Complex
Fenestration Daylighting Calculations[LINK]
The complex fenestration systems (CFS) daylighting
calculation method results in the same Daylighting Factor
style output as the it is described in Daylighting
Calculations chapter.
Transmitted solar radiation reaches the daylighting sensor
in two different ways. The first is an indirect path when
solar radiation is reflected from surfaces and uniformly
distributed into the space. The second is a direct path when
the sensor is directly illuminated by the fenestration
system.
For the indirect path, the method performs a one-bounce
calculation to determine the diffuse illumination for the
zone. For a certain sky condition, including the sun position,
the method will calculate which surfaces are illuminated from
each of the BSDF directions, taking into account the
reflectance of the surfaces. This indirect illumination is
calculated from both direct sunlight hitting a window with or
without a shading device and diffuse illumination calculated
from diffuse light coming into the zone from the sky or the
ground. This transmitted light strikes the zone interior
surfaces and creates a diffuse component. The CFS daylighting
method determines the contribution of each sky patch to the
illumination of the zone surfaces based on the BSDF
transmittances and then luminance is calculated based on the
surface reflection.
For the direct path, the window is subdivided using
existing subdivision procedures. From the center of each
subdivided element, the angle is calculated to the reference
point. The illuminance is calculated based on the BSDF data
for the outgoing direction that corresponds to that angle and
the incident illumination from sky, ground and sun.
Internal
Average Reflected Illuminance From Window[LINK]
To calculate internal average reflected illumiance from the
window it is necessary to calculate transmitted flux at the
window. Observing an infinitesimal window element, illuminance
can originate from the sky or sun, and in both cases the ray
can reach the window directly or after reflecting from the
ground. Based on this, the calculation of luminance at the
window is divided into three parts:
Sky-related illuminance and luminous flux
Sun-related illuminance and luminous flux, excluding
entering beam
Sun-related illuminance and luminous flux, due to entering
beam
where total illuminance will be calculated as a
superposition of these three parts.
For any case, illuminace at a window element can be
calculated by using the following general approach:
where
is the illuminance
at a window element,
represents the function of horizontal luminance from the
exterior element in the direction
,
represents the angle at which the ray hits the surface of the
window and
represents the
exterior element azimuth and altitude relative to the window
(see Figure 62).
Figure 62: Exterior Luminance Element
This will produce luminous flux at the interior side of the
window:
where
is given by equation
,
is the window transmittance
at the incoming angle
and
is infinitesimal window
element surface area.
Integrating luminous flux given by equation over entire
window area will give luminous flux on the interior side of
the window.
To calculate the interan average reflected illumiance from
the window, a simillar approch will be used as described in
the chapter “Internally-Reflected Component of Interior
Daylight Illuminance”, which gives the flux balance
equation:
where
represents first
reflected flux which in the case of non-CFS is calculated by
using the split-flux method. In the case of CFS, first the
reflected flux can be calculated more precisely by using light
patches area. Since each CFS is described by a BSDF, it is
possible to calculate the light patches for each outgoing
direction (see Figure 63).
Figure 63: Complex Fenestration System Light Patches
Considering the total flux passing through the window at
the outgoing direction “k”, the first reflect flux (
) can be calculated as:
where
is the total flux
entering the zone at the BSDF outgoing direction “k” and is
calculated by integrating equation over the entire window area
for a given outgoing direction “k”, N is the number of
interior surfaces hit by the BSDF outgoing direction “k” (see
Figure 63),
is the surface
(patch) area which the window from the BSDF outgoing direction
“k” makes at surface “a” and
is the visible reflectance from surface “a”.
Summing all the outgoing directions will result in total
first reflected flux:
Luminance from
Exterior Elements[LINK]
The case of CFS luminance from exterior elements can be
calculated by using BSDF incoming directions defined for a
given CFS. Applying equation for a certain incoming BSDF
direction will give:
This equation can be translated in the BSDF coordinate
system where instead of standard azimuth and altitude angles,
the equation will be transformed into the BSDF coordinate
system. In that case, equation becomes:
where
represents the
lambda value for the incoming direction “i”.
