Using EnergyPlus for Compliance — EnergyPlus 24.2

<< Prev | Table of Contents | Object Index | Next >>

Tabular Summary Reports[LINK]

Several predefined reports are available from the Output Table:Predefined object including the following.

  • Annual Building Utility Performance Summary

  • Input Verification and Results Summary

  • Demand End Use Components Summary

  • Source Energy End Use Components Summary

  • Climatic Data Summary

  • Equipment Summary

  • Envelope Summary

  • Surface Shadowing Summary

  • Shading Summary

  • Lighting Summary

  • HVAC Sizing Summary

  • System Summary

  • Component Sizing Summary

  • Outside Air Summary

  • Object Count Summary

In addition, specifying “All Summary” will enable all the reports in this category (more than are shown here).

Annual Building Utility Performance Summary[LINK]

First and foremost, the Annual Building Utility Performance Summary gives a good overview of the energy use by category:

Report: AnnualBuildingUtilityPerformanceSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

Values gathered over 8760.00 hours

Site and Source Energy

p1.5inp1.5inp1.5inp1.5in   & Total Energy [GJ] & Energy Per Total Building Area [MJ/m2] & Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy & 180.73 & 194.92 & 194.92
Net Site Energy & 180.73 & 194.92 & 194.92
Total Source Energy & 1141.64 & 1231.28 & 1231.28
Net Source Energy & 1141.64 & 1231.28 & 1231.28

Source to Site Energy Conversion Factors

  Source= > Site Conversion Factor
Electricity 0.293
Natural Gas 0.010
District Cooling 0.098
District Heating 0.033
Steam 0.250
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050

Building Area

  Area [m2]
Total Building Area 927.20
Net Conditioned Building Area 927.20
Unconditioned Building Area 0.00

End Uses

p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in   & Electricity [GJ] & Natural Gas [GJ] & Other Fuel [GJ] & District Cooling [GJ] & District Heating [GJ] & Water [m3]
Heating & 0.00 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00
Cooling & 16.56 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 81.24 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 47.70 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 6.59 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 0.48 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
  &   &   &   &   &   &  
Total End Uses & 152.57 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00

Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

p0.75inp0.75inp0.75inp0.75inp0.75inp0.75inp0.75inp0.75in   & Subcategory & Electricity [GJ] & Natural Gas [GJ] & Other Fuel [GJ] & District Cooling [GJ] & District Heating [GJ] & Water [m3]
Heating & Boiler & 0.00 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00
  & Boiler Parasitic & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Cooling & General & 16.56 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & GeneralLights & 81.24 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & General & 47.70 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & General & 6.59 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & General & 0.48 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00

Normalized Metrics

Utility Use Per Conditioned Floor Area

p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in   & Electricity Intensity [MJ/m2] & Natural Gas Intensity [MJ/m2] & Other Fuel Intensity [MJ/m2] & District Cooling Intensity [MJ/m2] & District Heating Intensity [MJ/m2] & Water Intensity [m3/m2]
Lighting & 87.62 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
HVAC & 25.49 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Other & 51.44 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Total & 164.55 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00

Utility Use Per Total Floor Area

p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in   & Electricity Intensity [MJ/m2] & Natural Gas Intensity [MJ/m2] & Other Fuel Intensity [MJ/m2] & District Cooling Intensity [MJ/m2] & District Heating Intensity [MJ/m2] & Water Intensity [m3/m2]
Lighting & 87.62 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
HVAC & 25.49 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Other & 51.44 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Total & 164.55 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00

Electric Loads Satisfied

p2.9inp1.5inp1.59in   & Electricity [GJ] & Percent Electricity [%]
Fuel-Fired Power Generation & 0.00 & 0.00
High Temperature Geothermal* & 0.00 & 0.00
Photovoltaic Power & 0.00 & 0.00
Wind Power* & 0.00 & 0.00
Net Decrease in On-Site Storage & 0.00 & 0.00
Total On-Site Electric Sources & 0.00 & 0.00
  &   &  
Electricity Coming From Utility & 152.57 & 100.00
Surplus Electricity Going To Utility & 0.00 & 0.00
Net Electricity From Utility & 152.57 & 100.00
  &   &  
Total On-Site and Utility Electric Sources & 152.57 & 100.00
Total Electricity End Uses & 152.57 & 100.00

On-Site Thermal Sources

  Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  

Water Source Summary

p3.0inp1.5inp1.5in   & Water [m3] & Percent Water [%]
Rainwater Collection & 0.00 & -
Condensate Collection & 0.00 & -
Groundwater Well & 0.00 & -
Total On Site Water Sources & 0.00 & -
- & - & -
Initial Storage & 0.00 & -
Final Storage & 0.00 & -
Change in Storage & 0.00 & -
- & - & -
Water Supplied by Utility & 0.00 & -
- & - & -
Total On Site, Change in Storage, and Utility Water Sources & 0.00 & -
Total Water End Uses & 0.00 & -

