This model simulates a variable-refrigerant-flow (or
variable-refrigerant-volume) air-conditioning system. This
system type models direct-expansion cooling and/or heating
coils configured in a zone terminal unit. For this system
type, the zone terminal units are “connected” to a zone via
the zone inlet and exhaust nodes. The zone terminal units are
identified in a ZoneTerminalUnitList
object. And finally, the name of the ZoneTerminalUnitList
object is entered as an input to the AirConditioner:VariableRefrigerantFlow
object. The Energyplus connection methodology is shown as
dashed and greyed arrows in the figure below according to the
following rules:
The zone inlet and zone exhaust node names are defined in a
ZoneHVAC:EquipmentConnections
object (bottom of figure).
A ZoneHVAC:TerminalUnit:VariableRefrigerantFlow
object will identify these zone exhaust and zone inlet node
names as the terminal unit’s air inlet and air outlet nodes,
respectively.
All zone terminal units that are connected to the same
AirConditioner: VariableRefrigerantFlow object are listed in a
ZoneTerminalUnitList
object.
The name of the ZoneTerminalUnitList
object is an input to the AirConditioner:
VariableRefrigerantFlow object.
The AirCondtiioner:VariableRefrigerantFlow object is not
listed in an AirloopHVAC object and, therefore, can only be
simulated if the terminal units are connected to the
AirCondtiioner:VariableRefrigerantFlow object using the ZoneTerminalUnitList.
Secondary ZoneHVAC equipment objects may be used in the
same zones as the terminal units for other purposes (e.g.,
code compliance)
The following schematic demonstrates these connection
rules.
Variable Refrigerant Flow
Schematic
Energyplus object type and object name, and node name
relationships are also shown in the following figure to aid in
the assembly of this HVAC system type.
This alpha field defines a unique user-assigned name for an
instance of a variable refrigerant flow heat pump. Any
reference to this heat pump will use this name. Since this
object is not listed in an AirloopHVAC object, the most likely
use of this name would be for reporting purposes.
This alpha field defines the name of the schedule (ref:
Schedule) that denotes whether the heat pump operates during a
given time period. A schedule value equal to 0 denotes that
the heat pump must be off for that time period. A value other
than 0 denotes that the heat pump is available to operate
during that time period. This schedule may be used to
completely disable the heat pump (and all of its terminal
units) as required. If this field is blank, the unit is
enabled the entire simulation.
This numeric field defines the total cooling capacity
(sensible + latent) of the heat pump at rated conditions in
watts. The cooling capacity must be greater than 0 or set to
autosize.
This numeric field defines the cooling coefficient of
performance at rated conditions. The cooling coefficient of
performance includes compressor power and condenser fan power.
This COP value does not account for impacts due to the supply
air fan. The nominal heat pump cooling COP must be greater
than 0. If this field is left blank, a default coefficient of
performance of 3.3 is assumed.
Field:
Minimum Outdoor Temperature in Cooling Mode[LINK]
This numeric field defines the minimum outdoor dry-bulb
temperature allowed for cooling operation. Below this
temperature, cooling is disabled. If this field is left blank,
the default value is -6ºC.
Field:
Maximum Outdoor Temperature in Cooling Mode[LINK]
This numeric field defines the maximum outdoor dry-bulb
temperature allowed for cooling operation. Above this
temperature, cooling is disabled. If this field is left blank,
the default value is 43ºC.
Field:
Cooling Capacity Ratio Modifier Function of Low Temperature
Curve Name[LINK]
This alpha field defines the cooling capacity ratio
modifier at low outdoor dry-bulb temperatures. This curve is a
bi-quadratic equation using weighted average indoor wet-bulb
temperature (i.e., the indoor terminal units weighted average
inlet temperatures) and condenser entering air dry-bulb
temperature as the independent variables. This performance
curve can be used to describe the cooling capacity ratio at
low outdoor temperatures (i.e., the following two curves are
used) or can be used to describe the performance for all
outdoor temperatures (i.e., the following two curves are not
used). For this system type it is likely that all three of
these performance curves will be required. See the Engineering
Reference for more discussion on using this input field.
Field:
Cooling Capacity Ratio Boundary Curve Name[LINK]
This alpha field defines the cooling capacity ratio
boundary curve name. This curve is a linear, quadratic or
cubic curve that defines a change in cooling capacity at a
specific condenser entering air dry-bulb temperature as a
function of indoor air wet-bulb temperature. This curve is
used when the trend in cooling capacity changes dramatically
as outdoor temperature changes. If the cooling capacity does
not change dramatically with changes in outdoor conditions,
this field may be left blank. See the Engineering Reference
for more discussion on using this input field.
Field:
Cooling Capacity Ratio Modifier Function of High Temperature
Curve Name[LINK]
This alpha field defines the cooling capacity ratio
modifier at high outdoor temperatures. This curve is a
bi-quadratic equation using weighted average indoor wet-bulb
temperature and condenser entering air dry-bulb temperature as
the independent variables. This curve is used when the trend
in cooling capacity changes dramatically as outdoor
temperature changes. If the cooling capacity does not change
dramatically with changes in outdoor conditions, this field
may be left blank. See the Engineering Reference for more
discussion on using this input field.
Field:
Cooling Energy Input Ratio Modifier Function of Low
Temperature Curve Name[LINK]
This alpha field defines the cooling energy input ratio
modifier at low outdoor temperatures. This curve is a
bi-quadratic equation with a weighted average indoor wet-bulb
temperature and condenser entering air dry-bulb temperature as
the independent variables. This performance curve can be used
to describe the cooling energy input ratio at low outdoor
temperatures (i.e., the following two curves are used) or can
be used to describe the performance for all outdoor
temperatures (i.e., the following two curves are not used).
For this system type it is likely that all three of these
performance curves will be required. See the Engineering
Reference for more discussion on using this input field.
Field:
Cooling Energy Input Ratio Boundary Name[LINK]
This alpha field defines the cooling energy input ratio
boundary curve name. This curve is a linear, quadratic or
cubic curve that defines a change in cooling energy at a
specific condenser entering air dry-bulb temperature as a
function of indoor air wet-bulb temperature. This curve is
used when the trend in cooling energy changes dramatically as
outdoor temperature changes. If the cooling energy does not
change dramatically with changes in outdoor conditions, this
field may be left blank. See the Engineering Reference for
more discussion on using this input field.
Field:
Cooling Energy Input Ratio Modifier Function of High
Temperature Curve Name[LINK]
This alpha field defines the cooling energy input ratio
modifier at high outdoor temperatures. This curve is a
bi-quadratic equation with weighted average indoor wet-bulb
temperature and condenser entering air dry-bulb temperature as
the independent variables. This curve is used when the trend
in cooling energy changes dramatically as outdoor temperature
changes. If the cooling energy does not change dramatically
with changes in outdoor conditions, this field may be left
blank. See the Engineering Reference for more discussion on
using this input field.
Field:
Cooling Energy Input Ratio Modifier Function of Low Part-Load
Ratio Curve Name[LINK]
This alpha field defines the cooling energy input ratio
modifier (function of part-load ratio when PLR is less than or
equal to 1) curve name. This curve is a linear, quadratic or
cubic equation with cooling part-load ratio used as the
independent variable. The cooling energy input ratio modifier
curve is normalized to 1 at a part-load ratio of 1 and is used
only when the operating part-load ratio is less than or equal
to 1.
Field:
Cooling Energy Input Ratio Modifier Function of HIgh Part-Load
Ratio Curve Name[LINK]
This alpha field defines the cooling energy input ratio
modifier (function of part-load ratio when PLR is greater than
1) curve name. This curve is a linear, quadratic or cubic
equation with cooling part-load ratio used as the independent
variable. The cooling energy input ratio modifier curve is
normalized to 1 at a part-load ratio of 1 and is used only
when the operating part-load ratio is greater than 1.
Field:
Cooling Combination Ratio Correction Factor Curve Name[LINK]
This alpha field defines the cooling combination ratio (CR)
correction factor curve name for combination ratios greater
than or equal to 1. The combination ratio is defined as the
total rated indoor terminal unit cooling capacity divided by
this heat pump’s gross rated total cooling capacity. The curve
is a linear, quadratic or cubic equation and uses the minimum
value of x in the curve object to determine the maximum
part-load ratio which is linearly proportional to capacity
(i.e., the minimum value of x [CR] in the curve object must be
≥1). The output of this curve provides a multiplier (>1)
which is applied to this heat pump’s Gross Rated Total Cooling
Capacity. Between a combination ratio of 1 and the curve’s
minimum value of x, the multiplier is linearly interpolated.
For combination ratio’s less than 1 (i.e., the total indoor
terminal unit capacity is less than this heat pump’s rated
total capacity), capacity is directly proportional to
part-load ratio and this curve will not be used.
This alpha field defines the cooling part-load fraction
correlation curve name. This curve is used to define the
cycling losses when the condenser’s compressors cycle on and
off. The compressor cycles when the cooling part-load ratio is
less than the Minimum Heat Pump Part-Load Ratio specified
later in this object’s inputs.
This numeric field defines the gross total heat pump
heating capacity at rated conditions in watts. The nominal
heat pump heating capacity must be greater than 0 or set to
autosize.
This numeric field defines the ratio of gross heating to
gross cooling capacity. The model assumes that when used, this
value will be greater than 1. A similar input is available in
the ZoneHVAC:TerminalUnit:VariableRefrigerantFlow
object. When the heating capacity is autosized, if this field
is non-blank, this ratio is used to scale the heating capacity
to the gross rated total cooling capacity regardless of the
value entered in the terminal unit objects. When the heating
capacity is not autosized, the gross rated heating capacity
will be equal to the sum of the terminal unit heating coil
size. If this field is blank and the terminal unit sizing
ratio input is also blank, then the heating capacity sizing
ratio is assumed to be 1. If this field is not blank and the
heating capacity sizing ratio in the terminal unit object(s)
is blank, then this ratio also applies to each heating coil.
If this field is not blank and the heating capacity sizing
ratio in the terminal units is also not blank, then the
terminal unit heating coil capacity sizing ratio input applies
to each heating coil.
This numeric field defines the heating coefficient of
performance at rated conditions. The heating coefficient of
performance includes compressor power and condenser fan power.
This gross COP value does NOT account for the supply air fan.
The nominal heat pump heating COP must be greater than 0. If
this field is left blank, a coefficient of performance of 3.4
is assumed.
Field:
Minimum Outdoor Temperature in Heating Mode[LINK]
This numeric field defines the minimum outdoor temperature
allowed for heating operation. Below this temperature, heating
is disabled. If this field is left blank, the default value is
-20ºC.
Field:
Maximum Outdoor Temperature in Heating Mode[LINK]
This numeric field defines the maximum outdoor temperature
allowed for heating operation. Above this temperature, heating
is disabled. If this field is left blank, the default value is
16ºC.
Field:
Heating Capacity Ratio Modifier Function of Low Temperature
Curve Name[LINK]
This alpha field defines the heating capacity ratio
modifier at low temperature curve name. This curve is a
bi-quadratic equation with a weighted average indoor dry-bulb
temperature (i.e., the indoor terminal units weighted average
inlet temperatures) and condenser entering air dry-bulb or
wet-bulb temperature as the independent variables. Since
manufacturers may provide performance data using either
outdoor dry-bulb or wet-bulb temperatures, either of these
temperature types may be used for heating performance curves
as specified in the Heating Performance Curve Outdoor
Temperature Type input field below. This performance curve can
be used to describe the heating capacity ratio at low outdoor
temperatures (i.e., the following two curves are used) or can
be used to describe the performance for all outdoor
temperatures (i.e., the following two curves are not used).
For this system type it is likely that all three of these
performance curves will be required. See the Engineering
Reference for more discussion on using this input field.
Field:
Heating Capacity Ratio Boundary Curve Name[LINK]
This alpha field defines the heating capacity ratio
boundary curve name. This curve is a quadratic or cubic curve
that defines a change in heating capacity at a specific
condenser entering air dry-bulb or wet-bulb temperature as a
function of indoor air dry-bulb temperature. Since
manufacturers may provide performance data using either
outdoor dry-bulb or wet-bulb temperatures, either of these
temperature types may be used for heating performance curves
as specified in the Heating Performance Curve Outdoor
Temperature Type input field below. This curve is used when
the trend in heating capacity changes dramatically as outdoor
temperature changes. If the heating capacity does not change
dramatically with changes in outdoor conditions, this field
may be left blank.