Luminous
Flux and Direct Illuminance at Interior Side of the
Window[LINK]
In the case of CFS it is of interest to calculate fluxes
for each outgoing BSDF direction. For a given amount of
illuminance at an incoming direction “i”, flux into direction
“o” will be calculated as:
where
is the direct-direct
transmittance for given incoming and outgoing directions (“i”
and “o”).
Figure 64: Complex Fenestration System Flux Transition -
Single Incoming Direction to Single Outgoing Direction
Total flux from the window at the outgoing direction “o”
can be calculated by summing over all the incoming
directions:
where
is the number of
BSDF incident directions.
Flux transmitted in the outgoing direction “o”, calculated
by equation , can be used for any given distribution of an
exterior luminous element. Knowing the intensity of the
luminous flux, the direct illuminance at a certain point is
calculated as:
where
is the direct
illuminance at the BSDF outgoing direction “o”,
is the spatial angle of the
element viewed from a certain reference point and
is the altitude of the window
element viewed from the reference point.
Handling Exterior
Obstructions[LINK]
Exterior obstructions are handled for two different cases.
The first case is to handle obstructions between the luminous
element (sky/ground/sun) and the CFS window element. In that
case, the direct illuminance at the window element is modified
for the product of all the obstruction transmittances between
the luminous and window elements, and equation is modified
as:
where
is the number of
exterior obstructions and
is
the visible transmittance of obstruction “p”.
The second case is to handle all obstructions between the
luminous elements and the ground element. The luminance from
the ground element is calculated as:
where
is the horizontal
illuminance and
is the ground
reflectance. Horizontal illuminance is obtained by the
integration over sky/sun elements and it is of interest to
examine if all elements are visible from a certain ground
point. The integration examines if the ray between the sky and
the ground element is hitting an obstruction. It does not take
into account whether or not the obstruction is transparent, it
simply counts the number of hits. The sky obstruction
multiplier is calculated as:
and in case the incoming element is from the ground, the
illuminance at the window element (equation ) will be
additionally modified from the sky obstruction multiplier:
Complex Fenestration Daylighting Calculations[LINK]
The complex fenestration systems (CFS) daylighting calculation method results in the same Daylighting Factor style output as the it is described in Daylighting Calculations chapter.
Transmitted solar radiation reaches the daylighting sensor in two different ways. The first is an indirect path when solar radiation is reflected from surfaces and uniformly distributed into the space. The second is a direct path when the sensor is directly illuminated by the fenestration system.
For the indirect path, the method performs a one-bounce calculation to determine the diffuse illumination for the zone. For a certain sky condition, including the sun position, the method will calculate which surfaces are illuminated from each of the BSDF directions, taking into account the reflectance of the surfaces. This indirect illumination is calculated from both direct sunlight hitting a window with or without a shading device and diffuse illumination calculated from diffuse light coming into the zone from the sky or the ground. This transmitted light strikes the zone interior surfaces and creates a diffuse component. The CFS daylighting method determines the contribution of each sky patch to the illumination of the zone surfaces based on the BSDF transmittances and then luminance is calculated based on the surface reflection.
For the direct path, the window is subdivided using existing subdivision procedures. From the center of each subdivided element, the angle is calculated to the reference point. The illuminance is calculated based on the BSDF data for the outgoing direction that corresponds to that angle and the incident illumination from sky, ground and sun.
Internal Average Reflected Illuminance From Window[LINK]
To calculate internal average reflected illumiance from the window it is necessary to calculate transmitted flux at the window. Observing an infinitesimal window element, illuminance can originate from the sky or sun, and in both cases the ray can reach the window directly or after reflecting from the ground. Based on this, the calculation of luminance at the window is divided into three parts:
Sky-related illuminance and luminous flux
Sun-related illuminance and luminous flux, excluding entering beam
Sun-related illuminance and luminous flux, due to entering beam
where total illuminance will be calculated as a superposition of these three parts.