Comfort and Setpoint Not Met Summary

p4.5inp1.5in   & Facility [Hours]
Time Set Point Not Met During Occupied Heating & 0.00
Time Set Point Not Met During Occupied Cooling & 213.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 & 72.50

Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Input Verification Summary[LINK]

The input verification summary gives a good overview of the facility being simulated:

Report: InputVerificationandResultsSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

General

p2.25inp3.74in   & Value
Program Version and Build & EnergyPlus 4.0.0.017, 9/17/2009 5:30 PM
Weather & Climate Zone 6 CA USA WYEC2-C-00006 WMO#=722970
Latitude [deg] & 33.90
Longitude [deg] & -118.5
Elevation [m] & 30.00
Time Zone & -8.0
North Axis Angle [deg] & 30.00
Rotation for Appendix G [deg] & 0.00
Hours Simulated [hrs] & 8760.00

ENVELOPE

Window-Wall Ratio

p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in   & Total & North (315 to 45 deg) & East (45 to 135 deg) & South (135 to 225 deg) & West (225 to 315 deg)
Gross Wall Area [m2] & 274.20 & 91.50 & 45.60 & 91.50 & 45.60
Window Opening Area [m2] & 60.90 & 20.85 & 9.12 & 21.81 & 9.12
Window-Wall Ratio [%] & 22.21 & 22.79 & 20.00 & 23.84 & 20.00

Skylight-Roof Ratio

  Total
Gross Roof Area [m2] 463.60
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00

PERFORMANCE

Zone Summary

p0.7inp0.4inp0.5inp0.5inp0.4inp0.5inp0.5inp0.5inp0.5inp0.5in   & Area [m2] & Conditioned (Y/N) & Volume [m3] & Multipliers & Gross Wall Area [m2] & Window Glass Area [m2] & Lighting [W/m2] & People [m2] per person & Plug and Process [W/m2]
PLENUM-1 & 463.60 & Yes & 283.20 & 1.00 & 54.84 & 0.00 & 0.0000 &   & 0.0000
SPACE1-1 & 99.16 & Yes & 239.25 & 1.00 & 73.20 & 21.81 & 15.9742 & 9.01 & 10.6495
SPACE2-1 & 42.73 & Yes & 103.31 & 1.00 & 36.48 & 9.12 & 16.0056 & 8.55 & 10.6704
SPACE3-1 & 96.48 & Yes & 239.25 & 1.00 & 73.20 & 20.85 & 16.4179 & 8.77 & 10.9453
SPACE4-1 & 42.73 & Yes & 103.31 & 1.00 & 36.48 & 9.12 & 16.0056 & 8.55 & 10.6704
SPACE5-1 & 182.49 & Yes & 447.68 & 1.00 & 0.00 & 0.00 & 16.2420 & 9.12 & 10.8280
Total & 927.20 &   & 1416.00 &   & 274.20 & 60.90 & 8.0889 & 17.83 & 5.3926
Conditioned Total & 927.20 &   & 1416.00 &   & 274.20 & 60.90 & 8.0889 & 17.83 & 5.3926
Unconditioned Total & 0.00 &   & 0.00 &   & 0.00 & 0.00 &   &   &  

Source Energy End Use Components Summary[LINK]

The source energy end use components summary gives a good overview of the source energy consumption broken down by end uses for the facility being simulated:

Report: SourceEnergyEndUseComponentsSummary

For: Entire Facility

Timestamp: 2011-10-07 20:53:43

Values gathered over 8760.00 hours

Source Energy End Use Components Summary

p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [GJ] & Source Natural Gas [GJ] & Source Other Fuel [GJ] & Source District Cooling [GJ] & Source District Heating [GJ]
Heating & 0.00 & 140.03 & 0.00 & 0.00 & 0.00
Cooling & 167.65 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 569.39 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 325.49 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 55.72 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 7.57 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1125.82 & 140.03 & 0.00 & 0.00 & 0.00

Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [MJ/m2] & Source Natural Gas [MJ/m2] & Source Other Fuel [MJ/m2] & Source District Cooling [MJ/m2] & Source District Heating [MJ/m2]
Heating & 0.00 & 151.02 & 0.00 & 0.00 & 0.00
Cooling & 180.82 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 614.09 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 351.05 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 60.10 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 8.16 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1214.22 & 151.02 & 0.00 & 0.00 & 0.00

Source Energy End Use Components Per Total Floor Area

p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [MJ/m2] & Source Natural Gas [MJ/m2] & Source Other Fuel [MJ/m2] & Source District Cooling [MJ/m2] & Source District Heating [MJ/m2]
Heating & 0.00 & 151.02 & 0.00 & 0.00 & 0.00
Cooling & 180.82 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 614.09 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 351.05 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 60.10 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 8.16 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1214.22 & 151.02 & 0.00 & 0.00 & 0.00

Other Summary Reports[LINK]

The Climatic Data Summary, Envelope Summary and Equipment Summary reports might be quite important to some reporting or presentation.

