The Daylighting:Controls
input objects using the DElight Daylight Method provides an
alternative daylighting model to the SplitFlux method. The
DElight method of analyzing daylighting applies to both simple
apertures (i.e., windows and skylights) and complex
fenestration systems that include geometrically complicated
shading (e.g., roof monitors) and/or optically complicated
glazings (e.g., prismatic or holographic glass). The DElight
daylighting calculation methods are derived from the
daylighting calculations in DOE-2.1E (as are the models
accessed with Daylighting:Controls
input object using the SplitFlux Daylighting Method), and
Superlite, with several key modifications. The engineering
documentation included here focuses on the details of these
differences from methods documented elsewhere. For the
details of the heritage calculations, refer to the section in
this documentation entitled “Daylighting Calculations” and to
[Winkelmann, 1983], [Winkelmann and Selkowitz, 1985], and
[Modest, 1982].
For each point in time, DElight calculates the interior
daylighting illuminance at user specified reference points and
then determines how much the electric lighting can be reduced
while still achieving a combined daylighting and electric
lighting illuminance target. The daylight illuminance level
in a zone depends on many factors, including exterior light
sources; location, size, and visible light transmittance of
simple and complex fenestration systems; reflectance of
interior surfaces; and location of reference points. The
subsequent reduction of electric lighting depends on daylight
illuminance level, design illuminance setpoint, fraction of
zone controlled by reference point, and type of lighting
control.
The DElight daylighting calculation has three main
steps:
1. Daylight Factor Calculation: Daylight
factors, which are ratios of interior illuminance to exterior
horizontal illuminance, are pre-calculated and stored for
later use. The user spcifies the coordinates of one or more
reference points in each daylit zone. DElight first calculates
the contribution of light transmitted through all simple and
complex fenestration systems in the zone to the illuminance at
each reference point, and to the luminance at subdivided nodal
patches of interior surfaces, for a given exterior luminous
environment (including sky, sun, and exterior reflecting
surfaces). The effect of inter-reflection of this initial
light between interior reflecting surfaces is then calculated,
resulting in a final total illuminance at each reference
point. This total illuminace is then divided by the exterior
horizontal illuminance for the given exterior environment to
give a daylight factor. Daylight factors are calculated for
each reference point, for a set of sun positions and sky
conditions that are representative of the building
location.
2. Time-Step Interior Daylighting Calculation:
A daylighting calculation is performed for each heat-balance
time step when the sun is up. In this calculation the
illuminance at the reference points in each zone is found by
interpolating the stored daylight factors using the current
time step sun position and sky condition, then multiplying by
the exterior horizontal illuminance.
3. Electric Lighting Control Calculation: The
electric lighting control system is simulated to determine the
proportion of lighting energy needed to make up the difference
between the daylighting illuminance level at the given time
step, and the design illuminance level. Finally, the zone
lighting electric reduction factor is passed to the thermal
calculation, which uses this factor to reduce the heat gain
from lights.
DElight
Daylight Factor Calculation Differences from SplitFlux
Methods[LINK]
Initial Interior Illuminance/Luminance
Calculation: DElight calculates the total initial
contribution of light transmitted through all simple
fenestration systems (i.e., windows and skylights) in the zone
to the illuminance at each reference point, and to the
luminance at each gridded nodal patch of interior surfaces.
This differs from the models behind the “Daylighting:Controls”
object using the SplitFlux Daylighting Method (henceforth
referred to as “SplitFlux”) in two ways. The first is that
SplitFlux calculates initial illuminace values at reference
points for each pair of reference point and aperture
(window/skylight) in the zone, whereas DElight calculates the
total contribution from all apertures to each reference
point. The second difference from SplitFlux is that the
initial luminance of interior surface nodal patches is
calculated to support the inter-reflection calculation
described below. This calculation uses the same formula as
SplitFlux modified for arbitrarily oriented surfaces (i.e.,
non-horizontal), and to calculate luminance rather than
illuminance. Note however, DElight does not account for
interior surface obstructions (e.g., partitions) in this
initial interior illuminance/luminance distribution. The
SplitFlux method does account for interior surface obstruction
of initial illuminance distribution on reference
points.
Reference Points: DElight allows up to 100
reference points to be arbitrarily positioned with a
daylighting zone. At this time all reference points are
assumed to be oriented on a horizontal virtual surface
“facing” toward the zenith and “seeing” the hemisphere above
the horizontal plane.
Complex Fenestration System Calculation:
DElight calculates the contribution to the initial interior
illuminance at each reference point, and to the luminance at
each gridded nodal patch of interior surfaces, of the light
transmitted by complex fenestration systems (CFS). The
analysis of a CFS within DElight is based on the
characterization of the system using bi-directional
transmittance distribution functions (BTDF), which must be
either pre-calculated (e.g., using ray-tracing techniques) or
pre-measured, prior to analysis by DElight. A BTDF is a set
of data for a given CFS, which gives the ratios of incident to
transmitted light for a range of incoming and outgoing
directions. As illustrated in Figure 1,
a BTDF can be thought of as collapsing a CFS to a “black box”
that is represented geometrically as a flat two-dimensional
light-transmitting surface that will be treated as an aperture
surface in the daylit zone description. For each incoming
direction across the exterior hemisphere of the CFS, varying
portions of that light are transmitted at multiple outgoing
directions across the interior hemisphere of the CFS. The
two-dimensional CFS “surface” and directional hemispheres are
“abstract” in that they may not literally correspond to actual
CFS component geometric details.
The pre-calculated or pre-measured BTDF for a CFS is
independent of its final position and orientation within a
building. Once a specific instance of a CFS aperture has been
positioned within a building, the incident light from all
exterior sources across the CFS exterior hemisphere can be
integrated over all incident directions for each relevant
transmitted direction to determine the light transmitted by
the CFS surface in that direction. The light transmitted by
the CFS aperture is then distributed to surfaces in the zone
according to its non-uniform directionality. The algorithms
for this BTDF treatment of CFS in DElight are still under
development, and are subject to change in the future.
Inter-reflected Interior Illuminance/Luminance
Calculation: The effect of inter-reflection of the
initial interior illuminance/luminance between interior
reflecting surfaces is calculated using a radiosity method
derived from Superlite [Modest, 1982]. This method subdivides
each reflecting surface in the zone into nodal patches and
uses view factors between all nodal patch pairs in an
iterative calculation of the total contribution of reflected
light within the zone. This method replaces the SplitFlux
method, resulting in a more accurate calculation of the varied
distribution of inter-reflected light throughout the zone.
The ability to input up to 100 reference points supports a
more complete assessment of this distribution. Also, the
radiosity method explicitly accounts for interior obstructions
between pairs of nodal patches. The split-flux method used in
the SplitFlux approach only implicitly accounts for interior
surfaces by including their reflectance and surface area in
the zone average surface reflectance calculations.
DElight
Time-Step Interior Daylighting Calculation Differences from
SplitFlux Methods[LINK]
Interior Illuminance Calculation: As
discussed above, DElight only calculates daylight factors for
the total contribution from all windows/skylights and CFS to
each defined reference point. Thus DElight does not support
dynamic control of fenestration shading during the subsequent
time-step calculations, as does SplitFlux method.
Visual Quality: DElight does not currently
calculate a measure of visual quality such as glare due to
daylighting. DElight does calculate luminance on nodal
patches of all interior, reflecting surfaces. A variety of
visual quality metrics could be calculated from these data in
future implementations.
Electric Lighting Control Calculation: Up to
100 reference points can be defined within a DElight
daylighting zone. One or more of these reference points must
be included in the control of the electric lighting system in
the zone. Each reference point input includes the fraction of
the zone controlled by that point. Values of 0.0 are valid,
which allows the definition of reference points for which
interior illuminance levels are calculated, but which do not
control the electric lighting. Any non-zero fraction is thus
the equivalent of a relative weighting given to that reference
point’s influence on the overall electric lighting control.
The sum of all fractions for defined reference points must
less than or equal to 1.0 for this relative weighting to make
physical sense. If the sum is less than 1.0, the remaining
fraction is assumed to have no lighting control.
Modest, M. 1982. A General Model for the Calculation of
Daylighting in Interior Spaces, Energy and Buildings 5, 66-79,
and Lawrence Berkeley Laboratory report no. LBL-12599A.
Winkelmann, F.C. 1983. Daylighting Calculation in
DOE-2. Lawrence Berkeley Laboratory report no.
LBL-11353, January 1983.
Winkelmann, F.C. and S. Selkowitz. 1985. Daylighting
Simulation in the DOE-2 Building
Energy Analysis Program. Energy and Buildings 8,
271-286.
DElight Daylighting Calculations[LINK]
The Daylighting:Controls input objects using the DElight Daylight Method provides an alternative daylighting model to the SplitFlux method. The DElight method of analyzing daylighting applies to both simple apertures (i.e., windows and skylights) and complex fenestration systems that include geometrically complicated shading (e.g., roof monitors) and/or optically complicated glazings (e.g., prismatic or holographic glass). The DElight daylighting calculation methods are derived from the daylighting calculations in DOE-2.1E (as are the models accessed with Daylighting:Controls input object using the SplitFlux Daylighting Method), and Superlite, with several key modifications. The engineering documentation included here focuses on the details of these differences from methods documented elsewhere. For the details of the heritage calculations, refer to the section in this documentation entitled “Daylighting Calculations” and to [Winkelmann, 1983], [Winkelmann and Selkowitz, 1985], and [Modest, 1982].
For each point in time, DElight calculates the interior daylighting illuminance at user specified reference points and then determines how much the electric lighting can be reduced while still achieving a combined daylighting and electric lighting illuminance target. The daylight illuminance level in a zone depends on many factors, including exterior light sources; location, size, and visible light transmittance of simple and complex fenestration systems; reflectance of interior surfaces; and location of reference points. The subsequent reduction of electric lighting depends on daylight illuminance level, design illuminance setpoint, fraction of zone controlled by reference point, and type of lighting control.
The DElight daylighting calculation has three main steps:
1. Daylight Factor Calculation: Daylight factors, which are ratios of interior illuminance to exterior horizontal illuminance, are pre-calculated and stored for later use. The user spcifies the coordinates of one or more reference points in each daylit zone. DElight first calculates the contribution of light transmitted through all simple and complex fenestration systems in the zone to the illuminance at each reference point, and to the luminance at subdivided nodal patches of interior surfaces, for a given exterior luminous environment (including sky, sun, and exterior reflecting surfaces). The effect of inter-reflection of this initial light between interior reflecting surfaces is then calculated, resulting in a final total illuminance at each reference point. This total illuminace is then divided by the exterior horizontal illuminance for the given exterior environment to give a daylight factor. Daylight factors are calculated for each reference point, for a set of sun positions and sky conditions that are representative of the building location.
2. Time-Step Interior Daylighting Calculation: A daylighting calculation is performed for each heat-balance time step when the sun is up. In this calculation the illuminance at the reference points in each zone is found by interpolating the stored daylight factors using the current time step sun position and sky condition, then multiplying by the exterior horizontal illuminance.
3. Electric Lighting Control Calculation: The electric lighting control system is simulated to determine the proportion of lighting energy needed to make up the difference between the daylighting illuminance level at the given time step, and the design illuminance level. Finally, the zone lighting electric reduction factor is passed to the thermal calculation, which uses this factor to reduce the heat gain from lights.
DElight Daylight Factor Calculation Differences from SplitFlux Methods[LINK]
Initial Interior Illuminance/Luminance Calculation: DElight calculates the total initial contribution of light transmitted through all simple fenestration systems (i.e., windows and skylights) in the zone to the illuminance at each reference point, and to the luminance at each gridded nodal patch of interior surfaces. This differs from the models behind the “Daylighting:Controls” object using the SplitFlux Daylighting Method (henceforth referred to as “SplitFlux”) in two ways. The first is that SplitFlux calculates initial illuminace values at reference points for each pair of reference point and aperture (window/skylight) in the zone, whereas DElight calculates the total contribution from all apertures to each reference point. The second difference from SplitFlux is that the initial luminance of interior surface nodal patches is calculated to support the inter-reflection calculation described below. This calculation uses the same formula as SplitFlux modified for arbitrarily oriented surfaces (i.e., non-horizontal), and to calculate luminance rather than illuminance. Note however, DElight does not account for interior surface obstructions (e.g., partitions) in this initial interior illuminance/luminance distribution. The SplitFlux method does account for interior surface obstruction of initial illuminance distribution on reference points.
Reference Points: DElight allows up to 100 reference points to be arbitrarily positioned with a daylighting zone. At this time all reference points are assumed to be oriented on a horizontal virtual surface “facing” toward the zenith and “seeing” the hemisphere above the horizontal plane.
Complex Fenestration System Calculation: DElight calculates the contribution to the initial interior illuminance at each reference point, and to the luminance at each gridded nodal patch of interior surfaces, of the light transmitted by complex fenestration systems (CFS). The analysis of a CFS within DElight is based on the characterization of the system using bi-directional transmittance distribution functions (BTDF), which must be either pre-calculated (e.g., using ray-tracing techniques) or pre-measured, prior to analysis by DElight. A BTDF is a set of data for a given CFS, which gives the ratios of incident to transmitted light for a range of incoming and outgoing directions. As illustrated in Figure 1, a BTDF can be thought of as collapsing a CFS to a “black box” that is represented geometrically as a flat two-dimensional light-transmitting surface that will be treated as an aperture surface in the daylit zone description. For each incoming direction across the exterior hemisphere of the CFS, varying portions of that light are transmitted at multiple outgoing directions across the interior hemisphere of the CFS. The two-dimensional CFS “surface” and directional hemispheres are “abstract” in that they may not literally correspond to actual CFS component geometric details.
The pre-calculated or pre-measured BTDF for a CFS is independent of its final position and orientation within a building. Once a specific instance of a CFS aperture has been positioned within a building, the incident light from all exterior sources across the CFS exterior hemisphere can be integrated over all incident directions for each relevant transmitted direction to determine the light transmitted by the CFS surface in that direction. The light transmitted by the CFS aperture is then distributed to surfaces in the zone according to its non-uniform directionality. The algorithms for this BTDF treatment of CFS in DElight are still under development, and are subject to change in the future.
DElight Time-Step Interior Daylighting Calculation Differences from SplitFlux Methods[LINK]
Interior Illuminance Calculation: As discussed above, DElight only calculates daylight factors for the total contribution from all windows/skylights and CFS to each defined reference point. Thus DElight does not support dynamic control of fenestration shading during the subsequent time-step calculations, as does SplitFlux method.
Visual Quality: DElight does not currently calculate a measure of visual quality such as glare due to daylighting. DElight does calculate luminance on nodal patches of all interior, reflecting surfaces. A variety of visual quality metrics could be calculated from these data in future implementations.
Electric Lighting Control Calculation: Up to 100 reference points can be defined within a DElight daylighting zone. One or more of these reference points must be included in the control of the electric lighting system in the zone. Each reference point input includes the fraction of the zone controlled by that point. Values of 0.0 are valid, which allows the definition of reference points for which interior illuminance levels are calculated, but which do not control the electric lighting. Any non-zero fraction is thus the equivalent of a relative weighting given to that reference point’s influence on the overall electric lighting control. The sum of all fractions for defined reference points must less than or equal to 1.0 for this relative weighting to make physical sense. If the sum is less than 1.0, the remaining fraction is assumed to have no lighting control.
References[LINK]
Modest, M. 1982. A General Model for the Calculation of Daylighting in Interior Spaces, Energy and Buildings 5, 66-79, and Lawrence Berkeley Laboratory report no. LBL-12599A.
Winkelmann, F.C. 1983. Daylighting Calculation in DOE-2. Lawrence Berkeley Laboratory report no. LBL-11353, January 1983.
Winkelmann, F.C. and S. Selkowitz. 1985. Daylighting Simulation in the DOE-2 Building Energy Analysis Program. Energy and Buildings 8, 271-286.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.