For any case, illuminace at a window element can be calculated by using the following general approach:
where
is the illuminance
at a window element,
represents the function of horizontal luminance from the
exterior element in the direction
,
represents the angle at which the ray hits the surface of the
window and
represents the
exterior element azimuth and altitude relative to the window
(see Figure 62).
Figure 62: Exterior Luminance Element
This will produce luminous flux at the interior side of the window:
where
is given by equation
,
is the window transmittance
at the incoming angle
and
is infinitesimal window
element surface area.
Integrating luminous flux given by equation over entire window area will give luminous flux on the interior side of the window.
To calculate the interan average reflected illumiance from the window, a simillar approch will be used as described in the chapter “Internally-Reflected Component of Interior Daylight Illuminance”, which gives the flux balance equation:
where
represents first
reflected flux which in the case of non-CFS is calculated by
using the split-flux method. In the case of CFS, first the
reflected flux can be calculated more precisely by using light
patches area. Since each CFS is described by a BSDF, it is
possible to calculate the light patches for each outgoing
direction (see Figure 63).
Figure 63: Complex Fenestration System Light Patches
Considering the total flux passing through the window at the outgoing direction “k”, the first reflect flux (
) can be calculated as:
where
is the total flux
entering the zone at the BSDF outgoing direction “k” and is
calculated by integrating equation over the entire window area
for a given outgoing direction “k”, N is the number of
interior surfaces hit by the BSDF outgoing direction “k” (see
Figure 63),
is the surface
(patch) area which the window from the BSDF outgoing direction
“k” makes at surface “a” and
is the visible reflectance from surface “a”.
Summing all the outgoing directions will result in total first reflected flux:
Luminance from Exterior Elements[LINK]
The case of CFS luminance from exterior elements can be calculated by using BSDF incoming directions defined for a given CFS. Applying equation for a certain incoming BSDF direction will give:
This equation can be translated in the BSDF coordinate system where instead of standard azimuth and altitude angles, the equation will be transformed into the BSDF coordinate system. In that case, equation becomes:
where
represents the
lambda value for the incoming direction “i”.
Luminous Flux and Direct Illuminance at Interior Side of the Window[LINK]
In the case of CFS it is of interest to calculate fluxes for each outgoing BSDF direction. For a given amount of illuminance at an incoming direction “i”, flux into direction “o” will be calculated as:
where
is the direct-direct
transmittance for given incoming and outgoing directions (“i”
and “o”).
Figure 64: Complex Fenestration System Flux Transition - Single Incoming Direction to Single Outgoing Direction
Total flux from the window at the outgoing direction “o” can be calculated by summing over all the incoming directions:
where
is the number of
BSDF incident directions.
Flux transmitted in the outgoing direction “o”, calculated by equation , can be used for any given distribution of an exterior luminous element. Knowing the intensity of the luminous flux, the direct illuminance at a certain point is calculated as:
where
is the direct
illuminance at the BSDF outgoing direction “o”,
is the spatial angle of the
element viewed from a certain reference point and
is the altitude of the window
element viewed from the reference point.
Handling Exterior Obstructions[LINK]
Exterior obstructions are handled for two different cases. The first case is to handle obstructions between the luminous element (sky/ground/sun) and the CFS window element. In that case, the direct illuminance at the window element is modified for the product of all the obstruction transmittances between the luminous and window elements, and equation is modified as:
where
is the number of
exterior obstructions and
is
the visible transmittance of obstruction “p”.
The second case is to handle all obstructions between the luminous elements and the ground element. The luminance from the ground element is calculated as:
where
is the horizontal
illuminance and
is the ground
reflectance. Horizontal illuminance is obtained by the
integration over sky/sun elements and it is of interest to
examine if all elements are visible from a certain ground
point. The integration examines if the ray between the sky and
the ground element is hitting an obstruction. It does not take
into account whether or not the obstruction is transparent, it
simply counts the number of hits. The sky obstruction
multiplier is calculated as:
and in case the incoming element is from the ground, the illuminance at the window element (equation ) will be additionally modified from the sky obstruction multiplier: