Group – Fluid Properties[LINK]
The Fluid Property routines in EnergyPlus have been
designed for ease of use and to allow users to add refrigerant
and glycol data to the input file without having to make any
changes to the program code. Fluid properties are calculated
by interpolating the tabulated data in the input file. The
main input requirement is that in order to add a new fluid, a
user must enter a full set of data. The user may determine the
interval between data points according to the desired accuracy
and range required. Data for a number of common fluids are
available in the required format in a reference dataset so
that the user may append this data to their input file. In
addition, data for Water, Ethylene Glycol (in various
concentrations from 0 to 90%), and Propylene Glycol (in
various concentrations from 0 to 90%) are available as default
values within EnergyPlus.
Each fluid is categorized as either a ‘Refrigerant’ or
‘Glycol’. Refrigerant data is further categorized as either
saturated or superheated. Saturated refrigerant data is
indexed, in the input data, according to pressure and
temperature i.e. the specific heat, density, enthalpy in the
input data are given for a given combination of pressure and
temperature. Saturated refrigerant data is indexed according
to pressure and quality. In the case of saturated pressure
data only a temperature index is used. Glycol data is indexed
in the input data according to temperature and concentration.
The input data structure for each property is essentially
two-dimensional (a matrix). However, since all fluid loops are
assumed to be of constant concentration, EnergyPlus internally
will interpolate from input data to data for the actual
concentration being used in a particular loop. This reduces
internally to a one-dimensional array of data for various
properties where temperature is the only variable. This saves
time since it reduces all interpolations for glycols to a
single dimension.
In most cases there will be combinations of index variable
(e.g. some combination of pressure and temperature) at which
either no data is available, or the property data is
invalid/irrelevant. For example, in the superheated
refrigerant data, some combinations of temperature and
pressure may correspond to a state in the saturated rather
than superheated region. Similarly, in the case of glycols
there may be some combinations of temperature and
concentration that would correspond to the frozen state. In
these cases, and where data is just not available, a zero
should be present in the data at these points to indicate an
invalid condition. EnergyPlus uses the presence of zeros to
detect invalid conditions and give warning messages.
FluidProperties:Name[LINK]
The names of each fluid for which property data is given in
the user input have to be specified in FluidProperties:Name
data objects. If data is to be included for a given fluid,
either a refrigerant or a glycol, then its name must be
included in the FluidProperties:Name
objects.
Field: Fluid Name[LINK]
Each fluid name is a unique identifier that will be used in
conjunction with the data statements described later in this
section. The fluid name is either referred to by a component
(in the case of a Refrigerant) or by another input line (in
the case of a Glycol). This list is simply a list of user
defined fluids present in the input data file.
Field: Fluid Type[LINK]
Each fluid name must be identified by type - either
Refrigerant or Glycol. This
designation determines what type of data EnergyPlus expects
for the fluid name. If the fluid name is defined as a
Refrigerant, the user must supply valid data for pressure,
enthalpy, specific heat, and density in the saturated region
and enthalpy and density in the superheated region. If the
fluid name is defined as a Glycol, the user must supply valid
data for specific heat, conductivity, viscosity, and density
at various concentrations (percentage of non-water liquid) and
temperatures.
An example of these statements in an input data file
is:
FluidProperties:Name,
R11, Refrigerant;
FluidProperties:Name,
R12, Refrigerant;
FluidProperties:Name,
R22, Refrigerant;
FluidProperties:Name,
NH3, Refrigerant;
FluidProperties:Name,
Steam, Refrigerant;
FluidProperties:Name,
SaltBrine, Glycol;
FluidProperties:Name,
NewGlycol, Glycol;
FluidProperties:GlycolConcentration[LINK]
This input syntax is used to specify fluids that will be
used with HVAC loops such as plant and condenser loops. It
allows the user to define a mixture of water and some other
substance and the particular concentration being used. The
fluid name will be referred to by the loops or components and
thus used to identify which value is valid for a particular
fluid at a particular temperature. A series of three inputs is
requires for each fluid concentration definition.
Each glycol concentration name is a unique identifier that
will be used to define a particular combination of water and
some other substance (usually another fluid). Other input
(such as loop definitions) will refer to this name, linking
the other input to the proper fluid definition.
Field: Glycol Type[LINK]
This field refers to the substance that is being mixed with
water to create the glycol. The user may either select from
the two default fluids (EthyleneGlycol or
PropyleneGlycol) or specify
UserDefinedGlycolType and use a name in the
subsequent field for fluids that have been entered elsewhere
in the input file. It should be noted that users must enter a
complete definition of new glycols—including values for
conductivity, specific heat, density, and viscosity at various
concentrations and temperatures—in order for them to be used
in conjunction with a user defined glycol type.
Field: User Defined
Glycol Name[LINK]
This field is the name used elsewhere in a FluidProperties:Name
object for defining your own glycol properties. This field is
left blank unless you enter
UserDefinedGlycolType in the previous
field.
Field: Glycol
Concentration[LINK]
This field allows the user to specify the actual
concentration of glycol being used for this particular fluid.
A concentration of 0.0 refers to pure water. A concentration
of 1.0 would denote 100% of the fluid referenced in the Glycol
Name input discussed above. Users should enter this value as a
decimal fraction since EnergyPlus will limit the range of
valid input values to between 0.0 and 1.0.
An example of this statement in an input data file is:
FluidProperties:GlycolConcentration,
EthGly25Percent, EthyleneGlycol, ,0.25;
FluidProperties:GlycolConcentration,
ProGly40Percent, PropyleneGlycol, ,0.40;
FluidProperties:GlycolConcentration,
HalfAndHalf, UserDefinedGlycolType, NewBrine, 0.5;
FluidProperties:Temperatures[LINK]
It is assumed that all fluid properties vary with
temperature. A common set of temperatures is required for each
set of fluid property data. Fluid property data supplied by
the user must correspondingly be given at these temperatures.
Since in most cases, refrigerant data can be specified at a
common set of temperatures, a single set of
‘FluidProperties:Temperatures’ can be referenced by a number
of sets of property data. This provides a more compact input
structure and avoids listing the temperatures multiple times.
In the case of glycol data the same set of temperatures have
to be used for each set of data at a given concentration.
Units for the temperatures are degrees Celsius.
This field is simply an unique identifier name that is used
to cross reference the list of temperatures with a specific
list of fluid property data. A single temperature list can be
used for more than one thermal property or fluid. For example,
the same temperature list can be used for the superheated
enthalpy of a refrigerant and the specific heat of a glycol if
appropriate.
Field(s) 1-250:
Temperature[LINK]
These fields (up to 250) are the temperatures at which the
data for the thermal properties are to be expected.
Temperatures are assumed to be in ascending order in units of
Celsius.
An example of this statement in an input data file is:
FluidProperties:Temperatures,
R11Temperatures,
-70,-65,-60,-55,-50,-45,-40,-35,-30,-25,-20,-15,-10,-5,0,2,4,6,8,10,12,
14,16,18,20,22,24,26,28,30,32,34,36,38,40,42,44,46,48,50,55,60,65,70,
75,80,85,90,95,100,105,110,115,120,125,130,135,140,145,150,155,160,
165,170,175,180,185,190,198;
FluidProperties:Saturated[LINK]
Refrigerant property data for the saturated region is
entered with the following syntax. For each set of property
data a unique name, the type of property, phase and the
corresponding list of temperatures have to be specified along
with the property values.
This name identifies the fluid for which data follows in
the remaining syntax. This fluid name must also be given in
the fluid names list (ref: FluidProperties:Names object) as a
Refrigerant.
Field: Fluid Property
Type[LINK]
This field identifies the fluid property for which data is
being entered with this statement. The options for the
saturated region are Enthalpy, Density,
SpecificHeat, and Pressure. The
units for these properties are J/kg, kg/m3, J/kg-K
and Pa, respectively.
Field: Fluid Phase[LINK]
In the saturated region, each property has two values: one
for the saturated liquid state and one for the saturated
gaseous state. Accordingly, the phase for which the saturated
property data applies is specified as either
Fluid or FluidGas. Data for
each phase are required and are interpolated according to
quality. However, in the case of saturated pressure data
values for only one phase are required (i.e. can be specified
with phase specified as either Fluid or FluidGas, as this is
irrelevant).
Field: Temperatures
Values Name[LINK]
This name refers to the corresponding list of temperatures
(ref: FluidProperties:Temperatures
object). Each temperature in the temperature list corresponds
to a data item found in the remaining fields of this syntax.
The first temperature in the temperature list corresponds to
the first fluid property value, the second temperature in the
temperature list corresponds to the second fluid property
value, etc.
Field(s) 1-250: Property
Value[LINK]
These fields (up to 250) are the values of the thermal
property specified in the fluid property type field for the
phase specified in the fluid phase field. The temperature list
specified in the temperature list name field links the data
with the corresponding temperatures.
An example of this statement in an input data file is:
FluidProperties:Saturated,
R11,Enthalpy,Fluid,R11Temperatures, ! Enthalpy in J/kg
153580,154600,156310,158580,161300,164380,167740,171330,175100,179020,183060,
187190,191400,195680,200000,201740,203490,205240,207000,208770,210530,212310,
214080,215870,217650,219860,221230,223030,224830,226630,228860,230250,232060,
233860,235700,237520,239350,241180,243010,246350,249450,254080,258730,263480,
268110,272860,277000,282410,287240,292120,297030,302000,307090,312080,317210,
322400,327670,333020,338460,344010,349680,355500,361480,367690,374100,381060,
388850,397280,426300;
FluidProperties:Superheated[LINK]
The format of the data for the superheated region is
similar to that of the saturated region but with the addition
of the pressure for which each set of property values applies.
A single temperature specification is required for each set of
property data at a number of pressures.
Field: Fluid Name[LINK]
This name identifies the fluid for which data follows in
the remaining syntax. This fluid name must show up in the
fluid names list (ref: FluidProperties:Names object) as a
Refrigerant.
Field: Fluid Property
Type[LINK]
This field identifies the fluid property for which data is
being entered with this statement. The options for the
superheated region are Enthalpy and
Density. The units for these properties are
J/kg and kg/m3, respectively.
Field: Temperatures
Values Name[LINK]
This name refers to the corresponding list of temperatures
(ref: FluidProperties:Temperatures
object). Each temperature in the temperature list corresponds
to a given property data item at each pressure. The first
temperature in the temperature list corresponds to the first
fluid property value, the second temperature in the
temperature list corresponds to the second fluid property
value, etc.
Field: Pressure[LINK]
In the superheated region, each fluid property is indexed
according to temperature and pressure. Thus, a pressure must
be listed for each set of property values. The units for
pressure are Pascals (Pa). Lists of properties are various
pressures and temperatures form a two-dimensional table from
which EnergyPlus interpolates to find the property value at a
specified temperature and pressure.
Field(s) 1-250:
Property Value[LINK]
These fields (up to 250) are the values of the thermal
property specified in the fluid property type field for the
phase specified in the fluid phase field. The temperature list
specified in the temperature list name field links the data
with the corresponding temperatures.
An example of this statement in an input data file is:
FluidProperties:Superheated,
R11,Density,SuperR11Temperatures, ! Density in kg/m^3
62000., !Pressure = 62000Pa
0,0,0,0,0,0,0,0.0139,0.0134,0.0129,0.0124,0.012,0.0116,0.0112,0.0109,0.0105,
0.0102,0.0099,0.0097,0.0094,0.0092,0.0089,0,0,0,0,0,0,0,0,0,0;
Glycol Fluid Types[LINK]
A full data set for a glycol fluid type in EnergyPlus
includes: a temperature list and lists of values for specific
heat at a given concentration. Data have to be given for at
least two different concentrations. The syntax lines for the
property value lists are described below.
FluidProperties:Concentration[LINK]
The format of the data for the glycols is similar to that
of superheated refrigerants except that data at a number of
concentrations is given, rather than pressures. The
concentration is listed before the rest of the data and is
normalized (i.e. in the range 0.0 to 1.0, rather than a
percentage). Note that glycol solutions are assumed to exist
in liquid form only in EnergyPlus.
Field: Fluid Name[LINK]
This name identifies the fluid for which data follows in
the remaining syntax. This fluid name must show up in the
fluid names list (ref: FluidProperties:Names object) as a
Glycol.. Note that users should not use
Water, EthyleneGlycol, or PropyleneGlycol as names since these
are default fluids.
