Summaries at End of Simulation[LINK]
Some classes of warnings produce more information at the end of the simulation. For example,
Loads Initialization did not Converge (CheckWarmupConvergence) after 25 warmup days.
Environment = SAN_FRANCISCO ANN CLG 1% CONDNS DB = >MWB
Max Temp Comparison = 9.15E-002 vs Temperature Convergence Tolerance = 4.00E-003 - Fail Convergence
Min Temp Comparison = 1.75E-003 vs Temperature Convergence Tolerance = 4.00E-003 - Pass Convergence
Max Cool Load Comparison = 2.9010E-002 vs Loads Convergence Tolerance = 4.00E-002 - Pass Convergence
Then, at the end of the simulation, you will see:
******** The following error categories occurred. Consider correcting or noting.
******** Loads Initialization did not Converge
******** ..1) very high thermal mass such as very thick concrete (solution: increase max number of warmup
******** .. days in the BUILDING object);
******** ..2) moderate mass and inadequate space conditioning such that the building keeps getting warmer
******** .. and warmer on successive days (solution: add HVAC, check building thermal properties,
******** .. check if infiltration is included, make sure HVAC properly controlled);
******** ..3) a soil layer modeled below the concrete slab - (solution remove this layer and read about
******** .. ground temperatures in the Auxiliary Programs document).
******** ..4) unreasonable (too small) limits in the BUILDING object for temperature (.4 default) or
******** .. loads tolerances (.04 default)
Summaries at End of Simulation[LINK]
Some classes of warnings produce more information at the end of the simulation. For example,
Documentation content copyright © 1996-2021 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.