The Airflow Network model provides the ability to simulate
multizone airflows driven by wind and also by forced air
distribution systems. The model can also simulate the heat and
moisture gains or losses from the air distribution system
itself (e.g., ductwork). When modeling air distribution
systems, the current version of the Airflow Network model is
allowed to simulate multiple forced air systems (i.e., AirLoopHVAC
object). Each forced air system allows a constant volume
supply air fan (Fan:ConstantVolume or Fan:OnOff), a VAV supply
air fan (Fan:VariableVolume), or a fan system model (Fan:SystemMode). The capabilities
of the model are to:
Simulate zone pressures due to envelope leakage and
forced air distribution during HVAC system fan
operation
Simulate node pressures in a forced air distribution
system during HVAC system fan operation
Calculate multizone airflows due to forced air, wind,
and surface leakage, including adjacent zones and outdoors,
during HVAC system fan operation
Simulate distribution system airflows, including supply
and return air leaks, during HVAC system fan
operation
Simulate air distribution system node temperatures and
humidity ratios during HVAC system fan operation
Calculate duct conduction losses during HVAC system fan
operation
Calculate vapor diffusion losses of ducts during HVAC
system fan operation
Calculate sensible and latent loads on the surrounding
zones due to supply and return air leaks in the air
distribution system during HVAC system fan operation
Simulate zone pressures due to envelope leakage driven
by wind when the HVAC system fan is off or if no air
distribution system is specified
Calculate multizone airflows due to wind and surface
leakage, including adjacent zones and outdoors when the HVAC
system fan is off or if no air distribution system is
specified
Allow zone exhaust fans to be included as part of the
airflow network
For airflow networks with a forced air distribution
system, calculate zone sensible and latent loads for two
different supply air fan operation modes as required: cycling
fan, cycling compressor (CyclingFanAndCompressor) and
continuous fan, cycling compressor
(ContinuousFanWithCyclingCompressor)
When multiple forced air systems (AirloopHVAC) are
present in the idf, all systems must be used in the Airflow
Network model.
The AirflowNetwork:MultiZone:Zone
object specifies the ventilation control that applies to all
of the openable exterior and interior windows and doors in the
corresponding thermal zone. Surface-level ventilation control
can be used to override the zone-level ventilation control if
required (see AirflowNetwork: MultiZone:Surface object
below).
AirflowNetwork:MultiZone:Surface
object indicates whether a heat transfer surface (wall,
window, etc.) has a crack or opening and references an object
in the list below that gives the air flow characteristics of
that crack, opening, or zone exhaust fan. The AirflowNetwork:MultiZone:Surface
object can also be used to specify individual ventilation
control for openable exterior and interior windows and
doors.
AirflowNetwork:Distribution:Component
objects consist of Leak, LeakageRatio, Duct,
ConstantPressureDrop, Fan, Coil, TerminalUnit,
OutdoorAirFlow and ReliefAirFlow.
The components provide a relationship between pressure and
airflow. The Leak and
Leakage components can be used to simulate
supply and/or return leaks in an air distribution
system. The Duct
and ConstantPressureDrop components can be
used to deliver forced air into conditioned spaces. The
components Fan, Coil, and TerminalUnit
reference normal EnergyPlus objects. OutdoorAirFlow,
and ReliefAirFlow specify the outdoor air flow rate
set by the Controller:OutdoorAir
object in the model. The Airflow Network model gets
information from these objects to perform an airflow network
simulation.
Figure 1
shows the relationships among AirflowNetwork:MultiZone objects
and between AirflowNetwork:MultiZone objects and regular
EnergyPlus objects. In this figure an arrow from object A to
object B means A references B, i.e., one of the inputs in A is
the name of object B. For example, one input for
AirflowNetwork: MultiZone:Surface is the name of a heat
transfer surface, and another is the name of a crack or
opening object. The arrow between AirflowNetwork:MultiZone:Surface
and AirflowNetwork:MultiZone:ExternalNode
is shown dashed to indicate that this reference is not used
when wind pressure coefficients are calculated by the program
rather than being input by the user.
Figure 1
also shows the relationships among AirflowNetwork:Distribution
objects and between AirflowNetwork:Distribution objects and
regular EnergyPlus objects. The AirflowNetwork:Distribution:Linkage
objects link two nodes from AirflowNetwork:Distribution:Node
and/or AirflowNetwork:MultiZone:Zone
objects with a component defined in the object
AirflowNetwork:Distribution:Component. The solid arrows show a
reference from object A to object B. The dashed arrows
indicate the components which can be used in a linkage object.
The red arrows pointing to the Zone
object indicate the components that interact with the zone
air. For example, the temperature in a zone where a supply
leak terminates is used to calculate duct leakage energy loss.
The temperature in a zone where a duct component is located is
also used to calculate duct conduction loss.
Relationships among
AirflowNetwork objects (right-hand side) and between
AirflowNetwork objects and regular EnergyPlus objects. An
arrow from object A to object B means that A references B.
[fig:relationships-among-airflownetwork-objects]
Much of the information needed for the air flow calculation
is automatically extracted from the building description for
thermal modeling. This includes things like the volume and
neutral height of the zones, and the orientation and location
of the building surfaces that contain cracks or openings
through which air flows. From all of this information the
program creates a “pressure-flow network” that is solved each
timestep using iterative solution methods to obtain the
unknown pressures and air flows.
Figure 2
shows a plan view of a very simple air flow network that you
can construct using the above AirflowNetwork objects. There
are three thermal zones, Zone-1, Zone-2 and Zone-3. There are
openable exterior windows—Window-1, Window-2 and Window-3—and
openable interior doors—Door-12 and Door-23. Two External
Nodes are indicated. ExternalNode-1 is associated with the
façade that contains Window-1 and Window-2. ExternalNode-2 is
associated with the façade containing Window-3.
One possible air flow pattern is shown in this figure. The
actual air flow pattern in a particular timestep, and the size
of the flows, depends on many factors, such as (1) What is the
wind pressure distribution seen by the exterior windows? (2)
Are the exterior windows open or closed, and if open, how far
are they open? (3) Are the interior doors open or closed? (4)
What are the air temperature differences between zones and
between zones and the outdoor air (which affect buoyancy
flows)?
Plan view of a simple air flow
network showing a possible air flow pattern in which all of
the windows and doors are open. [fig:plan-view-of-a-simple-air-flow-network]
Figure 2
shows a possible air flow pattern in which all of the windows
and doors are open. Associated with the external nodes are
wind pressure coefficient distributions as a function of wind
direction that are input using two
AirflowNetwork:MultiZone:Wind Pressure Coefficient objects.
The nature of the air flows through the windows and doors is
specified using AirflowNetwork:MultiZone:Component:DetailedOpening
and AirflowNetwork:MultiZone:Component:SimpleOpening
objects. The Airflow Network model calculates the flows each
system timestep depending on various factors, including wind
direction and speed, size and vertical position of openings,
outdoor air temperature, and zone air temperatures.
Airflow
Network Example Files (included in the installation)[LINK]
Calculate air flows and pressures in ducts or other
components of a forced air distribution system.
Calculate zone loads when the supply air fan cycles on
and off during a system timestep using the
CyclingFanAndCompressor fan operation mode
(Fan:OnOff).
Determine the impact of zone exhaust fans on air flows,
pressures, air temperatures/humidity levels and energy
consumption.
The model is restricted to using a constant volume or
variable volume fan (Fan:ConstantVolume, Fan:OnOff,
and Fan:VariableVolume).
Air circulation and/or air temperature stratification
within a thermal zone. For example, you should not try to
divide a high space, such as an atrium, into subzones
separated by artificial horizontal surfaces that have cracks
or openings with the expectation that AirflowNetwork will give
you a realistic temperature in each subzone and/or a realistic
air flow between subzones.
The model is restricted to two types of air
distribution equipment terminal units
(AirTerminal:SingleDuct:ConstantVolume:Reheat and
AirTerminal:SingleDuct:VAV:Reheat).
Supply and return leaks are not allowed in an AirLoopHVAC.
They can only be modeled in the Zone
Equipment portion of the air loop (i.e., return leaks may be
modeled between the zone return node and the zone mixer inlet
or the zone mixer outlet and the zone equipment loop outlet;
and supply leaks may be modeled between the zone equipment
loop inlet and the AirLoopHVAC:ZoneSplitter
inlet node or the AirLoopHVAC:ZoneSplitter
outlet node and the zone supply node).
An air distribution system must be located inside the
building (i.e., the ducts must pass through zones within the
building).
The input specifications consist of five main sections:
AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol)
object, AirflowNetwork multizone data objects, AirflowNetwork
distribution node objects, AirflowNetwork distribution
component objects, and AirflowNetwork
distribution linkage objects. Each of these object
types is described in detail below.
The following selections are available to control the
Airflow Network simulation:
MultiZoneWithDistribution: MultiZone air
flow calculations are performed during all simulation
timesteps, including the impacts of the air distribution
system when a HVAC system fan is operating. Any
ZoneInfiltration:*,
ZoneVentilation:*, ZoneMixing
and ZoneCrossMixing
objects specified in the input data file are not
simulated.
MultiZoneWithoutDistribution: MultiZone
air flow calculations are performed during all simulation
timesteps, but the air distribution system portion of the
network is not modeled even if it is specified in the input
data file. Any ZoneInfiltration:*,
ZoneVentilation:*, ZoneMixing
and ZoneCrossMixing
objects specified in the input data file are not
simulated.
MultiZoneWithDistributionOnlyDuringFanOperation:
MultiZone air flow calculations, including the impacts of the
air distribution system, are only performed when the HVAC
system fan is operating. Any
ZoneInfiltration:*,
ZoneVentilation:*, ZoneMixing
and ZoneCrossMixing
objects specified in the input data file are used when the
HVAC system fan is OFF (if none are specified, then no air
flow calculations are performed when the fan is OFF).
NoMultiZoneOrDistribution: No multizone
air flow calculations (with or without the air distribution
system portion of the network) are performed during the
simulation. Any ZoneInfiltration:*,
ZoneVentilation:*, ZoneMixing
and ZoneCrossMixing
objects specified in the input data file are simulated (if
none are specified, then no air flow calculations are
performed). Note: Having an input data file with no AirflowNetwork:SimulationControl
objects gives the same impact – no multizone air flow
calculations. However, this choice is provided as a
convenience to the user to easily disable the multizone air
flow calculations for an input data file that already contains
AirflowNetwork objects.
Determines whether the wind pressure coefficients are input
by the user or calculated. The choices are
Input or
SurfaceAverageCalculation, with the default
being SurfaceAverageCalculation.
The second choice, SurfaceAverageCalculation, should only
be used for rectangular buildings. In this
case surface-average wind pressure coefficients vs. wind
direction are calculated by the program for the four vertical
façades and the roof based on user entries for “Building
Type,” “Azimuth Angle of Long Axis of Building,”
and “Ratio of Building
Width Along Short Axis to Width Along Long Axis” (see
description of these fields below). With this choice you do
not have to enter any of the following
objects: AirflowNetwork:MultiZone: Wind Pressure Coefficient
Array, AirflowNetwork:MultiZone:ExternalNode
and AirflowNetwork:MultiZone:WindPressureCoefficientValues.
Field:
Height Selection for Local Wind Pressure Calculation[LINK]
Determines whether the local wind pressure is calculated
based on either given external node heights or surface opening
heights. The choices are ExternalNode or
OpeningHeight, with the default being
OpeningHeight. The local outdoor wind speed calculation
procedure is given in the section of “Local Wind Speed
Calculation” in the Engineering Reference. The calculation
procedure requires the height input.
If ExternalNode, the heights given in the
AirflowNetwork:MultiZone:ExternalNode
objects are used to calculate local wind pressures based on
the given height local wind speed. Used only if Wind Pressure
Coefficient Type = INPUT (see description of previous
field).
If OpeningHeight, the number of the AirflowNetwork:MultiZone:ExternalNode
objects has to be equal to the number of external surfaces
defined in the AirflowNetwork:MultiZone:Surface
objects. The centroids in the z direction of the AirflowNetwork:MultiZone:Surface
objects are the heights used in the local wind pressure
calculation with the given height wind speed. The input is
required if Wind Pressure Coefficient Type = INPUT (see
description of previous field).
If Wind Pressure Coefficient Type =
SurfaceAverageCalculation, a value in this
field is not required and a blank may be entered. The default
choice is used internally to generate the AirflowNetwork:MultiZone:ExternalNode
objects
Used only if Wind Pressure Coefficient Type =
SurfaceAverageCalculation. The choices for Building
Type are LowRise and HighRise, with the default being
LowRise.
LowRise corresponds to a rectangular building whose height
is less than three times the width of the footprint
(w\(_{short}\) in
Figure 3)
and is less than three times the length of the footprint
(w\(_{long}\) in the
same figure).
HighRise corresponds to a rectangular building whose height
is more than three times the width of the footprint
(w\(_{short}\) in
Figure 3)
or is more than three times the length of the footprint
(w\(_{long}\) in the
same figure).
The maximum number of iterations allowed in finding an
AirflowNetwork solution. If the number of iterations at each
simulation timestep is above the maximum number of iterations
defined by this field, the program could not find the solution
and a Severe error is issued and the program is aborted. The
default value is 500.
Designates which method is used for AirflowNetwork
initialization. The choices for Initialization Type are
LinearInitializationMethod and ZeroNodePressures, with the
default being ZeroNodePressures.
The solution is assumed to have converged when \({{\left| {\,\sum\limits_{} {{{\mathop
m\limits^ \bullet }_{_i}}} } \right|} \mathord{\left/
{\vphantom {{\left| {\,\sum\limits_{} {{{\mathop m\limits^
\bullet }_{_i}}} } \right|} {\sum\limits_{} {\left| {{{\mathop
m\limits^ \bullet }_{_i}}} \right|} }}} \right. }
{\sum\limits_{} {\left| {{{\mathop m\limits^ \bullet }_{_i}}}
\right|} }}\) is less than the value specified for this
input field. This convergence criteria is equivalent to the
ratio of the absolute value of the sum of all network airflows
(\(\left| {\sum {{{\mathop m\limits^
\bullet }_{_i}}} } \right|\) ) to the sum of network
airflow magnitudes (\(\sum\limits_{}^{} {\left| {{{\mathop
m\limits^ \bullet }_{_i}}} \right|}\) ). The default
value is 1.0x10\(^{-4}\).
The solution is assumed to have converged when the
summation of the absolute value of all network airflows (\(\left| {\sum {{{\mathop m\limits^
\bullet }_{_i}}} } \right|\) ) is less than the value
specified for this input field. The default value is
1.0x10\(^{-6}\).
If the ratio of successive pressure corrections is less
than this limit, use Steffensen acceleration algorithm (Ref.
AirflowNetwork Model in the EnergyPlus Engineering Reference).
The range for this field is -1 to 1, with the default value
being -0.5.
Field:
Azimuth Angle of Long Axis of Building[LINK]
Gives the orientation of a rectangular building for
calculating wind pressure coefficients. This is the smaller of
the angles, measured clockwise, between North and the long
axis of the building (see Figure 3).
Used only if Wind Pressure Coefficient Type =
SurfaceAverageCalculation. The range for this input is 0 to
180, with the default value being 0.
Field:
Ratio of Building Width Along Short Axis to Width Along Long
Axis[LINK]
This is the aspect ratio of a rectangular footprint. It is
given by the width of the footprint along its short axis
divided by the width along the long axis (see Figure 3).
If the footprint is square, the value of this field is 1.0.
Used only if Wind Pressure Coefficient Type =
SurfaceAverageCalculation. The range for this input is > 0
to 1, with the default value being 1.
Footprint of a rectangular
building showing variables used by the program to calculate
surface-average wind pressure coefficients. The angle a is the
“Azimuth Angle of Long Axis of Building.” \(w_{short}/w_{long}\) is the
“Ratio of Building Width Along Short Axis to Width Along Long
Axis.” [fig:footprint-of-a-rectangular-building-showing]
Field:
Height Dependence of External Node Temperature[LINK]
This is an optional field. Input is Yes or No. The default
is No. Yes is that external node temperature is dependent on
node height. No means that external node temperature is
calculated with zero height.
This is an optional field. Input is Yes or No. The default
is No. Set this input to Yes to have zone equipment that are
currently unsupported in the AirflowNetwork model allowed in
the simulation. Setting this field to Yes, allows the
following equipment to be modeled along an AirflowNetwork
model: ZoneHVAC:Dehumidifier, ZoneHVAC:EnergyRecoveryVentilator,
WaterHeater:HeatPump:*. The AirflowNetwork model will exclude
mass balance in these equipment objects and assume the mass
flows are self-balanced in the equipment objects.
An IDF example is shown below:
AirflowNetwork:SimulationControl,
AirflowNetwork_All, !- Name
MultiZoneWithDistribution, !- AirflowNetwork Control
Input, !- Wind Pressure Coefficient Type
Every 30 Degrees, !- AirflowNetwork Wind Pressure Coefficient Array Name
OpeningHeight, !- Height Selection for Local Wind Speed Calculation
LowRise, !- Building Type
500, !- Maximum Number of Iterations {dimensionless}
ZeroNodePressures, !- Initialization Type
1.0E-05, !- Relative Airflow Convergence Tolerance {dimensionless}
1.0E-06, !- Absolute Airflow Convergence Tolerance {kg/s}
-0.5, !- Convergence Acceleration Limit {dimensionless}
0.0, !- Azimuth Angle of Long Axis of Building {deg}
1.0; !- Ratio of Building Width Along Short Axis to Width Along Long Axis
If the AirflowNetwork:SimulationControl
object is not provided in an input file, the default input
object will be created by the program internally, as long as
following conditions are satisfied:
AirflowNetwork:SimulationControl,
AFNDefaultControl, !- Name
MultizoneWithoutDistribution, !- AirflowNetwork Control
SurfaceAverageCalculation, !- Wind Pressure Coefficient Type
OpeningHeight, !- Height Selection for Local Wind Pressure Calculation
LOWRISE, !- Building Type
500, !- Maximum Number of Iterations {dimensionless}
ZeroNodePressures, !- Initialization Type
1.0E-04, !- Relative Airflow Convergence Tolerance {dimensionless}
1.0E-06, !- Absolute Airflow Convergence Tolerance {kg/s}
-0.5, !- Convergence Acceleration Limit {dimensionless}
0.0, !- Azimuth Angle of Long Axis of Building {deg}
1.0; !- Ratio of Building Width Along Short Axis to Width Along Long Axis
AirflowNetwork:MultiZone data objects are used to calculate
multizone airflows. This section describes the input
requirements for the following objects:
AirflowNetwork:MultiZone:Zone
AirflowNetwork:MultiZone data objects are used to calculate
multizone airflows. This section describes the input
requirements for the following objects:
This object is required to perform Airflow Network
calculations. Note that ventilation control for all openings
is provided at the zone level as default and individual
ventilation control of a surface opening can be used to
override the zone-level control (see the AirflowNetwork:MultiZone:Surface
object description below).
Specifies the type of zone-level natural ventilation
control.
Let T\(_{out}\) equal the
outdoor air temperature, T\(_{zone}\) equal the previous
timestep’s zone air temperature, T\(_{set}\) equal the Vent
Temperature Schedule value, H\(_{zone}\) equal the specific
enthalpy of zone air from the previous timestep, and H\(_{out}\) equal the specific
enthalpy of outdoor air. Then the four allowed choices for
Ventilation Control Mode are:
NoVent: All of the zone’s openable windows
and doors are closed at all times independent of indoor or
outdoor conditions. The Venting Availability Schedule is
ignored in this case. This is the default value for this
field.
Temperature: All of the zone’s openable
windows and doors are opened if T\(_{zone}\) > T\(_{out}\)and
T\(_{zone}\) > T\(_{set}\)and
Venting Availability Schedule (see below) allows venting.
Enthalpy: All of the zone’s openable
windows and doors are opened if H\(_{zone}\) > H\(_{out}\)and
T\(_{zone}\) > T\(_{set}\)and
Venting Availability Schedule allows venting.
Constant: Whenever this object’s Venting
Availability Schedule allows venting, all of the zone’s
openable windows and doors are open, independent of indoor or
outdoor conditions. Note that “Constant” here means that the
size of each opening is fixed while venting; the air flow
through each opening can, of course, vary from timestep to
timestep.
ASHRAE55Adaptive: All of the zone’s
operable windows and doors are opened if the operative
temperature is greater than the comfort temperature (central
line) calculated from the ASHRAE Standard 55-2010 adaptive
comfort model and Venting Availability Schedule allows
venting.
CEN15251Adaptive: All of the zone’s
operable windows and doors are opened if the operative
temperature is greater than the comfort temperature (central
line) calculated from the CEN15251 adaptive comfort model and
Venting Availability Schedule allows venting.
Field:
Ventilation Control Zone Temperature Setpoint Schedule
Name[LINK]
The name of a schedule of zone air temperature set points
that controls the opening of windows and doors in the thermal
zone to provide natural ventilation. This setpoint is the
temperature above which all the openable windows and doors in
the zone will be opened if the conditions described in the
previous field Ventilation Control Mode are met.
(The discussion under the field Window/Door Opening Factor
in the AirflowNetwork:MultiZone:Surface
object describes how the actual opening area of a window or
door in a particular timestep is determined.)
Modulation of Openings
The following five fields can be used to modulate the
window/door openings when Ventilation Control Mode =
Temperature or Enthalpy. These fields determine a factor
between 0 and 1 that multiplies the opening factor of each
window and door in the zone according to the control action
shown in Figure 5
for Ventilation Control Mode = Temperature and in Figure 6
for Ventilation Control Mode = Enthalpy. Modulation of the
openings can reduce the large temperature swings that can
occur if the windows/doors are open too far when they are
venting, especially when there is a large inside-outside
temperature difference.
The modulation takes the following form when Ventilation
Control Mode = Temperature:
if T\(_{zone}\) - T\(_{out}\) < = [Lower Value
on Inside/Outside Temperature Difference for Modulating the
Venting Open Factor] then Multiplication
factor = 1.0
if [Lower Value on Inside/Outside
Temperature Difference for Modulating the Venting Open Factor]
< T\(_{zone}\) - T\(_{out}\) < [Upper Value on
Inside/Outside Temperature Difference for Modulating the
Venting Open Factor] then Multiplication
factor varies linearly from 1.0 to [Limit Value on Multiplier
for Modulating Venting Open Factor]
if T\(_{zone}\) - T\(_{out}\) > = [Upper Value on
Inside/Outside Temperature Difference for Modulating the
Venting Open Factor] then Multiplication
factor = [Limit Value on Multiplier for Modulating Venting
Open Factor]
One way of “tuning” the following modulation control
parameters is to perform a sensitivity analysis for winter
and/or summer design days to determine what combination of
values causes the biggest reduction in zone air temperature
fluctuations due to venting.
Note that the default values for the following fields are
such that, if none of the fields are specified, the default
values are assigned.
See Figure 5
or Figure 6.
This field applies only if Ventilation Control Mode =
Temperature or Enthalpy. This value may be from zero to 1.0,
with the default being 0.0.
Field:
Indoor and Outdoor Temperature Difference Lower Limit For
Maximum Venting Open Factor[LINK]
See Figure 5.
This field applies only if Ventilation Control Mode =
Temperature. This value may be from zero to less than 100 °C,
with the default being 0 °C. The value for this field must be
less than the value specified for the following field.
Field:
Indoor and Outdoor Temperature Difference Upper Limit for
Minimun Venting Open Factor[LINK]
See Figure 5.
This field applies only if Ventilation Control Mode =
Temperature. This value must be greater than 0 °C, with the
default being 100 °C. The value for this field must be greater
than the value specified for the previous field..
Field:
Indoor and Outdoor Enthalpy Difference Lower Limit For Maximum
Venting Open Factor[LINK]
See Figure 6.
This field applies only if Ventilation Control Mode =
Enthalpy. This value may be from zero to less than 300,000
J/kg, with the default being 0 J/kg. The value for this field
must be less than the value specified for the following
field.
Field:
Indoor and Outdoor Enthalpy Difference Upper Limit for Minimun
Venting Open Factor[LINK]
See Figure 6.
This field applies only if Ventilation Control Mode =
Enthalpy. This value must be greater than zero, with the
default being 300,000 J/kg. The value for this field must be
greater than the value specified for the previous field.
The name of a schedule that specifies when venting is
available. A zero or negative schedule value means venting is
not allowed. A value greater than zero means venting can occur
if other venting control conditions (specified by Ventilation
Control Mode and Vent Temperature Schedule Name) are
satisfied. This schedule name should not be confused with Vent
Temperature Schedule Name.
If a Venting Availability Schedule Name is not specified,
it is assumed that venting is always available.
Using Venting Availability Schedule allows you to turn off
venting at certain times of the day (at night, for example),
of the week (on weekends, for example), or of the year (during
the winter, for example).
If used with Ventilation Control Mode = Constant, the
ventilation rate is constant only when this schedule allows
venting; otherwise the ventilation rate is set to zero.
If Ventilation Control Mode = NoVent, this schedule has no
effect.
Field:
Single Sided Wind Pressure Coefficient Algorithm[LINK]
Specifies the type of single sided wind pressure
coefficient algorithm to be used for the zone. This field is
optional and is only used if Wind Pressure Coefficient Type is
set to SurfaceAverageCalculation. The default is Standard and
the two valid choices are:
Standard: A single wind pressure
coefficient is applied to all openings in the zone, as
calculated using SurfaceAverageCalculation.
Advanced: EnergyPlus calculates modified
wind pressure coefficients for the two openings in the zone.
This model is only valid for zones with two openings, both of
which are on a single façade (i.e. are coplanar). For zones
with more than two openings, consider combining the openings
into two. The modified wind pressure coefficients account for
wind direction and turbulence effects on single sided
ventilation rates. See the Engineering Reference for a
detailed description of the Advanced algorithm. When the
Advanced algorithm is selected, the difference between the two
modified wind pressure coefficients are output to the .eio
file.
This is the whole building width along the direction of the
facade of this zone, or \(W_F\) in Figure 4. This field
is used in the Single Sided Wind Pressure Coefficient
Algorithm. This field is optional and is only used if the
Single Sided Wind Pressure Coefficient Algorithm is set to
Advanced. The value must be greater than 0.0 m, with the
default being 10 m.
Footprint of a rectangular
building showing \(W_F\), the
“Façade Width”, used by the Single Sided Wind Pressure
Coefficient Algorithm. [fig:single-sided-footprint]
The name of an AirlowNetwork:OccupantVentilationControl
object. The object is used to perform advanced window opening
control based on occupant conditions. When an object name is
given, advanced window opening control is performed and, the
ventilation control defined in the Ventilation Control Mode
field will be overridden.
Note: The Occupant Ventilation Control
object can be assigned to a zone
(AirflowNetwork:MultiZone:Zone) or a surface
(AirflowNetwork:MultiZone:Surface). When the object is
assigned to a zone, the Occupant Ventilation Control is
assigned to the surfaces belonging to the zone automatically.
The surface objects must have an associated AirflowNetwork:MultiZone:Component:DetailedOpening,AirflowNetwork:MultiZone:Component:HorizontalOpening,
or AirflowNetwork:MultiZone:Component:SimpleOpening
component specified in the field of Leakage Component Name.
All output variables will be shown under surface names only,
and not under zone names.
Modulation of venting area
according to inside-outside temperature difference. [fig:modulation-of-venting-area-according-to]Modulation of venting area
according to inside-outside enthalpy difference. [fig:modulation-of-venting-area-according-to-001]
Note: In order to establish an airflow
network, each AirflowNetwork:MultiZone:Zone
object must have at least two surfaces defined with AirflowNetwork:MultiZone:Surface
objects, so that air can flow from one zone into other zones
(or to outdoors) through the network (air mass flow
conserved). In addition, for all AirflowNetwork:MultiZone:Surface
objects facing the same Zone
(ref. BuildingSurface:Detailed), at least two different
environments must be defined for the other side of these
surfaces (e.g., an external node and an adjacent zone, two
adjacent zones, or two external nodes).
An IDF example is shown below:
AirflowNetwork:MultiZone:Zone,
RESISTIVE ZONE, !- Name of Associated Thermal Zone
Temperature, !- Ventilation Control Mode
WindowVentSched, !- Vent Temperature Schedule Name
0.3, !- Limit Value on Multiplier for Modulating Venting Open Factor
!- {dimensionless}
5.0, !- Lower Value on Inside/Outside Temperature Difference for
!- Modulating the Venting Open Factor {deltaC}
10.0, !- Upper Value on Inside/Outside Temperature Difference for
!- Modulating the Venting Open Factor {deltaC}
0.0, !- Lower Value on Inside/Outside Enthalpy Difference for Modulating
!- the Venting Open Factor {J/kg}
300000.0, !- Upper Value on Inside/Outside Enthalpy Difference for Modulating
!- the Venting Open Factor {J/kg}
VentingSched; !- Venting Availability Schedule Name
The AirflowNetwork:MultiZone:Surface
object specifies the properties of a surface “linkage” through
which air flows. This linkage is always associated with a
building surface (wall, roof, floor, or a ceiling) or
subsurface (door, glass door, or window) with both faces
exposed to air. The linkage specifies two connected nodes: two
zone nodes defined in AirflowNetwork:MultiZone:Zone
objects based on inside and outside face environment for an
interior surface, or a zone node defined in an AirflowNetwork:MultiZone:Zone
object based on inside face environment and an external node
defined in an AirflowNetwork:MultiZone:ExternalNode
object for an exterior surface. The associated leakage
component for this surface can be a crack (or surface
effective leakage area) in an exterior or interior heat
transfer surface or subsurface, or an exterior or interior
window, door or glass door (heat transfer subsurface) that can
be opened to allow air flow. The allowed surface air leakage
components are:
The three “opening” components are used to modulate
openness based on required conditions.
The AirflowNetwork:MultiZone:Surface
object allows a heat transfer surface or subsurface to have
one crack (or one surface effective leakage area object), or a
subsurface (i.e., window, door or glass door) to have one
opening (detailed, simple, or horizontal).
An interior heat transfer surface
(BuildingSurface:Detailed) whose surface name is used as the
input for the Outside Boundary Condition Object field is
adiabatic and is not allowed as an AirflowNetwork:MultiZone:Surface.
A heat transfer surface defined in the
BuildingSurface:Detailed:ExteriorNaturalVentedCavity is also
not allowed.
When a non-rectangular subsurface is used, the model will
automatically convert it into a rectangular subsurface using
equivalent width and height based on an entered choice from
the Equivalent Rectangle Method field or a default choice.
When an air boundary surface or subsurface is used
(Construction:AirBoundary), all types of leakage component are
allowed except AirflowNetwork:MultiZone:Component:ZoneExhaustFan.
The only allowed venting control type for an air boundary
surface is Constant, and the venting schedule is ignored
(which means the opening is always fully open at the specified
Window/Door Opening Factor, or Crack Factor). EnergyManagementSystem:Actuator
“AirFlow Network Window/Door Opening” is available for special
applications where control of the air boundary opening is
required.
This is the name of the corresponding surface (wall, roof,
ceiling, floor, window, door or glass door).
Information on this surface is used by the program as
follows:
For a linkage associated with an exterior heat transfer
surface: air flow through this linkage is between the outside
environment and the thermal zone to which the surface
belongs.
For a linkage associated with an interior (i.e.,
interzone) heat transfer surface: air flow through this
linkage is between the thermal zones separated by the surface
(i.e., the thermal zone associated with the inside face
environment and the thermal zone associated with the outside
face environment).
This heat transfer surface determines the height of the
linkage, which is used in calculating buoyancy-related flow
through the linkage.
The surface may be an air boundary surface or
subsurface (Construction:AirBoundary).
Note: It is possible to define an
interzone surface twice in EnergyPlus, once in each of the
zones that the surface separates. Previously this was a
requirement of EnergyPlus (prior to version 2.0), but now it
is optional and the user also has the option of only defining
the surface once (EnergyPlus defines the second surface
automatically within the program). For each interzone surface,
use only one (of possible two) interzone surface names in the
AirflowNetwork:MultiZone:Surface
object for “Surface Name.” Do not enter two
AirflowNetwork:MultiZone:Surface
objects corresponding to the two possible interzone names.
This would cause the air flow through the surface to be
counted twice.
If the name of an opening component
(i.e. AirflowNetwork:MultiZone:Component:DetailedOpening.
AirflowNetwork:MultiZone:Component:HorizontalOpening, or AirflowNetwork:MultiZone:Component:SimpleOpening
is given here, then the Surface Name in the previous field
must be that of a window, door or glass door heat transfer
subsurface or a building surface which is an air boundary.
Otherwise an error message will be reported.
If the name of an AirflowNetwork:MultiZone:Surface:Crack
object or AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea
object is given here, the program will position the crack at
the average height of the associated heat transfer surface or
subsurface. The user can define multiple heat transfer
surfaces (e.g., split a wall into several surfaces) to be more
precise in establishing the crack location. Similarly, the
user can define multiple heat transfer surfaces if a wall, for
example, has multiple cracks or openings that need to be
defined individually.
If the name of an AirflowNetwork:MultiZone:Component:ZoneExhaustFan
is given here, then the Surface Name in the previous field
must be that of an exterior heat transfer surface. The zone
name defined in the Zone
Name field for this heat transfer surface must be the same
zone name defined in the ZoneHVAC:EquipmentConnections
object (which references a ZoneHVAC:EquipmentList
containing the name of the corresponding zone exhaust
fan).Otherwise an error message will be reported. When this
zone exhaust fan is operating for a simulation timestep, all
surface-level controls described below are ignored for that
timestep.
The name of the associated AirflowNetwork:MultiZone:ExternalNode
object, which determines the wind pressure coefficients for
the heat transfer surface. Used only if Surface Name is for an
exterior surface.
The AirflowNetwork model uses a combination of factors to
determine the actual opening area for a window or door when it
is venting. For example, consider a window that is 1.5m high
and 2.0m wide (excluding frame). Assume that the AirflowNetwork:MultiZone:Component:DetailedOpening
for this window has Type of Large Vertical Opening = 1
(non-pivoting window), Height Factor = 0.5 and Width Factor =
0.8. Then when the window is fully open, the opening area =
height of opening (0.5x1.5) times width of opening (0.8x2.0) =
0.75x1.6 = 1.2 m\(^{2}\). If
the Window/Door Opening Factor is 0.75, then the opening area
= 0.75x1.2 = 0.9 m\(^{2}\).
If, in addition, the window is in a thermal zone for which
opening modulation has been specified (ref:
AirflowNetwork:MultiZone:Zone) and the multiplication factor
due to modulation is 0.3 in a particular timestep, then the
actual opening factor that timestep = 0.3x0.75 = 0.225 and the
actual opening area that timestep = 0.3x0.9 = 0.27 m\(^{2}\).
\(\Delta P\) is the
pressure difference across crack (Pa)
\(n\) is the air flow
exponent (dimensionless)
The following fields control venting. They are used
only when Name of Associated Heat Transfer Surface is that of
an openable exterior or interior window, door or glass door.
They only apply to openings, and do not apply to surface
cracks, effective leakage area or zone exhaust fans. If none
of these fields is specified, or if Ventilation Control Mode =
ZoneLevel, venting is controlled by the AirflowNetwork:MultiZone:Zone
object for the thermal zone containing the window or door
(ref: AirflowNetwork:MultiZone:Zone
Data).
Specifies the type of surface-level natural ventilation
control.
Let \(T_{out}\) equals the
outdoor air temperature, \(T_{zone}\) equals the previous
timestep’s zone air temperature, \(T_{set}\) equals the Vent
Temperature Schedule value, \(H_{zone}\) equals the specific
enthalpy of zone air from the previous timestep, and \(H_{out}\) equals the specific
enthalpy of outdoor air. Then the four allowed choices for
Ventilation Control Mode are:
NoVent: The openable window or door
associated with this surface is closed at all times
independent of indoor or outdoor conditions. The Venting
Availability Schedule is ignored in this case.
Temperature: The openable window or door
associated with this surface is opened if \(T_{zone} > T_{out}\)and\(T_{zone} >
T_{set}\)and Venting Availability
Schedule (see below) allows venting.
Enthalpy: The openable window or door
associated with this surface is opened if \(H_{zone} > H_{out}\)and\(T_{zone} >
T_{set}\)and Venting Availability
Schedule allows venting.
Constant: Whenever this object’s Venting
Availability Schedule allows venting, the openable window or
door associated with this surface is open, independent of
indoor or outdoor conditions. Note that “Constant” here means
that the size of this opening is fixed while venting; the air
flow through this opening can, of course, vary from timestep
to timestep. If the surface is an air boundary
(Construction:AirBoundary) then Constant is the only valid
option (other options will throw a warning and be reset to
Constant).
ASHRAE55Adaptive: The openable window or
door associated with this surface is opened if the operative
temperature is greater than the comfort temperature (central
line) calculated from the ASHRAE Standard 55-2010 adaptive
comfort model and Venting Availability
Schedule allows venting.
CEN15251Adaptive: The openable window or
door associated with this surface is opened if the operative
temperature is greater than the comfort temperature (central
line) calculated from the CEN15251 adaptive comfort model
and Venting Availability Schedule allows
venting.
ZoneLevel: Venting of the window or door
is not controlled individually, but is controlled instead at
the zone level. This means that the venting is determined by
the AirflowNetwork:MultiZone:Zone
object for the thermal zone containing the window or door
(ref: AirflowNetwork:MultiZone:Zone
object). This is the default value for this field.
AdjacentTemperature: This choice is used
for an interior surface only. The openable interior window or
door associated with this surface is opened if \(T_{zone} > T_{adjacent\
zone}\)and\(T_{zone} > T_{set}\)and Venting Availability Schedule (see below)
allows venting, where \(T_{adjacent\
zone}\) is the adjacent zone temperature.
AdjacentEnthalpy: This choice is also used
for an interior surface only. The interior openable window or
door associated with this surface is opened if \(H_{zone} > H_{adjacent\
zone}\)and\(T_{zone} > T_{set}\)and Venting Availability Schedule allows
venting, where \(H_{adjacent\
zone}\) is the adjacent zone specific enthalpy.
Field:
Ventilation Control Zone Temperature Setpoint Schedule
Name[LINK]
The name of a schedule of zone air temperature set points
that controls the opening of a window or door associated with
this surface to provide natural ventilation. This setpoint is
the temperature above which this openable window or door will
be opened if the conditions described in the previous field
Ventilation Control Mode are met.
(The discussion under the field Window/Door Opening Factor
in this object describes how the actual opening area of a
window or door in a particular timestep is determined.)
Modulation of Openings
The following five fields can be used to modulate this
window/door opening when Ventilation Control Mode =
Temperature or Enthalpy. These fields determine a factor
between 0 and 1 that multiplies the opening factor of this
window or door according to the control action shown in
Figure 5
for Ventilation Control Mode = Temperature and in Figure 6
for Ventilation Control Mode = Enthalpy. Modulation of this
opening can reduce the large temperature swings that can occur
if the window/door is open too far when it is venting,
especially when there is a large inside-outside temperature
difference.
The modulation takes the following form when Ventilation
Control Mode = Temperature:
if T\(_{zone}\) - T\(_{out}\) < = [Lower Value on
Inside/Outside Temperature Difference for Modulating the
Venting Open Factor] then Multiplication
factor = 1.0
if [Lower Value on Inside/Outside
Temperature Difference for Modulating the Venting Open Factor]
< T\(_{zone}\) - T\(_{out}\) < [Upper Value on
Inside/Outside Temperature Difference for Modulating the
Venting Open Factor] then Multiplication
factor varies linearly from 1.0 to [Limit Value on Multiplier
for Modulating Venting Open Factor]
if T\(_{zone}\) - T\(_{out}\) > = [Upper Value on
Inside/Outside Temperature Difference for Modulating the
Venting Open Factor] then Multiplication
factor = [Limit Value on Multiplier for Modulating Venting
Open Factor]
One way of “tuning” the following modulation control
parameters is to perform a sensitivity analysis for winter
and/or summer design days to determine what combination of
values causes the biggest reduction in zone air temperature
fluctuations due to venting.
Note that the default values for the following fields are
such that, if none of the fields are specified, modulation
will not occur.
See Figure 5
or Figure 6.
This field applies only if Ventilation Control Mode =
Temperature or Enthalpy. This value may be from zero to 1.0,
with the default being 0.0.
Field:
Indoor and Outdoor Temperature Difference Lower Limit For
Maximum Venting Open Factor[LINK]
See Figure 5.
This field applies only if Ventilation Control Mode =
Temperature. This value may be from zero to less than 100°C,
with the default being 0°C. The value for this field must be
less than the value specified for the following field.
Field:
Indoor and Outdoor Temperature Difference Upper Limit for
Minimun Venting Open Factor[LINK]
See Figure 5.
This field applies only if Ventilation Control Mode =
Temperature. This value must be greater than 0°C, with the
default being 100°C. The value for this field must be greater
than the value specified for the previous field.
Field:
Indoor and Outdoor Enthalpy Difference Lower Limit For Maximum
Venting Open Factor[LINK]
See Figure 6.
This field applies only if Ventilation Control Mode =
Enthalpy. This value may be from zero to less than 300,000
J/kg, with the default being 0 J/kg. The value for this field
must be less than the value specified for the following
field.
Field:
Indoor and Outdoor Enthalpy Difference Upper Limit for Minimun
Venting Open Factor[LINK]
See Figure 6.
This field applies only if Ventilation Control Mode =
Enthalpy. This value must be greater than zero, with the
default being 300,000 J/kg. The value for this field must be
greater than the value specified for the previous field.
The name of a schedule that specifies when venting is
available. A zero or negative schedule value means venting is
not allowed. A value greater than zero means venting can occur
if other venting control conditions (specified by Ventilation
Control Mode and Vent Temperature Schedule Name) are
satisfied. This schedule name should not be confused with Vent
Temperature Schedule Name. If the surface is an air boundary
(Construction:AirBoundary) then this field is ignored and
venting is always available.
If a Venting Availability Schedule Name is not specified,
it is assumed that venting is always available.
Using Venting Availability Schedule allows you to turn off
venting at certain times of the day (at night, for example),
week (on weekends, for example), or year (during the winter,
for example).
If used with Ventilation Control Mode = Constant, the
ventilation rate is constant only when this schedule allows
venting; otherwise the ventilation rate is set to zero.
If Ventilation Control Mode = NoVent, this schedule has no
effect.
Note: In order to establish an airflow
network, each AirflowNetwork:MultiZone:Zone
object must have at least two surfaces defined with AirflowNetwork:MultiZone:Surface
objects, so that air can flow from one zone into other zones
(or to outdoors) through the network (air mass flow
conserved). In addition, for all AirflowNetwork:MultiZone:Surface
objects facing the same Zone
Name (ref. BuildingSurface:Detailed), at least two different
environments must be defined for the other side of these
surfaces (e.g., an external node and an adjacent zone, two
adjacent zones, or two external nodes).
The name of an AirlowNetwork:OccupantVentilationControl
object. The object is used to perform advanced window opening
control based on occupant conditions. When an object name is
given, advanced window opening control is performed and, the
Ventilation Control defined in the Ventilation Control Mode
field will be overridden.
This field is applied to a non-rectangular window or door.
The equivalent rectangular surface has the same area as the
non-rectangular one. The valid choices are: PolygonHeight,
BaseSurfaceAspectRatio, and UserDefinedAspectRatio, with the
default of PolygonHeight. When PolygonHeight is entered, the
equivalent width is equal to the area divided by the
PolygonHeight for a non-horizontal surface. When a surface is
horizontal with the same height for all vertices, the model
will automatically switch a choice to BaseSurfaceAspectRatio
if a base surface is rectangular, or UserDefinedAspectRatio
with the default value if a base surface is non-rectangular.
When BaseSurfaceAspectRatio is entered for a rectangular base
surface, the equivalent height is equal to Square Root of Area
divided by the base surface aspect ratio. The equivalent width
is equal to the equivalent height times the base surface
aspect ratio. When a base surface is non-rectangular, the
model will automatically switch the choice to PolygonHeight
for a non-horizontal base surface, and UserDefinedAspectRatio
with the default value if a base surface is horizontal. When
UserDefinedAspectRatio is entered, the equivalent height is
equal to Square Root of Area divided by
UserDefinedAspectRatio. The equivalent width is equal to the
equivalent height times the user-defined aspect ratio.
This field applies only if Equivalent Rectangle Method =
UserDefinedAspectRatio. This value must be greater than zero,
with the default being 1.0.
IDF examples are provided below:
AirflowNetwork:MultiZone:Surface,
Zn001:Wall001, !- Name of Associated Heat Transfer Surface
CR-1, !- Leakage Component Name
SFacade, !- External Node Name
1.0; !- Window/Door Opening Factor, or Crack Factor {dimensionless}
AirflowNetwork:MultiZone:Surface,
Zn001:Wall001:Win001, !- Name of Associated Heat Transfer Surface
WiOpen1, !- Leakage Component Name
SFacade, !- External Node Name
0.5; !- Window/Door Opening Factor, or Crack Factor {dimensionless}
AirflowNetwork:MultiZone:Surface,
Zn003:Wall003, !- Name of Associated Heat Transfer Surface
Zone3 Exhaust Fan, !- Leakage Component Name
EFacade, !- External Node Name
1.0; !- Window/Door Opening Factor, or Crack Factor {dimensionless}
AirflowNetwork:MultiZone:Surface,
Zn001:Wall001:Win002, !- Name of Associated Heat Transfer Surface
WiOpen2, !- Leakage Component Name
WFacade, !- External Node Name
0.5; !- Window/Door Opening Factor, or Crack Factor {dimensionless}
Temperature, !- Ventilation Control Mode
WindowVentSched, !- Vent Temperature Schedule Name
0.3, !- Limit Value on Multiplier for Modulating Venting Open Factor
!- {dimensionless}
5.0, !- Lower Value on Inside/Outside Temperature Difference for
!- Modulating the Venting Open Factor {deltaC}
10.0, !- Upper Value on Inside/Outside Temperature Difference for
!- Modulating the Venting Open Factor {deltaC}
0.0, !- Lower Value on Inside/Outside Enthalpy Difference for Modulating
!- the Venting Open Factor {J/kg}
300000.0, !- Upper Value on Inside/Outside Enthalpy Difference for Modulating
!- the Venting Open Factor {J/kg}
VentingSched; !- Venting Availability Schedule Name
This object specifies the reference conditions for
temperature, humidity, and pressure which correspond to the AirflowNetwork:MultiZone:Surface:Crack
object.
The reference humidity ratio in kgWater/kgDryAir under
which the Surface Crack Data were obtained. The default value
is 0 kgWater/kgDryAir.
An IDF example is provided below:
AirflowNetwork:MultiZone:ReferenceCrackConditions,
ReferenceCrackConditions, !- Name of Reference Crack Conditions
20.0, !- Reference Temperature for Crack Data {C}
101325, !- Reference Barometric Pressure for Crack Data {Pa}
0.0; !- Reference Humidity Ratio for Crack Data {kgWater/kgDryAir}
This object specifies the properties of air flow through a
crack and the associated measurement conditions. The following
power law form is used that gives air flow through the crack
as a function of the pressure difference across the crack:
\(\nu_o\) = Air kinetic
viscosity at the reference air temperature provided by the
object AirflowNetwork:MultiZone:ReferenceCrackConditions
specified in the field Reference Crack Conditions [m\(^{2}\)/s]
Note: The correction factor shown above is use for this
particular component as specified.
Field:
Air Mass Flow Coefficient at Reference Conditions[LINK]
The value of the air mass flow coefficient,\({C_Q}\) , in the crack air flow
equation. It has units of kg/s at 1Pa. This value must be
greater than zero.
The name of the AirflowNetwork:MultiZone:ReferenceCrackConditions
object which specifies the conditions under which the air mass
flow coefficient was measured. If the user omits this field
and only one AirflowNetwork:MultiZone:ReferenceCrackConditions
object is defined in the input data file, then those reference
crack conditions will be used. If the user omits this field
and either zero or more than one AirflowNetwork:MultiZone:ReferenceCrackConditions
objects are defined in the input data file, then the default
conditions for the AirflowNetwork:MultiZone: Reference Crack
Conditions object will be used.
An IDF example is shown below:
AirflowNetwork:MultiZone:Surface:Crack,
CR-1, !- Name of Surface Crack Component
0.01, !- Air Mass Flow Coefficient at Reference Conditions {kg/s}
0.667, !- Air Mass Flow Exponent {dimensionless}
ReferenceCrackConditions; !- Reference Crack Conditions
This numeric field is used to input the effective leakage
area in square meters. The effective leakage area is used to
characterize openings for infiltration calculations (ASHRAE
Handbook of Fundamentals, 1997, pp 25.18). This value must be
greater than zero.
This numeric field is used to input the pressure difference
exponent. The valid range of the exponent is from 0.5 to 1.0,
with a default value of 0.65.
Note: There are two common sets of reference conditions:
\(C_{d}\) = 1.0 and \(\Delta P\) = 4 Pa, or \(C_d\) = 0.6 and \(\Delta P\) = 10 Pa
An IDF example is shown below:
AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea,
SurfaceELR, !- Name of surface effective leakage area component
0.07, !- Effective leakage area {dimensionless}
1.00, !- Discharge coefficient {dimensionless}
4.0, !- Reference pressure difference {Pa}
0.65; !- Air mass flow exponent {dimensionless}
The specified flow object is used to specify flow through a
surface. The object has three fields and will cause the mass
flow \(\dot m\) to be set
appropriately as \[\dot m =
F\] when the mass flow rate \(F\) is specified or as \[\dot m = \rho Q\] when the
volume flow rate \(Q\) is
specified. A positive value of the flow directs the flow from
node 1 of the linkage to node 2, and a negative value directs
the flow from node 2 to node 1 of the linkage. For surface
linkages that are part of the building envelope, a positive
value means flow from inside to the outdoors (exfiltration)
and a negative value is a flow from the outside to inside
(infiltration).
This object specifies the properties of air flow through
windows and doors (window, door and glass door heat transfer
subsurfaces) when they are closed or open. The fields are
similar to those for AirflowNetwork:MultiZone:SurfaceCrack
object when the window or door is closed, but additional
fields are required to describe the air flow characteristics
when the window or door is open. These additional fields
include opening type, opening dimensions, degree of opening,
and opening schedule.
The AirflowNetwork model assumes that open windows or doors
are vertical or close to vertical; for this reason they are
called “Large Vertical Openings.” Such openings can have air
flow moving simultaneously in two different directions
depending on stack effects and wind conditions (for example,
flow from inside to outside at the top of a window and from
outside to inside at the bottom). AirflowNetwork models such
two-directional flow, but only for vertical openings.
It is assumed that the air flow through a window opening is
unaffected by the presence of a shading device such as a shade
or blind on the window. Also, the calculation of conductive
heat transfer and solar gain through a window or door assumes
that the window or door is closed.
The AirflowNetwork model does not have a model for
bi-directional flow through large horizontal openings in
exterior surfaces. For this reason, AirflowNetwork:MultiZone:Component:DetailedOpening
should not be used for exterior horizontal openings.
The best modeling technique in this case is to put an AirflowNetwork:MultiZone:Surface:Crack
object in a horizontal surface and use a large air mass flow
coefficient. Crack flow is assumed to be uni-directional in
any given timestep (but can reverse flow direction from
timestep to timestep).
A subsurface multiplier may be used to represent multiple
subsurfaces and calculates total air flow when the subsurface
(window, glassdoor, or door) is either closed or open. The
total airflow across the surface is equal to the airflow based
on the surface geometry multiplied by the subsurface
multiplier.
Field:
Air Mass Flow Coefficient When Opening is Closed[LINK]
Crack flow is assumed when the window or door is closed.
The units for this air mass flow coefficient (\({C_{Q,\;unit\;length}}\) ) are
different from the units for \({C_Q}\) (kg/s at 1 Pa pressure
difference) defined in an AirflowNetwork:MultiZone:Surface:Crack
object. There is no default but the entered value must be
greater than zero. The program will automatically generate
four cracks around the perimeter of the window or door–one
along the bottom, one along the top, and one on each side. The
temperature correction factor used in the AirflowNetwork:MultiZone:Surface:Crack
object is not used for this component to calculate air mass
flow rate.
Field:
Air Mass Flow Exponent When Opening Is Closed[LINK]
Crack flow is assumed when the window or door is closed. In
this case, the value of this field is the exponent,
n, in the crack air flow equation. The valid range
for this exponent is 0.5 to 1.0, with the default value being
0.65. Mass Flow Rate = Air Mass Flow Coefficient (deltaP) Air
Mass Flow Exponent.
Field:
Type of Rectanguler Large Vertical Opening (LVO)[LINK]
This alpha field specifies the type of rectangular window
or door. (Open windows or doors are also called Large Vertical
Openings (LVOs). The choices for the opening type are
NonPivoted (LVO Type 1) and
HorizontallyPivoted (LVO Type 2) with the
default being NonPivoted. The NonPivoted type
represents a regular window or door. The HorizontallyPivoted
type represents a window with a horizontal axis (i.e., a
horizontally-pivoting window) and cannot be used for a
door.
Field:
Extra Crack Length or Height of Pivoting Axis[LINK]
Specifies window or door characteristics that depend on the
LVO type.
For LVO Type 1 (rectangular non-pivoted windows and doors)
this field is the extra crack length in meters due to multiple
openable parts, if present. “Extra” here means in addition to
the length, calculated by the program, of the cracks on the
top, bottom and sides of the window/door.
For LVO Type 2 (rectangular horizontally-pivoted windows)
this field gives the height of the pivoting axis measured from
the bottom of the glazed part of the window (m).
Field:
Number of Sets of Opening Factor Data[LINK]
This is the number of the following sets of data for
opening factor, discharge coefficient, width factor, height
factor, and start height factor. From two to four of these
sets must be defined. The first set should be for Opening
Factor = 0.0 and the last set should be for Opening Factor =
1.0. For example, if only two sets are defined, the first set
should be for Opening Factor = 0.0 and the second set should
be for Opening Factor = 1.0, as shown below in the IDF example
below.
An “opening factor” refers to the amount that a window or
door is opened. The program linearly interpolates each
timestep between the values of discharge coefficient, width
factor, etc., in these sets using the opening factor for the
window or door for the timestep. (See discussion under the
field Window/Door Opening Factor in the
AirflowNetwork:Multizone:Zone object for a description of how
the AirflowNetwork model determines the time-step value of the
opening factor.)
Each field is described for as many groups as required in
the previous field (number of sets of opening factor data). As
the final field has specific requirements, this field (n) will
be described.
The first opening factor of a window or door. This value
must be 0.0. The default value is also 0.0.
For LVO Type 1 (rectangular non-pivoted window or door),
the Opening Factor corresponds to the fraction of window or
door that is opened.
For LVO Type 2 (rectangular horizontally-pivoted windows),
the Opening Factor is determined by the window opening angle.
For example, an opening angle of 45° corresponds to an Opening
Factor of 0.50 since the maximum opening angle is 90°.
Field:
Discharge Coefficient for Opening Factor 1[LINK]
The discharge coefficient of the window or door for Opening
Factor 1. The range is greater than 0.0 to less than or equal
to 1.0. The default value is 0.001. The Discharge Coefficient
indicates the fractional effectiveness for air flow through a
window or door at that Opening Factor.
Note: In the following, “window width” and
“window height” are glazing dimensions; they do not include
the frame, if present.
The Width Factor of the rectangular window or door for
Opening Factor 1. The Width Factor is the opening width
divided by the window or door width (see Figure 7).
The range is 0.0 to 1.0. The default value is 0.0. Note that
the width factor applies to rectangular windows or doors where
the width is assumed constant along the entire height of the
opening.
The Height Factor of the rectangular window or door for
Opening Factor 1. The Height Factor is the opening height
divided by the window or door height (see Figure 7).
The range is 0.0 to 1.0. The default value is 0.0. Note that
the height factor applies to rectangular windows or doors
where the height is assumed constant along the entire width of
the opening.
Field:
Start Height Factor for Opening Factor 1[LINK]
The Start Height Factor of the window or door for Opening
Factor 1. The Start Height Factor is the Start Height divided
by the window or door height (see Figure 7).
The range is 0.0 to 1.0. The default is 0. Start Height is the
distance between the bottom of the window or door and the
bottom of the window or door opening. The sum of the Height
Factor and the Start Height Factor must be less than 1.0 in
order to have the opening within the window or door
dimensions.
Window (or door) showing
geometrical factors associated with an opening through which
air flows. [fig:window-or-door-showing-geometrical-factors]
When Number of Sets of Opening Factor Data = n, the value
of Opening Factor n must be set to 1.0.
Field:
Discharge Coefficient for Opening Factor <n>[LINK]
The discharge coefficient of the window or door for Opening
Factor n. The range is greater than 0.0 to less than or equal
to 1.0. The default value is 1.0.
The Width Factor of the rectangular window or door for
Opening Factor n. The Width Factor is the opening width
divided by the window or door width (see Figure 7).
The range is 0.0 to 1.0. The default value is 1.0.
The Height Factor of the rectangular window or door for
Opening Factor n. The Height Factor is the opening height
divided by the window or door height (see Figure 7).
The range is 0.0 to 1.0. The default value is 1.0.
Field:
Start Height Factor for Opening Factor <n>[LINK]
The Start Height Factor of the window or door for Opening
Factor n. The Start Height Factor is the Start Height divided
by the window or door height (see Figure 7).
The range is 0.0 to 1.0. The default is 0.
When the opening factor value (as described under the field
Window/Door Opening Factor in the AirflowNetwork:MultiZone:Surface
object) is between two Opening Factor field values, the values
of Discharge Coefficient, Width Factor, Height Factor, and
Start Height Factor are linearly interpolated.
An IDF example is shown below:
AirflowNetwork:MultiZone:Component:DetailedOpening,
WiOpen1, !- Detailed Opening Name
0.001, !- Air Mass Flow Coefficient When Opening is Closed {kg/s-m}
0.667, !- Air Mass Flow Exponent When Opening is Closed {dimensionless}
NonPivoted, !- Type of Large Vertical Opening (LVO)
0.0, !- Extra crack length for LVO type 1 with multiple openable parts,
!- or Height of pivoting axis for LVO type 2 {m}
2, !- Number of Sets of Opening Factor Data
0.0, !- Opening factor 1 {dimensionless}
0.5, !- Discharge coefficient for opening factor 1 {dimensionless}
0.0, !- Width factor for opening factor 1 {dimensionless}
1.0, !- Height factor for opening factor 1 {dimensionless}
0.0, !- Start height factor for opening factor 1 {dimensionless}
1.0, 0.6, 1.0, 1.0, 0.0; !- Set of values for opening factor 2
This object specifies the properties of air flow through
windows, doors and glass doors (heat transfer subsurfaces
defined as a subset of FenestrationSurface:Detailed
objects) when they are closed or open. This AirflowNetwork
model assumes that these openings are horizontal or close to
horizontal and are interzone surfaces. The second and third
input fields are similar to those for AirflowNetwork:MultiZone:Surface:Crack,
when the window or door is closed, but additional information
is required to describe the air flow characteristics when the
window or door is open. This additional information is
specified in the last two input fields. The airflow across the
opening consists of two types of flows: forced and buoyancy.
The forced flow is caused by the pressure difference between
two zones, while the buoyancy flow only occurs when the air
density in the upper zone is greater than the air density in
the lower zone. This opening also allows for the possibility
of two-way flow when forced and buoyancy flows co-exist. This
object’s openness can also be modulated based on the same
opening factor control as an AirflowNetwork:MultiZone:Component:DetailedOpening
object. However, the opening factor is only applied to the
subsurface width. The opening width is equal to opening factor
multiplied by the subsurface width.
A subsurface multiplier may be used to represent multiple
subsurfaces and calculates total air flow when the subsurface
(window, glassdoor, or door) is either closed or open. The
total airflow across the surface is equal to the airflow based
on the surface geometry multiplied by the subsurface
multiplier.
Field:
Air Mass Flow Coefficient When Opening is Closed[LINK]
The value of the air mass flow coefficient, \({C_{Q,\;unit\;length}}\) , in the
horizontal opening air flow equation. It has units of kg/s-m
at 1Pa. The temperature correction factor is not applied to
the mass flow calculation. This is a required input field and
the entered value must be greater than zero.
Field:
Air Mass Flow Exponent When Opening is Closed[LINK]
The value of the exponent, n, in the crack air
flow equation. The valid range is 0.5 to 1.0, with the default
value being 0.65.
This numeric field is used to represent the angle between
the horizontal plane and a sloped plane under the horizontal
opening. Sloping plane angle = 90 is equivalent to fully open.
The valid range is >0 to 90, with the default value being
90.
This numeric field is used to input the discharge
coefficient. This is a required field and the entered value
must be greater than zero.
An IDF example is shown below:
AirflowNetwork:MultiZone:Component:HorizontalOpening,
HrOpen, !- Name
0.001, !- Air Mass Flow Coefficient When Opening is Closed {kg/s-m}
0.667, !- Air Mass Flow Exponent When Opening is Closed {dimensionless}
90.0, !- Sloping Plane Angle
0.2; !- Discharge Coefficient
This object specifies the properties of air flow through
windows, doors and glass doors (heat transfer subsurfaces)
when they are closed or open. The AirflowNetwork model assumes
that open windows or doors are vertical or close to vertical.
The second and third fields are similar to those for AirflowNetwork:MultiZone:Surface:Crack,
when the window or door is closed, but additional information
is required to describe the air flow characteristics when the
window or door is open. This additional information is
specified in the last two fields. Compared to the object AirflowNetwork:MultiZone:Component:DetailedOpening,
which requires more inputs at different opening factors, this
object needs comparatively less inputs. For this reason it is
called a simple opening. This opening also allows for the
possibility of two-way flow due to temperature and resulting
density differences. Therefore, it is possible to have a
positive pressure difference at the top of the opening, and a
negative pressure difference at the bottom (or vice versa)
when the neutral height is between the bottom and top heights
of the associated surface. This object’s openness can also be
modulated based on the same opening factor control as an AirflowNetwork:MultiZone:Component:DetailedOpening
object. However, the opening factor is only applied to the
subsurface width. The opening width is equal to opening factor
multiplied by the subsurface width.
A subsurface multiplier may be used to represent multiple
subsurfaces and calculates total air flow when the subsurface
(window, glassdoor, or door) is either closed or open. The
total airflow across the surface is equal to the airflow based
on the surface geometry multiplied by the subsurface
multiplier.
Field:
Air Mass Flow Coefficient When Opening is Closed[LINK]
The value of the air mass flow coefficient, \({C_{Q,\;unit\;length}}\) , in the
simple opening air flow equation. It has units of kg/s-m at
1Pa. The temperature correction factor is not applied for mass
flow calculation.
Field:
Air Mass Flow Exponent When Opening is Closed[LINK]
The value of the exponent, n, in the crack air flow
equation. The valid range is 0.5 to 1.0, with the default
value being 0.65. Mass Flow Rate = Air Mass Flow
Coefficient (deltaP)^Air Mass Flow Exponent.
Field:
Minimum Density Difference for Two-Way Flow[LINK]
This numeric field is used to input the minimum density
difference above which two-way or one way flow may occur due
to stack effect with the window being open. Two-way flow
occurs only when the neutral plane is within the opening.
Density differences less than this value result in one-way
flow only with the window being closed. The minimum value for
this field is greater than zero.
This numeric field is used to input the discharge
coefficient. This value must be greater than zero.
An IDF example is shown below:
AirflowNetwork:MultiZone:Component:SimpleOpening,
WiOpen2, !- Simple Opening Name
0.001, !- Air Mass Flow Coefficient When Opening Is Closed {kg/s-m}
0.650, !- Air Mass Flow Exponent When Opening Is Closed {dimensionless}
0.0001, !- Minimum density difference for two-way flow (kg/m3)
1.0; !- Discharge coefficient (dimensionless)
This object specifies the properties of air flow through an
exterior heat transfer surface with a zone exhaust fan. The
zone exhaust fan turns on or off based on the availability
schedule defined in the corresponding Fan:ZoneExhaust
object. When the exhaust fan mass flow rate is greater than
zero, the airflow network model treats this object as a
constant volume fan. When the fan is off based on the
availability schedule, the model treats this object as a
crack.
When the fan is on, the air mass flow rate modeled for the
airflow network is based on the value defined in the
MaximumFlow Rate field of the Fan:ZoneExhaust
object. The airflow direction is from the corresponding zone
to outdoors.
When the fan is off, the following power law form is used
that gives air flow through the crack as a function of the
pressure difference across the crack:
\(\nu_o\) = Air kinetic
viscosity at the reference air temperature provided by the
object AirflowNetwork:MultiZone:ReferenceCrackConditions
specified in the field Reference Crack Conditions [m\(^{2}\)/s]
Note: The correction factor shown above is used when the
exhaust fan is off. The airflow direction is based on the
pressure difference between the zone and outdoors.
Field:
Air Mass Flow Coefficient When the Zone Exhaust Fan is Off at
Reference Conditions[LINK]
The value of the air mass flow coefficient,\({C_Q}\) , in the crack air flow
equation. It has units of kg/s at 1Pa. This value must be
greater than zero. The value is used when the fan is off.
Field:
Air Mass Flow Exponent When the Zone Exhaust Fan is Off[LINK]
The value of the exponent, n, in the crack air
flow equation. The valid range is 0.5 to 1.0, with the default
value being 0.65. The value is used when the fan is off.
The name of the AirflowNetwork:MultiZone:ReferenceCrackConditions
object which specifies the conditions under which the air mass
flow coefficient was measured. If the user omits this field
and only one AirflowNetwork:MultiZone:ReferenceCrackConditions
object is defined in the input data file, then those reference
crack conditions will be used. If the user omits this field
and either zero or more than one AirflowNetwork:MultiZone:ReferenceCrackConditions
objects are defined in the input data file, then the default
conditions for the AirflowNetwork:MultiZone: Reference Crack
Conditions object will be used.
An IDF example is shown below:
AirflowNetwork:MultiZone:Component:ZoneExhaustFan,
Zone3 Exhaust Fan, !- Name
0.01, !- Air Mass Flow Coefficient When the Zone Exhaust Fan is Off at Reference Conditions {kg/s}
0.667; !- Air Mass Flow Exponent When the Zone Exhaust Fan is Off{dimensionless}
ReferenceCrackConditions; !- Reference Crack Conditions
External nodes in the AirflowNetwork model define
environmental conditions outside of the building. These
conditions include wind pressure coefficients that vary from
façade to façade and can be highly dependent on the building
geometry.
The external node name is associated with a particular
building façade. This name is referenced by the External Node
Name field of an AirflowNetwork:MultiZone:Surface
object.
The name of a specific AirflowNetwork:MultiZone:WindPressureCoefficientValues
object, curve, or table (which gives wind pressure
coefficients for the façade as a function of angle of wind
incident on the façade). Curves or tables should have the
domain of 0 to 180 degrees or 0 to 360 degrees, depending upon
the symmetry field (see below).
Specifies the symmetry of the above named curve. The
default is No, meaning that the curve will be evaluated from 0
to 360 degrees. Specify Yes for a curve that is symmetric
about zero and is evaluated only up to 180 degrees. For this
type of curve, an angle of 270 degrees is passed to the curve
as 90 degrees.
Specifies which wind angle should be used to calculate the
wind pressure coefficient. The default is Absolute, meaning
that the absolute wind direction angle will be used.
Specifying Relative means that the angle will be relative to
the surface normal. For a surface facing due east, the angle 0
corresponds to wind blowing perpendicular to and at the
surface with absolute direction 90 degrees, while 90 degrees
corresponds to wind blowing parallel to the surface from the
right (facing outward) with an absolute direction of 180
degrees.
IDF examples are provided below:
AirflowNetwork:MultiZone:ExternalNode,
NFacade, !- Name
1.524, !- External Node Height {m}
NFacade_WPCValue; !- Wind Pressure Coefficient Curve Name
AirflowNetwork:MultiZone:ExternalNode,
EFacade, !- Name
1.524, !- External Node Height {m}
EFacade_WPCValue; !- Wind Pressure Coefficient Curve Name
AirflowNetwork:MultiZone:ExternalNode,
SFacade, !- Name
1.524, !- External Node Height {m}
SFacade_WPCValue; !- Wind Pressure Coefficient Curve Name
AirflowNetwork:MultiZone:ExternalNode,
WFacade, !- Name
1.524, !- External Node Height {m}
WFacade_WPCValue; !- Wind Pressure Coefficient Curve Name
AirflowNetwork:MultiZone:ExternalNode,
Horizontal, !- Name
3.028, !- External Node Height {m}
Horizontal_WPCValue; !- Wind Pressure Coefficient Curve Name
This object specifies up to 36 wind pressure coefficients
(WPCs) for an AirflowNetwork:MultiZone:ExternalNode.
These coefficients are defined for each of the wind directions
defined in the unique AirflowNetwork:MultiZone:WindPressureCoefficientArray
object. In the air flow calculation, interpolation of the
specified WPC values is done for time-step values of wind
direction.
Field:
Wind Pressure Coefficient Value 1 to Wind Pressure Coefficient
Value N[LINK]
The WPC (wind pressure coefficient) value for the building
façade indicated by the External Node Name field above. This
WPC value corresponds to the first wind direction in the AirflowNetwork:MultiZone:WindPressureCoefficientArray.
Note that WPC values can be positive, negative or zero.
Wind pressure coefficients are reported in the eplusout.eio
either from inputs using “INPUT” as the choice for the Wind
Pressure Coefficient Type field defined in the
AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol)
object, or from internal calculation using
SurfaceAverageCalculation as the choice for the Wind Pressure
Coefficient Type field defined in the same object. Below is an
output example from the eplusout.eio file:
The AirflowNetwork:OccupantVentilationControl
object provides control options with minimum opening and
closing time checks and opening and closing probability
values. In general, the probability values could be a constant
or a specific function. Due to lack of real data, two
schedules are selected to represent probability values. If
real data are available, this object may be modified to adopt
new data.
The field represents the minimum time that windows will
remain open. If a window has been open for a time less than
this value, the window will remain open.
The field represents the minimum time that windows will
remain closed. If a window has been closed for a time less
than this value, the window will remain closed.
Field:
Thermal Comfort Low Temperature Curve Name[LINK]
This alpha field defines the name of a curve to be used for
thermal comfort temperature calculation at low outdoor
dry-bulb temperature. This curve is a linear or quadratic
equation using outdoor dry-bulb temperatures as an independent
variable. This performance curve can be used to describe the
thermal comfort temperature at low outdoor dry-bulb
temperature. It allows maximum two curves to describe the
thermal comfort temperature in two different outdoor dry-bulb
temperature regions. If a single curve is used, blanks are
entered in the following two fields.
Field:
Thermal Comfort Temperature Boundary Point[LINK]
When there are two piecewise curves to represent thermal
comfort temperature calculation, this field represents a
boundary point of outdoor dry-bulb temperature. The low
temperature curve and the high temperature curve should have
the same values at the boundary point. If a single curve is
used, this field may be left blank.
Field:
Thermal Comfort High Temperature Curve Name[LINK]
This alpha field defines the name of a curve to be used for
thermal comfort temperature calculation at high outdoor
dry-bulb temperature. This curve is a linear or quadratic
equation using outdoor dry-bulb temperatures as an independent
variable. This performance curve can be used to describe the
thermal comfort temperature at high outdoor dry-bulb
temperature. It allows maximum two curves to describe the
thermal comfort temperature in two different outdoor dry-bulb
temperature regions. If a single curve is used, blanks are
entered in this field.
Field:
Maximum Threshold for Persons Dissatisfied PPD[LINK]
This field is used to calculate the comfort band as a
function of predicted percentage of dissatisfied (PPD). The
default value is 10%. The equation is based on curve fit and
is valid between 0% and 35%.
Input is Yes or No. The default is No. If Yes, an occupancy
check is performed used in the opening probability check. If
No, the occupancy check is bypassed.
The name of a schedule of opening probability that controls
the opening of windows and doors in the thermal zone to
provide natural ventilation. If the probability value is
greater a random number, windows are allowed to open.
Otherwise, the output will be false. This control will occur
when minimum time checks for both opening and closing are
satisfied.
The name of a schedule of closing probability that controls
the closing of windows and doors in the thermal zone to reduce
natural ventilation. If the probability value is greater a
random number, windows are allowed to be closed. Otherwise,
the output will be false. This control will occur when minimum
time checks for both opening and closing are satisfied.
An IDF example is provided below:
AirlowNetwork:OccupantVentilationControl,
VentilationControl, !- Name
5.0, !- Minimum Opening Time
5.0, !- Minimum Opening Time
ComfortLowTempCurve, !- Thermal Comfort Low Temperature Curve Name
10.0, !- Thermal Comfort Temperature Boundary Point
ComfortHighTempCurve, !- Thermal Comfort High Temperature Curve Name
10.0, !- Maximum Threshold for Persons Dissatisfied PPD
Yes, !- Occupancy Check
OpeningProbabilitySch, !- Opening Probability Schedule Name
ClosingProbabilitySch; !- Closing Probability Schedule Name
The AirflowNetwork:ZoneControl:PressureController
object is used to control a zone to a specified indoor level
of pressure using the AirflowNetwork model. The specified
pressure setpoint is used to calculate the required zone
exhaust fan flow rate in a controlled zone or relief air flow
rate in an AirLoop.
The object has a similar function as ZoneControl:Thermostat.
When an AirLoop serves multiple zones, the controlled zone
will reach the specified setpoint, while other zones will not
be controlled precisely.
Field:
Pressure Control Availability Schedule Name[LINK]
This field contains the name of a schedule that determines
whether or not the AirflowNetwork:ZoneControl:PressureController
is available. When the schedule value is zero, the AirflowNetwork:ZoneControl:PressureController
is bypassed (not available to operate). When the schedule
value is greater than zero, the AirflowNetwork:ZoneControl:PressureController
is available to perform pressure control. When
AirflowNetwork:Distribution:Component:ZoneExhaustFan in
entered in the Control Object Type field, the model will
calculate the required zone exhaust fan airflow rate to reach
the pressure setpoint. When an AirflowNetwork:Distribution:Component:ReliefAirFlow
is entered in the Control Object Type field, the model will
calculate the central relief flow rate in an outdoor air
mixer. If this field is left blank, the schedule has a value
of 1 for all time periods. Schedule values must be between 0
and 1.
This field contains the name of a schedule that contains
the zone air pressure setpoint as a function of time. The
units for pressure setpoint are Pascal. The setpoint values in
the schedule must be between -50 and 100 Pascal.
An IDF example is provided below:
AirflowNetwork:ZoneControl:PressureController,
Pressure Controller1, !- Name
EAST ZONE, !- Controlled Zone Name
AirflowNetwork:MultiZone:Component:ZoneExhaustFan, !- Control Object type
East Zone Exhaust Fan, !- Control Object Name
PressureAvailSchedule, !- Pressure Control Availability Schedule Name
PressureSetpointSchedule; !- Pressure Setpoint Schedule Name
The next two objects of AirflowNetwork:IntraZone:Node
and AirflowNetwork:IntraZone:Linkage
are used with RoomAir:Node:AirflowNetwork
objects together to simulate multiple internal airflows via
multiple intrazone nodes and linkages in a thermal zone. The
mixed-air assumption for zone air conditions is not always
appropriate. EnergyPlus includes several RoomAir models that
can model the implications for different flow patterns on
variations in temperature within the zone. However none of
them are generalized enough for different types of air flow
situations and none are coupled tightly with AirflowNetwork. A
general RoomAir model based on pressure network solver will
allow modeling a variety of spaces types not currently covered
by existing models such as tall spaces.
Recent advancements have been made to AirflowNetwork to
model large horizontal openings. This new development makes
AirflowNetwork useful for not only modeling air movement
between zones (and outdoors), but also within individual
thermal zones.
The possible combination will allow the EnergyPlus to
simulate a thermal zone using a network approach by assuming
internal nodes connected by user-defined patterns of
temperatures and airflows. It should be pointed out that the
new model works when the MultiZoneWithoutDistribution is
selected in the field of AirflowNetwork Control of the
AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol)
object. The model cannot work with other choices.
This object allows users to input multiple nodes in a zone.
A single object represent a node. If there is only one node
per zone, then use the AirflowNetwork:MultiZone:Zone
input object. The zone node is not defined in this object.
The name identifies the node for later reference and in the
output listing. Each node should have a unique name. This name
can be referenced as AirflowNetworkNodeNames.
The input object specifies a connection between two AirflowNetwork:IntraZone:Node
objects and an AiflowNetwork component defined elsewhere. The
object also allow users to specify a connection between an AirflowNetwork:IntraZone:Node
and an adjacent zone defined in an AirflowNetwork:MultiZone:Zone
object. This object provides flexibility to define a linkage
either in the same zone or in two different zones.
The input designates an AirflowNetwork component name
associated with the two nodes. The component name should be
one of the AirflowNetwork:MultiZone:Component object names.
The component is used for intrazone node connection only. If
the next field is specified, the input of this field could be
a blank.
It should be pointed out that an AirflowNetwork:MultiZone:Surface
object allows following five
AirflowNetwork:MultiZone:Component objects:
However, an AirflowNetwork:IntraZone:Linkage
object without a surface connection has connection with two
intrazone nodes in the same zone and allows two
AirflowNetwork:MultiZone:Component objects due to lack of
geometry inputs.
The input specifies an AirflowNetwork:MultiZone:Surface
object name, when the nodes defined above are not located in
the same zone. The surface linkage will be connected by the
above two nodes, instead of zone nodes in normal definition.
In other words, the connection defined in an AirflowNetwork:MultiZone:Surface
is removed. Instead, this new connection replaces the the
connection specified before. A warning message is issued to
let users be aware of the changes. Since each AirflowNetwork:MultiZone:Surface
object has its own component defined in the Leakage Component
Name field, the input of the Component Name field in this
object will be ignored.
An IDF example is provided below:
AirflowNetwork:IntraZone:Linkage,
IntraZoneMiddleUpperLink, !- Name
LeftUpper, !- Node 1 Name
CentralUpper, !- Node 2 Name
CR-1; !- Component Name
AirflowNetwork:IntraZone:Linkage,
IntraZoneLeftUpperLink,
LeftUpper, !- Node 1 Name
EAST_ZONE_T, !- Node 2 Name
CR-1, !- Component Name
Surface_11_T; !- Surface Name
The previous sections of this AirflowNetwork model
discussion describe input objects used for multizone airflow
calculations. The following sections describe input objects
used for air distribution system simulations. These objects
work when control option “MultiZone with Distribution” or
“MultiZone with Distribution Only During Fan Operation” is
defined in the AirflowNetwork Control field in the
AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol)
object.
The first section presents the input object for
distribution system nodes. Although thermal zones are required
to perform air distribution system simulations, the thermal
zones are already defined in the multizone input section
(described previously), so that there is no need to repeat the
inputs for thermal zones when modeling an air distribution
system. The same is also true for surface air leakage. This
section has only one object: AirflowNetwork:Distribution:Node.
The AirflowNetwork:Distribution:DuctViewFactors
object is used to represent the information needed for
simplified surface-to-duct radiation heat transfer. View
factors from each duct object to each referenced surface are
provided by the user. EnergyPlus calculates the heat gain to
the duct from the referenced surfaces. If the object is
included, radiation is calculated for the referenced duct;
radiation is neglected of the object is omitted.
The AirflowNetwork:Distribution:Node
object is used to represent air distribution system nodes for
the AirflowNetwork model. The EnergyPlus nodes defined in an
AirLoopHVAC
are a subset of the nodes used to simulate the distribution
system using the AirflowNetwork model. For example, the inlet
node of a fan and the outlet node of a coil defined in an AirLoopHVAC
must be defined as nodes using the AirflowNetwork:Distribution:Node
object. A set of EnergyPlus Zone
Equipment nodes is also a subset of the
AirflowNetwork:Distribution:Nodes. For example, zone inlet and
outlet nodes must be defined as nodes using the
AirflowNetwork:Distribution: Node object. In addition,
although mixers and splitters are defined as objects with
inlet and outlet nodes within EnergyPlus, the AirflowNetwork:Distribution:Node
object treats mixers and splitters as single nodes. The node
objects are referenced by AirflowNetwork:Distribution:Linkage
objects.