Field:
Heating Capacity Ratio Modifier Function of High Temperature
Curve Name[LINK]
This alpha field defines the heating capacity ratio
modifier at high temperature curve name. This curve is a
bi-quadratic equation with a weighted average indoor dry-bulb
temperature and condenser entering air dry-bulb or wet-bulb
temperature as the independent variables. Since manufacturers
may provide performance data using either outdoor dry-bulb or
wet-bulb temperatures, either of these temperature types may
be used for heating performance curves as specified in the
Heating Performance Curve Outdoor Temperature Type input field
below. This curve is used when the trend in heating capacity
changes dramatically as outdoor temperature changes. If the
heating capacity does not change dramatically with changes in
outdoor conditions, this field may be left blank.
Field:
Heating Energy Input Ratio Modifier Function of Low
Temperature Curve Name[LINK]
This alpha field defines the heating energy input ratio
modifier at low temperature curve name. This curve is a
bi-quadratic equation with a weighted average indoor dry-bulb
temperature and condenser entering air dry-bulb or wet-bulb
temperature as the independent variables. Since manufacturers
may provide performance data using either outdoor dry-bulb or
wet-bulb temperatures, either of these temperature types may
be used for heating performance curves as specified in the
Heating Performance Curve Outdoor Temperature Type input field
below. This performance curve can be used to describe the
heating energy input ratio at low outdoor temperatures (i.e.,
the following two curves are used) or can be used to describe
the performance for all outdoor temperatures (i.e., the
following two curves are not used).
Field:
Heating Energy Input Ratio Boundary Curve Name[LINK]
This alpha field defines the heating energy input ratio
boundary curve name. This curve is a quadratic or cubic curve
that defines a change in heating energy at a specific
condenser entering air dry-bulb or wet-bulb temperature as a
function of indoor air dry-bulb temperature. Since
manufacturers may provide performance data using either
outdoor dry-bulb or wet-bulb temperatures, either of these
temperature types may be used for heating performance curves
as specified in the Heating Performance Curve Outdoor
Temperature Type input field below. This curve is used when
the trend in heating energy changes dramatically as outdoor
temperature changes. If the heating energy does not change
dramatically with changes in outdoor conditions, this field
may be left blank.
Field:
Heating Energy Input Ratio Modifier Function of High
Temperature Curve Name[LINK]
This alpha field defines the heating energy input ratio
modifier at high temperature curve name. This curve is a
bi-quadratic equation with a weighted average indoor dry-bulb
temperature and condenser entering air dry-bulb or wet-bulb
temperature as the independent variables. Since manufacturers
may provide performance data using either outdoor dry-bulb or
wet-bulb temperatures, either of these temperature types may
be used for heating performance curves as specified in the
Heating Performance Curve Outdoor Temperature Type input field
below. This curve is used when the trend in heating energy
changes dramatically as outdoor temperature changes. If the
heating energy does not change dramatically with changes in
outdoor conditions, this field may be left blank.
Field:
Heating Performance Curve Outdoor Temperature Type[LINK]
This choice field defines the outdoor temperature type used
for all performance curves. The valid choices are
DryBulbTemperature and WetBulbTemperature. The default value
is WetBulbTemperature. Manufacturers will typically provide
heating performance data as a function of outdoor air wet-bulb
temperatures. This means that the performance (e.g., capacity
and energy input ratio) curves will use outdoor wet-bulb
temperature as one of the independent variables. At times,
manufacturers will only provide performance data as a function
of outdoor dry-bulb temperatures. In this case, all
performance curves shall be developed using outdoor dry-bulb
temperature and this field shall be selected as
DryBulbTemperature.
Field:
Heating Energy Input Ratio Modifier Function of Low Part-Load
Ratio Curve Name[LINK]
This alpha field defines the heating energy input ratio
modifier (function of part-load ratio when PLR is less than or
equal to 1) curve name. This curve is a linear, quadratic, or
cubic equation with heating part-load ratio used as the
independent variable. The heating energy input ratio modifier
curve is normalized to 1 at a part-load ratio of 1 and is used
only when the part-load ratio is less than or equal to 1.
Field:
Heating Energy Input Ratio Modifier Function of High Part-Load
Ratio Curve Name[LINK]
This alpha field defines the heating energy input ratio
modifier (function of part-load ratio when PLR is greater than
1) curve name. This curve is a linear, quadratic, or cubic
equation with heating part-load ratio used as the independent
variable. The heating energy input ratio modifier curve is
normalized to 1 at a part-load ratio of 1 and is used only
when the part-load ratio is greater than 1.
Field:
Heating Combination Ratio Correction Factor Curve Name[LINK]
This alpha field defines the heating combination ratio (CR)
correction factor curve name for combination ratios greater
than or equal to 1. The combination ratio is defined as the
total rated indoor heating capacity divided by the rated heat
pump heating capacity. The curve is either quadratic or cubic
and uses the minimum value of x in the curve object to
determine the maximum part-load ratio which is linearly
proportional to capacity (i.e., the minimum value of x in the
curve object must be ≥1). The output of this curve provides a
multiplier (>1) which is applied to the Nominal Heat Pump
Heating Capacity. Between a combination ratio of 1 and the
curve’s minimum value of x, the multiplier is linearly
interpolated. For combination ratio’s less than 1, capacity is
directly proportional to part-load ratio and this curve will
not be used. If this field is left blank, the Cooling
Combination Ratio Correction factor will be used.
This alpha field defines the heating part-load fraction
correlation curve name. This curve is used to define the
cycling losses when the condenser’s compressors cycle on and
off. The compressor cycles when the indoor to outdoor heating
capacity ratio is less than the Minimum Heat Pump Part-Load
Ratio specified in the following field.
This numeric field specifies the minimum operating
part-load ratio (PLR) of the heat pump. When the heat pump
operates at a PLR below this value, the heat pump’s compressor
will cycle to meet the cooling or heating demand. Above this
value, the heat pump’s compressor operates the entire time
step to meet the cooling or heating demand. The minimum value
for this field is 0. If this field is left blank, the default
value is 0.15. When the heat pump compressor cycles, the
previous field is used to determine cycling losses.
Field:
Zone Name for Master Thermostat Location[LINK]
This alpha field defines the name of the zone where the
“master” thermostat is located. When the heat pump is
connected to multiple zone terminal units, one terminal unit
must be selected as the master thermostat. The remaining
thermostats are slaves and can operate only in the same mode
as the master thermostat.
Field:
Master Thermostat Priority Control Type[LINK]
This choice field determines the logic used to simulate the
“master” thermostat. Valid choices are LoadPriority,
ZonePriority, ThermostatOffsetPriority,
MasterThermostatPriority, and Scheduled. The default value is
MasterThermostatPriority. When LoadPriority is selected, the
total zone load is used to choose the operating mode as either
cooling or heating. When ZonePriority is selected, the number
of zones requiring cooling or heating determines the operating
mode. When ThermostatOffsetPriority is selected, the zone
farthest from the thermostat set point determines the
operating mode. The MasterThermostatPriority choice operates
the system according the zone load where the master thermostat
is located. The heat pump can also be scheduled to operate in
either cooling or heating mode. For scheduled operation, a
schedule name is entered in the following field.
This alpha field identifies the schedule used when the
previous field is set to Scheduled. Schedule values of 0
denote cooling mode while values of 1 denote heating mode. Any
other values will force the system off.
This alpha field defines the name of the zone terminal unit
list. The name specified here should match the name of a valid
ZoneTerminalUnitList
object. In addition, each name specified in this list should
match the name of a valid ZoneHVAC:TerminalUnit:
VariableRefrigerantFlow object. All terminal units connected
to this heat pump must be listed in this ZoneTerminalUnitList
object.
Note: the previous field is designated at the last field
necessary to simulate the variable refrigerant flow heat pump.
The following fields do not have to be entered, however,
piping loses, defrost operation, crankcase heater operation,
and basin heater operation will not be modeled. Defaults for
fields not entered may also not apply. These remaining fields
must be entered if that portion of the model is to be
simulated.
This choice field defines the configuration of the heat
pump refrigeration system. Valid choices are
Yes and No. If Yes is
selected, heat recovery is enabled and the heat pump can
independently cool and heat different zones. If No is
selected, the heat pump is only able to cool or heat for any
given time step.
Field:
Equivalent Piping Length used for Piping Correction Factor in
Cooling Mode[LINK]
This numeric field defines the equivalent pipe length in
meters between the farthest terminal unit and the heat pump
condenser. This value includes the gas refrigerant line length
(for both horizontal and vertical distances), fitting losses,
pipe bends, and other connections that contribute to piping
losses. This field is used to calculate the piping correction
factor in cooling mode. This value defines the head losses due
to the pipe length between the farthest terminal unit and the
heat pump condenser and impacts the maximum available capacity
in cooling mode.
Field:
Vertical Height used for Piping Correction Factor[LINK]
This numeric field defines the vertical pipe height in
meters between the highest or lowest terminal unit and the
heat pump condenser. This value defines the gravitational
losses due to a change in height between the highest (positive
value), or lowest (negative value) terminal unit and the heat
pump condenser. The distance specified here is applied to the
piping correction factor calculation for both cooling and
heating. If the distance between the highest terminal unit
above the heat pump condenser is greater than the distance
between the lowest terminal unit below the condenser enter the
difference between the highest and lowest terminal units as a
positive distance, otherwise enter this difference as a
negative distance. Example: if the distance from the heat pump
condenser to the highest terminal unit above the condenser is
10 m and the distance from the heat pump condenser to the
lowest terminal unit below the condenser is -15 m, then enter
a value of -5 m in this field. This head loss impacts the
maximum available capacity in cooling mode.
Field:
Piping Correction Factor for Length in Cooling Mode Curve
Name[LINK]
This alpha field defines the linear, quadratic, or cubic
curve name used to calculate the piping correction factor for
length in cooling mode. Piping losses are a function of piping
length. If sufficient piping loss information is available
where piping losses are also a function of combination ratio
(i.e., in addition to length), a biquadratic performance curve
may be used.
Field:
Piping Correction Factor for Height in Cooling Mode
Coefficient[LINK]
This numeric field defines the coefficient used to
calculate the piping correction factor for height in cooling
mode.
Field:
Equivalent Piping Length used for Piping Correction Factor in
Heating Mode[LINK]
This numeric field defines the equivalent pipe length in
meters between the farthest terminal unit and the heat pump
condenser. This value includes the liquid refrigerant line
length (for both horizontal and vertical distances), fitting
losses, pipe bends, and other connections that contribute to
piping losses. This field is used to calculate the piping
correction factor in heating mode. This value defines the head
losses due to the pipe length between the farthest terminal
unit and the heat pump condenser and impacts the maximum
available capacity in heating mode.
Field:
Piping Correction Factor for Length in Heating Mode Curve
Name[LINK]
This alpha field defines the linear, quadratic, or cubic
curve name used to calculate the piping correction factor for
length in heating mode. Piping losses are a function of piping
length. If sufficient piping loss information is available
where piping losses are also a function of combination ratio
(i.e., in addition to length), a biquadratic performance curve
may be used.
Field:
Piping Correction Factor for Height in Heating Mode
Coefficient[LINK]
This numeric field defines the coefficient used to
calculate the piping correction factor for height in heating
mode.
Field:
Crankcase Heater Power per Compressor[LINK]
This numeric field defines the electrical power consumed by
the crankcase heater in watts for each compressor.
This crankcase heater power is consumed when the outdoor
temperature is below the maximum outdoor dry-bulb temperature
for crankcase heater operation. The minimum value for this
field is 0. If this field is left blank, the default value is
33 watts. Crankcase heater electrical consumption is applied
only when the compressor is off or is applied during the off
cycle when the compressor is cycling below the Minimum Heat
Pump Part-Load Ratio. This field is only used to calculate
crankcase heater power and has no impact on heat pump
performance.
