UtilityCost:Charge:Block[LINK]
The UtilityCost:Charge:Block
objects is also used extensively for tariff calculation. It is
used to compute energy and demand charges that are structured
in blocks of charges. It may also be used for taxes,
surcharges and any other charges that occur on a utility bill
but those are more commonly simple flat charges so UtilityCost:Charge:Simple
is more commonly used for those functions. As many UtilityCost:Charge:Block
objects as needed may be defined for a single tariff and they
will be added together. Blocks are a structure used by almost
all utilities for calculating energy and demand charges and
they allow the utility to charge more or less per unit of
energy or demand if more units are used.
Field: Charge Variable
Name[LINK]
This is the name associated with the UtilityCost:Charge:Block
object and will appear in the report. In addition, the results
of the UtilityCost:Charge:Block
are stored in a variable with the same name. That way, the
results may be used for further calculation.
Field: Tariff Name[LINK]
The name of the tariff that this UtilityCost:Charge:Block
is associated with.
Field: Source Variable[LINK]
The name of the source used by the UtilityCost:Charge:Block.
This is usually the name of the variable holding the energy or
demand but may also be the name of any variable including the
subtotal or basis if other charges are based on those.
Field: Season[LINK]
This is the name (or number) of a season for which the UtilityCost:Charge:Block
is calculated. If this is set to annual, the calculations are
performed for the UtilityCost:Charge:Block
for the entire year (all months) otherwise it is calculated
only for those months in the season defined. The season is
defined by the Season Schedule in the UtilityCost:Tariff
object. The choices for seasons are the following names or
numbers may be used:
- Annual
- Summer
- Winter
- Spring
- Fall
Field: Category Variable
Name[LINK]
All charges get added somewhere in the hierarchy described
in the introduction to EnergyPlus economics above. This field
shows where the charge should be added. The reason to enter
this field appropriately is so that the charge gets reported
in a reasonable category. The charge automatically gets added
to the variable that is the category. The choices for this
field are limited to:
- EnergyCharges
- DemandCharges
- ServiceCharges
- Basis
- Adjustment
- Surcharge
- Subtotal
- Taxes
- Total
- NotIncluded
Field: Remaining Into
Variable[LINK]
If the blocks do not use all of the energy or demand from
the source, some energy and demand remains, then the remaining
amount should be assigned to a variable. If no variable is
assigned and some amount of energy or demand is not used in
the block structure a warning will be issued.
Field:
Block Size Multiplier Value or Variable Name[LINK]
The sizes of the blocks are usually used directly but if a
value or a variable is entered here, the block sizes entered
in the rest of the charge are first multiplied by the entered
value prior to being used. This is common for rates that are
kWh/kW rates and in that case the variable that holds the
monthly total electric demand would be entered. If no value is
entered, a default value of one is assumed so that the block
sizes remain exactly as entered. This field is unusual for the
EnergyPlus syntax because it can be either a number or a name
of a variable.
Field:
Block Size 1 Value or Variable Name[LINK]
The size of the first block of the charges is entered here.
For most rates that use multiple blocks, this will be the
value for the first block size. Additional block sizes are
entered with every other field. A default variable named
“remaining” contains a large value and this may be used when
the remaining amount should be included in that block. This
field and the next field may be repeated in groups of two for
as many blocks as are defined. This field is unusual for the
EnergyPlus syntax because it can be either a number or a name
of a variable.
Field:
Block 1 Cost per Unit Value or Variable Name[LINK]
The cost of the first block. This value is also repeated
for every other field in the charge. As many blocks may be
entered as are needed. This field and the previous field may
be repeated in groups of two for as many blocks as are
defined. This field is unusual for the EnergyPlus syntax
because it can be either a number or a name of a variable. For
SellToUtility tariffs, the values in this field are usually
expressed as negative numbers.
These last two fields may be repeated fifteen times. If
more blocks are defined by the utility, the computation can be
continued using another UtilityCost:Charge:Block
and using the variable from Remaining Into Variable as the
source variable.
UtilityCost:Charge:Block[LINK]
The UtilityCost:Charge:Block objects is also used extensively for tariff calculation. It is used to compute energy and demand charges that are structured in blocks of charges. It may also be used for taxes, surcharges and any other charges that occur on a utility bill but those are more commonly simple flat charges so UtilityCost:Charge:Simple is more commonly used for those functions. As many UtilityCost:Charge:Block objects as needed may be defined for a single tariff and they will be added together. Blocks are a structure used by almost all utilities for calculating energy and demand charges and they allow the utility to charge more or less per unit of energy or demand if more units are used.
Field: Charge Variable Name[LINK]
This is the name associated with the UtilityCost:Charge:Block object and will appear in the report. In addition, the results of the UtilityCost:Charge:Block are stored in a variable with the same name. That way, the results may be used for further calculation.
Field: Tariff Name[LINK]
The name of the tariff that this UtilityCost:Charge:Block is associated with.
Field: Source Variable[LINK]
The name of the source used by the UtilityCost:Charge:Block. This is usually the name of the variable holding the energy or demand but may also be the name of any variable including the subtotal or basis if other charges are based on those.
Field: Season[LINK]
This is the name (or number) of a season for which the UtilityCost:Charge:Block is calculated. If this is set to annual, the calculations are performed for the UtilityCost:Charge:Block for the entire year (all months) otherwise it is calculated only for those months in the season defined. The season is defined by the Season Schedule in the UtilityCost:Tariff object. The choices for seasons are the following names or numbers may be used:
Field: Category Variable Name[LINK]
All charges get added somewhere in the hierarchy described in the introduction to EnergyPlus economics above. This field shows where the charge should be added. The reason to enter this field appropriately is so that the charge gets reported in a reasonable category. The charge automatically gets added to the variable that is the category. The choices for this field are limited to:
Field: Remaining Into Variable[LINK]
If the blocks do not use all of the energy or demand from the source, some energy and demand remains, then the remaining amount should be assigned to a variable. If no variable is assigned and some amount of energy or demand is not used in the block structure a warning will be issued.
Field: Block Size Multiplier Value or Variable Name[LINK]
The sizes of the blocks are usually used directly but if a value or a variable is entered here, the block sizes entered in the rest of the charge are first multiplied by the entered value prior to being used. This is common for rates that are kWh/kW rates and in that case the variable that holds the monthly total electric demand would be entered. If no value is entered, a default value of one is assumed so that the block sizes remain exactly as entered. This field is unusual for the EnergyPlus syntax because it can be either a number or a name of a variable.
Field: Block Size 1 Value or Variable Name[LINK]
The size of the first block of the charges is entered here. For most rates that use multiple blocks, this will be the value for the first block size. Additional block sizes are entered with every other field. A default variable named “remaining” contains a large value and this may be used when the remaining amount should be included in that block. This field and the next field may be repeated in groups of two for as many blocks as are defined. This field is unusual for the EnergyPlus syntax because it can be either a number or a name of a variable.
Field: Block 1 Cost per Unit Value or Variable Name[LINK]
The cost of the first block. This value is also repeated for every other field in the charge. As many blocks may be entered as are needed. This field and the previous field may be repeated in groups of two for as many blocks as are defined. This field is unusual for the EnergyPlus syntax because it can be either a number or a name of a variable. For SellToUtility tariffs, the values in this field are usually expressed as negative numbers.
These last two fields may be repeated fifteen times. If more blocks are defined by the utility, the computation can be continued using another UtilityCost:Charge:Block and using the variable from Remaining Into Variable as the source variable.