Field: Fluid Property
Type[LINK]
This field identifies the fluid property for which data is
being entered with this statement. The required data for
glycols includes SpecificHeat with units of
J/kg-K, Density with units of
kg/m3, Conductivity with units of
W/m-K, and Viscosity with units of
N-s/m2.
Field: Temperatures
Values Name[LINK]
This name refers to the corresponding list of temperatures
(ref: FluidProperties:Temperatures
object). Each temperature in the temperature list corresponds
to a data item found in the remaining fields of this syntax.
The first temperature in the temperature list corresponds to
the first fluid property value, the second temperature in the
temperature list corresponds to the second fluid property
value, etc.
Field: Concentration[LINK]
A concentration must be listed for the values of specific
heat that follow. Lists of properties are various
concentrations and temperatures form a two-dimensional table
from which EnergyPlus interpolates to find the property value
at a specified temperature and concentration. Concentrations
are specified in a normalized form (i.e. in the range 0.0 to
1.0, rather than a percentage)
Field(s) 1-250:
Property Value[LINK]
These fields (up to 250) are the values of the thermal
property specified in the fluid property type field for the
phase specified in the fluid phase field. The temperature list
specified in the temperature list name field links the data
with the corresponding temperatures.
An example of this statement in an input data file is:
FluidProperties:Concentration,
NewGlycol,SpecificHeat ,GlycolTemperatures, ! Spec. heat in J/kg-K
0.8, ! Concentration
2572,2600,2627,2655,2683,2710,2738,2766,2793,2821,2849,2876,2904,2931,2959,
2987,3014,3042,3070,3097,3125,3153,3180,3208,3236,3263,3291,3319,3346,3374,
3402,3429,3457;
Group – Fluid Properties[LINK]
The Fluid Property routines in EnergyPlus have been designed for ease of use and to allow users to add refrigerant and glycol data to the input file without having to make any changes to the program code. Fluid properties are calculated by interpolating the tabulated data in the input file. The main input requirement is that in order to add a new fluid, a user must enter a full set of data. The user may determine the interval between data points according to the desired accuracy and range required. Data for a number of common fluids are available in the required format in a reference dataset so that the user may append this data to their input file. In addition, data for Water, Ethylene Glycol (in various concentrations from 0 to 90%), and Propylene Glycol (in various concentrations from 0 to 90%) are available as default values within EnergyPlus.
Each fluid is categorized as either a ‘Refrigerant’ or ‘Glycol’. Refrigerant data is further categorized as either saturated or superheated. Saturated refrigerant data is indexed, in the input data, according to pressure and temperature i.e. the specific heat, density, enthalpy in the input data are given for a given combination of pressure and temperature. Saturated refrigerant data is indexed according to pressure and quality. In the case of saturated pressure data only a temperature index is used. Glycol data is indexed in the input data according to temperature and concentration. The input data structure for each property is essentially two-dimensional (a matrix). However, since all fluid loops are assumed to be of constant concentration, EnergyPlus internally will interpolate from input data to data for the actual concentration being used in a particular loop. This reduces internally to a one-dimensional array of data for various properties where temperature is the only variable. This saves time since it reduces all interpolations for glycols to a single dimension.
In most cases there will be combinations of index variable (e.g. some combination of pressure and temperature) at which either no data is available, or the property data is invalid/irrelevant. For example, in the superheated refrigerant data, some combinations of temperature and pressure may correspond to a state in the saturated rather than superheated region. Similarly, in the case of glycols there may be some combinations of temperature and concentration that would correspond to the frozen state. In these cases, and where data is just not available, a zero should be present in the data at these points to indicate an invalid condition. EnergyPlus uses the presence of zeros to detect invalid conditions and give warning messages.
FluidProperties:Name[LINK]
The names of each fluid for which property data is given in the user input have to be specified in FluidProperties:Name data objects. If data is to be included for a given fluid, either a refrigerant or a glycol, then its name must be included in the FluidProperties:Name objects.
Field: Fluid Name[LINK]
Each fluid name is a unique identifier that will be used in conjunction with the data statements described later in this section. The fluid name is either referred to by a component (in the case of a Refrigerant) or by another input line (in the case of a Glycol). This list is simply a list of user defined fluids present in the input data file.