Report: ClimaticDataSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

SizingPeriod:DesignDay

p1.2inp0.7inp0.7inp0.7inp0.7inp0.7inp0.7in   & Maximum Dry Bulb [C] & Daily Temperature Range [C] & Humidity Value & Humidity Type & Wind Speed [m/s] & Wind Direction
LOS_ANGELES_CA_USA HEATING 99% CONDITIONS & 7.40 & 0.00 & 7.40 & 0 & 2.80 & 70.00
LOS_ANGELES_CA_USA COOLING 1% CONDITIONS DB= > MWB & 27.00 & 6.10 & 17.60 & 0 & 4.40 & 250.00

Weather Statistics File

p2.15inp3.84in   & Value
Reference & CZ06RV2
Site:Location & Climate Zone 6 CA USA
Latitude & N 33° 54’
Longitude & W 118° 30’
Time Zone & GMT -8.0 Hours
Elevation & 30m above sea level
Standard Pressure at Elevation & 100965Pa
Data Source & WYEC2-C-00006
WMO Station & 722970
Design Conditions & Climate Design Data 2005 ASHRAE Handbook
Heating Design Temperature 99.6% (C) & 4.9
Heating Design Temperature 99% (C) & 6.2
Cooling Design Temperature 0.4% (C) & 33.1
Cooling Design Temperature 1% (C) & 30.9
Cooling Design Temperature 2% (C) & 29.2
Maximum Dry Bulb Temperature (C) & 31.7°
Maximum Dry Bulb Occurs on & Sep 24
Minimum Dry Bulb Temperature (C) & 3.5°
Minimum Dry Bulb Occurs on & Jan 8
Maximum Dew Point Temperature (C) & 20.9
Maximum Dew Point Occurs on & Jun 20
Minimum Dew Point Temperature (C) & -21.7
Minimum Dew Point Occurs on & Dec 27
Heating Degree-Days (base 10°C) & 2
Cooling Degree-Days (base 18°C) & 216
Köppen Classification & Csb
Köppen Description & Mediterranean climate (dry warm summer, mild winter, lat. 30-45°N)
Köppen Recommendation &  
ASHRAE Climate Zone & 3C
ASHRAE Description & Warm-Marine

Report: EnvelopeSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

Opaque Exterior

p0.66inp0.66inp0.6inp0.6inp0.6inp0.6inp0.6inp0.6inp0.6in   & Construction & Reflectance & U-Factor with Film [W/m2-K] & U-Factor no Film [W/m2-K] & Gross Area [m2] & Azimuth [deg] & Tilt [deg] & Cardinal Direction
WALL-1PF & WALL-1 & 0.22 & 0.384 & 0.408 & 18.30 & 210.00 & 90.00 & S
WALL-1PR & WALL-1 & 0.22 & 0.384 & 0.408 & 9.12 & 120.00 & 90.00 & E
WALL-1PB & WALL-1 & 0.22 & 0.384 & 0.408 & 18.30 & 30.00 & 90.00 & N
WALL-1PL & WALL-1 & 0.22 & 0.384 & 0.408 & 9.12 & 300.00 & 90.00 & W
TOP-1 & ROOF-1 & 0.35 & 0.268 & 0.282 & 463.60 & 210.00 & 0.00 &  
FRONT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 73.20 & 210.00 & 90.00 & S
F1-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 99.16 & 30.00 & 180.00 &  
RIGHT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 36.48 & 120.00 & 90.00 & E
F2-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 42.73 & 300.00 & 180.00 &  
BACK-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 73.20 & 30.00 & 90.00 & N
F3-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 96.48 & 74.22 & 180.00 &  
LEFT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 36.48 & 300.00 & 90.00 & W
F4-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 42.73 & 120.00 & 180.00 &  
F5-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 182.49 & 30.00 & 180.00 &  