This numeric field defines the number of compressors in the
heat pump condensing unit and is used exclusively to determine
the operating characteristics of the crankcase heater. For
example, if the number of compressors is 3, one crankcase
heater will operate when the heat pump condensing unit’s
part-load ratio is less than or equal to 0.67 (when the ratio
of compressor size to total compressor capacity input is 0.33)
and the outdoor temperature is below the maximum outdoor
temperature for crankcase heater operation. Similarly, two
crankcase heaters will operate when the heat pump condensing
unit’s PLR is less than or equal to 0.33 and the outdoor
temperature is below the maximum outdoor temperature for
crankcase heater operation. If the heat pump condensing unit
is off, all 3 crankcase heaters will operate if the outdoor
temperature is below the maximum outdoor temperature for
crankcase heater operation. The minimum value for this field
is 1. If this field is left blank, the default value is 2.
This field is only used to calculate crankcase heater power
and has no impact on heat pump performance.
Field:
Ratio of Compressor Size to Total Compressor Capacity[LINK]
This numeric field defines the size of the first stage
compressor to the total compressor capacity and is used
exclusively for calculating crankcase heater energy. If this
field and the previous field are left blank, the default value
is 0.5. If this field is left blank and the previous field is
not blank, the compressors are assumed to be equally sized.
When the number of compressors is greater than 2, the
2nd stage compressor and all additional compressors
are assumed to be equally sized. This field is only used to
calculate crankcase heater power and has no impact on heat
pump performance.
Field:
Maximum Outdoor Dry-bulb Temperature for Crankcase Heater[LINK]
This numeric field defines the maximum outdoor temperature,
in degrees Celsius, below which the crankcase heater will
operate. If this field is left blank, the default value is 0C.
This field is only used to calculate crankcase heater power
and has no impact on heat pump performance.
This alpha field has two choices: reverse-cycle or
resistive. If the reverse-cycle strategy is selected, the
heating cycle is reversed periodically to provide heat to melt
frost accumulated on the outdoor coil. If a resistive defrost
strategy is selected, the frost is melted using an electric
resistance heater. If this input field is left blank, the
default defrost strategy is reverse-cycle. Defrost can be
disabled by entering a resistive defrost strategy using a
timed defrost control, a 0 defrost time period fraction and a
0 resistive defrost heater capacity in the following inputs
fields. This method is used when the Maximum Outdoor Dry-Bulb
Temperature for Defrost Operation field value is greater than
the expected minimum outdoor dry-bulb temperature simulated in
the weather file.
This alpha field has two choices: timed or on-demand. If
timed control is selected, the defrost time period is
calculated based on a fixed value of compressor runtime
whether or not frost has actually accumulated. For timed
defrost control, the fractional amount of time the unit is in
defrost is entered in the input field “Defrost Time Period
Fraction” described below. If on-demand defrost control is
selected, the defrost time period is calculated based on
outdoor weather (humidity ratio) conditions. Regardless of
which defrost control is selected, defrost does not occur
above the user specified outdoor temperature entered in the
input field “Maximum Outdoor Dry-bulb Temperature for Defrost
Operation” described above. If this input field is left blank,
the default defrost control is timed.
Field:
Defrost Energy Input Ratio Modifier Function of Temperature
Curve Name[LINK]
This alpha field defines the name of a bi-quadratic
performance curve (ref: Performance Curves) that parameterizes
the variation of the energy input ratio (EIR) during
reverse-cycle defrost periods as a function of the outdoor air
dry-bulb temperature and the weighted average wet-bulb
temperature of the air entering the indoor terminal units. The
output of this curve is multiplied by the coil capacity, the
fractional defrost time period and the runtime fraction of the
heating coil to give the defrost power at the specific
temperatures at which the indoor and outdoor coils are
operating. The curve is normalized to a value of 1.0 at the
rating point conditions.
This numeric field defines the fraction of compressor
runtime when the defrost cycle is active. For example, if the
defrost cycle is active for 3.5 minutes for every 60 minutes
of compressor runtime, then the user should enter 3.5/60 =
0.058333. The value for this input field must be greater than
or equal to 0. If this input field is left blank, the default
value is 0.058333.
This numeric field defines the capacity of the resistive
defrost heating element in Watts. This input field is used
only when the selected defrost strategy is ‘resistive’ (see
input field “Defrost Strategy” above). The value for this
input field must be greater than or equal to 0. If this input
field is left blank, the default value is 0.
Field:
Maximum Outdoor Dry-bulb Temperature for Defrost
Operation[LINK]
This numeric field defines the outdoor air dry-bulb
temperature above which outdoor coil defrosting is disabled.
If this input field is left blank, the default value is 5 C.
Defrost can be completely eliminated by selecting a
temperature lower than the minimum expected outdoor
temperature found in the weather file.
This alpha field defines the name of the condenser inlet
air or water node. For Condenser type = AirCooled, this node
name should also be listed in an OutdoorAir:Node
or OutdoorAir:NodeList
object. If this field is blank, the model assumes an
air-cooled condenser and the weather file is used to define
the outdoor conditions entering the condenser. If this field
is not blank, the node conditions are used to define the
outdoor air or inlet water conditions entering the condenser.
A node name is typically entered here for air-cooled systems
when conditions other than those found in the weather file
should be used (ref. OutdoorAir:Node
related to height above ground).
This numeric field defines the condenser water volume flow
rate in cubic meters per second. This field is autosizable and
only used for water-cooled systems.
\(Tcond\,inlet\) = the
temperature of the air entering the condenser coil (C)
\(Twb,o\) = the wet-bulb
temperature of the outdoor air (C)
\(Tdb,o\) = the dry-bulb
temperature of the outdoor air (C)
The resulting condenser inlet air temperature is used by
the Cooling Capacity Ratio Modifier Curve (function of
temperature) and the Cooling Energy Input Ratio Modifier Curve
(function of temperature). The default value for this field is
0.9, although valid entries can range from 0.0 to 1.0. This
field is not used when Condenser Type = Air Cooled and the
simulation is calculating heating performance.
If the user wants to model an air-cooled condenser, they
should simply specify AirCooled in the field Condenser Type.
In this case, the Cooling Capacity Ratio Modifier Curve
(function of temperature) and the Cooling Energy Input Ratio
Modifier Curve (function of temperature) input fields for this
object should reference performance curves that are a function
of outdoor dry-bulb temperature.
If the user wishes to model an evaporative-cooled condenser
AND they have performance curves that are a function of the
wet-bulb temperature of air entering the condenser coil, then
the user should specify Condenser Type = EvapCooled and the
evaporative condenser effectiveness value should be entered as
1.0. In this case, the Cooling Capacity Ratio Modifier Curve
(function of temperature) and the Cooling Energy Input Ratio
Modifier Curve (function of temperature) input fields for this
object should reference performance curves that are a function
of the wet-bulb temperature of air entering the condenser
coil.
If the user wishes to model an air-cooled condenser that
has evaporative media placed in front of it to cool the air
entering the condenser coil, then the user should specify
Condenser Type = EvapCooled. The user must also enter the
appropriate evaporative effectiveness for the media. In this
case, the Cooling Capacity Ratio Modifier Curve (function of
temperature) and the Cooling Energy Input Ratio Modifier Curve
(function of temperature) input fields for this object should
reference performance curves that are a function of outdoor
dry-bulb temperature. Be aware that the evaporative media will
significantly reduce the dry-bulb temperature of the air
entering the condenser coil, so the Cooling Capacity and
Cooling EIR Modifier Curves must be valid for the expected
range of dry-bulb temperatures that will be entering the
condenser coil.
The air volume flow rate, in m3 per second,
entering the evaporative condenser. This value is used to
calculate the amount of water used to evaporatively cool the
condenser inlet air. The minimum value for this field must be
greater than zero, and this input field is autosizable
(equivalent to 0.000144 m3/s per watt of rated
total cooling capacity [850 cfm/ton]). This field is not used
when Condenser Type = AirCooled.
Field:
Evaporative Condenser Pump Rated Power Consumption[LINK]
The rated power of the evaporative condenser water pump in
Watts. This value is used to calculate the power required to
pump the water used to evaporatively cool the condenser inlet
air. The default value for this input field is zero, but it is
autosizable (equivalent to 0.004266 W per watt [15 W/ton] of
rated total cooling capacity). This field is not used when
Condenser Type = AirCooled.
This numeric field contains the capacity of the heat pump’s
electric basin heater in watts per degree Kelvin. This field
only applies for Condenser Type = EvaporativelyCooled. This
field is used in conjunction with the Basin Heater Setpoint
Temperature described in the following field. The basin heater
electric power is equal to this field multiplied by the
difference between the basin heater set point temperature and
the outdoor dry-bulb temperature. The basin heater only
operates when the heat pump compressor(s) is off, regardless
of the basin heater schedule described below. The basin heater
capacity must be greater than or equal to zero, with a default
value of zero if this field is left blank.
This numeric field contains the set point temperature (˚C)
for the basin heater described in the previous field. This
field only applies for Condenser Type = EvaporativelyCooled.
The basin heater is active when the outdoor air dry-bulb
temperature falls below this setpoint temperature, as long as
the heat pump is off. This set point temperature must be
greater than or equal to 2˚C, and the default value is 2˚C if
this field is left blank.
This alpha field contains the name of the basin heater
operating schedule. This field only applies for Condenser Type
= EvaporativelyCooled. The basin heater operating schedule is
assumed to be an on/off schedule and the heater is available
to operate any time the schedule value is greater than 0. The
basin heater operates when scheduled on and the outdoor air
dry-bulb temperature is below the set point temperature
described in the previous field. If this field is left blank,
the basin heater is available to operate throughout the
simulation. Regardless of this schedule, the basin heater may
only operate when the heat pump is off.
This alpha field determines the type of fuel that this
variable refrigerant flow system uses. This field has seven
choices: Electricity, NaturalGas, PropaneGas, Diesel,
Gasoline, FuelOil#1, FuelOil#2, OtherFuel1, and OtherFuel2.
The default is Electricity. The use of alternate fuel types
assumes an engine drives the variable speed compression system
and also accounts for condenser air flow (i.e., a fan attached
to the engine provides air flow through the outdoor
condenser.
Field:
Minimum Outdoor Temperature in Heat Recovery Mode[LINK]
This numeric field defines the minimum outdoor dry-bulb
temperature allowed for heat recovery operation. Below this
temperature, heat recovery is disabled. This input must be
greater than the larger of the minimum outdoor temperature in
cooling or heating mode. If this field is left blank, the
default value is the higher of the Minimum Outdoor Temperature
in Cooling Mode or Minimum Outdoor Temperature in Heating Mode
inputs. This system may still operate in cooling or heating
only mode when outdoor temperatures are below the minimum
outdoor temperature in heat recovery mode. This input is only
used when Heat Pump Waste Heat Recovery is selected as
Yes.
Field:
Maximum Outdoor Temperature in Heat Recovery Mode[LINK]
This numeric field defines the maximum outdoor dry-bulb
temperature allowed for heat recovery operation. Above this
temperature, heat recovery is disabled. This input must be
less than the smaller of the maximum outdoor temperature in
cooling or heating mode. If this field is left blank, the
default value is the lower of the Maximum Outdoor Temperature
in Cooling Mode or Maximum Outdoor Temperature in Heating Mode
inputs.. This system may still operate in cooling or heating
only mode when outdoor temperatures are above the maximum
outdoor temperature in heat recovery mode. This input is only
used when Heat Pump Waste Heat Recovery is selected as
Yes.
This alpha field defines the cooling capacity modifier when
heat recovery mode is active. This modifier is used as a
multiplier for available cooling capacity, and when in heat
recovery mode, this modifier is usually less than 1. This
curve is either a bi-quadratic equation using weighted average
indoor temperature (i.e., the indoor terminal units weighted
average inlet temperatures) and condenser entering air
temperature as the independent variables or a cubic curve
based on part-load ratio. This performance curve can be used
to describe the cooling capacity modifier as either a constant
(e.g., temperature or part-load ratio term coefficients are
0), a cooling modifier that varies with either indoor
temperature and/or outdoor temperature, or part-load ratio
(e.g., one or more temperature or part-load ratio term
coefficients are 0), or varies with both indoor and outdoor
temperatures or part-load ratio (e.g., all temperature or
part-load ratio term coefficients are non-zero). If this field
is left blank, and heat recovery operating mode is selected,
the default constant modifier is 0.9. This modifier is applied
only when heat recovery mode is active. To model a heat
recovery system which has no degradation in cooling
performance when heat recovery mode is active, or if the
degradation is not constant at different operating conditions,
a performance curve object must be used. This input is only
used when Heat Pump Waste Heat Recovery is selected as Yes and
the system changes from cooling only mode to heat recovery
mode.