In summary, all nodes used to define an AirLoopHVAC
(except splitters, mixers, and outdoor air systems which are
treated as single nodes) and its connections to a thermal zone
must be specified as AirflowNetwork:Distribution:Nodes. If
distribution system air leaks are to be modeled, additional
AirflowNetwork:Distribution:Nodes may be defined along with
AirflowNetwork:Distribution:Components (e.g., leak or leak
ratio) to define the air leakage characteristics.
Note: Supply and return leaks are not allowed in an AirLoopHVAC.
They can only be modeled in the Zone
Equipment Loop (i.e., return leaks may be modeled between the
zone return node and the zone mixer inlet or the zone mixer
outlet and the zone equipment loop outlet; and supply leaks
may be modeled between the zone equipment loop inlet and the
AirLoopHVAC:ZoneSplitter
inlet node or the AirLoopHVAC:ZoneSplitter
outlet node and the zone supply node).
The name of an air distribution system node. This node name
is referenced by an AirflowNetwork:Distribution:Linkage
and in the output listing. Each node should have a unique name
within the AirflowNetwork:Distribution:Node
objects (however, the node name may be used elsewhere as
regular EnergyPlus node names such as the fan inlet node or
coil outlet node).
Designates node names defined in another EnergyPlus object,
so that the AirflowNetwork:Distribution:Node
object is able to get input parameters and node conditions
from the associated EnergyPlus node or object. The actual node
name is entered here and represents a node already defined in
an AirLoopHVAC
or zone equipment loop. This field is left blank if the
EnergyPlus Node Type field below is entered as Mixer,
Splitter, Outdoor air System, or Other.
OAMixerOutdoorAirStreamNode:
Represents an external node name specified as an Outdoor Air
Stream Node Name in the OutdoorAir:Mixer
object when the AirLoopHVAC:OutdoorAirSystem
object is used.
OutdoorAir: Represents an external
node name defined in the OutdoorAir:Node
object when the AirLoopHVAC:OutdoorAirSystem
and an exhaust energy recovery system (air-to-air heat
exchanger) are used.
Other: Represents a type not already
defined above.
Note: Both the OutdoorAir:NodeList
and OutdoorAir:Node
node types represent a node to outdoor air conditions. Either
one of these node types can be used to represent an external
node when an air-to-air heat exchanger is used to recover
energy from the exhaust air stream as part of an AirLoopHVAC:OutdoorAirSystem
object. Node type OAMixerOutdoorAirStreamNode does not
represent an external node when an OutdoorAir:NodeList
or OutdoorAir:Node
object is specified. If no exhaust heat recovery system (i.e.,
air-to-air heat exchanger) is specified in the AirLoopHVAC:OutdoorAirSystem,
the node type OAMixerOutdoorAirStreamNode represents an
external node.
Designates the reference height in meters used to calculate
relative pressure. The default value is 0 meters.
IDF examples are provided below:
AirflowNetwork:Distribution:Node,
EquipmentInletNode, !- Name
Zone Equipment Inlet Node, !- Component Name or Node Name
Other, !- Component Object Type or Node Type
3.0; !- Node Height {m}
AirflowNetwork:Distribution:Node,
SupplyMainNode, !- Name
, !- Component Name or Node Name
Other, !- Component Object Type or Node Type
3.0; !- Node Height {m}
AirflowNetwork:Distribution:Node,
MainSplitterNode, !- Name
, !- Component Name or Node Name
AirLoopHVAC:ZoneSplitter, !- Component Object Type or Node Type
3.0; !- Node Height {m}
AirflowNetwork:Distribution:Node,
MainSplitterNode, !- Name of Node
, !- Name of Associated EnergyPlus Node or Object
AirLoopHVAC:ZoneSplitter, !- EnergyPlus Object or Node Type
3.0; !- Node Height {m}
The next section describes AirflowNetwork Distribution
Components, with 7 available types listed below. All required
fields for each component represent a relationship between
pressure difference and airflow. The components are referenced
in AirflowNetwork:Distribution:Linkage
objects.
This component may be also called a power law component and
is used to represent a supply or return air leak in an air
distribution system. Its relationship between pressure
difference and airflow may be expressed as:
\[\dot m = {C_T}C{\left( {\Delta
P} \right)^n}\]
where
\(\dot m\) = Air mass
flow rate through the component [kg/s]
C = Air mass flow coefficient (kg/s at 1 Pa pressure
difference)
\(\Delta P\) = Total
pressure loss across the element [Pa]
A unique name identifying a supply or return air leak in an
air distribution system. This unique name will be referenced
by an AirflowNetwork:Distribution:Linkage
object to represent a component leak.
This numeric field is defined as the air mass flow
coefficient at 1 Pa pressure difference across this component.
Valid entries must be greater than zero.
This numeric field is defined as the pressure difference
exponent across the component. Valid entries are from 0.5 to
1.0, with the default value being 0.65.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:Leak,
MainSupplyLeak, !- Name of Supply or Return Leak
0.0001, !- Air Mass Flow Coefficient {kg/s}
0.65; !- Air Mass Flow Exponent {dimensionless}
AirflowNetwork:Distribution:Component:Leak,
ZoneSupplyLeak, !- Name of Supply or Return Leak
0.01, !- Air Mass Flow Coefficient {kg/s}
0.65; !- Air Mass Flow Exponent {dimensionless}
The leakage ratio component is generally used to define
supply and return leaks with respect to a constant fan flow.
This object requires 5 inputs. The relationship between
pressure and airflow may be expressed as a power law
element:
\[\dot m = {C_{equ}}{\left(
{\Delta P} \right)^n}\]
where
\(\rho\) = Air density
[kg/m\(^{3}\)]
\(\Delta P\) = Total
pressure loss across the element [Pa]
\(n\) = Air mass flow
exponent
\(C_{equ}\) = Equivalent
air mass flow coefficient
A unique name identifying a supply or return air leak
(ratio with respect to the constant volume fan flow rate) in
an air distribution system. This unique name will be
referenced in an AirflowNetwork:Distribution:Linkage
object to represent a component.
This numeric field is used to input the effective leakage
ratio. This value must be greater than zero and less than or
equal to 1. The effective leakage ratio is used to
characterize supply and return leaks with respect to the
constant fan flow (supply or return air leak flow rate divided
by the maximum air flow rate for the fan). When a VAV system
is used with Supply Fan Object Type = Fan:VariableVolume
in the AirflowNetwork:Distribution:Component:Fan
object, the ratio for a supply leak is defined as the value of
supply air leak flow rate divided by the supply fan air flow
rate at the current time step. The inputs of the rest of 3
fields are not used.
This numeric field is used to input the maximum flow rate
for a constant volume fan [m\(^{3}\)/s]. This value must be
greater than 0 m\(^{3}\)/s.
When a VAV system is used with Supply Fan Object Type = Fan:VariableVolume
in the AirflowNetwork:Distribution:Component:Fan
object, this input is not used, because the real supply fan
flow rate at the current time step is used to calculate the
amount of a supply leak.
This numeric field is used to input the reference pressure
difference [Pa]. This value must be greater than 0 Pa. When a
VAV system is used with Supply Fan Object Type = Fan:VariableVolume
in the AirflowNetwork:Distribution:Component:Fan
object, this input is not used, because the real supply fan
flow rate at the current time step is used to calculate the
amount of a supply leak.
This numeric field is used to input the pressure difference
exponent. The value of the exponent can be from 0.5 to 1.0,
with the default value being 0.65. When a VAV system is used
with Supply Fan Object Type = Fan:VariableVolume
in the AirflowNetwork:Distribution:Component:Fan
object, this input is not used, because the real supply fan
flow rate at the current time step is used to calculate the
amount of a supply leak.
Note: The reference pressure difference is defined as the
difference between pressures of originate and terminate nodes
for supply and return leaks. In general, it may require that a
simulation be performed with an initial guess for reference
pressure difference using design day conditions. After
obtaining pressures at the leakage nodes, more realistic
reference pressure differences can be entered. It should be
pointed out that since pressures at the nodes vary with
temperature and other conditions, the effective leakage ratio
is only an estimate. In other words, the exact leakage ratio
may not be available.
When a VAV system is used with Supply Fan Object Type = Fan:VariableVolume
in the AirflowNetwork:Distribution:Component:Fan
object, the AirflowNetwork:Distribution:Component:LeakageRatio
object has to be used to define a supply leak. The other
components cannot be used. In addition, the first node in a AirflowNetwork:Distribution:Linkage
to define a supply leak has to be the node in the duct to
originate a supply leak, and the second node has to be the
node of a zone to terminate a supply leak. In other words, the
supply leak has to flow from node 1 to node 2. When this
object is used to define a return leak, the first node in a AirflowNetwork:Distribution:Linkage
has to be a thermal zone to originate a leak, and the second
node has to be the node of a duct to terminate a leak.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:LeakageRatio,
Zone1SupplyLeakELA, !- Name of Effective Leakage Ratio
0.043527, !- Effective Leakage Ratio {dimensionless}
1.0, !- Maximum Flow Rate {m3/s}
20.0, !- Reference Pressure Difference {Pa}
0.65; !- Air Mass Flow Exponent {dimensionless}
This object represents a duct component and requires 9
input fields, one alpha field and 8 numeric fields. An
additional two fields can be used to define the convection
coefficients on the inner and outer surfaces of the duct. The
relationship between pressure and airflow across the component
may be expressed as (2001 ASHRAE Handbook of Fundamentals,
Chapter 34):
\[\dot m = \sqrt {\frac{{2\rho
{A^2}\Delta P}}{{fL/D + \sum {C_d}}}}\]
where
\(\dot m\) = Mass flow
rate of air through the component [kg/s]
r = Air density [kg/m\(^{3}\)]
A = Cross sectional area [m\(^{2}\)]
\(\Delta P\) = Total
pressure loss across the component [Pa]
A unique name for an AirflowNetwork duct component in an
air distribution system. This unique name will be referenced
by an AirflowNetwork:Distribution:Linkage
object to represent a component.
This numeric field is used to input cross section area
[m\(^{2}\)]. The model
assumes that this element has no area change along its length.
Otherwise, effective cross sectional area is required.
This numeric field is used to input surface roughness [m].
This value must be greater than zero, and the default value is
0.0009 m.
Field:
Coefficient for Local Dynamic Loss Due to fitting[LINK]
This numeric field is defined as a coefficient for dynamic
loss [dimensionless]. It represents dynamic loss due to
fittings (such as an elbow).
Field:
Heat Transmittance Coefficient (U-Factor) for Duct Wall
Construction[LINK]
This numeric field is defines the heat transmittance
coefficient (U value, W/m\(^{2}\)-K) for the duct wall
construction. Film coefficents are calculated automatically,
unless directly specified below.
Field:
Overall Moisture Transmittance Coefficient from Air to
Air[LINK]
This numeric field is defined as the overall moisture
transmittance coefficient (kg/m\(^{2}\)) from air to air,
including film coefficients at both surfaces.
This numeric field defines the outside convection
coefficient (W/m\(^{2}\)-K).
If the field is omitted, the film coeffient is calculated
automatically as described in ASTM C1340.
This numeric field defines the inside convection
coefficient (W/m\(^{2}\)-K).
If the field is omitted, the film coeffient is calculated
automatically as described in ASTM C1340.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:Duct,
MainTruck1, !- Name of Duct Component
3.0, !- Duct Length {m}
0.6, !- Hydraulic Diameter {m}
0.2827, !- Cross Section Area {m2}
0.0009, !- Surface Roughness {m}
0.01, !- Coefficient for local dynamic loss due to fitting {dimensionless}
0.772, !- Heat Transmittance Coefficient (U-Factor) for Duct Wall Construction {W/m2-K}
0.0001; !- Overall moisture transmittance coefficient from air to air {kg/m2}
This component represents a constant or variable volume fan
in the air distribution system (AirLoopHVAC). The air flow
rate and air conditions (temperature and humidity) are
obtained from the associated Fan:ConstantVolume,Fan:OnOff,Fan:VariableVolume,
or Fan:SystemModel
object.
The name identifying an AirflowNetwork constant volume fan
in an air distribution system. This name must be the same as
the name of the associated Fan:ConstantVolume, Fan:OnOff,Fan:VariableVolume,
or Fan:SystemModel
object. This name will be referenced by an AirflowNetwork:Distribution:Linkage
object to represent a component.
Note: Make sure that the volumetric air flow rates for the
fan, coils, and parent components (e.g., unitary system or
furnace) are the same so that fan energy and air distribution
system losses/gains are properly calculated.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:Fan,
Supply Fan 1, !- Name of Constant Volume Fan
Fan:ConstantVolume; !- Supply fan type
This component represents a cooling or heating coil. The
main purpose for this object is to get calculated values (air
flow and temperature/humidity conditions) from the associated
coil models.
The name identifying an AirflowNetwork cooling coil or
heating coil defined in an air loop. This name must be the
same name as the associated coil object. This unique name will
be referenced by an AirflowNetwork:Distribution:Linkage
object to represent a component.
For this component, the relationship between airflow and
pressure is similar to the component AirflowNetwork:Distribution:Component:Duct.
However, the model assumes very small surface roughness
(10\(^{-4}\)) and no local
dynamic loss due to fittings for this component. Therefore,
this component only requires two numerical fields. Heat and
moisture exchange from surroundings is ignored.
Note: Make sure that the volumetric air flow rates for the
fan, coils, and parent components (e.g., unitary system or
furnace) are the same so that fan energy and air distribution
system losses/gains are properly calculated.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:Coil,
ACDXCoil 1, !- Name of Associated EnergyPlus Coil
Coil:Cooling:DX:SingleSpeed, !- EnergyPlus Coil Type
0.1, !- Air Path Length {m}
1.00; !- Air Path Hydraulic Diameter {m}
AirflowNetwork:Distribution:Component:Coil,
HP Heating Coil 1, !- Name of Associated EnergyPlus Coil
Coil:Heating:DX:SingleSpeed, !- EnergyPlus Coil Type
0.1, !- Air Path Length {m}
1.00; !- Air Path Hydraulic Diameter {m}
This component represents an air-to-air heat exchanger
typically used in combination with a cooling coil to enhance
dehumidification or in an outside air system to recover energy
from exhaust air to pretreat incoming outdoor ventilation air.
The cooling coils with enhanced dehumidification are defined
in the two objects CoilSystem:Cooling:DX:HeatExchangerAssisted
and CoilSystem:Cooling:Water:HeatExchangerAssisted
using one of three heat exchanger objects specified below. The
exhaust air energy recovery system also has the same
restriction using the one of three heat exchanger objects. The
main purpose for this object is to obtain calculated values
(air flow and temperature/humidity conditions) from the
associated heat exchanger models for the airflow network
calculations.
The name identifying an AirflowNetwork heat exchanger
defined in an air loop. This name must be the same name that
is used in the associated heat exchanger object. This unique
name will be referenced by an AirflowNetwork:Distribution:Linkage
object to represent a component.
For this component, the relationship between airflow and
pressure is similar to the component AirflowNetwork:Distribution:Component:Duct.
However, the model assumes very small surface roughness
(10\(^{-4}\)) and no local
dynamic loss due to fittings for this component. Therefore,
this component only requires two numerical fields. Heat and
moisture exchange from surroundings are ignored.
Note: When a heat exchanger is used as a component of
either CoilSystem:Cooling:DX:HeatExchangerAssisted
or CoilSystem:Cooling:Water:HeatExchangerAssisted,
the heat exchanger acts as two components in an air primary
loop. For example, an air-to-air heat exchanger has a
component connected to the supply air side (equivalent to a
supply coil) and a component connected to exhaust air side
(equivalent to an exhaust coil). The desiccant heat exchanger
has a component connected to regeneration air side (equivalent
to a regeneration air coil) and a component connected to
process air side (equivalent to a process air coil).
Therefore, each air-to-air heat exchanger used in this
configuration requires two linkage objects (instead of only
one linkage object as required for other AirflowNetwork
components).
When a heat exchanger is used in an exhaust air energy
recovery system (i.e., in an AirLoopHVAC:OutdoorAirSystem
object to recover waste heat from exhaust air to pretreat
incoming outdoor ventilation air), the heat exchanger is
treated as a single component. The AirflowNetwork model only
connects the two nodes associated with the incoming outdoor
ventilation air, while the two exhaust nodes are not defined
as part of the AirflowNetwork model. Therefore, each heat
exchanger component used in an exhaust air energy recovery
system has only one linkage object, similar to AirflowNetwork
coil components.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:HeatExchanger,
OA Heat Recovery 1, !- HeatExchanger Name
HeatExchanger:AirToAir:SensibleAndLatent, !- HeatExchanger Object Type
0.1, !- Air Path Length {m}
1.00; !- Air Path Hydraulic Diameter {m}
AirflowNetwork:Distribution:Component:HeatExchanger,
Desiccant Heat Exchanger 1, !- HeatExchanger Name
HeatExchanger:Desiccant:BalancedFlow, !- HeatExchanger Object Type
0.1, !- Air Path Length {m}
1.00; !- Air Path Hydraulic Diameter {m}
This component represents a terminal unit for reheating the
incoming supply air. The main purpose is to get calculated
values from the terminal unit models.
A name identifying an AirflowNetwork terminal unit defined
in a zone equipment list. This name must be the same as the
associated terminal unit object. This unique name will be
referenced by an AirflowNetwork:Distribution:Linkage
object to represent a component.
It should be noted that the relationship for this component
between airflow and pressure is similar to the component AirflowNetwork:Distribution:Component:Duct.
However, the model assumes very small surface roughness
(10\(^{-4}\)) and no local
dynamic loss due to fittings for this component. Therefore,
this component only requires two numerical fields. Heat and
moisture exchange from surroundings is ignored.
AirflowNetwork:Distribution:Component:TerminalUnit,
Reheat Zone 1, !- Name of Associated Energyplus Terminal Unit
AirTerminal:SingleDuct:ConstantVolume:Reheat, !- EnergyPlus Terminal Unit Type
0.1, !- Air Path Length {m}
0.44; !- Air Path Hydraulic Diameter {m}
This component represents a constant pressure drop
component. It is generally used to simulate a constant
pressure drop filter. The mathematical equation may be written
as:
A unique name identifying an AirflowNetwork constant
pressure drop component in an air distribution system. This
unique name will be referenced by an AirflowNetwork:
Distribution:Linkage object to represent a component.
Field:
Pressure Difference across the Component[LINK]
This numeric field is used to input the pressure difference
across the element [Pa].
Note: This object should be used with caution. Each node
connected to this object cannot be a node for a mixer or
splitter, a node in an AirLoopHVAC,
or a node in a zone configuration loop. It is recommended that
duct components be specified at both ends of this object.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:ConstantPressureDrop,
SupplyCPDComp, ! Name of Constant Pressure Drop Component
1.0; ! Pressure Difference Across the Component [Pa]
The AirflowNetwork:Distribution:Component:OutdoorAirFlow
object is used to allow the AirflowNetwork model to include
the outdoor air flow rate in the airflow network. When the
outdoor air mass flow rate is greater than zero, the airflow
network model treats this object as a constant volume fan and
the flow rate is provided by the Controller:OutdoorAir
object. When there is no outdoor air flow rate, the model
treats this object as a crack and a power law is assumed.
The name identifying an AirflowNetwork OutdoorAirFlow
defined in an air loop as an OutdoorAir:Mixer
object. This name must be the same name as the associated OutdoorAir:Mixer
object.
Field:
Air Mass Flow Coefficient When No Outdoor Air Flow at
Reference Conditions[LINK]
The value of the air mass flow coefficient, \({C_Q}\), in the crack air flow
equation. It has units of kg/s at 1Pa. This value must be
greater than zero. The value is used when when the outdoor
mass flow rate is zero from the Controller:OutdoorAir
object.
Field:
Air Mass Flow Exponent When No Outdoor Air Flow[LINK]
The value of the exponent, n, in the crack air
flow equation. The valid range is 0.5 to 1.0, with the default
value being 0.65. The value is used when the outdoor mass flow
rate is zero from the Controller:OutdoorAir
object.
The name of the AirflowNetwork:MultiZone:ReferenceCrackConditions
object which specifies the conditions under which the air mass
flow coefficient was measured. If the user omits this field
and only one AirflowNetwork:MultiZone:ReferenceCrackConditions
object is defined in the input data file, then those reference
crack conditions will be used. If the user omits this field
and either zero or more than one AirflowNetwork:MultiZone:ReferenceCrackConditions
objects are defined in the input data file, then the default
conditions for the AirflowNetwork:MultiZone: Reference Crack
Conditions object will be used.
IDF examples are provided below:
AirflowNetwork:MultiZone:Component:OutdoorAirFlow,
OAFlow, !- Name
OA Mixer 1, !- Outdoor Air Mixer Name
0.01, !- Air Mass Flow Coefficient When No Outdoor Air Flow at Reference Conditions {kg/s}
0.667; !- Air Mass Flow Exponent When No Outdoor Air Flow {dimensionless}
AirflowNetwork:Distribution:Node,
OA System Node, !- Name
, !- Component Name or Node Name
AirLoopHVAC:OutdoorAirSystem, !- Component Object Type or Node Type
3.0; !- Node Height {m}
AirflowNetwork:Distribution:Node,
OA Inlet Node, !- Name
Outside Air Inlet Node, !- Component Name or Node Name
OAMixerOutdoorAirStreamNode, !- Component Object Type or Node Type
1.5; !- Node Height {m}
AirflowNetwork:Distribution:Linkage,
OASystemFanLink, !- Name
OA Inlet Node, !- Node 1 Name
OA System Node, !- Node 2 Name
OAFlow; !- Component Name
The AirflowNetwork:Distribution:Component:ReliefAirFlow
object is used to allow the AirflowNetwork model to perform
pressure control by varying the amount of relief air flow rate
between 0 and the flow rate specified by the Controller:OutdoorAir
object. When the outdoor air mass flow rate is greater than
zero, the airflow network model treats this object as a
constant volume fan and the flow rate is varied to reach
pressure control. When there is no outdoor air flow rate, the
model treats this object as a crack and a power law is
assumed.
The name identifying an AirflowNetwork OutdoorAirFlow
defined in an air loop as an OutdoorAir:Mixer
object. This name must be the same name as the associated OutdoorAir:Mixer
object.
Field:
Air Mass Flow Coefficient When No Outdoor Air Flow at
Reference Conditions[LINK]
The value of the air mass flow coefficient, \({C_Q}\), in the crack air flow
equation. It has units of kg/s at 1Pa. This value must be
greater than zero. The value is used when the outdoor mass
flow rate is zero from the Controller:OutdoorAir
object.
Field:
Air Mass Flow Exponent When No Outdoor Air Flow[LINK]
The value of the exponent, n, in the crack air
flow equation. The valid range is 0.5 to 1.0, with the default
value being 0.65. The value is used when the outdoor mass flow
rate is zero from the Controller:OutdoorAir
object.
The name of the AirflowNetwork:MultiZone:ReferenceCrackConditions
object which specifies the conditions under which the air mass
flow coefficient was measured. If the user omits this field
and only one AirflowNetwork:MultiZone:ReferenceCrackConditions
object is defined in the input data file, then those reference
crack conditions will be used. If the user omits this field
and either zero or more than one AirflowNetwork:MultiZone:ReferenceCrackConditions
objects are defined in the input data file, then the default
conditions for the AirflowNetwork:MultiZone: Reference Crack
Conditions object will be used.
IDF examples are provided below:
AirflowNetwork:ZoneControl:PressureController,
Pressure Controller1, !- Name
EAST ZONE, !- Controlled Zone Name
AirflowNetwork:Distribution:Component:ReliefAirFlow, !- Control Object type
ReliefFlow, !- Control Name
PressureAvailSchedule, !- Pressure Control Availability Schedule Name
PressureSetpointSchedule; !- Pressure Setpoint Schedule Name
AirflowNetwork:MultiZone:Component:ReliefAirFlow,
ReliefFlow, !- Name
OA Mixer 1, !- Outdoor Air Mixer Name
0.01, !- Air Mass Flow Coefficient When No Outdoor Air Flow at Reference Conditions {kg/s}
0.667; !- Air Mass Flow Exponent When No Outdoor Air Flow {dimensionless}
AirflowNetwork:Distribution:Node,
OA System Node, !- Name
, !- Component Name or Node Name
AirLoopHVAC:OutdoorAirSystem, !- Component Object Type or Node Type
3.0; !- Node Height {m}
AirflowNetwork:Distribution:Node,
OA Inlet Node, !- Name
Outside Air Inlet Node, !- Component Name or Node Name
OAMixerOutdoorAirStreamNode, !- Component Object Type or Node Type
1.5; !- Node Height {m}
AirflowNetwork:Distribution:Linkage,
OASystemFanLink, !- Name
OA System Node, !- Node 1 Name
OA Inlet Node, !- Node 2 Name
ReliefFlow; !- Component Name
Designates an AirflowNetwork component name associated with
the two nodes. The component name should be one of the
AirflowNetwork:Distribution:Component… object names.
Designates a thermal zone where the linkage is located. The
information provides the ambient conditions for duct elements
to calculate duct conduction losses (only used if component is
AirflowNetwork:Distribution:Component:Duct).
An IDF example is provided below:
AirflowNetwork:Distribution:Linkage,
Main Link 1, !- Name of Linkage
EquipmentInletNode, !- Node 1 Name
SupplyMainNode, !- Node 2 Name
MainTruck1, !- Component Name
Attic Zone; !- Thermal Zone Name
The AirflowNetwork linkage used in following output
variables includes surfaces defined in AirflowNetwork:MultiZone:Surface
objects, and linkages defined in AirflowNetwork:Distribution:Linkage
objects. The surface linkages represent airflows through
surface cracks or openings between two zones or between a zone
and outdoors. The distribution linkages represent airflows in
an air distribution system.
HVAC,Average,AFN Node Temperature [C]
HVAC,Average,AFN Node Humidity Ratio
[kgWater/kgDryAir]
HVAC,Average,AFN Node Total Pressure [Pa]
HVAC,Average,AFN Node Wind Pressure [Pa]
HVAC,Average,AFN Node CO2 Concentration [ppm]
HVAC,Average,AFN Node Generic Air Contaminant
Concentration [ppm]
HVAC,Average,AFN Linkage Node 1 to Node 2 Mass Flow
Rate [kg/s]
HVAC,Average,AFN Linkage Node 2 to Node 1 Mass Flow
Rate [kg/s]
This is the AirflowNetwork node temperature output in
degrees C. When a Fan:OnOff
object is used and is scheduled to operate in the cycling fan
operation mode, this value for AirflowNetwork:Distribution:Node
objects reflects the temperature when the fan is operating
(ON).
This is the AirflowNetwork node humidity ratio output in
kgWater/kgDryAir. When a Fan:OnOff
object is used and is scheduled to operate in the cycling fan
operation mode, this value for AirflowNetwork:Distribution:Node
objects reflects the humidity ratio when the fan is operating
(ON).
This is the AirflowNetwork node total pressure in Pa with
respect to outdoor barometric pressure. The total pressure is
the sum of static pressure, dynamic pressure, and elevation
impact at the node’s relative height. When a Fan:OnOff
object is used and is scheduled to operate in the cycling fan
operation mode, the value for AirflowNetwork:Distribution:Node
objects reflects the total pressure when the fan is operating
(ON). The total pressures for nodes associate with AirflowNetwork:MultiZone:Zone
objects are reported in different output variables
(below).
This is the AirflowNetwork node carbon dioxide
concentration level in parts per million (ppm). When a Fan:OnOff
object is used and is scheduled to operate in the cycling fan
operation mode, this value for AirflowNetwork:Distribution:Node
objects reflects the carbon dioxide when the fan is operating
(ON).
AFN
Node Generic Air Contaminant Concentration [ppm][LINK]
This is the AirflowNetwork node generic contaminant
concentration level in parts per million (ppm). When a Fan:OnOff
object is used and is scheduled to operate in the cycling fan
operation mode, this value for AirflowNetwork:Distribution:Node
objects reflects the carbon dioxide when the fan is operating
(ON).
This is the AirflowNetwork average zone total pressure in
Pa with respect to outdoor barometric pressure. This output is
only available when a Fan:OnOff
object is used in the air distribution system. The average
zone pressure is weighted by the system fan part-load ratio
using the calculated zone pressures during the fan on and off
periods for the system timestep. The system fan part-load
ratio is defined as the ratio of the air distribution system
mass flow rate (average for the simulation timestep) to the
system design mass flow rate.
Average zone pressure = (Zone pressure during on cycle *
Part-load ratio) + Zone
pressure during off cycle * (1.0 – Part-load ratio)
This is the AirflowNetwork zone total pressure in Pa with
respect to outdoor barometric pressure when the air
distribution system fan is operating (ON). This output is only
available when a Fan:OnOff
object is used in the air distribution system. When the fan
part-load ratio is equal to 0.0, this pressure value will be
zero because the air distribution system is not simulated when
the fan is off for the entire timestep.
This is the AirflowNetwork zone total pressure in Pa with
respect to outdoor barometric pressure when the air
distribution system fan is not operating (OFF). This output is
only available when a Fan:OnOff
object is used in the air distribution system. Even if the fan
part-load ratio is equal to 1.0, the pressure calculated as if
the fan were not operating (OFF) is reported.
This is the AirflowNetwork wind pressure output in Pa. The
wind pressure depends on several factors, including wind
speed, wind direction, the wind-pressure coefficient (Cp)
values for the AirflowNetwork:MultiZone:ExternalNode
associated with the heat transfer surface and the site wind
conditions.
In this case, the output represents the wind pressures for
the five external nodes defined above.
AFN
Linkage Node 1 to Node 2 Mass Flow Rate [kg/s][LINK]
This is the AirflowNetwork linkage mass flow rate output in
kg/s in the direction from Node 1 to Node 2. It reports
surface airflows through a crack or opening, and through
linkages defined in an AirflowNetwork:Distribution:Linkage
object. The surface linkage is divided into two types of
surfaces, exterior surface and interior surface. Node 1 for an
exterior surface linkage is a thermal zone and Node 2 is an
external node. The value of AFN Linkage Node 1 to Node 2 Mass
Flow Rate represents the flow rate from a thermal zone to
outdoors. The flow direction through an interior surface crack
or opening is defined from a thermal zone defined by a
surface’s Zone
Name (Node 1) to an adjacent thermal zone defined by a
surface’s OutsideFaceEnvironment (Node 2). For an AirflowNetwork:Distribution:Linkage
object, the value represents the air mass flow rate flowing
from Node 1 to Node 2.
When a Fan:OnOff
object is used, the air mass flow rates reported for the AirflowNetwork:Distribution:Linkage
objects are the values when the fan is operating (ON). It is
assumed that the air mass flow rates when the fan is off are
zero for the distribution system air linkage objects. The air
mass flow rates for the AirflowNetwork:MultiZone:Surface
object are reported in different output variables (below).
AFN
Linkage Node 2 to Node 1 Mass Flow Rate [kg/s][LINK]
This is the AirflowNetwork linkage mass flow rate output in
kg/s in the direction from Node 2 to Node 1. It reports
airflows from surfaces through a crack or opening, and from
linkages defined in an AirflowNetwork:Distribution:Linkage
object. Node 1 and Node 2 for a surface or subsurface are
defined in the same manner as AFN Linkage Node 1 to Node 2
Mass Flow Rate.
When a Fan:OnOff
object is used, the air mass flow rates reported for the AirflowNetwork:Distribution:Linkage
objects are the values when the fan is operating (ON). It is
assumed that the air mass flow rates when the fan is off are
zero for the distribution system air linkage objects. The air
mass flow rates for the AirflowNetwork:MultiZone:Surface
object are reported in different output variables (below).
AFN
Linkage Node 1 to 2 Average Mass Flow Rate [kg/s][LINK]
This is the AirflowNetwork linkage average mass flow rate
in kg/s in the direction from Node 1 to Node 2 defined in the
AirflowNetwork:MultiZone:Surface
objects. This output is only available when a Fan:OnOff
object is used in the air distribution system. The average
mass flow rate is weighted by the system fan part-load ratio
using the calculated air mass flow rates during the fan on and
off periods for the system timestep. The system fan part-load
ratio is defined as the ratio of the air distribution system
mass flow rate (average for the simulation timestep) to the
system design mass flow rate.
Average surface mass flow rate = (Surface mass flow rate
during on cycle * Part-load ratio) + Surface mass flow rate
during off cycle * (1.0 – Part-load ratio)
AFN
Linkage Node 2 to 1 Average Mass Flow Rate [kg/s][LINK]
This is the AirflowNetwork linkage average mass flow rate
in kg/s in the direction from Node 2 to Node 1 defined in the
AirflowNetwork:MultiZone:Surface
objects. This output is only available when a Fan:OnOff
object is used in the air distribution system. The average
mass flow rate is weighted by the system fan part-load ratio
using the calculated air mass flow rates during the fan on and
off periods for the system timestep. The system fan part-load
ratio is defined as the ratio of the air distribution system
mass flow rate (average for the simulation timestep) to the
system design mass flow rate.
This is the AirflowNetwork linkage volume flow rate output
in m\(^{3}\)/s in the
direction from the Node 1 to Node 2. It is defined in the same
manner as AFN Linkage Node 1 to Node 2 Mass Flow Rate.
When a Fan:OnOff
object is used, the air volume flow rates reported for the AirflowNetwork:Distribution:Linkage
objects are the values when the fan is operating (ON). It is
assumed that the air volume flow rates when the fan is off are
zero for the distribution system air linkage objects. The air
volume flow rates for the AirflowNetwork:MultiZone:Surface
object are reported in different output variables (below).
This is the AirflowNetwork linkage volume flow rate output
in m\(^{3}\)/s in the
direction from Node 2 to Node 1. It is defined in the same
manner as AFN Linkage Node 2 to Node 1 Mass Flow Rate.
When a Fan:OnOff
object is used, the air volume flow rates reported for the AirflowNetwork:Distribution:Linkage
objects are the values when the fan is operating (ON). It is
assumed that the air volume flow rates when the fan is off are
zero for the distribution system air linkage objects. The air
volume flow rates for the AirflowNetwork:MultiZone:Surface
object are reported in different output variables (below).
AFN
Linkage Node 1 to 2 Average Volume Flow Rate [m\(^{3}\)/s][LINK]
This is the AirflowNetwork linkage average volume flow rate
in m\(^{3}\)/s in the
direction from Node 1 to Node 2 defined in the AirflowNetwork:MultiZone:Surface
objects. This output is only available when a Fan:OnOff
object is used. The average volume flow rate is weighted by
the system fan part-load ratio using the calculated air volume
flow rates during the fan on and off periods for the system
timestep.
Average surface volume flow rate = (Surface volume flow
rate during on cycle * Part-load ratio) + Surface volume flow
rate during off cycle * (1.0 – Part-load ratio)
AFN
Linkage Node 2 to 1 Average Volume Flow Rate [m\(^{3}\)/s][LINK]
This is the AirflowNetwork linkage average volume flow rate
in m\(^{3}\)/s in the
direction from Node 2 to Node 1 defined in the AirflowNetwork:MultiZone:Surface
objects. This output is only available when a Fan:OnOff
object is used. The average volume flow rate is weighted by
the system fan part-load ratio using the calculated air volume
flow rates during the fan on and off periods for the system
timestep.
AFN
Linkage Node 1 to Node 2 Pressure Difference [Pa][LINK]
This is the pressure difference across a linkage in Pa. The
linkage includes both objects: AirflowNetwork:MultiZone:Surface
and AirflowNetwork: Distribution:Linkage.
When a Fan:OnOff
object is used, the pressure differences reported for the AirflowNetwork:Distribution:Linkage
objects are the values calculated when the fan is operating
(ON). It is assumed that the pressure differences when the fan
is off are zero for the distribution system air linkage
objects. The pressure differences defined in the AirflowNetwork:MultiZone:Surface
are reported in different output variables (below).
AFN
Surface Average Pressure Difference [Pa][LINK]
This is the average pressure difference across a linkage in
Pa for the AirflowNetwork:MultiZone:Surface
objects only when a Fan:OnOff
object is used. The average pressure difference is weighted by
the system fan part-load ratio using the calculated pressure
differences during the fan on and off periods for the system
timestep. The system fan part-load ratio is defined as the
ratio of the air distribution system mass flow rate (average
for the simulation timestep) to the system design mass flow
rate.
Surface Average Pressure Difference = (Surface Average
Pressure Difference during on cycle * Part-load ratio) +
Surface Average Pressure Difference during off cycle * (1.0 -
Part-load ratio)
AFN
Surface On Cycle Pressure Difference [Pa][LINK]
This is the pressure difference across a linkage in Pa for
the AirflowNetwork:MultiZone:Surface
objects only when the air distribution system fan is operating
(ON). This output is only available when a Fan:OnOff
object is used. When the fan part-load ratio is equal to 0.0,
this pressure difference value will be zero because the air
distribution system is not simulated when the fan is off for
the entire timestep.
AFN
Surface Off Cycle Pressure Difference [Pa][LINK]
This is the pressure difference across a linkage in Pa for
the AirflowNetwork:MultiZone:Surface
objects only when the air distribution system fan is not
operating (OFF). This output is only available when a Fan:OnOff
object is used. Even if the fan part-load ratio is equal to
1.0, the pressure difference calculated as if the fan were not
operating (OFF) is reported.
AFN
Surface Venting Window or Door Opening Factor [][LINK]
The current time-step value of the venting opening factor
for a particular window or door. When the window or door is
venting, this is the input value of the opening factor (see AirflowNetwork:MultiZone:Surface,
Window/Door Opening Factor) times the multiplier for venting
modulation (see description of next output variable, “Opening
Factor Multiplier for AirflowNetwork Venting Modulation”). For
example, if the input Window/Door opening factor is 0.5 and
the modulation multiplier is 0.7, then the value of this
output variable will be 0.5x0.7 = 0.35.
AFN
Surface Venting Window or Door Opening Modulation Multiplier
[][LINK]
This is the multiplier on a window or door opening factor
when venting modulation is in effect. See “Modulation of
Openings” under AirflowNetwork:MultiZone:Zone
for a description of how the multiplier is determined.
When modulation is in effect the value of the multiplier is
between 0.0 and 1.0. When modulation does not apply the value
of the multiplier may be –1.0. When modulation applies but the
surface is not venting, the value is –1.0. This is summarized
in the following table. In this table, “Zone”
means a thermal zone for which AirflowNetwork:MultiZone:Zone
has been specified. See object AirflowNetwork: MultiZone:Zone
for definition of “Ventilation Control Mode.”
Value of opening factor multiplier for different
venting conditions
Is surface in a Zone?
Ventilation Control Mode
Is surface venting?
Value of opening factor
multiplier
Yes
0.0 to 1.0
No
-1.0
Yes
0.0 to 1.0
Yes
No
-1.0
Constant
Yes
1.0
NoVent
No
-1.0
AFN
Surface Venting Inside Setpoint Temperature [C][LINK]
The time-step value of the venting setpoint temperature for
the zone to which the surface belongs. This setpoint is
determined from the Vent Temperature Schedule input (ref:
AirflowNetwork:MultiZone:Zone).
A value of 1.0 means venting through the surface can occur
if venting control conditions are satisfied. A value of 0.0
means venting through the surface cannot occur under any
circumstances. This value is determined by the Venting
Availability Schedule input (ref: AirflowNetwork:MultiZone:Zone
or AirflowNetwork:MultiZone:Surface).
AFN
Zone Infiltration Sensible Heat Gain Rate [W][LINK]
The average convective sensible heat gain rate, in Watts,
to the zone air corresponding to the Zone
Infiltration flows from both AirflowNetwork:MultiZone:Surface:Crack
and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea
only averaged over the reporting period. This value is
calculated for each timestep when the outdoor dry-bulb
temperature is higher than the zone temperature; otherwise,
the sensible gain rate is set to 0.
When a Fan:OnOff
object is used, this reported value is weighted by the system
run time fraction using the calculated infiltration sensible
gain rate during the system on and off cycles for the
reporting period:
Infiltration Sensible Gain Rate = (Infiltration Sensible
Gain Rate during on cycle * Run time fraction) + Infiltration
Sensible Gain Rate during off cycle * (1.0 – Run time
fraction)
AFN
Zone Infiltration Sensible Heat Gain Energy [J][LINK]
The average convective sensible heat gain, in Joules, to
the zone air corresponding to the Zone
Infiltration flows from both AirflowNetwork:MultiZone:Surface:Crack
and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea
only averaged over the reporting period. This value is
calculated for each timestep when the outdoor dry-bulb
temperature is higher than the zone temperature; otherwise,
the sensible gain rate is set to 0.
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated infiltration sensible
gain during the system on and off cycles for the reporting
period:
Infiltration Sensible Gain = (Infiltration Sensible Gain
during on cycle * Run time fraction) + Infiltration Sensible
Gain during off cycle * (1.0 – Run time fraction)
AFN
Zone Infiltration Sensible Heat Loss Rate [W][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated infiltration sensible
loss rate during the system on and off cycles for the
reporting period:
Infiltration Sensible Loss Rate = (Infiltration Sensible
Loss Rate during on cycle * Run time fraction) + Infiltration
Sensible Loss Rate during off cycle * (1.0 – Run time
fraction)
AFN
Zone Infiltration Sensible Heat Loss Energy [J][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated infiltration sensible
loss rate during the system on and off cycles for the
reporting period:
Infiltration Sensible Loss = (Infiltration Sensible Loss
during on cycle * Run time fraction) + Infiltration Sensible
Loss during off cycle * (1.0 – Run time fraction)
AFN
Zone Infiltration Latent Heat Gain Rate [W][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated infiltration latent
gain rate during the system on and off cycles for the
reporting period:
Infiltration Latent Gain Rate = (Infiltration Latent Gain
Rate during on cycle * Run time fraction) + Infiltration
Latent Gain Rate during off cycle * (1.0 – Run time
fraction)
AFN
Zone Infiltration Latent Heat Gain Energy [J][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated infiltration latent
gain during the system on and off cycles for the reporting
period:
Infiltration Latent Gain = (Infiltration Latent Gain during
on cycle * Run time fraction) + Infiltration Latent Gain
during off cycle * (1.0 – Run time fraction)
AFN
Zone Infiltration Latent Heat Loss Rate [W][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated infiltration latent
loss rate during the system on and off cycles for the
reporting period:
Infiltration Latent Loss Rate = (Infiltration Latent Gain
Loss Rate during on cycle * Run time fraction) + Infiltration
Latent Loss Rate during off cycle * (1.0 – Run time
fraction)
AFN
Zone Infiltration Latent Heat Loss Energy [J][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated infiltration latent
loss during the system on and off cycles for the reporting
period:
Infiltration Latent Loss = (Infiltration Latent Gain Loss
during on cycle * Run time fraction) + Infiltration Latent
Loss during off cycle * (1.0 – Run time fraction)
AFN
Zone Ventilation Sensible Heat Gain Rate [W][LINK]
When a Fan:OnOff
object is used, this reported value is weighted by the system
run time fraction using the calculated ventilation sensible
gain rate during the system on and off cycles for the
reporting period:
Ventilation Sensible Gain Rate = (Ventilation Sensible Gain
Rate during on cycle * Run time fraction) + Ventilation
Sensible Gain Rate during off cycle * (1.0 – Run time
fraction)
AFN
Zone Ventilation Sensible Heat Gain Energy [J][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated ventilation sensible
gain during the system on and off cycles for the reporting
period:
Ventilation Sensible Gain = (Ventilation Sensible Gain
during on cycle * Run time fraction) + Ventilation Sensible
Gain during off cycle * (1.0 – Run time fraction)
AFN
Zone Ventilation Sensible Heat Loss Rate [W][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated ventilation sensible
loss rate during the system on and off cycles for the
reporting period:
Ventilation Sensible Loss Rate = (Ventilation Sensible Loss
Rate during on cycle * Run time fraction) + Ventilation
Sensible Loss Rate during off cycle * (1.0 – Run time
fraction)
AFN
Zone Ventilation Sensible Heat Loss Energy [J][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated Ventilation sensible
loss rate during the system on and off cycles for the
reporting period:
Ventilation Sensible Loss = (Ventilation Sensible Loss
during on cycle * Run time fraction) + Ventilation Sensible
Loss during off cycle * (1.0 – Run time fraction)
AFN Zone
Ventilation Latent Heat Gain Rate [W][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated Ventilation latent gain
rate during the system on and off cycles for the reporting
period:
Ventilation Latent Gain Rate = (Ventilation Latent Gain
Rate during on cycle * Run time fraction) + Ventilation Latent
Gain Rate during off cycle * (1.0 – Run time fraction)
AFN
Zone Ventilation Latent Heat Gain Energy [J][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated ventilation latent gain
during the system on and off cycles for the reporting
period:
Ventilation Latent Gain = (Ventilation Latent Gain during
on cycle * Run time fraction) + Ventilation Latent Gain during
off cycle * (1.0 – Run time fraction)
AFN Zone
Ventilation Latent Heat Loss Rate [W][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated Ventilation latent loss
rate during the system on and off cycles for the reporting
period:
Ventilation Latent Loss Rate = (Ventilation Latent Gain
Loss Rate during on cycle * Run time fraction) + Ventilation
Latent Loss Rate during off cycle * (1.0 – Run time
fraction)
AFN
Zone Ventilation Latent Heat Loss Energy [J][LINK]
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated Ventilation latent loss
during the system on and off cycles for the reporting
period:
Ventilation Latent Loss = (Ventilation Latent Gain Loss
during on cycle * Run time fraction) + Ventilation Latent Loss
during off cycle * (1.0 – Run time fraction)
The average convective sensible heat gain rate, in Watts,
to the zone air corresponding to the Zone
Mixing Volume averaged over the reporting period. The
mixing-volume is defined as incoming volume flow from other
adjacent zones where the air temperature is higher than the
temperature in this zone. For example, there are two zones
(Zone 2 and Zone
3) adjacent to this zone (Zone 1). Zone
1 receives airflows from both Zone
2 and Zone
3. The air temperature is 21°C in Zone
1. The air temperatures are 20°C in Zone
2 and 22°C in Zone
3. The sensible gain rate only includes heat gain from Zone
3 with respect to Zone
1. The energy received from Zone
2 is considered as a sensible loss, instead of a gain, because
the air temperature in Zone
2 is lower than in Zone
1.
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated mixing sensible gain
rate during the system on and off cycles for the reporting
period:
Mixing Sensible Gain Rate = (Mixing Sensible Gain Rate
during on cycle * Run time fraction) + Mixing Sensible Gain
Rate during off cycle * (1.0 – Run time fraction)
The average convective sensible heat loss rate, in Watts,
to the zone air corresponding to the Zone
Mixing Volume averaged over the reporting period.
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated mixing sensible loss
rate during the on and off cycles for the reporting
period:
Mixing Sensible Loss Rate = (Mixing Sensible Loss Rate
during on cycle * Run time fraction) + Mixing Sensible Loss
Rate during off cycle * (1.0 – Run time fraction)
AFN Zone
Mixing Sensible Heat Gain Energy [J][LINK]
The total convective sensible heat gain, in Joules, to the
zone air corresponding to the Zone
Mixing Volume summed over the reporting period.
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated mixing sensible gain
during the on and off cycles for the reporting period:
Mixing Sensible Gain = (Mixing Sensible Gain during on
cycle * Run time fraction) + Mixing Sensible Gain during off
cycle * (1.0 – Run time fraction)
AFN Zone
Mixing Sensible Heat Loss Energy [J][LINK]
The total convective sensible heat loss, in Joules, to the
zone air corresponding to the Zone
Mixing Volume summed over the reporting period.
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated mixing sensible loss
during the on and off cycles for the reporting period:
Mixing Sensible Loss = (Mixing Sensible Loss during on
cycle * Run time fraction) + Mixing Sensible Loss during off
cycle * (1.0 – Run time fraction)
The average convective latent heat gain rate, in Watts, to
the zone air corresponding to the Zone
Mixing Volume averaged over the reporting period.
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated mixing latent gain rate
during the on and off cycles for the reporting period:
Mixing Latent Gain Rate = (Mixing Latent Gain Rate during
on cycle * Run time fraction) + Mixing Latent Gain Rate during
off cycle * (1.0 – Run time fraction)
The total convective latent heat gain, in Joules, to the
zone air corresponding to the Zone
Mixing Volume summed over the reporting period.
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated mixing latent gain
during the on and off cycles for the reporting period:
Mixing Latent Gain = (Mixing Latent Gain during on cycle *
Run time fraction) + Mixing Latent Gain during off cycle *
(1.0 – Run time fraction)
The average convective latent heat loss rate, in Watts, to
the zone air corresponding to the Zone
Mixing Volume averaged over the reporting period.
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated mixing latent loss rate
during the on and off cycles for the reporting period:
Mixing Latent Loss Rate = (Mixing Latent Loss Rate during
on cycle * Run time fraction) + Mixing Latent Loss Rate during
off cycle * (1.0 – Run time fraction)
The total convective latent heat loss, in Joules, to the
zone air corresponding to the Zone
Mixing Volume summed over the reporting period.
When a Fan:OnOff
object is used, the reported value is weighted by the system
run time fraction using the calculated mixing latent loss
during the on and off cycles for the reporting period:
Mixing Latent Loss = (Mixing Latent Loss during on cycle *
Run time fraction) + Mixing Latent Loss during off cycle *
(1.0 – Run time fraction)
This is a sum of mass flow rates from adjacent zones
multiplied by the corresponding zone carbon dioxide
concentration level to the receiving zone. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the mixing mass flow rate calculated
during the fan on and off periods for the simulation
timestep.
AFN
Zone Mixing Generic Air Contaminant Mass Flow Rate [kg/s][LINK]
This is a sum of mass flow rates from adjacent zones
multiplied by the corresponding zone generic contaminant
concentration level to the receiving zone. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the mixing mass flow rate calculated
during the fan on and off periods for the simulation
timestep.
AFN
Zone Duct Leaked Air Sensible Heat Gain Rate [W][LINK]
This is the average sensible heat gain rate, in Watts, to a
specific zone due to supply air leaks from the forced air
distribution system. This value is averaged over the reporting
period. A sensible heat gain occurs when duct air is warmer
than zone air. It should be pointed out that when multiple
supply air leaks are present in a single zone, the output
value is the summation of all the supply air leak gains in
this zone. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Leaked Air Sensible Heat Gain Energy [J][LINK]
This is the total sensible heat gain, in Joules, to a
specific zone due to supply air leaks summed over the
reporting period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Leaked Air Sensible Heat Loss Rate [W][LINK]
This is the average sensible heat loss rate, in Watts, to a
specific zone due to supply air leaks from the forced air
distribution system. This value is averaged over the reporting
period. A sensible heat loss occurs when duct air is cooler
than zone air. It should be pointed out that when multiple
supply air leaks are present in this zone, the output value is
the summation of all the supply air leak losses in this zone.
When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Leaked Air Sensible Heat Loss Energy [J][LINK]
This is the total sensible heat loss, in Joules, to a
specific zone due to supply air leaks summed over the
reporting period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Leaked Air Latent Heat Gain Rate [W][LINK]
This is the average latent heat gain rate, in Watts, to a
specific zone due to supply air leaks from the forced air
distribution system for the reported time period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Leaked Air Latent Heat Gain Energy [J][LINK]
This is the total latent heat gain, in Joules, to a
specific zone due to supply air leaks summed over the
reporting period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Leaked Air Latent Heat Loss Rate [W][LINK]
This is the average latent heat loss rate, in Watts, to a
specific zone due to supply air leaks from the forced air
distribution system for the reported time period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Leaked Air Latent Heat Loss Energy [J][LINK]
This is the total latent heat loss, in Joules, to a
specific zone due to supply air leaks summed over the
reporting period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Conduction Sensible Heat Gain Rate [W][LINK]
This is the average sensible heat gain rate, in Watts, of
duct conduction to a specific zone where the ducts are
located. This value is averaged over the reporting period. A
sensible heat gain occurs when duct air is warmer than the
zone air. It should be pointed out that when ducts are located
in different zones, the total duct conduction loss should be
the summation of the duct conduction losses in these zones.
When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Conduction Sensible Heat Gain Energy [J][LINK]
This is the total sensible heat gain, in Joules, to a
specific zone due to duct conduction summed over the reporting
period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Conduction Sensible Heat Loss Rate [W][LINK]
This is the average sensible heat loss rate, in Watts, of
duct conduction to a specific zone where the ducts are
located. This value is averaged over the reporting period. A
sensible heat loss occurs when duct air is cooler than the
zone air. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Conduction Sensible Heat Loss Energy [J][LINK]
This is the total sensible heat loss, in Joules, to a
specific zone due to duct conduction summed over the reporting
period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Diffusion Latent Heat Gain Rate [W][LINK]
This is the average latent heat gain rate, in Watts, of
vapor diffusion through the walls of the air distribution
system to a specific zone where the ducts are located. This
value is averaged over the reporting period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Diffusion Latent Heat Gain Energy [J][LINK]
This is the total latent heat gain, in Joules, to a
specific zone due to duct vapor diffusion summed over the
reporting period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Diffusion Latent Heat Loss Rate [W][LINK]
This is the average latent heat loss rate, in Watts, of
duct vapor diffusion to a specific zone where the ducts are
located. This value is averaged over the reporting period.
When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Duct Diffusion Latent Heat Loss Energy [J][LINK]
This is the total latent heat loss, in Joules, to a
specific zone due to duct vapor diffusion summed over the
reporting period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Distribution Sensible Heat Gain Rate [W][LINK]
This is the average total sensible heat gain rate, in
Watts, in a specific zone caused by the forced air
distribution system. The total sensible gain rate is the sum
of duct leakage sensible gain rate and duct conduction
sensible gain rate. This value is averaged over the reporting
period. The multizone airflow sensible gain rate is excluded
in this output variable. The output of multizone airflow
sensible gain is reported in the previously-described output
variables AFN Zone
Infiltration Sensible Heat Gain Rate and AFN Zone
Mixing Sensible Heat Gain Rate. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Distribution Sensible Heat Gain Energy [J][LINK]
This is the total sensible heat gain, in Joules, in a
specific zone caused by the forced air distribution system.
The total sensible gain is the sum of duct leakage sensible
gain and duct conduction sensible gain. This value is summed
over the reporting period. The multizone airflow sensible gain
is excluded in this output variable. The output of multizone
airflow sensible gain is reported in the previously-described
output variables AFN Zone
Infiltration Sensible Heat Gain Energy and AFN Zone
Mixing Sensible Heat Gain Energy. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Distribution Sensible Heat Loss Rate [W][LINK]
This is the average total sensible heat loss rate, in
Watts, in a specific zone caused by the forced air
distribution system. The total sensible loss rate is the sum
of duct leakage sensible loss rate and duct conduction
sensible loss rate. This value is averaged over the reporting
period. The multizone airflow sensible loss rate is excluded
in this output variable. The output of multizone airflow
sensible loss rate is reported in the previously-described
output variables AFN Zone
Infiltration Sensible Heat Loss Rate and AFN Zone
Mixing Sensible Heat Loss Rate. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Distribution Sensible Heat Loss Energy [J][LINK]
This is the total sensible heat loss, in Joules, in a
specific zone caused by the forced air distribution system.
The total sensible loss is the sum of duct leakage sensible
loss and duct conduction sensible loss. This value is summed
over the reporting period. The multizone airflow sensible loss
is excluded in this output variable. The output of multizone
airflow sensible loss is reported in the previously-described
output variables AFN Zone
Infiltration Sensible Heat Loss Energy and AFN Zone
Mixing Sensible Heat Loss Energy. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
This is the average total latent heat gain rate, in Watts,
in a specific zone caused by the forced air distribution
system. The total latent gain rate is the sum of duct leakage
latent gain rate and duct conduction latent gain rate. This
value is averaged over the reporting period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Distribution Latent Heat Gain Energy [J][LINK]
This is the total latent heat gain, in Joules, in a
specific zone caused by the forced air distribution system.
The total latent gain is the sum of duct leakage latent gain
and duct diffusion latent gain. This value is summed over the
reporting period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
This is the average total latent heat loss rate, in Watts,
in a specific zone caused by the forced air distribution
system. The total latent loss rate is a sum of duct leakage
latent loss rate and duct diffusion latent loss rate. This
value is averaged over the reporting period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Distribution Latent Heat Loss Energy [J][LINK]
This is the total latent heat loss, in Joules, in a
specific zone caused by the forced air distribution system.
The total latent loss is the sum of duct leakage latent loss
and duct diffusion latent loss. This value is summed over the
reporting period. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
NOTE: The following output variables
should not be confused with similar output variables for the
infiltration, mixing, and cross mixing objects (Ref.
Infiltration Output, Mixing Output, or Cross Mixing Output).
The output variables described below refer to infiltration,
mixing, and cross-mixing when an Airflow Network Simulation is
performed. The following output variables are always used to
describe infiltration, mixing, and cross mixing when the
AirflowNetwork Control field in the AirflowNetwork:SimulationControl
object is set to “MultiZoneWithoutDistribution” or
“MultiZoneWithDistribution”. In this case the output variables
for the infiltration, mixing, and cross mixing objects will
always be 0.
In contrast, the following output variables are only used
to describe infiltration, mixing, and cross mixing when the
AirflowNetwork Control field in the AirflowNetwork:SimulationControl
object is set to
“MultiZoneAirflowWithDistributionOnlyDuringFanOperation” and
the fan is operating. When the fan is not operating, the
output variables for the infiltration, mixing, and cross
mixing objects are used.
In the case where the AirflowNetwork Control field in the
AirflowNetwork:SimulationControl
object is set to “NoMultiZoneOrDistribution”, the following
output variables are not used and the output variables for the
infiltration, mixing, and cross mixing objects are used
instead.
AFN
Zone Infiltration Sensible Heat Gain Energy [J][LINK]
The total convective sensible heat gain, in Joules, to the
zone air corresponding to the Zone
Infiltration Volume summed over the reporting period. This
value is calculated for each timestep when the outdoor
dry-bulb temperature is higher than the zone temperature,
otherwise the sensible gain is set to 0. When a Fan:OnOff
object is used, the reported value is for the system on
cycle.
AFN
Zone Infiltration Sensible Heat Loss Energy [J][LINK]
The total convective sensible heat loss, in Joules to the
zone air corresponding to the Zone
Infiltration Volume summed over the reporting period. When a
Fan:OnOff
object is used, the reported value is for the system on
cycle.
The volume of outdoor air flow into the zone from
window/door cracks in the exterior surfaces of the zone from
both AirflowNetwork:MultiZone:Surface:Crack
and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea
only averaged over the reporting period (i.e., the sum of
infiltration and crack flows from the exterior into the zone).
The zone air density is used to calculate the zone
infiltration volume based on the mass flow rate. Note that
AirflowNetwork Zone
Infiltration Volume will be zero if all of the flows through
the zone’s exterior surfaces are out of the zone. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the infiltration volume calculated
during the fan on and off periods for the simulation
timestep.
The mass of air corresponding to the AirflowNetwork Zone
Infiltration Volume from both AirflowNetwork:MultiZone:Surface:Crack
and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea
only averaged over the reporting period. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the infiltration mass calculated
during the fan on and off periods for the simulation
timestep.
The number of air changes per hour produced by outdoor air
flow into the zone from window/door cracks in the exterior
surfaces of the zone from both AirflowNetwork:MultiZone:Surface:Crack
and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea
only averaged over the reporting period (i.e. the sum of
infiltration and crack flows from the exterior into the zone).
The target zone air density is used to calculate the zone
infiltration air change rate based on the mass flow rate Note
that, like Zone
Infiltration Volume, Zone
Infiltration Air Change Rate will be zero if all flows through
the zone’s exterior surfaces are out of the zone. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the infiltration air change rate
calculated during the fan on and off periods for the
simulation timestep.
The volume of outdoor air flow into the zone from
window/door openings in the exterior surfaces of the zone from
AirflowNetwork:MultiZone:Component:DetailedOpening,AirflowNetwork:MultiZone:Component:SimpleOpening,
and AirflowNetwork:MultiZone:Component:HorizontalOpening
only averaged over the reporting period (i.e., the sum of
ventilation and opening flows from the exterior into the
zone). The zone air density is used to calculate the zone
ventilation volume based on the mass flow rate. Note that
AirflowNetwork Zone
Ventilation Volume will be zero if all of the flows through
the zone’s exterior surfaces are out of the zone. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the ventilation volume calculated
during the fan on and off periods for the simulation
timestep.
The number of air changes per hour produced by outdoor air
flow into the zone from window/door openings in the exterior
surfaces of the zone from AirflowNetwork:MultiZone:Component:DetailedOpening,AirflowNetwork:MultiZone:Component:SimpleOpening,
and AirflowNetwork:MultiZone:Component:HorizontalOpening
only averaged over the reporting period (i.e. the sum of
ventilation and opening flows from the exterior into the
zone). The target zone air density is used to calculate the
zone ventilation air change rate based on the mass flow rate
Note that, like Zone
Ventilation Volume, Zone
Ventilation Air Change Rate will be zero if all flows through
the zone’s exterior surfaces are out of the zone. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the ventilation air change rate
calculated during the fan on and off periods for the
simulation timestep.
This is a measure of interzone air flow for each thermal
zone. It is the volume of air flow into the zone from adjacent
zones through window/door openings and cracks in the interior
heat transfer surfaces of the zone. The target zone air
density is used to calculate the zone mixing volume based on
the mass flow rate. This variable does not include flows that
are from the zone to adjacent zones. Note that Zone
Mixing Volume will be zero if all flows through the zone’s
interior surfaces are out of the zone. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the mixing volume calculated during
the fan on and off periods for the simulation timestep.
The mass of air corresponding to the AFN Zone
Mixing Volume. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the mixing mass calculated during
the fan on and off periods for the simulation timestep.
This is a sum of mass flow rates from adjacent zones to the
receiving zone. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the mixing mass flow rate calculated
during the fan on and off periods for the simulation
timestep.
AFN Zone
Outdoor Air CO2 Mass Flow Rate [kg/s][LINK]
This is a sum of mass flow rates from outdoors multiplied
by the outdoor carbon dioxide concentration level to the
receiving zone. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the outdoor mass flow rate
calculated during the fan on and off periods for the
simulation timestep.
AFN
Zone Outdoor Air Generic Air Contaminant Mass Flow Rate
[kg/s][LINK]
This is a sum of mass flow rates from outdoors multiplied
by the outdoor generic air contaminant concentration level to
the receiving zone. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the outdoor mass flow rate
calculated during the fan on and off periods for the
simulation timestep
This is a sum of mass flow rates from outdoors to the
receiving zone. When a Fan:OnOff
object is used, the reported value is weighted by the system
fan part-load ratio using the outdoor mass flow rate
calculated during the fan on and off periods for the
simulation timestep.
This is a sum of mass flow rates from adjacent zones or
outdoors multiplied by the carbon dioxide concentration
differences between the corresponding zone and the receiving
zone.
AFN
Zone Total Generic Air Contaminant Mass Flow Rate [kg/s][LINK]
This is a sum of mass flow rates from adjacent zones or
outdoors multiplied by the generic contaminant concentration
differences between the corresponding zone and the receiving
zone.
AFN
Surface Venting Window or Door Opening Factor at Previous Time
Step [][LINK]
The value of the venting opening factor for a particular
window or door at the previous time step. When the window or
door is venting, this is the input value of the opening factor
(see AirflowNetwork:MultiZone:Surface,
Window/Door Opening Factor) times the multiplier for venting
modulation (see description of next output variable, “Opening
Factor Multiplier for AirflowNetwork Venting Modulation”). For
example, if the input Window/Door opening factor is 0.5 and
the modulation multiplier is 0.7, then the value of this
output variable will be 0.5*0.7 = 0.35.
This output is the opening elapsed time in the units of
minutes since the windows closed.
AFN
Surface Opening Status at Previous Time Step [][LINK]
This is the window or door opening factor control status at
the previous time step using an AirflowNetwork:OccupantVentilationControl
object, which can have three integer values: 0, 1, and 2. A 0
value indicates no occupant ventilation control. The opening
factor is determined by the Ventilation Control Mode field. A
value of 1 indicates that a window or door is allowed to open.
The value of 1 is determined when the opening elapsed time is
less than the minimum opening time. A value of 2 denotes that
a window or door is forced to close. The value of 2 is
determined when the closing elapsed time is less than the
minimum closing time.
This is the window or door opening factor control status at
the current time step using an AirflowNetwork:OccupantVentilationControl
object, which can have three integer values: 0, 1, and 2. A 0
value indicates no occupant ventilation control. The opening
factor is determined by the Ventilation Control Mode field. A
value of 1 indicates that a window or door is allowed to open.
The value of 1 is determined when the opening elapsed time is
less than the minimum opening time. A value of 2 denotes that
a window or door is forced to close. The value of 2 is
determined when the closing elapsed time is less than the
minimum closing time.
This is the opening probability status at the current time
step using an AirflowNetwork:OccupantVentilationControl
object, which can have three integer values: 0, 1, and 2. A 0
value indicates no opening probability control action. A value
of 1 indicates that a window or door is forced to open when
the opening status is 0. A value of 2 denotes that the status
at the previous time step will be kept.
This is the closing probability status at the current time
step using an AirflowNetwork:OccupantVentilationControl
object, which can have three integer values: 0, 1, and 2. A 0
value indicates no closing probability control action. A value
of 1 indicates that a window or door is forced to close when
the opening status is 0. A value of 2 denotes that the status
at the previous time step will be kept.
This is the RoomAirflowNetwork node total pressure in Pa
with respect to outdoor barometric pressure. The total
pressure is the sum of static pressure, dynamic pressure, and
elevation impact at the node’s relative height.
AFN Zone
Exfiltration Heat Transfer Rate [W][LINK]
AFN
Zone Exfiltration Sensible Heat Transfer Rate [W][LINK]
AFN
Zone Exfiltration Latent Heat Transfer Rate [W][LINK]
These output variables represent the heat emitted to
ambient from exfiltration in Watts. The exfiltration rate is
calculated by solving a mass flow balance on the zone airflow
network including infiltration, ventilation, outdoor air
mixing, zone-to-zone mixing, and all of the zone inlet,
exhaust, and return nodes. The latent parts are determined by
taking the difference between the total and the sensible rate.
Positive values indicate the zone injects heat to the
environment, while negative values indicate the building
extracts heat from the environment.
Group – Airflow Network[LINK]
Overview[LINK]
The Airflow Network model provides the ability to simulate multizone airflows driven by wind and also by forced air distribution systems. The model can also simulate the heat and moisture gains or losses from the air distribution system itself (e.g., ductwork). When modeling air distribution systems, the current version of the Airflow Network model is allowed to simulate multiple forced air systems (i.e., AirLoopHVAC object). Each forced air system allows a constant volume supply air fan (Fan:ConstantVolume or Fan:OnOff), a VAV supply air fan (Fan:VariableVolume), or a fan system model (Fan:SystemMode). The capabilities of the model are to:
Simulate zone pressures due to envelope leakage and forced air distribution during HVAC system fan operation
Simulate node pressures in a forced air distribution system during HVAC system fan operation
Calculate multizone airflows due to forced air, wind, and surface leakage, including adjacent zones and outdoors, during HVAC system fan operation
Simulate distribution system airflows, including supply and return air leaks, during HVAC system fan operation
Simulate air distribution system node temperatures and humidity ratios during HVAC system fan operation
Calculate duct conduction losses during HVAC system fan operation
Calculate vapor diffusion losses of ducts during HVAC system fan operation
Calculate sensible and latent loads on the surrounding zones due to supply and return air leaks in the air distribution system during HVAC system fan operation
Simulate zone pressures due to envelope leakage driven by wind when the HVAC system fan is off or if no air distribution system is specified
Calculate multizone airflows due to wind and surface leakage, including adjacent zones and outdoors when the HVAC system fan is off or if no air distribution system is specified
Allow zone exhaust fans to be included as part of the airflow network
For airflow networks with a forced air distribution system, calculate zone sensible and latent loads for two different supply air fan operation modes as required: cycling fan, cycling compressor (CyclingFanAndCompressor) and continuous fan, cycling compressor (ContinuousFanWithCyclingCompressor)
When multiple forced air systems (AirloopHVAC) are present in the idf, all systems must be used in the Airflow Network model.
Summary of Objects[LINK]
Before describing the Airflow Network input objects in detail, we list all of the objects and then give a short description of what the objects do.
The Airflow Network input objects are:
AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol)
AirflowNetwork:MultiZone:Zone
AirflowNetwork:MultiZone:Surface
AirflowNetwork:MultiZone:Component:SimpleOpening
AirflowNetwork:MultiZone:Component:DetailedOpening
AirflowNetwork:MultiZone:Component:HorizontalOpening
AirflowNetwork:MultiZone:Surface:Crack
AirflowNetwork:MultiZone:ReferenceCrackConditions
AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea
AirflowNetwork:MultiZone:SpecifiedFlowRate
AirflowNetwork:MultiZone:Component:ZoneExhaustFan
AirflowNetwork:MultiZone:ExternalNode
AirflowNetwork:MultiZone:WindPressureCoefficientArray
AirflowNetwork:MultiZone:WindPressureCoefficientValues
AirflowNetwork:IntraZone:Node
AirflowNetwork:IntraZone:Linkage
AirflowNetwork:Distribution:Node
AirflowNetwork:Distribution:Component:Leak
AirflowNetwork:Distribution:Component:LeakageRatio
AirflowNetwork:Distribution:Component:Duct
AirflowNetwork:Distribution:Component:ConstantPressureDrop
AirflowNetwork:Distribution:Component:Fan
AirflowNetwork:Distribution:Component:Coil
AirflowNetwork:Distribution:Component:HeatExchanger
AirflowNetwork:Distribution:Component:TerminalUnit
AirflowNetwork:Distribution:Component:OutdoorAirFlow
AirflowNetwork:Distribution:Component:ReliefAirFlow
AirflowNetwork:Distribution:Linkage
AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol) defines basic run parameters for the air flow calculations and specifies whether wind pressure coefficients are input by the user or, for rectangular buildings, calculated by the program.
The AirflowNetwork:MultiZone:Zone object specifies the ventilation control that applies to all of the openable exterior and interior windows and doors in the corresponding thermal zone. Surface-level ventilation control can be used to override the zone-level ventilation control if required (see AirflowNetwork: MultiZone:Surface object below).
AirflowNetwork:MultiZone:Surface object indicates whether a heat transfer surface (wall, window, etc.) has a crack or opening and references an object in the list below that gives the air flow characteristics of that crack, opening, or zone exhaust fan. The AirflowNetwork:MultiZone:Surface object can also be used to specify individual ventilation control for openable exterior and interior windows and doors.
AirflowNetwork:MultiZone:ReferenceCrackConditions is used to normalize crack information that is based on measurements of crack air flow.
AirflowNetwork:Distribution:Node represents air distribution system nodes for the AirflowNetwork model. A set of an AirLoopHVAC and ZoneHVAC:EquipmentList nodes is a subset of the AirflowNetwork:Distribution:Nodes.
AirflowNetwork:Distribution:Component objects consist of Leak, LeakageRatio, Duct, ConstantPressureDrop, Fan, Coil, TerminalUnit, OutdoorAirFlow and ReliefAirFlow. The components provide a relationship between pressure and airflow. The Leak and Leakage components can be used to simulate supply and/or return leaks in an air distribution system. The Duct and ConstantPressureDrop components can be used to deliver forced air into conditioned spaces. The components Fan, Coil, and TerminalUnit reference normal EnergyPlus objects. OutdoorAirFlow, and ReliefAirFlow specify the outdoor air flow rate set by the Controller:OutdoorAir object in the model. The Airflow Network model gets information from these objects to perform an airflow network simulation.
AirflowNetwork:Distribution:Linkage object represents a connection between two node objects and an AirflowNetwork component. The node objects can be an AirflowNetwork:Distribution:Node, AirflowNetwork:MultiZone:ExternalNode or AirflowNetwork:MultiZone:Zone.
If you input wind pressure coefficients, AirflowNetwork:MultiZone:Surface also has an associated AirflowNetwork:MultiZone:ExternalNode, that, via the AirflowNetwork:MultiZone:Wind-PressureCoefficientArray and AirflowNetwork:MultiZone:WindPressureCoefficientValues objects, gives the wind pressure distribution vs. wind direction for that node and, implicitly, for the cracks and openings in the exterior surfaces associated with that node.
Figure 1 shows the relationships among AirflowNetwork:MultiZone objects and between AirflowNetwork:MultiZone objects and regular EnergyPlus objects. In this figure an arrow from object A to object B means A references B, i.e., one of the inputs in A is the name of object B. For example, one input for AirflowNetwork: MultiZone:Surface is the name of a heat transfer surface, and another is the name of a crack or opening object. The arrow between AirflowNetwork:MultiZone:Surface and AirflowNetwork:MultiZone:ExternalNode is shown dashed to indicate that this reference is not used when wind pressure coefficients are calculated by the program rather than being input by the user.
Figure 1 also shows the relationships among AirflowNetwork:Distribution objects and between AirflowNetwork:Distribution objects and regular EnergyPlus objects. The AirflowNetwork:Distribution:Linkage objects link two nodes from AirflowNetwork:Distribution:Node and/or AirflowNetwork:MultiZone:Zone objects with a component defined in the object AirflowNetwork:Distribution:Component. The solid arrows show a reference from object A to object B. The dashed arrows indicate the components which can be used in a linkage object. The red arrows pointing to the Zone object indicate the components that interact with the zone air. For example, the temperature in a zone where a supply leak terminates is used to calculate duct leakage energy loss. The temperature in a zone where a duct component is located is also used to calculate duct conduction loss.
Much of the information needed for the air flow calculation is automatically extracted from the building description for thermal modeling. This includes things like the volume and neutral height of the zones, and the orientation and location of the building surfaces that contain cracks or openings through which air flows. From all of this information the program creates a “pressure-flow network” that is solved each timestep using iterative solution methods to obtain the unknown pressures and air flows.
Figure 2 shows a plan view of a very simple air flow network that you can construct using the above AirflowNetwork objects. There are three thermal zones, Zone-1, Zone-2 and Zone-3. There are openable exterior windows—Window-1, Window-2 and Window-3—and openable interior doors—Door-12 and Door-23. Two External Nodes are indicated. ExternalNode-1 is associated with the façade that contains Window-1 and Window-2. ExternalNode-2 is associated with the façade containing Window-3.
One possible air flow pattern is shown in this figure. The actual air flow pattern in a particular timestep, and the size of the flows, depends on many factors, such as (1) What is the wind pressure distribution seen by the exterior windows? (2) Are the exterior windows open or closed, and if open, how far are they open? (3) Are the interior doors open or closed? (4) What are the air temperature differences between zones and between zones and the outdoor air (which affect buoyancy flows)?
Figure 2 shows a possible air flow pattern in which all of the windows and doors are open. Associated with the external nodes are wind pressure coefficient distributions as a function of wind direction that are input using two AirflowNetwork:MultiZone:Wind Pressure Coefficient objects. The nature of the air flows through the windows and doors is specified using AirflowNetwork:MultiZone:Component:DetailedOpening and AirflowNetwork:MultiZone:Component:SimpleOpening objects. The Airflow Network model calculates the flows each system timestep depending on various factors, including wind direction and speed, size and vertical position of openings, outdoor air temperature, and zone air temperatures.
Airflow Network Example Files (included in the installation)[LINK]
AirflowNetwork3zVent.idf
AirflowNetwork3zVentAutoWPC.idf
AirflowNetworkOccupantVentilationControl.idf
AirflowNetwork_Attic_Duct.idf
AirflowNetwork_Simple_House.idf
AirflowNetwork_Simple_SmallOffice.idf
AirflowNetwork_MultiAirLoops.idf
AirflowNetwork_MultiZone_House.idf
AirflowNetwork_MultiZone_House_OvercoolDehumid.idf
AirflowNetwork_MultiZone_House_TwoSpeed.idf
AirflowNetwork_MultiZone_LocalNode.idf
AirflowNetwork_MultiZone_SmallOffice.idf
AirflowNetwork_MultiZone_SmallOffice_CoilHXAssistedDX.idf
AirflowNetwork_MultiZone_SmallOffice_GenericContam.idf
AirflowNetwork_MultiZone_SmallOffice_HeatRecoveryHXSL.idf
AirflowNetwork_MultiZone_SmallOffice_VAV.idf
AirflowNetwork_MultiZone_HorizontalOpening.idf
AirflowNetwor_PressureControl.idf
CrossVent_1Zone_AirflowNetwork.idf
CrossVent_1Zone_AirflowNetwork_with2CrossflowJets.idf
DisplacementVent_Nat_AirflowNetwork.idf
DisplacementVent_Nat_AirflowNetwork_AdaptiveComfort.idf
EMSAirflowNetworkOpeningControlByHumidity.idf
HybridVentilationControl.idf
RoomAirflowNetwork.idf
What the Airflow Network Model Can and Cannot Do[LINK]
Here is a list of some of the things that the Airflow Network calculation can and cannot model.
Can Do[LINK]
Air flow through cracks in exterior or interzone surfaces.
Air flow through cracks around windows and doors when closed.
Natural ventilation (i.e., air flow through open or partially open exterior windows and doors).
Zone level control of natural ventilation (all windows/doors in a zone that are defined with a component opening object have identical controls).
Individual surface control of natural ventilation for a subsurface (window, door, or glassdoor).
Modulation of natural ventilation to prevent large zone air temperature swings.
Interzone air flow (i.e., air flow through open interzone windows and doors, and through cracks in interzone surfaces).
Dependence of air flow on buoyancy effects and wind pressure.
Dependence of wind pressure on wind speed, wind direction and surface orientation.
Supply and return air leaks in an air distribution system.
Account for the effect of supply-air and/or return-air leakage on zone pressure when a forced air distribution system is present and is operating.
When duct leakage is modeled and the HVAC system is on, interzone airflow or infiltration/exfiltration can occur due to changes in zone pressure.
Bi-directional flow through large openings. See discussion below under AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:HorizontalOpening, and AirflowNetwork:MultiZone:Component:SimpleOpening.
Calculate air flows and pressures in ducts or other components of a forced air distribution system.
Calculate zone loads when the supply air fan cycles on and off during a system timestep using the CyclingFanAndCompressor fan operation mode (Fan:OnOff).
Determine the impact of zone exhaust fans on air flows, pressures, air temperatures/humidity levels and energy consumption.
Cannot Do or Restricted[LINK]
The model is restricted to using a constant volume or variable volume fan (Fan:ConstantVolume, Fan:OnOff, and Fan:VariableVolume).
Air circulation and/or air temperature stratification within a thermal zone. For example, you should not try to divide a high space, such as an atrium, into subzones separated by artificial horizontal surfaces that have cracks or openings with the expectation that AirflowNetwork will give you a realistic temperature in each subzone and/or a realistic air flow between subzones.
The model is restricted to eleven types of coils that can be in the air distribution system (Coil:Cooling:DX:SingleSpeed, Coil:Heating:Fuel, Coil:Heating:Electric, Coil:Heating:DX:SingleSpeed, Coil:Cooling:Water, Coil:Heating:Water, Coil:Cooling:Water:DetailedGeometry, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:MultiSpeed, Coil:Heating:DX:MultiSpeed, and Coil:Heating:Desuperheater).
The model is restricted to two types of air distribution equipment terminal units (AirTerminal:SingleDuct:ConstantVolume:Reheat and AirTerminal:SingleDuct:VAV:Reheat).
Supply and return leaks are not allowed in an AirLoopHVAC. They can only be modeled in the Zone Equipment portion of the air loop (i.e., return leaks may be modeled between the zone return node and the zone mixer inlet or the zone mixer outlet and the zone equipment loop outlet; and supply leaks may be modeled between the zone equipment loop inlet and the AirLoopHVAC:ZoneSplitter inlet node or the AirLoopHVAC:ZoneSplitter outlet node and the zone supply node).
An air distribution system must be located inside the building (i.e., the ducts must pass through zones within the building).
Zone exhaust fans must be defined in ZoneHVAC:EquipmentConnections objects.
The input specifications consist of five main sections: AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol) object, AirflowNetwork multizone data objects, AirflowNetwork distribution node objects, AirflowNetwork distribution component objects, and AirflowNetwork distribution linkage objects. Each of these object types is described in detail below.
AirflowNetwork:SimulationControl[LINK]
The basic run parameters for this model are defined in this unique object which has the following input specifications:
Inputs[LINK]
Field: Name[LINK]
This is a unique character string associated with this instance of the AirflowNetwork:SimulationControl object. At this time, only one AirflowNetwork:SimulationControl object can be specified in an input data file (idf).
Field: AirflowNetwork Control[LINK]
The following selections are available to control the Airflow Network simulation:
MultiZoneWithDistribution: MultiZone air flow calculations are performed during all simulation timesteps, including the impacts of the air distribution system when a HVAC system fan is operating. Any ZoneInfiltration:*, ZoneVentilation:*, ZoneMixing and ZoneCrossMixing objects specified in the input data file are not simulated.
MultiZoneWithoutDistribution: MultiZone air flow calculations are performed during all simulation timesteps, but the air distribution system portion of the network is not modeled even if it is specified in the input data file. Any ZoneInfiltration:*, ZoneVentilation:*, ZoneMixing and ZoneCrossMixing objects specified in the input data file are not simulated.
MultiZoneWithDistributionOnlyDuringFanOperation: MultiZone air flow calculations, including the impacts of the air distribution system, are only performed when the HVAC system fan is operating. Any ZoneInfiltration:*, ZoneVentilation:*, ZoneMixing and ZoneCrossMixing objects specified in the input data file are used when the HVAC system fan is OFF (if none are specified, then no air flow calculations are performed when the fan is OFF).
NoMultiZoneOrDistribution: No multizone air flow calculations (with or without the air distribution system portion of the network) are performed during the simulation. Any ZoneInfiltration:*, ZoneVentilation:*, ZoneMixing and ZoneCrossMixing objects specified in the input data file are simulated (if none are specified, then no air flow calculations are performed). Note: Having an input data file with no AirflowNetwork:SimulationControl objects gives the same impact – no multizone air flow calculations. However, this choice is provided as a convenience to the user to easily disable the multizone air flow calculations for an input data file that already contains AirflowNetwork objects.
Note: A ZoneInfiltration:* object indicates any one of ZoneInfiltration:DesignFlowRate, ZoneInfiltration:EffectiveLeakageArea,and ZoneInfiltration:FlowCoefficient objects.A object ofZoneVentilation:* indicates any one of ZoneVentilation:DesignFlowRate and ZoneVentilation:WindandStackOpenArea objects.
Field: Wind Pressure Coefficient Type[LINK]
Determines whether the wind pressure coefficients are input by the user or calculated. The choices are Input or SurfaceAverageCalculation, with the default being SurfaceAverageCalculation.
If INPUT, you must enter an AirflowNetwork:MultiZone:WindPressureCoefficientArray object, one or more AirflowNetwork:MultiZone:ExternalNode objects, and one or more AirflowNetwork:MultiZone:WindPressureCoefficientValues objects.
The second choice, SurfaceAverageCalculation, should only be used for rectangular buildings. In this case surface-average wind pressure coefficients vs. wind direction are calculated by the program for the four vertical façades and the roof based on user entries for “Building Type,” “Azimuth Angle of Long Axis of Building,” and “Ratio of Building Width Along Short Axis to Width Along Long Axis” (see description of these fields below). With this choice you do not have to enter any of the following objects: AirflowNetwork:MultiZone: Wind Pressure Coefficient Array, AirflowNetwork:MultiZone:ExternalNode and AirflowNetwork:MultiZone:WindPressureCoefficientValues.
Field: Height Selection for Local Wind Pressure Calculation[LINK]
Determines whether the local wind pressure is calculated based on either given external node heights or surface opening heights. The choices are ExternalNode or OpeningHeight, with the default being OpeningHeight. The local outdoor wind speed calculation procedure is given in the section of “Local Wind Speed Calculation” in the Engineering Reference. The calculation procedure requires the height input.
If ExternalNode, the heights given in the AirflowNetwork:MultiZone:ExternalNode objects are used to calculate local wind pressures based on the given height local wind speed. Used only if Wind Pressure Coefficient Type = INPUT (see description of previous field).
If OpeningHeight, the number of the AirflowNetwork:MultiZone:ExternalNode objects has to be equal to the number of external surfaces defined in the AirflowNetwork:MultiZone:Surface objects. The centroids in the z direction of the AirflowNetwork:MultiZone:Surface objects are the heights used in the local wind pressure calculation with the given height wind speed. The input is required if Wind Pressure Coefficient Type = INPUT (see description of previous field).
If Wind Pressure Coefficient Type = SurfaceAverageCalculation, a value in this field is not required and a blank may be entered. The default choice is used internally to generate the AirflowNetwork:MultiZone:ExternalNode objects
Field: Building Type[LINK]
Used only if Wind Pressure Coefficient Type = SurfaceAverageCalculation. The choices for Building Type are LowRise and HighRise, with the default being LowRise.
LowRise corresponds to a rectangular building whose height is less than three times the width of the footprint (w\(_{short}\) in Figure 3) and is less than three times the length of the footprint (w\(_{long}\) in the same figure).
HighRise corresponds to a rectangular building whose height is more than three times the width of the footprint (w\(_{short}\) in Figure 3) or is more than three times the length of the footprint (w\(_{long}\) in the same figure).
Field: Maximum Number of Iterations[LINK]
The maximum number of iterations allowed in finding an AirflowNetwork solution. If the number of iterations at each simulation timestep is above the maximum number of iterations defined by this field, the program could not find the solution and a Severe error is issued and the program is aborted. The default value is 500.
Field: Initialization Type[LINK]
Designates which method is used for AirflowNetwork initialization. The choices for Initialization Type are LinearInitializationMethod and ZeroNodePressures, with the default being ZeroNodePressures.
Field: Relative Airflow Convergence Tolerance[LINK]
The solution is assumed to have converged when \({{\left| {\,\sum\limits_{} {{{\mathop m\limits^ \bullet }_{_i}}} } \right|} \mathord{\left/ {\vphantom {{\left| {\,\sum\limits_{} {{{\mathop m\limits^ \bullet }_{_i}}} } \right|} {\sum\limits_{} {\left| {{{\mathop m\limits^ \bullet }_{_i}}} \right|} }}} \right. } {\sum\limits_{} {\left| {{{\mathop m\limits^ \bullet }_{_i}}} \right|} }}\) is less than the value specified for this input field. This convergence criteria is equivalent to the ratio of the absolute value of the sum of all network airflows (\(\left| {\sum {{{\mathop m\limits^ \bullet }_{_i}}} } \right|\) ) to the sum of network airflow magnitudes (\(\sum\limits_{}^{} {\left| {{{\mathop m\limits^ \bullet }_{_i}}} \right|}\) ). The default value is 1.0x10\(^{-4}\).
Field: Absolute Airflow Convergence Tolerance[LINK]
The solution is assumed to have converged when the summation of the absolute value of all network airflows (\(\left| {\sum {{{\mathop m\limits^ \bullet }_{_i}}} } \right|\) ) is less than the value specified for this input field. The default value is 1.0x10\(^{-6}\).
Field: Convergence Acceleration Limit[LINK]
If the ratio of successive pressure corrections is less than this limit, use Steffensen acceleration algorithm (Ref. AirflowNetwork Model in the EnergyPlus Engineering Reference). The range for this field is -1 to 1, with the default value being -0.5.
Field: Azimuth Angle of Long Axis of Building[LINK]
Gives the orientation of a rectangular building for calculating wind pressure coefficients. This is the smaller of the angles, measured clockwise, between North and the long axis of the building (see Figure 3). Used only if Wind Pressure Coefficient Type = SurfaceAverageCalculation. The range for this input is 0 to 180, with the default value being 0.
Field: Ratio of Building Width Along Short Axis to Width Along Long Axis[LINK]
This is the aspect ratio of a rectangular footprint. It is given by the width of the footprint along its short axis divided by the width along the long axis (see Figure 3). If the footprint is square, the value of this field is 1.0. Used only if Wind Pressure Coefficient Type = SurfaceAverageCalculation. The range for this input is > 0 to 1, with the default value being 1.
Field: Height Dependence of External Node Temperature[LINK]
This is an optional field. Input is Yes or No. The default is No. Yes is that external node temperature is dependent on node height. No means that external node temperature is calculated with zero height.
Field: Allow Unsupported Zone Equipment[LINK]
This is an optional field. Input is Yes or No. The default is No. Set this input to Yes to have zone equipment that are currently unsupported in the AirflowNetwork model allowed in the simulation. Setting this field to Yes, allows the following equipment to be modeled along an AirflowNetwork model: ZoneHVAC:Dehumidifier, ZoneHVAC:EnergyRecoveryVentilator, WaterHeater:HeatPump:*. The AirflowNetwork model will exclude mass balance in these equipment objects and assume the mass flows are self-balanced in the equipment objects.
An IDF example is shown below:
If the AirflowNetwork:SimulationControl object is not provided in an input file, the default input object will be created by the program internally, as long as following conditions are satisfied:
The number of AirflowNetwork:MultiZone:Zone objects >= 1
The number of AirflowNetwork:MultiZone:Surface objects >= 2
The default input object is shown below:
AirflowNetwork:MultiZone data objects are used to calculate multizone airflows. This section describes the input requirements for the following objects:
AirflowNetwork:MultiZone data objects are used to calculate multizone airflows. This section describes the input requirements for the following objects:
AirflowNetwork:MultiZone:Zone
AirflowNetwork:MultiZone:Surface
AirflowNetwork:MultiZone:Surface:Crack
AirflowNetwork:MultiZone:ReferenceCrackConditions
AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea
AirflowNetwork:MultiZone:Component:DetailedOpening
AirflowNetwork:MultiZone:Component:SimpleOpening
AirflowNetwork:MultiZone:Component:HorizontalOpening
AirflowNetwork:MultiZone:Component:ZoneExhaustFan
AirflowNetwork:MultiZone:ExternalNode
AirflowNetwork:MultiZone:WindPressureCoefficientArray
AirflowNetwork:MultiZone:WindPressureCoefficientValues
A detailed description for each of these objects is provided below.
AirflowNetwork:MultiZone:Zone[LINK]
This object allows control of natural ventilation through exterior and interior openings in a zone, where “opening” is defined as an openable window or door. (Note that only window, door or glass door subsurfaces in a zone that are specified using AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:HorizontalOpening or AirflowNetwork:MultiZone:Component:SimpleOpening and have an associated AirflowNetwork:MultiZone:Surface object are considered to be openings). The control will be applied in the same way to all of the openings in the zone.
This object is required to perform Airflow Network calculations. Note that ventilation control for all openings is provided at the zone level as default and individual ventilation control of a surface opening can be used to override the zone-level control (see the AirflowNetwork:MultiZone:Surface object description below).
Field: Zone Name[LINK]
The name of the EnergyPlus thermal zone corresponding to the AirflowNetwork zone.
Field: Ventilation Control Mode[LINK]
Specifies the type of zone-level natural ventilation control.
Let T\(_{out}\) equal the outdoor air temperature, T\(_{zone}\) equal the previous timestep’s zone air temperature, T\(_{set}\) equal the Vent Temperature Schedule value, H\(_{zone}\) equal the specific enthalpy of zone air from the previous timestep, and H\(_{out}\) equal the specific enthalpy of outdoor air. Then the four allowed choices for Ventilation Control Mode are:
NoVent: All of the zone’s openable windows and doors are closed at all times independent of indoor or outdoor conditions. The Venting Availability Schedule is ignored in this case. This is the default value for this field.
Temperature: All of the zone’s openable windows and doors are opened if T\(_{zone}\) > T\(_{out}\) and T\(_{zone}\) > T\(_{set}\) and Venting Availability Schedule (see below) allows venting.
Enthalpy: All of the zone’s openable windows and doors are opened if H\(_{zone}\) > H\(_{out}\) and T\(_{zone}\) > T\(_{set}\) and Venting Availability Schedule allows venting.
Constant: Whenever this object’s Venting Availability Schedule allows venting, all of the zone’s openable windows and doors are open, independent of indoor or outdoor conditions. Note that “Constant” here means that the size of each opening is fixed while venting; the air flow through each opening can, of course, vary from timestep to timestep.
ASHRAE55Adaptive: All of the zone’s operable windows and doors are opened if the operative temperature is greater than the comfort temperature (central line) calculated from the ASHRAE Standard 55-2010 adaptive comfort model and Venting Availability Schedule allows venting.
CEN15251Adaptive: All of the zone’s operable windows and doors are opened if the operative temperature is greater than the comfort temperature (central line) calculated from the CEN15251 adaptive comfort model and Venting Availability Schedule allows venting.
Field: Ventilation Control Zone Temperature Setpoint Schedule Name[LINK]
The name of a schedule of zone air temperature set points that controls the opening of windows and doors in the thermal zone to provide natural ventilation. This setpoint is the temperature above which all the openable windows and doors in the zone will be opened if the conditions described in the previous field Ventilation Control Mode are met.
The Ventilation Control Zone Temperature Setpoint Schedule Name applies only to windows and doors in the zone that are specified using AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:HorizontalOpening or AirflowNetwork:MultiZone:Component:SimpleOpening and have an associated AirflowNetwork:MultiZone:Surface object.
(The discussion under the field Window/Door Opening Factor in the AirflowNetwork:MultiZone:Surface object describes how the actual opening area of a window or door in a particular timestep is determined.)
Modulation of Openings
The following five fields can be used to modulate the window/door openings when Ventilation Control Mode = Temperature or Enthalpy. These fields determine a factor between 0 and 1 that multiplies the opening factor of each window and door in the zone according to the control action shown in Figure 5 for Ventilation Control Mode = Temperature and in Figure 6 for Ventilation Control Mode = Enthalpy. Modulation of the openings can reduce the large temperature swings that can occur if the windows/doors are open too far when they are venting, especially when there is a large inside-outside temperature difference.
The modulation takes the following form when Ventilation Control Mode = Temperature:
if T\(_{zone}\) - T\(_{out}\) < = [Lower Value on Inside/Outside Temperature Difference for Modulating the Venting Open Factor] then Multiplication factor = 1.0
if [Lower Value on Inside/Outside Temperature Difference for Modulating the Venting Open Factor] < T\(_{zone}\) - T\(_{out}\) < [Upper Value on Inside/Outside Temperature Difference for Modulating the Venting Open Factor] then Multiplication factor varies linearly from 1.0 to [Limit Value on Multiplier for Modulating Venting Open Factor]
if T\(_{zone}\) - T\(_{out}\) > = [Upper Value on Inside/Outside Temperature Difference for Modulating the Venting Open Factor] then Multiplication factor = [Limit Value on Multiplier for Modulating Venting Open Factor]
One way of “tuning” the following modulation control parameters is to perform a sensitivity analysis for winter and/or summer design days to determine what combination of values causes the biggest reduction in zone air temperature fluctuations due to venting.
Note that the default values for the following fields are such that, if none of the fields are specified, the default values are assigned.
Field: Minimum Venting Open Factor[LINK]
See Figure 5 or Figure 6. This field applies only if Ventilation Control Mode = Temperature or Enthalpy. This value may be from zero to 1.0, with the default being 0.0.
Field: Indoor and Outdoor Temperature Difference Lower Limit For Maximum Venting Open Factor[LINK]
See Figure 5. This field applies only if Ventilation Control Mode = Temperature. This value may be from zero to less than 100 °C, with the default being 0 °C. The value for this field must be less than the value specified for the following field.
Field: Indoor and Outdoor Temperature Difference Upper Limit for Minimun Venting Open Factor[LINK]
See Figure 5. This field applies only if Ventilation Control Mode = Temperature. This value must be greater than 0 °C, with the default being 100 °C. The value for this field must be greater than the value specified for the previous field..
Field: Indoor and Outdoor Enthalpy Difference Lower Limit For Maximum Venting Open Factor[LINK]
See Figure 6. This field applies only if Ventilation Control Mode = Enthalpy. This value may be from zero to less than 300,000 J/kg, with the default being 0 J/kg. The value for this field must be less than the value specified for the following field.
Field: Indoor and Outdoor Enthalpy Difference Upper Limit for Minimun Venting Open Factor[LINK]
See Figure 6. This field applies only if Ventilation Control Mode = Enthalpy. This value must be greater than zero, with the default being 300,000 J/kg. The value for this field must be greater than the value specified for the previous field.
Field: Venting Availability Schedule Name[LINK]
The name of a schedule that specifies when venting is available. A zero or negative schedule value means venting is not allowed. A value greater than zero means venting can occur if other venting control conditions (specified by Ventilation Control Mode and Vent Temperature Schedule Name) are satisfied. This schedule name should not be confused with Vent Temperature Schedule Name.
If a Venting Availability Schedule Name is not specified, it is assumed that venting is always available.
Using Venting Availability Schedule allows you to turn off venting at certain times of the day (at night, for example), of the week (on weekends, for example), or of the year (during the winter, for example).
If used with Ventilation Control Mode = Constant, the ventilation rate is constant only when this schedule allows venting; otherwise the ventilation rate is set to zero.
If Ventilation Control Mode = NoVent, this schedule has no effect.
Field: Single Sided Wind Pressure Coefficient Algorithm[LINK]
Specifies the type of single sided wind pressure coefficient algorithm to be used for the zone. This field is optional and is only used if Wind Pressure Coefficient Type is set to SurfaceAverageCalculation. The default is Standard and the two valid choices are:
Standard: A single wind pressure coefficient is applied to all openings in the zone, as calculated using SurfaceAverageCalculation.
Advanced: EnergyPlus calculates modified wind pressure coefficients for the two openings in the zone. This model is only valid for zones with two openings, both of which are on a single façade (i.e. are coplanar). For zones with more than two openings, consider combining the openings into two. The modified wind pressure coefficients account for wind direction and turbulence effects on single sided ventilation rates. See the Engineering Reference for a detailed description of the Advanced algorithm. When the Advanced algorithm is selected, the difference between the two modified wind pressure coefficients are output to the .eio file.
Field: Façade Width[LINK]
This is the whole building width along the direction of the facade of this zone, or \(W_F\) in Figure 4. This field is used in the Single Sided Wind Pressure Coefficient Algorithm. This field is optional and is only used if the Single Sided Wind Pressure Coefficient Algorithm is set to Advanced. The value must be greater than 0.0 m, with the default being 10 m.
Field: Occupant Ventilation Control Name[LINK]
The name of an AirlowNetwork:OccupantVentilationControl object. The object is used to perform advanced window opening control based on occupant conditions. When an object name is given, advanced window opening control is performed and, the ventilation control defined in the Ventilation Control Mode field will be overridden.
Note: The Occupant Ventilation Control object can be assigned to a zone (AirflowNetwork:MultiZone:Zone) or a surface (AirflowNetwork:MultiZone:Surface). When the object is assigned to a zone, the Occupant Ventilation Control is assigned to the surfaces belonging to the zone automatically. The surface objects must have an associated AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:HorizontalOpening, or AirflowNetwork:MultiZone:Component:SimpleOpening component specified in the field of Leakage Component Name. All output variables will be shown under surface names only, and not under zone names.
Note: In order to establish an airflow network, each AirflowNetwork:MultiZone:Zone object must have at least two surfaces defined with AirflowNetwork:MultiZone:Surface objects, so that air can flow from one zone into other zones (or to outdoors) through the network (air mass flow conserved). In addition, for all AirflowNetwork:MultiZone:Surface objects facing the same Zone (ref. BuildingSurface:Detailed), at least two different environments must be defined for the other side of these surfaces (e.g., an external node and an adjacent zone, two adjacent zones, or two external nodes).
An IDF example is shown below:
AirflowNetwork:MultiZone:Surface[LINK]
The AirflowNetwork:MultiZone:Surface object specifies the properties of a surface “linkage” through which air flows. This linkage is always associated with a building surface (wall, roof, floor, or a ceiling) or subsurface (door, glass door, or window) with both faces exposed to air. The linkage specifies two connected nodes: two zone nodes defined in AirflowNetwork:MultiZone:Zone objects based on inside and outside face environment for an interior surface, or a zone node defined in an AirflowNetwork:MultiZone:Zone object based on inside face environment and an external node defined in an AirflowNetwork:MultiZone:ExternalNode object for an exterior surface. The associated leakage component for this surface can be a crack (or surface effective leakage area) in an exterior or interior heat transfer surface or subsurface, or an exterior or interior window, door or glass door (heat transfer subsurface) that can be opened to allow air flow. The allowed surface air leakage components are:
AirflowNetwork:MultiZone:Surface:Crack
AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea
AirflowNetwork:MultiZone:SpecifiedFlowRate
AirflowNetwork:MultiZone:Component:DetailedOpening
AirflowNetwork:MultiZone:Component:HorizontalOpening
AirflowNetwork:MultiZone:Component:SimpleOpening
AirflowNetwork:MultiZone:Component:ZoneExhaustFan
The three “opening” components are used to modulate openness based on required conditions.
The AirflowNetwork:MultiZone:Surface object allows a heat transfer surface or subsurface to have one crack (or one surface effective leakage area object), or a subsurface (i.e., window, door or glass door) to have one opening (detailed, simple, or horizontal).
An interior heat transfer surface (BuildingSurface:Detailed) whose surface name is used as the input for the Outside Boundary Condition Object field is adiabatic and is not allowed as an AirflowNetwork:MultiZone:Surface. A heat transfer surface defined in the BuildingSurface:Detailed:ExteriorNaturalVentedCavity is also not allowed.
When a non-rectangular subsurface is used, the model will automatically convert it into a rectangular subsurface using equivalent width and height based on an entered choice from the Equivalent Rectangle Method field or a default choice.
When an air boundary surface or subsurface is used (Construction:AirBoundary), all types of leakage component are allowed except AirflowNetwork:MultiZone:Component:ZoneExhaustFan. The only allowed venting control type for an air boundary surface is Constant, and the venting schedule is ignored (which means the opening is always fully open at the specified Window/Door Opening Factor, or Crack Factor). EnergyManagementSystem:Actuator “AirFlow Network Window/Door Opening” is available for special applications where control of the air boundary opening is required.
Field: Surface Name[LINK]
This is the name of the corresponding surface (wall, roof, ceiling, floor, window, door or glass door).
Information on this surface is used by the program as follows:
For a linkage associated with an exterior heat transfer surface: air flow through this linkage is between the outside environment and the thermal zone to which the surface belongs.
For a linkage associated with an interior (i.e., interzone) heat transfer surface: air flow through this linkage is between the thermal zones separated by the surface (i.e., the thermal zone associated with the inside face environment and the thermal zone associated with the outside face environment).
This heat transfer surface determines the height of the linkage, which is used in calculating buoyancy-related flow through the linkage.
The surface may be an air boundary surface or subsurface (Construction:AirBoundary).
Note: It is possible to define an interzone surface twice in EnergyPlus, once in each of the zones that the surface separates. Previously this was a requirement of EnergyPlus (prior to version 2.0), but now it is optional and the user also has the option of only defining the surface once (EnergyPlus defines the second surface automatically within the program). For each interzone surface, use only one (of possible two) interzone surface names in the AirflowNetwork:MultiZone:Surface object for “Surface Name.” Do not enter two AirflowNetwork:MultiZone:Surface objects corresponding to the two possible interzone names. This would cause the air flow through the surface to be counted twice.
Field: Leakage Component Name[LINK]
The name of the AirflowNetwork:MultiZone:Surface:Crack, AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea, AirflowNetwork:MultiZone:Component:SimpleOpening, AirflowNetwork:MultiZone:Component:HorizontalOpening, AirflowNetwork:MultiZone:Component:DetailedOpening or AirflowNetwork:MultiZone:Component:ZoneExhaustFan object associated with this air flow linkage.
If the name of an opening component (i.e. AirflowNetwork:MultiZone:Component:DetailedOpening. AirflowNetwork:MultiZone:Component:HorizontalOpening, or AirflowNetwork:MultiZone:Component:SimpleOpening is given here, then the Surface Name in the previous field must be that of a window, door or glass door heat transfer subsurface or a building surface which is an air boundary. Otherwise an error message will be reported.
If the name of an AirflowNetwork:MultiZone:Surface:Crack object or AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea object is given here, the program will position the crack at the average height of the associated heat transfer surface or subsurface. The user can define multiple heat transfer surfaces (e.g., split a wall into several surfaces) to be more precise in establishing the crack location. Similarly, the user can define multiple heat transfer surfaces if a wall, for example, has multiple cracks or openings that need to be defined individually.
If the name of an AirflowNetwork:MultiZone:Component:ZoneExhaustFan is given here, then the Surface Name in the previous field must be that of an exterior heat transfer surface. The zone name defined in the Zone Name field for this heat transfer surface must be the same zone name defined in the ZoneHVAC:EquipmentConnections object (which references a ZoneHVAC:EquipmentList containing the name of the corresponding zone exhaust fan).Otherwise an error message will be reported. When this zone exhaust fan is operating for a simulation timestep, all surface-level controls described below are ignored for that timestep.
Field: External Node Name[LINK]
The name of the associated AirflowNetwork:MultiZone:ExternalNode object, which determines the wind pressure coefficients for the heat transfer surface. Used only if Surface Name is for an exterior surface.
If Wind Pressure Coefficient Type = SurfaceAverageCalculation in the AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol) object, this field is not used and a blank may be entered. If the surface is an interior (i.e., interzone) surface, leave this field blank.
When there is an input object of either ZoneProperty:LocalEnvironment or SurfaceProperty:LocalEnvironment, LocalEnvironment is enable, so that entered names of OutdoorAir:Node can be used as inputs for this field. More descrption of use can be found in OutdoorAir:Node.
Field: Window/Door Opening Factor, or Crack Factor[LINK]
If this linkage is associated with an AirflowNetwork:MultiZone:Component:DetailedOpening or AirflowNetwork:MultiZone:Component:SimpleOpening object (which means it is an openable window or door), then this field is called “Window/Door Opening Factor” and represents the value of the Opening Factor that is in effect when the Vent Temperature Schedule (defined in the AirflowNetwork:MultiZone:Zone object) indicates that this window or door is open.
The AirflowNetwork model uses a combination of factors to determine the actual opening area for a window or door when it is venting. For example, consider a window that is 1.5m high and 2.0m wide (excluding frame). Assume that the AirflowNetwork:MultiZone:Component:DetailedOpening for this window has Type of Large Vertical Opening = 1 (non-pivoting window), Height Factor = 0.5 and Width Factor = 0.8. Then when the window is fully open, the opening area = height of opening (0.5x1.5) times width of opening (0.8x2.0) = 0.75x1.6 = 1.2 m\(^{2}\). If the Window/Door Opening Factor is 0.75, then the opening area = 0.75x1.2 = 0.9 m\(^{2}\).
If, in addition, the window is in a thermal zone for which opening modulation has been specified (ref: AirflowNetwork:MultiZone:Zone) and the multiplication factor due to modulation is 0.3 in a particular timestep, then the actual opening factor that timestep = 0.3x0.75 = 0.225 and the actual opening area that timestep = 0.3x0.9 = 0.27 m\(^{2}\).
If this linkage is associated with an AirflowNetwork:MultiZone:Surface:Crack object, the following crack air flow equation is used.
\[Q = \left( Crack\;Factor \right) * C_T * C_Q \left( \Delta P \right)^{n}\]
Where
\(Q\) is the air mass flow (kg/s)
\(C_Q\) is the air mass flow coefficient (kg/s @ 1 Pa)
\(C_T\) is the reference condition temperature correction factor (dimensionless). See AirflowNetwork:MultiZone:Surface:Crack object.
\(\Delta P\) is the pressure difference across crack (Pa)
\(n\) is the air flow exponent (dimensionless)
The following fields control venting. They are used only when Name of Associated Heat Transfer Surface is that of an openable exterior or interior window, door or glass door. They only apply to openings, and do not apply to surface cracks, effective leakage area or zone exhaust fans. If none of these fields is specified, or if Ventilation Control Mode = ZoneLevel, venting is controlled by the AirflowNetwork:MultiZone:Zone object for the thermal zone containing the window or door (ref: AirflowNetwork:MultiZone:Zone Data).
Field: Ventilation Control Mode[LINK]
Specifies the type of surface-level natural ventilation control.
Let \(T_{out}\) equals the outdoor air temperature, \(T_{zone}\) equals the previous timestep’s zone air temperature, \(T_{set}\) equals the Vent Temperature Schedule value, \(H_{zone}\) equals the specific enthalpy of zone air from the previous timestep, and \(H_{out}\) equals the specific enthalpy of outdoor air. Then the four allowed choices for Ventilation Control Mode are:
NoVent: The openable window or door associated with this surface is closed at all times independent of indoor or outdoor conditions. The Venting Availability Schedule is ignored in this case.
Temperature: The openable window or door associated with this surface is opened if \(T_{zone} > T_{out}\) and \(T_{zone} > T_{set}\) and Venting Availability Schedule (see below) allows venting.
Enthalpy: The openable window or door associated with this surface is opened if \(H_{zone} > H_{out}\) and \(T_{zone} > T_{set}\) and Venting Availability Schedule allows venting.
Constant: Whenever this object’s Venting Availability Schedule allows venting, the openable window or door associated with this surface is open, independent of indoor or outdoor conditions. Note that “Constant” here means that the size of this opening is fixed while venting; the air flow through this opening can, of course, vary from timestep to timestep. If the surface is an air boundary (Construction:AirBoundary) then Constant is the only valid option (other options will throw a warning and be reset to Constant).
ASHRAE55Adaptive: The openable window or door associated with this surface is opened if the operative temperature is greater than the comfort temperature (central line) calculated from the ASHRAE Standard 55-2010 adaptive comfort model and Venting Availability Schedule allows venting.
CEN15251Adaptive: The openable window or door associated with this surface is opened if the operative temperature is greater than the comfort temperature (central line) calculated from the CEN15251 adaptive comfort model and Venting Availability Schedule allows venting.
ZoneLevel: Venting of the window or door is not controlled individually, but is controlled instead at the zone level. This means that the venting is determined by the AirflowNetwork:MultiZone:Zone object for the thermal zone containing the window or door (ref: AirflowNetwork:MultiZone:Zone object). This is the default value for this field.
AdjacentTemperature: This choice is used for an interior surface only. The openable interior window or door associated with this surface is opened if \(T_{zone} > T_{adjacent\ zone}\) and \(T_{zone} > T_{set}\) and Venting Availability Schedule (see below) allows venting, where \(T_{adjacent\ zone}\) is the adjacent zone temperature.
AdjacentEnthalpy: This choice is also used for an interior surface only. The interior openable window or door associated with this surface is opened if \(H_{zone} > H_{adjacent\ zone}\) and \(T_{zone} > T_{set}\) and Venting Availability Schedule allows venting, where \(H_{adjacent\ zone}\) is the adjacent zone specific enthalpy.
Field: Ventilation Control Zone Temperature Setpoint Schedule Name[LINK]
The name of a schedule of zone air temperature set points that controls the opening of a window or door associated with this surface to provide natural ventilation. This setpoint is the temperature above which this openable window or door will be opened if the conditions described in the previous field Ventilation Control Mode are met.
The Ventilation Control Zone Temperature Setpoint Schedule applies only to a window or door attached to this surface that is specified using AirflowNetwork:MultiZone:Component:DetailedOpening or AirflowNetwork:MultiZone:Component:SimpleOpening.
(The discussion under the field Window/Door Opening Factor in this object describes how the actual opening area of a window or door in a particular timestep is determined.)
Modulation of Openings
The following five fields can be used to modulate this window/door opening when Ventilation Control Mode = Temperature or Enthalpy. These fields determine a factor between 0 and 1 that multiplies the opening factor of this window or door according to the control action shown in Figure 5 for Ventilation Control Mode = Temperature and in Figure 6 for Ventilation Control Mode = Enthalpy. Modulation of this opening can reduce the large temperature swings that can occur if the window/door is open too far when it is venting, especially when there is a large inside-outside temperature difference.
The modulation takes the following form when Ventilation Control Mode = Temperature:
if T\(_{zone}\) - T\(_{out}\) < = [Lower Value on Inside/Outside Temperature Difference for Modulating the Venting Open Factor] then Multiplication factor = 1.0
if [Lower Value on Inside/Outside Temperature Difference for Modulating the Venting Open Factor] < T\(_{zone}\) - T\(_{out}\) < [Upper Value on Inside/Outside Temperature Difference for Modulating the Venting Open Factor] then Multiplication factor varies linearly from 1.0 to [Limit Value on Multiplier for Modulating Venting Open Factor]
if T\(_{zone}\) - T\(_{out}\) > = [Upper Value on Inside/Outside Temperature Difference for Modulating the Venting Open Factor] then Multiplication factor = [Limit Value on Multiplier for Modulating Venting Open Factor]
One way of “tuning” the following modulation control parameters is to perform a sensitivity analysis for winter and/or summer design days to determine what combination of values causes the biggest reduction in zone air temperature fluctuations due to venting.
Note that the default values for the following fields are such that, if none of the fields are specified, modulation will not occur.
Field: Minimum Venting Open Factor[LINK]
See Figure 5 or Figure 6. This field applies only if Ventilation Control Mode = Temperature or Enthalpy. This value may be from zero to 1.0, with the default being 0.0.
Field: Indoor and Outdoor Temperature Difference Lower Limit For Maximum Venting Open Factor[LINK]
See Figure 5. This field applies only if Ventilation Control Mode = Temperature. This value may be from zero to less than 100°C, with the default being 0°C. The value for this field must be less than the value specified for the following field.
Field: Indoor and Outdoor Temperature Difference Upper Limit for Minimun Venting Open Factor[LINK]
See Figure 5. This field applies only if Ventilation Control Mode = Temperature. This value must be greater than 0°C, with the default being 100°C. The value for this field must be greater than the value specified for the previous field.
Field: Indoor and Outdoor Enthalpy Difference Lower Limit For Maximum Venting Open Factor[LINK]
See Figure 6. This field applies only if Ventilation Control Mode = Enthalpy. This value may be from zero to less than 300,000 J/kg, with the default being 0 J/kg. The value for this field must be less than the value specified for the following field.
Field: Indoor and Outdoor Enthalpy Difference Upper Limit for Minimun Venting Open Factor[LINK]
See Figure 6. This field applies only if Ventilation Control Mode = Enthalpy. This value must be greater than zero, with the default being 300,000 J/kg. The value for this field must be greater than the value specified for the previous field.
Field: Venting Availability Schedule Name[LINK]
The name of a schedule that specifies when venting is available. A zero or negative schedule value means venting is not allowed. A value greater than zero means venting can occur if other venting control conditions (specified by Ventilation Control Mode and Vent Temperature Schedule Name) are satisfied. This schedule name should not be confused with Vent Temperature Schedule Name. If the surface is an air boundary (Construction:AirBoundary) then this field is ignored and venting is always available.
If a Venting Availability Schedule Name is not specified, it is assumed that venting is always available.
Using Venting Availability Schedule allows you to turn off venting at certain times of the day (at night, for example), week (on weekends, for example), or year (during the winter, for example).
If used with Ventilation Control Mode = Constant, the ventilation rate is constant only when this schedule allows venting; otherwise the ventilation rate is set to zero.
If Ventilation Control Mode = NoVent, this schedule has no effect.
Note: In order to establish an airflow network, each AirflowNetwork:MultiZone:Zone object must have at least two surfaces defined with AirflowNetwork:MultiZone:Surface objects, so that air can flow from one zone into other zones (or to outdoors) through the network (air mass flow conserved). In addition, for all AirflowNetwork:MultiZone:Surface objects facing the same Zone Name (ref. BuildingSurface:Detailed), at least two different environments must be defined for the other side of these surfaces (e.g., an external node and an adjacent zone, two adjacent zones, or two external nodes).
Field: Occupant Ventilation Control Name[LINK]
The name of an AirlowNetwork:OccupantVentilationControl object. The object is used to perform advanced window opening control based on occupant conditions. When an object name is given, advanced window opening control is performed and, the Ventilation Control defined in the Ventilation Control Mode field will be overridden.
Field: Equivalent Rectangle Method[LINK]
This field is applied to a non-rectangular window or door. The equivalent rectangular surface has the same area as the non-rectangular one. The valid choices are: PolygonHeight, BaseSurfaceAspectRatio, and UserDefinedAspectRatio, with the default of PolygonHeight. When PolygonHeight is entered, the equivalent width is equal to the area divided by the PolygonHeight for a non-horizontal surface. When a surface is horizontal with the same height for all vertices, the model will automatically switch a choice to BaseSurfaceAspectRatio if a base surface is rectangular, or UserDefinedAspectRatio with the default value if a base surface is non-rectangular. When BaseSurfaceAspectRatio is entered for a rectangular base surface, the equivalent height is equal to Square Root of Area divided by the base surface aspect ratio. The equivalent width is equal to the equivalent height times the base surface aspect ratio. When a base surface is non-rectangular, the model will automatically switch the choice to PolygonHeight for a non-horizontal base surface, and UserDefinedAspectRatio with the default value if a base surface is horizontal. When UserDefinedAspectRatio is entered, the equivalent height is equal to Square Root of Area divided by UserDefinedAspectRatio. The equivalent width is equal to the equivalent height times the user-defined aspect ratio.
Field: Equivalent Rectangle Aspect Ratio[LINK]
This field applies only if Equivalent Rectangle Method = UserDefinedAspectRatio. This value must be greater than zero, with the default being 1.0.
IDF examples are provided below:
AirflowNetwork:MultiZone:ReferenceCrackConditions[LINK]
This object specifies the reference conditions for temperature, humidity, and pressure which correspond to the AirflowNetwork:MultiZone:Surface:Crack object.
Inputs[LINK]
Field: Name[LINK]
The name of this Reference Crack Conditons object. This name is referenced by an AirflowNetwork:MultiZone:Surface:Crack object.
Field: Reference Temperature[LINK]
The reference temperature in °C under which the Surface Crack Data were obtained. The default value is 20°C.
Field: Reference Barometric Pressure[LINK]
The reference barometric pressure in Pa under which the Surface Crack Data were obtained. The default value is 101325 Pa.
Field: Reference Humidity Ratio[LINK]
The reference humidity ratio in kgWater/kgDryAir under which the Surface Crack Data were obtained. The default value is 0 kgWater/kgDryAir.
An IDF example is provided below:
AirflowNetwork:MultiZone:Surface:Crack[LINK]
This object specifies the properties of air flow through a crack and the associated measurement conditions. The following power law form is used that gives air flow through the crack as a function of the pressure difference across the crack:
\[Q = \left( Crack\;Factor \right) * C_T * C_Q \left( \Delta P \right)^{n}\]
Where
Q = air mass flow (kg/s)
C\(_{Q}\) = air mass flow coefficient (kg/s-Pa\(^{n}\) @ 1 Pa)
C\(_{T}\) = reference condition temperature correction factor (dimensionless)
\(\Delta P\) = pressure difference across crack (Pa)
n = air flow exponent (dimensionless)
\[{C_T} = {\left[ {\frac{{{\rho_o}}}{\rho }} \right]^{n - 1}}{\left[ {\frac{{{\nu_o}}}{\nu }} \right]^{2n - 1}}\]
where
\(\rho\) = Air density at the specific air temperature and humidity ratio conditions [kg/m\(^{3}\)]
\(\nu\) = Air kinetic viscosity at the specific air temperature condition [m\(^{2}\)/s]
\(\rho_o\) = Air density at the reference air conditions provided by the object AirflowNetwork:MultiZone:ReferenceCrackConditions specified in the field Reference Crack Conditions [kg/m\(^{3}\)]
\(\nu_o\) = Air kinetic viscosity at the reference air temperature provided by the object AirflowNetwork:MultiZone:ReferenceCrackConditions specified in the field Reference Crack Conditions [m\(^{2}\)/s]
Note: The correction factor shown above is use for this particular component as specified.
Inputs[LINK]
Field: Name[LINK]
This is a name for this AirflowNetwork:MultiZone:Surface:Crack object. It is referenced by an AirflowNetwork:MultiZone:Surface object.
Field: Air Mass Flow Coefficient at Reference Conditions[LINK]
The value of the air mass flow coefficient,\({C_Q}\) , in the crack air flow equation. It has units of kg/s at 1Pa. This value must be greater than zero.
Field: Air Mass Flow Exponent[LINK]
The value of the exponent, n, in the crack air flow equation. The valid range is 0.5 to 1.0, with the default value being 0.65.
Field: Reference Crack Conditions[LINK]
The name of the AirflowNetwork:MultiZone:ReferenceCrackConditions object which specifies the conditions under which the air mass flow coefficient was measured. If the user omits this field and only one AirflowNetwork:MultiZone:ReferenceCrackConditions object is defined in the input data file, then those reference crack conditions will be used. If the user omits this field and either zero or more than one AirflowNetwork:MultiZone:ReferenceCrackConditions objects are defined in the input data file, then the default conditions for the AirflowNetwork:MultiZone: Reference Crack Conditions object will be used.
An IDF example is shown below:
AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea[LINK]
The effective leakage area (ELA) object is used to define surface air leakage. It has
five fields. The relationship between pressure and airflow may be expressed as:
\[\dot m = ELA*{C_d}\sqrt {2\rho } *{\left( {\Delta {P_r}} \right)^{0.5 - n}}{\left( {\Delta P} \right)^n}\]
where
\(\dot m\) = Air mass flow rate [kg/s]
\(\rm{ELA}\) = Effective leakage area [m\(^{2}\)]
\(\rho\) = Air density [kg/m\(^{3}\)]
\(\Delta {P_r}\) = Reference pressure difference [Pa]
\(\Delta P\) = Pressure difference across this component [Pa]
\(C_{d}\) = Discharge coefficient [dimensionless]
\(n\) = Air mass flow exponent [dimensionless]
Inputs[LINK]
Field: Name[LINK]
This is a name for this AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea object. It is referenced by an AirflowNetwork:MultiZone:Surface object.
Field: Effective Leakage Area[LINK]
This numeric field is used to input the effective leakage area in square meters. The effective leakage area is used to characterize openings for infiltration calculations (ASHRAE Handbook of Fundamentals, 1997, pp 25.18). This value must be greater than zero.
Field: Discharge Coefficient[LINK]
This numeric field is used to input the discharge coefficient. This value must be greater than zero, with a default value of 1.0.
Field: Reference Pressure Difference[LINK]
This numeric field is used to input the reference pressure difference [Pa]. This value must be greater than zero, with a default value of 4.0 Pa.
Field: Air Mass Flow Exponent[LINK]
This numeric field is used to input the pressure difference exponent. The valid range of the exponent is from 0.5 to 1.0, with a default value of 0.65.
Note: There are two common sets of reference conditions: \(C_{d}\) = 1.0 and \(\Delta P\) = 4 Pa, or \(C_d\) = 0.6 and \(\Delta P\) = 10 Pa
An IDF example is shown below:
AirflowNetwork:MultiZone:SpecifiedFlowRate[LINK]
The specified flow object is used to specify flow through a surface. The object has three fields and will cause the mass flow \(\dot m\) to be set appropriately as \[\dot m = F\] when the mass flow rate \(F\) is specified or as \[\dot m = \rho Q\] when the volume flow rate \(Q\) is specified. A positive value of the flow directs the flow from node 1 of the linkage to node 2, and a negative value directs the flow from node 2 to node 1 of the linkage. For surface linkages that are part of the building envelope, a positive value means flow from inside to the outdoors (exfiltration) and a negative value is a flow from the outside to inside (infiltration).
Inputs[LINK]
Field: Name[LINK]
This is a name for this object. It is referenced by an AirflowNetwork:MultiZone:Surface object.
Field: Air Flow Value[LINK]
This numeric field is used to input the flow rate \(F\) or \(Q\). The units of the value are determined by the following field.
Field: Air Flow Units[LINK]
This choice field determines the units of the air flow value. Two options are available, “kg/s” and “m3/s”.
An IDF example is shown below:
AirflowNetwork:MultiZone:Component:DetailedOpening[LINK]
This object specifies the properties of air flow through windows and doors (window, door and glass door heat transfer subsurfaces) when they are closed or open. The fields are similar to those for AirflowNetwork:MultiZone:SurfaceCrack object when the window or door is closed, but additional fields are required to describe the air flow characteristics when the window or door is open. These additional fields include opening type, opening dimensions, degree of opening, and opening schedule.
The AirflowNetwork model assumes that open windows or doors are vertical or close to vertical; for this reason they are called “Large Vertical Openings.” Such openings can have air flow moving simultaneously in two different directions depending on stack effects and wind conditions (for example, flow from inside to outside at the top of a window and from outside to inside at the bottom). AirflowNetwork models such two-directional flow, but only for vertical openings.
It is assumed that the air flow through a window opening is unaffected by the presence of a shading device such as a shade or blind on the window. Also, the calculation of conductive heat transfer and solar gain through a window or door assumes that the window or door is closed.
The AirflowNetwork model does not have a model for bi-directional flow through large horizontal openings in exterior surfaces. For this reason, AirflowNetwork:MultiZone:Component:DetailedOpening should not be used for exterior horizontal openings. The best modeling technique in this case is to put an AirflowNetwork:MultiZone:Surface:Crack object in a horizontal surface and use a large air mass flow coefficient. Crack flow is assumed to be uni-directional in any given timestep (but can reverse flow direction from timestep to timestep).
For large horizontal openings in interior surfaces, see AirflowNetwork:MultiZone:Component:HorizontalOpening.
A subsurface multiplier may be used to represent multiple subsurfaces and calculates total air flow when the subsurface (window, glassdoor, or door) is either closed or open. The total airflow across the surface is equal to the airflow based on the surface geometry multiplied by the subsurface multiplier.
Inputs[LINK]
Field: Name[LINK]
The name of this AirflowNetwork:MultiZone:Component:DetailedOpening object. It is referenced by an AirflowNetwork:Multizone:Surface object.
Field: Air Mass Flow Coefficient When Opening is Closed[LINK]
Crack flow is assumed when the window or door is closed. The units for this air mass flow coefficient (\({C_{Q,\;unit\;length}}\) ) are different from the units for \({C_Q}\) (kg/s at 1 Pa pressure difference) defined in an AirflowNetwork:MultiZone:Surface:Crack object. There is no default but the entered value must be greater than zero. The program will automatically generate four cracks around the perimeter of the window or door–one along the bottom, one along the top, and one on each side. The temperature correction factor used in the AirflowNetwork:MultiZone:Surface:Crack object is not used for this component to calculate air mass flow rate.
Field: Air Mass Flow Exponent When Opening Is Closed[LINK]
Crack flow is assumed when the window or door is closed. In this case, the value of this field is the exponent, n, in the crack air flow equation. The valid range for this exponent is 0.5 to 1.0, with the default value being 0.65. Mass Flow Rate = Air Mass Flow Coefficient (deltaP) Air Mass Flow Exponent.
Field: Type of Rectanguler Large Vertical Opening (LVO)[LINK]
This alpha field specifies the type of rectangular window or door. (Open windows or doors are also called Large Vertical Openings (LVOs). The choices for the opening type are NonPivoted (LVO Type 1) and HorizontallyPivoted (LVO Type 2) with the default being NonPivoted. The NonPivoted type represents a regular window or door. The HorizontallyPivoted type represents a window with a horizontal axis (i.e., a horizontally-pivoting window) and cannot be used for a door.
Field: Extra Crack Length or Height of Pivoting Axis[LINK]
Specifies window or door characteristics that depend on the LVO type.
For LVO Type 1 (rectangular non-pivoted windows and doors) this field is the extra crack length in meters due to multiple openable parts, if present. “Extra” here means in addition to the length, calculated by the program, of the cracks on the top, bottom and sides of the window/door.
For LVO Type 2 (rectangular horizontally-pivoted windows) this field gives the height of the pivoting axis measured from the bottom of the glazed part of the window (m).
Field: Number of Sets of Opening Factor Data[LINK]
This is the number of the following sets of data for opening factor, discharge coefficient, width factor, height factor, and start height factor. From two to four of these sets must be defined. The first set should be for Opening Factor = 0.0 and the last set should be for Opening Factor = 1.0. For example, if only two sets are defined, the first set should be for Opening Factor = 0.0 and the second set should be for Opening Factor = 1.0, as shown below in the IDF example below.
An “opening factor” refers to the amount that a window or door is opened. The program linearly interpolates each timestep between the values of discharge coefficient, width factor, etc., in these sets using the opening factor for the window or door for the timestep. (See discussion under the field Window/Door Opening Factor in the AirflowNetwork:Multizone:Zone object for a description of how the AirflowNetwork model determines the time-step value of the opening factor.)
Field Group: Opening Factor, Discharge Coefficient, Width Factor, Height Factor, Start Height Factor[LINK]
Each field is described for as many groups as required in the previous field (number of sets of opening factor data). As the final field has specific requirements, this field (n) will be described.
Field: Opening Factor 11[LINK]
The first opening factor of a window or door. This value must be 0.0. The default value is also 0.0.
For LVO Type 1 (rectangular non-pivoted window or door), the Opening Factor corresponds to the fraction of window or door that is opened.
For LVO Type 2 (rectangular horizontally-pivoted windows), the Opening Factor is determined by the window opening angle. For example, an opening angle of 45° corresponds to an Opening Factor of 0.50 since the maximum opening angle is 90°.
Field: Discharge Coefficient for Opening Factor 1[LINK]
The discharge coefficient of the window or door for Opening Factor 1. The range is greater than 0.0 to less than or equal to 1.0. The default value is 0.001. The Discharge Coefficient indicates the fractional effectiveness for air flow through a window or door at that Opening Factor.
Note: In the following, “window width” and “window height” are glazing dimensions; they do not include the frame, if present.
Field: Width Factor for Opening Factor 1[LINK]
The Width Factor of the rectangular window or door for Opening Factor 1. The Width Factor is the opening width divided by the window or door width (see Figure 7). The range is 0.0 to 1.0. The default value is 0.0. Note that the width factor applies to rectangular windows or doors where the width is assumed constant along the entire height of the opening.
Field: Height Factor for Opening Factor 1[LINK]
The Height Factor of the rectangular window or door for Opening Factor 1. The Height Factor is the opening height divided by the window or door height (see Figure 7). The range is 0.0 to 1.0. The default value is 0.0. Note that the height factor applies to rectangular windows or doors where the height is assumed constant along the entire width of the opening.
Field: Start Height Factor for Opening Factor 1[LINK]
The Start Height Factor of the window or door for Opening Factor 1. The Start Height Factor is the Start Height divided by the window or door height (see Figure 7). The range is 0.0 to 1.0. The default is 0. Start Height is the distance between the bottom of the window or door and the bottom of the window or door opening. The sum of the Height Factor and the Start Height Factor must be less than 1.0 in order to have the opening within the window or door dimensions.
Field: Opening Factor <n>[LINK]
When Number of Sets of Opening Factor Data = n, the value of Opening Factor n must be set to 1.0.
Field: Discharge Coefficient for Opening Factor <n>[LINK]
The discharge coefficient of the window or door for Opening Factor n. The range is greater than 0.0 to less than or equal to 1.0. The default value is 1.0.
Field: Width Factor for Opening Factor <n>[LINK]
The Width Factor of the rectangular window or door for Opening Factor n. The Width Factor is the opening width divided by the window or door width (see Figure 7). The range is 0.0 to 1.0. The default value is 1.0.
Field: Height Factor for Opening Factor <n>[LINK]
The Height Factor of the rectangular window or door for Opening Factor n. The Height Factor is the opening height divided by the window or door height (see Figure 7). The range is 0.0 to 1.0. The default value is 1.0.
Field: Start Height Factor for Opening Factor <n>[LINK]
The Start Height Factor of the window or door for Opening Factor n. The Start Height Factor is the Start Height divided by the window or door height (see Figure 7). The range is 0.0 to 1.0. The default is 0.
When the opening factor value (as described under the field Window/Door Opening Factor in the AirflowNetwork:MultiZone:Surface object) is between two Opening Factor field values, the values of Discharge Coefficient, Width Factor, Height Factor, and Start Height Factor are linearly interpolated.
An IDF example is shown below:
AirflowNetwork:MultiZone:Component:HorizontalOpening[LINK]
This object specifies the properties of air flow through windows, doors and glass doors (heat transfer subsurfaces defined as a subset of FenestrationSurface:Detailed objects) when they are closed or open. This AirflowNetwork model assumes that these openings are horizontal or close to horizontal and are interzone surfaces. The second and third input fields are similar to those for AirflowNetwork:MultiZone:Surface:Crack, when the window or door is closed, but additional information is required to describe the air flow characteristics when the window or door is open. This additional information is specified in the last two input fields. The airflow across the opening consists of two types of flows: forced and buoyancy. The forced flow is caused by the pressure difference between two zones, while the buoyancy flow only occurs when the air density in the upper zone is greater than the air density in the lower zone. This opening also allows for the possibility of two-way flow when forced and buoyancy flows co-exist. This object’s openness can also be modulated based on the same opening factor control as an AirflowNetwork:MultiZone:Component:DetailedOpening object. However, the opening factor is only applied to the subsurface width. The opening width is equal to opening factor multiplied by the subsurface width.
A subsurface multiplier may be used to represent multiple subsurfaces and calculates total air flow when the subsurface (window, glassdoor, or door) is either closed or open. The total airflow across the surface is equal to the airflow based on the surface geometry multiplied by the subsurface multiplier.
Inputs[LINK]
Field: Name[LINK]
This is a name for this AirflowNetwork:MultiZone:Component:HorizontalOpening object. It is referenced by an AirflowNetwork:MultiZone:Surface object.
Field: Air Mass Flow Coefficient When Opening is Closed[LINK]
The value of the air mass flow coefficient, \({C_{Q,\;unit\;length}}\) , in the horizontal opening air flow equation. It has units of kg/s-m at 1Pa. The temperature correction factor is not applied to the mass flow calculation. This is a required input field and the entered value must be greater than zero.
Field: Air Mass Flow Exponent When Opening is Closed[LINK]
The value of the exponent, n, in the crack air flow equation. The valid range is 0.5 to 1.0, with the default value being 0.65.
Field: Sloping Plane Angle[LINK]
This numeric field is used to represent the angle between the horizontal plane and a sloped plane under the horizontal opening. Sloping plane angle = 90 is equivalent to fully open. The valid range is >0 to 90, with the default value being 90.
Field: Discharge Coefficient[LINK]
This numeric field is used to input the discharge coefficient. This is a required field and the entered value must be greater than zero.
An IDF example is shown below:
AirflowNetwork:MultiZone:Component:SimpleOpening[LINK]
This object specifies the properties of air flow through windows, doors and glass doors (heat transfer subsurfaces) when they are closed or open. The AirflowNetwork model assumes that open windows or doors are vertical or close to vertical. The second and third fields are similar to those for AirflowNetwork:MultiZone:Surface:Crack, when the window or door is closed, but additional information is required to describe the air flow characteristics when the window or door is open. This additional information is specified in the last two fields. Compared to the object AirflowNetwork:MultiZone:Component:DetailedOpening, which requires more inputs at different opening factors, this object needs comparatively less inputs. For this reason it is called a simple opening. This opening also allows for the possibility of two-way flow due to temperature and resulting density differences. Therefore, it is possible to have a positive pressure difference at the top of the opening, and a negative pressure difference at the bottom (or vice versa) when the neutral height is between the bottom and top heights of the associated surface. This object’s openness can also be modulated based on the same opening factor control as an AirflowNetwork:MultiZone:Component:DetailedOpening object. However, the opening factor is only applied to the subsurface width. The opening width is equal to opening factor multiplied by the subsurface width.
A subsurface multiplier may be used to represent multiple subsurfaces and calculates total air flow when the subsurface (window, glassdoor, or door) is either closed or open. The total airflow across the surface is equal to the airflow based on the surface geometry multiplied by the subsurface multiplier.
Inputs[LINK]
Field: Name[LINK]
This is a name for this AirflowNetwork:MultiZone:Component:SimpleOpening object. It is referenced by an AirflowNetwork:MultiZone:Surface object.
Field: Air Mass Flow Coefficient When Opening is Closed[LINK]
The value of the air mass flow coefficient, \({C_{Q,\;unit\;length}}\) , in the simple opening air flow equation. It has units of kg/s-m at 1Pa. The temperature correction factor is not applied for mass flow calculation.
Field: Air Mass Flow Exponent When Opening is Closed[LINK]
The value of the exponent, n, in the crack air flow equation. The valid range is 0.5 to 1.0, with the default value being 0.65. Mass Flow Rate = Air Mass Flow Coefficient (deltaP)^Air Mass Flow Exponent.
Field: Minimum Density Difference for Two-Way Flow[LINK]
This numeric field is used to input the minimum density difference above which two-way or one way flow may occur due to stack effect with the window being open. Two-way flow occurs only when the neutral plane is within the opening. Density differences less than this value result in one-way flow only with the window being closed. The minimum value for this field is greater than zero.
Field: Discharge Coefficient[LINK]
This numeric field is used to input the discharge coefficient. This value must be greater than zero.
An IDF example is shown below:
AirflowNetwork:MultiZone:Component:ZoneExhaustFan[LINK]
This object specifies the properties of air flow through an exterior heat transfer surface with a zone exhaust fan. The zone exhaust fan turns on or off based on the availability schedule defined in the corresponding Fan:ZoneExhaust object. When the exhaust fan mass flow rate is greater than zero, the airflow network model treats this object as a constant volume fan. When the fan is off based on the availability schedule, the model treats this object as a crack.
When the fan is on, the air mass flow rate modeled for the airflow network is based on the value defined in the MaximumFlow Rate field of the Fan:ZoneExhaust object. The airflow direction is from the corresponding zone to outdoors.
When the fan is off, the following power law form is used that gives air flow through the crack as a function of the pressure difference across the crack:
\[Q = \left( Crack\;Factor \right) * C_T * C_Q \left( \Delta P \right)^{n}\]
Where
Q = air mass flow (kg/s)
C\(_{Q}\) = air mass flow coefficient (kg/s-Pa\(^{n}\) @ 1 Pa)
C\(_{T}\) = reference condition temperature correction factor (dimensionless)
\(\Delta P\) = pressure difference across crack (Pa)
n = air flow exponent (dimensionless)
\[{C_T} = {\left[ {\frac{{{\rho_o}}}{\rho }} \right]^{n - 1}}{\left[ {\frac{{{\nu_o}}}{\nu }} \right]^{2n - 1}}\]
where
\(\rho\) = Air density at the specific air temperature and humidity ratio conditions [kg/m\(^{3}\)]
\(\nu\) = Air kinetic viscosity at the specific air temperature condition [m\(^{2}\)/s]
\(\rho_o\) = Air density at the reference air conditions provided by the object AirflowNetwork:MultiZone:ReferenceCrackConditions specified in the field Reference Crack Conditions [kg/m\(^{3}\)]
\(\nu_o\) = Air kinetic viscosity at the reference air temperature provided by the object AirflowNetwork:MultiZone:ReferenceCrackConditions specified in the field Reference Crack Conditions [m\(^{2}\)/s]
Note: The correction factor shown above is used when the exhaust fan is off. The airflow direction is based on the pressure difference between the zone and outdoors.
Inputs[LINK]
Field: Name[LINK]
This is the name for this instance of the AirflowNetwork:MultiZone:Component:ZoneExhaustFan object. This name must be the same name defined in the Fan:ZoneExhaust object. It is referenced by an AirflowNetwork:Multizone:Surface object.
Field: Air Mass Flow Coefficient When the Zone Exhaust Fan is Off at Reference Conditions[LINK]
The value of the air mass flow coefficient,\({C_Q}\) , in the crack air flow equation. It has units of kg/s at 1Pa. This value must be greater than zero. The value is used when the fan is off.
Field: Air Mass Flow Exponent When the Zone Exhaust Fan is Off[LINK]
The value of the exponent, n, in the crack air flow equation. The valid range is 0.5 to 1.0, with the default value being 0.65. The value is used when the fan is off.
Field: Reference Crack Conditions[LINK]
The name of the AirflowNetwork:MultiZone:ReferenceCrackConditions object which specifies the conditions under which the air mass flow coefficient was measured. If the user omits this field and only one AirflowNetwork:MultiZone:ReferenceCrackConditions object is defined in the input data file, then those reference crack conditions will be used. If the user omits this field and either zero or more than one AirflowNetwork:MultiZone:ReferenceCrackConditions objects are defined in the input data file, then the default conditions for the AirflowNetwork:MultiZone: Reference Crack Conditions object will be used.
An IDF example is shown below:
AirflowNetwork:MultiZone:ExternalNode[LINK]
External nodes in the AirflowNetwork model define environmental conditions outside of the building. These conditions include wind pressure coefficients that vary from façade to façade and can be highly dependent on the building geometry.
AirflowNetwork:MultiZone:ExternalNode objects do not have to be entered if Wind Pressure Coefficient Type = SurfaceAverageCalculation in the AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol) object.
Inputs[LINK]
Field: Name[LINK]
The external node name is associated with a particular building façade. This name is referenced by the External Node Name field of an AirflowNetwork:MultiZone:Surface object.
Field: External Node Height[LINK]
Designates the reference height, in meters, used to calculate relative pressure. The default value is 0 meters.
Field: Wind Pressure Coefficient Curve Name[LINK]
The name of a specific AirflowNetwork:MultiZone:WindPressureCoefficientValues object, curve, or table (which gives wind pressure coefficients for the façade as a function of angle of wind incident on the façade). Curves or tables should have the domain of 0 to 180 degrees or 0 to 360 degrees, depending upon the symmetry field (see below).
Field: Symmetric Wind Pressure Coefficient Curve[LINK]
Specifies the symmetry of the above named curve. The default is No, meaning that the curve will be evaluated from 0 to 360 degrees. Specify Yes for a curve that is symmetric about zero and is evaluated only up to 180 degrees. For this type of curve, an angle of 270 degrees is passed to the curve as 90 degrees.
Field: Wind Angle Type[LINK]
Specifies which wind angle should be used to calculate the wind pressure coefficient. The default is Absolute, meaning that the absolute wind direction angle will be used. Specifying Relative means that the angle will be relative to the surface normal. For a surface facing due east, the angle 0 corresponds to wind blowing perpendicular to and at the surface with absolute direction 90 degrees, while 90 degrees corresponds to wind blowing parallel to the surface from the right (facing outward) with an absolute direction of 180 degrees.
IDF examples are provided below:
AirflowNetwork:MultiZone:WindPressureCoefficientArray[LINK]
The reference height and wind directions are first specified under the AirflowNetwork:MultiZone:WindPressureCoefficientArray object. The user may specify up to 36 different wind directions in ascending order. These are then referenced by AirflowNetwork:MultiZone:WindPressureCoefficientValues objects defined for each AirflowNetwork:MultiZone:ExternalNode.
The AirflowNetwork:MultiZone:WindPressureCoefficientArray object is unique and needs to be entered only if Wind Pressure Coefficient Type = INPUT in the AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol) object. If Wind Pressure Coefficient Type = SurfaceAverageCalculation, this object is not required.
Inputs[LINK]
Field: Name[LINK]
The name of this AirflowNetwork:MultiZone:WindPressureCoefficientArray object. This name is referenced by each AirflowNetwork:MultiZone:WindPressureCoefficientValues object which, for each AirflowNetwork:MultiZone:ExternalNode, gives the wind pressure coefficients at each of the wind directions listed in the AirflowNetwork:MultiZone:WindPressureCoefficientArray. This name is also referenced by the AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol) object, indicating that this AirflowNetwork:MultiZone:WindPressureCoefficientArray and the pressure coefficients in the associated AirflowNetwork:MultiZone:WindPressureCoefficientValues objects will be used in the air flow simulation.
Field: Wind Direction 1-Wind Direction N[LINK]
Each field references the wind direction corresponding to the first through the Nth WPC value in each of the AirflowNetwork:MultiZone:WindPressureCoefficientValues objects. N can be as high as 36.
An IDF example is provided below:
AirflowNetwork:MultiZone:WindPressureCoefficientValues[LINK]
This object specifies up to 36 wind pressure coefficients (WPCs) for an AirflowNetwork:MultiZone:ExternalNode. These coefficients are defined for each of the wind directions defined in the unique AirflowNetwork:MultiZone:WindPressureCoefficientArray object. In the air flow calculation, interpolation of the specified WPC values is done for time-step values of wind direction.
AirflowNetwork:MultiZone:WindPressureCoefficientValues objects need to be entered only if the Wind Pressure Coefficient Type = INPUT in the AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol) object. If Wind Pressure Coefficient Type = SurfaceAverageCalculation, this object is not required and is not used.
Inputs[LINK]
Field: Name[LINK]
The name of this WindPressureCoefficientValues object. This name can be referenced by multiple AirflowNetwork:MultiZone:ExternalNode objects.
Field: WindPressureCoefficientArray Name[LINK]
Name of the associated AirflowNetwork:MultiZone:WindPressureCoefficientArray, which lists the wind direction corresponding to each wind pressure coefficient value in this AirflowNetwork:MultiZone:WindPressureCoefficientValues object.
Field: Wind Pressure Coefficient Value 1 to Wind Pressure Coefficient Value N[LINK]
The WPC (wind pressure coefficient) value for the building façade indicated by the External Node Name field above. This WPC value corresponds to the first wind direction in the AirflowNetwork:MultiZone:WindPressureCoefficientArray. Note that WPC values can be positive, negative or zero.
Obtaining WPC values[LINK]
WPC values can be obtained from wind tunnel measurements, CFD calculations, or from published values for different building shapes.
For rectangular buildings EnergyPlus will automatically calculate surface-averaged Cp values for the walls and roof of the building if you specify Wind Pressure Coefficient Type = SurfaceAverageCalculation in the AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol) object. In this case you do not have to enter any AirflowNetwork:MultiZone:WindPressureCoefficientValues objects.
Wind pressure coefficients are reported in the eplusout.eio either from inputs using “INPUT” as the choice for the Wind Pressure Coefficient Type field defined in the AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol) object, or from internal calculation using SurfaceAverageCalculation as the choice for the Wind Pressure Coefficient Type field defined in the same object. Below is an output example from the eplusout.eio file:
An IDF example is provided below:
AirflowNetwork:OccupantVentilationControl[LINK]
The AirflowNetwork:OccupantVentilationControl object provides control options with minimum opening and closing time checks and opening and closing probability values. In general, the probability values could be a constant or a specific function. Due to lack of real data, two schedules are selected to represent probability values. If real data are available, this object may be modified to adopt new data.
Inputs[LINK]
Field: Name[LINK]
This is the name of the object.
Field: Minimum Opening Time[LINK]
The field represents the minimum time that windows will remain open. If a window has been open for a time less than this value, the window will remain open.
Field: Minimum Closing Time[LINK]
The field represents the minimum time that windows will remain closed. If a window has been closed for a time less than this value, the window will remain closed.
Field: Thermal Comfort Low Temperature Curve Name[LINK]
This alpha field defines the name of a curve to be used for thermal comfort temperature calculation at low outdoor dry-bulb temperature. This curve is a linear or quadratic equation using outdoor dry-bulb temperatures as an independent variable. This performance curve can be used to describe the thermal comfort temperature at low outdoor dry-bulb temperature. It allows maximum two curves to describe the thermal comfort temperature in two different outdoor dry-bulb temperature regions. If a single curve is used, blanks are entered in the following two fields.
Field: Thermal Comfort Temperature Boundary Point[LINK]
When there are two piecewise curves to represent thermal comfort temperature calculation, this field represents a boundary point of outdoor dry-bulb temperature. The low temperature curve and the high temperature curve should have the same values at the boundary point. If a single curve is used, this field may be left blank.
Field: Thermal Comfort High Temperature Curve Name[LINK]
This alpha field defines the name of a curve to be used for thermal comfort temperature calculation at high outdoor dry-bulb temperature. This curve is a linear or quadratic equation using outdoor dry-bulb temperatures as an independent variable. This performance curve can be used to describe the thermal comfort temperature at high outdoor dry-bulb temperature. It allows maximum two curves to describe the thermal comfort temperature in two different outdoor dry-bulb temperature regions. If a single curve is used, blanks are entered in this field.
Field: Maximum Threshold for Persons Dissatisfied PPD[LINK]
This field is used to calculate the comfort band as a function of predicted percentage of dissatisfied (PPD). The default value is 10%. The equation is based on curve fit and is valid between 0% and 35%.
\[\Theta = -0.0028 (100-PPD)^2 + 0.3419 (100-PPD) - 6.6275\]
where
\(\Theta\) is the comfort band (degC)
PPD is predicted percentage person of dissatisfied (%)
Field: Occupancy Check[LINK]
Input is Yes or No. The default is No. If Yes, an occupancy check is performed used in the opening probability check. If No, the occupancy check is bypassed.
Field: Opening Probability Schedule Name[LINK]
The name of a schedule of opening probability that controls the opening of windows and doors in the thermal zone to provide natural ventilation. If the probability value is greater a random number, windows are allowed to open. Otherwise, the output will be false. This control will occur when minimum time checks for both opening and closing are satisfied.
Field: Closing Probability Schedule Name[LINK]
The name of a schedule of closing probability that controls the closing of windows and doors in the thermal zone to reduce natural ventilation. If the probability value is greater a random number, windows are allowed to be closed. Otherwise, the output will be false. This control will occur when minimum time checks for both opening and closing are satisfied.
An IDF example is provided below:
AirflowNetwork:ZoneControl:PressureController[LINK]
The AirflowNetwork:ZoneControl:PressureController object is used to control a zone to a specified indoor level of pressure using the AirflowNetwork model. The specified pressure setpoint is used to calculate the required zone exhaust fan flow rate in a controlled zone or relief air flow rate in an AirLoop.
The object has a similar function as ZoneControl:Thermostat. When an AirLoop serves multiple zones, the controlled zone will reach the specified setpoint, while other zones will not be controlled precisely.
Inputs[LINK]
Field: Name[LINK]
Unique identifying name for the AirflowNetwork:ZoneControl:PressureController.
Field: Control Zone Name[LINK]
Name of the zone that is being controlled.
Field: Control Object Type[LINK]
This field specifies the control type to be used for pressure control. Available control types are: AirflowNetwork:MultiZone:Component:ZoneExhaustFan and AirflowNetwork:Distribution:Component:ReliefAirFlow.
Field: Control Object Name[LINK]
The corresponding control object name.
Field: Pressure Control Availability Schedule Name[LINK]
This field contains the name of a schedule that determines whether or not the AirflowNetwork:ZoneControl:PressureController is available. When the schedule value is zero, the AirflowNetwork:ZoneControl:PressureController is bypassed (not available to operate). When the schedule value is greater than zero, the AirflowNetwork:ZoneControl:PressureController is available to perform pressure control. When AirflowNetwork:Distribution:Component:ZoneExhaustFan in entered in the Control Object Type field, the model will calculate the required zone exhaust fan airflow rate to reach the pressure setpoint. When an AirflowNetwork:Distribution:Component:ReliefAirFlow is entered in the Control Object Type field, the model will calculate the central relief flow rate in an outdoor air mixer. If this field is left blank, the schedule has a value of 1 for all time periods. Schedule values must be between 0 and 1.
Field: Pressure Setpoint Schedule Name[LINK]
This field contains the name of a schedule that contains the zone air pressure setpoint as a function of time. The units for pressure setpoint are Pascal. The setpoint values in the schedule must be between -50 and 100 Pascal.
An IDF example is provided below:
AirflowNetwork with RoomAir Models[LINK]
The next two objects of AirflowNetwork:IntraZone:Node and AirflowNetwork:IntraZone:Linkage are used with RoomAir:Node:AirflowNetwork objects together to simulate multiple internal airflows via multiple intrazone nodes and linkages in a thermal zone. The mixed-air assumption for zone air conditions is not always appropriate. EnergyPlus includes several RoomAir models that can model the implications for different flow patterns on variations in temperature within the zone. However none of them are generalized enough for different types of air flow situations and none are coupled tightly with AirflowNetwork. A general RoomAir model based on pressure network solver will allow modeling a variety of spaces types not currently covered by existing models such as tall spaces.
Recent advancements have been made to AirflowNetwork to model large horizontal openings. This new development makes AirflowNetwork useful for not only modeling air movement between zones (and outdoors), but also within individual thermal zones.
The possible combination will allow the EnergyPlus to simulate a thermal zone using a network approach by assuming internal nodes connected by user-defined patterns of temperatures and airflows. It should be pointed out that the new model works when the MultiZoneWithoutDistribution is selected in the field of AirflowNetwork Control of the AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol) object. The model cannot work with other choices.
AirflowNetwork:IntraZone:Node[LINK]
This object allows users to input multiple nodes in a zone. A single object represent a node. If there is only one node per zone, then use the AirflowNetwork:MultiZone:Zone input object. The zone node is not defined in this object.
Field: Name[LINK]
The name identifies the node for later reference and in the output listing. Each node should have a unique name. This name can be referenced as AirflowNetworkNodeNames.
Field: RoomAir:Node:AirflowNetwork Name[LINK]
The name of a RoomAir:Node:AirflowNetwork object, which is also defined in a RoomAirSettings:AirflowNetwork object (zone based).
Field: Zone Name[LINK]
The name of a zone object, which is also defined in a AirflowNetwork:MultiZone:Zone object (zone based).
Field: Node Height[LINK]
This field requires input of node height in meters.
An IDF example is provided below:
VentilationControl, !- Name
AirflowNetwork:IntraZone:Linkage[LINK]
The input object specifies a connection between two AirflowNetwork:IntraZone:Node objects and an AiflowNetwork component defined elsewhere. The object also allow users to specify a connection between an AirflowNetwork:IntraZone:Node and an adjacent zone defined in an AirflowNetwork:MultiZone:Zone object. This object provides flexibility to define a linkage either in the same zone or in two different zones.
Field: Name[LINK]
The name identifies the linkage for later reference and in the output listing. Each linkage should have a unique name.
Field: Node 1 Name[LINK]
The input designates a node name where airflow starts. The node name should be defined in an AirflowNetwork:IntraZone:Node object or an AirflowNetwork:MultiZone:Zone object.
Field: Node 2 Name[LINK]
The input designates a node name where airflow ends. The node name should be defined in an AirflowNetwork:IntraZone:Node object or an AirflowNetwork:MultiZone:Zone object.
Note: One of Node 1 and Node 2 should be defined as an AirflowNetwork:IntraZone:Node object. In other words, both nodes cannot be defined as AirflowNetwork:MultiZone:Zone object. This type of connection should be defined as an AirflowNetwork:MultiZone:Surface object.
Field: Component Name[LINK]
The input designates an AirflowNetwork component name associated with the two nodes. The component name should be one of the AirflowNetwork:MultiZone:Component object names. The component is used for intrazone node connection only. If the next field is specified, the input of this field could be a blank.
It should be pointed out that an AirflowNetwork:MultiZone:Surface object allows following five AirflowNetwork:MultiZone:Component objects:
AirflowNetwork:MultiZone:Component:DetailedOpening,
AirflowNetwork:MultiZone:Component:SimpleOpening,
AirflowNetwork:MultiZone:Surface:Crack,
AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea,
AirflowNetwork:MultiZone:Component:HorizontalOpening
However, an AirflowNetwork:IntraZone:Linkage object without a surface connection has connection with two intrazone nodes in the same zone and allows two AirflowNetwork:MultiZone:Component objects due to lack of geometry inputs.
AirflowNetwork:MultiZone:Surface:Crack,
AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea,
Field: Connection Surface[LINK]
The input specifies an AirflowNetwork:MultiZone:Surface object name, when the nodes defined above are not located in the same zone. The surface linkage will be connected by the above two nodes, instead of zone nodes in normal definition. In other words, the connection defined in an AirflowNetwork:MultiZone:Surface is removed. Instead, this new connection replaces the the connection specified before. A warning message is issued to let users be aware of the changes. Since each AirflowNetwork:MultiZone:Surface object has its own component defined in the Leakage Component Name field, the input of the Component Name field in this object will be ignored.
An IDF example is provided below:
The previous sections of this AirflowNetwork model discussion describe input objects used for multizone airflow calculations. The following sections describe input objects used for air distribution system simulations. These objects work when control option “MultiZone with Distribution” or “MultiZone with Distribution Only During Fan Operation” is defined in the AirflowNetwork Control field in the AirflowNetwork:[SimulationControl](../input-output-reference/group-simulation-parameters.html#simulationcontrol) object.
The first section presents the input object for distribution system nodes. Although thermal zones are required to perform air distribution system simulations, the thermal zones are already defined in the multizone input section (described previously), so that there is no need to repeat the inputs for thermal zones when modeling an air distribution system. The same is also true for surface air leakage. This section has only one object: AirflowNetwork:Distribution:Node.
AirflowNetwork:Distribution:DuctViewFactors[LINK]
The AirflowNetwork:Distribution:DuctViewFactors object is used to represent the information needed for simplified surface-to-duct radiation heat transfer. View factors from each duct object to each referenced surface are provided by the user. EnergyPlus calculates the heat gain to the duct from the referenced surfaces. If the object is included, radiation is calculated for the referenced duct; radiation is neglected of the object is omitted.
Field: Name of Linkage[LINK]
Name of the linkage object in which the view factors are applied.
Field: Surface Exposure Fraction[LINK]
The fraction, range 0 to 1, of the duct surface that is exposed to the zone for a partially buried duct (dimensionless).
Field: Surface Emittance[LINK]
The air duct surface emittance factor in the range 0 to 1 based on the material properties (dimensionless).
Field: Surface <#> Name[LINK]
This field specifies the name of the surface seen by the duct.
Field: View Factor <#>[LINK]
This field specifies the view factor from the duct to the surface.
This object is extensible, so additional pairs of the last two fields can be added to the end of this object.
An IDF example is provided below:
AirflowNetwork:Distribution:Node[LINK]
The AirflowNetwork:Distribution:Node object is used to represent air distribution system nodes for the AirflowNetwork model. The EnergyPlus nodes defined in an AirLoopHVAC are a subset of the nodes used to simulate the distribution system using the AirflowNetwork model. For example, the inlet node of a fan and the outlet node of a coil defined in an AirLoopHVAC must be defined as nodes using the AirflowNetwork:Distribution:Node object. A set of EnergyPlus Zone Equipment nodes is also a subset of the AirflowNetwork:Distribution:Nodes. For example, zone inlet and outlet nodes must be defined as nodes using the AirflowNetwork:Distribution: Node object. In addition, although mixers and splitters are defined as objects with inlet and outlet nodes within EnergyPlus, the AirflowNetwork:Distribution:Node object treats mixers and splitters as single nodes. The node objects are referenced by AirflowNetwork:Distribution:Linkage objects.
In summary, all nodes used to define an AirLoopHVAC (except splitters, mixers, and outdoor air systems which are treated as single nodes) and its connections to a thermal zone must be specified as AirflowNetwork:Distribution:Nodes. If distribution system air leaks are to be modeled, additional AirflowNetwork:Distribution:Nodes may be defined along with AirflowNetwork:Distribution:Components (e.g., leak or leak ratio) to define the air leakage characteristics.
Note: Supply and return leaks are not allowed in an AirLoopHVAC. They can only be modeled in the Zone Equipment Loop (i.e., return leaks may be modeled between the zone return node and the zone mixer inlet or the zone mixer outlet and the zone equipment loop outlet; and supply leaks may be modeled between the zone equipment loop inlet and the AirLoopHVAC:ZoneSplitter inlet node or the AirLoopHVAC:ZoneSplitter outlet node and the zone supply node).
Inputs[LINK]
Field: Name[LINK]
The name of an air distribution system node. This node name is referenced by an AirflowNetwork:Distribution:Linkage and in the output listing. Each node should have a unique name within the AirflowNetwork:Distribution:Node objects (however, the node name may be used elsewhere as regular EnergyPlus node names such as the fan inlet node or coil outlet node).
Field:Component Name or Node Name[LINK]
Designates node names defined in another EnergyPlus object, so that the AirflowNetwork:Distribution:Node object is able to get input parameters and node conditions from the associated EnergyPlus node or object. The actual node name is entered here and represents a node already defined in an AirLoopHVAC or zone equipment loop. This field is left blank if the EnergyPlus Node Type field below is entered as Mixer, Splitter, Outdoor air System, or Other.
Field: Component Object Type or Node Type[LINK]
This choice field distinguishes the node type for the EnergyPlus node or object name defined above. Five node types are available:
AirLoopHVAC:ZoneMixer: Represents an AirLoopHVAC:ZoneMixer object defined in EnergyPlus
AirLoopHVAC:ZoneSplitter: Represents an AirLoopHVAC:ZoneSplitter object defined in EnergyPlus
AirLoopHVAC:OutdoorAirSystem: Represents an AirLoopHVAC:OutdoorAirSystem object used in EnergyPlus
OAMixerOutdoorAirStreamNode: Represents an external node name specified as an Outdoor Air Stream Node Name in the OutdoorAir:Mixer object when the AirLoopHVAC:OutdoorAirSystem object is used.
OutdoorAir:NodeList: Represents an external node name defined in the OutdoorAir:NodeList object when the AirLoopHVAC:OutdoorAirSystem object and an exhaust energy recovery system (air-to-air heat exchanger) are used.
OutdoorAir: Represents an external node name defined in the OutdoorAir:Node object when the AirLoopHVAC:OutdoorAirSystem and an exhaust energy recovery system (air-to-air heat exchanger) are used.
Other: Represents a type not already defined above.
Note: Both the OutdoorAir:NodeList and OutdoorAir:Node node types represent a node to outdoor air conditions. Either one of these node types can be used to represent an external node when an air-to-air heat exchanger is used to recover energy from the exhaust air stream as part of an AirLoopHVAC:OutdoorAirSystem object. Node type OAMixerOutdoorAirStreamNode does not represent an external node when an OutdoorAir:NodeList or OutdoorAir:Node object is specified. If no exhaust heat recovery system (i.e., air-to-air heat exchanger) is specified in the AirLoopHVAC:OutdoorAirSystem, the node type OAMixerOutdoorAirStreamNode represents an external node.
Field: Node Height[LINK]
Designates the reference height in meters used to calculate relative pressure. The default value is 0 meters.
IDF examples are provided below:
The next section describes AirflowNetwork Distribution Components, with 7 available types listed below. All required fields for each component represent a relationship between pressure difference and airflow. The components are referenced in AirflowNetwork:Distribution:Linkage objects.
AirflowNetwork:Distribution:Component:Leak
AirflowNetwork:Distribution:Component:LeakageRatio
AirflowNetwork:Distribution:Component:Duct
AirflowNetwork:Distribution:Component:Fan
AirflowNetwork:Distribution:Component:Coil
AirflowNetwork:Distribution:Component:HeatExchanger
AirflowNetwork:Distribution:Component:TerminalUnit
AirflowNetwork:Distribution:Component:ConstantPressureDrop
AirflowNetwork:Distribution:Component:Leak[LINK]
This component may be also called a power law component and is used to represent a supply or return air leak in an air distribution system. Its relationship between pressure difference and airflow may be expressed as:
\[\dot m = {C_T}C{\left( {\Delta P} \right)^n}\]
where
\(\dot m\) = Air mass flow rate through the component [kg/s]
C = Air mass flow coefficient (kg/s at 1 Pa pressure difference)
\(\Delta P\) = Total pressure loss across the element [Pa]
n = Air mass flow exponent
C\(_{T}\) = Temperature correction factor
\[{C_T} = {\left[ {\frac{{{\rho_o}}}{\rho }} \right]^{n - 1}}{\left[ {\frac{{{\nu_o}}}{\nu }} \right]^{2n - 1}}\]
where
\(\rho\) = Air density at the specific air temperature and humidity ratio conditions [kg/m\(^{3}\)]
\(\nu\) = Air kinetic viscosity at the specific air temperature condition [m\(^{2}\)/s]
\(\rho_o\) = Air density at air conditions of 20°C, 0 kg/kg and 101325 Pa [kg/m\(^{3}\)]
\(\nu_o\) = Air kinetic viscosity at an air temperature of 20°C [m\(^{2}\)/s]
Note: The correction factor shown above is use for this particular component as specified.
Inputs[LINK]
Field: Name[LINK]
A unique name identifying a supply or return air leak in an air distribution system. This unique name will be referenced by an AirflowNetwork:Distribution:Linkage object to represent a component leak.
Field: Air Mass Flow Coefficient[LINK]
This numeric field is defined as the air mass flow coefficient at 1 Pa pressure difference across this component. Valid entries must be greater than zero.
Field: Air Mass Flow Exponent[LINK]
This numeric field is defined as the pressure difference exponent across the component. Valid entries are from 0.5 to 1.0, with the default value being 0.65.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:LeakageRatio[LINK]
The leakage ratio component is generally used to define supply and return leaks with respect to a constant fan flow. This object requires 5 inputs. The relationship between pressure and airflow may be expressed as a power law element:
\[\dot m = {C_{equ}}{\left( {\Delta P} \right)^n}\]
where
\(\rho\) = Air density [kg/m\(^{3}\)]
\(\Delta P\) = Total pressure loss across the element [Pa]
\(n\) = Air mass flow exponent
\(C_{equ}\) = Equivalent air mass flow coefficient
\[{C_{equ}}\,\,\,\,\,\, = r*{Q_r}*\rho *{\left( {\Delta {P_r}} \right)^{ - n}}\]
where
\(\rho\) = Effective leakage ratio [dimensionless]
\(Q_{r}\) = Maximum airflow rate [m\(^{3}\)/s]
\(\Delta {P_r}\) = Reference pressure difference [Pa]
\(n\) = Air mass flow exponent [dimensionless]
The above calculation is valid only for a HVAC system using a constant volume supply fan: Fan:ConstantVolume or Fan:OnOff.
Inputs[LINK]
Field: Name[LINK]
A unique name identifying a supply or return air leak (ratio with respect to the constant volume fan flow rate) in an air distribution system. This unique name will be referenced in an AirflowNetwork:Distribution:Linkage object to represent a component.
Field: Effective Leakage Ratio[LINK]
This numeric field is used to input the effective leakage ratio. This value must be greater than zero and less than or equal to 1. The effective leakage ratio is used to characterize supply and return leaks with respect to the constant fan flow (supply or return air leak flow rate divided by the maximum air flow rate for the fan). When a VAV system is used with Supply Fan Object Type = Fan:VariableVolume in the AirflowNetwork:Distribution:Component:Fan object, the ratio for a supply leak is defined as the value of supply air leak flow rate divided by the supply fan air flow rate at the current time step. The inputs of the rest of 3 fields are not used.
Field: Maximum Flow Rate[LINK]
This numeric field is used to input the maximum flow rate for a constant volume fan [m\(^{3}\)/s]. This value must be greater than 0 m\(^{3}\)/s. When a VAV system is used with Supply Fan Object Type = Fan:VariableVolume in the AirflowNetwork:Distribution:Component:Fan object, this input is not used, because the real supply fan flow rate at the current time step is used to calculate the amount of a supply leak.
Field: Reference Pressure Difference[LINK]
This numeric field is used to input the reference pressure difference [Pa]. This value must be greater than 0 Pa. When a VAV system is used with Supply Fan Object Type = Fan:VariableVolume in the AirflowNetwork:Distribution:Component:Fan object, this input is not used, because the real supply fan flow rate at the current time step is used to calculate the amount of a supply leak.
Field: Air Mass Flow Exponent[LINK]
This numeric field is used to input the pressure difference exponent. The value of the exponent can be from 0.5 to 1.0, with the default value being 0.65. When a VAV system is used with Supply Fan Object Type = Fan:VariableVolume in the AirflowNetwork:Distribution:Component:Fan object, this input is not used, because the real supply fan flow rate at the current time step is used to calculate the amount of a supply leak.
Note: The reference pressure difference is defined as the difference between pressures of originate and terminate nodes for supply and return leaks. In general, it may require that a simulation be performed with an initial guess for reference pressure difference using design day conditions. After obtaining pressures at the leakage nodes, more realistic reference pressure differences can be entered. It should be pointed out that since pressures at the nodes vary with temperature and other conditions, the effective leakage ratio is only an estimate. In other words, the exact leakage ratio may not be available.
When a VAV system is used with Supply Fan Object Type = Fan:VariableVolume in the AirflowNetwork:Distribution:Component:Fan object, the AirflowNetwork:Distribution:Component:LeakageRatio object has to be used to define a supply leak. The other components cannot be used. In addition, the first node in a AirflowNetwork:Distribution:Linkage to define a supply leak has to be the node in the duct to originate a supply leak, and the second node has to be the node of a zone to terminate a supply leak. In other words, the supply leak has to flow from node 1 to node 2. When this object is used to define a return leak, the first node in a AirflowNetwork:Distribution:Linkage has to be a thermal zone to originate a leak, and the second node has to be the node of a duct to terminate a leak.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:Duct[LINK]
This object represents a duct component and requires 9 input fields, one alpha field and 8 numeric fields. An additional two fields can be used to define the convection coefficients on the inner and outer surfaces of the duct. The relationship between pressure and airflow across the component may be expressed as (2001 ASHRAE Handbook of Fundamentals, Chapter 34):
\[\dot m = \sqrt {\frac{{2\rho {A^2}\Delta P}}{{fL/D + \sum {C_d}}}}\]
where
\(\dot m\) = Mass flow rate of air through the component [kg/s]
r = Air density [kg/m\(^{3}\)]
A = Cross sectional area [m\(^{2}\)]
\(\Delta P\) = Total pressure loss across the component [Pa]
L = Duct length [m]
D = Hydraulic diameter [m]
C\(_{d}\) = Dynamic loss coefficient due to fitting [dimensionless]
f = Friction factor
The friction factor can be calculated using the nonlinear Colebrook equation (ASHRAE Handbook of Fundamentals, 1997. p. 2.9, Eq. 29b)
\[\frac{1}{{\sqrt f }} = 1.44 + 2*\log \left( {\frac{D}{\varepsilon }} \right) - 2*\log \left( {1 + \frac{{9.3}}{{{\mathop{\rm Re}\nolimits} *\varepsilon /D*\sqrt f }}} \right)\]
where
e = Surface roughness [m]
Re = Reynolds number = \(\frac{\rho VD}{\mu}\)
Inputs[LINK]
Field: Name[LINK]
A unique name for an AirflowNetwork duct component in an air distribution system. This unique name will be referenced by an AirflowNetwork:Distribution:Linkage object to represent a component.
Field: Duct Length[LINK]
This numeric field is used to input duct length [m]. This value must be greater than zero.
Field: Hydraulic Diameter[LINK]
This numeric field is used to input hydraulic diameter, which is defined as:
\[{D_h} = \frac{{4A}}{P}\]
where
D\(_{h}\) = Hydraulic diameter [m]
A = Duct cross sectional area [m\(^{2}\)]
P = Perimeter of cross section [m]
Field: Cross Section Area[LINK]
This numeric field is used to input cross section area [m\(^{2}\)]. The model assumes that this element has no area change along its length. Otherwise, effective cross sectional area is required.
Field: Surface Roughness[LINK]
This numeric field is used to input surface roughness [m]. This value must be greater than zero, and the default value is 0.0009 m.
Field: Coefficient for Local Dynamic Loss Due to fitting[LINK]
This numeric field is defined as a coefficient for dynamic loss [dimensionless]. It represents dynamic loss due to fittings (such as an elbow).
Field: Heat Transmittance Coefficient (U-Factor) for Duct Wall Construction[LINK]
This numeric field is defines the heat transmittance coefficient (U value, W/m\(^{2}\)-K) for the duct wall construction. Film coefficents are calculated automatically, unless directly specified below.
Field: Overall Moisture Transmittance Coefficient from Air to Air[LINK]
This numeric field is defined as the overall moisture transmittance coefficient (kg/m\(^{2}\)) from air to air, including film coefficients at both surfaces.
Field: Outside Convection Coefficient[LINK]
This numeric field defines the outside convection coefficient (W/m\(^{2}\)-K). If the field is omitted, the film coeffient is calculated automatically as described in ASTM C1340.
Field: Inside Convection Coefficient[LINK]
This numeric field defines the inside convection coefficient (W/m\(^{2}\)-K). If the field is omitted, the film coeffient is calculated automatically as described in ASTM C1340.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:Fan[LINK]
This component represents a constant or variable volume fan in the air distribution system (AirLoopHVAC). The air flow rate and air conditions (temperature and humidity) are obtained from the associated Fan:ConstantVolume, Fan:OnOff, Fan:VariableVolume, or Fan:SystemModel object.
Inputs[LINK]
Field: Fan Name[LINK]
The name identifying an AirflowNetwork constant volume fan in an air distribution system. This name must be the same as the name of the associated Fan:ConstantVolume, Fan:OnOff, Fan:VariableVolume, or Fan:SystemModel object. This name will be referenced by an AirflowNetwork:Distribution:Linkage object to represent a component.
Field: Supply Fan Object Type[LINK]
This choice field defines the type of fan. The only valid choices are Fan:OnOff, Fan:ConstantVolume, Fan:VariableVolume, and Fan:SystemModel with the default being Fan:ConstantVolume. Both cycling and continuous fan operating modes are allowed for Fan:OnOff. Only the continuous fan operating mode is allowed for Fan:ConstantVolume with constant volume and Fan:VariableVolume with variable volume, respectively. An advanced fan model for Fan:SystemModel is also allowed.
Note: Make sure that the volumetric air flow rates for the fan, coils, and parent components (e.g., unitary system or furnace) are the same so that fan energy and air distribution system losses/gains are properly calculated.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:Coil[LINK]
This component represents a cooling or heating coil. The main purpose for this object is to get calculated values (air flow and temperature/humidity conditions) from the associated coil models.
Inputs[LINK]
Field: Coil Name[LINK]
The name identifying an AirflowNetwork cooling coil or heating coil defined in an air loop. This name must be the same name as the associated coil object. This unique name will be referenced by an AirflowNetwork:Distribution:Linkage object to represent a component.
Field: Coil Object Type[LINK]
This field requires input of the coil type used in the AirflowNetwork model. The available choices are:
Coil:Cooling:DX:SingleSpeed
Coil:Heating:Fuel
Coil:Heating:Electric
Coil:Heating:DX:SingleSpeed
Coil:Cooling:Water
Coil:Heating:Water
Coil:Cooling:Water:DetailedGeometry
Coil:Cooling:DX:TwoStageWithHumidityControlMode
Coil:Cooling:DX:MultiSpeed
Coil:Heating:DX:MultiSpeed
Coil:Heating:Desuperheater
Field: Air Path Length[LINK]
This numeric field is used to input air path length for the coil [m]. This value must be greater than 0 meters.
Field: Air Path Hydraulic Diameter[LINK]
This numeric field is used to input hydraulic diameter of a coil’s air path, which is defined as:
\[{D_h} = \frac{{4A}}{P}\]
where
D\(_{h}\) = Hydraulic diameter [m]
A = Duct cross section area [m\(^{2}\)]
P = Perimeter of cross section [m]
For this component, the relationship between airflow and pressure is similar to the component AirflowNetwork:Distribution:Component:Duct. However, the model assumes very small surface roughness (10\(^{-4}\)) and no local dynamic loss due to fittings for this component. Therefore, this component only requires two numerical fields. Heat and moisture exchange from surroundings is ignored.
Note: Make sure that the volumetric air flow rates for the fan, coils, and parent components (e.g., unitary system or furnace) are the same so that fan energy and air distribution system losses/gains are properly calculated.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:HeatExchanger[LINK]
This component represents an air-to-air heat exchanger typically used in combination with a cooling coil to enhance dehumidification or in an outside air system to recover energy from exhaust air to pretreat incoming outdoor ventilation air. The cooling coils with enhanced dehumidification are defined in the two objects CoilSystem:Cooling:DX:HeatExchangerAssisted and CoilSystem:Cooling:Water:HeatExchangerAssisted using one of three heat exchanger objects specified below. The exhaust air energy recovery system also has the same restriction using the one of three heat exchanger objects. The main purpose for this object is to obtain calculated values (air flow and temperature/humidity conditions) from the associated heat exchanger models for the airflow network calculations.
Inputs[LINK]
Field: Heat Exchanger Name[LINK]
The name identifying an AirflowNetwork heat exchanger defined in an air loop. This name must be the same name that is used in the associated heat exchanger object. This unique name will be referenced by an AirflowNetwork:Distribution:Linkage object to represent a component.
Field: Heat Exchanger Object Type[LINK]
This field requires input of the heat exchanger type. The available choices are:
HeatExchanger:AirToAir:FlatPlate
HeatExchanger:AirToAir:SensibleAndLatent
HeatExchanger:Desiccant:BalancedFlow
Field: Air Path Length[LINK]
This numeric field is used to input air path length for the heat exchanger coil [m]. This value must be greater than 0 meters.
Field: Air Path Hydraulic Diameter[LINK]
This numeric field is used to input hydraulic diameter of a heat exchanger coil’s air path, which is defined as:
\[{D_h} = \frac{{4A}}{P}\]
where
D\(_{h}\) = Hydraulic diameter [m]
A = Duct cross section area [m\(^{2}\)]
P = Perimeter of cross section [m]
For this component, the relationship between airflow and pressure is similar to the component AirflowNetwork:Distribution:Component:Duct. However, the model assumes very small surface roughness (10\(^{-4}\)) and no local dynamic loss due to fittings for this component. Therefore, this component only requires two numerical fields. Heat and moisture exchange from surroundings are ignored.
Note: When a heat exchanger is used as a component of either CoilSystem:Cooling:DX:HeatExchangerAssisted or CoilSystem:Cooling:Water:HeatExchangerAssisted, the heat exchanger acts as two components in an air primary loop. For example, an air-to-air heat exchanger has a component connected to the supply air side (equivalent to a supply coil) and a component connected to exhaust air side (equivalent to an exhaust coil). The desiccant heat exchanger has a component connected to regeneration air side (equivalent to a regeneration air coil) and a component connected to process air side (equivalent to a process air coil). Therefore, each air-to-air heat exchanger used in this configuration requires two linkage objects (instead of only one linkage object as required for other AirflowNetwork components).
When a heat exchanger is used in an exhaust air energy recovery system (i.e., in an AirLoopHVAC:OutdoorAirSystem object to recover waste heat from exhaust air to pretreat incoming outdoor ventilation air), the heat exchanger is treated as a single component. The AirflowNetwork model only connects the two nodes associated with the incoming outdoor ventilation air, while the two exhaust nodes are not defined as part of the AirflowNetwork model. Therefore, each heat exchanger component used in an exhaust air energy recovery system has only one linkage object, similar to AirflowNetwork coil components.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:TerminalUnit[LINK]
This component represents a terminal unit for reheating the incoming supply air. The main purpose is to get calculated values from the terminal unit models.
Inputs[LINK]
Field: Terminal Unit Name[LINK]
A name identifying an AirflowNetwork terminal unit defined in a zone equipment list. This name must be the same as the associated terminal unit object. This unique name will be referenced by an AirflowNetwork:Distribution:Linkage object to represent a component.
Field: Terminal Unit Object Type[LINK]
This field requires input of the terminal unit type used in the AirflowNetwork model. The available types are AirTerminal:SingleDuct:ConstantVolume:Reheat and AirTerminal:SingleDuct:VAV:Reheat. The AirTerminal:SingleDuct:ConstantVolume:Reheat type is used when the Supply Fan Object Type in the AirflowNetwork:Distribution:Component:Fan is either Fan:ConstantVolume or Fan:OnOff. The AirTerminal:SingleDuct:VAV:Reheat type is used when the Supply Fan Object Type in the AirflowNetwork:Distribution:Component:Fan is Fan:VariableVolume only.
Field: Air Path Length[LINK]
This numeric field is used to input the air path length for the terminal unit [m]. This value must be greater than 0 meters.
Field: Air Path Hydraulic Diameter[LINK]
This numeric field is used to input hydraulic diameter for the terminal unit’s air path, which is defined as:
\[{D_h} = \frac{{4A}}{P}\]
where
D\(_{h}\) = Hydraulic diameter [m]
A = Duct cross section area [m\(^{2}\)]
P = Perimeter of cross section [m]
It should be noted that the relationship for this component between airflow and pressure is similar to the component AirflowNetwork:Distribution:Component:Duct. However, the model assumes very small surface roughness (10\(^{-4}\)) and no local dynamic loss due to fittings for this component. Therefore, this component only requires two numerical fields. Heat and moisture exchange from surroundings is ignored.
Note: The AirflowNetwork:Distribution:Component:TerminalUnit object is used to represent an AirTerminal:SingleDuct:ConstantVolume:Reheat or an AirTerminal:SingleDuct:VAV:Reheat object in an AirflowNetwork simulation. The AirflowNetwork:Distribution:Component:TerminalUnit should not be used to represent any other air terminal unit types. When the ZoneHVAC:EquipmentList object specifies an Air:Terminal:SingleDuct:ConstantVolume:NoReheat object, the AirflowNetwork:Distribution:Component:Duct object should be used instead.
The AirTerminal:SingleDuct:VAV:Reheat object has two components: a damper and a reheat coil. When the AirTerminal:SingleDuct:VAV:Reheat type is used, two objects of AirflowNetwork:Distribution:Linkage have to be used to make two links, one of which is a link to connect two nodes for a damper, and the other is a link to connect two nodes for a reheat coil.
When a VAV system is used with Supply Fan Object Type = Fan:VariableVolume in the AirflowNetwork:Distribution:Component:Fan object, the type of all terminals has to be AirTerminal:SingleDuct:VAV:Reheat. The object of Air:Terminal:SingleDuct:ConstantVolume:NoReheat is not allowed.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:ConstantPressureDrop[LINK]
This component represents a constant pressure drop component. It is generally used to simulate a constant pressure drop filter. The mathematical equation may be written as:
\[\Delta P = const\]
Inputs[LINK]
Field: Name[LINK]
A unique name identifying an AirflowNetwork constant pressure drop component in an air distribution system. This unique name will be referenced by an AirflowNetwork: Distribution:Linkage object to represent a component.
Field: Pressure Difference across the Component[LINK]
This numeric field is used to input the pressure difference across the element [Pa].
Note: This object should be used with caution. Each node connected to this object cannot be a node for a mixer or splitter, a node in an AirLoopHVAC, or a node in a zone configuration loop. It is recommended that duct components be specified at both ends of this object.
An IDF example is provided below:
AirflowNetwork:Distribution:Component:OutdoorAirFlow[LINK]
The AirflowNetwork:Distribution:Component:OutdoorAirFlow object is used to allow the AirflowNetwork model to include the outdoor air flow rate in the airflow network. When the outdoor air mass flow rate is greater than zero, the airflow network model treats this object as a constant volume fan and the flow rate is provided by the Controller:OutdoorAir object. When there is no outdoor air flow rate, the model treats this object as a crack and a power law is assumed.
Inputs[LINK]
Field: Name[LINK]
This is the name for this instance of the AirflowNetwork:Distribution:Component:OutdoorAirFlow object.
Field: Outdoor Air Mixer Name[LINK]
The name identifying an AirflowNetwork OutdoorAirFlow defined in an air loop as an OutdoorAir:Mixer object. This name must be the same name as the associated OutdoorAir:Mixer object.
Field: Air Mass Flow Coefficient When No Outdoor Air Flow at Reference Conditions[LINK]
The value of the air mass flow coefficient, \({C_Q}\), in the crack air flow equation. It has units of kg/s at 1Pa. This value must be greater than zero. The value is used when when the outdoor mass flow rate is zero from the Controller:OutdoorAir object.
Field: Air Mass Flow Exponent When No Outdoor Air Flow[LINK]
The value of the exponent, n, in the crack air flow equation. The valid range is 0.5 to 1.0, with the default value being 0.65. The value is used when the outdoor mass flow rate is zero from the Controller:OutdoorAir object.
Field: Reference Crack Conditions[LINK]
The name of the AirflowNetwork:MultiZone:ReferenceCrackConditions object which specifies the conditions under which the air mass flow coefficient was measured. If the user omits this field and only one AirflowNetwork:MultiZone:ReferenceCrackConditions object is defined in the input data file, then those reference crack conditions will be used. If the user omits this field and either zero or more than one AirflowNetwork:MultiZone:ReferenceCrackConditions objects are defined in the input data file, then the default conditions for the AirflowNetwork:MultiZone: Reference Crack Conditions object will be used.
IDF examples are provided below:
AirflowNetwork:Distribution:Component:ReliefAirFlow[LINK]
The AirflowNetwork:Distribution:Component:ReliefAirFlow object is used to allow the AirflowNetwork model to perform pressure control by varying the amount of relief air flow rate between 0 and the flow rate specified by the Controller:OutdoorAir object. When the outdoor air mass flow rate is greater than zero, the airflow network model treats this object as a constant volume fan and the flow rate is varied to reach pressure control. When there is no outdoor air flow rate, the model treats this object as a crack and a power law is assumed.
Inputs[LINK]
Field: Name[LINK]
This is the name for this instance of the AirflowNetwork:Distribution:Component:ReliefAirFlow object.
Field: Outdoor Air Mixer Name[LINK]
The name identifying an AirflowNetwork OutdoorAirFlow defined in an air loop as an OutdoorAir:Mixer object. This name must be the same name as the associated OutdoorAir:Mixer object.
Field: Air Mass Flow Coefficient When No Outdoor Air Flow at Reference Conditions[LINK]
The value of the air mass flow coefficient, \({C_Q}\), in the crack air flow equation. It has units of kg/s at 1Pa. This value must be greater than zero. The value is used when the outdoor mass flow rate is zero from the Controller:OutdoorAir object.
Field: Air Mass Flow Exponent When No Outdoor Air Flow[LINK]
The value of the exponent, n, in the crack air flow equation. The valid range is 0.5 to 1.0, with the default value being 0.65. The value is used when the outdoor mass flow rate is zero from the Controller:OutdoorAir object.
Field: Reference Crack Conditions[LINK]
The name of the AirflowNetwork:MultiZone:ReferenceCrackConditions object which specifies the conditions under which the air mass flow coefficient was measured. If the user omits this field and only one AirflowNetwork:MultiZone:ReferenceCrackConditions object is defined in the input data file, then those reference crack conditions will be used. If the user omits this field and either zero or more than one AirflowNetwork:MultiZone:ReferenceCrackConditions objects are defined in the input data file, then the default conditions for the AirflowNetwork:MultiZone: Reference Crack Conditions object will be used.
IDF examples are provided below:
AirflowNetwork:Distribution:Linkage[LINK]
The AirflowNetwork:Distribution:Linkage represents a connection between two AirflowNetwork:Distribution:Node objects and an AirflowNetwork component defined above. In addition, the relative height from node height to linkage height for each node is required.
Inputs[LINK]
Field: Name[LINK]
The name identifies the linkage for later reference and in the output listing. Each linkage should have a unique name.
Field: Node 1 Name[LINK]
Designates a node name where airflow starts. The node name should be defined in an AirflowNetwork:Distribution:Node object.
Field: Node 2 Name[LINK]
Designates a node name where airflow ends. The node name should be defined in an AirflowNetwork:Distribution:Node object.
Field: Component Name[LINK]
Designates an AirflowNetwork component name associated with the two nodes. The component name should be one of the AirflowNetwork:Distribution:Component… object names.
Field: Thermal Zone Name[LINK]
Designates a thermal zone where the linkage is located. The information provides the ambient conditions for duct elements to calculate duct conduction losses (only used if component is AirflowNetwork:Distribution:Component:Duct).
An IDF example is provided below:
Outputs[LINK]
The AirflowNetwork nodes in the following output variables includes zones defined in AirflowNetwork:MultiZone:Zone objects, external nodes defined in AirflowNetwork:MultiZone:ExternalNode objects, and nodes defined in AirflowNetwork:Distribution:Node objects.
The AirflowNetwork linkage used in following output variables includes surfaces defined in AirflowNetwork:MultiZone:Surface objects, and linkages defined in AirflowNetwork:Distribution:Linkage objects. The surface linkages represent airflows through surface cracks or openings between two zones or between a zone and outdoors. The distribution linkages represent airflows in an air distribution system.
HVAC,Average,AFN Node Temperature [C]
HVAC,Average,AFN Node Humidity Ratio [kgWater/kgDryAir]
HVAC,Average,AFN Node Total Pressure [Pa]
HVAC,Average,AFN Node Wind Pressure [Pa]
HVAC,Average,AFN Node CO2 Concentration [ppm]
HVAC,Average,AFN Node Generic Air Contaminant Concentration [ppm]
HVAC,Average,AFN Linkage Node 1 to Node 2 Mass Flow Rate [kg/s]
HVAC,Average,AFN Linkage Node 2 to Node 1 Mass Flow Rate [kg/s]
HVAC,Average,AFN Linkage Node 1 to Node 2 Volume Flow Rate [m3/s]
HVAC,Average,AFN Linkage Node 2 to Node 1 Volume Flow Rate [m3/s]
HVAC,Average,AFN Linkage Node 1 to Node 2 Pressure Difference [Pa]
HVAC,Average,AFN Surface Venting Window or Door Opening Factor []
HVAC,Average,AFN Surface Venting Window or Door Opening Modulation Multiplier []
HVAC,Average,AFN Surface Venting Inside Setpoint Temperature [C]
HVAC,Average,AFN Surface Venting Availability Status []
HVAC,Average,AFN Zone Infiltration Sensible Heat Gain Rate [W]
HVAC,Sum,AFN Zone Infiltration Sensible Heat Gain Energy [J]
HVAC,Average,AFN Zone Ventilation Sensible Heat Gain Rate [W]
HVAC,Sum,AFN Zone Ventilation Sensible Heat Gain Energy [J]
HVAC,Average,AFN Zone Mixing Sensible Heat Gain Rate [W]
HVAC,Sum,AFN Zone Mixing Sensible Heat Gain Energy [J]
HVAC,Average,AFN Zone Infiltration Sensible Heat Loss Rate [W]
HVAC,Sum,AFN Zone Infiltration Sensible Heat Loss Energy [J]
HVAC,Average,AFN Zone Ventilation Sensible Heat Loss Rate [W]
HVAC,Sum,AFN Zone Ventilation Sensible Heat Loss Energy [J]
HVAC,Average,AFN Zone Mixing Sensible Heat Loss Rate [W]
HVAC,Sum,AFN Zone Mixing Sensible Heat Loss Energy [J]
HVAC,Average,AFN Zone Infiltration Latent Heat Gain Rate [W]
HVAC,Sum,AFN Zone Infiltration Latent Heat Gain Energy [J]
HVAC,Average,AFN Zone Infiltration Latent Heat Loss Rate [W]
HVAC,Sum,AFN Zone Infiltration Latent Heat Loss Energy [J]
HVAC,Average,AFN Zone Ventilation Latent Heat Gain Rate [W]
HVAC,Sum,AFN Zone Ventilation Latent Heat Gain Energy [J]
HVAC,Average,AFN Zone Ventilation Latent Heat Loss Rate [W]
HVAC,Sum,AFN Zone Ventilation Latent Heat Loss Energy [J]
HVAC,Average,AFN Zone Mixing Latent Heat Gain Rate [W]
HVAC,Sum,AFN Zone Mixing Latent Heat Gain Energy [J]
HVAC,Average,AFN Zone Mixing Latent Heat Loss Rate [W]
HVAC,Sum,AFN Zone Mixing Latent Heat Loss Energy [J]
HVAC,Average,AFN Zone Duct Leaked Air Sensible Heat Gain Rate [W]
HVAC,Sum,AFN Zone Duct Leaked Air Sensible Heat Gain Energy [J]
HVAC,Average,AFN Zone Duct Leaked Air Sensible Heat Loss Rate [W]
HVAC,Sum,AFN Zone Duct Leaked Air Sensible Heat Loss Energy [J]
HVAC,Average,AFN Zone Duct Leaked Air Latent Heat Gain Rate [W]
HVAC,Sum,AFN Zone Duct Leaked Air Latent Heat Gain Energy [J]
HVAC,Average,AFN Zone Duct Leaked Air Latent Heat Loss Rate [W]
HVAC,Sum,AFN Zone Duct Leaked Air Latent Heat Loss Energy [J]
HVAC,Average,AFN Zone Duct Conduction Sensible Heat Gain Rate [W]
HVAC,Sum,AFN Zone Duct Conduction Sensible Heat Gain Energy [J]
HVAC,Average,AFN Zone Duct Conduction Sensible Heat Loss Rate [W]
HVAC,Sum,AFN Zone Duct Conduction Sensible Heat Loss Energy [J]
HVAC,Average,AFN Zone Duct Diffusion Latent Heat Gain Rate [W]
HVAC,Sum,AFN Zone Duct Diffusion Latent Heat Gain Energy [J]
HVAC,Average,AFN Zone Duct Diffusion Latent Heat Loss Rate [W]
HVAC,Sum,AFN Zone Duct Diffusion Latent Heat Loss Energy [J]
HVAC,Average,AFN Distribution Sensible Heat Gain Rate [W]
HVAC,Sum,AFN Distribution Sensible Heat Gain Energy [J]
HVAC,Average,AFN Distribution Sensible Heat Loss Rate [W]
HVAC,Sum,AFN Distribution Sensible Heat Loss Energy [J]
HVAC,Average,AFN Distribution Latent Heat Gain Rate [W]
HVAC,Sum,AFN Distribution Latent Heat Gain Energy [J]
HVAC,Average,AFN Distribution Latent Heat Loss Rate [W]
HVAC,Sum,AFN Distribution Latent Heat Loss Energy [J]
HVAC,Sum,AFN Zone Infiltration Volume [m3]
HVAC,Sum,AFN Zone Infiltration Mass [kg]
HVAC,Average,AFN Zone Infiltration Air Change Rate [ach]
HVAC,Sum,AFN Zone Ventilation Volume [m3]
HVAC,Sum,AFN Zone Ventilation Mass [kg]
HVAC,Average,AFN Zone Ventilation Air Change Rate [ach]
HVAC,Sum,AFN Zone Mixing Volume [m3]
HVAC,Sum,AFN Zone Mixing Mass [kg]
HVAC,Average,AFN Zone Exfiltration Heat Transfer Rate [W]
HVAC,Average,AFN Zone Exfiltration Sensible Heat Transfer Rate [W]
HVAC,Average,AFN Zone Exfiltration Latent Heat Transfer Rate [W]
The following output variables are reported only when a Fan:OnOff object is used:
HVAC,Average,AFN Zone Average Pressure [Pa]
HVAC,Average,AFN Zone On Cycle Pressure [Pa]
HVAC,Average,AFN Zone Off Cycle Pressure [Pa]
HVAC,Average,AFN Linkage Node 1 to 2 Average Mass Flow Rate [kg/s]
HVAC,Average,AFN Linkage Node 2 to 1 Average Mass Flow Rate [kg/s]
HVAC,Average,AFN Linkage Node 1 to 2 Average Volume Flow Rate [m3/s]
HVAC,Average,AFN Linkage Node 2 to 1 Average Volume Flow Rate [m3/s]
HVAC,Average,AFN Surface Average Pressure Difference [Pa]
HVAC,Average,AFN Surface On Cycle Pressure Difference [Pa]
HVAC,Average,AFN Surface Off Cycle Pressure Difference [Pa]
The following output variables are reported only when an AirflowNetwork:OccupantVentilationControl object is used:
HVAC,Average,AFN Surface Venting Window or Door Opening Factor at Previous Time Step []
HVAC,Average,AFN Surface Opening Elapsed Time [min]
HVAC,Average,AFN Surface Closing Elapsed Time [min]
HVAC,Average,AFN Surface Opening Status at Previous Time Step []
HVAC,Average,AFN Surface Opening Status []
HVAC,Average,AFN Surface Opening Probability Status []
HVAC,Average,AFN Surface Closing Probability Status []
The following are reported only when an integrated model of RoomAir and AirflowNetwork is used:
HVAC,Average, RoomAirflowNetwork Node Total Pressure [Pa]
HVAC,Average, RoomAirflowNetwork Node Temperature [C]
HVAC,Average, RoomAirflowNetwork Node Humidity Ratio [kgWater/kgDryAir]
AFN Node Temperature [C][LINK]
This is the AirflowNetwork node temperature output in degrees C. When a Fan:OnOff object is used and is scheduled to operate in the cycling fan operation mode, this value for AirflowNetwork:Distribution:Node objects reflects the temperature when the fan is operating (ON).
AFN Node Humidity Ratio [kgWater/kgDryAir][LINK]
This is the AirflowNetwork node humidity ratio output in kgWater/kgDryAir. When a Fan:OnOff object is used and is scheduled to operate in the cycling fan operation mode, this value for AirflowNetwork:Distribution:Node objects reflects the humidity ratio when the fan is operating (ON).
AFN Node Total Pressure [Pa][LINK]
This is the AirflowNetwork node total pressure in Pa with respect to outdoor barometric pressure. The total pressure is the sum of static pressure, dynamic pressure, and elevation impact at the node’s relative height. When a Fan:OnOff object is used and is scheduled to operate in the cycling fan operation mode, the value for AirflowNetwork:Distribution:Node objects reflects the total pressure when the fan is operating (ON). The total pressures for nodes associate with AirflowNetwork:MultiZone:Zone objects are reported in different output variables (below).
AFN Node CO2 Concentration [ ppm][LINK]
This is the AirflowNetwork node carbon dioxide concentration level in parts per million (ppm). When a Fan:OnOff object is used and is scheduled to operate in the cycling fan operation mode, this value for AirflowNetwork:Distribution:Node objects reflects the carbon dioxide when the fan is operating (ON).
AFN Node Generic Air Contaminant Concentration [ppm][LINK]
This is the AirflowNetwork node generic contaminant concentration level in parts per million (ppm). When a Fan:OnOff object is used and is scheduled to operate in the cycling fan operation mode, this value for AirflowNetwork:Distribution:Node objects reflects the carbon dioxide when the fan is operating (ON).
AFN Zone Average Pressure [Pa][LINK]
This is the AirflowNetwork average zone total pressure in Pa with respect to outdoor barometric pressure. This output is only available when a Fan:OnOff object is used in the air distribution system. The average zone pressure is weighted by the system fan part-load ratio using the calculated zone pressures during the fan on and off periods for the system timestep. The system fan part-load ratio is defined as the ratio of the air distribution system mass flow rate (average for the simulation timestep) to the system design mass flow rate.
Average zone pressure = (Zone pressure during on cycle * Part-load ratio) + Zone pressure during off cycle * (1.0 – Part-load ratio)
AFN Zone On Cycle Pressure [Pa][LINK]
This is the AirflowNetwork zone total pressure in Pa with respect to outdoor barometric pressure when the air distribution system fan is operating (ON). This output is only available when a Fan:OnOff object is used in the air distribution system. When the fan part-load ratio is equal to 0.0, this pressure value will be zero because the air distribution system is not simulated when the fan is off for the entire timestep.
AFN Zone Off Cycle Pressure [Pa][LINK]
This is the AirflowNetwork zone total pressure in Pa with respect to outdoor barometric pressure when the air distribution system fan is not operating (OFF). This output is only available when a Fan:OnOff object is used in the air distribution system. Even if the fan part-load ratio is equal to 1.0, the pressure calculated as if the fan were not operating (OFF) is reported.