Fenestration

p0.6inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5in   & Construction & Area of One Opening [m2] & Area of Openings [m2] & U-Factor [W/m2-K] & SHGC & Visible Transmittance & Shade Control & Parent Surface & Azimuth [deg] & Cardinal Direction
WF-1 & DBL CLR 3MM/13MM AIR & 16.56 & 16.56 & 2.720 & 0.764 & 0.812 & No & FRONT-1 & 210.00 & S
DF-1 & SGL GREY 3MM & 5.25 & 5.25 & 5.894 & 0.716 & 0.611 & No & FRONT-1 & 210.00 & S
WR-1 & DBL CLR 3MM/13MM AIR & 9.12 & 9.12 & 2.720 & 0.764 & 0.812 & No & RIGHT-1 & 120.00 & E
WB-1 & DBL CLR 3MM/13MM AIR & 16.44 & 16.44 & 2.720 & 0.764 & 0.812 & No & BACK-1 & 30.00 & N
DB-1 & SGL GREY 3MM & 4.41 & 4.41 & 5.894 & 0.716 & 0.611 & No & BACK-1 & 30.00 & N
WL-1 & DBL CLR 3MM/13MM AIR & 9.12 & 9.12 & 2.720 & 0.764 & 0.812 & No & LEFT-1 & 300.00 & W
Total or Average &   &   & 60.90 & 3.22 & 0.756 & 0.780 &   &   &   &  
North Total or Average &   &   & 20.85 & 3.39 & 0.754 & 0.769 &   &   &   &  
Non-North Total or Average &   &   & 40.05 & 3.14 & 0.757 & 0.785 &   &   &   &  

: *ShadingSummary ** March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WF-1 DF-1 WR-1 WB-1 DB-1 WL-1 0.00 0.75 1.00 0.00 0.00 0.00 0.00 0.13 1.00 0.00 0.00 0.00 0.26 0.59 0.00 0.00 0.00 1.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.35 0.00 0.00 0.00 1.00 0.00 0.92 1.00 0.00 0.00 0.00 0.30 0.62 1.00 0.00 0.00 0.00 0.74 0.94 0.00 0.00 0.00 1.00
indow]( ntrol ../input-output -reference/group -thermal-zone-d escription-geo metry.html#wind ow)
  Name Type S haded Constructi on Control Glare Control

None          

Report: LightingSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

Interior Lighting

  Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Average Hours/Week [hr] Return Air Fraction Conditioned (Y/N)
SPACE1-1 LIGHTS 1 SPACE1-1 15.9742 99.16 1584.00 GeneralLights LIGHTS-1 0.00 0.2000 Y
SPACE2-1 LIGHTS 1 SPACE2-1 16.0056 42.73 684.00 GeneralLights LIGHTS-1 0.00 0.2000 Y
SPACE3-1 LIGHTS 1 SPACE3-1 16.4179 96.48 1584.00 GeneralLights LIGHTS-1 0.00 0.2000 Y
SPACE4-1 LIGHTS 1 SPACE4-1 16.0056 42.73 684.00 GeneralLights LIGHTS-1 0.00 0.2000 Y
SPACE5-1 LIGHTS 1 SPACE5-1 16.2420 182.49 2964.00 GeneralLights LIGHTS-1 0.00 0.2000 Y
Interior Lighting Total   16.1777 463.60 7500.00          

Daylighting

  Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            

Exterior Lighting

  Total Watts Astronomical Clock/Schedule Schedule Name Average Annual Hours/Week
Exterior Lighting Total 0.00      

Report: EquipmentSummary

For: Entire Facility

Timestamp: 2009-09-17 17:30:22

Central Plant

  Type Nominal Capacity [W] Nominal Efficiency [W/W]
CENTRAL CHILLER Chiller:Electric 25311.64 3.20
CENTRAL BOILER Boiler:HotWater 56191.29 0.80

Cooling Coils

  Type Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W]
MAIN COOLING COIL 1 Coil:Cooling:Water 28159.12 19476.53 8682.60 0.69 -

Heating Coils

  Type Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPACE1-1 ZONE COIL Coil:Heating:Water 10384.85 -
SPACE2-1 ZONE COIL Coil:Heating:Water 8470.48 -
SPACE3-1 ZONE COIL Coil:Heating:Water 10477.88 -
SPACE4-1 ZONE COIL Coil:Heating:Water 11334.29 -
SPACE5-1 ZONE COIL Coil:Heating:Water 11391.33 -
MAIN HEATING COIL 1 Coil:Heating:Water 4061.83 -

Fans

  Type Total Efficiency [W/W] Delta Pressure [pa] Max Flow Rate [m3/s] Rated Power [W] Motor Heat In Air Fraction End Use
SUPPLY FAN 1 Fan:VariableVolume 0.70 600.00 1.28 1099.23 1.00 General

Pumps

  Type Control Head [pa] Power [W] Motor Efficiency [W/W]
HW CIRC PUMP Pump:VariableSpeed INTERMITTENT 179352.00 312.23 0.90
CW CIRC PUMP Pump:VariableSpeed INTERMITTENT 179352.00 231.95 0.90

Service Water Heating

  Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
None