This numeric field defines the fraction of cooling capacity
available when the system transitions from cooling only
operation to simultaneous cooling and heating. It is common
for the cooling capacity to decrease before the system
recovers. If this field is left blank, a default value of 0.5
is used (50% reduction in cooling capacity at the start of
heat recovery mode). The system will recovery according to the
time constant entered in Heat Recovery Cooling Capacity Time
Constant input field. If the transition period will not be
modeled, this input field must be set to 1. This input is only
used when Heat Pump Waste Heat Recovery is selected as Yes and
the system changes from cooling only mode to heat recovery
mode. Refer to the engineering reference document discussion
on the variable refrigerant flow heat pump model section for
transition from cooling only mode to heat recovery mode for a
more detailed description.
Field:
Heat Recovery Cooling Capacity Time Constant[LINK]
This numeric field defines the cooling capacity time
constant, in hours, used to model the time it takes for the
system to change from cooling only operation to simultaneous
cooling and heating. Total response time is defined as 5 time
constants. If this field is left blank, a default value of
0.083 is used. If the transition period will not be modeled,
the Initial Heat Recovery Cooling Capacity Fraction field must
be set to 1. This input is only used when Heat Pump Waste Heat
Recovery is selected as Yes and the system changes from
cooling only mode to heat recovery mode. Refer to the
engineering reference document discussion on the variable
refrigerant flow heat pump model section for transition from
cooling only mode to heat recovery mode for a more detailed
description.
Field:
Heat Recovery Cooling Energy Modifier Curve Name[LINK]
This alpha field defines the cooling energy modifier when
heat recovery mode is active. This modifier is used as a
multiplier for operating cooling energy, and when in heat
recovery mode, this modifier is usually greater than 1. This
curve is a bi-quadratic equation using weighted average indoor
temperature (i.e., the indoor terminal units weighted average
inlet temperatures) and condenser entering air temperature as
the independent variables. This performance curve can be used
to describe the cooling energy modifier as either a constant
(e.g., temperature term coefficients are 0), a cooling energy
modifier that varies with indoor and/or outdoor temperatures
(e.g., one or more temperature term coefficients are 0), or
varies with both indoor and outdoor temperatures (e.g.,
temperature term coefficients are non-zero). If this field is
left blank, and heat recovery operating mode is selected, the
default constant modifier is 1.1. This modifier is applied
only when heat recovery mode is active. To model a heat
recovery system which has no degradation in cooling
performance when heat recovery mode is active, or if the
degradation is not constant at different operating conditions,
a performance curve object must be used. This input is only
used when Heat Pump Waste Heat Recovery is selected as Yes and
the system changes from cooling only mode to heat recovery
mode.
Field:
Initial Heat Recovery Cooling Energy Fraction[LINK]
This numeric field defines the fraction of cooling energy
consumed when the system transitions from cooling only
operation to simultaneous cooling and heating. It is common
for the cooling energy to drop before the system recovers. If
this field is left blank, a default value of 1 is used (no
change in energy at the start of heat recovery mode). If the
transition period will not be modeled, this input field must
be set to 1. This input is only used when Heat Pump Waste Heat
Recovery is selected as Yes and the system changes from
cooling only mode to heat recovery mode. Refer to the
engineering reference document discussion on the variable
refrigerant flow heat pump model section for transition from
cooling only mode to heat recovery mode for a more detailed
description.
Field:
Heat Recovery Cooling Energy Time Constant[LINK]
This numeric field defines the cooling energy time
constant, in hours, used to model the time it takes for the
system to transition from cooling only operation to
simultaneous cooling and heating. Total response time is
defined as 5 time constants. If this field is left blank, a
default value of 0.0 is used. If the transition period will
not be modeled, the Initial Heat Recovery Cooling Energy
Fraction field must be set to 1. This input is only used when
Heat Pump Waste Heat Recovery is selected as Yes and the
system changes from cooling only mode to heat recovery mode.
Refer to the engineering reference document discussion on the
variable refrigerant flow heat pump model section for
transition from cooling only mode to heat recovery mode for a
more detailed description.
This alpha field defines the heating capacity modifier when
heat recovery mode is active. This modifier is used as a
multiplier for available heating capacity, and when in heat
recovery mode, this modifier is usually less than 1. This
curve is a bi-quadratic equation using weighted average indoor
temperature (i.e., the indoor terminal units weighted average
inlet temperatures) and condenser entering air temperature as
the independent variables. This performance curve can be used
to describe the heating capacity modifier as either a constant
(e.g., temperature term coefficients are 0), a heating
modifier that varies with indoor and/or outdoor temperatures
(e.g., one or more temperature term coefficients are 0), or
varies with both indoor and outdoor temperatures (e.g.,
temperature term coefficients are non-zero). If this field is
left blank, and heat recovery operating mode is selected, the
default constant modifier is 0.9. This modifier is applied
only when heat recovery mode is active. To model a heat
recovery system which has no degradation in heating
performance when heat recovery mode is active, or if the
degradation is not constant at different operating conditions,
a performance curve object must be used. This input is only
used when Heat Pump Waste Heat Recovery is selected as Yes and
the system changes from heating only mode to heat recovery
mode.
This numeric field defines the fraction of heating capacity
available when the system changes from heating only operation
to simultaneous heating and cooling. It is common for the
heating capacity to decrease before the system recovers. If
this field is left blank, a default value of 0.5 is used (50%
reduction in heating capacity at the start of heat recovery
mode). The system will recovery according to the time constant
entered in Heat Recovery Heating Capacity Time Constant input
field. If the transition period will not be modeled, this
input field must be set to 1. This input is only used when
Heat Pump Waste Heat Recovery is selected as Yes and the
system changes from heating only mode to heat recovery mode.
Refer to the engineering reference document discussion on the
variable refrigerant flow heat pump model section for
transition from cooling only mode to heat recovery mode for a
more detailed description.
Field:
Heat Recovery Heating Capacity Time Constant[LINK]
This numeric field defines the heating capacity time
constant, in hours, used to model the time it takes for the
system to transition from cooling only operation to
simultaneous cooling and heating. Total response time is
defined as 5 time constants. If this field is left blank, a
default value of 0.083 is used. If the transition period will
not be modeled, the Initial Heat Recovery Heating Capacity
Fraction field must be set to 1. This input is only used when
Heat Pump Waste Heat Recovery is selected as Yes and the
system changes from heating only mode to heat recovery mode.
Refer to the engineering reference document discussion on the
variable refrigerant flow heat pump model section for
transition from cooling only mode to heat recovery mode for a
more detailed description.
Field:
Heat Recovery Heating Energy Modifier Curve Name[LINK]
This alpha field defines the heating energy modifier when
heat recovery mode is active. This modifier is used as a
multiplier for operating heating energy, and when in heat
recovery mode, this modifier is usually greater than 1. This
curve is a bi-quadratic equation using weighted average indoor
temperature (i.e., the indoor terminal units weighted average
inlet temperatures) and condenser entering air temperature as
the independent variables. This performance curve can be used
to describe the heating energy modifier as either a constant
(e.g., temperature term coefficients are 0), a heating energy
modifier that varies with indoor and/or outdoor temperatures
(e.g., one or more temperature term coefficients are 0), or
varies with both indoor and outdoor temperatures (e.g.,
temperature term coefficients are non-zero). If this field is
left blank, and heat recovery operating mode is selected, the
default constant modifier is 1.1. This modifier is applied
only when heat recovery mode is active. To model a heat
recovery system which has no degradation in heating
performance when heat recovery mode is active, or if the
degradation is not constant at different operating conditions,
a performance curve object must be used. This input is only
used when Heat Pump Waste Heat Recovery is selected as Yes and
the system changes from heating only mode to heat recovery
mode.
Field:
Initial Heat Recovery Heating Energy Fraction[LINK]
This numeric field defines the fraction of heating energy
consumed when the system changes from heating only operation
to simultaneous heating and cooling. It is common for the
heating energy to decrease before the system recovers. If this
field is left blank, a default value of 0.5 is used (50%
reduction in heating energy at the start of heat recovery
mode). The system will recovery according to the time constant
entered in Heat Recovery Heating Energy Time Constant input
field. If the transition period will not be modeled, this
input field must be set to 1. This input is only used when
Heat Pump Waste Heat Recovery is selected as Yes and the
system changes from heating only mode to heat recovery mode.
Refer to the engineering reference document discussion on the
variable refrigerant flow heat pump model section for
transition from cooling only mode to heat recovery mode for a
more detailed description.
Field:
Heat Recovery Heating Energy Time Constant[LINK]
This numeric field defines the heating energy time
constant, in hours, used to model the time it takes for the
system to change from cooling only operation to simultaneous
cooling and heating. Total response time is defined as 5 time
constants. If this field is left blank, a default value of 0.0
is used. If the transition period will not be modeled, the
Initial Heat Recovery Heating Energy Fraction field must be
set to 1. This input is only used when Heat Pump Waste Heat
Recovery is selected as Yes and the system changes from
heating only mode to heat recovery mode. Refer to the
engineering reference document discussion on the variable
refrigerant flow heat pump model section for transition from
cooling only mode to heat recovery mode for a more detailed
description.