Field: Fluid Type[LINK]
Each fluid name must be identified by type - either Refrigerant or Glycol. This designation determines what type of data EnergyPlus expects for the fluid name. If the fluid name is defined as a Refrigerant, the user must supply valid data for pressure, enthalpy, specific heat, and density in the saturated region and enthalpy and density in the superheated region. If the fluid name is defined as a Glycol, the user must supply valid data for specific heat, conductivity, viscosity, and density at various concentrations (percentage of non-water liquid) and temperatures.
An example of these statements in an input data file is:
FluidProperties:GlycolConcentration[LINK]
This input syntax is used to specify fluids that will be used with HVAC loops such as plant and condenser loops. It allows the user to define a mixture of water and some other substance and the particular concentration being used. The fluid name will be referred to by the loops or components and thus used to identify which value is valid for a particular fluid at a particular temperature. A series of three inputs is requires for each fluid concentration definition.
Field: Name[LINK]
Each glycol concentration name is a unique identifier that will be used to define a particular combination of water and some other substance (usually another fluid). Other input (such as loop definitions) will refer to this name, linking the other input to the proper fluid definition.
Field: Glycol Type[LINK]
This field refers to the substance that is being mixed with water to create the glycol. The user may either select from the two default fluids (EthyleneGlycol or PropyleneGlycol) or specify UserDefinedGlycolType and use a name in the subsequent field for fluids that have been entered elsewhere in the input file. It should be noted that users must enter a complete definition of new glycols—including values for conductivity, specific heat, density, and viscosity at various concentrations and temperatures—in order for them to be used in conjunction with a user defined glycol type.
Field: User Defined Glycol Name[LINK]
This field is the name used elsewhere in a FluidProperties:Name object for defining your own glycol properties. This field is left blank unless you enter UserDefinedGlycolType in the previous field.
Field: Glycol Concentration[LINK]
This field allows the user to specify the actual concentration of glycol being used for this particular fluid. A concentration of 0.0 refers to pure water. A concentration of 1.0 would denote 100% of the fluid referenced in the Glycol Name input discussed above. Users should enter this value as a decimal fraction since EnergyPlus will limit the range of valid input values to between 0.0 and 1.0.
An example of this statement in an input data file is:
FluidProperties:Temperatures[LINK]
It is assumed that all fluid properties vary with temperature. A common set of temperatures is required for each set of fluid property data. Fluid property data supplied by the user must correspondingly be given at these temperatures. Since in most cases, refrigerant data can be specified at a common set of temperatures, a single set of ‘FluidProperties:Temperatures’ can be referenced by a number of sets of property data. This provides a more compact input structure and avoids listing the temperatures multiple times. In the case of glycol data the same set of temperatures have to be used for each set of data at a given concentration. Units for the temperatures are degrees Celsius.
Field: Name[LINK]
This field is simply an unique identifier name that is used to cross reference the list of temperatures with a specific list of fluid property data. A single temperature list can be used for more than one thermal property or fluid. For example, the same temperature list can be used for the superheated enthalpy of a refrigerant and the specific heat of a glycol if appropriate.
Field(s) 1-250: Temperature[LINK]
These fields (up to 250) are the temperatures at which the data for the thermal properties are to be expected. Temperatures are assumed to be in ascending order in units of Celsius.
An example of this statement in an input data file is:
FluidProperties:Saturated[LINK]
Refrigerant property data for the saturated region is entered with the following syntax. For each set of property data a unique name, the type of property, phase and the corresponding list of temperatures have to be specified along with the property values.
Field: Name[LINK]
This name identifies the fluid for which data follows in the remaining syntax. This fluid name must also be given in the fluid names list (ref: FluidProperties:Names object) as a Refrigerant.
Field: Fluid Property Type[LINK]
This field identifies the fluid property for which data is being entered with this statement. The options for the saturated region are Enthalpy, Density, SpecificHeat, and Pressure. The units for these properties are J/kg, kg/m3, J/kg-K and Pa, respectively.
Field: Fluid Phase[LINK]
In the saturated region, each property has two values: one for the saturated liquid state and one for the saturated gaseous state. Accordingly, the phase for which the saturated property data applies is specified as either Fluid or FluidGas. Data for each phase are required and are interpolated according to quality. However, in the case of saturated pressure data values for only one phase are required (i.e. can be specified with phase specified as either Fluid or FluidGas, as this is irrelevant).
