Group - Airflow[LINK]
An important characteristic of energy consumption in
buildings is the airflow between zones and airflow due to
natural ventilation (e.g., open windows) or
mechanically-induced ventilation (e.g., exhaust air fans).
This group of objects describes those elements.
The AirflowNetwork model can also be used to model
infiltration and mixing (zone-to-zone air flow) with or
without the HVAC air distribution system operating (see Group
- Airflow Network).
ZoneInfiltration:DesignFlowRate[LINK]
Infiltration is the unintended flow of air from the outdoor
environment directly into a thermal zone. Infiltration is
generally caused by the opening and closing of exterior doors,
cracks around windows, and even in very small amounts through
building elements. The basic equation used to calculate
infiltration with this object is:
\[Infiltration = \left(
{{I_{design}}} \right)\left( {{F_{schedule}}} \right)\left[ {A
+ B\left| {\left( {{T_{zone}} - {T_{odb}}} \right)} \right| +
C\left( {WindSpeed} \right) + D\left( {Windspee{d^2}} \right)}
\right]\]
More advanced infiltration calculations are possible using
the EnergyPlus AirflowNetwork model for natural infiltration
driven by wind and/or by forced air. Infiltration described by
the equation shown above is entered into EnergyPlus using the
following syntax. Exfiltration (the leakage of zone air to the
outside) is generally handled better as zone exhaust air in
the zone equipment description. The equation must always yield
a non-negative results; negative values are set to 0.0.
The question of typical values for these coefficients is
subject to debate. Ideally, one should do a detailed analysis
of the infiltration situation and then determine a custom set
of coefficients using methods such as those laid out in
Chapter 26 of the ASHRAE Handbook of Fundamentals. The
EnergyPlus defaults are 1,0,0,0 which give a constant volume
flow of infiltration under all conditions.
BLAST (one of the EnergyPlus predecessors) used the
following values as defaults: 0.606, 0.03636, 0.1177, 0. These
coefficients produce a value of 1.0 at 0C deltaT and 3.35 m/s
(7.5 mph) windspeed, which corresponds to a typical summer
condition. At a winter condition of 40C deltaT and 6 m/s (13.4
mph) windspeed, these coefficients would increase the
infiltration rate by a factor of 2.75.
In DOE-2 (the other EnergyPlus predecessor), the air change
method defaults are (adjusted to SI units) 0, 0, 0.224
(windspeed), 0. With these coefficients, the summer conditions
above would give a factor of 0.75, and the winter conditions
would give 1.34. A windspeed of 4.47 m/s (10 mph) gives a
factor of 1.0.
The source of the BLAST defaults is noted in the BLAST
documentation as:
“Empirical equation and the coefficient default were
determined from ASHRAE journal articles and other data on the
effects of outdoor weather conditions.”
The source of the DOE-2 defaults is based on examining the
infiltration relationships described in the ASHRAE Handbook of
Fundamentals.
The EnergyPlus example files use all of the above, the
BLAST defaults in some (e.g., GeometryTest), the DOE-2
defaults in some (e.g., 5ZoneAirCooled), and the EnergyPlus
defaults in some (e.g., LgOffVAVDetCoil).
The local outdoor dry-bulb temperature used in the above
basic equation (Todb) is typically a function of
the height of the zone centroid above ground. The
corresponding zone name is given in the second field. The
local outdoor dry-bulb temperature calculation procedure is
given in the section of “Local Outdoor Air Temperature
Calculation” in the Engineering Reference.
The local outdoor wind speed used in the above basic
equation (WindSpeed) is also a function of the height of the
zone centroid above ground. The corresponding zone name is
given in the second filed. The local outdoor wind speed
calculation procedure is given in the section of “Local Wind
Speed Calculation” in the Engineering Reference.
Note: When the value of the Wind Speed Profile Exponent
field in the Site:HeightVariation
is equal to 0.0. The local wind speed is always equal to the
wind speed given in the weather data and will not be dependent
on zone centroid height. Similarly, if the value of the Air
Temperature Gradient Coefficient is set equal to 0 the local
air dry-bulb temperature is also always equal to the air
dry-bulb temperature given in the weather data and will not be
dependent on zone centroid height.
One or more infiltration objects can be defined for each
zone, and the resulting infiltration rate for the zone will
simply be the summation of the flow rates specified by the
infiltration objects.
The name of the ZoneInfiltration:DesignFlowRate
object. This needs to be unique across all different
ZoneInfiltration objects.
Field: Zone or ZoneList
Name[LINK]
This field is the name of the zone (ref: Zone) or ZoneList
(ref: ZoneLIst) and attaches a particular infiltration
statement to a thermal zone or set of thermal zones in the
building. When the ZoneList
option is used then this infiltration definition is applied to
each of the zones in the zone list effecting a global
definition for the amount of infiltration flow rate in the
zone. The Zonelist option can be used effectively with the
flow/area, flow/exteriorarea, flow/exteriorwallarea, or
airchanges/hour of the Design Flow Rate Calculation
Method.
The name of the actual infiltration object becomes
and
should be less than the standard length (100 characters) for a
name field. If it is greater than this standard length, it may
be difficult to specify in output reporting as it will be
truncated. A warning will be shown if the generated name is
greater than 100 characters. If it duplicates another such
concatenated name, there will be a severe error and terminate
the run.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the maximum design volume flow rate
(Idesign) (see Design Flow Rate Calculation Method
field and related subsequent fields). This fraction between
0.0 and 1.0 is noted as Fschedule in the above
equation.
Field:
Design Flow Rate Calculation Method[LINK]
This field is a key/choice field that tells which of the
next four fields are filled and is descriptive of the method
for calculating the design volume flow rate. The key/choices
are:
- Flow/Zone
- With this choice, the method used will be a straight
insertion of the design volume flow rate. (The Design Flow
Rate field should be filled.)
- Flow/Area
- With this choice, the method used will be a factor per
floor area of the zone. (The flow per Zone Area field should
be filled).
- Flow/ExteriorArea
- With this choice, the method used will be a factor per
exterior surface area of the zone. (The flow per Exterior
Surface Area field should be filled).
- Flow/ExteriorWallArea
- With this choice, the method used will be a factor per
exterior wall surface area of the zone. (The flow per Exterior
Surface Area field should be filled).
- AirChanges/Hour
- With this choice, the method used will be the number of
air changes per hour for the infiltration amount. This factor,
along with the Zone Volume, will be used to determine the
Design Flow Rate. (The Air Changes per Hour field should be
filled).
Field: Design Flow Rate[LINK]
This field denotes the full design volume flow rate
(m3/s). The previous field should choose
“flow/zone” as the choice. The design volume flow rate (noted
as Idesign in the above equation) is the maximum
amount of infiltration expected at design conditions. The
design value is modified by the schedule fraction (see
Field:Schedule Name) and user specified coefficients (see
“coefficient” fields below). The resulting volume flow rate is
converted to mass flow using the current outdoor air density
at each time step.
Field: Flow per Zone
Floor Area[LINK]
This factor (m3/s-m2) is used, along
with the Zone
Area to determine the maximum Design Flow Rate as described in
the Design Flow Rate field. The choice from the method field
should be “Flow/Area”.
Field: Flow per
Exterior Surface Area[LINK]
This factor (m3/s-m2) is used, along
with the Exterior Surface Area in the Zone
to determine the maximum Design Flow Rate as described in the
Design Flow Rate field. The choice from the method field
should be “Flow/Exteriorarea” or “Flow/ExteriorWallArea”.
Field: Air Changes per
Hour[LINK]
This factor is used, along with the Zone
Volume to determine the maximum Design Flow Rate as described
in the Design Flow Rate field. The choice from the method
field should be “AirChanges/Hour”.
Field: Constant Term
Coefficient[LINK]
This number is the “A” parameter in the above infiltration
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter, however, is a constant under all conditions and is
not modified by any environmental effect. As a result, it is
dimensionless.
Field: Temperature
Term Coefficient[LINK]
This number is the “B” parameter in the above infiltration
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter is modified by the temperature difference between
the outdoor and indoor air dry-bulb temperatures. The units
for this parameter are inverse Celsius.
Field: Velocity Term
Coefficient[LINK]
This number is the “C” parameter in the above infiltration
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter is modified by the speed of wind being experienced
outside the building. The units for this parameter are
s/m.
Field:
Velocity Squared Term Coefficient[LINK]
This number is the “D” parameter in the above infiltration
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter is modified by square of the speed of wind being
experienced outside the building. The units for this parameter
are s2/m2.
An IDF example:
ZoneInfiltration:DesignFlowRate,
Infiltration 1, !- Name
DORM ROOMS AND COMMON AREAS, !- Zone Name
Infiltration Sch, !- Schedule Name
Flow/Zone, !- Design Flow Rate Calculation Method
2.831685, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s/m2}
, !- Flow per Exterior Surface Area {m3/s/m2}
, !- Air Changes per Hour
0.6060000 , !- Constant Term Coefficient
3.6359996E-02, !- Temperature Term Coefficient
0.1177165 , !- Velocity Term Coefficient
0.0000000E+00; !- Velocity Squared Term Coefficient
Global Infiltration example:
ZoneList,OfficeZones,Left Fork, Middle Fork, Right Fork;
ZoneInfiltration:DesignFlowRate,
OfficeZones Infiltration, !- Name
OfficeZones, !- Zone or ZoneList Name
Infiltration Sch, !- Schedule Name
AirChanges/Hour, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
, !- Flow per Exterior Surface Area {m3/s-m2}
4.7, !- Air Changes per Hour
0.6060000, !- Constant Term Coefficient
3.6359996E-02, !- Temperature Term Coefficient
0.1177165, !- Velocity Term Coefficient
0.0000000E+00; !- Velocity Squared Term Coefficient
ZoneInfiltration:EffectiveLeakageArea[LINK]
ZoneInfiltration:EffectiveLeakageArea
model is similar to the other infiltration objects but uses a
different equation to model the unintended flow of air from
the outdoor environment directly into a thermal zone.
Infiltration is generally caused by the opening and closing of
exterior doors, cracks around windows, and even in very small
amounts through building elements. This model is based on work
by Sherman and Grimsrud (1980) and is appropriate for smaller,
residential-type buildings. The equation used to calculate
infiltration in the effective leakage area model is:
\[Infiltration = \left(
{{F_{Schedule}}} \right)\frac{{{A_L}}}{{1000}}\sqrt
{{C_s}\Delta T + {C_w}{{\left( {WindSpeed}
\right)}^2}}\]
where \(\Delta T\) is the
average difference between zone air temperature and the
outdoor air temperature and the other coefficients are
described below.
Note that the coefficients for the “EffectiveLeakageArea”
model are not interchangeable with the similarly named
coefficients in the “FlowCoefficient” model (see ZoneInfiltration:FlowCoefficient
object).
One or more infiltration objects of different types can be
defined for each zone, and the resulting infiltration rate for
the zone will simply be the summation of the flow rates
specified by the infiltration objects.
The name of the ZoneInfiltration:EffectiveLeakageArea
object. This needs to be unique across all different
ZoneInfiltration objects.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches
a particular infiltration statement to a thermal zone in the
building.
Field: Schedule Name[LINK]
This field is the name of a schedule (ref: Schedule) that
modifies the volume flow rate calculated by the model. This
fraction between 0.0 and 1.0 is noted as Fschedule
in the above equation.
Field: Effective Air
Leakage Area[LINK]
This field is the effective air leakage area, in
cm2, at 4 Pa. This is the value \({A_L}\)in the equation above.
Effective leakage area data can be obtained from a
whole-building pressure test (eg. blower door test). ASHRAE
Handbook of Fundamentals also lists typical values component
leakage areas for low-rise residential (e.g. Table 1 in
Chapter 26 of HoF 2001). The value should correspond to a
pressure difference of 4 Pa.
Field: Stack Coefficient[LINK]
This field is the value of the stack coefficient, \({C_s}\) in the equation above.
The coefficient has units of
(L/s)2/(cm4·K). Values for the “Basic
Model Stack Coefficient” listed in the ASHRAE Handbook of
Fundamentals (2005 and 2001) are:
One story house Two story house Three story house
0.000145 0.000290 0.000435
Field: Wind Coefficient[LINK]
This field is the value of the wind coefficient, \({C_w}\) in the equation above.
The coefficient has units of
(L/s)2/(cm4·(m/s)2). Values
for the “Basic Model Wind Coefficient” listed in the ASHRAE
Handbook of Fundamentals (2005 chapter 27; 2001, Chapter 26)
depend on the type of shelter and are listed in the following
tables.
Shelter class One story house Two story house Three story
house
1 0.000319 0.000420 0.000494
2 0.000246 0.000325 0.000382
3 0.000174 0.000231 0.000271
4 0.000104 0.000137 0.000161
5 0.000032 0.000042 0.000049
Shelter class Description
1 No obstructions or local shielding
2 Typical shelter for an isolated rural house
3 Typical shelter caused by other buildings across the
street
4 Typical shelter for urban buildings on larger lots
5 Typical shelter produced by buildings that are
immediately adjacent.
An example IDF object is
ZoneInfiltration:EffectiveLeakageArea,
LIVING ZONE Infil 1, !- Name
LIVING ZONE, !- Zone Name
INF-SCHED, !- Schedule Name
500.0, !- Effective Air Leakage Area
0.000145, !- Stack Coefficient
0.000174 ; !- Wind Coefficient
ZoneInfiltration:FlowCoefficient[LINK]
ZoneInfiltration:FlowCoefficient
model is similar to the other infiltration objects but uses a
different equation to model the unintended flow of air from
the outdoor environment directly into a thermal zone.
Infiltration is generally caused by the opening and closing of
exterior doors, cracks around windows, and even in very small
amounts through building elements. This reformulated model is
based on the AIM-2 model by Walker and Wilson (1998) and is
appropriate for smaller, residential-type buildings. The
equation used to calculate infiltration in the flow
coefficient model is:
\[Infiltration = \left(
{{F_{Schedule}}} \right)\sqrt {{{\left( {c\,{C_s}\Delta {T^n}}
\right)}^2} + {{\left( {c\,{C_w}{{\left( {s * WindSpeed}
\right)}^{2n}}} \right)}^2}}\]
Where \(\Delta T\) is the
average difference between zone air temperature and the
outdoor air temperature and the other coefficients are
described below.
Note that the coefficients for the “Flow Coefficient” model
are not interchangeable with the similarly named coefficients
in the “Effective Leakage Area” model (see ZoneInfiltration:EffectiveLeakageArea
object).
One or more infiltration objects of different types can be
defined for each zone, and the resulting infiltration rate for
the zone will simply be the summation of the flow rates
specified by the infiltration objects.
The name of the ZoneInfiltration:FlowCoefficient
object. This needs to be unique across all different
ZoneInfiltration objects.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches
a particular infiltration statement to a thermal zone in the
building.
Field: Schedule Name[LINK]
This field is the name of a schedule (ref: Schedule) that
modifies the volume flow rate calculated by the model. This
fraction between 0.0 and 1.0 is noted as Fschedule
in the above equation.
Field: Flow Coefficient[LINK]
This field is the flow coefficient in
m3/(s·Pan). This is the value \(c\) in the equation above. The
flow coefficient can be determined from the effective leakage
area and whole-building pressure tests (eg. blower door
test).
Field: Stack
Coefficient[LINK]
This field is the value of the stack coefficient, \({C_s}\) in the equation above.
The coefficient has units of (Pa/K)n. Values for
the “Enhanced Model Stack Coefficient” listed in the ASHRAE
Handbook of Fundamentals (2005 and 2001) are:
One story house Two story house Three story house
With Flue 0.069 0.089 0.107
No Flue 0.054 0.078 0.098
Field: Pressure Exponent[LINK]
This field is the value of the pressure exponent,
n in the equation above. The pressure exponent
generally lies between 0.6 and 0.7 with a typical value of
n = 0.67 for the enhanced model.
Field: Wind Coefficient[LINK]
This field is the value of the wind coefficient, \({C_w}\) in the equation above.
The coefficient has units of
(Pa·s2/m2)n. Values for the
“Enhanced Model Wind Coefficient” listed in the ASHRAE
Handbook of Fundamentals (2005 and 2001) are:
One story house Two story house Three story house
Basement/slab;With Flue 0.142 0.156 0.167
Basement/slab; No Flue 0.156 0.170 0.170
Crawlspace; With Flue 0.128 0.142 0.154
Crawlspace; No Flue 0.128 0.142 0.151
Field: Shelter Factor[LINK]
This field is the value of the wind coefficient, \(s\) in the equation above. The
coefficient is dimensionless. Values for the “Enhanced Model
Shelter Factor” listed in the ASHRAE Handbook of Fundamentals
(2005 and 2001) are:
Shelter class No Flue One story house with flue Two story
house with flue Three story house with flue
1 1.00 1.10 1.07 1.06
2 0.90 1.02 0.98 0.97
3 0.70 0.86 0.81 0.79
4 0.50 0.70 0.64 0.61
5 0.30 0.54 0.47 0.43
Shelter class Description
1 No obstructions or local shielding
2 Typical shelter for an isolated rural house
3 Typical shelter caused by other buildings across the
street
4 Typical shelter for urban buildings on larger lots
5 Typical shelter produced by buildings that are
immediately adjacent.
An Example IDF object is:
ZoneInfiltration:FlowCoefficient,
LIVING ZONE Infil 1, !- Name
LIVING ZONE, !- Zone Name
INF-SCHED, !- Schedule Name
0.05, !- Flow Coefficient
0.089, !- Stack Coefficient
0.67 , !- Pressure Exponent
0.156 , !- Wind Coefficient
0.64; !- Shelter Factor
HVAC,Sum,Zone Infiltration Sensible Heat Loss Energy [J]
HVAC,Sum,Zone Infiltration Sensible Heat Gain Energy [J]
HVAC,Sum,Zone Infiltration Latent Heat Loss Energy [J]
HVAC,Sum,Zone Infiltration Latent Heat Gain Energy [J]
HVAC,Sum,Zone Infiltration Total Heat Loss Energy [J]
HVAC,Sum,Zone Infiltration Total Heat Gain Energy [J]
HVAC,Average,Zone Infiltration Current Density Volume Flow Rate [m3/s]
HVAC,Average,Zone Infiltration Standard Density Volume Flow Rate [m3/s]
HVAC,Sum,Zone Infiltration Current Density Volume [m3]
HVAC,Sum,Zone Infiltration Standard Density Volume [m3]
HVAC,Sum,Zone Infiltration Mass [kg]
HVAC,Sum,Zone Infiltration Mass Flow Rate [kg/s]
HVAC,Average,Zone Infiltration Air Change Rate [ach]
Note: If ZoneInfiltration:* objects and ZoneAirBalance:OutdoorAir
(with Air Balance Method = Quadrature) objects reference the
same Zone
Name, the above infiltration output variables will not be
reported for that zone. Instead, output variables for zone
outdoor air flow will be reported by the corresponding ZoneAirBalance:OutdoorAir
object.
Zone
Infiltration Sensible Heat Loss Energy [J][LINK]
The sensible (temperature) heat loss that occurs when the
infiltration air temperature (outdoor) < zone air
temperature.
Zone
Infiltration Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat gain that occurs when the
infiltration air temperature (outdoor) >= zone air
temperature.
Zone
Infiltration Latent Heat Loss Energy [J][LINK]
The latent heat loss that occurs when the infiltration air
humidity ratio (outdoor) < zone air humidity ratio.
Zone
Infiltration Latent Heat Gain Energy [J][LINK]
The latent heat gain that occurs when the infiltration air
humidity ratio (outdoor) >= zone air humidity ratio.
Zone
Infiltration Total Heat Loss Energy [J][LINK]
The total heat loss that occurs when the sum of Zone
Infiltration Sensible Heat Gain Energy and Zone
Infiltration Latent Heat Gain Energy < the sum of Zone
Infiltration Sensible Heat Loss Energy and Zone
Infiltration Latent Heat Loss Energy.
Zone
Infiltration Total Heat Gain Energy [J][LINK]
The total heat gain that occurs when the sum of Zone
Infiltration Sensible Heat Gain Energy and Zone
Infiltration Latent Heat Gain Energy >= the sum of Zone
Infiltration Sensible Heat Loss Energy and Zone
Infiltration Latent Heat Loss Energy.
Zone
Infiltration Current Density Volume [m3][LINK]
Zone
Infiltration Current Density Volume Flow Rate [m3/s][LINK]
These outputs are the total volume and volume flow rate of
infiltration air based on the current density of zone air.
Zone
Infiltration Standard Density Volume [m3][LINK]
Zone
Infiltration Standard Density Volume Flow Rate [m3/s][LINK]
These outputs are the total volume and volume flow rate of
infiltration air based on the standard density of air.
Standard density in EnergyPlus corresponds to 20ºC drybulb,
dry air, and nominally adjusted for elevation.
Zone Infiltration Mass
[kg][LINK]
The mass flow of the Infiltration air.
Zone
Infiltration Mass Flow Rate [kg/s][LINK]
The mass flow rate of the Infiltration air.
Zone
Infiltration Air Change Rate [ach][LINK]
The rate of infiltration in air changes per hour.
ZoneVentilation:DesignFlowRate[LINK]
Ventilation is the purposeful flow of air from the outdoor
environment directly into a thermal zone in order to provide
some amount of non-mechanical cooling. Ventilation, as
specified by the input syntax for the ZoneVentilation:DesignFlowRate
object, is intended to model “simple” ventilation as opposed
to the more detailed ventilation investigations that can be
performed with the AirflowNetwork model or with air systems
that have outdoor air mixers. Zone
ventilation, as specified via this input object, can be
controlled by a schedule and through the specification of
minimum, maximum and delta temperatures as described below.
The temperatures can be either single constant values for the
entire simulation or schedules which can vary over time. As
with infiltration, the actual flow rate of ventilation air can
be modified by the temperature difference between the inside
and outside environment and the wind speed. The basic equation
used to calculate ventilation with this model is:
\[Ventilation = \left(
{{V_{design}}} \right)\left( {{F_{schedule}}} \right)\left[ {A
+ B\left| {{T_{zone}} - {T_{odb}}} \right| + C\left(
{WindSpeed} \right) + D\left( {WindSpee{d^2}} \right)}
\right]\]
Similar to infiltration, the question of typical values for
these coefficients is subject to debate. Ideally, one should
do a detailed analysis of the ventilation situation and then
determine a custom set of coefficients using methods such as
those laid out in Chapter 26 of the ASHRAE Handbook of
Fundamentals. The EnergyPlus defaults are 1,0,0,0 which give a
constant volume flow of ventilation under all conditions. The
following discussion is duplicated from the infiltration
design flow rate object. The equation must always yield a
non-negative results; negative values are set to 0.0.
BLAST (one of the EnergyPlus predecessors) used the
following values as defaults: 0.606, 0.03636, 0.1177, 0. These
coefficients produce a value of 1.0 at 0C deltaT and 3.35 m/s
(7.5 mph) windspeed, which corresponds to a typical summer
condition. At a winter condition of 40C deltaT and 6 m/s (13.4
mph) windspeed, these coefficients would increase the
infiltration rate by a factor of 2.75.
In DOE-2 (the other EnergyPlus predecessor), the air change
method defaults are (adjusted to SI units) 0, 0, 0.224
(windspeed), 0. With these coefficients, the summer conditions
above would give a factor of 0.75, and the winter conditions
would give 1.34. A windspeed of 4.47 m/s (10 mph) gives a
factor of 1.0.
The source of the BLAST defaults is noted in the BLAST
documentation as:
“Empirical equation and the coefficient default were
determined from ASHRAE journal articles and other data on the
effects of outdoor weather conditions.”
The source of the DOE-2 defaults is based on examining the
infiltration relationships described in the ASHRAE
Handbook of Fundamentals.
The local outdoor dry-bulb temperature used in the above
basic equation (Todb) is typically a function of
the height of the zone centroid above ground. The
corresponding zone name is given in the second field. The
local outdoor dry-bulb temperature calculation procedure is
described in the “Local Outdoor Air Temperature Calculation”
section of the Engineering Reference.
The local outdoor wind speed used in the above basic
equation (WindSpeed) is also a function of the height of the
zone centroid above ground. The corresponding zone name is
given in the second field. The local outdoor wind speed
calculation procedure is described in the “Local Wind Speed
Calculation” section of the Engineering Reference.
Note: When the value of the Wind Speed Profile Exponent
field in the Site:HeightVariation
object is equal to 0.0, the local wind speed is always equal
to the wind speed given in the weather data and will not be
dependent on zone centroid height. Similarly, if the value of
the Air Temperature Gradient Coefficient is set equal to 0,
the local air dry-bulb temperature is also always equal to the
air dry-bulb temperature given in the weather data and will
not be dependent on zone centroid height.
One or more ventilation objects (i.e., ZoneVentilation:DesignFlowRate
and/or ZoneVentilation:WindandStackOpenArea) can be defined
for each zone, and the resulting ventilation rate for the zone
will simply be the summation of the flow rates specified by
the ventilation objects.
More advanced ventilation calculations are possible using
the EnergyPlus AirflowNetwork model.
The name of the ZoneVentilation:DesignFlowRate
object.
Field: Zone or ZoneList
Name[LINK]
This field is the name of the zone (ref: Zone) or ZoneList
(ref: ZoneList) and attaches a particular ventilation
statement to a thermal zone or set of thermal zones in the
building. When the ZoneList
option is used then this ventilation definition is applied to
each of the zones in the zone list effecting a global
definition for the amount of infiltration flow rate in the
zone. The Zonelist option can be used effectively with the
flow/area, flow/person, or airchanges/hour of the Design Flow
Rate Calculation Method.
The name of the actual ventilation object becomes
and
should be less than the standard length (100 characters) for a
name field. If it is greater than this standard length, it may
be difficult to specify in output reporting as it will be
truncated. A warning will be shown if the generated name is
greater than 100 characters. If it duplicates another such
concatenated name, there will be a severe error and terminate
the run.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the maximum design volume flow rate
(Vdesign) (see Design Flow Rate Calculation Method
field and related subsequent fields). This fraction between
0.0 and 1.0 is noted as Fschedule in the above
equation.
Field:
Design Flow Rate Calculation Method[LINK]
This field is a key/choice field that tells which of the
next four fields are filled and is descriptive of the method
for calculating the design volume flow rate. The key/choices
are:
- Flow/Zone
- With this choice, the method used will be a straight
insertion of the design volume flow rate. (The Design Flow
Rate field should be filled.)
- Flow/Area
- With this choice, the method used will be a factor per
floor area of the zone. (The Flow per Zone Floor Area field
should be filled).
- Flow/Person
- With this choice, the method used will be a factor per
nominal number of people in the zone. (The Flow per Person
field should be filled).
- AirChanges/Hour
- With this choice, the method used will be the number of
air changes per hour for the infiltration amount. This factor,
along with the Zone Volume, will be used to determine the
Design Flow Rate. (The Air Changes per Hour field should be
filled).
Field: Design Flow Rate[LINK]
This field denotes the full design volume flow rate
(m3/s). The previous field should choose
“flow/zone” as the choice. The design volume flow rate (noted
as Vdesign in the above equation) is the maximum
amount of ventilation expected at design conditions. The
design value is modified by the schedule fraction (see Field:
Schedule Name) and user specified coefficients (see four
“coefficient” fields below).
Field: Flow Rate
per Zone Floor Area[LINK]
This factor (m3/s-m2) is used, along
with the Zone
Area to determine the maximum Design Volume Flow Rate as
described in the Design Volume Flow Rate field. The choice
from the method field should be “flow/area”.
Field: Flow Rate per
Person[LINK]
This factor (m3/s-person) is used, along with
the nominal (maximum) number of occupants (people) in the Zone
to determine the maximum Design Volume Flow Rate as described
in the Design Volume Flow Rate field. The choice from the
method field should be “flow/person”.
Field: Air Changes per
Hour[LINK]
- With this choice, the method used will be the number of
air changes per hour for the ventilation amount. This factor,
along with the Zone Volume, will be used to determine the
Design Flow Rate. The choice from the method field should be
“AirChanges/Hour”.
Field: Ventilation Type[LINK]
This alpha character string defines the type of ventilation
as one of the following options: Natural, Exhaust, Intake, or
Balanced. Natural ventilation is assumed to be air
movement/exchange as a result of openings in the building
façade and will not consume any fan energy. Values for fan
pressure and efficiency for natural ventilation are ignored.
For either Exhaust or Intake, values for fan pressure and
efficiency define the fan electric consumption. For Natural
and Exhaust ventilation, the conditions of the air entering
the space are assumed to be equivalent to outside air
conditions. For Intake and Balanced ventilation, an
appropriate amount of fan heat is added to the entering air
stream. For Balanced ventilation, both an intake fan and an
exhaust fan are assumed to co-exist, both having the same flow
rate and power consumption (using the entered values for fan
pressure rise and fan total efficiency). Thus, the fan
electric consumption for Balanced ventilation is twice that
for the Exhaust or Intake ventilation types which employ only
a single fan.
Field: Fan Pressure Rise[LINK]
This is the pressure rise experienced across the fan in
Pascals (N/m2). This is a function of the fan and
plays a role in determining the amount of energy consumed by
the fan.
Field: Fan Total
Efficiency[LINK]
This value is the overall efficiency of the fan, i.e., the
ratio of the power delivered to the fluid to the electrical
input power. It is the product of the motor efficiency and the
impeller efficiency. The motor efficiency is the power
delivered to the shaft divided by the electrical power input
to the motor. The impeller efficiency is power delivered to
the fluid (air) divided by the shaft power. The power
delivered to the fluid is the mass flow rate of the air
multiplied by the pressure rise divided by the air density.
This input value must be between 0 and 1.”
Field: Constant
Term Coefficient[LINK]
This number is the “A” parameter in the above ventilation
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter, however, is a constant under all conditions and is
not modified by any environmental effect. As a result, it is
dimensionless.
Field:
Temperature Term Coefficient[LINK]
This number is the “B” parameter in the above ventilation
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter is modified by the temperature difference between
the outdoor and indoor air dry-bulb temperatures. The units
for this parameter are inverse Celsius.
Field: Velocity
Term Coefficient[LINK]
This number is the “C” parameter in the above ventilation
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter is modified by the speed of wind being experienced
outside the building. The units for this parameter are
s/m.
Field:
Velocity Squared Term Coefficient[LINK]
This number is the “D” parameter in the above ventilation
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter is modified by square of the speed of wind being
experienced outside the building. The units for this parameter
are s2/m2.
Field: Minimum
Indoor Temperature[LINK]
This is the indoor temperature (in Celsius) below which
ventilation is shutoff. The minimum value for this field is
-100.0C and the maximum value is 100.0C. The default value is
-100.0C if the field is left blank. This lower temperature
limit is intended to avoid overcooling a space and thus result
in a heating load. For example, if the user specifies a
minimum temperature of 20C, ventilation is assumed to be
available if the zone air temperature is above 20C. If the
zone air temperature drops below 20C, then ventilation is
automatically turned off.
Field:
Minimum Indoor Temperature Schedule Name[LINK]
This alpha field defines the name of a schedule (ref.
Schedule objects) which contains the minimum indoor
temperature (in Celsius) below which ventilation is shutoff as
a function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field and has the same functionality as
the Minimum Indoor Temperature field. If the user enters a
valid schedule name, the minimum temperature values specified
in this schedule will override the constant value specified in
the Minimum Indoor Temperature field.
Field: Maximum
Indoor Temperature[LINK]
This is the indoor temperature (in Celsius) above which
ventilation is shutoff. The minimum value for this field is
-100.0C and the maximum value is 100.0C. The default value is
100.0C if the field is left blank. This upper temperature
limit is intended to avoid overheating a space and thus result
in a cooling load. For example, if the user specifies a
maximum temperature of 28C, ventilation is assumed to be
available if the zone air temperature is below 28C. If the
zone air temperature increases to 28C, then ventilation is
automatically turned off.
Field:
Maximum Indoor Temperature Schedule Name[LINK]
This alpha field defines the name of a schedule (ref.
Schedule objects) which contains the maximum indoor
temperature (in Celsius) above which ventilation is shutoff as
a function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field and has the same functionality as
the Maximum Indoor Temperature field. If the user enters a
valid schedule name, the maximum temperature values specified
in this schedule will override the constant value specified in
the Maximum Indoor Temperature field.
Field: Delta Temperature[LINK]
This is the temperature difference (in Celsius) between the
indoor and outdoor air dry-bulb temperatures below which
ventilation is shutoff. The minimum value for this field is
-100.0C and the default value is also -100.0C if the field is
left blank. This field allows ventilation to be stopped if the
temperature outside is too warm and could potentially heat the
space. For example, if the user specifies a delta temperature
of 2C, ventilation is assumed to be available if the outside
air temperature is at least 2C cooler than the zone air
temperature. If the outside air dry-bulb temperature is less
than 2C cooler than the indoor dry-bulb temperature, then
ventilation is automatically turned off.
The values for this field can include negative numbers.
This allows ventilation to occur even if the outdoor
temperature is above the indoor temperature. The Delta
Temperature is used in the code in the following way:
IF ((IndoorTemp - OutdoorTemp) < DeltaTemperature) Then ventilation is not allowed.
Thus, if a large negative number is input for
DeltaTemperature, the ventilation can be kept on even if the
outdoor temperature is greater than the indoor temperature.
This is useful for uncontrolled natural ventilation (open
windows) or as a way to estimate the effect of required
ventilation air for load calculations.
Field: Delta
Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the temperature difference
(in Celsius) between the indoor and outdoor air dry-bulb
temperatures below which ventilation is shutoff as a function
of time. The minimum temperature difference value in the
schedule can be -100C. This field is an optional field and has
the same functionality as the Delta Temperature field. If the
user enters a valid schedule name, the delta temperature
values specified in this schedule will override the constant
value specified in the Delta Temperature field.
Field: Minimum
Outdoor Temperature[LINK]
This is the outdoor temperature (in Celsius) below which
ventilation is shut off. The minimum value for this field is
-100.0C and the maximum value is 100.0C. The default value is
-100.0C if the field is left blank. This lower temperature
limit is intended to avoid overcooling a space, which could
result in a heating load.
Field:
Minimum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the minimum outdoor
temperature (in Celsius) below which ventilation is shutoff as
a function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field and has the same functionality as
the Minimum Outdoor Temperature field. If the user enters a
valid schedule name, the temperature values in this schedule
will override the constant value specified in the Minimum
Outdoor Temperature field.
Field: Maximum
Outdoor Temperature[LINK]
This is the outdoor temperature (in Celsius) above which
ventilation is shut off. The minimum value for this field is
-100.0C and the maximum value is 100.0C. The default value is
100.0C if the field is left blank. This upper temperature
limit is intended to avoid overheating a space, which could
result in a cooling load.
Field:
Maximum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the minimum outdoor
temperature (in Celsius) above which ventilation is shutoff as
a function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field and has the same functionality as
the Maximum Outdoor Temperature field. If the user enters a
valid schedule name, the temperature values in this schedule
will override the constant value specified in the Maximum
Outdoor Temperature field.
Field: Maximum Wind
Speed[LINK]
This is the wind speed (m/s) above which ventilation is
shut off. This can help simulate conditions where one would
normally close windows to avoid chaos in a space (papers
blowing around, etc.).
Two IDF examples are provided below:
ZoneVentilation:DesignFlowRate,
Ventilation 1, !- Name
ZONE 2, !- Zone Name
Simple Vent, !- Schedule Name
Flow/Zone, !- Design Volume Flow Rate calculation method
6.131944, !- Design Volume Flow Rate {m3/s}
, !- Volume Flow Rate per area {m3/s/m2}
, !- Volume Flow Rate per person {m3/s/person}
, !- Air Changes Per Hour
INTAKE, !- Ventilation Type
400.0, !- Fan Pressure Rise{Pa}
0.9, !- Fan Total Efficiency
0.6060000 , !- Constant Term Coefficient
2.0199999E-02, !- Temperature Term Coefficient
5.9800001E-04, !- Velocity Term Coefficient
0.0000000E+00!- Velocity Squared Term Coefficient
18.0, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
1.0; !- Delta temperature {C}
ZoneVentilation:DesignFlowRate,
SPACE1-1 Ventl 1, !- Name
SPACE1-1, !- Zone Name
NightVentSched, !- SCHEDULE Name
Flow/Zone, !- Design Volume Flow Rate calculation method
.05295, !- Design Volume Flow Rate {m3/s}
, !- Volume Flow Rate per area {m3/s/m2}
, !- Volume Flow Rate per person {m3/s/person}
, !- Air Changes Per Hour
Intake, !- Ventilation Type
67., !- Fan Pressure Rise
.7, !- Fan Total Efficiency
1, !- Constant Term Coefficient
0, !- Temperature Term Coefficient
0, !- Velocity Term Coefficient
0, !- Velocity Squared Term Coefficient
, !- Minimum Indoor Temperature {C}
MinIndoorTemp, !- Minimum Indoor Temperature Schedule Name
, !- Maximum Indoor Temperature {C}
MaxIndoorTemp, !- Maximum Indoor Temperature Schedule Name
, !- Delta Temperature {deltaC}
DeltaTemp, !- Delta Temperature Schedule Name
, !- Minimum Outdoor Temperature {C}
MinOutdoorTemp, !- Minimum Outdoor Temperature Schedule Name
, !- Maximum Outdoor Temperature {C}
MaxOutdoorTemp, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum WindSpeed {m/s}
Global Ventilation example:
Zonelist, West-East Zones, West Zone, East Zone;
ZoneVentilation:DesignFlowRate,
West-East Zones Ventilation, !- Name
West-East Zones, !- Zone or ZoneList Name
VentSched, !- Schedule Name
AirChanges/Hour, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow Rate per Zone Floor Area {m3/s-m2}
, !- Flow Rate per Person {m3/s-person}
1.7, !- Air Changes per Hour
Intake, !- Ventilation Type
67., !- Fan Pressure Rise {Pa}
0.7, !- Fan Total Efficiency
1, !- Constant Term Coefficient
0, !- Temperature Term Coefficient
0, !- Velocity Term Coefficient
0, !- Velocity Squared Term Coefficient
, !- Minimum Indoor Temperature {C}
MinIndoorTemp, !- Minimum Indoor Temperature Schedule Name
, !- Maximum Indoor Temperature {C}
MaxIndoorTemp, !- Maximum Indoor Temperature Schedule Name
, !- Delta Temperature {deltaC}
DeltaTemp, !- Delta Temperature Schedule Name
, !- Minimum Outdoor Temperature {C}
MinOutdoorTemp, !- Minimum Outdoor Temperature Schedule Name
, !- Maximum Outdoor Temperature {C}
MaxOutdoorTemp, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea[LINK]
For this model, the ventilation air flow rate is a function
of wind speed and thermal stack effect, along with the area of
the opening being modeled. This object can be used alone or in
combination with ZoneVentilation:DesignFlowRate
objects. This model is intended for simplified ventilation
calculations as opposed to the more detailed ventilation
investigations that can be performed with the AirflowNetwork
model. Using the “Wind and Stack with Open Area” model, the
natural ventilation flow rate can be controlled by a
multiplier fraction schedule applied to the user-defined
opening area and through the specification of minimum, maximum
and delta temperatures. The temperatures can be either single
constant values for the entire simulation or schedules which
can vary over time. The equation used to calculate the
ventilation rate driven by wind is:
\[{Q_w} =
{C_w}{A_{opening}}{F_{schedule}}V\]
where,
Qw= Volumetric air flow rate driven by
wind [m3/s]
Cw= Opening effectiveness
[dimensionless]
Aopening= Opening area
[m2]
Fschedule = Open area fraction
[user-defined schedule value, dimensionless]
V= Local wind speed [m/s]
The equation used to calculate the ventilation rate due to
stack effect is:
\[{Q_s} =
{C_D}{A_{opening}}{F_{schedule}}\sqrt {2g\Delta
{H_{NPL}}(|{T_{zone}} - {T_{odb}}|/{T_{zone}})}\]
where,
Qs= Volumetric air flow rate due to
stack effect [m3/s]
CD= Discharge coefficient for opening
[dimensionless]
Aopening= Opening area
[m2]
Fschedule = Open area fraction
[user-defined schedule value, dimensionless]
ΔHNPL= Height from midpoint of lower
opening to the neutral pressure level [m].
Estimation of this value is difficult; refer to Chapter 16
of the 2009 ASHRAE Handbook of Fundamentals for guidance.
Tzone= Zone
air dry-bulb temperature [K]
Todb= Local outdoor air dry-bulb
temperature [K]
The total ventilation rate calculated by this model is the
quadrature sum of the wind and stack air flow components:
\[Ventilatio{n_{WindAndStack}} =
\sqrt {{Q_s}^2 + {Q_w}^2}\]
The local outdoor air dry-bulb temperature used in the
stack effect equation (Todb) is typically a
function of the height of the zone centroid above ground. The
corresponding zone name is given in the second field. The
local outdoor air dry-bulb temperature calculation procedure
is described in the “Local Outdoor Air Temperature
Calculation” section of the Engineering Reference.
The local outdoor wind speed used in the above wind-driven
equation (V) is also a function of the height of the zone
centroid above ground. The corresponding zone name is given in
the second field. The local outdoor wind speed calculation
procedure is described in the “Local Wind Speed Calculation”
section of the Engineering Reference.
Note: When the value of the Wind Speed Profile Exponent
field in the Site:HeightVariation
object is equal to 0.0, the local wind speed is always equal
to the wind speed given in the weather data and will not be
dependent on zone centroid height. Similarly, if the value of
the Air Temperature Gradient Coefficient is set equal to 0,
the local air dry-bulb temperature is also always equal to the
air dry-bulb temperature given in the weather data and will
not be dependent on zone centroid height.
One or more ventilation objects (i.e., ZoneVentilation:DesignFlowRate
and/or ZoneVentilation:WindandStackOpenArea) can be defined
for each zone, and the resulting ventilation rate for the zone
will simply be the summation of the flow rates specified by
the ventilation objects.
More advanced ventilation calculations are possible using
the EnergyPlus AirflowNetwork model.
The name of the ZoneVentilation:WindandStackOpenArea
object.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches
a particular ventilation statement to a thermal zone in the
building.
Field: Opening Area[LINK]
This is the opening area exposed to outdoors
(m2) in a zone.
Field:
Opening Area Fraction Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule)
which modifies the Opening Area value (see previous field).
The schedule values must be any positive number between 0 and
1 as a fraction. The actual opening area in a zone for a
particular simulation time step is defined as the product of
the Opening Area input field and the value specified by the
schedule named in this input field.
Field: Opening
Effectiveness[LINK]
This field is the opening effectiveness (Cw).
The value must be between 0.0 and 1.0 or the value can be
autocalculated. If a real value is input, that constant value
will be used in the calculations. Otherwise, this field can be
left blank (default = Autocalculate) or the user can input
Autocalculate. Based on recommended values
provided in Chapter 16 of the 2009 ASHRAE Handbook of
Fundamentals, Cw = 0.55 for perpendicular winds and
Cw = 0.3 for diagonal winds. For Autocalculate, any
angles between perpendicular and diagonal are linearly
interpolated between 0.3 and 0.55 by the model.
Field: Effective Angle[LINK]
This is the angle in degrees counting from the North
clockwise to the opening outward normal. The value must be
between 0 and 360, with the default being 0 if this input
field is left blank. The Effective Angle is 0 if the opening
outward normal faces North, 90 if faces East, 180 if faces
South, and 270 if faces West. The value is fixed and
independent of coordinate system defined in the GlobalGeometryRules
object. This input field value is used to calculate the angle
between the wind direction and the opening outward normal to
determine the opening effectiveness values when the input
field Opening Effectiveness = Autocalculate.
Field: Height Difference[LINK]
This is the height difference between the midpoint of the
lower opening and the neutral pressure level in meters. This
value is a required user input.
Note: Estimation of the height difference is difficult for
natural ventilated buildings. Chapter 16 of the 2009 ASHRAE
Handbook of Fundamentals may provide guidance for estimating
the height difference.
Field:
Discharge Coefficient for Opening[LINK]
This is the discharge coefficient for the opening
(CD). The value must be between 0.0 and 1.0, or the
value can be autocalculated. If a real value is input, that
constant value will be used in the calculations. Otherwise,
this field can be left blank (default = Autocalculate) or the
user can input Autocalculate. For
Autocalculate, the program will determine the discharge
coefficient based on the following equation:
\[{C_D} = 0.40 + 0.0045\left|
{{T_{zone}} - {T_{odb}}} \right|\]
Field: Minimum
Indoor Temperature[LINK]
This is the indoor temperature (in Celsius) below which
ventilation is shutoff. The minimum value for this field is
-100.0C and the maximum value is 100.0C. The default value is
-100.0C if the field is left blank. This lower temperature
limit is intended to avoid overcooling a space and thus result
in a heating load. For example, if the user specifies a
minimum temperature of 20C, ventilation is assumed to be
available if the zone air temperature is above 20C. If the
zone air temperature drops below 20C, then ventilation is
automatically turned off.
Field:
Minimum Indoor Temperature Schedule Name[LINK]
This alpha field defines the name of a schedule (ref.
Schedule objects) which contains the minimum indoor
temperature (in Celsius) below which ventilation is shutoff as
a function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field and has the same functionality as
the Minimum Indoor Temperature field. If the user enters a
valid schedule name, the minimum temperature values specified
in this schedule will override the constant value specified in
the Minimum Indoor Temperature field.
Field: Maximum
Indoor Temperature[LINK]
This is the indoor temperature (in Celsius) above which
ventilation is shutoff. The minimum value for this field is
-100.0C and the maximum value is 100.0C. The default value is
100.0C if the field is left blank. This upper temperature
limit is intended to avoid overheating a space and thus result
in a cooling load. For example, if the user specifies a
maximum temperature of 28C, ventilation is assumed to be
available if the zone air temperature is below 28C. If the
zone air temperature increases to 28C, then ventilation is
automatically turned off.
Field:
Maximum Indoor Temperature Schedule Name[LINK]
This alpha field defines the name of a schedule (ref.
Schedule objects) which contains the maximum indoor
temperature (in Celsius) above which ventilation is shutoff as
a function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field and has the same functionality as
the Maximum Indoor Temperature field. If the user enters a
valid schedule name, the maximum temperature values specified
in this schedule will override the constant value specified in
the Maximum Indoor Temperature field.
Field: Delta
Temperature[LINK]
This is the temperature difference (in Celsius) between the
indoor and outdoor air dry-bulb temperatures below which
ventilation is shutoff. The minimum value for this field is
-100.0C and the default value is also -100.0C if the field is
left blank. This field allows ventilation to be stopped if the
temperature outside is too warm and could potentially heat the
space. For example, if the user specifies a delta temperature
of 2C, ventilation is assumed to be available if the outside
air temperature is at least 2C cooler than the zone air
temperature. If the outside air dry-bulb temperature is less
than 2C cooler than the indoor dry-bulb temperature, then
ventilation is automatically turned off.
The values for this field can include negative numbers.
This allows ventilation to occur even if the outdoor
temperature is above the indoor temperature. The Delta
Temperature is used in the code in the following way:
IF ((IndoorTemp - OutdoorTemp) < DeltaTemperature) Then ventilation is not allowed.
Thus, if a large negative number is input for
DeltaTemperature, the ventilation can be kept on even if the
outdoor temperature is greater than the indoor temperature.
This is useful for uncontrolled natural ventilation (open
windows) or as a way to estimate the effect of required
ventilation air for load calculations.
Field: Delta
Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the temperature difference
(in Celsius) between the indoor and outdoor air dry-bulb
temperatures below which ventilation is shutoff as a function
of time. The minimum temperature difference value in the
schedule can be -100C. This field is an optional field and has
the same functionality as the Delta Temperature field. If the
user enters a valid schedule name, the delta temperature
values specified in this schedule will override the constant
value specified in the Delta Temperature field.
Field: Minimum
Outdoor Temperature[LINK]
This is the outdoor temperature (in Celsius) below which
ventilation is shut off. The minimum value for this field is
-100.0C and the maximum value is 100.0C. The default value is
-100.0C if the field is left blank. This lower temperature
limit is intended to avoid overcooling a space, which could
result in a heating load.
Field:
Minimum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the minimum outdoor
temperature (in Celsius) below which ventilation is shutoff as
a function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field and has the same functionality as
the Minimum Outdoor Temperature field. If the user enters a
valid schedule name, the temperature values in this schedule
will override the constant value specified in the Minimum
Outdoor Temperature field.
Field: Maximum
Outdoor Temperature[LINK]
This is the outdoor temperature (in Celsius) above which
ventilation is shut off. The minimum value for this field is
-100.0C and the maximum value is 100.0C. The default value is
100.0C if the field is left blank. This upper temperature
limit is intended to avoid overheating a space, which could
result in a cooling load.
Field:
Maximum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the minimum outdoor
temperature (in Celsius) above which ventilation is shutoff as
a function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field and has the same functionality as
the Maximum Outdoor Temperature field. If the user enters a
valid schedule name, the temperature values in this schedule
will override the constant value specified in the Maximum
Outdoor Temperature field.
Field: Maximum Wind
Speed[LINK]
This is the wind speed (m/s) above which ventilation is
shut off. This can help simulate conditions where one would
normally close windows to avoid chaos in a space (papers
blowing around, etc.).
An IDF example is provided below:
ZoneVentilation:WindandStackOpenArea,
ZONE 3 Ventl 1, !- Name
ZONE 3, !- Zone Name
0.5, !- Opening Area {m2}
Constant, !- Opening Area Fraction Schedule Name
AutoCalculate, !- Opening Effectiveness
0.0, !- Effective Angle {deg}
1.0, !- Height Difference {m}
AutoCalculate, !- Discharge Coefficient for Opening
18.0, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
1.0; !- Delta Temperature {deltaC}
**
Current ventilation output variables:
HVAC,Sum,Zone Ventilation Sensible Heat Loss Energy [J]
HVAC,Sum,Zone Ventilation Sensible Heat Gain Energy [J]
HVAC,Sum,Zone Ventilation Latent Heat Loss Energy [J]
HVAC,Sum,Zone Ventilation Latent Heat Gain Energy [J]
HVAC,Sum,Zone Ventilation Total Heat Loss Energy [J]
HVAC,Sum,Zone Ventilation Total Heat Gain Energy [J]
HVAC,Average,Zone Ventilation Current Density Volume Flow Rate [m3/s]
HVAC,Average,Zone Ventilation Standard Density Volume Flow Rate [m3/s]
HVAC,Sum,Zone Ventilation Current Density Volume [m3]
HVAC,Sum,Zone Ventilation Standard Density Volume [m3]
HVAC,Sum,Zone Ventilation Mass [kg]
HVAC,Sum,Zone Ventilation Mass Flow Rate [kg/s]
HVAC,Average,Zone Ventilation Air Change Rate [ach]
HVAC,Sum,Zone Ventilation Fan Electric Energy [J]
HVAC,Average,Zone Ventilation Air Inlet Temperature [C]
Note: If ZoneVentilation:* objects and ZoneAirBalance:OutdoorAir
(with Air Balance Method = Quadrature) objects reference the
same Zone
Name, the above ventilation output variables will not be
reported for that zone. Instead, output variables for zone
outdoor air flow will be reported by the corresponding ZoneAirBalance:OutdoorAir
object.
Zone
Ventilation Sensible Heat Loss Energy [J][LINK]
The sensible (temperature) heat loss that occurs when the
ventilation inlet air temperature < zone air temperature.
If multiple ventilation objects are specified for a particular
zone, the ventilation inlet air temperature is from all ZoneVentilation:DesignFlowRate
and ZoneVentilation:WindandStackOpenArea
objects specified for the zone.
Zone
Ventilation Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat gain that occurs when the
ventilation inlet air temperature >= zone air temperature.
If multiple ventilation objects are specified for a particular
zone, the ventilation inlet air temperature is from all ZoneVentilation:DesignFlowRate
and ZoneVentilation:WindandStackOpenArea
objects specified for the zone.
Zone
Ventilation Latent Heat Loss Energy [J][LINK]
The latent heat loss that occurs when the Ventilation air
humidity ratio (outdoor) < zone air humidity ratio from all
ZoneVentilation:DesignFlowRate
and ZoneVentilation:WindandStackOpenArea
objects specified for the zone.
Zone
Ventilation Latent Heat Gain Energy [J][LINK]
The latent heat gain that occurs when the Ventilation air
humidity ratio (outdoor) >= zone air humidity ratio from
all ZoneVentilation:DesignFlowRate
and ZoneVentilation:WindandStackOpenArea
objects specified for the zone.
Zone
Ventilation Total Heat Loss Energy [J][LINK]
The total heat loss that occurs when the sum of Zone
Ventilation Sensible Heat Gain Energy and Zone
Ventilation Latent Heat Gain Energy < the sum of Zone
Ventilation Sensible Heat Loss Energy and Zone
Ventilation Latent Heat Loss Energy.
Zone
Ventilation Total Heat Gain Energy [J][LINK]
The total heat gain that occurs when the sum of Zone
Ventilation Sensible Heat Gain Energy and Zone
Ventilation Latent Heat Gain Energy >= the sum of Zone
Ventilation Sensible Heat Loss Energy and Zone
Ventilation Latent Heat Loss Energy.
Zone
Ventilation Current Density Volume [m3][LINK]
Zone
Ventilation Current Density Volume Flow Rate [m3/s][LINK]
These outputs are the total volume and volume flow rate of
ventilation air based on the current density of zone air.
Zone
Ventilation Standard Density Volume [m3][LINK]
Zone
Ventilation Standard Density Volume Flow Rate [m3/s][LINK]
These outputs are the total volume and volume flow rate of
ventilation air based on the standard density of air. Standard
density in EnergyPlus corresponds to 20ºC drybulb, dry air,
and nominally adjusted for elevation.
Zone Ventilation Mass
[kg][LINK]
This output is the total mass flow into a particular zone
from outdoors.
Zone Ventilation
Mass Flow Rate [kg/s][LINK]
This output is the total mass flow rate into a particular
zone from outdoors.
Zone Ventilation
Air Change Rate [ach][LINK]
The volume flow rate of the ventilation air in air changes
per hour.
Zone
Ventilation Fan Electric Energy [J][LINK]
The fan electrical consumption for Intake or Exhaust
ventilation types (for ZoneVentilation:DesignFlowRate
objects only).
Zone
Ventilation Air Inlet Temperature [C][LINK]
This is equal to the outdoor air temperature except when
INTAKE fan power is included (for ZoneVentilation:DesignFlowRate
objects only). When intake fan power is used, then the
additional heat due to the fan is added to the outdoor
temperature and this will be reported as the inlet air
temperature. If multiple ventilation objects are specified for
a particular zone, the reported value is the mass flow
weighted temperature for the multiple ventilation objects
specified for this zone.
ZoneAirBalance:OutdoorAir[LINK]
This model calculates a combined zone outdoor airflow by
including interactions between mechanical ventilation,
infiltration and duct leakage. It is mainly applied to a
single zone (e.g., residential) building. The model combines
all outdoor airflows from ZoneInfiltration and ZoneVentilation
objects in the same zone. This object also includes the
induced outdoor airflows due to unbalanced duct leakage, and
unbalanced outdoor airflows introduced by unbalanced airflows
from ZoneHVAC:EnergyRecoveryVentilator
objects when the exhaust airflow is greater than the supply
outdoor airflow. This model is intended for simplified outdoor
airflow calculations as opposed to the more detailed outdoor
airflow investigations that can be performed with the
AirflowNetwork model. The equation used to calculate the
combined zone outdoor airflow is:
\[Q = \sqrt {{Q_n}^2 +
{Q_{u,v}}^2 + {Q_{u,l}}^2} + {Q_{b,v}}\]
where,
Q= Combined outdoor airflow with infiltration,
balanced and unbalanced outdoor air flows, and unbalanced duct
leakage [m3/s]
Qn= Natural infiltration airflow from
ZoneInfiltration:* objects [m3/s]
Qb,v= Balanced ventilation airflow,
excluding infiltration [m3/s]
Qu,v= Unbalanced ventilation airflow,
excluding infiltration [m3/s]
Qu,l= Unbalanced duct leakage: the
difference between supply and return leaks
[m3/s]
This object cannot be used simultaneously with the
EnergyPlus AirflowNetwork model. If the AirflowNetwork model
is active for a simulation time step, the Air Balance Method
is reset to “None” for that time step. More advanced outdoor
airflow calculations are possible using the EnergyPlus
AirflowNetwork model.
This object does not combine any airflows from Fan:ZoneExhaust
objects and is independent of HVAC equipment operation.
This object will not work with the AvailabilityManager:HybridVentilation
object in the same zone, when the Simple Airflow Control Type
Schedule Name is provided in the HybridVentilation object. For
this case, the Air Balance Method is reset to “None”.
The name of the ZoneOutdoorAir:Combined object.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches
a combined outdoor airflow statement to a thermal zone in the
building.
Field: Air Balance
Method[LINK]
This choice field determines the air balance method. Two
choices are Quadrature and None. If Quadrature, the combined
zone outdoor air flow is calculated based on the above
equation. If None, no combining of outdoor air will be
performed (i.e., any ZoneInfiltration:* and ZoneVentilation:*
objects specified for this zone are simulated
individually).
Field:
Induced Outdoor Air Due to Unbalanced Duct Leakage[LINK]
This is the induced outdoor airflow rate, in
m3/s, due to unbalanced duct leakage. If left
blank, the default value is 0.
Field:
Induced Outdoor Air Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule)
which modifies the induced outdoor airflow rate value (see
previous field). The schedule values must be any positive
number between 0 and 1 as a fraction. The actual induced
outdoor airflow rate in a zone for a particular simulation
time step is defined as the product of the Induced Outdoor Air
Due to Unbalanced Duct
Leakage input field and the value specified by the schedule
named in this input field.
Note: Since this object is independent of HVAC operation,
the inputs for the last two fields should be carefully
selected to match HVAC system operation schedules.
An IDF example is provided below:
ZoneAirBalance:OutdoorAir,
ZONE 2 Balance 1, !- Name
ZONE 2, !- Zone Name
Quadrature, !- Air Balance Method
0.00, !- Induced Outdoor Air Due to Unbalanced Duct Leakage {m3/s}
Constant; !- Induced Outdoor Air Schedule Name
ZoneAirBalance:OutdoorAir
output variables will be provided when the Air Balance Method
is Quadrature. Output variables from the associated
ZoneVentilation:* and ZoneInfiltration:* objects for the same
zone will not be produced when ZoneAirBalance:OutdoorAir
output variables are available. If the Air Balance Method =
None, then no ZoneAirBalance:OutputAir outputs will be
produced and the associated ZoneVentilation:* and
ZoneInfiltration:* objects will specify their output variables
for the zone.
HVAC,Sum,Zone Combined Outdoor Air Sensible Heat Loss Energy [J]
HVAC,Sum,Zone Combined Outdoor Air Sensible Heat Gain Energy [J]
HVAC,Sum,Zone Combined Outdoor Air Latent Heat Loss Energy [J]
HVAC,Sum,Zone Combined Outdoor Air Latent Heat Gain Energy [J]
HVAC,Sum,Zone Combined Outdoor Air Total Heat Loss Energy [J]
HVAC,Sum,Zone Combined Outdoor Air Total Heat Gain Energy [J]
HVAC,Average,Zone Combined Outdoor Air Current Density Volume Flow Rate [m3/s]
HVAC,Average,Zone Combined Outdoor Air Standard Density Volume Flow Rate [m3/s]
HVAC,Sum,Zone Combined Outdoor Air Current Density Volume [m3]
HVAC,Sum,Zone Combined Outdoor Air Standard Density Volume [m3]
HVAC,Sum,Zone Combined Outdoor Air Mass [kg]
HVAC,Sum,Zone Combined Outdoor Air Mass Flow Rate [kg/s]
HVAC,Average, Zone Combined Outdoor Air Changes per Hour [ach]
HVAC,Sum, Zone Combined Outdoor Air Fan Electric Energy [J]
Zone
Combined Outdoor Air Sensible Heat Loss Energy [J][LINK]
The sensible (temperature) heat loss that occurs when the
outdoor air temperature < zone air temperature.
Zone
Combined Outdoor Air Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat gain that occurs when the
outdoor air temperature >= zone air temperature.
Zone
Combined Outdoor Air Latent Heat Loss Energy [J][LINK]
The latent heat loss that occurs when the outdoor air
humidity ratio < zone air humidity ratio.
Zone
Combined Outdoor Air Latent Heat Gain Energy [J][LINK]
The latent heat gain that occurs when the outdoor air
humidity ratio >= zone air humidity ratio.
Zone
Combined Outdoor Air Total Heat Loss Energy [J][LINK]
The total heat loss that occurs when the sum of Zone
Combined Outdoor Air Sensible Heat Gain Energy and Zone
Combined Outdoor Air Latent Heat Gain Energy < the sum of
Zone
Combined Outdoor Air Sensible Heat Loss Energy and Zone
Combined Outdoor Air Latent Heat Loss Energy.
Zone
Combined Outdoor Air Total Heat Gain Energy [J][LINK]
The total heat gain that occurs when the sum of Zone
Combined Outdoor Air Sensible Heat Gain Energy and Zone
Combined Outdoor Air Latent Heat Gain Energy >= the sum of
Zone
Combined Outdoor Air Sensible Heat Loss Energy and Zone
Combined Outdoor Air Latent Heat Loss Energy.
Zone
Combined Outdoor Air Current Density Volume [m3][LINK]
Zone
Combined Outdoor Air Current Density Volume Flow Rate
[m3/s][LINK]
These outputs are the total volume and volume flow rate of
outdoor air based on the current density of zone air.
Zone
Combined Outdoor Air Standard Density Volume [m3][LINK]
Zone
Combined Outdoor Air Standard Density Volume Flow Rate
[m3/s][LINK]
These outputs are the total volume and volume flow rate of
outdoor air based on the standard density of air. Standard
density in EnergyPlus corresponds to 20ºC drybulb, dry air,
and nominally adjusted for elevation.
Zone Combined
Outdoor Air Mass [kg][LINK]
This output is the total mass flow into a particular zone
from outdoors.
Zone
Combined Outdoor Air Mass Flow Rate [kg/s][LINK]
This output is the total mass flow rate into a particular
zone from outdoors.
Zone
Combined Outdoor Air Changes per Hour [ach][LINK]
The volume flow rate of the ventilation air in air changes
per hour.
Zone
Combined Outdoor Air Fan Electric Energy [J][LINK]
The fan electrical consumption for Intake, Exhaust, or
Balanced ventilation types (for
ZoneVentilation:DesignFlowRate
objects used to calculate a combined zone outdoor
airflow).
In EnergyPlus, the ZoneMixing
syntax is intended to allow simplified treatment of air
exchange between zones. Note that this statement only affects
the energy balance of the “receiving” zone and that this
statement will not produce any effect on the “source” zone.
Mixing statements can be complementary and include multiple
zones, but the balancing of flows between zones is left to the
user’s discretion. The use of the Cross Mixing syntax (ref:
Cross Mixing) can allow for automatic balancing of flows and
energy flow rates between zones but is hindered by the
limitation of only a single cross mixing statement per zone.
The use of Refrigeration Door
Mixing syntax (ref: Refrigeration Door
Mixing) automatically balances the flow and energy between two
zones and allows multiple mixing statements per zone. More
advanced mixing calculations are possible using the EnergyPlus
AirflowNetwork model for multi-zone airflow with or without
HVAC system operation. Mixing is entered using the following
syntax.
The name of the ZoneMixing
object.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) receiving
the amount of air being exchanged and attaches a particular
mixing statement to a thermal zone in the building.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the maximum design volume flow rate parameter (see
next field). This fraction between 0.0 and 1.0 modifies the
design level parameter.
Field:
Design Flow Rate Calculation Method[LINK]
This field is a key/choice field that tells which of the
next four fields are filled and is descriptive of the method
for calculating the design volume flow rate. The key/choices
are:
- Flow/Zone
- With this choice, the method used will be a straight
insertion of the design volume flow rate. (The Design Flow
Rate field should be filled.)
- Flow/Area
- With this choice, the method used will be a factor per
floor area of the zone. (The Flow per Zone Floor Area field
should be filled).
- Flow/Person
- With this choice, the method used will be a factor per
nominal number of people in the zone. (The Flow per Person
field should be filled).
- AirChanges/Hour
- With this choice, the method used will be the number of
air changes per hour for the infiltration amount. This factor,
along with the Zone Volume, will be used to determine the
Design Flow Rate. (The Air Changes per Hour field should be
filled).
Field: Design Flow Rate[LINK]
This field denotes the full design volume flow rate
(m3/s). The previous field should choose
“flow/zone” as the choice. The design volume flow rate is the
maximum amount of mixing air expected. The design value is
modified by the schedule fraction (see Field: Schedule Name)
and user specified coefficients (see four “coefficient” fields
below).
Field: Flow
Rate per Zone Floor Area[LINK]
This factor (m3/s-m2) is used, along
with the Zone
Area to determine the maximum Design Volume Flow Rate as
described in the Design Volume Flow Rate field. The choice
from the method field should be “Flow/Area”.
Field: Flow Rate per
Person[LINK]
This factor (m3/s-person) is used, along with
the nominal (maximum) number of occupants (people) in the Zone
to determine the maximum Design Volume Flow Rate as described
in the Design Volume Flow Rate field. The choice from the
method field should be “Flow/Person”.
Field: Air Changes per
Hour[LINK]
- With this choice, the method used will be the number of
air changes per hour for the mixing amount. This factor, along
with the Zone Volume, will be used to determine the Design
Flow Rate. The choice from the method field should be
“AirChanges/Hour”.
Field: Source Zone Name[LINK]
This field is the name of the “source” zone (ref: Zone)
that exhausts the amount of air specified by the design level
and schedule fields to the zone named in the zone name
field.
Field: Delta
Temperature[LINK]
This number controls when mixing air from the source zone
is sent to the receiving zone. This parameter is a temperature
and is expressed in units of Celsius. If this field is
positive, the temperature of the zone from which the air is
being drawn (source zone) must be “Delta Temperature” warmer
than the receiving zone air or else no mixing occurs. If this
field is negative, the temperature of the source zone must be
“Delta Temperature” cooler than the receiving zone air or else
no mixing occurs. If this parameter is zero, mixing occurs
regardless of the relative zone temperatures.
Field: Delta
Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the temperature difference
(in Celsius) between the source zone and receiving zone air
dry-bulb temperatures as a function of time. This field is an
optional field and has the same functionality as the Delta
Temperature field. If the user enters a valid schedule name,
the delta temperature values specified in this schedule will
supersede the constant value specified in the Delta
Temperature field.
Field:
Minimum Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the minimum receiving zone
temperature (in Celsius) below which mixing is shutoff as a
function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
minimum zone temperature control is not applied.
Field:
Maximum Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the maximum receiving zone
temperature (in Celsius) above which mixing is shutoff as a
function of time. The maximum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
maximum zone temperature control is not applied.
Note: The maximum zone temperature when
mixing is shutoff must be greater than or equal to the minimum
zone temperature when mixing is shutoff at any given time.
Otherwise, warnings will be issued and the maximum zone
shutoff temperature will be set to the minimum zone shutoff
temperature.
Field:
Minimum Source Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the minimum source zone
temperature (in Celsius) below which mixing is shutoff as a
function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
minimum source zone temperature control is not applied.
Field:
Maximum Source Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the maximum source zone
temperature (in Celsius) above which mixing is shutoff as a
function of time. The maximum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
maximum source zone temperature control is not applied.
Note: The maximum source zone temperature
when mixing is shutoff must be greater than or equal to the
minimum source zone temperature when mixing is shutoff at any
given time. Otherwise, warnings will be issued and the maximum
source zone shutoff temperature will be set to the minimum
source zone shutoff temperature.
Field:
Minimum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the minimum outdoor
temperature (in Celsius) below which mixing is shutoff as a
function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
minimum outdoor temperature control is not applied.
Field:
Maximum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the maximum outdoor
temperature (in Celsius) above which mixing is shutoff as a
function of time. The maximum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
maximum outdoor temperature control is not applied.
Note: The maximum outdoor temperature when
mixing is shutoff must be greater than or equal to the minimum
outdoor temperature which mixing is shutoff at any given time.
Otherwise, a warning will be issued and the maximum outdoor
shutoff temperature will be set to the minimum outdoor shutoff
temperature.
An IDF Example:
ZoneMixing,
Kitchen_ZN_1_FLR_1 Exhaust Fanmixing_0, !- Name
Kitchen_ZN_1_FLR_1, !- Zone Name
Hours_of_operation, !- Schedule Name
Flow/Zone, !- Design Flow Rate Calculation Method
1.4540, !- Design Level
, !- Volume Flow Rate per Area {m3/s/m2}
, !- Volume Flow Rate Per Person {m3/s/person}
, !- Air Changes per Hour {ACH}
CAFETERIA_ZN_1_FLR_1, !- Source Zone Name
0.0; !- Delta Temperature
HVAC,Sum,Zone Mixing Volume [m3]
HVAC,Sum,Zone Mixing Current Density Volumetric Flow Rate [m3/s]
HVAC,Sum,Zone Mixing Standard Density Volumetric Flow Rate [m3/s]
HVAC,Sum,Zone Mixing Mass [kg]
HVAC,Sum,Zone Mixing Mass Flow Rate [kg/s]
HVAC,Sum,Zone Mixing Sensible Heat Loss Energy [J]
HVAC,Sum,Zone Mixing Sensible Heat Gain Energy [J]
HVAC,Sum,Zone Mixing Latent Heat Loss Energy [J]
HVAC,Sum,Zone Mixing Latent Heat Gain Energy [J]
HVAC,Sum,Zone Mixing Total Heat Loss [J]
HVAC,Sum,Zone Mixing Total Heat Gain Energy [J]
Zone Mixing Volume [m3][LINK]
The air volume in m3 entering the zone due to
the sum of mixing, cross-mixing, and refrigeration-door mixing
during the hour or timestep.
Zone
Mixing Current Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering
the zone due to the sum of mixing, cross-mixing, and
refrigeration-door mixing during the hour or timestep using
the density of air evaluated at current zone air
conditions.
Zone
Mixing Standard Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering
the zone due to the sum of mixing, cross-mixing, and
refrigeration-door mixing during the hour or timestep using
the density of air evaluated at standard conditions.
Zone Mixing Mass [kg][LINK]
The air mass in kg entering the zone due to the sum of
mixing, cross-mixing, and refrigeration-door mixing during the
hour or timestep. The air mass is calculated using the air
volume flow from each “source” zone and the density of air
calculated for the average conditions (temperature and
humidity) between the “source” and “receiving” zones.
Zone Mixing Mass Flow
Rate [kg/s][LINK]
The air mass flow rate in kg/s entering the zone due to the
sum of mixing, cross-mixing, and refrigeration-door mixing
during the hour or timestep.
Zone Mixing
Sensible Heat Loss Energy [J][LINK]
Zone Mixing
Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat transfer due to the sum of
mixing, cross-mixing, and refrigeration-door mixing in the
host (receiving) zone is the sum of all the incoming air mass
flow rates multiplied by the elapsed time, the specific heat
(calculated for the average conditions (temperature and
humidity) between the “source” and “receiving” zones) and the
temperature differences between the host zone and
corresponding source zones. If the heat transfer is negative,
the heat transfer is considered to be a zone mixing sensible
heat loss. If the heat transfer is positive, the heat transfer
is considered to be a zone mixing sensible heat gain.
Zone Mixing
Latent Heat Loss Energy [J][LINK]
Zone Mixing
Latent Heat Gain Energy [J][LINK]
The latent heat transfer due to the sum of mixing,
cross-mixing, and refrigeration-door mixing in the host
(receiving) zone is the sum of all the incoming air mass flow
rates multiplied by the elapsed time, the heat of vaporization
(calculated for the average conditions (temperature and
humidity) between the “source” and “receiving” zones) and the
humidity ratio differences between the host zone and
corresponding source zones. If the heat transfer is negative,
the heat transfer is considered to be a zone mixing latent
heat loss. If the heat transfer is positive, the heat transfer
is considered to be a zone mixing latent heat gain.
Zone Mixing
Total Heat Loss Energy [J][LINK]
The total heat loss due to the sum of mixing, cross-mixing,
and refrigeration-door mixing that occurs when the sum of Zone
Mixing Sensible Heat Gain Energy and Zone
Mixing Latent Heat Gain Energy < the sum of Zone
Mixing Sensible Heat Loss Energy and Zone
Mixing Latent Heat Loss Energy.
Zone Mixing
Total Heat Gain Energy [J][LINK]
The total heat gain due to the sum of mixing, cross-mixing,
and refrigeration-door mixing that occurs when the sum of Zone
Mixing Sensible Heat Gain Energy and Zone
Mixing Latent Heat Gain Energy >= the sum of Zone
Mixing Sensible Heat Loss Energy and Zone
Mixing Latent Heat Loss Energy.
ZoneCrossMixing[LINK]
The ZoneCrossMixing
syntax is ideally suited for two zones that exchange an equal
amount of air between each other and do not have any air
exchange with other zones. As with Mixing (ref: Mixing), this
is a simplified view of interzone airflow in EnergyPlus. The
main difference between Mixing and Cross Mixing is that Cross
Mixing has an energy effect on both the source and the
receiving zone, thus maintaining both the air mass and energy
balances in the two zones.
Cross Mixing can be entered once, in one of the mixing
zones; or twice, once for each zone. The object should be
entered once if Delta Temperature > 0.0 and it is desirable
to have mixing only when the source zone is warmer than the
receiving zone. This might be the case when the warmer zone is
below the colder zone and the mixing is buoyancy driven. If
the zones are next to each other, separated by an open
doorway, it would be more suitable to input a cross mixing
object for each zone. Then mixing would occur if the zone
temperatures differed by Delta Temperature or greater
regardless of which is the warmer zone.
If Delta Temperature = 0.0, Cross Mixing can be entered
either once or twice: the effect is exactly the same.
Cross Mixing is entered using the following syntax.
The name of the ZoneCrossMixing
object.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) receiving
the amount of air being exchanged and attaches a particular
cross mixing statement to a thermal zone in the building.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the maximum design volume flow rate parameter (see
next field). This fraction between 0.0 and 1.0 modifies the
design level parameter.
Field:
Design Flow Rate Calculation Method[LINK]
This field is a key/choice field that tells which of the
next four fields are filled and is descriptive of the method
for calculating the design volume flow rate. The key/choices
are:
- Flow/Zone
- With this choice, the method used will be a straight
insertion of the design volume flow rate. (The Design Flow
Rate field should be filled.)
- Flow/Area
- With this choice, the method used will be a factor per
floor area of the zone. (The Flow per Zone Floor Area field
should be filled).
- Flow/Person
- With this choice, the method used will be a factor per
nominal number of people in the zone. (The flow per person
field should be filled).
- AirChanges/Hour
- With this choice, the method used will be the number of
air changes per hour for the infiltration amount. This factor,
along with the Zone Volume, will be used to determine the
Design Flow Rate. (The Air Changes per Hour field should be
filled).
Field: Design Flow Rate[LINK]
This field denotes the full design volume flow rate
(m3/s). The previous field should choose
“flow/zone” as the choice. The design volume flow rate is the
maximum amount of mixing air expected. The design value is
modified by the schedule fraction (see Field: Schedule Name)
and user specified coefficients (see four “coefficient” fields
below).
Field: Flow
Rate per Zone Floor Area[LINK]
This factor (m3/s-m2) is used, along
with the Zone
Area to determine the maximum Design Volume Flow Rate as
described in the Design Volume Flow Rate field. The choice
from the method field should be “Flow/Area”.
Field: Flow Rate per
Person[LINK]
This factor (m3/s-person) is used, along with
the nominal (maximum) number of occupants (people) in the Zone
to determine the maximum Design Volume Flow Rate as described
in the Design Volume Flow Rate field. The choice from the
method field should be “Flow/Person”.
Field: Air Changes per
Hour[LINK]
- With this choice, the method used will be the number of
air changes per hour for the mixing amount. This factor, along
with the Zone Volume, will be used to determine the Design
Flow Rate. The choice from the method field should be
“AirChanges/Hour”.
Field: Source Zone Name[LINK]
This field is the name of the “source” zone (ref: Zone)
that exhausts the amount of air specified by the design level
and schedule fields to the zone named in the zone name field.
In reality, the “source” and “receiving” zones are
interchangeable since the cross-mixed air affects both
zones.
Field: Delta
Temperature[LINK]
This number controls when mixing air from the source zone
is sent to the receiving zone. This parameter is a temperature
and is expressed in units of Celsius. If this field is
positive, the temperature of the zone from which air is being
drawn (“source zone”) must be “Delta Temperature” warmer than
the zone air or no mixing occurs. If this field is zero,
mixing occurs regardless of the relative air temperatures.
Negative values for “Delta Temperature” are not permitted.
Field: Delta
Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the temperature difference
(in Celsius) between the source zone and receiving zone air
dry-bulb temperatures as a function of time. This field is an
optional field and has the same functionality as the Delta
Temperature field. If the user enters a valid schedule name,
the delta temperature values specified in this schedule will
supersede the constant value specified in the Delta
Temperature field.
Field:
Minimum Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the minimum receiving zone
temperature (in Celsius) below which cross mixing is shutoff
as a function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
minimum zone temperature control is not applied.
Field:
Maximum Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the maximum receiving zone
temperature (in Celsius) above which cross mixing is shutoff
as a function of time. The maximum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
maximum zone temperature control is not applied.
Note: The maximum zone temperature when
cross mixing is shutoff must be greater than or equal to the
minimum zone temperature when cross mixing is shutoff at any
given time. Otherwise, warnings will be issued and the maximum
zone shutoff temperature will be set to the minimum zone
shutoff temperature.
Field:
Minimum Source Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the minimum source zone
temperature (in Celsius) below which cross mixing is shutoff
as a function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
minimum source zone temperature control is not applied.
Field:
Maximum Source Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the maximum source zone
temperature (in Celsius) above which cross mixing is shutoff
as a function of time. The maximum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
maximum source zone temperature control is not applied.
Note: The maximum source zone temperature
when cross mixing is shutoff must be greater than or equal to
the minimum source zone temperature when cross mixing is
shutoff at any given time. Otherwise, warnings will be issued
and the maximum source zone shutoff temperature will be set to
the minimum source zone shutoff temperature.
Field:
Minimum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the minimum outdoor
temperature (in Celsius) below which cross mixing is shutoff
as a function of time. The minimum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
minimum outdoor temperature control is not applied.
Field:
Maximum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref.
Schedule objects) which contains the maximum outdoor
temperature (in Celsius) above which cross mixing is shutoff
as a function of time. The maximum temperature value in the
schedule can be -100C and the maximum value can be 100C. This
field is an optional field. If this field is not entered, the
maximum outdoor temperature control is not applied.
Note: The maximum outdoor temperature when
cross mixing is shutoff must be greater than or equal to the
minimum outdoor temperature which cross mixing is shutoff at
any given time. Otherwise, a warning will be issued and the
maximum outdoor shutoff temperature will be set to the minimum
outdoor shutoff temperature.
An IDF Example:
ZoneCrossMixing,
1stFloor-Garage, !- Name
GARAGE, !- Zone Name
Always On, !- SCHEDULE Name
Flow/Zone, !- Design Flow Rate calculation method
0.1, !- Design Flow Rate {m3/s}
, !- Flow Rate per Area {m3/s/m2}
, !- Flow Rate per Person {m3/s/person}
, !- Air Changes Per Hour
1ST-FLOOR, !- Source Zone Name
1.0; !- Delta temp
ZoneCrossMixing,
Garage-1stFloor, !- Name
1ST-FLOOR, ! Zone Name
Always On, !- SCHEDULE Name
flow/zone, !- Design Flow Rate calculation method
0.1, !- Design Flow Rate {m3/s}
, !- Flow Rate per area {m3/s/m2}
, !- Flow Rate per person {m3/s/person}
, !- Air Changes Per Hour
GARAGE, ! Source Zone Name
1.0; ! Delta temp
HVAC,Sum,Zone Mixing Volume [m3]
HVAC,Sum,Zone Mixing Current Density Volumetric Flow Rate [m3/s]
HVAC,Sum,Zone Mixing Standard Density Volumetric Flow Rate [m3/s]
HVAC,Sum,Zone Mixing Mass [kg]
HVAC,Sum,Zone Mixing Mass Flow Rate [kg/s]
HVAC,Sum,Zone Mixing Sensible Heat Loss Energy [J]
HVAC,Sum,Zone Mixing Sensible Heat Gain Energy [J]
HVAC,Sum,Zone Mixing Latent Heat Loss Energy [J]
HVAC,Sum,Zone Mixing Latent Heat Gain Energy [J]
HVAC,Sum,Zone Mixing Total Heat Loss Energy [J]
HVAC,Sum,Zone Mixing Total Heat Gain Energy [J]
Zone Mixing Volume [m3][LINK]
The air volume in m3 entering the zone due to
the sum of mixing, cross-mixing, and refrigeration-door mixing
during the hour or timestep.
Zone
Mixing Current Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering
the zone due to the sum of mixing, cross-mixing, and
refrigeration-door mixing during the hour or timestep using
the density of air evaluated at current zone air
conditions.
Zone
Mixing Standard Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering
the zone due to the sum of mixing, cross-mixing, and
refrigeration-door mixing during the hour or timestep using
the density of air evaluated at standard conditions.
Zone Mixing Mass [kg][LINK]
The air mass in kg entering the zone due to the sum of
mixing, cross-mixing, and refrigeration-door mixing during the
hour or timestep. The air mass is calculated using the air
volume flow from each “source” zone and the density of air
calculated for the average conditions (temperature and
humidity) between the “source” and “receiving” zones.
Zone Mixing Mass
Flow Rate [kg/s][LINK]
The air mass flow rate in kg/s entering the zone due to the
sum of mixing, cross-mixing, and refrigeration-door mixing
during the hour or timestep.
Zone Mixing
Sensible Heat Loss Energy [J][LINK]
Zone Mixing
Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat transfer due to the sum of
mixing, cross-mixing, and refrigeration-door mixing in the
host (receiving) zone is the sum of all the incoming air mass
flow rates multiplied by the elapsed time, the specific heat
(calculated for the average conditions (temperature and
humidity) between the “source” and “receiving” zones) and the
temperature differences between the host zone and
corresponding source zones. If the heat transfer is negative,
the heat transfer is considered to be a zone mixing sensible
heat loss. If the heat transfer is positive, the heat transfer
is considered to be a zone mixing sensible heat gain.
Zone Mixing
Latent Heat Loss Energy [J][LINK]
Zone Mixing
Latent Heat Gain Energy [J][LINK]
The latent heat transfer due to the sum of mixing,
cross-mixing, and refrigeration-door mixing in the host
(receiving) zone is the sum of all the incoming air mass flow
rates multiplied by the elapsed time, the heat of vaporization
(calculated for the average conditions (temperature and
humidity) between the “source” and “receiving” zones) and the
humidity ratio differences between the host zone and
corresponding source zones. If the heat transfer is negative,
the heat transfer is considered to be a zone mixing latent
heat loss. If the heat transfer is positive, the heat transfer
is considered to be a zone mixing latent heat gain.
Zone Mixing
Total Heat Loss Energy [J][LINK]
The total heat loss due to the sum of mixing, cross-mixing,
and refrigeration-door mixing that occurs when the sum of Zone
Mixing Sensible Heat Gain Energy and Zone
Mixing Latent Heat Gain Energy < the sum of Zone
Mixing Sensible Heat Loss Energy and Zone
Mixing Latent Heat Loss Energy.
Zone Mixing
Total Heat Gain Energy [J][LINK]
The total heat gain due to the sum of mixing, cross-mixing,
and refrigeration-door mixing that occurs when the sum of Zone
Mixing Sensible Heat Gain Energy and Zone
Mixing Latent Heat Gain Energy >= the sum of Zone
Mixing Sensible Heat Loss Energy and Zone
Mixing Latent Heat Loss Energy.
ZoneRefrigerationDoorMixing[LINK]
The ZoneRefrigerationDoorMixing
syntax is ideally suited for two zones, at least one of which
is refrigerated, that exchange an equal amount of dry air.
They may also have mixed air from other zones, but only one
object should be entered for any one pair of zones. As with
Mixing (ref: Mixing), this is a simplified view of interzone
airflow in EnergyPlus. The ZoneRefrigerationDoorMixing
approach shares some features of both Mixing and Cross Mixing.
Like Cross Mixing, RefrigerationDoorMixing has an energy
effect on both the source and the receiving zone, thus
maintaining both the air mass and energy balances in the two
zones. Like Mixing, the refrigerated zone can exchange air
with multiple zones. Unlike either of the other two mixing
objects, the RefrigeratedDoorMixing always calculates the air
exchange based on the zone temperature and relative humidity.
That is, the user does not specify the air flow rate. The user
can moderate the flow through a door-opening schedule.
Unlike, Cross Mixing, Refrigeration Door
Mixing can only be entered once for any unique pair of zones.
It doesn’t matter which zone is listed first and the zones
will automatically switch back and forth between source and
receiving zones depending upon which zone is colder.
Refrigeration Door
Mixing is entered using the following syntax.
The name of the ZoneRefrigerationDoorMixing
object.
Field: Zone 1 Name[LINK]
This field is the name of one of the two zones (ref: Zone)
exchanging air and attaches a particular refrigeration door
mixing statement to both thermal zones in the building.
Field: Zone 2 Name[LINK]
This field is the name of the other zone (ref: Zone)
exchanging air and attaches a particular refrigeration door
mixing statement to both thermal zones in the building.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the door opening between the two zones and should
contain values between 0.0 and 1.0.
Field: Door Height[LINK]
This field denotes the door opening height (m). The default
value is 3 m.
Field: Door Area[LINK]
This field denotes the door opening area (m2).
The default value is 9 m2.
Field: Door Protection
Type[LINK]
This field is a key/choice field that tells how the door is
protected. The impact of this choice is decribed in the
Engineering Reference. The key/choices are:
- None
- None, or no door protection is the default choice
- AirCurtain
- StripCurtain
An IDF Example:
ZoneRefrigerationDoorMixing,
Freezer1_Cooler1, !- Name
Freezer1, !- Zone 1 Name
Cooler1, !- Zone 2 Name
Freezer1DoorSched, !- Schedule Name
1.8, !- Door height {m}
2.3, !- Door area {m2}
StripCurtain; !- Door protection type
HVAC,Sum,Zone Mixing Volume [m3]
HVAC,Sum,Zone Mixing Current Density Volumetric Flow Rate [m3/s]
HVAC,Sum,Zone Mixing Standard Density Volumetric Flow Rate [m3/s]
HVAC,Sum,Zone Mixing Mass [kg]
HVAC,Sum,Zone Mixing Mass Flow Rate [kg/s]
HVAC,Sum,Zone Mixing Sensible Heat Loss Energy [J]
HVAC,Sum,Zone Mixing Sensible Heat Gain Energy [J]
HVAC,Sum,Zone Mixing Latent Heat Loss Energy [J]
HVAC,Sum,Zone Mixing Latent Heat Gain Energy [J]
HVAC,Sum,Zone Mixing Total Heat Loss Energy [J]
HVAC,Sum,Zone Mixing Total Heat Gain Energy [J]
Zone Mixing Volume [m3][LINK]
The air volume in m3 entering the zone due to
the sum of mixing, cross-mixing, and refrigeration-door mixing
during the hour or timestep.
Zone
Mixing Current Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering
the zone due to the sum of mixing, cross-mixing, and
refrigeration-door mixing during the hour or timestep using
the density of air evaluated at current zone air
conditions.
Zone
Mixing Standard Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering
the zone due to the sum of mixing, cross-mixing, and
refrigeration-door mixing during the hour or timestep using
the density of air evaluated at standard conditions.
Zone Mixing Mass [kg][LINK]
The air mass in kg entering the zone due to the sum of
mixing, cross-mixing, and refrigeration-door mixing during the
hour or timestep. The air mass is calculated using the air
volume flow from each “source” zone and the density of air
calculated for the average conditions (temperature and
humidity) between the “source” and “receiving” zones.
Zone Mixing Mass
Flow Rate [kg/s][LINK]
The air mass flow rate in kg/s entering the zone due to the
sum of mixing, cross-mixing, and refrigeration-door mixing
during the hour or timestep.
Zone Mixing
Sensible Heat Loss Energy [J][LINK]
Zone Mixing
Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat transfer due to the sum of
mixing, cross-mixing, and refrigeration-door mixing in the
host (receiving) zone is the sum of all the incoming air mass
flow rates multiplied by the elapsed time, the specific heat
(calculated for the average conditions (temperature and
humidity) between the “source” and “receiving” zones) and the
temperature differences between the host zone and
corresponding source zones. If the heat transfer is negative,
the heat transfer is considered to be a zone mixing sensible
heat loss. If the heat transfer is positive, the heat transfer
is considered to be a zone mixing sensible heat gain.
Zone Mixing
Latent Heat Loss Energy [J][LINK]
Zone Mixing
Latent Heat Gain Energy [J][LINK]
The latent heat transfer due to the sum of mixing,
cross-mixing, and refrigeration-door mixing in the host
(receiving) zone is the sum of all the incoming air mass flow
rates multiplied by the elapsed time, the heat of vaporization
(calculated for the average conditions (temperature and
humidity) between the “source” and “receiving” zones) and the
humidity ratio differences between the host zone and
corresponding source zones. If the heat transfer is negative,
the heat transfer is considered to be a zone mixing latent
heat loss. If the heat transfer is positive, the heat transfer
is considered to be a zone mixing latent heat gain.
Zone Mixing
Total Heat Loss Energy [J][LINK]
The total heat loss due to the sum of mixing, cross-mixing,
and refrigeration-door mixing that occurs when the sum of Zone
Mixing Sensible Heat Gain Energy and Zone
Mixing Latent Heat Gain Energy < the sum of Zone
Mixing Sensible Heat Loss Energy and Zone
Mixing Latent Heat Loss Energy.
Zone Mixing
Total Heat Gain Energy [J][LINK]
- The total heat gain due to the sum of mixing,
cross-mixing, and refrigeration-door mixing that occurs when
the sum of Zone Mixing Sensible Heat Gain Energy and Zone
Mixing Latent Heat Gain Energy >= the sum of Zone Mixing
Sensible Heat Loss Energy and Zone Mixing Latent Heat Loss
Energy.
ZoneEarthtube (Earth
Tube)[LINK]
An earth tube is a long, underground metal or plastic pipe
through which air is drawn. During cooling season, as air
travels through the pipe, it gives up some of its heat to the
surrounding soil and enters the room as cooler air. Similarly,
during heating season, as air travels through the pipe, it
receives some of its heat from the soil and enters the room as
warmer air. Simple earth tubes in EnergyPlus can be controlled
by a schedule and through the specification of minimum,
maximum, and delta temperatures as described below. As with
infiltration and ventilation, the actual flow rate of air
through the earth tube can be modified by the temperature
difference between the inside and outside environment and the
wind speed. The basic equation used to calculate air flow rate
of earth tube in EnergyPlus is:
\[EarthTubeFlowRate = \left(
{{E_{design}}} \right)\left( {{F_{schedule}}} \right)\left[ {A
+ B\left| {{T_{zone}} - {T_{odb}}} \right| + C\left(
{WindSpeed} \right) + D\left( {WindSpee{d^2}} \right)}
\right]\]
For the simulation of the earth tube, a weather data file
is required and, therefore, the earth tube cannot run without
weather data file. The required input fields to simulate the
earth tube include the average soil surface temperature, the
amplitude of soil surface temperature, and the phase constant
of soil surface temperature. These fields should be calculated
in advance by using a separate stand-alone program
(CalcSoilSurfTemp) and should be input into earth tube.
CalcSoilSurfTemp
- Auxiliary Programs Document[LINK]
The CalcSoilSurfTemp program is simple and requires only
two input fields : soil condition and soil surface condition
in addition to a valid weather file. For soil condition, the
user should select the number corresponding to the actual
condition of the soil surrounding the earth tube from the four
following options: 1. HEAVY AND SATURATED, 2. HEAVY AND DAMP,
3. HEAVY AND DRY and 4. LIGHT AND DRY. This determines the
thermal diffusivity and thermal conductivity of the
surrounding soil. For soil surface conditions, the user should
select the number corresponding to the actual condition of the
ground surface above the earth tube from the eight following
options: 1. BARE AND WET, 2. BARE AND MOIST, 3. BARE AND ARID,
4. BARE AND DRY, 5. COVERED AND WET, 6. COVERED AND MOIST, 7.
COVERED AND ARID and 8. COVERED AND DRY. This determines the
absorption coefficient and the fraction of evaporation rate of
the ground surface.
From this information and an analysis of the weather for
the location selected, the CalcSoilSurfTemp program (ref.
Auxiliary Programs document) calculates the three parameters
listed above. The user must then add these parameters as input
into EnergyPlus. The full input description of an earth tube
in EnergyPlus is given below.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches
a particular earth tube statement to a thermal zone in the
building.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the maximum design volume flow rate parameter (see
next field). This fraction between 0.0 and 1.0 is noted as
Fschedule in the above equation.
Field: Design Flow Rate[LINK]
This number (noted as Edesign in the above
equation) is the maximum amount of air mass flow rate of the
earth tube expected at design conditions. The flow rate is
expressed in units of m3/s. The design value is
modified by the schedule fraction (see previous field) and
user specified coefficients (see last four fields).
Field:
Minimum Zone Temperature when Cooling[LINK]
This is the indoor temperature (in Celsius) below which the
earth tube is shut off. This lower temperature limit is
intended to avoid overcooling a space and thus result in a
heating load. For example, if the user specifies a minimum
temperature of 20C, earth tube is assumed to be available if
the zone air temperature is above 20C. If the zone air
temperature drops below 20C, then earth tube is automatically
turned off.
Field:
Maximum Zone Temperature when Heating[LINK]
This is the indoor temperature (in Celsius) above which the
earth tube is shut off. This higher temperature limit is
intended to avoid overheating a space and thus result in a
cooling load. For example, if the user specifies a maximum
temperature of 20C, earth tube is assumed to be available if
the zone air temperature is below 20C. If the zone air
temperature rises above 20C, then earth tube is automatically
turned off.
Field: Delta
Temperature[LINK]
This is the temperature difference (in Celsius) between the
indoor and outdoor air dry-bulb temperatures below which the
earth tube is shut off. This is to allow the earth tube to be
stopped either if the temperature outside is too warm and
could potentially heat the space or if the temperature outside
is too cold and could potentially cool the space. For example,
if the user specifies a delta temperature of 2C, earth tube is
assumed to be available if the temperature difference between
indoor and outdoor temperature is at least 2C. If the outside
air dry-bulb temperature is less than 2C cooler or warmer than
the indoor dry-bulb temperature, then the earth tube is
automatically turned off.
Field: Earthtube Type[LINK]
This alpha character string defines the type of earth tube
as one of the following options: Natural, Exhaust, or Intake.
A natural earth tube is assumed to be air movement/exchange
that will not consume any fan energy or is the result of
natural air flow through the tube and into the building.
Values for fan pressure and efficiency for a natural flow
earth tube are ignored. For either EXHAUST or Intake, values
for fan pressure and efficiency define the fan electric
consumption. For Natural and Exhaustearth tubes, the
conditions of the air entering the space are assumed to be
equivalent to the air which is cooled or heated by passing
along the pipe. For Intake earth tubes, an appropriate amount
of fan heat is added to the air stream.
Field: Fan Pressure
Rise[LINK]
This is the pressure rise experienced across the fan in
Pascals (N/m2). This is a function of the fan and
plays a role in determining the amount of energy consumed by
the fan.
Field: Fan Total
Efficiency[LINK]
This is the total fan efficiency (a decimal number between
0.0 and 1.0). This is a function of the fan and plays a role
in determining the amount of energy consumed by the fan.
Field: Pipe Radius[LINK]
This is the radius of the earth tube/pipe (in meters). This
plays a role in determining the amount of heat transferred
from the surrounding soil to the air passing along the pipe.
If the pipe has non-circular cross section, user can use the
concept of hydraulic diameter as follows.
However, since this field requires the pipe radius,
hydraulic diameter should be divided by two.
Field: Pipe Thickness[LINK]
This is the thickness of the pipe wall (in meters). This
plays a role in determining the amount of heat transferred
from the surrounding soil to the air passing along the
pipe.
Field: Pipe Length[LINK]
This is the total length of the pipe (in meters). This
plays a role in determining the amount of heat transferred
from the surrounding soil to the air passing along the pipe.
As the length of the pipe becomes longer, the amount of the
heat transfer becomes larger.
Field: Pipe Thermal
Conductivity[LINK]
This is the thermal conductivity of the pipe (in W/mC).
This plays a role in determining the amount of heat
transferred from the surrounding soil to the air passing along
the pipe.
Field: Pipe
Depth Under Ground Surface[LINK]
This is the depth of the pipe under the ground surface (in
meters). This plays a role in determining the temperature of
the soil surrounding the pipe.
Field: Soil Condition[LINK]
This alpha character string defines the actual condition of
the soil surrounding the earth tube and can be one of any of
the following options: HeavyAndSaturated, HeavyAndDamp,
HeavyAndDry or LightAndDry. This determines the thermal
diffusivity and thermal conductivity of the surrounding soil,
which play a role in determining the amount of heat
transferred from the surrounding soil to the air passing along
the pipe.
Field: Average
Soil Surface Temperature[LINK]
This is the annual average soil surface temperature
straight above the earth tube, which plays a role in
determining the temperature of the soil surrounding the pipe.
This field should be calculated in advance using the separate
CalcSoilSurfTemp program.
Field:
Amplitude of Soil Surface Temperature[LINK]
This is the amplitude of soil surface temperature above the
earth tube, which plays a role in determining the temperature
of the soil surrounding the pipe. This is the difference
between the maximum and minimum soil surface temperature for
the whole year divided by two. This field should be calculated
in advance using the separate CalcSoilSurfTemp program.
Field:
Phase Constant of Soil Surface Temperature[LINK]
This is the phase constant of the soil surface temperature
straight above the earth tube, which play a role in
determining the temperature of the soil surrounding the pipe
at particular time. This is the time elapsed from the
beginning of the year until the soil surface temperature
reaches the minimum value of the year. This field should be
calculated in advance using the separate CalcSoilSurfTemp
program.
Field: Constant
Term Flow Coefficient[LINK]
This number is the “A” parameter in the above earth tube
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter, however, is a constant under all conditions and is
not modified by any environmental effect. As a result, it is
dimensionless.
Field:
Temperature Term Flow Coefficient[LINK]
This number is the “B” parameter in the above earth tube
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter is modified by the temperature difference between
the outdoor and indoor air dry-bulb temperatures. The units
for this parameter are inverse Celsius.
Field: Velocity
Term Flow Coefficient[LINK]
This number is the “C” parameter in the above earth tube
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter is modified by the speed of wind being experienced
outside the building. The units for this parameter are
s/m.
Field:
Velocity Squared Term Flow Coefficient[LINK]
This number is the “D” parameter in the above earth tube
equation. It is part of the user specified modifying
parameters that are a function of environmental factors. This
parameter is modified by square of the speed of wind being
experienced outside the building. The units for this parameter
are s2/m2.
An IDF example:
EARTHTUBE,
Zone 2, !- Zone Name
Simple EarthTube, !- Schedule Name
3.425198, !- Design Volume Flow Rate
10.0, !- Minimum Zone Temperature when Cooling
30.0, !- Maximum Zone Temperature when Heating
1.0, !- Delta Temperature
NATURAL, !- EarthTube Type
350.0, !- Fan Pressure Rise
0.9, !- Fan Total Efficiency
0.25, !- Pipe Radius
0.2, !- Pipe Thickness
15.0, !- Pipe Length
200.0, !- Pipe Thermal Conductivity
3.5, !- Pipe Depth Under Ground Surface
HeavyAndDamp, !- Soil Condition
15.0, !- Average Soil Surface Temperature
5.6, !- Amplitude of Soil Surface Temperature
0.0, !- Phase Constant of Soil Surface Temperature
0.6060000 , !- Constant Term Flow Coef
2.0199999E-02, !- Temp Term Flow Coef
5.9800001E-04, !- Velocity Term Flow Coef
0.0000000E+00; !- Velocity**2 Term Flow Coef
ZoneEarthTube Outputs[LINK]
Current Earth Tube output variables:
HVAC,Sum,Earth Tube Zone Sensible Cooling Energy [J]
HVAC,Average,Earth Tube Zone Sensible Cooling Rate [W]
HVAC,Sum,Earth Tube Zone Sensible Heating Energy [J]
HVAC,Average,Earth Tube Zone Sensible Heating Rate [W]
HVAC,Sum,Earth Tube Air Flow Volume [m3]
HVAC,Average,Earth Tube Air Current Density Volumetric Flow Rate [m3/s]
HVAC,Average,Earth Tube Air Standard Density Volumetric Flow Rate [m3/s]
HVAC,Sum,Earth Tube Air Flow Mass [kg]
HVAC,Average,Earth Tube Air Mass Flow Rate [kg/s]
HVAC,Sum,Earth Tube Fan Electric Energy [J]
HVAC,Average,Earth Tube Fan Electric Power [W]
HVAC,Average,Earth Tube Zone Inlet Air Temperature [C]
HVAC,Average,Earth Tube Ground Interface Temperature [C]
HVAC,Average,Earth Tube Outdoor Air Heat Transfer Rate [W]
Earth Tube
Zone Sensible Cooling Energy [J][LINK]
Earth Tube
Zone Sensible Cooling Rate [W][LINK]
These are the energy and rate associated with the zone
cooling provided by the air from the earth tube. This occurs
when the earth tube outlet air temperature is less than zone
air temperature.
Earth Tube
Zone Sensible Heating Energy [J][LINK]
Earth Tube
Zone Sensible Heating Rate [W][LINK]
These are the energy and rate associated with the zone
heating provided by the air from the earth tube. This occurs
when the earth tube outlet air temperature is greater than the
zone air temperature.
Earth Tube Air Flow
Volume [m3][LINK]
The volume flow of air through the earth tube.
Earth
Tube Air Current Density Volumetric Flow Rate [m3/s][LINK]
The volume flow rate of air through the earth tube
evaluating density at current zone conditions.
Earth
Tube Air Standard Density Volumetric Flow Rate [m3/s][LINK]
The volume flow rate of air through the earth tube
evaluating density at standard conditions.
Earth Tube Air Flow Mass
[kg][LINK]
The mass flow of air through the earth tube.
Earth Tube Air Mass
Flow Rate [kg/s][LINK]
The mass flow rate of air through the earth tube.
Earth Tube Fan
Electric Energy [J][LINK]
Earth Tube Fan
Electric Power [W][LINK]
These are the fan electricity consumption and power for
intake or exhaust earth tube types.
Earth Tube
Zone Inlet Air Temperature [C][LINK]
This is the temperature of the air entering the zone after
passing through the earth tube [C]. This temperature includes
the cooling or heating of outdoor air as it passes along the
pipe. When intake fan assist is used, then the additional heat
due to the fan is included in the inlet air temperature.
Earth Tube
Ground Interface Temperature [C][LINK]
This is the average temperature of the ground along the
outer surface of the earth tube [C].
Earth
Tube Outdoor Air Heat Transfer Rate [W][LINK]
This is the rate of heat transfer from the earth tube to
the outdoor air [W]. Positive values indicate the rate at
which outdoor air is preheated; negative values indicate the
rate of precooling.
ZoneCoolTower:Shower[LINK]
A cooltower (which is sometimes referred to as a wind tower
or a shower cooling tower) is a component that is intended to
model a passive downdraught evaporative cooling (PDEC) that is
designed to capture the wind at the top of a tower and cool
the outside air using water evaporation before delivering it
to a space. The air flow in these systems is natural as the
evaporation process increases the density of the air causing
it to fall through the tower and into the space without the
aid of a fan. A cooltower typically consists of a water spray
or an evaporative pad, a shaft, and a water tank or reservoir.
Wind catchers to improve the wind-driven performance at the
top of the tower are optional. Water is pumped over an
evaporative device by water pump which is the only component
consumed power for this system. This water cools and
humidifies incoming air and then the cool, dense air naturally
falls down through shaft and leaves through large openings at
the bottom of cooltowers.
The shower cooling tower can be controlled by a schedule
and the specification of maximum water flow rate and volume
flow rate as well as minimum indoor temperature. The actual
flow rate of water and air can be controlled as users specify
the fractions of water loss and flow schedule. The required
input fields include effective tower height and exit area to
obtain the temperature and flow rate of the air exiting the
tower. A schedule and rated power for the water pump are also
required to determine the power consumed. The component
typically has a stand alone water system that is not added to
the water consumption from mains. However, users are required
to specify the water source through an optional field, the
name of water supply storage tank, in case any water comes
from a water main. The model is described more fully in the
Engineering Reference document.
This model requires weather information obtained from
either design day or weather file specifications. The control
is accomplished by either specifying the water flow rate or
obtaining the velocity at the outlet with inputs and weather
conditions when the water flow rate is unknown. As with
infiltration, ventilation, and earth tubes, the component is
treated in a similar fashion to “natural ventilation” in
EnergyPlus.
This field is a unique user assigned name for each
cooltower. Any reference to this unit by another object will
use this name.
Field: Availability
Schedule Name[LINK]
This field is the name of the schedule that denotes whether
the cooltower can run during a given time period. A schedule
value greater than 0 (usually 1 is used) indicates that the
cooltower is available and can be on during the time period. A
value less than or equal to 0 (usually 0 is used) denotes that
the cooltower is not available and must be off for the time
period. If this field is blank, the schedule has values of 1
for all time periods.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches
a particular cooltower statement to a thermal zone in the
building.
Field: Water
Supply Storage Tank Name[LINK]
This field is optional. It is used to describe where the
cooltower obtains water used for evaporative cooling. If blank
or omitted, then the cooltower will obtain water directly from
local water main. If the name of a Water Storage Tank object
is used here, then the cooltower will obtain its water from
that tank. If a tank is specified, the cooltower will attempt
to obtain all the water it uses from the tank. However, if the
tank cannot provide all the water the cooltower needs, then
the cooltower will still operate and obtain the rest of the
water it needs from the mains (referred to as ‘Starved’
water).
Field: Flow Control Type[LINK]
This field specifies how the user wishes to control the
cooltower. The air flow from the cooltower may be controlled
by either the water flow rate along with the water pump
schedule or naturally driven by wind flow. The user must
select from the following options:
WaterFlowSchedule and
WindDrivenFlow. If the user either wishes to
control the water flow rate or has information about the water
flow rate, WaterFlowSchedule must be
selected. WindDrivenFlow for cooltower flow
control must be selected when the water flow rate is unknown
and the user wishes to have the flow rate of both air and
water controlled by the external weather conditions (wind
speed). If the user does not select a control type,
WindDrivenFlow is assumed as a flow control
type.
Field: Pump Flow
Rate Schedule Name[LINK]
This field modifies the maximum flow rate of water through
the cooltower in m3/sec. This input is “optional.” If the user
does not enter a schedule, the flow rate through the cooltower
is assumed to be constant during all hours that it is
operating based on the value entered in the previous input
field. Note that the values for this schedule must be between
zero and one.
Field: Maximum Water
Flow Rate[LINK]
This field is the maximum water flow rate distributed to
the tower in m3/s. This limit is intended to avoid over
estimation of water flow rate, which leads higher air flow
rate and exit temperature of the air.
Field: Effective Tower
Height[LINK]
This field is the effective tower height for evaporative
cooling, from the water spray to the top of the exit in m.
Field: Airflow Outlet
Area[LINK]
This field is the area at the exit of the tower in m2. This
field is used to determine the air flow rate leaving the tower
with the velocity of the air flow.
Field: Maximum Air Flow
Rate[LINK]
This field is the maximum volumetric flow rate of the air
leaving the tower in m3/s. This airflow maximum allows the
cooltower performance to be limited if the outside wind speed
and the tower height are relatively high and thus result in
high airflow supplied to the space.
Field: Minimum
Indoor Temperature[LINK]
This field is the minimum indoor temperature in Celsius
below which cooltower is shutoff. This lower temperature limit
is intended to avoid overcooling a space and thus result in a
heating load. For example, if the user specifies a minimum
temperature of 20°C, cooltower is assumed to be available if
the zone air temperature is above 20°C. If the zone air
temperature drops below 20°C, then cooltower is automatically
turned off.
Field: Fraction of Water
Loss[LINK]
This field specifies the fraction of the loss of water
during either operation or transient operation. If the user
does not enter a fraction, no loss of water is assumed and the
cooltower water consumption includes only evaporation. Note
that the fraction must be between zero and one.
Field: Fraction of
Flow Schedule[LINK]
This field specifies the fraction of the airflow that
actually goes to the outside. The user who wishes to control
the actual flow to the inside of the building must specify the
value of the fraction. If the user does not enter a fraction,
the calculated flow rate is the “zone cooltower volume flow
rate.” Note that the fraction must be between zero and
one.
Field: Rated Power
Consumption[LINK]
This field is the pump’s rated power consumption in
Watts.
Below is an example input for a cooltower.
ZoneCoolTower:Shower
Cool Tower 1, !- Name of cooltowers
Zone 1, !- Zone name
Simple Vent, !- Schedule
, !- Name of water supply storage tanks
WindDrivenFlow, !- Flow control type
0.0005, !- Water flow rate from the spray in m3/s
, !- schedule for flow rate (optional, non-existent means constant)
5.0, !- Effective tower height in m
1.0, !- Exit area in m2
10.0, !- Maximum supply air volume flow rate in m3/s
18.0, !- Minimum indoor temperature to prevent overcooling in C
0.05, !- Fraction of Water loss
0.05, !- Fraction of flow that goes to outside
250.0; !- Rated power consumption in W
HVAC,Sum,Zone Cooltower Sensible Heat Loss Energy [J]
HVAC,Average,Zone Cooltower Sensible Heat Loss Rate [W]
HVAC,Sum,Zone Cooltower Latent Heat Loss Energy [J]
HVAC,Average,Zone Cooltower Latent Heat Loss Rate [W]
HVAC,Sum,Zone Cooltower Air Volume [m3]
HVAC,Average,Zone Cooltower Air Current Density Volumetric Flow Rate [m3/s]
HVAC,Average,Zone Cooltower Air Standard Density Volumetric Flow Rate [m3/s]
HVAC,Sum,Zone Cooltower Air Mass [kg]
HVAC,Average,Zone Cooltower Air Mass Flow Rate [kg/s]
HVAC,Average,Zone Cooltower Air Inlet Temperature [C]
HVAC,Average,Zone Cooltower Air Inlet Humidity Ratio [kgWater/kgDryAir]
HVAC,Average,Zone Cooltower Air Outlet Temperature [C]
HVAC,Average,Zone Cooltower Air Outlet Humidity Ratio [kgWater/kgDryAir]
HVAC,Average,Zone Cooltower Pump Electric Power [W]
HVAC,Sum,Zone Cooltower Pump Electric Energy [J]
HVAC,Sum,Zone Cooltower Water Volume [m3]
HVAC,Sum,Zone Cooltower Mains Water Volume [m3]
HVAC,Sum,Zone Cooltower Storage Tank Water Volume [m3]
HVAC,Sum,Zone Cooltower Starved Mains Water Volume [m3]
Zone
Cooltower Sensible Heat Loss Energy [J][LINK]
Zone
Cooltower Sensible Heat Loss Rate [W][LINK]
The sensible heat loss that occurs when the temperature at
the exit of the cooltower is less than that of the zone.
Zone
Cooltower Latent Heat Loss Energy [J][LINK]
Zone Cooltower
Latent Heat Loss Rate [W][LINK]
The latent heat loss that occurs when the humidity ratio at
the exit of the cooltower is greater than that of the
zone.
Zone
Cooltower Air Current Density Volumetric Flow Rate [m3/s][LINK]
The volumetric flow rate of the air leaving the cooltower
evaluating density at current zone conditions.
Zone
Cooltower Air Standard Density Volumetric Flow Rate
[m3/s][LINK]
The volumetric flow rate of the air leaving the cooltower
evaluating density at standard conditions.
Zone Cooltower Air
Volume [m3][LINK]
The sum of actual volumetric flow of the air leaving
cooltower
Zone Cooltower
Air Mass Flow Rate [kg/s][LINK]
The mass flow rate of the air leaving the cooltower
Zone Cooltower Air Mass
[kg][LINK]
The sum of actual mass flow of the air leaving the
cooltower
Zone Cooltower
Air Inlet Temperature [C][LINK]
The dry-bulb temperature of the outdoor air the inlet of
the cooltower
Zone
Cooltower Air Inlet Humidity Ratio [kgWater/kgDryAir][LINK]
The humidity ratio of the outdoorair at the inlet of the
cooltower
Zone
Cooltower Air Outlet Temperature [C][LINK]
The temperature at the exit of the cooltower.
Zone
Cooltower Air Outlet Humidity Ratio [kgWater/kgDryAir][LINK]
The humidity ratio of the air at the exit of the
cooltower.
Zone Cooltower Water
Volume [m3][LINK]
The water consumption includes not only the direct
thermodynamics of water evaporation but also other sources of
consumption such as drift or concentration blow down specified
by users throughout all processes during the operation.
Zone Cooltower
Mains Water Volume [m3][LINK]
This is the water consumed by the cooltower that actually
be met by the mains water. This output variable appears only
when the water comes from mains.
Zone
Cooltower Storage Tank Water Volume [m3][LINK]
This is the water consumed by the cooltower that actually
be met by the water storage tank. If any amount of the water
is starved from mains, this water consumption is the
difference between the Zone
Cooltower Water Volume and the following output. This output
variable appears only when the water comes from storage tank
waters.
Zone
Cooltower Starved Mains Water Volume [m3][LINK]
This is the source (mains) of water consumed by the
cooltower that could not actually be met by the storage tank.
This output variable appears only when the water comes from
storage tank waters.
Zone Cooltower
Pump Electric Power [W][LINK]
The power consumed by the recirculating pump in Watts.
Zone Cooltower
Pump Electric Energy [J][LINK]
The energy consumed by the recirculating pump in
Joules.
ZoneThermalChimney
(Thermal Chimney)[LINK]
A thermal chimney is a vertical shaft utilizing solar
radiation to enhance the natural ventilation in buildings. It
consists of a absorber wall, air gap and glass cover with high
solar transmissivity. For the high solar absorption, it is
usually south facing.
The key output parameter in the thermal chimney model is
the enhanced amount of natural ventilation rate caused by the
presence of a thermal chimney. In order to determine the
enhanced ventilation, the discharge air temperature from a
thermal chimney should be calculated, which, in turn, should
be computed based on the information on the absorber wall
temperature, glass cover temperature and the vertical air
temperature distribution within the thermal chimney. Among
them, energy balances for the absorber wall and the glass
cover are carried out using the existing algorithm currently
available in EnergyPlus, which has the similar approach to the
Trombe wall. As stated in the Trombe wall object as well, this
approach allows the flexibility for users to specify the
various wall parameters and to explore unusual configurations.
On the other hand, the vertical air temperature distribution
and the resultant discharge air temperature of the thermal
chimney are computed using the separate thermal chimney
algorithm described in the Engineering Reference document.
Similar to the Trombe wall model, a zone is coupled to the
desired surface via an interzone partition. To simulate the
thermal chimney, the Solar Distribution field in the Building
object should be set to FullInteriorAndExterior so that the
majority of the solar flux is directed on the absorber wall.
For a normal sized thermal chimney zone, the user can set the
Zone
Inside Convection Algorithm to “Detailed”, which takes into
account natural convection effects intended for a normal zone.
For a narrow cavity zone having high aspect ratios, there is
no built-in algorithm for calculating the correct convection
coefficients on the inside of thermal chimney zone walls. One
option is to use the “Detailed” convection algorithm similar
to the Trombe wall model. However, some error may be incurred
when used with a narrow zone. Another option is to use the SurfaceProperty:ConvectionCoefficients
object to schedule coefficients that have been determined
beforehand by the user. In addition, the wall construction of
the adjoining zone must be the mirror image of the wall
construction in the thermal chimney zone.
The full input description of a thermal chimney in
EnergyPlus is given below.
This field is a unique user assigned name for an instance
of the thermal chimney system.
Field: Zone Name[LINK]
This field is the name of the thermal chimney zone (ref:
Zone). Since the thermal chimney is not only a system
component but also a zone itself, this field is also
necessary. It should be differentiated from the Zone
name field described later.
Field:
Availability Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that
denotes whether the thermal chimney can operate during a given
time period. A schedule value greater than 0 (usually 1 is
used) indicates that the system is available and can be on
during the time period. A value less than or equal to 0
(usually 0 is used) denotes that the system is not available
and must be off for the time period. If this field is blank,
the schedule has values of 1 for all time periods.
Field: Width of the
Absorber Wall[LINK]
This number is the width of the absorber wall in the
thermal chimney. The width is expressed in units of m. Even
though this value is specified in Surface objects as well,
this value is used to compute the discharge air temperature
and the enhanced ventilation rate caused by the thermal
chimney.
Field:
Cross Sectional Area of Air Channel Outlet[LINK]
This number is the cross sectional area of air channel
outlet. The area is expressed in units of m2. The
enhanced air flow rate by the thermal chimney is dependent on
cross sectional areas of air channel inlet and outlet. Cross
sectional areas of air channel inlet will be described later
in conjunction with the distance from the top of thermal
chimney to each inlet and relative ratios of air flow rates
passing through each inlet.
Field: Discharge
Coefficient[LINK]
This dimensionless number is the discharge coefficient of
the thermal chimney. The ventilation rate enhanced by the
thermal chimney is also dependent on the discharge
coefficient.
Field: Zone <#> Name[LINK]
This field is the name of the zone (ref: Zone) to which the
thermal chimney is attached. It is used in conjunction with
the next three fields. Note that up to 20 sets of zone name,
distance from the top of the thermal chimney to each inlet,
relative ratios of air flow rates passing through each zone
and cross sectional areas of each air channel inlet may be
entered for a single thermal chimney if multiple zones share
the common thermal chimney.
Field:
Distance from Top of Thermal Chimney to Inlet <#>[LINK]
This field is the distance from the top of the thermal
chimney to each inlet corresponding to each zone. It is used
in conjunction with the zone name, relative ratios of air flow
rates passing through each zone and cross sectional areas of
each air channel inlet. The distance is expressed in units of
m. The air flow rate enhanced by the thermal chimney is
dependent on the distance between the thermal chimney outlet
and inlet.
Field:
Relative Ratios of Air Flow Rates Passing through Zone
<#>[LINK]
This dimensionless number is the relative ratio of air flow
rates enhanced by the thermal chimney passing through each
zone. The total air flow rate enhanced by the thermal chimney
is distributed to each zone based on this number if multiple
zones share the common thermal chimney. It is used in
conjunction with the zone name, the distance from the top of
the thermal chimney to each inlet and cross sectional areas of
each air channel inlet. Note that the sum of all ratios must
be equal to 1.0.
Field:
Cross Sectional Areas of Air Channel Inlet <#>[LINK]
This field is the cross sectional areas of each air channel
inlet corresponding to each zone. It is used in conjunction
with the zone name, the distance from the top of the thermal
chimney to each inlet and relative ratios of air flow rates
passing through each zone. The area is expressed in units of
m2. The air flow rate enhanced by the thermal
chimney is dependent on cross sectional areas of air channel
inlet and outlet.
An IDF example:
ZoneThermalChimney,
ThermalChimney1, !- Name of Thermal Chimney System
ThermalChimneyZone, !- Name of Thermal Chimney Zone
ThermalChimneyAvail, !- Availability Schedule Name
3.5, !- Width of the Absorber Wall
0.04, !- Cross Sectional Area of Air Channel Outlet
0.8, !- Discharge Coefficient
Zone1, !- Zone Name 1
8.0, !- Distance from the Top of the Thermal Chimney to Inlet 1
0.8, !- Relative Ratios of Air Flow Rates Passing through Zone 1
0.02, !- Cross Sectional Areas of Air Channel Inlet 1
Zone2, !- Zone Name 2
5.0, !- Distance from the Top of the Thermal Chimney to Inlet 2
0.2, !- Relative Ratios of Air Flow Rates Passing through Zone 2
0.02; !- Cross Sectional Areas of Air Channel Inlet 2
ZoneThermalChimney
Outputs[LINK]
Current ThermalChimney output variables:
HVAC,Average,Zone Thermal Chimney Current Density Volumetric Flow Rate [m3/s]
HVAC,Average,Zone Thermal Chimney Standard Density Volumetric Flow Rate [m3/s]
HVAC,Average,Zone Thermal Chimney Mass Flow Rate [kg/s]
HVAC,Average,Zone Thermal Chimney Outlet Temperature [C]
HVAC,Sum,Zone Thermal Chimney Heat Loss Energy [J]
HVAC,Sum,Zone Thermal Chimney Heat Gain Energy [J]
HVAC,Sum,Zone Thermal Chimney Volume [m3]
HVAC,Sum,Zone Thermal Chimney Mass [kg]
Zone Thermal
Chimney Heat Loss Energy [J][LINK]
The sensible (temperature) heat loss of each zone that
occurs when the thermal chimney cools the zone air.
Zone Thermal
Chimney Heat Gain Energy [J][LINK]
The sensible (temperature) heat gain of each zone that
occurs when the thermal chimney heats the zone air.
Zone Thermal Chimney
Volume [m3][LINK]
The air volumetric flow of each zone enhanced by the
thermal chimney.
Zone Thermal Chimney
Mass [kg][LINK]
The air mass flow of each zone enhanced by the thermal
chimney.
Zone
Thermal Chimney Current Density Volumetric Flow Rate
[m3/s][LINK]
The total air volumetric flow rate caused by the thermal
chimney evaluating density at the current zone conditions.
Zone
Thermal Chimney Standard Density Volumetric Flow Rate
[m3/s][LINK]
The total air volumetric flow rate caused by the thermal
chimney evaluating density at standard conditions.
Zone Thermal
Chimney Mass Flow Rate [kg/s][LINK]
The total air mass flow rate caused by the thermal
chimney.
Zone
Thermal Chimney Outlet Temperature [C][LINK]
The temperature of the air which is discharged from the
thermal chimney through the outlet.
ZoneAirMassFlowConservation[LINK]
This global object allows users to trigger the zone air
mass flow conservation calculation when desired. This object
has two input fields; the first choice input field allows the
user whether to enforce or not to enforce the zone air mass
flow conservation; and the second input field allows the user
to specify how infiltration object mass flow rate is
calculated for zone air mass flow balance calculation. The
first input field of this object has two choice KEYs: “Yes”
and “No”. If this input is specified as “Yes”, then energy
plus attempts to enforce the zone mass conservation, or else
if it is specified as “No”, then EnergyPlus calculation
defaults to zone air flow balance calculation that does not
include zone mixing objects and that assumes self-balanced
simple flow objects procedure, which may not necessarily
enforce zone air mass flow conservation unless the user has
specified a balanced flow to begin with. The zone air mass
flow conservation primarily accounts for the zonemixing
objects air flow in the zone air flow mass balance
calculation. In additional to the zonemixing object flow, the
procedure accounts for zone exhaust fan flows by providing
additional infiltration air flows when required in order to
balance the zone air mass flow. Hence, zonemixing object must
to be defined to trigger zone air mass flow conservation
calculation, whereas infiltration object is required only for
zones which are used as a source zone of the zone mixing
object. Zone
air mass flow balance calculation is enforced both for the
receiving and source zones of every mixing object defined. The
zone air mass flow conservation calculation uses two steps
procedure.
First, the ZoneMixing
object mass flow rate is adjusted or modified in order to
balance zone air mass flow while assuming the zone
infiltration object air mass flow self-balanced. This step
will always results in balanced zone air mass for receiving
zones of ZoneMixing
object but it may not necessarily result in a balanced air
mass flow for source zones. Infiltration objects air mass flow
rate defined for receiving zones are always calculated based
on user inputs and assumed to be self-balanced. The
infiltration mass flow rate of zones that serve only as a
source zone may require adjusting base infiltration flow,
which is calculated based on user inputs in the infiltration
objects, in order to balance the zone air mass flow, i.e., the
second calculation step replenishes the source zones with
additional infiltration air mass flow when required. This
second step is required in zones which serve as a source zone
for zone mixing objects and when the zone mixing source mass
flow rate exceeds the supply air mass flow rate. There are two
calculation procedures that users can choose from on how the
infiltration flow rate is calculated for source zones that
need infiltration object mass flow in order to balance the
zone air mass flow. The second optional input field “Source Zone
Infiltration Treatment” provides two Key choice inputs:
“AddInfiltrationFlow” and
“AdjustInfiltrationFlow”.
AddInfiltrationFlow: Energyplus adds
infiltration air mass flow rate on top of the base
infiltration flow, which is calculated using the infiltration
object user inputs, in order to balance the zone air mass
flow. This additional infiltration air mass flow is not
self-balanced, i.e., it is always assumed incoming flow. If no
infiltration air is required in order to be balance the zone
air mass flow, then the additional infiltration air mass flow
rate is set to zero. The base infiltration flow calculated
using the infiltration object user inputs is always assumed to
be self-balanced.
AdjustInfiltrationFlow: Energyplus may
adjust the base flow calculated using the infiltration object
user inputs if it is required in order to balance the zone air
mass flow. If it is not required to adjust the base
infiltration air flow, then the base infiltration air mass
flow, which is calculated from user input of the infiltration
object, is retained and assumed self-balanced. The report
variable “Zone
Infiltration Air Mass Flow Balance Status” indicates whether
the infiltration object air mass flow is adjusted or not. If
the value of this report variable is 0, then
the zone infiltration object mass flow rate is not included in
the zone mass flow balance hence the infiltration air flow
rate calculated based on the user specified inputs is
manintained as is and assumed self-balanced for current
timestep. If the value of this report variable is 1, then the
zone infiltration object mass flow rate is included in the
zone mass flow balance, hence the user specified infiltration
rate is modified and it is considered as incoming flow to the
zone, i.e., self-balanced assumption is not valid for current
time step.
This object is optional, only required in the input data
file if the user wishes to enforce the zone air mass flow
balance calculation that includes zonemixing and infiltration
objects.
Field:
Adjust Zone Mixing For Zone Air Mass Flow Balance[LINK]
It has two choice KEYs: “Yes” and “No”. If this input is
specified as “Yes”, then Energyplus attempts to enforce the
zone mass conservation, or else if it is specified as “No”,
then EnergyPlus calculation defaults to the existing
procedure, which may not necessarily enforce zone mass
conservation unless the user specified a balanced flow to
begin with. The default input is “No”. Note that “No” input
may also results in balanced flow depending on the system
specified. If this input field is specified as “No”, then the
next input field it not used.
Field:
Source Zone Infiltration Treatment[LINK]
It has two choice KEYs: “AddInfiltrationFlow” and
“AdjustInfiltrationFlow”. If this input is specified as
“AddInfiltrationFlow”, then Energyplus adds infiltration air
mass flow on top of the base infiltration flow calculated
using the infiltration object user inputs in order to balance
the zone air mass flow. The additional infiltration air mass
flow is not self-balanced. If this input is specified as
“AdjustInfiltrationFlow”, then Energyplus may adjust the base
flow calculated using the infiltration object user inputs if
it is required inorder to balance the zone air mass flow. If
it not required to adjust the base infiltration flow
calculated using the user specified infiltration object
inputs, then the base infiltration air mass flow is assumed
self-balanced.
And, a default IDF example is shown below:
ZoneAirMassFlowConservation,
Yes, !- Adjust Zone Mixing For Zone Air Mass Flow Balance
AdjustInfiltrationFlow; !- Source Zone Infiltration Treatment
Current ZoneAirMassFlowConservation
output variables:
HVAC, Average, Zone Supply Air Mass Flow Rate [kg/s]
HVAC, Average, Zone Exhaust Air Mass Flow Rate [kg/s]
HVAC, Average, Zone Return Air Mass Flow Rate [kg/s]
HVAC, Average, Zone Mixing Receiving Air Mass Flow Rate [kg/s]
HVAC, Average, Zone Mixing Source Air Mass Flow Rate [kg/s]
HVAC, Average, Zone Infiltration Air Mass Flow Balance Status, []
HVAC, Average, Zone Mass Balance Infiltration Air Mass Flow Rate, [kg/s]
Zone Supply Air
Mass Flow Rate [kg/s][LINK]
This output variable represents the total supply air mass
flow rate of a zone. The value is determined by summing the
supply air mass flow rates contributions from all supply air
inlet nodes of a zone.
Zone Exhaust Air
Mass Flow Rate [kg/s][LINK]
This output variable represents the total exhaust air mass
flow rate of a zone. The value is determined by summing the
exhaust air mass flow rates contributions from all exhaust air
nodes of a zone.
Zone Return Air
Mass Flow Rate [kg/s][LINK]
This output variable represents the total return air mass
flow rate of a zone. The value is determined by summing the
return air mass flow rates contributions from return air nodes
of a zone.
Zone
Mixing Receiving Air Mass Flow Rate [kg/s][LINK]
This output variable represents the total zone mixing air
mass flow rate of a receiving zone from one or more mixing
objects. The value is determined by summing the air mass flow
contributions from all zone mixing objects connected to a
single receiving zone.
Zone Mixing
Source Air Mass Flow Rate [kg/s][LINK]
This output variable represents the total zone mixing
source air mass flow rate of a source zone feeding one or more
mixing objects. The value is determined by summing the air
mass flow contributions from all zone mixing objects connected
to a single source zone.
Zone
Infiltration Air Mass Flow Balance Status [][LINK]
This output variable indicates the status of the
infiltration object mass flow rate use for balancing the zone
mass flow at each time step. It has values of either
0 or 1. If the value of this
report variable is 0 then the zone
infiltration object mass flow rate is not used in the zone
mass conservation calculation, hence the infiltration rate
calculated based on the user specified inputs is manintained
and the infiltration rate is assumed as self-balanced for
current timestep. If the value is 1 then the zone infiltration
object mass flow rate is included in the zone air mass flow
balance calculation, hence the user specified infiltration
rate is modified and it is considered as incoming flow to the
zone, i.e., self-balanced assumption is not valid for this
zone and current time step.
Zone
Mass Balance Infiltration Air Mass Flow Rate [kg/s][LINK]
This output variable represents the zone infiltration air
mass flow rate in kg/s. This output variable is reported only
for source zones and when the zone air mass flow balance flag
is set to “Yes” and its value depends on the “Source Zone
Infiltration Treatment” method specified. When the
infiltration treatment method selected is
“AddInfiltrationFlow” this report variable represents
additional infiltration air mass flow rate added on top of the
base infiltration air flow calculated using the user inputs
inroder to balance the zone air mass flow. In this case, the
base infiltration air mass flow calculated using the user
specified input is assumed self-balanced. When the
infiltration treatment method selected is
“AdjustInfiltrationFlow” this report variable represents the
base infiltration air mass flow calculated using the user
inputs and can be adjuted as needed in roder to balance the
zone air mass flow. If the value of the output variable “Zone
Infiltration Air Mass Flow Balance Status” is
0, then the infiltration air mass flow rate
calculated based on the user specified inputs is manintained
and the infiltration rate is assumed as self-balanced for
current timestep, or else if Zone
Infiltration Air Mass Flow Balance Status” is
1, then user specified infiltration rate is
adjusted and it is considered as incoming flow to the zone,
i.e., self-balanced assumption is not valid for this zone and
current time step.
Group - Airflow[LINK]
An important characteristic of energy consumption in buildings is the airflow between zones and airflow due to natural ventilation (e.g., open windows) or mechanically-induced ventilation (e.g., exhaust air fans). This group of objects describes those elements.
The AirflowNetwork model can also be used to model infiltration and mixing (zone-to-zone air flow) with or without the HVAC air distribution system operating (see Group - Airflow Network).
ZoneInfiltration:DesignFlowRate[LINK]
Infiltration is the unintended flow of air from the outdoor environment directly into a thermal zone. Infiltration is generally caused by the opening and closing of exterior doors, cracks around windows, and even in very small amounts through building elements. The basic equation used to calculate infiltration with this object is:
\[Infiltration = \left( {{I_{design}}} \right)\left( {{F_{schedule}}} \right)\left[ {A + B\left| {\left( {{T_{zone}} - {T_{odb}}} \right)} \right| + C\left( {WindSpeed} \right) + D\left( {Windspee{d^2}} \right)} \right]\]
More advanced infiltration calculations are possible using the EnergyPlus AirflowNetwork model for natural infiltration driven by wind and/or by forced air. Infiltration described by the equation shown above is entered into EnergyPlus using the following syntax. Exfiltration (the leakage of zone air to the outside) is generally handled better as zone exhaust air in the zone equipment description. The equation must always yield a non-negative results; negative values are set to 0.0.
The question of typical values for these coefficients is subject to debate. Ideally, one should do a detailed analysis of the infiltration situation and then determine a custom set of coefficients using methods such as those laid out in Chapter 26 of the ASHRAE Handbook of Fundamentals. The EnergyPlus defaults are 1,0,0,0 which give a constant volume flow of infiltration under all conditions.
BLAST (one of the EnergyPlus predecessors) used the following values as defaults: 0.606, 0.03636, 0.1177, 0. These coefficients produce a value of 1.0 at 0C deltaT and 3.35 m/s (7.5 mph) windspeed, which corresponds to a typical summer condition. At a winter condition of 40C deltaT and 6 m/s (13.4 mph) windspeed, these coefficients would increase the infiltration rate by a factor of 2.75.
In DOE-2 (the other EnergyPlus predecessor), the air change method defaults are (adjusted to SI units) 0, 0, 0.224 (windspeed), 0. With these coefficients, the summer conditions above would give a factor of 0.75, and the winter conditions would give 1.34. A windspeed of 4.47 m/s (10 mph) gives a factor of 1.0.
The source of the BLAST defaults is noted in the BLAST documentation as:
“Empirical equation and the coefficient default were determined from ASHRAE journal articles and other data on the effects of outdoor weather conditions.”
The source of the DOE-2 defaults is based on examining the infiltration relationships described in the ASHRAE Handbook of Fundamentals.
The EnergyPlus example files use all of the above, the BLAST defaults in some (e.g., GeometryTest), the DOE-2 defaults in some (e.g., 5ZoneAirCooled), and the EnergyPlus defaults in some (e.g., LgOffVAVDetCoil).
The local outdoor dry-bulb temperature used in the above basic equation (Todb) is typically a function of the height of the zone centroid above ground. The corresponding zone name is given in the second field. The local outdoor dry-bulb temperature calculation procedure is given in the section of “Local Outdoor Air Temperature Calculation” in the Engineering Reference.
The local outdoor wind speed used in the above basic equation (WindSpeed) is also a function of the height of the zone centroid above ground. The corresponding zone name is given in the second filed. The local outdoor wind speed calculation procedure is given in the section of “Local Wind Speed Calculation” in the Engineering Reference.
One or more infiltration objects can be defined for each zone, and the resulting infiltration rate for the zone will simply be the summation of the flow rates specified by the infiltration objects.
Inputs[LINK]
Field: Name[LINK]
The name of the ZoneInfiltration:DesignFlowRate object. This needs to be unique across all different ZoneInfiltration objects.
Field: Zone or ZoneList Name[LINK]
This field is the name of the zone (ref: Zone) or ZoneList (ref: ZoneLIst) and attaches a particular infiltration statement to a thermal zone or set of thermal zones in the building. When the ZoneList option is used then this infiltration definition is applied to each of the zones in the zone list effecting a global definition for the amount of infiltration flow rate in the zone. The Zonelist option can be used effectively with the flow/area, flow/exteriorarea, flow/exteriorwallarea, or airchanges/hour of the Design Flow Rate Calculation Method.
The name of the actual infiltration object becomes and
should be less than the standard length (100 characters) for a
name field. If it is greater than this standard length, it may
be difficult to specify in output reporting as it will be
truncated. A warning will be shown if the generated name is
greater than 100 characters. If it duplicates another such
concatenated name, there will be a severe error and terminate
the run.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design volume flow rate (Idesign) (see Design Flow Rate Calculation Method field and related subsequent fields). This fraction between 0.0 and 1.0 is noted as Fschedule in the above equation.
Field: Design Flow Rate Calculation Method[LINK]
This field is a key/choice field that tells which of the next four fields are filled and is descriptive of the method for calculating the design volume flow rate. The key/choices are:
Field: Design Flow Rate[LINK]
This field denotes the full design volume flow rate (m3/s). The previous field should choose “flow/zone” as the choice. The design volume flow rate (noted as Idesign in the above equation) is the maximum amount of infiltration expected at design conditions. The design value is modified by the schedule fraction (see Field:Schedule Name) and user specified coefficients (see “coefficient” fields below). The resulting volume flow rate is converted to mass flow using the current outdoor air density at each time step.
Field: Flow per Zone Floor Area[LINK]
This factor (m3/s-m2) is used, along with the Zone Area to determine the maximum Design Flow Rate as described in the Design Flow Rate field. The choice from the method field should be “Flow/Area”.
Field: Flow per Exterior Surface Area[LINK]
This factor (m3/s-m2) is used, along with the Exterior Surface Area in the Zone to determine the maximum Design Flow Rate as described in the Design Flow Rate field. The choice from the method field should be “Flow/Exteriorarea” or “Flow/ExteriorWallArea”.
Field: Air Changes per Hour[LINK]
This factor is used, along with the Zone Volume to determine the maximum Design Flow Rate as described in the Design Flow Rate field. The choice from the method field should be “AirChanges/Hour”.
Field: Constant Term Coefficient[LINK]
This number is the “A” parameter in the above infiltration equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter, however, is a constant under all conditions and is not modified by any environmental effect. As a result, it is dimensionless.
Field: Temperature Term Coefficient[LINK]
This number is the “B” parameter in the above infiltration equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter is modified by the temperature difference between the outdoor and indoor air dry-bulb temperatures. The units for this parameter are inverse Celsius.
Field: Velocity Term Coefficient[LINK]
This number is the “C” parameter in the above infiltration equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter is modified by the speed of wind being experienced outside the building. The units for this parameter are s/m.
Field: Velocity Squared Term Coefficient[LINK]
This number is the “D” parameter in the above infiltration equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter is modified by square of the speed of wind being experienced outside the building. The units for this parameter are s2/m2.
An IDF example:
Global Infiltration example:
ZoneInfiltration:EffectiveLeakageArea[LINK]
ZoneInfiltration:EffectiveLeakageArea model is similar to the other infiltration objects but uses a different equation to model the unintended flow of air from the outdoor environment directly into a thermal zone. Infiltration is generally caused by the opening and closing of exterior doors, cracks around windows, and even in very small amounts through building elements. This model is based on work by Sherman and Grimsrud (1980) and is appropriate for smaller, residential-type buildings. The equation used to calculate infiltration in the effective leakage area model is:
\[Infiltration = \left( {{F_{Schedule}}} \right)\frac{{{A_L}}}{{1000}}\sqrt {{C_s}\Delta T + {C_w}{{\left( {WindSpeed} \right)}^2}}\]
where \(\Delta T\) is the average difference between zone air temperature and the outdoor air temperature and the other coefficients are described below.
Note that the coefficients for the “EffectiveLeakageArea” model are not interchangeable with the similarly named coefficients in the “FlowCoefficient” model (see ZoneInfiltration:FlowCoefficient object).
One or more infiltration objects of different types can be defined for each zone, and the resulting infiltration rate for the zone will simply be the summation of the flow rates specified by the infiltration objects.
Inputs[LINK]
Field: Name[LINK]
The name of the ZoneInfiltration:EffectiveLeakageArea object. This needs to be unique across all different ZoneInfiltration objects.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches a particular infiltration statement to a thermal zone in the building.
Field: Schedule Name[LINK]
This field is the name of a schedule (ref: Schedule) that modifies the volume flow rate calculated by the model. This fraction between 0.0 and 1.0 is noted as Fschedule in the above equation.
Field: Effective Air Leakage Area[LINK]
This field is the effective air leakage area, in cm2, at 4 Pa. This is the value \({A_L}\)in the equation above. Effective leakage area data can be obtained from a whole-building pressure test (eg. blower door test). ASHRAE Handbook of Fundamentals also lists typical values component leakage areas for low-rise residential (e.g. Table 1 in Chapter 26 of HoF 2001). The value should correspond to a pressure difference of 4 Pa.
Field: Stack Coefficient[LINK]
This field is the value of the stack coefficient, \({C_s}\) in the equation above. The coefficient has units of (L/s)2/(cm4·K). Values for the “Basic Model Stack Coefficient” listed in the ASHRAE Handbook of Fundamentals (2005 and 2001) are:
One story house Two story house Three story house
0.000145 0.000290 0.000435
Field: Wind Coefficient[LINK]
This field is the value of the wind coefficient, \({C_w}\) in the equation above. The coefficient has units of (L/s)2/(cm4·(m/s)2). Values for the “Basic Model Wind Coefficient” listed in the ASHRAE Handbook of Fundamentals (2005 chapter 27; 2001, Chapter 26) depend on the type of shelter and are listed in the following tables.
Shelter class One story house Two story house Three story house
1 0.000319 0.000420 0.000494
2 0.000246 0.000325 0.000382
3 0.000174 0.000231 0.000271
4 0.000104 0.000137 0.000161
5 0.000032 0.000042 0.000049
Shelter class Description
1 No obstructions or local shielding
2 Typical shelter for an isolated rural house
3 Typical shelter caused by other buildings across the street
4 Typical shelter for urban buildings on larger lots
5 Typical shelter produced by buildings that are immediately adjacent.
An example IDF object is
ZoneInfiltration:FlowCoefficient[LINK]
ZoneInfiltration:FlowCoefficient model is similar to the other infiltration objects but uses a different equation to model the unintended flow of air from the outdoor environment directly into a thermal zone. Infiltration is generally caused by the opening and closing of exterior doors, cracks around windows, and even in very small amounts through building elements. This reformulated model is based on the AIM-2 model by Walker and Wilson (1998) and is appropriate for smaller, residential-type buildings. The equation used to calculate infiltration in the flow coefficient model is:
\[Infiltration = \left( {{F_{Schedule}}} \right)\sqrt {{{\left( {c\,{C_s}\Delta {T^n}} \right)}^2} + {{\left( {c\,{C_w}{{\left( {s * WindSpeed} \right)}^{2n}}} \right)}^2}}\]
Where \(\Delta T\) is the average difference between zone air temperature and the outdoor air temperature and the other coefficients are described below.
Note that the coefficients for the “Flow Coefficient” model are not interchangeable with the similarly named coefficients in the “Effective Leakage Area” model (see ZoneInfiltration:EffectiveLeakageArea object).
One or more infiltration objects of different types can be defined for each zone, and the resulting infiltration rate for the zone will simply be the summation of the flow rates specified by the infiltration objects.
Inputs[LINK]
Field: Name[LINK]
The name of the ZoneInfiltration:FlowCoefficient object. This needs to be unique across all different ZoneInfiltration objects.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches a particular infiltration statement to a thermal zone in the building.
Field: Schedule Name[LINK]
This field is the name of a schedule (ref: Schedule) that modifies the volume flow rate calculated by the model. This fraction between 0.0 and 1.0 is noted as Fschedule in the above equation.
Field: Flow Coefficient[LINK]
This field is the flow coefficient in m3/(s·Pan). This is the value \(c\) in the equation above. The flow coefficient can be determined from the effective leakage area and whole-building pressure tests (eg. blower door test).
Field: Stack Coefficient[LINK]
This field is the value of the stack coefficient, \({C_s}\) in the equation above. The coefficient has units of (Pa/K)n. Values for the “Enhanced Model Stack Coefficient” listed in the ASHRAE Handbook of Fundamentals (2005 and 2001) are:
One story house Two story house Three story house
With Flue 0.069 0.089 0.107
No Flue 0.054 0.078 0.098
Field: Pressure Exponent[LINK]
This field is the value of the pressure exponent, n in the equation above. The pressure exponent generally lies between 0.6 and 0.7 with a typical value of n = 0.67 for the enhanced model.
Field: Wind Coefficient[LINK]
This field is the value of the wind coefficient, \({C_w}\) in the equation above. The coefficient has units of (Pa·s2/m2)n. Values for the “Enhanced Model Wind Coefficient” listed in the ASHRAE Handbook of Fundamentals (2005 and 2001) are:
One story house Two story house Three story house
Basement/slab;With Flue 0.142 0.156 0.167
Basement/slab; No Flue 0.156 0.170 0.170
Crawlspace; With Flue 0.128 0.142 0.154
Crawlspace; No Flue 0.128 0.142 0.151
Field: Shelter Factor[LINK]
This field is the value of the wind coefficient, \(s\) in the equation above. The coefficient is dimensionless. Values for the “Enhanced Model Shelter Factor” listed in the ASHRAE Handbook of Fundamentals (2005 and 2001) are:
Shelter class No Flue One story house with flue Two story house with flue Three story house with flue
1 1.00 1.10 1.07 1.06
2 0.90 1.02 0.98 0.97
3 0.70 0.86 0.81 0.79
4 0.50 0.70 0.64 0.61
5 0.30 0.54 0.47 0.43
Shelter class Description
1 No obstructions or local shielding
2 Typical shelter for an isolated rural house
3 Typical shelter caused by other buildings across the street
4 Typical shelter for urban buildings on larger lots
5 Typical shelter produced by buildings that are immediately adjacent.
An Example IDF object is:
Outputs[LINK]
Zone Infiltration Sensible Heat Loss Energy [J][LINK]
The sensible (temperature) heat loss that occurs when the infiltration air temperature (outdoor) < zone air temperature.
Zone Infiltration Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat gain that occurs when the infiltration air temperature (outdoor) >= zone air temperature.
Zone Infiltration Latent Heat Loss Energy [J][LINK]
The latent heat loss that occurs when the infiltration air humidity ratio (outdoor) < zone air humidity ratio.
Zone Infiltration Latent Heat Gain Energy [J][LINK]
The latent heat gain that occurs when the infiltration air humidity ratio (outdoor) >= zone air humidity ratio.
Zone Infiltration Total Heat Loss Energy [J][LINK]
The total heat loss that occurs when the sum of Zone Infiltration Sensible Heat Gain Energy and Zone Infiltration Latent Heat Gain Energy < the sum of Zone Infiltration Sensible Heat Loss Energy and Zone Infiltration Latent Heat Loss Energy.
Zone Infiltration Total Heat Gain Energy [J][LINK]
The total heat gain that occurs when the sum of Zone Infiltration Sensible Heat Gain Energy and Zone Infiltration Latent Heat Gain Energy >= the sum of Zone Infiltration Sensible Heat Loss Energy and Zone Infiltration Latent Heat Loss Energy.
Zone Infiltration Current Density Volume [m3][LINK]
Zone Infiltration Current Density Volume Flow Rate [m3/s][LINK]
These outputs are the total volume and volume flow rate of infiltration air based on the current density of zone air.
Zone Infiltration Standard Density Volume [m3][LINK]
Zone Infiltration Standard Density Volume Flow Rate [m3/s][LINK]
These outputs are the total volume and volume flow rate of infiltration air based on the standard density of air. Standard density in EnergyPlus corresponds to 20ºC drybulb, dry air, and nominally adjusted for elevation.
Zone Infiltration Mass [kg][LINK]
The mass flow of the Infiltration air.
Zone Infiltration Mass Flow Rate [kg/s][LINK]
The mass flow rate of the Infiltration air.
Zone Infiltration Air Change Rate [ach][LINK]
The rate of infiltration in air changes per hour.
ZoneVentilation:DesignFlowRate[LINK]
Ventilation is the purposeful flow of air from the outdoor environment directly into a thermal zone in order to provide some amount of non-mechanical cooling. Ventilation, as specified by the input syntax for the ZoneVentilation:DesignFlowRate object, is intended to model “simple” ventilation as opposed to the more detailed ventilation investigations that can be performed with the AirflowNetwork model or with air systems that have outdoor air mixers. Zone ventilation, as specified via this input object, can be controlled by a schedule and through the specification of minimum, maximum and delta temperatures as described below. The temperatures can be either single constant values for the entire simulation or schedules which can vary over time. As with infiltration, the actual flow rate of ventilation air can be modified by the temperature difference between the inside and outside environment and the wind speed. The basic equation used to calculate ventilation with this model is:
\[Ventilation = \left( {{V_{design}}} \right)\left( {{F_{schedule}}} \right)\left[ {A + B\left| {{T_{zone}} - {T_{odb}}} \right| + C\left( {WindSpeed} \right) + D\left( {WindSpee{d^2}} \right)} \right]\]
Similar to infiltration, the question of typical values for these coefficients is subject to debate. Ideally, one should do a detailed analysis of the ventilation situation and then determine a custom set of coefficients using methods such as those laid out in Chapter 26 of the ASHRAE Handbook of Fundamentals. The EnergyPlus defaults are 1,0,0,0 which give a constant volume flow of ventilation under all conditions. The following discussion is duplicated from the infiltration design flow rate object. The equation must always yield a non-negative results; negative values are set to 0.0.
BLAST (one of the EnergyPlus predecessors) used the following values as defaults: 0.606, 0.03636, 0.1177, 0. These coefficients produce a value of 1.0 at 0C deltaT and 3.35 m/s (7.5 mph) windspeed, which corresponds to a typical summer condition. At a winter condition of 40C deltaT and 6 m/s (13.4 mph) windspeed, these coefficients would increase the infiltration rate by a factor of 2.75.
In DOE-2 (the other EnergyPlus predecessor), the air change method defaults are (adjusted to SI units) 0, 0, 0.224 (windspeed), 0. With these coefficients, the summer conditions above would give a factor of 0.75, and the winter conditions would give 1.34. A windspeed of 4.47 m/s (10 mph) gives a factor of 1.0.
The source of the BLAST defaults is noted in the BLAST documentation as:
“Empirical equation and the coefficient default were determined from ASHRAE journal articles and other data on the effects of outdoor weather conditions.”
The source of the DOE-2 defaults is based on examining the infiltration relationships described in the ASHRAE Handbook of Fundamentals.
The local outdoor dry-bulb temperature used in the above basic equation (Todb) is typically a function of the height of the zone centroid above ground. The corresponding zone name is given in the second field. The local outdoor dry-bulb temperature calculation procedure is described in the “Local Outdoor Air Temperature Calculation” section of the Engineering Reference.
The local outdoor wind speed used in the above basic equation (WindSpeed) is also a function of the height of the zone centroid above ground. The corresponding zone name is given in the second field. The local outdoor wind speed calculation procedure is described in the “Local Wind Speed Calculation” section of the Engineering Reference.
One or more ventilation objects (i.e., ZoneVentilation:DesignFlowRate and/or ZoneVentilation:WindandStackOpenArea) can be defined for each zone, and the resulting ventilation rate for the zone will simply be the summation of the flow rates specified by the ventilation objects.
More advanced ventilation calculations are possible using the EnergyPlus AirflowNetwork model.
Inputs[LINK]
Field: Name[LINK]
The name of the ZoneVentilation:DesignFlowRate object.
Field: Zone or ZoneList Name[LINK]
This field is the name of the zone (ref: Zone) or ZoneList (ref: ZoneList) and attaches a particular ventilation statement to a thermal zone or set of thermal zones in the building. When the ZoneList option is used then this ventilation definition is applied to each of the zones in the zone list effecting a global definition for the amount of infiltration flow rate in the zone. The Zonelist option can be used effectively with the flow/area, flow/person, or airchanges/hour of the Design Flow Rate Calculation Method.
The name of the actual ventilation object becomes and
should be less than the standard length (100 characters) for a
name field. If it is greater than this standard length, it may
be difficult to specify in output reporting as it will be
truncated. A warning will be shown if the generated name is
greater than 100 characters. If it duplicates another such
concatenated name, there will be a severe error and terminate
the run.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design volume flow rate (Vdesign) (see Design Flow Rate Calculation Method field and related subsequent fields). This fraction between 0.0 and 1.0 is noted as Fschedule in the above equation.
Field: Design Flow Rate Calculation Method[LINK]
This field is a key/choice field that tells which of the next four fields are filled and is descriptive of the method for calculating the design volume flow rate. The key/choices are:
Field: Design Flow Rate[LINK]
This field denotes the full design volume flow rate (m3/s). The previous field should choose “flow/zone” as the choice. The design volume flow rate (noted as Vdesign in the above equation) is the maximum amount of ventilation expected at design conditions. The design value is modified by the schedule fraction (see Field: Schedule Name) and user specified coefficients (see four “coefficient” fields below).
Field: Flow Rate per Zone Floor Area[LINK]
This factor (m3/s-m2) is used, along with the Zone Area to determine the maximum Design Volume Flow Rate as described in the Design Volume Flow Rate field. The choice from the method field should be “flow/area”.
Field: Flow Rate per Person[LINK]
This factor (m3/s-person) is used, along with the nominal (maximum) number of occupants (people) in the Zone to determine the maximum Design Volume Flow Rate as described in the Design Volume Flow Rate field. The choice from the method field should be “flow/person”.
Field: Air Changes per Hour[LINK]
Field: Ventilation Type[LINK]
This alpha character string defines the type of ventilation as one of the following options: Natural, Exhaust, Intake, or Balanced. Natural ventilation is assumed to be air movement/exchange as a result of openings in the building façade and will not consume any fan energy. Values for fan pressure and efficiency for natural ventilation are ignored. For either Exhaust or Intake, values for fan pressure and efficiency define the fan electric consumption. For Natural and Exhaust ventilation, the conditions of the air entering the space are assumed to be equivalent to outside air conditions. For Intake and Balanced ventilation, an appropriate amount of fan heat is added to the entering air stream. For Balanced ventilation, both an intake fan and an exhaust fan are assumed to co-exist, both having the same flow rate and power consumption (using the entered values for fan pressure rise and fan total efficiency). Thus, the fan electric consumption for Balanced ventilation is twice that for the Exhaust or Intake ventilation types which employ only a single fan.
Field: Fan Pressure Rise[LINK]
This is the pressure rise experienced across the fan in Pascals (N/m2). This is a function of the fan and plays a role in determining the amount of energy consumed by the fan.
Field: Fan Total Efficiency[LINK]
This value is the overall efficiency of the fan, i.e., the ratio of the power delivered to the fluid to the electrical input power. It is the product of the motor efficiency and the impeller efficiency. The motor efficiency is the power delivered to the shaft divided by the electrical power input to the motor. The impeller efficiency is power delivered to the fluid (air) divided by the shaft power. The power delivered to the fluid is the mass flow rate of the air multiplied by the pressure rise divided by the air density. This input value must be between 0 and 1.”
Field: Constant Term Coefficient[LINK]
This number is the “A” parameter in the above ventilation equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter, however, is a constant under all conditions and is not modified by any environmental effect. As a result, it is dimensionless.
Field: Temperature Term Coefficient[LINK]
This number is the “B” parameter in the above ventilation equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter is modified by the temperature difference between the outdoor and indoor air dry-bulb temperatures. The units for this parameter are inverse Celsius.
Field: Velocity Term Coefficient[LINK]
This number is the “C” parameter in the above ventilation equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter is modified by the speed of wind being experienced outside the building. The units for this parameter are s/m.
Field: Velocity Squared Term Coefficient[LINK]
This number is the “D” parameter in the above ventilation equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter is modified by square of the speed of wind being experienced outside the building. The units for this parameter are s2/m2.
Field: Minimum Indoor Temperature[LINK]
This is the indoor temperature (in Celsius) below which ventilation is shutoff. The minimum value for this field is -100.0C and the maximum value is 100.0C. The default value is -100.0C if the field is left blank. This lower temperature limit is intended to avoid overcooling a space and thus result in a heating load. For example, if the user specifies a minimum temperature of 20C, ventilation is assumed to be available if the zone air temperature is above 20C. If the zone air temperature drops below 20C, then ventilation is automatically turned off.
Field: Minimum Indoor Temperature Schedule Name[LINK]
This alpha field defines the name of a schedule (ref. Schedule objects) which contains the minimum indoor temperature (in Celsius) below which ventilation is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field and has the same functionality as the Minimum Indoor Temperature field. If the user enters a valid schedule name, the minimum temperature values specified in this schedule will override the constant value specified in the Minimum Indoor Temperature field.
Field: Maximum Indoor Temperature[LINK]
This is the indoor temperature (in Celsius) above which ventilation is shutoff. The minimum value for this field is -100.0C and the maximum value is 100.0C. The default value is 100.0C if the field is left blank. This upper temperature limit is intended to avoid overheating a space and thus result in a cooling load. For example, if the user specifies a maximum temperature of 28C, ventilation is assumed to be available if the zone air temperature is below 28C. If the zone air temperature increases to 28C, then ventilation is automatically turned off.
Field: Maximum Indoor Temperature Schedule Name[LINK]
This alpha field defines the name of a schedule (ref. Schedule objects) which contains the maximum indoor temperature (in Celsius) above which ventilation is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field and has the same functionality as the Maximum Indoor Temperature field. If the user enters a valid schedule name, the maximum temperature values specified in this schedule will override the constant value specified in the Maximum Indoor Temperature field.
Field: Delta Temperature[LINK]
This is the temperature difference (in Celsius) between the indoor and outdoor air dry-bulb temperatures below which ventilation is shutoff. The minimum value for this field is -100.0C and the default value is also -100.0C if the field is left blank. This field allows ventilation to be stopped if the temperature outside is too warm and could potentially heat the space. For example, if the user specifies a delta temperature of 2C, ventilation is assumed to be available if the outside air temperature is at least 2C cooler than the zone air temperature. If the outside air dry-bulb temperature is less than 2C cooler than the indoor dry-bulb temperature, then ventilation is automatically turned off.
The values for this field can include negative numbers. This allows ventilation to occur even if the outdoor temperature is above the indoor temperature. The Delta Temperature is used in the code in the following way:
Thus, if a large negative number is input for DeltaTemperature, the ventilation can be kept on even if the outdoor temperature is greater than the indoor temperature. This is useful for uncontrolled natural ventilation (open windows) or as a way to estimate the effect of required ventilation air for load calculations.
Field: Delta Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the temperature difference (in Celsius) between the indoor and outdoor air dry-bulb temperatures below which ventilation is shutoff as a function of time. The minimum temperature difference value in the schedule can be -100C. This field is an optional field and has the same functionality as the Delta Temperature field. If the user enters a valid schedule name, the delta temperature values specified in this schedule will override the constant value specified in the Delta Temperature field.
Field: Minimum Outdoor Temperature[LINK]
This is the outdoor temperature (in Celsius) below which ventilation is shut off. The minimum value for this field is -100.0C and the maximum value is 100.0C. The default value is -100.0C if the field is left blank. This lower temperature limit is intended to avoid overcooling a space, which could result in a heating load.
Field: Minimum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the minimum outdoor temperature (in Celsius) below which ventilation is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field and has the same functionality as the Minimum Outdoor Temperature field. If the user enters a valid schedule name, the temperature values in this schedule will override the constant value specified in the Minimum Outdoor Temperature field.
Field: Maximum Outdoor Temperature[LINK]
This is the outdoor temperature (in Celsius) above which ventilation is shut off. The minimum value for this field is -100.0C and the maximum value is 100.0C. The default value is 100.0C if the field is left blank. This upper temperature limit is intended to avoid overheating a space, which could result in a cooling load.
Field: Maximum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the minimum outdoor temperature (in Celsius) above which ventilation is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field and has the same functionality as the Maximum Outdoor Temperature field. If the user enters a valid schedule name, the temperature values in this schedule will override the constant value specified in the Maximum Outdoor Temperature field.
Field: Maximum Wind Speed[LINK]
This is the wind speed (m/s) above which ventilation is shut off. This can help simulate conditions where one would normally close windows to avoid chaos in a space (papers blowing around, etc.).
Two IDF examples are provided below:
Global Ventilation example:
ZoneVentilation:WindandStackOpenArea[LINK]
For this model, the ventilation air flow rate is a function of wind speed and thermal stack effect, along with the area of the opening being modeled. This object can be used alone or in combination with ZoneVentilation:DesignFlowRate objects. This model is intended for simplified ventilation calculations as opposed to the more detailed ventilation investigations that can be performed with the AirflowNetwork model. Using the “Wind and Stack with Open Area” model, the natural ventilation flow rate can be controlled by a multiplier fraction schedule applied to the user-defined opening area and through the specification of minimum, maximum and delta temperatures. The temperatures can be either single constant values for the entire simulation or schedules which can vary over time. The equation used to calculate the ventilation rate driven by wind is:
\[{Q_w} = {C_w}{A_{opening}}{F_{schedule}}V\]
where,
Qw= Volumetric air flow rate driven by wind [m3/s]
Cw= Opening effectiveness [dimensionless]
Aopening= Opening area [m2]
Fschedule = Open area fraction [user-defined schedule value, dimensionless]
V= Local wind speed [m/s]
The equation used to calculate the ventilation rate due to stack effect is:
\[{Q_s} = {C_D}{A_{opening}}{F_{schedule}}\sqrt {2g\Delta {H_{NPL}}(|{T_{zone}} - {T_{odb}}|/{T_{zone}})}\]
where,
Qs= Volumetric air flow rate due to stack effect [m3/s]
CD= Discharge coefficient for opening [dimensionless]
Aopening= Opening area [m2]
Fschedule = Open area fraction [user-defined schedule value, dimensionless]
ΔHNPL= Height from midpoint of lower opening to the neutral pressure level [m].
Estimation of this value is difficult; refer to Chapter 16 of the 2009 ASHRAE Handbook of Fundamentals for guidance.
Tzone= Zone air dry-bulb temperature [K]
Todb= Local outdoor air dry-bulb temperature [K]
The total ventilation rate calculated by this model is the quadrature sum of the wind and stack air flow components:
\[Ventilatio{n_{WindAndStack}} = \sqrt {{Q_s}^2 + {Q_w}^2}\]
The local outdoor air dry-bulb temperature used in the stack effect equation (Todb) is typically a function of the height of the zone centroid above ground. The corresponding zone name is given in the second field. The local outdoor air dry-bulb temperature calculation procedure is described in the “Local Outdoor Air Temperature Calculation” section of the Engineering Reference.
The local outdoor wind speed used in the above wind-driven equation (V) is also a function of the height of the zone centroid above ground. The corresponding zone name is given in the second field. The local outdoor wind speed calculation procedure is described in the “Local Wind Speed Calculation” section of the Engineering Reference.
One or more ventilation objects (i.e., ZoneVentilation:DesignFlowRate and/or ZoneVentilation:WindandStackOpenArea) can be defined for each zone, and the resulting ventilation rate for the zone will simply be the summation of the flow rates specified by the ventilation objects.
More advanced ventilation calculations are possible using the EnergyPlus AirflowNetwork model.
Inputs[LINK]
Field: Name[LINK]
The name of the ZoneVentilation:WindandStackOpenArea object.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches a particular ventilation statement to a thermal zone in the building.
Field: Opening Area[LINK]
This is the opening area exposed to outdoors (m2) in a zone.
Field: Opening Area Fraction Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) which modifies the Opening Area value (see previous field). The schedule values must be any positive number between 0 and 1 as a fraction. The actual opening area in a zone for a particular simulation time step is defined as the product of the Opening Area input field and the value specified by the schedule named in this input field.
Field: Opening Effectiveness[LINK]
This field is the opening effectiveness (Cw). The value must be between 0.0 and 1.0 or the value can be autocalculated. If a real value is input, that constant value will be used in the calculations. Otherwise, this field can be left blank (default = Autocalculate) or the user can input Autocalculate. Based on recommended values provided in Chapter 16 of the 2009 ASHRAE Handbook of Fundamentals, Cw = 0.55 for perpendicular winds and Cw = 0.3 for diagonal winds. For Autocalculate, any angles between perpendicular and diagonal are linearly interpolated between 0.3 and 0.55 by the model.
Field: Effective Angle[LINK]
This is the angle in degrees counting from the North clockwise to the opening outward normal. The value must be between 0 and 360, with the default being 0 if this input field is left blank. The Effective Angle is 0 if the opening outward normal faces North, 90 if faces East, 180 if faces South, and 270 if faces West. The value is fixed and independent of coordinate system defined in the GlobalGeometryRules object. This input field value is used to calculate the angle between the wind direction and the opening outward normal to determine the opening effectiveness values when the input field Opening Effectiveness = Autocalculate.
Field: Height Difference[LINK]
This is the height difference between the midpoint of the lower opening and the neutral pressure level in meters. This value is a required user input.
Field: Discharge Coefficient for Opening[LINK]
This is the discharge coefficient for the opening (CD). The value must be between 0.0 and 1.0, or the value can be autocalculated. If a real value is input, that constant value will be used in the calculations. Otherwise, this field can be left blank (default = Autocalculate) or the user can input Autocalculate. For Autocalculate, the program will determine the discharge coefficient based on the following equation:
\[{C_D} = 0.40 + 0.0045\left| {{T_{zone}} - {T_{odb}}} \right|\]
Field: Minimum Indoor Temperature[LINK]
This is the indoor temperature (in Celsius) below which ventilation is shutoff. The minimum value for this field is -100.0C and the maximum value is 100.0C. The default value is -100.0C if the field is left blank. This lower temperature limit is intended to avoid overcooling a space and thus result in a heating load. For example, if the user specifies a minimum temperature of 20C, ventilation is assumed to be available if the zone air temperature is above 20C. If the zone air temperature drops below 20C, then ventilation is automatically turned off.
Field: Minimum Indoor Temperature Schedule Name[LINK]
This alpha field defines the name of a schedule (ref. Schedule objects) which contains the minimum indoor temperature (in Celsius) below which ventilation is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field and has the same functionality as the Minimum Indoor Temperature field. If the user enters a valid schedule name, the minimum temperature values specified in this schedule will override the constant value specified in the Minimum Indoor Temperature field.
Field: Maximum Indoor Temperature[LINK]
This is the indoor temperature (in Celsius) above which ventilation is shutoff. The minimum value for this field is -100.0C and the maximum value is 100.0C. The default value is 100.0C if the field is left blank. This upper temperature limit is intended to avoid overheating a space and thus result in a cooling load. For example, if the user specifies a maximum temperature of 28C, ventilation is assumed to be available if the zone air temperature is below 28C. If the zone air temperature increases to 28C, then ventilation is automatically turned off.
Field: Maximum Indoor Temperature Schedule Name[LINK]
This alpha field defines the name of a schedule (ref. Schedule objects) which contains the maximum indoor temperature (in Celsius) above which ventilation is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field and has the same functionality as the Maximum Indoor Temperature field. If the user enters a valid schedule name, the maximum temperature values specified in this schedule will override the constant value specified in the Maximum Indoor Temperature field.
Field: Delta Temperature[LINK]
This is the temperature difference (in Celsius) between the indoor and outdoor air dry-bulb temperatures below which ventilation is shutoff. The minimum value for this field is -100.0C and the default value is also -100.0C if the field is left blank. This field allows ventilation to be stopped if the temperature outside is too warm and could potentially heat the space. For example, if the user specifies a delta temperature of 2C, ventilation is assumed to be available if the outside air temperature is at least 2C cooler than the zone air temperature. If the outside air dry-bulb temperature is less than 2C cooler than the indoor dry-bulb temperature, then ventilation is automatically turned off.
The values for this field can include negative numbers. This allows ventilation to occur even if the outdoor temperature is above the indoor temperature. The Delta Temperature is used in the code in the following way:
Thus, if a large negative number is input for DeltaTemperature, the ventilation can be kept on even if the outdoor temperature is greater than the indoor temperature. This is useful for uncontrolled natural ventilation (open windows) or as a way to estimate the effect of required ventilation air for load calculations.
Field: Delta Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the temperature difference (in Celsius) between the indoor and outdoor air dry-bulb temperatures below which ventilation is shutoff as a function of time. The minimum temperature difference value in the schedule can be -100C. This field is an optional field and has the same functionality as the Delta Temperature field. If the user enters a valid schedule name, the delta temperature values specified in this schedule will override the constant value specified in the Delta Temperature field.
Field: Minimum Outdoor Temperature[LINK]
This is the outdoor temperature (in Celsius) below which ventilation is shut off. The minimum value for this field is -100.0C and the maximum value is 100.0C. The default value is -100.0C if the field is left blank. This lower temperature limit is intended to avoid overcooling a space, which could result in a heating load.
Field: Minimum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the minimum outdoor temperature (in Celsius) below which ventilation is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field and has the same functionality as the Minimum Outdoor Temperature field. If the user enters a valid schedule name, the temperature values in this schedule will override the constant value specified in the Minimum Outdoor Temperature field.
Field: Maximum Outdoor Temperature[LINK]
This is the outdoor temperature (in Celsius) above which ventilation is shut off. The minimum value for this field is -100.0C and the maximum value is 100.0C. The default value is 100.0C if the field is left blank. This upper temperature limit is intended to avoid overheating a space, which could result in a cooling load.
Field: Maximum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the minimum outdoor temperature (in Celsius) above which ventilation is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field and has the same functionality as the Maximum Outdoor Temperature field. If the user enters a valid schedule name, the temperature values in this schedule will override the constant value specified in the Maximum Outdoor Temperature field.
Field: Maximum Wind Speed[LINK]
This is the wind speed (m/s) above which ventilation is shut off. This can help simulate conditions where one would normally close windows to avoid chaos in a space (papers blowing around, etc.).
An IDF example is provided below:
**
Outputs[LINK]
Current ventilation output variables:
Zone Ventilation Sensible Heat Loss Energy [J][LINK]
The sensible (temperature) heat loss that occurs when the ventilation inlet air temperature < zone air temperature. If multiple ventilation objects are specified for a particular zone, the ventilation inlet air temperature is from all ZoneVentilation:DesignFlowRate and ZoneVentilation:WindandStackOpenArea objects specified for the zone.
Zone Ventilation Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat gain that occurs when the ventilation inlet air temperature >= zone air temperature. If multiple ventilation objects are specified for a particular zone, the ventilation inlet air temperature is from all ZoneVentilation:DesignFlowRate and ZoneVentilation:WindandStackOpenArea objects specified for the zone.
Zone Ventilation Latent Heat Loss Energy [J][LINK]
The latent heat loss that occurs when the Ventilation air humidity ratio (outdoor) < zone air humidity ratio from all ZoneVentilation:DesignFlowRate and ZoneVentilation:WindandStackOpenArea objects specified for the zone.
Zone Ventilation Latent Heat Gain Energy [J][LINK]
The latent heat gain that occurs when the Ventilation air humidity ratio (outdoor) >= zone air humidity ratio from all ZoneVentilation:DesignFlowRate and ZoneVentilation:WindandStackOpenArea objects specified for the zone.
Zone Ventilation Total Heat Loss Energy [J][LINK]
The total heat loss that occurs when the sum of Zone Ventilation Sensible Heat Gain Energy and Zone Ventilation Latent Heat Gain Energy < the sum of Zone Ventilation Sensible Heat Loss Energy and Zone Ventilation Latent Heat Loss Energy.
Zone Ventilation Total Heat Gain Energy [J][LINK]
The total heat gain that occurs when the sum of Zone Ventilation Sensible Heat Gain Energy and Zone Ventilation Latent Heat Gain Energy >= the sum of Zone Ventilation Sensible Heat Loss Energy and Zone Ventilation Latent Heat Loss Energy.
Zone Ventilation Current Density Volume [m3][LINK]
Zone Ventilation Current Density Volume Flow Rate [m3/s][LINK]
These outputs are the total volume and volume flow rate of ventilation air based on the current density of zone air.
Zone Ventilation Standard Density Volume [m3][LINK]
Zone Ventilation Standard Density Volume Flow Rate [m3/s][LINK]
These outputs are the total volume and volume flow rate of ventilation air based on the standard density of air. Standard density in EnergyPlus corresponds to 20ºC drybulb, dry air, and nominally adjusted for elevation.
Zone Ventilation Mass [kg][LINK]
This output is the total mass flow into a particular zone from outdoors.
Zone Ventilation Mass Flow Rate [kg/s][LINK]
This output is the total mass flow rate into a particular zone from outdoors.
Zone Ventilation Air Change Rate [ach][LINK]
The volume flow rate of the ventilation air in air changes per hour.
Zone Ventilation Fan Electric Energy [J][LINK]
The fan electrical consumption for Intake or Exhaust ventilation types (for ZoneVentilation:DesignFlowRate objects only).
Zone Ventilation Air Inlet Temperature [C][LINK]
This is equal to the outdoor air temperature except when INTAKE fan power is included (for ZoneVentilation:DesignFlowRate objects only). When intake fan power is used, then the additional heat due to the fan is added to the outdoor temperature and this will be reported as the inlet air temperature. If multiple ventilation objects are specified for a particular zone, the reported value is the mass flow weighted temperature for the multiple ventilation objects specified for this zone.
ZoneAirBalance:OutdoorAir[LINK]
This model calculates a combined zone outdoor airflow by including interactions between mechanical ventilation, infiltration and duct leakage. It is mainly applied to a single zone (e.g., residential) building. The model combines all outdoor airflows from ZoneInfiltration and ZoneVentilation objects in the same zone. This object also includes the induced outdoor airflows due to unbalanced duct leakage, and unbalanced outdoor airflows introduced by unbalanced airflows from ZoneHVAC:EnergyRecoveryVentilator objects when the exhaust airflow is greater than the supply outdoor airflow. This model is intended for simplified outdoor airflow calculations as opposed to the more detailed outdoor airflow investigations that can be performed with the AirflowNetwork model. The equation used to calculate the combined zone outdoor airflow is:
\[Q = \sqrt {{Q_n}^2 + {Q_{u,v}}^2 + {Q_{u,l}}^2} + {Q_{b,v}}\]
where,
Q= Combined outdoor airflow with infiltration, balanced and unbalanced outdoor air flows, and unbalanced duct leakage [m3/s]
Qn= Natural infiltration airflow from ZoneInfiltration:* objects [m3/s]
Qb,v= Balanced ventilation airflow, excluding infiltration [m3/s]
Qu,v= Unbalanced ventilation airflow, excluding infiltration [m3/s]
Qu,l= Unbalanced duct leakage: the difference between supply and return leaks [m3/s]
This object cannot be used simultaneously with the EnergyPlus AirflowNetwork model. If the AirflowNetwork model is active for a simulation time step, the Air Balance Method is reset to “None” for that time step. More advanced outdoor airflow calculations are possible using the EnergyPlus AirflowNetwork model.
This object does not combine any airflows from Fan:ZoneExhaust objects and is independent of HVAC equipment operation.
This object will not work with the AvailabilityManager:HybridVentilation object in the same zone, when the Simple Airflow Control Type Schedule Name is provided in the HybridVentilation object. For this case, the Air Balance Method is reset to “None”.
Inputs[LINK]
Field: Name[LINK]
The name of the ZoneOutdoorAir:Combined object.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches a combined outdoor airflow statement to a thermal zone in the building.
Field: Air Balance Method[LINK]
This choice field determines the air balance method. Two choices are Quadrature and None. If Quadrature, the combined zone outdoor air flow is calculated based on the above equation. If None, no combining of outdoor air will be performed (i.e., any ZoneInfiltration:* and ZoneVentilation:* objects specified for this zone are simulated individually).
Field: Induced Outdoor Air Due to Unbalanced Duct Leakage[LINK]
This is the induced outdoor airflow rate, in m3/s, due to unbalanced duct leakage. If left blank, the default value is 0.
Field: Induced Outdoor Air Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) which modifies the induced outdoor airflow rate value (see previous field). The schedule values must be any positive number between 0 and 1 as a fraction. The actual induced outdoor airflow rate in a zone for a particular simulation time step is defined as the product of the Induced Outdoor Air Due to Unbalanced Duct Leakage input field and the value specified by the schedule named in this input field.
An IDF example is provided below:
Outputs[LINK]
ZoneAirBalance:OutdoorAir output variables will be provided when the Air Balance Method is Quadrature. Output variables from the associated ZoneVentilation:* and ZoneInfiltration:* objects for the same zone will not be produced when ZoneAirBalance:OutdoorAir output variables are available. If the Air Balance Method = None, then no ZoneAirBalance:OutputAir outputs will be produced and the associated ZoneVentilation:* and ZoneInfiltration:* objects will specify their output variables for the zone.
Zone Combined Outdoor Air Sensible Heat Loss Energy [J][LINK]
The sensible (temperature) heat loss that occurs when the outdoor air temperature < zone air temperature.
Zone Combined Outdoor Air Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat gain that occurs when the outdoor air temperature >= zone air temperature.
Zone Combined Outdoor Air Latent Heat Loss Energy [J][LINK]
The latent heat loss that occurs when the outdoor air humidity ratio < zone air humidity ratio.
Zone Combined Outdoor Air Latent Heat Gain Energy [J][LINK]
The latent heat gain that occurs when the outdoor air humidity ratio >= zone air humidity ratio.
Zone Combined Outdoor Air Total Heat Loss Energy [J][LINK]
The total heat loss that occurs when the sum of Zone Combined Outdoor Air Sensible Heat Gain Energy and Zone Combined Outdoor Air Latent Heat Gain Energy < the sum of Zone Combined Outdoor Air Sensible Heat Loss Energy and Zone Combined Outdoor Air Latent Heat Loss Energy.
Zone Combined Outdoor Air Total Heat Gain Energy [J][LINK]
The total heat gain that occurs when the sum of Zone Combined Outdoor Air Sensible Heat Gain Energy and Zone Combined Outdoor Air Latent Heat Gain Energy >= the sum of Zone Combined Outdoor Air Sensible Heat Loss Energy and Zone Combined Outdoor Air Latent Heat Loss Energy.
Zone Combined Outdoor Air Current Density Volume [m3][LINK]
Zone Combined Outdoor Air Current Density Volume Flow Rate [m3/s][LINK]
These outputs are the total volume and volume flow rate of outdoor air based on the current density of zone air.
Zone Combined Outdoor Air Standard Density Volume [m3][LINK]
Zone Combined Outdoor Air Standard Density Volume Flow Rate [m3/s][LINK]
These outputs are the total volume and volume flow rate of outdoor air based on the standard density of air. Standard density in EnergyPlus corresponds to 20ºC drybulb, dry air, and nominally adjusted for elevation.
Zone Combined Outdoor Air Mass [kg][LINK]
This output is the total mass flow into a particular zone from outdoors.
Zone Combined Outdoor Air Mass Flow Rate [kg/s][LINK]
This output is the total mass flow rate into a particular zone from outdoors.
Zone Combined Outdoor Air Changes per Hour [ach][LINK]
The volume flow rate of the ventilation air in air changes per hour.
Zone Combined Outdoor Air Fan Electric Energy [J][LINK]
The fan electrical consumption for Intake, Exhaust, or Balanced ventilation types (for
ZoneVentilation:DesignFlowRate objects used to calculate a combined zone outdoor airflow).
ZoneMixing[LINK]
In EnergyPlus, the ZoneMixing syntax is intended to allow simplified treatment of air exchange between zones. Note that this statement only affects the energy balance of the “receiving” zone and that this statement will not produce any effect on the “source” zone. Mixing statements can be complementary and include multiple zones, but the balancing of flows between zones is left to the user’s discretion. The use of the Cross Mixing syntax (ref: Cross Mixing) can allow for automatic balancing of flows and energy flow rates between zones but is hindered by the limitation of only a single cross mixing statement per zone. The use of Refrigeration Door Mixing syntax (ref: Refrigeration Door Mixing) automatically balances the flow and energy between two zones and allows multiple mixing statements per zone. More advanced mixing calculations are possible using the EnergyPlus AirflowNetwork model for multi-zone airflow with or without HVAC system operation. Mixing is entered using the following syntax.
Inputs[LINK]
Field: Name[LINK]
The name of the ZoneMixing object.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) receiving the amount of air being exchanged and attaches a particular mixing statement to a thermal zone in the building.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design volume flow rate parameter (see next field). This fraction between 0.0 and 1.0 modifies the design level parameter.
Field: Design Flow Rate Calculation Method[LINK]
This field is a key/choice field that tells which of the next four fields are filled and is descriptive of the method for calculating the design volume flow rate. The key/choices are:
Field: Design Flow Rate[LINK]
This field denotes the full design volume flow rate (m3/s). The previous field should choose “flow/zone” as the choice. The design volume flow rate is the maximum amount of mixing air expected. The design value is modified by the schedule fraction (see Field: Schedule Name) and user specified coefficients (see four “coefficient” fields below).
Field: Flow Rate per Zone Floor Area[LINK]
This factor (m3/s-m2) is used, along with the Zone Area to determine the maximum Design Volume Flow Rate as described in the Design Volume Flow Rate field. The choice from the method field should be “Flow/Area”.
Field: Flow Rate per Person[LINK]
This factor (m3/s-person) is used, along with the nominal (maximum) number of occupants (people) in the Zone to determine the maximum Design Volume Flow Rate as described in the Design Volume Flow Rate field. The choice from the method field should be “Flow/Person”.
Field: Air Changes per Hour[LINK]
Field: Source Zone Name[LINK]
This field is the name of the “source” zone (ref: Zone) that exhausts the amount of air specified by the design level and schedule fields to the zone named in the zone name field.
Field: Delta Temperature[LINK]
This number controls when mixing air from the source zone is sent to the receiving zone. This parameter is a temperature and is expressed in units of Celsius. If this field is positive, the temperature of the zone from which the air is being drawn (source zone) must be “Delta Temperature” warmer than the receiving zone air or else no mixing occurs. If this field is negative, the temperature of the source zone must be “Delta Temperature” cooler than the receiving zone air or else no mixing occurs. If this parameter is zero, mixing occurs regardless of the relative zone temperatures.
Field: Delta Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the temperature difference (in Celsius) between the source zone and receiving zone air dry-bulb temperatures as a function of time. This field is an optional field and has the same functionality as the Delta Temperature field. If the user enters a valid schedule name, the delta temperature values specified in this schedule will supersede the constant value specified in the Delta Temperature field.
Field: Minimum Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the minimum receiving zone temperature (in Celsius) below which mixing is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the minimum zone temperature control is not applied.
Field: Maximum Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the maximum receiving zone temperature (in Celsius) above which mixing is shutoff as a function of time. The maximum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the maximum zone temperature control is not applied.
Field: Minimum Source Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the minimum source zone temperature (in Celsius) below which mixing is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the minimum source zone temperature control is not applied.
Field: Maximum Source Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the maximum source zone temperature (in Celsius) above which mixing is shutoff as a function of time. The maximum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the maximum source zone temperature control is not applied.
Field: Minimum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the minimum outdoor temperature (in Celsius) below which mixing is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the minimum outdoor temperature control is not applied.
Field: Maximum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the maximum outdoor temperature (in Celsius) above which mixing is shutoff as a function of time. The maximum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the maximum outdoor temperature control is not applied.
An IDF Example:
Outputs[LINK]
Zone Mixing Volume [m3][LINK]
The air volume in m3 entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep.
Zone Mixing Current Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep using the density of air evaluated at current zone air conditions.
Zone Mixing Standard Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep using the density of air evaluated at standard conditions.
Zone Mixing Mass [kg][LINK]
The air mass in kg entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep. The air mass is calculated using the air volume flow from each “source” zone and the density of air calculated for the average conditions (temperature and humidity) between the “source” and “receiving” zones.
Zone Mixing Mass Flow Rate [kg/s][LINK]
The air mass flow rate in kg/s entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep.
Zone Mixing Sensible Heat Loss Energy [J][LINK]
Zone Mixing Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat transfer due to the sum of mixing, cross-mixing, and refrigeration-door mixing in the host (receiving) zone is the sum of all the incoming air mass flow rates multiplied by the elapsed time, the specific heat (calculated for the average conditions (temperature and humidity) between the “source” and “receiving” zones) and the temperature differences between the host zone and corresponding source zones. If the heat transfer is negative, the heat transfer is considered to be a zone mixing sensible heat loss. If the heat transfer is positive, the heat transfer is considered to be a zone mixing sensible heat gain.
Zone Mixing Latent Heat Loss Energy [J][LINK]
Zone Mixing Latent Heat Gain Energy [J][LINK]
The latent heat transfer due to the sum of mixing, cross-mixing, and refrigeration-door mixing in the host (receiving) zone is the sum of all the incoming air mass flow rates multiplied by the elapsed time, the heat of vaporization (calculated for the average conditions (temperature and humidity) between the “source” and “receiving” zones) and the humidity ratio differences between the host zone and corresponding source zones. If the heat transfer is negative, the heat transfer is considered to be a zone mixing latent heat loss. If the heat transfer is positive, the heat transfer is considered to be a zone mixing latent heat gain.
Zone Mixing Total Heat Loss Energy [J][LINK]
The total heat loss due to the sum of mixing, cross-mixing, and refrigeration-door mixing that occurs when the sum of Zone Mixing Sensible Heat Gain Energy and Zone Mixing Latent Heat Gain Energy < the sum of Zone Mixing Sensible Heat Loss Energy and Zone Mixing Latent Heat Loss Energy.
Zone Mixing Total Heat Gain Energy [J][LINK]
The total heat gain due to the sum of mixing, cross-mixing, and refrigeration-door mixing that occurs when the sum of Zone Mixing Sensible Heat Gain Energy and Zone Mixing Latent Heat Gain Energy >= the sum of Zone Mixing Sensible Heat Loss Energy and Zone Mixing Latent Heat Loss Energy.
ZoneCrossMixing[LINK]
The ZoneCrossMixing syntax is ideally suited for two zones that exchange an equal amount of air between each other and do not have any air exchange with other zones. As with Mixing (ref: Mixing), this is a simplified view of interzone airflow in EnergyPlus. The main difference between Mixing and Cross Mixing is that Cross Mixing has an energy effect on both the source and the receiving zone, thus maintaining both the air mass and energy balances in the two zones.
Cross Mixing can be entered once, in one of the mixing zones; or twice, once for each zone. The object should be entered once if Delta Temperature > 0.0 and it is desirable to have mixing only when the source zone is warmer than the receiving zone. This might be the case when the warmer zone is below the colder zone and the mixing is buoyancy driven. If the zones are next to each other, separated by an open doorway, it would be more suitable to input a cross mixing object for each zone. Then mixing would occur if the zone temperatures differed by Delta Temperature or greater regardless of which is the warmer zone.
If Delta Temperature = 0.0, Cross Mixing can be entered either once or twice: the effect is exactly the same.
Cross Mixing is entered using the following syntax.
Inputs[LINK]
Field: Name[LINK]
The name of the ZoneCrossMixing object.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) receiving the amount of air being exchanged and attaches a particular cross mixing statement to a thermal zone in the building.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design volume flow rate parameter (see next field). This fraction between 0.0 and 1.0 modifies the design level parameter.
Field: Design Flow Rate Calculation Method[LINK]
This field is a key/choice field that tells which of the next four fields are filled and is descriptive of the method for calculating the design volume flow rate. The key/choices are:
Field: Design Flow Rate[LINK]
This field denotes the full design volume flow rate (m3/s). The previous field should choose “flow/zone” as the choice. The design volume flow rate is the maximum amount of mixing air expected. The design value is modified by the schedule fraction (see Field: Schedule Name) and user specified coefficients (see four “coefficient” fields below).
Field: Flow Rate per Zone Floor Area[LINK]
This factor (m3/s-m2) is used, along with the Zone Area to determine the maximum Design Volume Flow Rate as described in the Design Volume Flow Rate field. The choice from the method field should be “Flow/Area”.
Field: Flow Rate per Person[LINK]
This factor (m3/s-person) is used, along with the nominal (maximum) number of occupants (people) in the Zone to determine the maximum Design Volume Flow Rate as described in the Design Volume Flow Rate field. The choice from the method field should be “Flow/Person”.
Field: Air Changes per Hour[LINK]
Field: Source Zone Name[LINK]
This field is the name of the “source” zone (ref: Zone) that exhausts the amount of air specified by the design level and schedule fields to the zone named in the zone name field. In reality, the “source” and “receiving” zones are interchangeable since the cross-mixed air affects both zones.
Field: Delta Temperature[LINK]
This number controls when mixing air from the source zone is sent to the receiving zone. This parameter is a temperature and is expressed in units of Celsius. If this field is positive, the temperature of the zone from which air is being drawn (“source zone”) must be “Delta Temperature” warmer than the zone air or no mixing occurs. If this field is zero, mixing occurs regardless of the relative air temperatures. Negative values for “Delta Temperature” are not permitted.
Field: Delta Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the temperature difference (in Celsius) between the source zone and receiving zone air dry-bulb temperatures as a function of time. This field is an optional field and has the same functionality as the Delta Temperature field. If the user enters a valid schedule name, the delta temperature values specified in this schedule will supersede the constant value specified in the Delta Temperature field.
Field: Minimum Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the minimum receiving zone temperature (in Celsius) below which cross mixing is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the minimum zone temperature control is not applied.
Field: Maximum Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the maximum receiving zone temperature (in Celsius) above which cross mixing is shutoff as a function of time. The maximum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the maximum zone temperature control is not applied.
Field: Minimum Source Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the minimum source zone temperature (in Celsius) below which cross mixing is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the minimum source zone temperature control is not applied.
Field: Maximum Source Zone Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the maximum source zone temperature (in Celsius) above which cross mixing is shutoff as a function of time. The maximum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the maximum source zone temperature control is not applied.
Field: Minimum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the minimum outdoor temperature (in Celsius) below which cross mixing is shutoff as a function of time. The minimum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the minimum outdoor temperature control is not applied.
Field: Maximum Outdoor Temperature Schedule Name[LINK]
This alpha field contains the name of a schedule (ref. Schedule objects) which contains the maximum outdoor temperature (in Celsius) above which cross mixing is shutoff as a function of time. The maximum temperature value in the schedule can be -100C and the maximum value can be 100C. This field is an optional field. If this field is not entered, the maximum outdoor temperature control is not applied.
An IDF Example:
Outputs[LINK]
Zone Mixing Volume [m3][LINK]
The air volume in m3 entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep.
Zone Mixing Current Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep using the density of air evaluated at current zone air conditions.
Zone Mixing Standard Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep using the density of air evaluated at standard conditions.
Zone Mixing Mass [kg][LINK]
The air mass in kg entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep. The air mass is calculated using the air volume flow from each “source” zone and the density of air calculated for the average conditions (temperature and humidity) between the “source” and “receiving” zones.
Zone Mixing Mass Flow Rate [kg/s][LINK]
The air mass flow rate in kg/s entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep.
Zone Mixing Sensible Heat Loss Energy [J][LINK]
Zone Mixing Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat transfer due to the sum of mixing, cross-mixing, and refrigeration-door mixing in the host (receiving) zone is the sum of all the incoming air mass flow rates multiplied by the elapsed time, the specific heat (calculated for the average conditions (temperature and humidity) between the “source” and “receiving” zones) and the temperature differences between the host zone and corresponding source zones. If the heat transfer is negative, the heat transfer is considered to be a zone mixing sensible heat loss. If the heat transfer is positive, the heat transfer is considered to be a zone mixing sensible heat gain.
Zone Mixing Latent Heat Loss Energy [J][LINK]
Zone Mixing Latent Heat Gain Energy [J][LINK]
The latent heat transfer due to the sum of mixing, cross-mixing, and refrigeration-door mixing in the host (receiving) zone is the sum of all the incoming air mass flow rates multiplied by the elapsed time, the heat of vaporization (calculated for the average conditions (temperature and humidity) between the “source” and “receiving” zones) and the humidity ratio differences between the host zone and corresponding source zones. If the heat transfer is negative, the heat transfer is considered to be a zone mixing latent heat loss. If the heat transfer is positive, the heat transfer is considered to be a zone mixing latent heat gain.
Zone Mixing Total Heat Loss Energy [J][LINK]
The total heat loss due to the sum of mixing, cross-mixing, and refrigeration-door mixing that occurs when the sum of Zone Mixing Sensible Heat Gain Energy and Zone Mixing Latent Heat Gain Energy < the sum of Zone Mixing Sensible Heat Loss Energy and Zone Mixing Latent Heat Loss Energy.
Zone Mixing Total Heat Gain Energy [J][LINK]
The total heat gain due to the sum of mixing, cross-mixing, and refrigeration-door mixing that occurs when the sum of Zone Mixing Sensible Heat Gain Energy and Zone Mixing Latent Heat Gain Energy >= the sum of Zone Mixing Sensible Heat Loss Energy and Zone Mixing Latent Heat Loss Energy.
ZoneRefrigerationDoorMixing[LINK]
The ZoneRefrigerationDoorMixing syntax is ideally suited for two zones, at least one of which is refrigerated, that exchange an equal amount of dry air. They may also have mixed air from other zones, but only one object should be entered for any one pair of zones. As with Mixing (ref: Mixing), this is a simplified view of interzone airflow in EnergyPlus. The ZoneRefrigerationDoorMixing approach shares some features of both Mixing and Cross Mixing. Like Cross Mixing, RefrigerationDoorMixing has an energy effect on both the source and the receiving zone, thus maintaining both the air mass and energy balances in the two zones. Like Mixing, the refrigerated zone can exchange air with multiple zones. Unlike either of the other two mixing objects, the RefrigeratedDoorMixing always calculates the air exchange based on the zone temperature and relative humidity. That is, the user does not specify the air flow rate. The user can moderate the flow through a door-opening schedule.
Unlike, Cross Mixing, Refrigeration Door Mixing can only be entered once for any unique pair of zones. It doesn’t matter which zone is listed first and the zones will automatically switch back and forth between source and receiving zones depending upon which zone is colder.
Refrigeration Door Mixing is entered using the following syntax.
Inputs[LINK]
Field: Name[LINK]
The name of the ZoneRefrigerationDoorMixing object.
Field: Zone 1 Name[LINK]
This field is the name of one of the two zones (ref: Zone) exchanging air and attaches a particular refrigeration door mixing statement to both thermal zones in the building.
Field: Zone 2 Name[LINK]
This field is the name of the other zone (ref: Zone) exchanging air and attaches a particular refrigeration door mixing statement to both thermal zones in the building.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the door opening between the two zones and should contain values between 0.0 and 1.0.
Field: Door Height[LINK]
This field denotes the door opening height (m). The default value is 3 m.
Field: Door Area[LINK]
This field denotes the door opening area (m2). The default value is 9 m2.
Field: Door Protection Type[LINK]
This field is a key/choice field that tells how the door is protected. The impact of this choice is decribed in the Engineering Reference. The key/choices are:
An IDF Example:
Outputs[LINK]
Zone Mixing Volume [m3][LINK]
The air volume in m3 entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep.
Zone Mixing Current Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep using the density of air evaluated at current zone air conditions.
Zone Mixing Standard Density Volumetric Flow Rate [m3/s][LINK]
The air volumetric flow rate in m3/s entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep using the density of air evaluated at standard conditions.
Zone Mixing Mass [kg][LINK]
The air mass in kg entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep. The air mass is calculated using the air volume flow from each “source” zone and the density of air calculated for the average conditions (temperature and humidity) between the “source” and “receiving” zones.
Zone Mixing Mass Flow Rate [kg/s][LINK]
The air mass flow rate in kg/s entering the zone due to the sum of mixing, cross-mixing, and refrigeration-door mixing during the hour or timestep.
Zone Mixing Sensible Heat Loss Energy [J][LINK]
Zone Mixing Sensible Heat Gain Energy [J][LINK]
The sensible (temperature) heat transfer due to the sum of mixing, cross-mixing, and refrigeration-door mixing in the host (receiving) zone is the sum of all the incoming air mass flow rates multiplied by the elapsed time, the specific heat (calculated for the average conditions (temperature and humidity) between the “source” and “receiving” zones) and the temperature differences between the host zone and corresponding source zones. If the heat transfer is negative, the heat transfer is considered to be a zone mixing sensible heat loss. If the heat transfer is positive, the heat transfer is considered to be a zone mixing sensible heat gain.
Zone Mixing Latent Heat Loss Energy [J][LINK]
Zone Mixing Latent Heat Gain Energy [J][LINK]
The latent heat transfer due to the sum of mixing, cross-mixing, and refrigeration-door mixing in the host (receiving) zone is the sum of all the incoming air mass flow rates multiplied by the elapsed time, the heat of vaporization (calculated for the average conditions (temperature and humidity) between the “source” and “receiving” zones) and the humidity ratio differences between the host zone and corresponding source zones. If the heat transfer is negative, the heat transfer is considered to be a zone mixing latent heat loss. If the heat transfer is positive, the heat transfer is considered to be a zone mixing latent heat gain.
Zone Mixing Total Heat Loss Energy [J][LINK]
The total heat loss due to the sum of mixing, cross-mixing, and refrigeration-door mixing that occurs when the sum of Zone Mixing Sensible Heat Gain Energy and Zone Mixing Latent Heat Gain Energy < the sum of Zone Mixing Sensible Heat Loss Energy and Zone Mixing Latent Heat Loss Energy.
Zone Mixing Total Heat Gain Energy [J][LINK]
ZoneEarthtube (Earth Tube)[LINK]
An earth tube is a long, underground metal or plastic pipe through which air is drawn. During cooling season, as air travels through the pipe, it gives up some of its heat to the surrounding soil and enters the room as cooler air. Similarly, during heating season, as air travels through the pipe, it receives some of its heat from the soil and enters the room as warmer air. Simple earth tubes in EnergyPlus can be controlled by a schedule and through the specification of minimum, maximum, and delta temperatures as described below. As with infiltration and ventilation, the actual flow rate of air through the earth tube can be modified by the temperature difference between the inside and outside environment and the wind speed. The basic equation used to calculate air flow rate of earth tube in EnergyPlus is:
\[EarthTubeFlowRate = \left( {{E_{design}}} \right)\left( {{F_{schedule}}} \right)\left[ {A + B\left| {{T_{zone}} - {T_{odb}}} \right| + C\left( {WindSpeed} \right) + D\left( {WindSpee{d^2}} \right)} \right]\]
For the simulation of the earth tube, a weather data file is required and, therefore, the earth tube cannot run without weather data file. The required input fields to simulate the earth tube include the average soil surface temperature, the amplitude of soil surface temperature, and the phase constant of soil surface temperature. These fields should be calculated in advance by using a separate stand-alone program (CalcSoilSurfTemp) and should be input into earth tube.
CalcSoilSurfTemp - Auxiliary Programs Document[LINK]
The CalcSoilSurfTemp program is simple and requires only two input fields : soil condition and soil surface condition in addition to a valid weather file. For soil condition, the user should select the number corresponding to the actual condition of the soil surrounding the earth tube from the four following options: 1. HEAVY AND SATURATED, 2. HEAVY AND DAMP, 3. HEAVY AND DRY and 4. LIGHT AND DRY. This determines the thermal diffusivity and thermal conductivity of the surrounding soil. For soil surface conditions, the user should select the number corresponding to the actual condition of the ground surface above the earth tube from the eight following options: 1. BARE AND WET, 2. BARE AND MOIST, 3. BARE AND ARID, 4. BARE AND DRY, 5. COVERED AND WET, 6. COVERED AND MOIST, 7. COVERED AND ARID and 8. COVERED AND DRY. This determines the absorption coefficient and the fraction of evaporation rate of the ground surface.
From this information and an analysis of the weather for the location selected, the CalcSoilSurfTemp program (ref. Auxiliary Programs document) calculates the three parameters listed above. The user must then add these parameters as input into EnergyPlus. The full input description of an earth tube in EnergyPlus is given below.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches a particular earth tube statement to a thermal zone in the building.
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design volume flow rate parameter (see next field). This fraction between 0.0 and 1.0 is noted as Fschedule in the above equation.
Field: Design Flow Rate[LINK]
This number (noted as Edesign in the above equation) is the maximum amount of air mass flow rate of the earth tube expected at design conditions. The flow rate is expressed in units of m3/s. The design value is modified by the schedule fraction (see previous field) and user specified coefficients (see last four fields).
Field: Minimum Zone Temperature when Cooling[LINK]
This is the indoor temperature (in Celsius) below which the earth tube is shut off. This lower temperature limit is intended to avoid overcooling a space and thus result in a heating load. For example, if the user specifies a minimum temperature of 20C, earth tube is assumed to be available if the zone air temperature is above 20C. If the zone air temperature drops below 20C, then earth tube is automatically turned off.
Field: Maximum Zone Temperature when Heating[LINK]
This is the indoor temperature (in Celsius) above which the earth tube is shut off. This higher temperature limit is intended to avoid overheating a space and thus result in a cooling load. For example, if the user specifies a maximum temperature of 20C, earth tube is assumed to be available if the zone air temperature is below 20C. If the zone air temperature rises above 20C, then earth tube is automatically turned off.
Field: Delta Temperature[LINK]
This is the temperature difference (in Celsius) between the indoor and outdoor air dry-bulb temperatures below which the earth tube is shut off. This is to allow the earth tube to be stopped either if the temperature outside is too warm and could potentially heat the space or if the temperature outside is too cold and could potentially cool the space. For example, if the user specifies a delta temperature of 2C, earth tube is assumed to be available if the temperature difference between indoor and outdoor temperature is at least 2C. If the outside air dry-bulb temperature is less than 2C cooler or warmer than the indoor dry-bulb temperature, then the earth tube is automatically turned off.
Field: Earthtube Type[LINK]
This alpha character string defines the type of earth tube as one of the following options: Natural, Exhaust, or Intake. A natural earth tube is assumed to be air movement/exchange that will not consume any fan energy or is the result of natural air flow through the tube and into the building. Values for fan pressure and efficiency for a natural flow earth tube are ignored. For either EXHAUST or Intake, values for fan pressure and efficiency define the fan electric consumption. For Natural and Exhaustearth tubes, the conditions of the air entering the space are assumed to be equivalent to the air which is cooled or heated by passing along the pipe. For Intake earth tubes, an appropriate amount of fan heat is added to the air stream.
Field: Fan Pressure Rise[LINK]
This is the pressure rise experienced across the fan in Pascals (N/m2). This is a function of the fan and plays a role in determining the amount of energy consumed by the fan.
Field: Fan Total Efficiency[LINK]
This is the total fan efficiency (a decimal number between 0.0 and 1.0). This is a function of the fan and plays a role in determining the amount of energy consumed by the fan.
Field: Pipe Radius[LINK]
This is the radius of the earth tube/pipe (in meters). This plays a role in determining the amount of heat transferred from the surrounding soil to the air passing along the pipe. If the pipe has non-circular cross section, user can use the concept of hydraulic diameter as follows.
However, since this field requires the pipe radius, hydraulic diameter should be divided by two.
Field: Pipe Thickness[LINK]
This is the thickness of the pipe wall (in meters). This plays a role in determining the amount of heat transferred from the surrounding soil to the air passing along the pipe.
Field: Pipe Length[LINK]
This is the total length of the pipe (in meters). This plays a role in determining the amount of heat transferred from the surrounding soil to the air passing along the pipe. As the length of the pipe becomes longer, the amount of the heat transfer becomes larger.
Field: Pipe Thermal Conductivity[LINK]
This is the thermal conductivity of the pipe (in W/mC). This plays a role in determining the amount of heat transferred from the surrounding soil to the air passing along the pipe.
Field: Pipe Depth Under Ground Surface[LINK]
This is the depth of the pipe under the ground surface (in meters). This plays a role in determining the temperature of the soil surrounding the pipe.
Field: Soil Condition[LINK]
This alpha character string defines the actual condition of the soil surrounding the earth tube and can be one of any of the following options: HeavyAndSaturated, HeavyAndDamp, HeavyAndDry or LightAndDry. This determines the thermal diffusivity and thermal conductivity of the surrounding soil, which play a role in determining the amount of heat transferred from the surrounding soil to the air passing along the pipe.
Field: Average Soil Surface Temperature[LINK]
This is the annual average soil surface temperature straight above the earth tube, which plays a role in determining the temperature of the soil surrounding the pipe. This field should be calculated in advance using the separate CalcSoilSurfTemp program.
Field: Amplitude of Soil Surface Temperature[LINK]
This is the amplitude of soil surface temperature above the earth tube, which plays a role in determining the temperature of the soil surrounding the pipe. This is the difference between the maximum and minimum soil surface temperature for the whole year divided by two. This field should be calculated in advance using the separate CalcSoilSurfTemp program.
Field: Phase Constant of Soil Surface Temperature[LINK]
This is the phase constant of the soil surface temperature straight above the earth tube, which play a role in determining the temperature of the soil surrounding the pipe at particular time. This is the time elapsed from the beginning of the year until the soil surface temperature reaches the minimum value of the year. This field should be calculated in advance using the separate CalcSoilSurfTemp program.
Field: Constant Term Flow Coefficient[LINK]
This number is the “A” parameter in the above earth tube equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter, however, is a constant under all conditions and is not modified by any environmental effect. As a result, it is dimensionless.
Field: Temperature Term Flow Coefficient[LINK]
This number is the “B” parameter in the above earth tube equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter is modified by the temperature difference between the outdoor and indoor air dry-bulb temperatures. The units for this parameter are inverse Celsius.
Field: Velocity Term Flow Coefficient[LINK]
This number is the “C” parameter in the above earth tube equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter is modified by the speed of wind being experienced outside the building. The units for this parameter are s/m.
Field: Velocity Squared Term Flow Coefficient[LINK]
This number is the “D” parameter in the above earth tube equation. It is part of the user specified modifying parameters that are a function of environmental factors. This parameter is modified by square of the speed of wind being experienced outside the building. The units for this parameter are s2/m2.
An IDF example:
ZoneEarthTube Outputs[LINK]
Current Earth Tube output variables:
Earth Tube Zone Sensible Cooling Energy [J][LINK]
Earth Tube Zone Sensible Cooling Rate [W][LINK]
These are the energy and rate associated with the zone cooling provided by the air from the earth tube. This occurs when the earth tube outlet air temperature is less than zone air temperature.
Earth Tube Zone Sensible Heating Energy [J][LINK]
Earth Tube Zone Sensible Heating Rate [W][LINK]
These are the energy and rate associated with the zone heating provided by the air from the earth tube. This occurs when the earth tube outlet air temperature is greater than the zone air temperature.
Earth Tube Air Flow Volume [m3][LINK]
The volume flow of air through the earth tube.
Earth Tube Air Current Density Volumetric Flow Rate [m3/s][LINK]
The volume flow rate of air through the earth tube evaluating density at current zone conditions.
Earth Tube Air Standard Density Volumetric Flow Rate [m3/s][LINK]
The volume flow rate of air through the earth tube evaluating density at standard conditions.
Earth Tube Air Flow Mass [kg][LINK]
The mass flow of air through the earth tube.
Earth Tube Air Mass Flow Rate [kg/s][LINK]
The mass flow rate of air through the earth tube.
Earth Tube Fan Electric Energy [J][LINK]
Earth Tube Fan Electric Power [W][LINK]
These are the fan electricity consumption and power for intake or exhaust earth tube types.
Earth Tube Zone Inlet Air Temperature [C][LINK]
This is the temperature of the air entering the zone after passing through the earth tube [C]. This temperature includes the cooling or heating of outdoor air as it passes along the pipe. When intake fan assist is used, then the additional heat due to the fan is included in the inlet air temperature.
Earth Tube Ground Interface Temperature [C][LINK]
This is the average temperature of the ground along the outer surface of the earth tube [C].
Earth Tube Outdoor Air Heat Transfer Rate [W][LINK]
This is the rate of heat transfer from the earth tube to the outdoor air [W]. Positive values indicate the rate at which outdoor air is preheated; negative values indicate the rate of precooling.
ZoneCoolTower:Shower[LINK]
A cooltower (which is sometimes referred to as a wind tower or a shower cooling tower) is a component that is intended to model a passive downdraught evaporative cooling (PDEC) that is designed to capture the wind at the top of a tower and cool the outside air using water evaporation before delivering it to a space. The air flow in these systems is natural as the evaporation process increases the density of the air causing it to fall through the tower and into the space without the aid of a fan. A cooltower typically consists of a water spray or an evaporative pad, a shaft, and a water tank or reservoir. Wind catchers to improve the wind-driven performance at the top of the tower are optional. Water is pumped over an evaporative device by water pump which is the only component consumed power for this system. This water cools and humidifies incoming air and then the cool, dense air naturally falls down through shaft and leaves through large openings at the bottom of cooltowers.
The shower cooling tower can be controlled by a schedule and the specification of maximum water flow rate and volume flow rate as well as minimum indoor temperature. The actual flow rate of water and air can be controlled as users specify the fractions of water loss and flow schedule. The required input fields include effective tower height and exit area to obtain the temperature and flow rate of the air exiting the tower. A schedule and rated power for the water pump are also required to determine the power consumed. The component typically has a stand alone water system that is not added to the water consumption from mains. However, users are required to specify the water source through an optional field, the name of water supply storage tank, in case any water comes from a water main. The model is described more fully in the Engineering Reference document.
This model requires weather information obtained from either design day or weather file specifications. The control is accomplished by either specifying the water flow rate or obtaining the velocity at the outlet with inputs and weather conditions when the water flow rate is unknown. As with infiltration, ventilation, and earth tubes, the component is treated in a similar fashion to “natural ventilation” in EnergyPlus.
Inputs[LINK]
Field: Name[LINK]
This field is a unique user assigned name for each cooltower. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
This field is the name of the schedule that denotes whether the cooltower can run during a given time period. A schedule value greater than 0 (usually 1 is used) indicates that the cooltower is available and can be on during the time period. A value less than or equal to 0 (usually 0 is used) denotes that the cooltower is not available and must be off for the time period. If this field is blank, the schedule has values of 1 for all time periods.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and attaches a particular cooltower statement to a thermal zone in the building.
Field: Water Supply Storage Tank Name[LINK]
This field is optional. It is used to describe where the cooltower obtains water used for evaporative cooling. If blank or omitted, then the cooltower will obtain water directly from local water main. If the name of a Water Storage Tank object is used here, then the cooltower will obtain its water from that tank. If a tank is specified, the cooltower will attempt to obtain all the water it uses from the tank. However, if the tank cannot provide all the water the cooltower needs, then the cooltower will still operate and obtain the rest of the water it needs from the mains (referred to as ‘Starved’ water).
Field: Flow Control Type[LINK]
This field specifies how the user wishes to control the cooltower. The air flow from the cooltower may be controlled by either the water flow rate along with the water pump schedule or naturally driven by wind flow. The user must select from the following options: WaterFlowSchedule and WindDrivenFlow. If the user either wishes to control the water flow rate or has information about the water flow rate, WaterFlowSchedule must be selected. WindDrivenFlow for cooltower flow control must be selected when the water flow rate is unknown and the user wishes to have the flow rate of both air and water controlled by the external weather conditions (wind speed). If the user does not select a control type, WindDrivenFlow is assumed as a flow control type.
Field: Pump Flow Rate Schedule Name[LINK]
This field modifies the maximum flow rate of water through the cooltower in m3/sec. This input is “optional.” If the user does not enter a schedule, the flow rate through the cooltower is assumed to be constant during all hours that it is operating based on the value entered in the previous input field. Note that the values for this schedule must be between zero and one.
Field: Maximum Water Flow Rate[LINK]
This field is the maximum water flow rate distributed to the tower in m3/s. This limit is intended to avoid over estimation of water flow rate, which leads higher air flow rate and exit temperature of the air.
Field: Effective Tower Height[LINK]
This field is the effective tower height for evaporative cooling, from the water spray to the top of the exit in m.
Field: Airflow Outlet Area[LINK]
This field is the area at the exit of the tower in m2. This field is used to determine the air flow rate leaving the tower with the velocity of the air flow.
Field: Maximum Air Flow Rate[LINK]
This field is the maximum volumetric flow rate of the air leaving the tower in m3/s. This airflow maximum allows the cooltower performance to be limited if the outside wind speed and the tower height are relatively high and thus result in high airflow supplied to the space.
Field: Minimum Indoor Temperature[LINK]
This field is the minimum indoor temperature in Celsius below which cooltower is shutoff. This lower temperature limit is intended to avoid overcooling a space and thus result in a heating load. For example, if the user specifies a minimum temperature of 20°C, cooltower is assumed to be available if the zone air temperature is above 20°C. If the zone air temperature drops below 20°C, then cooltower is automatically turned off.
Field: Fraction of Water Loss[LINK]
This field specifies the fraction of the loss of water during either operation or transient operation. If the user does not enter a fraction, no loss of water is assumed and the cooltower water consumption includes only evaporation. Note that the fraction must be between zero and one.
Field: Fraction of Flow Schedule[LINK]
This field specifies the fraction of the airflow that actually goes to the outside. The user who wishes to control the actual flow to the inside of the building must specify the value of the fraction. If the user does not enter a fraction, the calculated flow rate is the “zone cooltower volume flow rate.” Note that the fraction must be between zero and one.
Field: Rated Power Consumption[LINK]
This field is the pump’s rated power consumption in Watts.
Below is an example input for a cooltower.
Outputs[LINK]
Zone Cooltower Sensible Heat Loss Energy [J][LINK]
Zone Cooltower Sensible Heat Loss Rate [W][LINK]
The sensible heat loss that occurs when the temperature at the exit of the cooltower is less than that of the zone.
Zone Cooltower Latent Heat Loss Energy [J][LINK]
Zone Cooltower Latent Heat Loss Rate [W][LINK]
The latent heat loss that occurs when the humidity ratio at the exit of the cooltower is greater than that of the zone.
Zone Cooltower Air Current Density Volumetric Flow Rate [m3/s][LINK]
The volumetric flow rate of the air leaving the cooltower evaluating density at current zone conditions.
Zone Cooltower Air Standard Density Volumetric Flow Rate [m3/s][LINK]
The volumetric flow rate of the air leaving the cooltower evaluating density at standard conditions.
Zone Cooltower Air Volume [m3][LINK]
The sum of actual volumetric flow of the air leaving cooltower
Zone Cooltower Air Mass Flow Rate [kg/s][LINK]
The mass flow rate of the air leaving the cooltower
Zone Cooltower Air Mass [kg][LINK]
The sum of actual mass flow of the air leaving the cooltower
Zone Cooltower Air Inlet Temperature [C][LINK]
The dry-bulb temperature of the outdoor air the inlet of the cooltower
Zone Cooltower Air Inlet Humidity Ratio [kgWater/kgDryAir][LINK]
The humidity ratio of the outdoorair at the inlet of the cooltower
Zone Cooltower Air Outlet Temperature [C][LINK]
The temperature at the exit of the cooltower.
Zone Cooltower Air Outlet Humidity Ratio [kgWater/kgDryAir][LINK]
The humidity ratio of the air at the exit of the cooltower.
Zone Cooltower Water Volume [m3][LINK]
The water consumption includes not only the direct thermodynamics of water evaporation but also other sources of consumption such as drift or concentration blow down specified by users throughout all processes during the operation.
Zone Cooltower Mains Water Volume [m3][LINK]
This is the water consumed by the cooltower that actually be met by the mains water. This output variable appears only when the water comes from mains.
Zone Cooltower Storage Tank Water Volume [m3][LINK]
This is the water consumed by the cooltower that actually be met by the water storage tank. If any amount of the water is starved from mains, this water consumption is the difference between the Zone Cooltower Water Volume and the following output. This output variable appears only when the water comes from storage tank waters.
Zone Cooltower Starved Mains Water Volume [m3][LINK]
This is the source (mains) of water consumed by the cooltower that could not actually be met by the storage tank. This output variable appears only when the water comes from storage tank waters.
Zone Cooltower Pump Electric Power [W][LINK]
The power consumed by the recirculating pump in Watts.
Zone Cooltower Pump Electric Energy [J][LINK]
The energy consumed by the recirculating pump in Joules.
ZoneThermalChimney (Thermal Chimney)[LINK]
A thermal chimney is a vertical shaft utilizing solar radiation to enhance the natural ventilation in buildings. It consists of a absorber wall, air gap and glass cover with high solar transmissivity. For the high solar absorption, it is usually south facing.
The key output parameter in the thermal chimney model is the enhanced amount of natural ventilation rate caused by the presence of a thermal chimney. In order to determine the enhanced ventilation, the discharge air temperature from a thermal chimney should be calculated, which, in turn, should be computed based on the information on the absorber wall temperature, glass cover temperature and the vertical air temperature distribution within the thermal chimney. Among them, energy balances for the absorber wall and the glass cover are carried out using the existing algorithm currently available in EnergyPlus, which has the similar approach to the Trombe wall. As stated in the Trombe wall object as well, this approach allows the flexibility for users to specify the various wall parameters and to explore unusual configurations. On the other hand, the vertical air temperature distribution and the resultant discharge air temperature of the thermal chimney are computed using the separate thermal chimney algorithm described in the Engineering Reference document.
Similar to the Trombe wall model, a zone is coupled to the desired surface via an interzone partition. To simulate the thermal chimney, the Solar Distribution field in the Building object should be set to FullInteriorAndExterior so that the majority of the solar flux is directed on the absorber wall. For a normal sized thermal chimney zone, the user can set the Zone Inside Convection Algorithm to “Detailed”, which takes into account natural convection effects intended for a normal zone. For a narrow cavity zone having high aspect ratios, there is no built-in algorithm for calculating the correct convection coefficients on the inside of thermal chimney zone walls. One option is to use the “Detailed” convection algorithm similar to the Trombe wall model. However, some error may be incurred when used with a narrow zone. Another option is to use the SurfaceProperty:ConvectionCoefficients object to schedule coefficients that have been determined beforehand by the user. In addition, the wall construction of the adjoining zone must be the mirror image of the wall construction in the thermal chimney zone.
The full input description of a thermal chimney in EnergyPlus is given below.
Field: Name[LINK]
This field is a unique user assigned name for an instance of the thermal chimney system.
Field: Zone Name[LINK]
This field is the name of the thermal chimney zone (ref: Zone). Since the thermal chimney is not only a system component but also a zone itself, this field is also necessary. It should be differentiated from the Zone name field described later.
Field: Availability Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that denotes whether the thermal chimney can operate during a given time period. A schedule value greater than 0 (usually 1 is used) indicates that the system is available and can be on during the time period. A value less than or equal to 0 (usually 0 is used) denotes that the system is not available and must be off for the time period. If this field is blank, the schedule has values of 1 for all time periods.
Field: Width of the Absorber Wall[LINK]
This number is the width of the absorber wall in the thermal chimney. The width is expressed in units of m. Even though this value is specified in Surface objects as well, this value is used to compute the discharge air temperature and the enhanced ventilation rate caused by the thermal chimney.
Field: Cross Sectional Area of Air Channel Outlet[LINK]
This number is the cross sectional area of air channel outlet. The area is expressed in units of m2. The enhanced air flow rate by the thermal chimney is dependent on cross sectional areas of air channel inlet and outlet. Cross sectional areas of air channel inlet will be described later in conjunction with the distance from the top of thermal chimney to each inlet and relative ratios of air flow rates passing through each inlet.
Field: Discharge Coefficient[LINK]
This dimensionless number is the discharge coefficient of the thermal chimney. The ventilation rate enhanced by the thermal chimney is also dependent on the discharge coefficient.
Field: Zone <#> Name[LINK]
This field is the name of the zone (ref: Zone) to which the thermal chimney is attached. It is used in conjunction with the next three fields. Note that up to 20 sets of zone name, distance from the top of the thermal chimney to each inlet, relative ratios of air flow rates passing through each zone and cross sectional areas of each air channel inlet may be entered for a single thermal chimney if multiple zones share the common thermal chimney.
Field: Distance from Top of Thermal Chimney to Inlet <#>[LINK]
This field is the distance from the top of the thermal chimney to each inlet corresponding to each zone. It is used in conjunction with the zone name, relative ratios of air flow rates passing through each zone and cross sectional areas of each air channel inlet. The distance is expressed in units of m. The air flow rate enhanced by the thermal chimney is dependent on the distance between the thermal chimney outlet and inlet.
Field: Relative Ratios of Air Flow Rates Passing through Zone <#>[LINK]
This dimensionless number is the relative ratio of air flow rates enhanced by the thermal chimney passing through each zone. The total air flow rate enhanced by the thermal chimney is distributed to each zone based on this number if multiple zones share the common thermal chimney. It is used in conjunction with the zone name, the distance from the top of the thermal chimney to each inlet and cross sectional areas of each air channel inlet. Note that the sum of all ratios must be equal to 1.0.
Field: Cross Sectional Areas of Air Channel Inlet <#>[LINK]
This field is the cross sectional areas of each air channel inlet corresponding to each zone. It is used in conjunction with the zone name, the distance from the top of the thermal chimney to each inlet and relative ratios of air flow rates passing through each zone. The area is expressed in units of m2. The air flow rate enhanced by the thermal chimney is dependent on cross sectional areas of air channel inlet and outlet.
An IDF example:
ZoneThermalChimney Outputs[LINK]
Current ThermalChimney output variables:
Zone Thermal Chimney Heat Loss Energy [J][LINK]
The sensible (temperature) heat loss of each zone that occurs when the thermal chimney cools the zone air.
Zone Thermal Chimney Heat Gain Energy [J][LINK]
The sensible (temperature) heat gain of each zone that occurs when the thermal chimney heats the zone air.
Zone Thermal Chimney Volume [m3][LINK]
The air volumetric flow of each zone enhanced by the thermal chimney.
Zone Thermal Chimney Mass [kg][LINK]
The air mass flow of each zone enhanced by the thermal chimney.
Zone Thermal Chimney Current Density Volumetric Flow Rate [m3/s][LINK]
The total air volumetric flow rate caused by the thermal chimney evaluating density at the current zone conditions.
Zone Thermal Chimney Standard Density Volumetric Flow Rate [m3/s][LINK]
The total air volumetric flow rate caused by the thermal chimney evaluating density at standard conditions.
Zone Thermal Chimney Mass Flow Rate [kg/s][LINK]
The total air mass flow rate caused by the thermal chimney.
Zone Thermal Chimney Outlet Temperature [C][LINK]
The temperature of the air which is discharged from the thermal chimney through the outlet.
ZoneAirMassFlowConservation[LINK]
This global object allows users to trigger the zone air mass flow conservation calculation when desired. This object has two input fields; the first choice input field allows the user whether to enforce or not to enforce the zone air mass flow conservation; and the second input field allows the user to specify how infiltration object mass flow rate is calculated for zone air mass flow balance calculation. The first input field of this object has two choice KEYs: “Yes” and “No”. If this input is specified as “Yes”, then energy plus attempts to enforce the zone mass conservation, or else if it is specified as “No”, then EnergyPlus calculation defaults to zone air flow balance calculation that does not include zone mixing objects and that assumes self-balanced simple flow objects procedure, which may not necessarily enforce zone air mass flow conservation unless the user has specified a balanced flow to begin with. The zone air mass flow conservation primarily accounts for the zonemixing objects air flow in the zone air flow mass balance calculation. In additional to the zonemixing object flow, the procedure accounts for zone exhaust fan flows by providing additional infiltration air flows when required in order to balance the zone air mass flow. Hence, zonemixing object must to be defined to trigger zone air mass flow conservation calculation, whereas infiltration object is required only for zones which are used as a source zone of the zone mixing object. Zone air mass flow balance calculation is enforced both for the receiving and source zones of every mixing object defined. The zone air mass flow conservation calculation uses two steps procedure.
First, the ZoneMixing object mass flow rate is adjusted or modified in order to balance zone air mass flow while assuming the zone infiltration object air mass flow self-balanced. This step will always results in balanced zone air mass for receiving zones of ZoneMixing object but it may not necessarily result in a balanced air mass flow for source zones. Infiltration objects air mass flow rate defined for receiving zones are always calculated based on user inputs and assumed to be self-balanced. The infiltration mass flow rate of zones that serve only as a source zone may require adjusting base infiltration flow, which is calculated based on user inputs in the infiltration objects, in order to balance the zone air mass flow, i.e., the second calculation step replenishes the source zones with additional infiltration air mass flow when required. This second step is required in zones which serve as a source zone for zone mixing objects and when the zone mixing source mass flow rate exceeds the supply air mass flow rate. There are two calculation procedures that users can choose from on how the infiltration flow rate is calculated for source zones that need infiltration object mass flow in order to balance the zone air mass flow. The second optional input field “Source Zone Infiltration Treatment” provides two Key choice inputs: “AddInfiltrationFlow” and “AdjustInfiltrationFlow”.
AddInfiltrationFlow: Energyplus adds infiltration air mass flow rate on top of the base infiltration flow, which is calculated using the infiltration object user inputs, in order to balance the zone air mass flow. This additional infiltration air mass flow is not self-balanced, i.e., it is always assumed incoming flow. If no infiltration air is required in order to be balance the zone air mass flow, then the additional infiltration air mass flow rate is set to zero. The base infiltration flow calculated using the infiltration object user inputs is always assumed to be self-balanced.
AdjustInfiltrationFlow: Energyplus may adjust the base flow calculated using the infiltration object user inputs if it is required in order to balance the zone air mass flow. If it is not required to adjust the base infiltration air flow, then the base infiltration air mass flow, which is calculated from user input of the infiltration object, is retained and assumed self-balanced. The report variable “Zone Infiltration Air Mass Flow Balance Status” indicates whether the infiltration object air mass flow is adjusted or not. If the value of this report variable is 0, then the zone infiltration object mass flow rate is not included in the zone mass flow balance hence the infiltration air flow rate calculated based on the user specified inputs is manintained as is and assumed self-balanced for current timestep. If the value of this report variable is 1, then the zone infiltration object mass flow rate is included in the zone mass flow balance, hence the user specified infiltration rate is modified and it is considered as incoming flow to the zone, i.e., self-balanced assumption is not valid for current time step.
This object is optional, only required in the input data file if the user wishes to enforce the zone air mass flow balance calculation that includes zonemixing and infiltration objects.
Inputs[LINK]
Field: Adjust Zone Mixing For Zone Air Mass Flow Balance[LINK]
It has two choice KEYs: “Yes” and “No”. If this input is specified as “Yes”, then Energyplus attempts to enforce the zone mass conservation, or else if it is specified as “No”, then EnergyPlus calculation defaults to the existing procedure, which may not necessarily enforce zone mass conservation unless the user specified a balanced flow to begin with. The default input is “No”. Note that “No” input may also results in balanced flow depending on the system specified. If this input field is specified as “No”, then the next input field it not used.
Field: Source Zone Infiltration Treatment[LINK]
It has two choice KEYs: “AddInfiltrationFlow” and “AdjustInfiltrationFlow”. If this input is specified as “AddInfiltrationFlow”, then Energyplus adds infiltration air mass flow on top of the base infiltration flow calculated using the infiltration object user inputs in order to balance the zone air mass flow. The additional infiltration air mass flow is not self-balanced. If this input is specified as “AdjustInfiltrationFlow”, then Energyplus may adjust the base flow calculated using the infiltration object user inputs if it is required inorder to balance the zone air mass flow. If it not required to adjust the base infiltration flow calculated using the user specified infiltration object inputs, then the base infiltration air mass flow is assumed self-balanced.
And, a default IDF example is shown below:
Outputs[LINK]
Current ZoneAirMassFlowConservation output variables:
Zone Supply Air Mass Flow Rate [kg/s][LINK]
This output variable represents the total supply air mass flow rate of a zone. The value is determined by summing the supply air mass flow rates contributions from all supply air inlet nodes of a zone.
Zone Exhaust Air Mass Flow Rate [kg/s][LINK]
This output variable represents the total exhaust air mass flow rate of a zone. The value is determined by summing the exhaust air mass flow rates contributions from all exhaust air nodes of a zone.
Zone Return Air Mass Flow Rate [kg/s][LINK]
This output variable represents the total return air mass flow rate of a zone. The value is determined by summing the return air mass flow rates contributions from return air nodes of a zone.
Zone Mixing Receiving Air Mass Flow Rate [kg/s][LINK]
This output variable represents the total zone mixing air mass flow rate of a receiving zone from one or more mixing objects. The value is determined by summing the air mass flow contributions from all zone mixing objects connected to a single receiving zone.
Zone Mixing Source Air Mass Flow Rate [kg/s][LINK]
This output variable represents the total zone mixing source air mass flow rate of a source zone feeding one or more mixing objects. The value is determined by summing the air mass flow contributions from all zone mixing objects connected to a single source zone.
Zone Infiltration Air Mass Flow Balance Status [][LINK]
This output variable indicates the status of the infiltration object mass flow rate use for balancing the zone mass flow at each time step. It has values of either 0 or 1. If the value of this report variable is 0 then the zone infiltration object mass flow rate is not used in the zone mass conservation calculation, hence the infiltration rate calculated based on the user specified inputs is manintained and the infiltration rate is assumed as self-balanced for current timestep. If the value is 1 then the zone infiltration object mass flow rate is included in the zone air mass flow balance calculation, hence the user specified infiltration rate is modified and it is considered as incoming flow to the zone, i.e., self-balanced assumption is not valid for this zone and current time step.
Zone Mass Balance Infiltration Air Mass Flow Rate [kg/s][LINK]
This output variable represents the zone infiltration air mass flow rate in kg/s. This output variable is reported only for source zones and when the zone air mass flow balance flag is set to “Yes” and its value depends on the “Source Zone Infiltration Treatment” method specified. When the infiltration treatment method selected is “AddInfiltrationFlow” this report variable represents additional infiltration air mass flow rate added on top of the base infiltration air flow calculated using the user inputs inroder to balance the zone air mass flow. In this case, the base infiltration air mass flow calculated using the user specified input is assumed self-balanced. When the infiltration treatment method selected is “AdjustInfiltrationFlow” this report variable represents the base infiltration air mass flow calculated using the user inputs and can be adjuted as needed in roder to balance the zone air mass flow. If the value of the output variable “Zone Infiltration Air Mass Flow Balance Status” is 0, then the infiltration air mass flow rate calculated based on the user specified inputs is manintained and the infiltration rate is assumed as self-balanced for current timestep, or else if Zone Infiltration Air Mass Flow Balance Status” is 1, then user specified infiltration rate is adjusted and it is considered as incoming flow to the zone, i.e., self-balanced assumption is not valid for this zone and current time step.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.