AirConditioner:VariableRefrigerantFlow,
VRF Heat Pump, !- Heat Pump Name
VRFCondAvailSched, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
3.16038, !- Gross Rated Cooling COP {W}
-5, !- Minimum Outdoor Temperature in Cooling Mode {C}
43, !- Maximum Outdoor Temperature in Cooling Mode {C}
VRFCoolCapFT, !- Cooling Capacity Ratio Modifier Function of Low Temperature Curve Name
VRFCoolCapFTBoundary, !- Cooling Capacity Ratio Boundary Curve Name
VRFCoolCapFTHi, !- Cooling Capacity Ratio Modifier Function of High Temperature Curve Name
VRFCoolEIRFT, !- Cooling Energy Input Ratio Modifier Function of Low Temperature Curve Name
VRFCoolEIRFTBoundary, !- Cooling Energy Input Ratio Boundary Curve Name
VRFCoolEIRFTHi, !- Cooling Energy Input Ratio Modifier Function of High Temperature Curve Name
CoolingEIRLowPLR, !- Cooling Energy Input Ratio Modifier Function of Low Part-Load Ratio Curve Name
CoolingEIRHiPLR, !- Cooling Energy Input Ratio Modifier Function of High Part-Load Ratio Curve Name
CoolingCombRatio, !- Cooling Combination Ratio Correction Factor Curve Name
VRFCPLFFPLR, !- Cooling Part-Load Fraction Correlation Curve Name
autosize, !- Gross Rated Heating Capacity {W}
, !- Rated Heating Capacity Sizing Ratio (W/W)
3.40909, !- Gross Rated Heating COP
-20, !- Minimum Outdoor Temperature in Heating Mode {C}
15.5, !- Maximum Outdoor Temperature in Heating Mode {C}
VRFHeatCapFT, !- Heating Capacity Ratio Modifier Function of Low Temperature Curve Name
VRFHeatCapFTBoundary, !- Heating Capacity Ratio Boundary Curve Name
VRFHeatCapFTHi, !- Heating Capacity Ratio Modifier Function of High Temperature Curve Name
VRFHeatEIRFT, !- Heating Energy Input Ratio Modifier Function of Low Temperature Curve Name
VRFHeatEIRFTBoundary, !- Heating Energy Input Ratio Boundary Curve Name
VRFHeatEIRFTHi, !- Heating Energy Input Ratio Modifier Function of High Temperature Curve Name
WetBulbTemperature, !- Heating Performance Curve Outdoor Temperature Type
HeatingEIRLowPLR, !- Heating Energy Input Ratio Modifier Function of Low Part-Load Ratio Curve Name
HeatingEIRHiPLR, !- Heating Energy Input Ratio Modifier Function of High Part-Load Ratio Curve Name
HeatingCombRatio, !- Heating Combination Ratio Correction Factor Curve Name
VRFCPLFFPLR, !- Heating Part-Load Fraction Correlation Curve Name
0.25, !- Minimum Heat Pump Part-Load Ratio
SPACE1-1, !- Zone Name for Master Thermostat Location
LoadPriority, !- Master Thermostat Priority Control Type
, !- Thermostat Priority Schedule Name
VRF Heat Pump TU List, !- Zone Terminal Unit List Name
No, !- Heat Pump Waste Heat Recovery
30, !- Equivalent Piping Length used for Piping Correction Factor in Cooling Mode {m}
10, !- Vertical Height used for Piping Correction Factor {m}
CoolingLengthCorrectionFactor, !- Piping Correction Factor for Length in Cooling Mode Curve Name
-0.000386, !- Piping Correction Factor for Height in Cooling Mode Coefficient
30, !- Equivalent Piping Length used for Piping Correction Factor in Heating Mode {m}
, !- Piping Correction Factor for Length in Heating Mode Curve Name
, !- Piping Correction Factor for Height in Heating Mode Coefficient
15, !- Crankcase Heater Power per Compressor {W}
3, !- Number of Compressors
0.33, !- Ratio of Compressor Size to Total Compressor Capacity
7, !- Maximum Outdoor Dry-bulb Temperature for Crankcase Heater {C}
Resistive, !- Defrost Strategy
Timed, !- Defrost Control
, !- Defrost Energy Input Ratio Modifier Function of Temperature Curve Name
, !- Defrost Time Period Fraction
autosize, !- Resistive Defrost Heater Capacity {W}
7, !- Maximum Outdoor Dry-bulb Temperature for Defrost Operation {C}
EvaporativelyCooled, !- Condenser Type
MyVRFOANode, !- Condenser Inlet Node Name
, !- Condenser Outlet Node Name
, !- Water Condenser Volume Flow Rate
, !- Evaporative Condenser Effectiveness {dimensionless}
autosize, !- Evaporative Condenser Air Flow Rate {m3/s}
autosize, !- Evaporative Condenser Pump Rated Power Consumption {W}
, !- Supply Water Storage Tank Name
200, !- Basin Heater Capacity {W/K}
, !- Basin Heater Set Point Temperature (C)
, !- Basin Heater Operating Schedule Name
, !- Fuel Type
, !- Minimum Outdoor Temperature in Heat Recovery Mode (C)
, !- Maximum Outdoor Temperature in Heat Recovery Mode (C)
, !- Heat Recovery Cooling Capacity Modifier Function of Temperature Curve Name
, !- Initial Heat Recovery Cooling Capacity Fraction
, !- Heat Recovery Cooling Capacity Time Constant (hr)
, !- Heat Recovery Cooling Energy Modifier Function of Temperature Curve Name
, !- Initial Heat Recovery Cooling Energy Fraction
, !- Heat Recovery Cooling Energy Time Constant (hr)
, !- Heat Recovery Heating Capacity Modifier Function of Temperature Curve Name
, !- Initial Heat Recovery Heating Capacity Fraction
, !- Heat Recovery Heating Capacity Time Constant (hr)
, !- Heat Recovery Heating Energy Modifier Function of Temperature Curve Name
, !- Initial Heat Recovery Heating Energy Fraction
; !- Heat Recovery Heating Energy Time Constant (hr)
This output field is the operating total cooling capacity
of the variable refrigerant flow heat pump in Watts. This
value is calculated for each HVAC system time step being
simulated, and the results are averaged for the time step
being reported. This value should match the sum of the
individual zone terminal unit output variables for Zone
VRF Air Terminal Total Cooling Rate.
This output field is the operating total heating capacity
of the variable refrigerant flow heat pump in Watts. The
capacity includes any degradation due to defrost mode. This
value is calculated for each HVAC system time step being
simulated, and the results are averaged for the time step
being reported. This value should match the sum of the
individual zone terminal unit output variables for Zone
VRF Air Terminal Total Heating Rate.
This output field is the cooling mode electricity
consumption rate of the variable refrigerant flow heat pump in
Watts. The consumption includes electricity used by the
compressor (including crankcase heater), and the condenser
fan. This value is calculated for each HVAC system time step
being simulated, and the results are averaged for the time
step being reported. The choice of an alternate fuel type (see
Fuel Type input) will result in a change in the output
variable name (e.g., Variable Refrigerant Flow Heat Pump
Cooling NaturalGas Consumption Rate).
This output field is the cooling mode electricity
consumption of the variable refrigerant flow heat pump in
Joules for the time period being reported. The consumption
includes electricity used by the compressor (including
crankcase heater), and the condenser fan. This value is
calculated for each HVAC system time step being simulated, and
the results are summed for the time step being reported. This
output is also added to a meter with Resource Type =
Electricity, End Use Key = Cooling, Group Key = System (Ref.
Output:Meter
objects). The choice of an alternate fuel type (see Fuel Type
input) will result in a change in the output variable name
(e.g., Variable Refrigerant Flow Heat Pump Cooling NaturalGas
Consumption). The resource type meter will also be modified to
reflect the chosen fuel type (e.g., Resource Type =
NaturalGas).
This output field is the heating mode electricity
consumption rate of the variable refrigerant flow heat pump in
Watts. The consumption includes electricity used by the
compressor (including crankcase heater), additional energy
required for defrost, and the condenser fan. This value is
calculated for each HVAC system time step being simulated, and
the results are averaged for the time step being reported. The
choice of an alternate fuel type (see Fuel Type input) will
result in a change in the output variable name (e.g., Variable
Refrigerant Flow Heat Pump Heating NaturalGas Consumption
Rate).
This output field is the heating mode electricity
consumption of the variable refrigerant flow heat pump in
Joules for the time period being reported. The consumption
includes electricity used by the compressor (including
crankcase heater), additional energy required for defrost, and
the condenser fan. This value is calculated for each HVAC
system time step being simulated, and the results are summed
for the time step being reported. This output is also added to
a meter with Resource Type = Electricity, End Use Key =
Heating, Group Key = System (Ref. Output:Meter
objects). The choice of an alternate fuel type (see Fuel Type
input) will result in a change in the output variable name
(e.g., Variable Refrigerant Flow Heat Pump Heating NaturalGas
Consumption). The resource type meter will also be modified to
reflect the chosen fuel type (e.g., Resource Type =
NaturalGas).
This is the operating cooling coefficient of performance
for the heat pump. This value is calculated using the ratio of
VRF Heat Pump Total Cooling Rate and Variable Refrigerant Flow
Heat Pump Cooling Electric Consumption Rate output variables.
Crankcase heater (usually 0 in cooling mode), evaporative
condenser water pump, and defrost (usually 0 in cooling mode)
consumption rate output variables are included in this
calculation. This value is specific to outdoor unit
performance in cooling mode, is calculated for each HVAC
system time step being simulated, and the results are averaged
for the time step being reported.
This is the operating heating coefficient of performance
for the heat pump. This value is calculated using the ratio of
VRF Heat Pump Total Heating Rate and Variable Refrigerant Flow
Heat Pump Heating Electric Consumption Rate output variables.
Crankcase heater, evaporative condenser water pump (usually 0
in heating mode), and defrost consumption rate output
variables are included in this calculation. This value is
specific to outdoor unit performance in heating mode, is
calculated for each HVAC system time step being simulated, and
the results are averaged for the time step being reported.
This is the operating coefficient of performance for the
heat pump. This value is calculated using the ratio of the
total terminal unit coil capacity (cooling plus heating and
accounts for piping losses) and total system electric
consumption rate (compressor, crankcase heater, evaporative
condenser water pump, defrost, and terminal unit parasitic
electric consumption rate). This output variable does not
include pump power for a water-cooled system. This value is
specific to overall system performance, is calculated for each
HVAC system time step being simulated, and the results are
averaged for the time step being reported.
This is the electricity consumption rate of the heat pump
defrost in Watts when the unit is in defrost mode (timed,
reverse-cycle). . The choice of an alternate fuel type (see
Fuel Type input) will result in a change in the output
variable name (e.g., Variable Refrigerant Flow Heat Pump
NaturalGas Defrost Consumption Rate).
This is the electricity consumption of the heat pump in
Joules for the time step being reported. This consumption is
applicable when the unit is in defrost mode (reverse-cycle or
resistive). This output is also added to a meter with Resource
Type = Electricity, End Use Key = Heating, Group Key = System
(Ref. Output:Meter
objects). The choice of an alternate fuel type (see Fuel Type
input) will result in a change in the output variable name
(e.g., Variable Refrigerant Flow Heat Pump NaturalGas Defrost
Consumption). The resource type meter will also be modified to
reflect the chosen fuel type (e.g., Resource Type =
NaturalGas).
This output field is the part-load ratio of the heat pump
condenser. Heat pump part-load ratio is defined as the total
coil load divided by the heat pump’s maximum available
capacity at the current operating conditions. This value is
calculated for each HVAC system time step being simulated, and
the results are averaged for the time step being reported.
This output field is the runtime fraction of the heat pump
condenser’s first stage compressor. Heat pump runtime fraction
is defined as the fraction of time the first stage compressor
is on during a given time period and includes cycling losses.
This value is calculated as the ratio of the VRF Heat Pump
Cycling Ratio and the output of the Cooling Part-Load Fraction
Correlation Curve object as the specific cycling ratio. This
value is calculated for each HVAC system time step being
simulated, and the results are averaged for the time step
being reported.
This output field is the cycling ratio of the heat pump
condenser’s first stage compressor. Heat pump cycling ratio is
defined as the fraction of time the first stage compressor is
on during a given time period. This value is calculated for
each HVAC system time step being simulated, and the results
are averaged for the time step being reported.
This output field is an integer representation of the
operating mode of the variable refrigerant flow heat pump. The
operating mode for cooling mode is indicated by a 1 and
heating mode is indicated by a 2. A value of 0 is reported if
the heat pump is off. This value is calculated for each HVAC
system time step being simulated, and the results are averaged
for the time step being reported.
VRF Heat
Pump Condenser Inlet Temperature [C][LINK]
This is the inlet air temperature entering the condenser
coil in degrees C. This value can represent the outdoor air
dry-bulb temperature, wet-bulb temperature, or somewhere in
between from the weather data being used, depending on the
value used in the input field “Evaporative Condenser
Effectiveness”. The temperature reported here is used in the
various modifier curves related to temperature (e.g., Total
Cooling Capacity Modifier Curve [function of temperature]).
(The use of the word Condenser here is taken from
cooling operation – the same device can also be an evaporator
during heating operation.)
VRF Heat
Pump Condenser Outlet Temperature [C][LINK]
This is the condenser coil outlet water temperature in
degrees C. This value is calculated for each HVAC system time
step being simulated, and the results are averaged for the
time step being reported. This value is only reported for
water-cooled systems. (The use of the word Condenser
here is taken from cooling operation – the same device can
also be an evaporator during heating operation.)
VRF Heat
Pump Condenser Mass Flow Rate [kg/s][LINK]
This is the condenser coil outlet water mass flow rate in
kilograms per second. This value is calculated for each HVAC
system time step being simulated, and the results are averaged
for the time step being reported. This value is only reported
for water-cooled systems. (The use of the word
Condenser here is taken from cooling operation – the
same device can also be an evaporator during heating
operation.)
VRF Heat
Pump Condenser Heat Transfer Rate [W][LINK]
This is the condenser coil heat transfer rate in Watts.
This value is calculated for each HVAC system time step being
simulated, and the results are averaged for the time step
being reported. This value is only reported for water-cooled
systems. (The use of the word Condenser here is taken
from cooling operation – the same device can also be an
evaporator during heating operation.)
VRF
Heat Pump Condenser Heat Transfer Energy [J][LINK]
This is the condenser coil heat transfer in Joules. This
value is calculated for each HVAC system time step being
simulated, and the results are summed for the time step being
reported. This value is only reported for water-cooled
systems. (The use of the word Condenser here is taken
from cooling operation – the same device can also be an
evaporator during heating operation.)
VRF
Heat Pump Maximum Capacity Cooling Rate [W][LINK]
This output field is the maximum available terminal unit
cooling capacity in Watts allowed for the current time step
being reported. If the terminal units request more capacity
than is actually available from the variable refrigerant flow
heat pump, the individual terminal units will be limited to
this value. A maximum limit of 1E+20 is reported when there is
sufficient capacity available to meet all requests from the
terminal units. This output variable easily identifies times
when the total terminal unit cooling load exceeds the heat
pump’s available cooling capacity.
VRF
Heat Pump Maximum Capacity Heating Rate [W][LINK]
This output field is the maximum available terminal unit
heating capacity in Watts allowed for the current time step
being reported. If the terminal units request more capacity
than is actually available from the variable refrigerant flow
heat pump, the individual terminal units will be limited to
this value. A maximum limit of 1E+20 is reported when there is
sufficient capacity available to meet all requests from the
terminal units. This output variable easily identifies times
when the total terminal unit heating load exceeds the heat
pump’s available heating capacity.
VRF
Heat Pump Terminal Unit Cooling Load Rate [W][LINK]
This output field is the sum of the terminal unit cooling
coil loads in Watts for the current time step being reported.
This value is derived directly from the cooling coils and
represents the total cooling load on the VRF system after
piping losses have been accounted for. The total cooling load
will be less than the variable refrigerant flow total cooling
capacity reported when piping losses are modeled (i.e., when
piping losses are < 1).
VRF
Heat Pump Terminal Unit Heating Load Rate [W][LINK]
This output field is the sum of the terminal unit heating
coil loads in Watts for the current time step being reported.
This value is derived directly from the heating coils and
represents the total heating load on the VRF system after
piping losses have been accounted for. The total heating load
will be less than the variable refrigerant flow total heating
capacity reported when piping losses are modeled (i.e., when
piping losses are < 1).
VRF
Heat Pump Crankcase Heater Electric Power [W][LINK]
This output field is the average electricity consumption
rate of the heat pump’s crankcase heaters in Watts for the
time step being reported.
VRF
Heat Pump Crankcase Heater Electric Energy [J][LINK]
This output field is the electricity consumption rate of
the heat pump’s crankcase heaters in Joules for the time step
being reported. This output is also added to a meter with
Resource Type = Electricity, End Use Key = Cooling, Group Key
= System (ref. Output:Meter
objects).
VRF
Heat Pump Evaporative Condenser Water Use Volume [m3][LINK]
This output is the amount of water used to evaporatively
cool the condenser coil inlet air, in cubic meters. This
output is also added to a meter with Resource Type = Water,
End Use Key = Cooling, Group Key = System (ref. Output:Meter
objects).
VRF
Heat Pump Evaporative Condenser Pump Electric Power [W][LINK]
This is the average electricity consumption rate of the
evaporative condenser water pump in Watts for the time step
being reported.
VRF
Heat Pump Evaporative Condenser Pump Electric Energy [J][LINK]
This is the electricity consumption rate of the evaporative
condenser water pump in Joules for the time step being
reported. This output is also added to a meter with Resource
Type = Electricity, End Use Key = Cooling, Group Key = System
(ref. Output:Meter
objects).
VRF Heat
Pump Basin Heater Electric Power [W][LINK]
This output is the electric consumption rate of the heat
pump’s basin heater (for evaporatively-cooled condenser type)
in Watts. This basin heater only operates when the variable
refrigerant flow heat pump’s compressor(s) is off and
therefore is reported as 0 anytime the compressor operates. If
the compressor is cycling (see VRF Heat Pump Cycling Ratio
output variable above), the basin heater electric power is
proportional to one minus the cycling ratio of the compressor
(i.e., the basin heater is on when the compressor is off).
VRF Heat
Pump Basin Heater Electric Energy [J][LINK]
This output is the electric consumption of the heat pump’s
basin heater (for evaporatively-cooled condenser type) in
Joules. This output is also added to a meter with Resource
Type = Electricity, End Use Key = Cooling, Group Key = System
(Ref. Output:Meter
objects).
VRF
Heat Pump Heat Recovery Status Change Multiplier [][LINK]
This output applies only when heat recovery is used and
represents the multiplier used to derate the capacity of the
system when transitioning from cooling or heating mode to heat
recovery mode. This value is 1 when derating does not apply
(i.e., the system has not recently changed modes to provide
heat recovery). Derating during a transition period is applied
according to the inputs for Heat Recovery Fraction and Heat
Recovery Time Constant. To turn transition derating off, set
Heat Recovery Fraction to 1. Refer to the engineering
reference document discussion on the variable refrigerant flow
heat pump model section for transition from cooling only mode
to heat recovery mode for a more detailed description.
The zone terminal unit list defines the names of the
terminal units connected to a single variable refrigerant flow
air-conditioning system. The zone terminal unit list is used
exclusively in the variable refrigerant flow (VRF) air
conditioner object (ref:
AirConditioner:VariableRefrigerantFlow). Up to 20 terminal
units may be connected to a single VRF outdoor condensing
unit. This list is extensible if additional indoor terminal
units are required. The name of this zone terminal unit list
object is then input into the corresponding variable
refrigerant flow air conditioner object. The following figure
demonstrates this concept.
This alpha field defines the name of the zone terminal unit
used in a variable refrigerant air conditioner. The zone
terminal unit must be connected to a zone using the ZoneHVAC:EquipmentConnections
object. The terminal unit air inlet node is the same name as a
zone exhaust node. The terminal unit air outlet node is the
same name as a zone inlet node. The IDD is supplied with 20
fields for this. The object is extensible and you can change
the IDD by adding more fields or, if you are using text editor
for your input file, just add to the list of names.
ZoneTerminalUnitList,
VRF Heat Pump TU List, !- Zone Terminal Unit List Name
TU3, !- Zone Terminal Unit Name 1
TU4, !- Zone Terminal Unit Name 2
TU1, !- Zone Terminal Unit Name 3
TU2, !- Zone Terminal Unit Name 4
TU5; !- Zone Terminal Unit Name 5
Group - Variable Refrigerant Flow Equipment[LINK]
AirConditioner:VariableRefrigerantFlow[LINK]
This model simulates a variable-refrigerant-flow (or variable-refrigerant-volume) air-conditioning system. This system type models direct-expansion cooling and/or heating coils configured in a zone terminal unit. For this system type, the zone terminal units are “connected” to a zone via the zone inlet and exhaust nodes. The zone terminal units are identified in a ZoneTerminalUnitList object. And finally, the name of the ZoneTerminalUnitList object is entered as an input to the AirConditioner:VariableRefrigerantFlow object. The Energyplus connection methodology is shown as dashed and greyed arrows in the figure below according to the following rules:
The zone inlet and zone exhaust node names are defined in a ZoneHVAC:EquipmentConnections object (bottom of figure).
A ZoneHVAC:TerminalUnit:VariableRefrigerantFlow object will identify these zone exhaust and zone inlet node names as the terminal unit’s air inlet and air outlet nodes, respectively.
All zone terminal units that are connected to the same AirConditioner: VariableRefrigerantFlow object are listed in a ZoneTerminalUnitList object.
The name of the ZoneTerminalUnitList object is an input to the AirConditioner: VariableRefrigerantFlow object.
The AirCondtiioner:VariableRefrigerantFlow object is not listed in an AirloopHVAC object and, therefore, can only be simulated if the terminal units are connected to the AirCondtiioner:VariableRefrigerantFlow object using the ZoneTerminalUnitList.
Secondary ZoneHVAC equipment objects may be used in the same zones as the terminal units for other purposes (e.g., code compliance)
The following schematic demonstrates these connection rules.
Energyplus object type and object name, and node name relationships are also shown in the following figure to aid in the assembly of this HVAC system type.
Inputs[LINK]
Field: Heat Pump Name[LINK]
This alpha field defines a unique user-assigned name for an instance of a variable refrigerant flow heat pump. Any reference to this heat pump will use this name. Since this object is not listed in an AirloopHVAC object, the most likely use of this name would be for reporting purposes.
Field: Availability Schedule Name[LINK]
This alpha field defines the name of the schedule (ref: Schedule) that denotes whether the heat pump operates during a given time period. A schedule value equal to 0 denotes that the heat pump must be off for that time period. A value other than 0 denotes that the heat pump is available to operate during that time period. This schedule may be used to completely disable the heat pump (and all of its terminal units) as required. If this field is blank, the unit is enabled the entire simulation.
Field: Gross Rated Total Cooling Capacity[LINK]
This numeric field defines the total cooling capacity (sensible + latent) of the heat pump at rated conditions in watts. The cooling capacity must be greater than 0 or set to autosize.
Field: Gross Rated Cooling COP[LINK]
This numeric field defines the cooling coefficient of performance at rated conditions. The cooling coefficient of performance includes compressor power and condenser fan power. This COP value does not account for impacts due to the supply air fan. The nominal heat pump cooling COP must be greater than 0. If this field is left blank, a default coefficient of performance of 3.3 is assumed.
Field: Minimum Outdoor Temperature in Cooling Mode[LINK]
This numeric field defines the minimum outdoor dry-bulb temperature allowed for cooling operation. Below this temperature, cooling is disabled. If this field is left blank, the default value is -6ºC.
Field: Maximum Outdoor Temperature in Cooling Mode[LINK]
This numeric field defines the maximum outdoor dry-bulb temperature allowed for cooling operation. Above this temperature, cooling is disabled. If this field is left blank, the default value is 43ºC.
Field: Cooling Capacity Ratio Modifier Function of Low Temperature Curve Name[LINK]
This alpha field defines the cooling capacity ratio modifier at low outdoor dry-bulb temperatures. This curve is a bi-quadratic equation using weighted average indoor wet-bulb temperature (i.e., the indoor terminal units weighted average inlet temperatures) and condenser entering air dry-bulb temperature as the independent variables. This performance curve can be used to describe the cooling capacity ratio at low outdoor temperatures (i.e., the following two curves are used) or can be used to describe the performance for all outdoor temperatures (i.e., the following two curves are not used). For this system type it is likely that all three of these performance curves will be required. See the Engineering Reference for more discussion on using this input field.
Field: Cooling Capacity Ratio Boundary Curve Name[LINK]
This alpha field defines the cooling capacity ratio boundary curve name. This curve is a linear, quadratic or cubic curve that defines a change in cooling capacity at a specific condenser entering air dry-bulb temperature as a function of indoor air wet-bulb temperature. This curve is used when the trend in cooling capacity changes dramatically as outdoor temperature changes. If the cooling capacity does not change dramatically with changes in outdoor conditions, this field may be left blank. See the Engineering Reference for more discussion on using this input field.
Field: Cooling Capacity Ratio Modifier Function of High Temperature Curve Name[LINK]
This alpha field defines the cooling capacity ratio modifier at high outdoor temperatures. This curve is a bi-quadratic equation using weighted average indoor wet-bulb temperature and condenser entering air dry-bulb temperature as the independent variables. This curve is used when the trend in cooling capacity changes dramatically as outdoor temperature changes. If the cooling capacity does not change dramatically with changes in outdoor conditions, this field may be left blank. See the Engineering Reference for more discussion on using this input field.
Field: Cooling Energy Input Ratio Modifier Function of Low Temperature Curve Name[LINK]
This alpha field defines the cooling energy input ratio modifier at low outdoor temperatures. This curve is a bi-quadratic equation with a weighted average indoor wet-bulb temperature and condenser entering air dry-bulb temperature as the independent variables. This performance curve can be used to describe the cooling energy input ratio at low outdoor temperatures (i.e., the following two curves are used) or can be used to describe the performance for all outdoor temperatures (i.e., the following two curves are not used). For this system type it is likely that all three of these performance curves will be required. See the Engineering Reference for more discussion on using this input field.
Field: Cooling Energy Input Ratio Boundary Name[LINK]
This alpha field defines the cooling energy input ratio boundary curve name. This curve is a linear, quadratic or cubic curve that defines a change in cooling energy at a specific condenser entering air dry-bulb temperature as a function of indoor air wet-bulb temperature. This curve is used when the trend in cooling energy changes dramatically as outdoor temperature changes. If the cooling energy does not change dramatically with changes in outdoor conditions, this field may be left blank. See the Engineering Reference for more discussion on using this input field.
Field: Cooling Energy Input Ratio Modifier Function of High Temperature Curve Name[LINK]
This alpha field defines the cooling energy input ratio modifier at high outdoor temperatures. This curve is a bi-quadratic equation with weighted average indoor wet-bulb temperature and condenser entering air dry-bulb temperature as the independent variables. This curve is used when the trend in cooling energy changes dramatically as outdoor temperature changes. If the cooling energy does not change dramatically with changes in outdoor conditions, this field may be left blank. See the Engineering Reference for more discussion on using this input field.