Field: Temperatures Values Name[LINK]
This name refers to the corresponding list of temperatures (ref: FluidProperties:Temperatures object). Each temperature in the temperature list corresponds to a data item found in the remaining fields of this syntax. The first temperature in the temperature list corresponds to the first fluid property value, the second temperature in the temperature list corresponds to the second fluid property value, etc.
Field(s) 1-250: Property Value[LINK]
These fields (up to 250) are the values of the thermal property specified in the fluid property type field for the phase specified in the fluid phase field. The temperature list specified in the temperature list name field links the data with the corresponding temperatures.
An example of this statement in an input data file is:
FluidProperties:Superheated[LINK]
The format of the data for the superheated region is similar to that of the saturated region but with the addition of the pressure for which each set of property values applies. A single temperature specification is required for each set of property data at a number of pressures.
Field: Fluid Name[LINK]
This name identifies the fluid for which data follows in the remaining syntax. This fluid name must show up in the fluid names list (ref: FluidProperties:Names object) as a Refrigerant.
Field: Fluid Property Type[LINK]
This field identifies the fluid property for which data is being entered with this statement. The options for the superheated region are Enthalpy and Density. The units for these properties are J/kg and kg/m3, respectively.
Field: Temperatures Values Name[LINK]
This name refers to the corresponding list of temperatures (ref: FluidProperties:Temperatures object). Each temperature in the temperature list corresponds to a given property data item at each pressure. The first temperature in the temperature list corresponds to the first fluid property value, the second temperature in the temperature list corresponds to the second fluid property value, etc.
Field: Pressure[LINK]
In the superheated region, each fluid property is indexed according to temperature and pressure. Thus, a pressure must be listed for each set of property values. The units for pressure are Pascals (Pa). Lists of properties are various pressures and temperatures form a two-dimensional table from which EnergyPlus interpolates to find the property value at a specified temperature and pressure.
Field(s) 1-250: Property Value[LINK]
These fields (up to 250) are the values of the thermal property specified in the fluid property type field for the phase specified in the fluid phase field. The temperature list specified in the temperature list name field links the data with the corresponding temperatures.
An example of this statement in an input data file is:
Glycol Fluid Types[LINK]
A full data set for a glycol fluid type in EnergyPlus includes: a temperature list and lists of values for specific heat at a given concentration. Data have to be given for at least two different concentrations. The syntax lines for the property value lists are described below.
FluidProperties:Concentration[LINK]
The format of the data for the glycols is similar to that of superheated refrigerants except that data at a number of concentrations is given, rather than pressures. The concentration is listed before the rest of the data and is normalized (i.e. in the range 0.0 to 1.0, rather than a percentage). Note that glycol solutions are assumed to exist in liquid form only in EnergyPlus.
Field: Fluid Name[LINK]
This name identifies the fluid for which data follows in the remaining syntax. This fluid name must show up in the fluid names list (ref: FluidProperties:Names object) as a Glycol.. Note that users should not use Water, EthyleneGlycol, or PropyleneGlycol as names since these are default fluids.
Field: Fluid Property Type[LINK]
This field identifies the fluid property for which data is being entered with this statement. The required data for glycols includes SpecificHeat with units of J/kg-K, Density with units of kg/m3, Conductivity with units of W/m-K, and Viscosity with units of N-s/m2.
Field: Temperatures Values Name[LINK]
This name refers to the corresponding list of temperatures (ref: FluidProperties:Temperatures object). Each temperature in the temperature list corresponds to a data item found in the remaining fields of this syntax. The first temperature in the temperature list corresponds to the first fluid property value, the second temperature in the temperature list corresponds to the second fluid property value, etc.
Field: Concentration[LINK]
A concentration must be listed for the values of specific heat that follow. Lists of properties are various concentrations and temperatures form a two-dimensional table from which EnergyPlus interpolates to find the property value at a specified temperature and concentration. Concentrations are specified in a normalized form (i.e. in the range 0.0 to 1.0, rather than a percentage)
Field(s) 1-250: Property Value[LINK]
These fields (up to 250) are the values of the thermal property specified in the fluid property type field for the phase specified in the fluid phase field. The temperature list specified in the temperature list name field links the data with the corresponding temperatures.
An example of this statement in an input data file is: