeatMassFlow\(_{zone}\))/NonCoinHeatMassFlow\(_{sys}\)

SysHeatOutHumRat = (W\(_{OA,zone\\ peak}\) *DesHeatMassFlow\(_{zone}\))/NonCoinHeatMassFlow\(_{sys}\)

At the end of the zone loop calculate mixed air conditions and the system sensible cooling capacity.

FracOA = \(\rho\)\(_{air}\) * DesOutAirVolFlow\(_{sys}\)/ NonCoinHeatMassFlow\(_{sys}\)

T\(_{mix}\) = SysHeatOutTemp * FracOA + SysHeatRetTemp * (1 - FracOA)

W\(_{mix}\) = SysHeatOutHumRat * FracOA + SysHeatRetHumRat *

(1 - FracOA)

SysHeatlCap = C\(_{p,air}\) * NonCoinHeatlMassFlow *( T\(_{sup}\)-T\(_{mix}\))

Then (for noncoincident sizing) the variables calculated in section (ii) are moved into the CalcSysSizing Array.

  1. We now have the calculated system sizing data. This data needs to be altered to take into account the user input system design flow rates (if any), or the fact that the user may have requested that the system flow rate be sized on the ventilation requirement. Note that user specified sizing ratios have already been applied to the zone sizing data which have been used in out preceding system sizing calculation. Thus the user specified sizing ratios do not have to be explicitly taken into account at the system level.

First we move the calculated system sizing data from CalcSysSizing array into the FinalSysSizing array. FinalSysSizing will contain the user modified system design data when we are all done.

Loop over the air loops.

  1. As in the zone case, the user specified system design flow rates are turned into sizing ratios by dividing the user input value by the calculated value. The same strategy is employed for sizing on the ventilation requirement: the design ventilation flow rate is divided by the calculated design flow rate value. For each air loop this gives us a SizRat\(_{cool}\) and SizRat\(_{heat}\).

CoinCoolMassFlow = SizRat\(_{cool}\) * CoinCoolMassFlow\(_{calc}\)

NonCoinCoolMassFlow = SizRat\(_{cool}\) * NonCoinCoolMassFlow\(_{calc}\)

DesCoolVolFlow = SizRat\(_{cool}\) * DesCoolVolFlow\(_{calc}\)

Since the flow rates have been altered the outside air fraction will change. This will alter the design mixed air conditions and lead to an altered value for the cooling capacity. This must be done for the time-step sequence and for the peak value.

Loop over the zone timesteps (index = i).

CoolFlowSeq\(_{sys}\)(i) = SizRat\(_{cool}\) * CoolFlowSeq\(_{sys,calc}\)(i)

FracOA = \(\rho\)\(_{air}\) * DesOutAirVolFlow\(_{sys}\)/ CoolFlowSeq\(_{sys}\)(i)

T\(_{mix}\) = SysCoolOutTempSeq(i) *FracOA +  SysCoolRetTempSeq(i) *(1-FracOA)

SensCoolCapSeq(i) = C\(_{p,air}\) * CoolFlowSeq\(_{sys}\)(i) *( T\(_{mix}\)-T\(_{sup}\))

Do the same calculation for peak cooling.

FracOA = \(\rho\)\(_{air}\) * DesOutAirVolFlow\(_{sys}\)/ DesCoolVolFlow

T\(_{mix}\) = CoolOutTemp\(_{sys}\) *FracOA + CoolRetTemp\(_{sys}\) *(1-FracOA)

W\(_{mix}\) = CoolOutHumRat\(_{sys}\) *FracOA + CoolRetHumRat\(_{sys}\) * (1-FracOA)

SensCoolCap\(_{sys}\) = C\(_{p,air}\) * DesCoolVolFlow\(_{sys}\) *( T\(_{mix}\)-T\(_{sup}\))

T\(_{mix}\) and W\(_{mix}\) are saved in FinalSysSizing .

Do the same calculation for the heating case.

CoinHeatMassFlow = SizRat\(_{heat}\) * CoinHeatMassFlow\(_{calc}\)

NonCoinHeatMassFlow = SizRat\(_{heat}\) * NonCoinHeatMassFlow\(_{calc}\)

DesHeatVolFlow = SizRat\(_{heat}\) * DesHeatVolFlow\(_{calc}\)

Loop over the zone timesteps (index = i).

HeatFlowSeq\(_{sys}\)(i) = SizRat\(_{Heat}\) * HeatFlowSeq\(_{sys,calc}\)(i)

FracOA = \(\rho\)\(_{air}\) * DesOutAirVolFlow\(_{sys}\)/ HeatFlowSeq\(_{sys}\)(i)

T\(_{mix}\) = SysHeatOutTempSeq(i) * FracOA + SysHeatRetTempSeq(i) * (1-FracOA)

HeatCapSeq(i) = C\(_{p,air}\) * HeatFlowSeq\(_{sys}\)(i) *(T\(_{sup}\)-T\(_{mix}\))

Do the same calculation for peak heating.

FracOA = \(\rho\)\(_{air}\) * DesOutAirVolFlow\(_{sys}\)/ DesHeatVolFlow

T\(_{mix}\) = HeatOutTemp\(_{sys}\) *FracOA + HeatRetTemp\(_{sys}\) * (1-FracOA)

W\(_{mix}\) = HeatOutHumRat\(_{sys}\) *FracOA + HeatRetHumRat\(_{sys}\) * (1-FracOA)

HeatCap\(_{sys}\) = C\(_{p,air}\) * DesHeatVolFlow\(_{sys}\) *( T\(_{sup}\)-T\(_{mix}\))

T\(_{mix}\) and W\(_{mix}\) are saved in FinalSysSizing .

DesMainVolFlow\(_{sys}\) = MAX(DesCoolVolFlow\(_{sys}\),DesHeatVolFlow\(_{sys}\))

At this point, the design main flow is the larger of the cooling design flow or the heating design flow. The program stores the information for which was dominant for each airloop in the boolean data structure variables sysSizeCoolingDominant and sysSizeHeatingDominant.

System Sizing Adjustments for Air Terminal Operation[LINK]

Additional adjustments are made to system air flow sizes based on details of the how the zone air terminals connected to the system will eventually operate. These system sizing adjustments were added as of version 8.9 of EnergyPlus. The basic idea is to account for operating details of the air terminal units attached to the system by making adjustments to the system sizing results after the zone equipment has been setup and sized. The routine ManageSystemSizingAdjustments has been added that first sets up the zone equipment and then makes adjustments to the system sizing by mining information from the air terminal models for minimum flow fractions, operating modes during heating, and any user-defined hard sizes to improve accuracy and robustness. Once the air terminals are setup, the actual operating flow rates during heating are often quite different from the design heating flow rate derived from the zone loads. The adjustment method scans all the air terminals and develops accurate values for the minimum and maximum flow rates that will occur during heating operation. Then the system design heating flow rate is adjusted to reflect this new result. For example in a VAV system with Normal action dampers that is cooling dominated, the heating design flow rate is no longer really related to the zone loads, but is the cooling design flow rate times the minimum flow fraction at the dampers. Similarly when heating loads dominate, the cooling design flow rate needs to be adjusted to account for how the terminals will really operate during cooling rather than the cooling-load-based sizing result.

The routine ManageSystemSizingAdjustments adjusts system sizing outcomes based on how the zone air terminals finish out their sizing. The zone models are executed to trigger their sizing routines, by calling ManageZoneEquipment(). Then for each airloop, the routine loops over all the zones attached to that air loop. The air terminal units are scanned to sum design flow rates. Every air terminal connected to a particular air loop is summed for: (1) minimum flow rate during heating operation (airLoopHeatingMinimumFlowRateSum), (2) maximum flow rate during heating operation (airLoopHeatingMaximumFlowRateSum), and (3) maximum flow rate (airLoopMaxFlowRateSum). The routine also stores zone level flow information for Standard 62.1 calculations, Vpz, Vpzmin, Vdz, and Vdzmin for both cooling and heating.

The three summed values for terminal air flows for each airloop are reported to the EIO and table summary report using the outputs "Sum of Air Terminal Maximum Heating Flow Rates [m3/s]," "Sum of Air Terminal Minimum Heating Flow Rates [m3/s]," and "Sum of Air Terminal Maximum Flow Rates [m3/s]."

The summed values are used to "Adjust" the system sizing results in the following ways. The setting for the type of zone sum to use can be either noncoincident or coincident (determined in the input field called Type of Zone Sum to Use in the Sizing:System input object). For noncoincident the design system heating flow rate is set to be the larger of the airloop heating maximum flow rate sum (from the air terminals) and the design flow rate from the load based calculations (described above). The design system main flow rate is set to be the larger of the airloop maximum flow rate sum (from the air terminals) and the design flow rate from the larger of the cooling and heating calculations. The cooling design flow rate is set differently depending on if the air loop was cooling dominant or heating dominant. For noncoincident and cooling dominant, the cooling design air flow rate is set to the design main air flow (typically the airLoopMaxFlowRateSum). For coincident and heating dominant, the cooling design air flow rate is set to the larger of the original cooling-load-based value for flow and the lowest value the air handler will really operate at (from the airLoopHeatingMinimumFlowRateSum).

For coincident type sums, the air terminal summation is not as useful because we generally expect that the straight sum of air terminal sizes will be larger than the coincident sum because by its very nature the straight sum is only expected to match noncoincident approach. Therefore the adjustments are more to keep design flows within bounds set by minimum and maximum sums so that the coincident sum is within physical bounds set by how the air terminals can operate. For coincident and cooling dominant airloops, (a) the heating design flow rate is the larger of the heating minimum flow rate (from the airLoopHeatingMinimumFlowRateSum) and the design heat flow from the coincident design calculation, (b) the main design flow is not typically altered but it will be checked to be at least as large as the heating minimum flow rate (from the airLoopHeatingMinimumFlowRateSum), and (c) the cooling design flow rate is set to the main design flow which we expect to be the result of the coincident design calculation. For coincident and heating dominant airloops, (a) the heating design flow rate is the larger of the heating maximum flow rate (from the airLoopHeatingMaximumFlowRateSum) and the design heat flow rate from the coincident design calculation, (b) the main design flow rate is set to be the larger of the heating maximum flow rate (from the airLoopHeatingMaximumFlowRateSum) and main design flow rate from the coincident sizing calculations, and (c) the cooling design flow rate is set to be the larger of the heating minimum flow rate (from the airLoopHeatingMinimumFlowRateSum) and the cooling design flow rate from the coincident calculation.

The resulting adjusted system sizes for each airloop are reported to the EIO and table summary report using the outputs "Adjusted Heating Design Air Flow Rate [m3/s]," "Adjusted Cooling Design Air Flow Rate [m3/s]," and "Adjusted Main Design Air Flow Rate [m3/s]."

Central Heating Maximum System Air Flow Ratio Sizing[LINK]

The routine ManageSystemSizingAdjustments also includes calculating the ratio for the central heating maximum system air flow rate to the maximum flow rate for the airloop. This ratio is the input field called Central Heating Maximum System Air Flow Ratio in the Sizing:System object and, as of version 8.9, can be autosized. The value is calculated even if the input was not autosized so that inputs can be checked. The corrected values are used to autosize the central heating flow ratio, if set to autosize by the user. The ratio is calculated by dividing the adjusted design heating flow by the adjusted design main flow.

System Design Outdoor Air Flow Rate[LINK]

The design outdoor air flow rate input in the Sizing:System object can be set to autosize. The sizing calculations for determining the system-level design outdoor air flow rate, Vot, depend on the method chosen in the field called System Output Air Method in Sizing:System, either ZoneSum or VentilationRateProcedure, and the design results at the zone level, see Zone Outdoor Air Design Data discussion below. The calculations generally follow the Standard 62.1 approach and are discussed separately in the Demand Controlled Ventilation section elsewhere in the Engineering Reference. The sizing calculations apply the Standard 62.1 calculations separately for both peak cooling design conditions and peak heating design conditions and take the larger to be the single design outdoor air volume flow rate. The predefined table summary report "Standard 62.1 Summary" provides comprehensive summary of the calculations for outdoor air rate. As of version 8.9, the system level summations and flow rate results are based on the adjusted system sizes and zone level summations that mine the individual air terminals attached to the air handlers.

This concludes the system design calculation.

Scalable System HVAC Sizing[LINK]

The scalable system sizing applies to system supply air flow rates and sysyem capacity in coolin and heating modes.

Scalable System Air Flow Sizing

The scalable sizing methods for supply air flow rate allowed are either, FlowPerFloorArea, FractionOfAutosizedCoolingAirflow, or FlowPerCoolingCapacity. The scalable system air flow sizing methods are defined as follows:

FlowPerFloorArea means the program calculates the cooling supply air volume flow rate from zone floor area served by the airloop and user specified Flow Per Floor Area value.

FractionOfAutosizedCoolingAirflow means the program calculates the cooling supply air volume flow rate from user specified fraction and the autosized design cooling supply air volume flow rate value determined by the simulation.

FractionOfAutosizedHeatingAirflow means the program calculates the heating supply air volume flow rate from user specified fraction and the autosized design heating supply air volume flow rate value determined by the simulation.

FlowPerCoolingCapacity means the supply air volume is calculated from user specified flow per cooling capacity and design cooling capacity determined by the simulation.

FlowPerHeatingCapacity means the supply air volume is calculated from user specified flow per heating capacity and design heating capacity determined by the simulation.

Scalable System Capacity Sizing

The scalable sizing methods for system capacity available are: CapacityPerFloorArea, FractionOfAutosizedCoolingCapacity and FractionOfAutosizedHeatingCapacity. The scalable system capacity sizing methods are defined as follows:

CapacityPerFloorArea means the program calculates the design capacity from user specified capacity per floor area and floor area of the zones served by the airloop.

FractionOfAutosizedCoolingCapacity means the program calculates the design cooling capacity from user specified fraction and the auto-sized design cooling capacity.

FractionOfAutosizedHeatingCapacity means the program calculates the design heating capacity from user specified fraction and the auto-sized design heating capacity.