Internal Zone Gains
Services[LINK]
Services are available to help with modeling internal
gains. Internal gains include the usual sources such as
people, lights, plug loads, etc., but in EnergyPlus there can
also be zone gains from the skin losses from certain equipment
such as thermal tanks, electric load center equipment and
refrigeration case credits. Developers adding new device
models, or adding skin loss modeling to exisiting device
models, need to use a call to SetupZoneInternalGains. This
call is defined in DataInterfaces.f90 and contains a number of
optional arguments depending on the type of internal gains
involved. The types of gains that can be added with this call
include convection, radiation, and latent gains to the zone,
convection and latent gains to the return air, carbon dioxide
gains to the zone and generic air contaminant gains to the
zone. For example, the call to register gains for the People
object includes convection(sensible), thermal radiation,
latent, and CO2 and is:
CALL
SetupZoneInternalGain(People(Loop)%ZonePtr, &
‘People’,
&
People(Loop)%Name, &
IntGainTypeOf_People, &
ConvectionGainRate =
People(Loop)%ConGainRate,&
ThermalRadiationGainRate = People(Loop)%RadGainRate,
&
LatentGainRate = People(Loop)%LatGainRate,
&
CarbonDioxideGainRate =
People(Loop)%CO2GainRate)
The refrigerated case model includes terms for sensible and
latent gains to both the zone and the return air. These are
really negative gains, or sinks, and the call to register them
is:
CALL
SetupZoneInternalGain(RefrigCase(CaseNum)%ActualZoneNum,
&
‘Refrigeration:Case’,
&
RefrigCase(CaseNum)%Name , &
IntGainTypeOf_RefrigerationCase, &
ConvectionGainRate =
RefrigCase(CaseNum)%SensZoneCreditRate , &
ReturnAirConvectionGainRate =
RefrigCase(CaseNum)%SensHVACCreditRate , &
LatentGainRate =
RefrigCase(CaseNum)%LatZoneCreditRate , &
ReturnAirLatentGainRate =
RefrigCase(CaseNum)%LatHVACCreditRate )
The module developer needs to program the model to update
the variable in their module, the one being registered by the
call, and central routines use pointers to include the term in
the appropriate energy balances elsewhere in the model. When
adding a new type of internal gain, the new device needs to be
added to arrays in DataHeatBalance.f90 called
ZoneIntGainDeviceTypes and
ccZoneIntGainDeviceTypes and a new unique
“IntGainTypeOf_” parameter.
Internal Zone Gains Services[LINK]
Services are available to help with modeling internal gains. Internal gains include the usual sources such as people, lights, plug loads, etc., but in EnergyPlus there can also be zone gains from the skin losses from certain equipment such as thermal tanks, electric load center equipment and refrigeration case credits. Developers adding new device models, or adding skin loss modeling to exisiting device models, need to use a call to SetupZoneInternalGains. This call is defined in DataInterfaces.f90 and contains a number of optional arguments depending on the type of internal gains involved. The types of gains that can be added with this call include convection, radiation, and latent gains to the zone, convection and latent gains to the return air, carbon dioxide gains to the zone and generic air contaminant gains to the zone. For example, the call to register gains for the People object includes convection(sensible), thermal radiation, latent, and CO2 and is:
CALL SetupZoneInternalGain(People(Loop)%ZonePtr, &
‘People’, &
People(Loop)%Name, &
IntGainTypeOf_People, &
ConvectionGainRate = People(Loop)%ConGainRate,&
ThermalRadiationGainRate = People(Loop)%RadGainRate, &
LatentGainRate = People(Loop)%LatGainRate, &
CarbonDioxideGainRate = People(Loop)%CO2GainRate)
The refrigerated case model includes terms for sensible and latent gains to both the zone and the return air. These are really negative gains, or sinks, and the call to register them is:
CALL SetupZoneInternalGain(RefrigCase(CaseNum)%ActualZoneNum, &
‘Refrigeration:Case’, &
RefrigCase(CaseNum)%Name , &
IntGainTypeOf_RefrigerationCase, &
ConvectionGainRate = RefrigCase(CaseNum)%SensZoneCreditRate , &
ReturnAirConvectionGainRate = RefrigCase(CaseNum)%SensHVACCreditRate , &
LatentGainRate = RefrigCase(CaseNum)%LatZoneCreditRate , &
ReturnAirLatentGainRate = RefrigCase(CaseNum)%LatHVACCreditRate )
The module developer needs to program the model to update the variable in their module, the one being registered by the call, and central routines use pointers to include the term in the appropriate energy balances elsewhere in the model. When adding a new type of internal gain, the new device needs to be added to arrays in DataHeatBalance.f90 called ZoneIntGainDeviceTypes and ccZoneIntGainDeviceTypes and a new unique “IntGainTypeOf_” parameter.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.