AFN Node Wind Pressure [Pa][LINK]
This is the AirflowNetwork wind pressure output in Pa. The wind pressure depends on several factors, including wind speed, wind direction, the wind-pressure coefficient (Cp) values for the AirflowNetwork:MultiZone:ExternalNode associated with the heat transfer surface and the site wind conditions.
When Wind Pressure Coefficient Type = “Input” in the AirflowNetwork:SimulationControl object, the output represents external node pressures driven by wind defined in an AirflowNetwork:MultiZone:ExternalNode object. When Wind Pressure Coefficient Type = “SurfaceAverageCalculation” in AirflowNetwork:SimulationControl, the program assumes five external nodes:
FACADE1 Representing north orientation
FACADE2 Representing east orientation
FACADE3 Representing south orientation
FACADE4 Representing west orientation
ROOF Representing horizontal orientation
In this case, the output represents the wind pressures for the five external nodes defined above.
AFN Linkage Node 1 to Node 2 Mass Flow Rate [kg/s][LINK]
This is the AirflowNetwork linkage mass flow rate output in kg/s in the direction from Node 1 to Node 2. It reports surface airflows through a crack or opening, and through linkages defined in an AirflowNetwork:Distribution:Linkage object. The surface linkage is divided into two types of surfaces, exterior surface and interior surface. Node 1 for an exterior surface linkage is a thermal zone and Node 2 is an external node. The value of AFN Linkage Node 1 to Node 2 Mass Flow Rate represents the flow rate from a thermal zone to outdoors. The flow direction through an interior surface crack or opening is defined from a thermal zone defined by a surface’s Zone Name (Node 1) to an adjacent thermal zone defined by a surface’s OutsideFaceEnvironment (Node 2). For an AirflowNetwork:Distribution:Linkage object, the value represents the air mass flow rate flowing from Node 1 to Node 2.
It should be pointed out that in general, each linkage has one directional flow at any given time, either from Node 1 to 2 or from Node 2 to 1. However, there are three components which may have flows in both directions simultaneously: AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening.
When a Fan:OnOff object is used, the air mass flow rates reported for the AirflowNetwork:Distribution:Linkage objects are the values when the fan is operating (ON). It is assumed that the air mass flow rates when the fan is off are zero for the distribution system air linkage objects. The air mass flow rates for the AirflowNetwork:MultiZone:Surface object are reported in different output variables (below).
AFN Linkage Node 2 to Node 1 Mass Flow Rate [kg/s][LINK]
This is the AirflowNetwork linkage mass flow rate output in kg/s in the direction from Node 2 to Node 1. It reports airflows from surfaces through a crack or opening, and from linkages defined in an AirflowNetwork:Distribution:Linkage object. Node 1 and Node 2 for a surface or subsurface are defined in the same manner as AFN Linkage Node 1 to Node 2 Mass Flow Rate.
When a Fan:OnOff object is used, the air mass flow rates reported for the AirflowNetwork:Distribution:Linkage objects are the values when the fan is operating (ON). It is assumed that the air mass flow rates when the fan is off are zero for the distribution system air linkage objects. The air mass flow rates for the AirflowNetwork:MultiZone:Surface object are reported in different output variables (below).
AFN Linkage Node 1 to 2 Average Mass Flow Rate [kg/s][LINK]
This is the AirflowNetwork linkage average mass flow rate in kg/s in the direction from Node 1 to Node 2 defined in the AirflowNetwork:MultiZone:Surface objects. This output is only available when a Fan:OnOff object is used in the air distribution system. The average mass flow rate is weighted by the system fan part-load ratio using the calculated air mass flow rates during the fan on and off periods for the system timestep. The system fan part-load ratio is defined as the ratio of the air distribution system mass flow rate (average for the simulation timestep) to the system design mass flow rate.
Average surface mass flow rate = (Surface mass flow rate during on cycle * Part-load ratio) + Surface mass flow rate during off cycle * (1.0 – Part-load ratio)
AFN Linkage Node 2 to 1 Average Mass Flow Rate [kg/s][LINK]
This is the AirflowNetwork linkage average mass flow rate in kg/s in the direction from Node 2 to Node 1 defined in the AirflowNetwork:MultiZone:Surface objects. This output is only available when a Fan:OnOff object is used in the air distribution system. The average mass flow rate is weighted by the system fan part-load ratio using the calculated air mass flow rates during the fan on and off periods for the system timestep. The system fan part-load ratio is defined as the ratio of the air distribution system mass flow rate (average for the simulation timestep) to the system design mass flow rate.
AFN Linkage Node 1 to Node 2 Volume Flow Rate [m\(^{3}\)/s][LINK]
This is the AirflowNetwork linkage volume flow rate output in m\(^{3}\)/s in the direction from the Node 1 to Node 2. It is defined in the same manner as AFN Linkage Node 1 to Node 2 Mass Flow Rate.
When a Fan:OnOff object is used, the air volume flow rates reported for the AirflowNetwork:Distribution:Linkage objects are the values when the fan is operating (ON). It is assumed that the air volume flow rates when the fan is off are zero for the distribution system air linkage objects. The air volume flow rates for the AirflowNetwork:MultiZone:Surface object are reported in different output variables (below).
AFN Linkage Node 2 to Node 1 Volume Flow Rate [m\(^{3}\)/s][LINK]
This is the AirflowNetwork linkage volume flow rate output in m\(^{3}\)/s in the direction from Node 2 to Node 1. It is defined in the same manner as AFN Linkage Node 2 to Node 1 Mass Flow Rate.
When a Fan:OnOff object is used, the air volume flow rates reported for the AirflowNetwork:Distribution:Linkage objects are the values when the fan is operating (ON). It is assumed that the air volume flow rates when the fan is off are zero for the distribution system air linkage objects. The air volume flow rates for the AirflowNetwork:MultiZone:Surface object are reported in different output variables (below).
AFN Linkage Node 1 to 2 Average Volume Flow Rate [m\(^{3}\)/s][LINK]
This is the AirflowNetwork linkage average volume flow rate in m\(^{3}\)/s in the direction from Node 1 to Node 2 defined in the AirflowNetwork:MultiZone:Surface objects. This output is only available when a Fan:OnOff object is used. The average volume flow rate is weighted by the system fan part-load ratio using the calculated air volume flow rates during the fan on and off periods for the system timestep.
Average surface volume flow rate = (Surface volume flow rate during on cycle * Part-load ratio) + Surface volume flow rate during off cycle * (1.0 – Part-load ratio)
AFN Linkage Node 2 to 1 Average Volume Flow Rate [m\(^{3}\)/s][LINK]
This is the AirflowNetwork linkage average volume flow rate in m\(^{3}\)/s in the direction from Node 2 to Node 1 defined in the AirflowNetwork:MultiZone:Surface objects. This output is only available when a Fan:OnOff object is used. The average volume flow rate is weighted by the system fan part-load ratio using the calculated air volume flow rates during the fan on and off periods for the system timestep.
AFN Linkage Node 1 to Node 2 Pressure Difference [Pa][LINK]
This is the pressure difference across a linkage in Pa. The linkage includes both objects: AirflowNetwork:MultiZone:Surface and AirflowNetwork: Distribution:Linkage.
When a Fan:OnOff object is used, the pressure differences reported for the AirflowNetwork:Distribution:Linkage objects are the values calculated when the fan is operating (ON). It is assumed that the pressure differences when the fan is off are zero for the distribution system air linkage objects. The pressure differences defined in the AirflowNetwork:MultiZone:Surface are reported in different output variables (below).
AFN Surface Average Pressure Difference [Pa][LINK]
This is the average pressure difference across a linkage in Pa for the AirflowNetwork:MultiZone:Surface objects only when a Fan:OnOff object is used. The average pressure difference is weighted by the system fan part-load ratio using the calculated pressure differences during the fan on and off periods for the system timestep. The system fan part-load ratio is defined as the ratio of the air distribution system mass flow rate (average for the simulation timestep) to the system design mass flow rate.
Surface Average Pressure Difference = (Surface Average Pressure Difference during on cycle * Part-load ratio) + Surface Average Pressure Difference during off cycle * (1.0 - Part-load ratio)
AFN Surface On Cycle Pressure Difference [Pa][LINK]
This is the pressure difference across a linkage in Pa for the AirflowNetwork:MultiZone:Surface objects only when the air distribution system fan is operating (ON). This output is only available when a Fan:OnOff object is used. When the fan part-load ratio is equal to 0.0, this pressure difference value will be zero because the air distribution system is not simulated when the fan is off for the entire timestep.
AFN Surface Off Cycle Pressure Difference [Pa][LINK]
This is the pressure difference across a linkage in Pa for the AirflowNetwork:MultiZone:Surface objects only when the air distribution system fan is not operating (OFF). This output is only available when a Fan:OnOff object is used. Even if the fan part-load ratio is equal to 1.0, the pressure difference calculated as if the fan were not operating (OFF) is reported.
AFN Surface Venting Window or Door Opening Factor [][LINK]
The current time-step value of the venting opening factor for a particular window or door. When the window or door is venting, this is the input value of the opening factor (see AirflowNetwork:MultiZone:Surface, Window/Door Opening Factor) times the multiplier for venting modulation (see description of next output variable, “Opening Factor Multiplier for AirflowNetwork Venting Modulation”). For example, if the input Window/Door opening factor is 0.5 and the modulation multiplier is 0.7, then the value of this output variable will be 0.5x0.7 = 0.35.
AFN Surface Venting Window or Door Opening Modulation Multiplier [][LINK]
This is the multiplier on a window or door opening factor when venting modulation is in effect. See “Modulation of Openings” under AirflowNetwork:MultiZone:Zone for a description of how the multiplier is determined.
When modulation is in effect the value of the multiplier is between 0.0 and 1.0. When modulation does not apply the value of the multiplier may be –1.0. When modulation applies but the surface is not venting, the value is –1.0. This is summarized in the following table. In this table, “Zone” means a thermal zone for which AirflowNetwork:MultiZone:Zone has been specified. See object AirflowNetwork: MultiZone:Zone for definition of “Ventilation Control Mode.”
AFN Surface Venting Inside Setpoint Temperature [C][LINK]
The time-step value of the venting setpoint temperature for the zone to which the surface belongs. This setpoint is determined from the Vent Temperature Schedule input (ref: AirflowNetwork:MultiZone:Zone).
AFN Surface Venting Availability Status [][LINK]
A value of 1.0 means venting through the surface can occur if venting control conditions are satisfied. A value of 0.0 means venting through the surface cannot occur under any circumstances. This value is determined by the Venting Availability Schedule input (ref: AirflowNetwork:MultiZone:Zone or AirflowNetwork:MultiZone:Surface).
AFN Zone Infiltration Sensible Heat Gain Rate [W][LINK]
The average convective sensible heat gain rate, in Watts, to the zone air corresponding to the Zone Infiltration flows from both AirflowNetwork:MultiZone:Surface:Crack and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea only averaged over the reporting period. This value is calculated for each timestep when the outdoor dry-bulb temperature is higher than the zone temperature; otherwise, the sensible gain rate is set to 0.
When a Fan:OnOff object is used, this reported value is weighted by the system run time fraction using the calculated infiltration sensible gain rate during the system on and off cycles for the reporting period:
Infiltration Sensible Gain Rate = (Infiltration Sensible Gain Rate during on cycle * Run time fraction) + Infiltration Sensible Gain Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Infiltration Sensible Heat Gain Energy [J][LINK]
The average convective sensible heat gain, in Joules, to the zone air corresponding to the Zone Infiltration flows from both AirflowNetwork:MultiZone:Surface:Crack and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea only averaged over the reporting period. This value is calculated for each timestep when the outdoor dry-bulb temperature is higher than the zone temperature; otherwise, the sensible gain rate is set to 0.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated infiltration sensible gain during the system on and off cycles for the reporting period:
Infiltration Sensible Gain = (Infiltration Sensible Gain during on cycle * Run time fraction) + Infiltration Sensible Gain during off cycle * (1.0 – Run time fraction)
AFN Zone Infiltration Sensible Heat Loss Rate [W][LINK]
The average convective sensible heat loss rate, in Watts, to the zone air corresponding to the Zone Infiltration flows from both AirflowNetwork:MultiZone:Surface:Crack and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea only averaged over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated infiltration sensible loss rate during the system on and off cycles for the reporting period:
Infiltration Sensible Loss Rate = (Infiltration Sensible Loss Rate during on cycle * Run time fraction) + Infiltration Sensible Loss Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Infiltration Sensible Heat Loss Energy [J][LINK]
The average convective sensible heat loss, in Joules, to the zone air corresponding to the Zone Infiltration flows from both AirflowNetwork:MultiZone:Surface:Crack and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea only averaged over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated infiltration sensible loss rate during the system on and off cycles for the reporting period:
Infiltration Sensible Loss = (Infiltration Sensible Loss during on cycle * Run time fraction) + Infiltration Sensible Loss during off cycle * (1.0 – Run time fraction)
AFN Zone Infiltration Latent Heat Gain Rate [W][LINK]
The average convective latent heat gain rate, in Watts, to the zone air corresponding to the Zone Infiltration flows from both AirflowNetwork:MultiZone:Surface:Crack and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea only averaged over the reporting period, when the outdoor humidity ratio is higher than the zone air humidity ratio.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated infiltration latent gain rate during the system on and off cycles for the reporting period:
Infiltration Latent Gain Rate = (Infiltration Latent Gain Rate during on cycle * Run time fraction) + Infiltration Latent Gain Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Infiltration Latent Heat Gain Energy [J][LINK]
The total convective latent heat gain, in Joules, to the zone air corresponding to the Zone Infiltration flows from both AirflowNetwork:MultiZone:Surface:Crack and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea only summed over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated infiltration latent gain during the system on and off cycles for the reporting period:
Infiltration Latent Gain = (Infiltration Latent Gain during on cycle * Run time fraction) + Infiltration Latent Gain during off cycle * (1.0 – Run time fraction)
AFN Zone Infiltration Latent Heat Loss Rate [W][LINK]
The average convective latent heat loss rate, in Watts, to the zone air corresponding to the Zone Infiltration flows from both AirflowNetwork:MultiZone:Surface:Crack and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea only averaged over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated infiltration latent loss rate during the system on and off cycles for the reporting period:
Infiltration Latent Loss Rate = (Infiltration Latent Gain Loss Rate during on cycle * Run time fraction) + Infiltration Latent Loss Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Infiltration Latent Heat Loss Energy [J][LINK]
The total convective latent heat loss, in Joules, to the zone air corresponding to the Zone Infiltration flows from both AirflowNetwork:MultiZone:Surface:Crack and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea only summed over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated infiltration latent loss during the system on and off cycles for the reporting period:
Infiltration Latent Loss = (Infiltration Latent Gain Loss during on cycle * Run time fraction) + Infiltration Latent Loss during off cycle * (1.0 – Run time fraction)
AFN Zone Ventilation Sensible Heat Gain Rate [W][LINK]
The average convective sensible heat gain rate, in Watts, to the zone air corresponding to the Zone Ventilation flows from AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening only averaged over the reporting period. This value is calculated for each timestep when the outdoor dry-bulb temperature is higher than the zone temperature; otherwise, the sensible gain rate is set to 0.
When a Fan:OnOff object is used, this reported value is weighted by the system run time fraction using the calculated ventilation sensible gain rate during the system on and off cycles for the reporting period:
Ventilation Sensible Gain Rate = (Ventilation Sensible Gain Rate during on cycle * Run time fraction) + Ventilation Sensible Gain Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Ventilation Sensible Heat Gain Energy [J][LINK]
The average convective sensible heat gain, in Joules, to the zone air corresponding to the Zone Ventilation flows from AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening only averaged over the reporting period. This value is calculated for each timestep when the outdoor dry-bulb temperature is higher than the zone temperature; otherwise, the sensible gain rate is set to 0.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated ventilation sensible gain during the system on and off cycles for the reporting period:
Ventilation Sensible Gain = (Ventilation Sensible Gain during on cycle * Run time fraction) + Ventilation Sensible Gain during off cycle * (1.0 – Run time fraction)
AFN Zone Ventilation Sensible Heat Loss Rate [W][LINK]
The average convective sensible heat loss rate, in Watts, to the zone air corresponding to the Zone Ventilation flows from AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening only averaged over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated ventilation sensible loss rate during the system on and off cycles for the reporting period:
Ventilation Sensible Loss Rate = (Ventilation Sensible Loss Rate during on cycle * Run time fraction) + Ventilation Sensible Loss Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Ventilation Sensible Heat Loss Energy [J][LINK]
The average convective sensible heat loss, in Joules, to the zone air corresponding to the Zone Ventilation flows from AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening only averaged over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated Ventilation sensible loss rate during the system on and off cycles for the reporting period:
Ventilation Sensible Loss = (Ventilation Sensible Loss during on cycle * Run time fraction) + Ventilation Sensible Loss during off cycle * (1.0 – Run time fraction)
AFN Zone Ventilation Latent Heat Gain Rate [W][LINK]
The average convective latent heat gain rate, in Watts, to the zone air corresponding to the Zone Ventilation flows from AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening only averaged over the reporting period, when the outdoor humidity ratio is higher than the zone air humidity ratio.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated Ventilation latent gain rate during the system on and off cycles for the reporting period:
Ventilation Latent Gain Rate = (Ventilation Latent Gain Rate during on cycle * Run time fraction) + Ventilation Latent Gain Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Ventilation Latent Heat Gain Energy [J][LINK]
The total convective latent heat gain, in Joules, to the zone air corresponding to the Zone Ventilation flows from AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening only summed over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated ventilation latent gain during the system on and off cycles for the reporting period:
Ventilation Latent Gain = (Ventilation Latent Gain during on cycle * Run time fraction) + Ventilation Latent Gain during off cycle * (1.0 – Run time fraction)
AFN Zone Ventilation Latent Heat Loss Rate [W][LINK]
The average convective latent heat loss rate, in Watts, to the zone air corresponding to the Zone Ventilation flows from AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening only averaged over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated Ventilation latent loss rate during the system on and off cycles for the reporting period:
Ventilation Latent Loss Rate = (Ventilation Latent Gain Loss Rate during on cycle * Run time fraction) + Ventilation Latent Loss Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Ventilation Latent Heat Loss Energy [J][LINK]
The total convective latent heat loss, in Joules, to the zone air corresponding to the Zone Ventilation flows from both AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening only summed over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated Ventilation latent loss during the system on and off cycles for the reporting period:
Ventilation Latent Loss = (Ventilation Latent Gain Loss during on cycle * Run time fraction) + Ventilation Latent Loss during off cycle * (1.0 – Run time fraction)
AFN Zone Mixing Sensible Heat Gain Rate [W][LINK]
The average convective sensible heat gain rate, in Watts, to the zone air corresponding to the Zone Mixing Volume averaged over the reporting period. The mixing-volume is defined as incoming volume flow from other adjacent zones where the air temperature is higher than the temperature in this zone. For example, there are two zones (Zone 2 and Zone 3) adjacent to this zone (Zone 1). Zone 1 receives airflows from both Zone 2 and Zone 3. The air temperature is 21°C in Zone 1. The air temperatures are 20°C in Zone 2 and 22°C in Zone 3. The sensible gain rate only includes heat gain from Zone 3 with respect to Zone 1. The energy received from Zone 2 is considered as a sensible loss, instead of a gain, because the air temperature in Zone 2 is lower than in Zone 1.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated mixing sensible gain rate during the system on and off cycles for the reporting period:
Mixing Sensible Gain Rate = (Mixing Sensible Gain Rate during on cycle * Run time fraction) + Mixing Sensible Gain Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Mixing Sensible Heat Loss Rate [W][LINK]
The average convective sensible heat loss rate, in Watts, to the zone air corresponding to the Zone Mixing Volume averaged over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated mixing sensible loss rate during the on and off cycles for the reporting period:
Mixing Sensible Loss Rate = (Mixing Sensible Loss Rate during on cycle * Run time fraction) + Mixing Sensible Loss Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Mixing Sensible Heat Gain Energy [J][LINK]
The total convective sensible heat gain, in Joules, to the zone air corresponding to the Zone Mixing Volume summed over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated mixing sensible gain during the on and off cycles for the reporting period:
Mixing Sensible Gain = (Mixing Sensible Gain during on cycle * Run time fraction) + Mixing Sensible Gain during off cycle * (1.0 – Run time fraction)
AFN Zone Mixing Sensible Heat Loss Energy [J][LINK]
The total convective sensible heat loss, in Joules, to the zone air corresponding to the Zone Mixing Volume summed over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated mixing sensible loss during the on and off cycles for the reporting period:
Mixing Sensible Loss = (Mixing Sensible Loss during on cycle * Run time fraction) + Mixing Sensible Loss during off cycle * (1.0 – Run time fraction)
AFN Zone Mixing Latent Heat Gain Rate [W][LINK]
The average convective latent heat gain rate, in Watts, to the zone air corresponding to the Zone Mixing Volume averaged over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated mixing latent gain rate during the on and off cycles for the reporting period:
Mixing Latent Gain Rate = (Mixing Latent Gain Rate during on cycle * Run time fraction) + Mixing Latent Gain Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Mixing Latent Heat Gain Energy [J][LINK]
The total convective latent heat gain, in Joules, to the zone air corresponding to the Zone Mixing Volume summed over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated mixing latent gain during the on and off cycles for the reporting period:
Mixing Latent Gain = (Mixing Latent Gain during on cycle * Run time fraction) + Mixing Latent Gain during off cycle * (1.0 – Run time fraction)
AFN Zone Mixing Latent Heat Loss Rate [W][LINK]
The average convective latent heat loss rate, in Watts, to the zone air corresponding to the Zone Mixing Volume averaged over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated mixing latent loss rate during the on and off cycles for the reporting period:
Mixing Latent Loss Rate = (Mixing Latent Loss Rate during on cycle * Run time fraction) + Mixing Latent Loss Rate during off cycle * (1.0 – Run time fraction)
AFN Zone Mixing Latent Heat Loss Energy [J][LINK]
The total convective latent heat loss, in Joules, to the zone air corresponding to the Zone Mixing Volume summed over the reporting period.
When a Fan:OnOff object is used, the reported value is weighted by the system run time fraction using the calculated mixing latent loss during the on and off cycles for the reporting period:
Mixing Latent Loss = (Mixing Latent Loss during on cycle * Run time fraction) + Mixing Latent Loss during off cycle * (1.0 – Run time fraction)
AFN Zone Mixing CO2 Mass Flow Rate [kg/s][LINK]
This is a sum of mass flow rates from adjacent zones multiplied by the corresponding zone carbon dioxide concentration level to the receiving zone. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the mixing mass flow rate calculated during the fan on and off periods for the simulation timestep.
AFN Zone Mixing Generic Air Contaminant Mass Flow Rate [kg/s][LINK]
This is a sum of mass flow rates from adjacent zones multiplied by the corresponding zone generic contaminant concentration level to the receiving zone. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the mixing mass flow rate calculated during the fan on and off periods for the simulation timestep.
AFN Zone Duct Leaked Air Sensible Heat Gain Rate [W][LINK]
This is the average sensible heat gain rate, in Watts, to a specific zone due to supply air leaks from the forced air distribution system. This value is averaged over the reporting period. A sensible heat gain occurs when duct air is warmer than zone air. It should be pointed out that when multiple supply air leaks are present in a single zone, the output value is the summation of all the supply air leak gains in this zone. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Leaked Air Sensible Heat Gain Energy [J][LINK]
This is the total sensible heat gain, in Joules, to a specific zone due to supply air leaks summed over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Leaked Air Sensible Heat Loss Rate [W][LINK]
This is the average sensible heat loss rate, in Watts, to a specific zone due to supply air leaks from the forced air distribution system. This value is averaged over the reporting period. A sensible heat loss occurs when duct air is cooler than zone air. It should be pointed out that when multiple supply air leaks are present in this zone, the output value is the summation of all the supply air leak losses in this zone. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Leaked Air Sensible Heat Loss Energy [J][LINK]
This is the total sensible heat loss, in Joules, to a specific zone due to supply air leaks summed over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Leaked Air Latent Heat Gain Rate [W][LINK]
This is the average latent heat gain rate, in Watts, to a specific zone due to supply air leaks from the forced air distribution system for the reported time period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Leaked Air Latent Heat Gain Energy [J][LINK]
This is the total latent heat gain, in Joules, to a specific zone due to supply air leaks summed over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Leaked Air Latent Heat Loss Rate [W][LINK]
This is the average latent heat loss rate, in Watts, to a specific zone due to supply air leaks from the forced air distribution system for the reported time period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Leaked Air Latent Heat Loss Energy [J][LINK]
This is the total latent heat loss, in Joules, to a specific zone due to supply air leaks summed over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Conduction Sensible Heat Gain Rate [W][LINK]
This is the average sensible heat gain rate, in Watts, of duct conduction to a specific zone where the ducts are located. This value is averaged over the reporting period. A sensible heat gain occurs when duct air is warmer than the zone air. It should be pointed out that when ducts are located in different zones, the total duct conduction loss should be the summation of the duct conduction losses in these zones. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Conduction Sensible Heat Gain Energy [J][LINK]
This is the total sensible heat gain, in Joules, to a specific zone due to duct conduction summed over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Conduction Sensible Heat Loss Rate [W][LINK]
This is the average sensible heat loss rate, in Watts, of duct conduction to a specific zone where the ducts are located. This value is averaged over the reporting period. A sensible heat loss occurs when duct air is cooler than the zone air. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Conduction Sensible Heat Loss Energy [J][LINK]
This is the total sensible heat loss, in Joules, to a specific zone due to duct conduction summed over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Diffusion Latent Heat Gain Rate [W][LINK]
This is the average latent heat gain rate, in Watts, of vapor diffusion through the walls of the air distribution system to a specific zone where the ducts are located. This value is averaged over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Diffusion Latent Heat Gain Energy [J][LINK]
This is the total latent heat gain, in Joules, to a specific zone due to duct vapor diffusion summed over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Diffusion Latent Heat Loss Rate [W][LINK]
This is the average latent heat loss rate, in Watts, of duct vapor diffusion to a specific zone where the ducts are located. This value is averaged over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Duct Diffusion Latent Heat Loss Energy [J][LINK]
This is the total latent heat loss, in Joules, to a specific zone due to duct vapor diffusion summed over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Distribution Sensible Heat Gain Rate [W][LINK]
This is the average total sensible heat gain rate, in Watts, in a specific zone caused by the forced air distribution system. The total sensible gain rate is the sum of duct leakage sensible gain rate and duct conduction sensible gain rate. This value is averaged over the reporting period. The multizone airflow sensible gain rate is excluded in this output variable. The output of multizone airflow sensible gain is reported in the previously-described output variables AFN Zone Infiltration Sensible Heat Gain Rate and AFN Zone Mixing Sensible Heat Gain Rate. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Distribution Sensible Heat Gain Energy [J][LINK]
This is the total sensible heat gain, in Joules, in a specific zone caused by the forced air distribution system. The total sensible gain is the sum of duct leakage sensible gain and duct conduction sensible gain. This value is summed over the reporting period. The multizone airflow sensible gain is excluded in this output variable. The output of multizone airflow sensible gain is reported in the previously-described output variables AFN Zone Infiltration Sensible Heat Gain Energy and AFN Zone Mixing Sensible Heat Gain Energy. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Distribution Sensible Heat Loss Rate [W][LINK]
This is the average total sensible heat loss rate, in Watts, in a specific zone caused by the forced air distribution system. The total sensible loss rate is the sum of duct leakage sensible loss rate and duct conduction sensible loss rate. This value is averaged over the reporting period. The multizone airflow sensible loss rate is excluded in this output variable. The output of multizone airflow sensible loss rate is reported in the previously-described output variables AFN Zone Infiltration Sensible Heat Loss Rate and AFN Zone Mixing Sensible Heat Loss Rate. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Distribution Sensible Heat Loss Energy [J][LINK]
This is the total sensible heat loss, in Joules, in a specific zone caused by the forced air distribution system. The total sensible loss is the sum of duct leakage sensible loss and duct conduction sensible loss. This value is summed over the reporting period. The multizone airflow sensible loss is excluded in this output variable. The output of multizone airflow sensible loss is reported in the previously-described output variables AFN Zone Infiltration Sensible Heat Loss Energy and AFN Zone Mixing Sensible Heat Loss Energy. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Distribution Latent Heat Gain Rate [W][LINK]
This is the average total latent heat gain rate, in Watts, in a specific zone caused by the forced air distribution system. The total latent gain rate is the sum of duct leakage latent gain rate and duct conduction latent gain rate. This value is averaged over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Distribution Latent Heat Gain Energy [J][LINK]
This is the total latent heat gain, in Joules, in a specific zone caused by the forced air distribution system. The total latent gain is the sum of duct leakage latent gain and duct diffusion latent gain. This value is summed over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Distribution Latent Heat Loss Rate [W][LINK]
This is the average total latent heat loss rate, in Watts, in a specific zone caused by the forced air distribution system. The total latent loss rate is a sum of duct leakage latent loss rate and duct diffusion latent loss rate. This value is averaged over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Distribution Latent Heat Loss Energy [J][LINK]
This is the total latent heat loss, in Joules, in a specific zone caused by the forced air distribution system. The total latent loss is the sum of duct leakage latent loss and duct diffusion latent loss. This value is summed over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
NOTE: The following output variables should not be confused with similar output variables for the infiltration, mixing, and cross mixing objects (Ref. Infiltration Output, Mixing Output, or Cross Mixing Output). The output variables described below refer to infiltration, mixing, and cross-mixing when an Airflow Network Simulation is performed. The following output variables are always used to describe infiltration, mixing, and cross mixing when the AirflowNetwork Control field in the AirflowNetwork:SimulationControl object is set to “MultiZoneWithoutDistribution” or “MultiZoneWithDistribution”. In this case the output variables for the infiltration, mixing, and cross mixing objects will always be 0.
In contrast, the following output variables are only used to describe infiltration, mixing, and cross mixing when the AirflowNetwork Control field in the AirflowNetwork:SimulationControl object is set to “MultiZoneAirflowWithDistributionOnlyDuringFanOperation” and the fan is operating. When the fan is not operating, the output variables for the infiltration, mixing, and cross mixing objects are used.
In the case where the AirflowNetwork Control field in the AirflowNetwork:SimulationControl object is set to “NoMultiZoneOrDistribution”, the following output variables are not used and the output variables for the infiltration, mixing, and cross mixing objects are used instead.
AFN Zone Infiltration Sensible Heat Gain Energy [J][LINK]
The total convective sensible heat gain, in Joules, to the zone air corresponding to the Zone Infiltration Volume summed over the reporting period. This value is calculated for each timestep when the outdoor dry-bulb temperature is higher than the zone temperature, otherwise the sensible gain is set to 0. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Infiltration Sensible Heat Loss Energy [J][LINK]
The total convective sensible heat loss, in Joules to the zone air corresponding to the Zone Infiltration Volume summed over the reporting period. When a Fan:OnOff object is used, the reported value is for the system on cycle.
AFN Zone Infiltration Volume [m3][LINK]
The volume of outdoor air flow into the zone from window/door cracks in the exterior surfaces of the zone from both AirflowNetwork:MultiZone:Surface:Crack and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea only averaged over the reporting period (i.e., the sum of infiltration and crack flows from the exterior into the zone). The zone air density is used to calculate the zone infiltration volume based on the mass flow rate. Note that AirflowNetwork Zone Infiltration Volume will be zero if all of the flows through the zone’s exterior surfaces are out of the zone. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the infiltration volume calculated during the fan on and off periods for the simulation timestep.
AFN Zone Infiltration Mass [kg][LINK]
The mass of air corresponding to the AirflowNetwork Zone Infiltration Volume from both AirflowNetwork:MultiZone:Surface:Crack and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea only averaged over the reporting period. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the infiltration mass calculated during the fan on and off periods for the simulation timestep.
AFN Zone Infiltration Air Change Rate [ach][LINK]
The number of air changes per hour produced by outdoor air flow into the zone from window/door cracks in the exterior surfaces of the zone from both AirflowNetwork:MultiZone:Surface:Crack and AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea only averaged over the reporting period (i.e. the sum of infiltration and crack flows from the exterior into the zone). The target zone air density is used to calculate the zone infiltration air change rate based on the mass flow rate Note that, like Zone Infiltration Volume, Zone Infiltration Air Change Rate will be zero if all flows through the zone’s exterior surfaces are out of the zone. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the infiltration air change rate calculated during the fan on and off periods for the simulation timestep.
AFN Zone Ventilation Volume [m3][LINK]
The volume of outdoor air flow into the zone from window/door openings in the exterior surfaces of the zone from AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening only averaged over the reporting period (i.e., the sum of ventilation and opening flows from the exterior into the zone). The zone air density is used to calculate the zone ventilation volume based on the mass flow rate. Note that AirflowNetwork Zone Ventilation Volume will be zero if all of the flows through the zone’s exterior surfaces are out of the zone. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the ventilation volume calculated during the fan on and off periods for the simulation timestep.
AFN Zone Ventilation Mass [kg][LINK]
The mass of air corresponding to the AirflowNetwork Zone Ventilation Volume from AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening only averaged over the reporting period. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the ventilation mass calculated during the fan on and off periods for the simulation timestep.
AFN Zone Ventilation Air Change Rate [ach][LINK]
The number of air changes per hour produced by outdoor air flow into the zone from window/door openings in the exterior surfaces of the zone from AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, and AirflowNetwork:MultiZone:Component:HorizontalOpening only averaged over the reporting period (i.e. the sum of ventilation and opening flows from the exterior into the zone). The target zone air density is used to calculate the zone ventilation air change rate based on the mass flow rate Note that, like Zone Ventilation Volume, Zone Ventilation Air Change Rate will be zero if all flows through the zone’s exterior surfaces are out of the zone. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the ventilation air change rate calculated during the fan on and off periods for the simulation timestep.
AFN Zone Mixing Volume [m3][LINK]
This is a measure of interzone air flow for each thermal zone. It is the volume of air flow into the zone from adjacent zones through window/door openings and cracks in the interior heat transfer surfaces of the zone. The target zone air density is used to calculate the zone mixing volume based on the mass flow rate. This variable does not include flows that are from the zone to adjacent zones. Note that Zone Mixing Volume will be zero if all flows through the zone’s interior surfaces are out of the zone. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the mixing volume calculated during the fan on and off periods for the simulation timestep.
AFN Zone Mixing Mass [kg][LINK]
The mass of air corresponding to the AFN Zone Mixing Volume. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the mixing mass calculated during the fan on and off periods for the simulation timestep.
AFN Zone Mixing Mass Flow Rate [kg/s][LINK]
This is a sum of mass flow rates from adjacent zones to the receiving zone. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the mixing mass flow rate calculated during the fan on and off periods for the simulation timestep.
AFN Zone Outdoor Air CO2 Mass Flow Rate [kg/s][LINK]
This is a sum of mass flow rates from outdoors multiplied by the outdoor carbon dioxide concentration level to the receiving zone. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the outdoor mass flow rate calculated during the fan on and off periods for the simulation timestep.
AFN Zone Outdoor Air Generic Air Contaminant Mass Flow Rate [kg/s][LINK]
This is a sum of mass flow rates from outdoors multiplied by the outdoor generic air contaminant concentration level to the receiving zone. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the outdoor mass flow rate calculated during the fan on and off periods for the simulation timestep
AFN Zone Outdoor Air Mass Flow Rate [kg/s][LINK]
This is a sum of mass flow rates from outdoors to the receiving zone. When a Fan:OnOff object is used, the reported value is weighted by the system fan part-load ratio using the outdoor mass flow rate calculated during the fan on and off periods for the simulation timestep.
AFN Zone Total CO2 Mass Flow Rate [kg/s][LINK]
This is a sum of mass flow rates from adjacent zones or outdoors multiplied by the carbon dioxide concentration differences between the corresponding zone and the receiving zone.
AFN Zone Total Generic Air Contaminant Mass Flow Rate [kg/s][LINK]
This is a sum of mass flow rates from adjacent zones or outdoors multiplied by the generic contaminant concentration differences between the corresponding zone and the receiving zone.
The following output variables are reported only when an AirflowNetwork:OccupantVentilationControl object is used:
AFN Surface Venting Window or Door Opening Factor at Previous Time Step [][LINK]
The value of the venting opening factor for a particular window or door at the previous time step. When the window or door is venting, this is the input value of the opening factor (see AirflowNetwork:MultiZone:Surface, Window/Door Opening Factor) times the multiplier for venting modulation (see description of next output variable, “Opening Factor Multiplier for AirflowNetwork Venting Modulation”). For example, if the input Window/Door opening factor is 0.5 and the modulation multiplier is 0.7, then the value of this output variable will be 0.5*0.7 = 0.35.
AFN Surface Opening Elapsed Time [min][LINK]
This output is the opening elapsed time in the units of minutes since the window opened.
AFN Surface Closing Elapsed Time [min][LINK]
This output is the opening elapsed time in the units of minutes since the windows closed.
AFN Surface Opening Status at Previous Time Step [][LINK]
This is the window or door opening factor control status at the previous time step using an AirflowNetwork:OccupantVentilationControl object, which can have three integer values: 0, 1, and 2. A 0 value indicates no occupant ventilation control. The opening factor is determined by the Ventilation Control Mode field. A value of 1 indicates that a window or door is allowed to open. The value of 1 is determined when the opening elapsed time is less than the minimum opening time. A value of 2 denotes that a window or door is forced to close. The value of 2 is determined when the closing elapsed time is less than the minimum closing time.
AFN Surface Opening Status [][LINK]
This is the window or door opening factor control status at the current time step using an AirflowNetwork:OccupantVentilationControl object, which can have three integer values: 0, 1, and 2. A 0 value indicates no occupant ventilation control. The opening factor is determined by the Ventilation Control Mode field. A value of 1 indicates that a window or door is allowed to open. The value of 1 is determined when the opening elapsed time is less than the minimum opening time. A value of 2 denotes that a window or door is forced to close. The value of 2 is determined when the closing elapsed time is less than the minimum closing time.
AFN Surface Opening Probability Status [][LINK]
This is the opening probability status at the current time step using an AirflowNetwork:OccupantVentilationControl object, which can have three integer values: 0, 1, and 2. A 0 value indicates no opening probability control action. A value of 1 indicates that a window or door is forced to open when the opening status is 0. A value of 2 denotes that the status at the previous time step will be kept.
AFN Surface Closing Probability Status [][LINK]
This is the closing probability status at the current time step using an AirflowNetwork:OccupantVentilationControl object, which can have three integer values: 0, 1, and 2. A 0 value indicates no closing probability control action. A value of 1 indicates that a window or door is forced to close when the opening status is 0. A value of 2 denotes that the status at the previous time step will be kept.
RoomAirflowNetwork Node Temperature [C][LINK]
This is the RoomAirflowNetwork node temperature output in degrees C.
RoomAirflowNetwork Node Humidity Ratio [kgWater/kgDryAir][LINK]
This is the RoomAirflowNetwork node humidity ratio output in kgWater/kgDryAir.
RoomAirflowNetwork Node Total Pressure [Pa][LINK]
This is the RoomAirflowNetwork node total pressure in Pa with respect to outdoor barometric pressure. The total pressure is the sum of static pressure, dynamic pressure, and elevation impact at the node’s relative height.
AFN Zone Exfiltration Heat Transfer Rate [W][LINK]
AFN Zone Exfiltration Sensible Heat Transfer Rate [W][LINK]
AFN Zone Exfiltration Latent Heat Transfer Rate [W][LINK]
These output variables represent the heat emitted to ambient from exfiltration in Watts. The exfiltration rate is calculated by solving a mass flow balance on the zone airflow network including infiltration, ventilation, outdoor air mixing, zone-to-zone mixing, and all of the zone inlet, exhaust, and return nodes. The latent parts are determined by taking the difference between the total and the sensible rate. Positive values indicate the zone injects heat to the environment, while negative values indicate the building extracts heat from the environment.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.