Field: Cooling Energy Input Ratio Modifier Function of Low Part-Load Ratio Curve Name[LINK]
This alpha field defines the cooling energy input ratio modifier (function of part-load ratio when PLR is less than or equal to 1) curve name. This curve is a linear, quadratic or cubic equation with cooling part-load ratio used as the independent variable. The cooling energy input ratio modifier curve is normalized to 1 at a part-load ratio of 1 and is used only when the operating part-load ratio is less than or equal to 1.
Field: Cooling Energy Input Ratio Modifier Function of HIgh Part-Load Ratio Curve Name[LINK]
This alpha field defines the cooling energy input ratio modifier (function of part-load ratio when PLR is greater than 1) curve name. This curve is a linear, quadratic or cubic equation with cooling part-load ratio used as the independent variable. The cooling energy input ratio modifier curve is normalized to 1 at a part-load ratio of 1 and is used only when the operating part-load ratio is greater than 1.
Field: Cooling Combination Ratio Correction Factor Curve Name[LINK]
This alpha field defines the cooling combination ratio (CR) correction factor curve name for combination ratios greater than or equal to 1. The combination ratio is defined as the total rated indoor terminal unit cooling capacity divided by this heat pump’s gross rated total cooling capacity. The curve is a linear, quadratic or cubic equation and uses the minimum value of x in the curve object to determine the maximum part-load ratio which is linearly proportional to capacity (i.e., the minimum value of x [CR] in the curve object must be ≥1). The output of this curve provides a multiplier (>1) which is applied to this heat pump’s Gross Rated Total Cooling Capacity. Between a combination ratio of 1 and the curve’s minimum value of x, the multiplier is linearly interpolated. For combination ratio’s less than 1 (i.e., the total indoor terminal unit capacity is less than this heat pump’s rated total capacity), capacity is directly proportional to part-load ratio and this curve will not be used.
Field: Cooling Part-Load Fraction Correlation Curve Name[LINK]
This alpha field defines the cooling part-load fraction correlation curve name. This curve is used to define the cycling losses when the condenser’s compressors cycle on and off. The compressor cycles when the cooling part-load ratio is less than the Minimum Heat Pump Part-Load Ratio specified later in this object’s inputs.
Field: Gross Rated Heating Capacity[LINK]
This numeric field defines the gross total heat pump heating capacity at rated conditions in watts. The nominal heat pump heating capacity must be greater than 0 or set to autosize.
Field: Rated Heating Capacity Sizing Ratio[LINK]
This numeric field defines the ratio of gross heating to gross cooling capacity. The model assumes that when used, this value will be greater than 1. A similar input is available in the ZoneHVAC:TerminalUnit:VariableRefrigerantFlow object. When the heating capacity is autosized, if this field is non-blank, this ratio is used to scale the heating capacity to the gross rated total cooling capacity regardless of the value entered in the terminal unit objects. When the heating capacity is not autosized, the gross rated heating capacity will be equal to the sum of the terminal unit heating coil size. If this field is blank and the terminal unit sizing ratio input is also blank, then the heating capacity sizing ratio is assumed to be 1. If this field is not blank and the heating capacity sizing ratio in the terminal unit object(s) is blank, then this ratio also applies to each heating coil. If this field is not blank and the heating capacity sizing ratio in the terminal units is also not blank, then the terminal unit heating coil capacity sizing ratio input applies to each heating coil.
Field: Gross Rated Heating COP[LINK]
This numeric field defines the heating coefficient of performance at rated conditions. The heating coefficient of performance includes compressor power and condenser fan power. This gross COP value does NOT account for the supply air fan. The nominal heat pump heating COP must be greater than 0. If this field is left blank, a coefficient of performance of 3.4 is assumed.
Field: Minimum Outdoor Temperature in Heating Mode[LINK]
This numeric field defines the minimum outdoor temperature allowed for heating operation. Below this temperature, heating is disabled. If this field is left blank, the default value is -20ºC.
Field: Maximum Outdoor Temperature in Heating Mode[LINK]
This numeric field defines the maximum outdoor temperature allowed for heating operation. Above this temperature, heating is disabled. If this field is left blank, the default value is 16ºC.
Field: Heating Capacity Ratio Modifier Function of Low Temperature Curve Name[LINK]
This alpha field defines the heating capacity ratio modifier at low temperature curve name. This curve is a bi-quadratic equation with a weighted average indoor dry-bulb temperature (i.e., the indoor terminal units weighted average inlet temperatures) and condenser entering air dry-bulb or wet-bulb temperature as the independent variables. Since manufacturers may provide performance data using either outdoor dry-bulb or wet-bulb temperatures, either of these temperature types may be used for heating performance curves as specified in the Heating Performance Curve Outdoor Temperature Type input field below. This performance curve can be used to describe the heating capacity ratio at low outdoor temperatures (i.e., the following two curves are used) or can be used to describe the performance for all outdoor temperatures (i.e., the following two curves are not used). For this system type it is likely that all three of these performance curves will be required. See the Engineering Reference for more discussion on using this input field.
Field: Heating Capacity Ratio Boundary Curve Name[LINK]
This alpha field defines the heating capacity ratio boundary curve name. This curve is a quadratic or cubic curve that defines a change in heating capacity at a specific condenser entering air dry-bulb or wet-bulb temperature as a function of indoor air dry-bulb temperature. Since manufacturers may provide performance data using either outdoor dry-bulb or wet-bulb temperatures, either of these temperature types may be used for heating performance curves as specified in the Heating Performance Curve Outdoor Temperature Type input field below. This curve is used when the trend in heating capacity changes dramatically as outdoor temperature changes. If the heating capacity does not change dramatically with changes in outdoor conditions, this field may be left blank.
Field: Heating Capacity Ratio Modifier Function of High Temperature Curve Name[LINK]
This alpha field defines the heating capacity ratio modifier at high temperature curve name. This curve is a bi-quadratic equation with a weighted average indoor dry-bulb temperature and condenser entering air dry-bulb or wet-bulb temperature as the independent variables. Since manufacturers may provide performance data using either outdoor dry-bulb or wet-bulb temperatures, either of these temperature types may be used for heating performance curves as specified in the Heating Performance Curve Outdoor Temperature Type input field below. This curve is used when the trend in heating capacity changes dramatically as outdoor temperature changes. If the heating capacity does not change dramatically with changes in outdoor conditions, this field may be left blank.
Field: Heating Energy Input Ratio Modifier Function of Low Temperature Curve Name[LINK]
This alpha field defines the heating energy input ratio modifier at low temperature curve name. This curve is a bi-quadratic equation with a weighted average indoor dry-bulb temperature and condenser entering air dry-bulb or wet-bulb temperature as the independent variables. Since manufacturers may provide performance data using either outdoor dry-bulb or wet-bulb temperatures, either of these temperature types may be used for heating performance curves as specified in the Heating Performance Curve Outdoor Temperature Type input field below. This performance curve can be used to describe the heating energy input ratio at low outdoor temperatures (i.e., the following two curves are used) or can be used to describe the performance for all outdoor temperatures (i.e., the following two curves are not used).
Field: Heating Energy Input Ratio Boundary Curve Name[LINK]
This alpha field defines the heating energy input ratio boundary curve name. This curve is a quadratic or cubic curve that defines a change in heating energy at a specific condenser entering air dry-bulb or wet-bulb temperature as a function of indoor air dry-bulb temperature. Since manufacturers may provide performance data using either outdoor dry-bulb or wet-bulb temperatures, either of these temperature types may be used for heating performance curves as specified in the Heating Performance Curve Outdoor Temperature Type input field below. This curve is used when the trend in heating energy changes dramatically as outdoor temperature changes. If the heating energy does not change dramatically with changes in outdoor conditions, this field may be left blank.
Field: Heating Energy Input Ratio Modifier Function of High Temperature Curve Name[LINK]
This alpha field defines the heating energy input ratio modifier at high temperature curve name. This curve is a bi-quadratic equation with a weighted average indoor dry-bulb temperature and condenser entering air dry-bulb or wet-bulb temperature as the independent variables. Since manufacturers may provide performance data using either outdoor dry-bulb or wet-bulb temperatures, either of these temperature types may be used for heating performance curves as specified in the Heating Performance Curve Outdoor Temperature Type input field below. This curve is used when the trend in heating energy changes dramatically as outdoor temperature changes. If the heating energy does not change dramatically with changes in outdoor conditions, this field may be left blank.
Field: Heating Performance Curve Outdoor Temperature Type[LINK]
This choice field defines the outdoor temperature type used for all performance curves. The valid choices are DryBulbTemperature and WetBulbTemperature. The default value is WetBulbTemperature. Manufacturers will typically provide heating performance data as a function of outdoor air wet-bulb temperatures. This means that the performance (e.g., capacity and energy input ratio) curves will use outdoor wet-bulb temperature as one of the independent variables. At times, manufacturers will only provide performance data as a function of outdoor dry-bulb temperatures. In this case, all performance curves shall be developed using outdoor dry-bulb temperature and this field shall be selected as DryBulbTemperature.
Field: Heating Energy Input Ratio Modifier Function of Low Part-Load Ratio Curve Name[LINK]
This alpha field defines the heating energy input ratio modifier (function of part-load ratio when PLR is less than or equal to 1) curve name. This curve is a linear, quadratic, or cubic equation with heating part-load ratio used as the independent variable. The heating energy input ratio modifier curve is normalized to 1 at a part-load ratio of 1 and is used only when the part-load ratio is less than or equal to 1.
Field: Heating Energy Input Ratio Modifier Function of High Part-Load Ratio Curve Name[LINK]
This alpha field defines the heating energy input ratio modifier (function of part-load ratio when PLR is greater than 1) curve name. This curve is a linear, quadratic, or cubic equation with heating part-load ratio used as the independent variable. The heating energy input ratio modifier curve is normalized to 1 at a part-load ratio of 1 and is used only when the part-load ratio is greater than 1.
Field: Heating Combination Ratio Correction Factor Curve Name[LINK]
This alpha field defines the heating combination ratio (CR) correction factor curve name for combination ratios greater than or equal to 1. The combination ratio is defined as the total rated indoor heating capacity divided by the rated heat pump heating capacity. The curve is either quadratic or cubic and uses the minimum value of x in the curve object to determine the maximum part-load ratio which is linearly proportional to capacity (i.e., the minimum value of x in the curve object must be ≥1). The output of this curve provides a multiplier (>1) which is applied to the Nominal Heat Pump Heating Capacity. Between a combination ratio of 1 and the curve’s minimum value of x, the multiplier is linearly interpolated. For combination ratio’s less than 1, capacity is directly proportional to part-load ratio and this curve will not be used. If this field is left blank, the Cooling Combination Ratio Correction factor will be used.
Field: Heating Part-Load Fraction Correlation Curve Name[LINK]
This alpha field defines the heating part-load fraction correlation curve name. This curve is used to define the cycling losses when the condenser’s compressors cycle on and off. The compressor cycles when the indoor to outdoor heating capacity ratio is less than the Minimum Heat Pump Part-Load Ratio specified in the following field.
Field: Minimum Heat Pump Part-Load Ratio[LINK]
This numeric field specifies the minimum operating part-load ratio (PLR) of the heat pump. When the heat pump operates at a PLR below this value, the heat pump’s compressor will cycle to meet the cooling or heating demand. Above this value, the heat pump’s compressor operates the entire time step to meet the cooling or heating demand. The minimum value for this field is 0. If this field is left blank, the default value is 0.15. When the heat pump compressor cycles, the previous field is used to determine cycling losses.
Field: Zone Name for Master Thermostat Location[LINK]
This alpha field defines the name of the zone where the “master” thermostat is located. When the heat pump is connected to multiple zone terminal units, one terminal unit must be selected as the master thermostat. The remaining thermostats are slaves and can operate only in the same mode as the master thermostat.
Field: Master Thermostat Priority Control Type[LINK]
This choice field determines the logic used to simulate the “master” thermostat. Valid choices are LoadPriority, ZonePriority, ThermostatOffsetPriority, MasterThermostatPriority, and Scheduled. The default value is MasterThermostatPriority. When LoadPriority is selected, the total zone load is used to choose the operating mode as either cooling or heating. When ZonePriority is selected, the number of zones requiring cooling or heating determines the operating mode. When ThermostatOffsetPriority is selected, the zone farthest from the thermostat set point determines the operating mode. The MasterThermostatPriority choice operates the system according the zone load where the master thermostat is located. The heat pump can also be scheduled to operate in either cooling or heating mode. For scheduled operation, a schedule name is entered in the following field.
Field: Thermostat Priority Schedule Name[LINK]
This alpha field identifies the schedule used when the previous field is set to Scheduled. Schedule values of 0 denote cooling mode while values of 1 denote heating mode. Any other values will force the system off.
Field: Zone Terminal Unit List Name[LINK]
This alpha field defines the name of the zone terminal unit list. The name specified here should match the name of a valid ZoneTerminalUnitList object. In addition, each name specified in this list should match the name of a valid ZoneHVAC:TerminalUnit: VariableRefrigerantFlow object. All terminal units connected to this heat pump must be listed in this ZoneTerminalUnitList object.
Field: Heat Pump Waste Heat Recovery[LINK]
This choice field defines the configuration of the heat pump refrigeration system. Valid choices are Yes and No. If Yes is selected, heat recovery is enabled and the heat pump can independently cool and heat different zones. If No is selected, the heat pump is only able to cool or heat for any given time step.
Field: Equivalent Piping Length used for Piping Correction Factor in Cooling Mode[LINK]
This numeric field defines the equivalent pipe length in meters between the farthest terminal unit and the heat pump condenser. This value includes the gas refrigerant line length (for both horizontal and vertical distances), fitting losses, pipe bends, and other connections that contribute to piping losses. This field is used to calculate the piping correction factor in cooling mode. This value defines the head losses due to the pipe length between the farthest terminal unit and the heat pump condenser and impacts the maximum available capacity in cooling mode.
Field: Vertical Height used for Piping Correction Factor[LINK]
This numeric field defines the vertical pipe height in meters between the highest or lowest terminal unit and the heat pump condenser. This value defines the gravitational losses due to a change in height between the highest (positive value), or lowest (negative value) terminal unit and the heat pump condenser. The distance specified here is applied to the piping correction factor calculation for both cooling and heating. If the distance between the highest terminal unit above the heat pump condenser is greater than the distance between the lowest terminal unit below the condenser enter the difference between the highest and lowest terminal units as a positive distance, otherwise enter this difference as a negative distance. Example: if the distance from the heat pump condenser to the highest terminal unit above the condenser is 10 m and the distance from the heat pump condenser to the lowest terminal unit below the condenser is -15 m, then enter a value of -5 m in this field. This head loss impacts the maximum available capacity in cooling mode.
Field: Piping Correction Factor for Length in Cooling Mode Curve Name[LINK]
This alpha field defines the linear, quadratic, or cubic curve name used to calculate the piping correction factor for length in cooling mode. Piping losses are a function of piping length. If sufficient piping loss information is available where piping losses are also a function of combination ratio (i.e., in addition to length), a biquadratic performance curve may be used.
Field: Piping Correction Factor for Height in Cooling Mode Coefficient[LINK]
This numeric field defines the coefficient used to calculate the piping correction factor for height in cooling mode.
Field: Equivalent Piping Length used for Piping Correction Factor in Heating Mode[LINK]
This numeric field defines the equivalent pipe length in meters between the farthest terminal unit and the heat pump condenser. This value includes the liquid refrigerant line length (for both horizontal and vertical distances), fitting losses, pipe bends, and other connections that contribute to piping losses. This field is used to calculate the piping correction factor in heating mode. This value defines the head losses due to the pipe length between the farthest terminal unit and the heat pump condenser and impacts the maximum available capacity in heating mode.
Field: Piping Correction Factor for Length in Heating Mode Curve Name[LINK]
This alpha field defines the linear, quadratic, or cubic curve name used to calculate the piping correction factor for length in heating mode. Piping losses are a function of piping length. If sufficient piping loss information is available where piping losses are also a function of combination ratio (i.e., in addition to length), a biquadratic performance curve may be used.
Field: Piping Correction Factor for Height in Heating Mode Coefficient[LINK]
This numeric field defines the coefficient used to calculate the piping correction factor for height in heating mode.
Field: Crankcase Heater Power per Compressor[LINK]
This numeric field defines the electrical power consumed by the crankcase heater in watts for each compressor. This crankcase heater power is consumed when the outdoor temperature is below the maximum outdoor dry-bulb temperature for crankcase heater operation. The minimum value for this field is 0. If this field is left blank, the default value is 33 watts. Crankcase heater electrical consumption is applied only when the compressor is off or is applied during the off cycle when the compressor is cycling below the Minimum Heat Pump Part-Load Ratio. This field is only used to calculate crankcase heater power and has no impact on heat pump performance.
Field: Number of Compressors[LINK]
This numeric field defines the number of compressors in the heat pump condensing unit and is used exclusively to determine the operating characteristics of the crankcase heater. For example, if the number of compressors is 3, one crankcase heater will operate when the heat pump condensing unit’s part-load ratio is less than or equal to 0.67 (when the ratio of compressor size to total compressor capacity input is 0.33) and the outdoor temperature is below the maximum outdoor temperature for crankcase heater operation. Similarly, two crankcase heaters will operate when the heat pump condensing unit’s PLR is less than or equal to 0.33 and the outdoor temperature is below the maximum outdoor temperature for crankcase heater operation. If the heat pump condensing unit is off, all 3 crankcase heaters will operate if the outdoor temperature is below the maximum outdoor temperature for crankcase heater operation. The minimum value for this field is 1. If this field is left blank, the default value is 2. This field is only used to calculate crankcase heater power and has no impact on heat pump performance.
Field: Ratio of Compressor Size to Total Compressor Capacity[LINK]
This numeric field defines the size of the first stage compressor to the total compressor capacity and is used exclusively for calculating crankcase heater energy. If this field and the previous field are left blank, the default value is 0.5. If this field is left blank and the previous field is not blank, the compressors are assumed to be equally sized. When the number of compressors is greater than 2, the 2nd stage compressor and all additional compressors are assumed to be equally sized. This field is only used to calculate crankcase heater power and has no impact on heat pump performance.
Field: Maximum Outdoor Dry-bulb Temperature for Crankcase Heater[LINK]
This numeric field defines the maximum outdoor temperature, in degrees Celsius, below which the crankcase heater will operate. If this field is left blank, the default value is 0C. This field is only used to calculate crankcase heater power and has no impact on heat pump performance.
Field: Defrost Strategy[LINK]
This alpha field has two choices: reverse-cycle or resistive. If the reverse-cycle strategy is selected, the heating cycle is reversed periodically to provide heat to melt frost accumulated on the outdoor coil. If a resistive defrost strategy is selected, the frost is melted using an electric resistance heater. If this input field is left blank, the default defrost strategy is reverse-cycle. Defrost can be disabled by entering a resistive defrost strategy using a timed defrost control, a 0 defrost time period fraction and a 0 resistive defrost heater capacity in the following inputs fields. This method is used when the Maximum Outdoor Dry-Bulb Temperature for Defrost Operation field value is greater than the expected minimum outdoor dry-bulb temperature simulated in the weather file.
Field: Defrost Control[LINK]
This alpha field has two choices: timed or on-demand. If timed control is selected, the defrost time period is calculated based on a fixed value of compressor runtime whether or not frost has actually accumulated. For timed defrost control, the fractional amount of time the unit is in defrost is entered in the input field “Defrost Time Period Fraction” described below. If on-demand defrost control is selected, the defrost time period is calculated based on outdoor weather (humidity ratio) conditions. Regardless of which defrost control is selected, defrost does not occur above the user specified outdoor temperature entered in the input field “Maximum Outdoor Dry-bulb Temperature for Defrost Operation” described above. If this input field is left blank, the default defrost control is timed.
Field: Defrost Energy Input Ratio Modifier Function of Temperature Curve Name[LINK]
This alpha field defines the name of a bi-quadratic performance curve (ref: Performance Curves) that parameterizes the variation of the energy input ratio (EIR) during reverse-cycle defrost periods as a function of the outdoor air dry-bulb temperature and the weighted average wet-bulb temperature of the air entering the indoor terminal units. The output of this curve is multiplied by the coil capacity, the fractional defrost time period and the runtime fraction of the heating coil to give the defrost power at the specific temperatures at which the indoor and outdoor coils are operating. The curve is normalized to a value of 1.0 at the rating point conditions.
Field: Defrost Time Period Fraction[LINK]
This numeric field defines the fraction of compressor runtime when the defrost cycle is active. For example, if the defrost cycle is active for 3.5 minutes for every 60 minutes of compressor runtime, then the user should enter 3.5/60 = 0.058333. The value for this input field must be greater than or equal to 0. If this input field is left blank, the default value is 0.058333.
Field: Resistive Defrost Heater Capacity[LINK]
This numeric field defines the capacity of the resistive defrost heating element in Watts. This input field is used only when the selected defrost strategy is ‘resistive’ (see input field “Defrost Strategy” above). The value for this input field must be greater than or equal to 0. If this input field is left blank, the default value is 0.
Field: Maximum Outdoor Dry-bulb Temperature for Defrost Operation[LINK]
This numeric field defines the outdoor air dry-bulb temperature above which outdoor coil defrosting is disabled. If this input field is left blank, the default value is 5 C. Defrost can be completely eliminated by selecting a temperature lower than the minimum expected outdoor temperature found in the weather file.
Field: Condenser Type[LINK]
This choice field defines the configuration of the heat pump condenser. Valid choices are AirCooled, EvaporativelyCooled, and WaterCooled.
Field: Condenser Inlet Node Name[LINK]
This alpha field defines the name of the condenser inlet air or water node. For Condenser type = AirCooled, this node name should also be listed in an OutdoorAir:Node or OutdoorAir:NodeList object. If this field is blank, the model assumes an air-cooled condenser and the weather file is used to define the outdoor conditions entering the condenser. If this field is not blank, the node conditions are used to define the outdoor air or inlet water conditions entering the condenser. A node name is typically entered here for air-cooled systems when conditions other than those found in the weather file should be used (ref. OutdoorAir:Node related to height above ground).
Field: Condenser Outlet Node Name[LINK]
This alpha field defines the name of the condenser outlet water node. This field is only used for water-cooled systems.
Field: Water Condenser Volume Flow Rate[LINK]
This numeric field defines the condenser water volume flow rate in cubic meters per second. This field is autosizable and only used for water-cooled systems.
Field: Evaporative Condenser Effectiveness[LINK]
The effectiveness of the evaporative condenser, which is used to determine the temperature of the air entering the outdoor condenser coil as follows:
\[Tcond\,inlet = \,\left( {Twb,o} \right)\,\, + \,\,\left( {1 - EvapCondEffectiveness} \right)\left( {Tdb,o\,\, - Twb,o} \right)\]
where
\(Tcond\,inlet\) = the temperature of the air entering the condenser coil (C)
\(Twb,o\) = the wet-bulb temperature of the outdoor air (C)
\(Tdb,o\) = the dry-bulb temperature of the outdoor air (C)
The resulting condenser inlet air temperature is used by the Cooling Capacity Ratio Modifier Curve (function of temperature) and the Cooling Energy Input Ratio Modifier Curve (function of temperature). The default value for this field is 0.9, although valid entries can range from 0.0 to 1.0. This field is not used when Condenser Type = Air Cooled and the simulation is calculating heating performance.
If the user wants to model an air-cooled condenser, they should simply specify AirCooled in the field Condenser Type. In this case, the Cooling Capacity Ratio Modifier Curve (function of temperature) and the Cooling Energy Input Ratio Modifier Curve (function of temperature) input fields for this object should reference performance curves that are a function of outdoor dry-bulb temperature.
If the user wishes to model an evaporative-cooled condenser AND they have performance curves that are a function of the wet-bulb temperature of air entering the condenser coil, then the user should specify Condenser Type = EvapCooled and the evaporative condenser effectiveness value should be entered as 1.0. In this case, the Cooling Capacity Ratio Modifier Curve (function of temperature) and the Cooling Energy Input Ratio Modifier Curve (function of temperature) input fields for this object should reference performance curves that are a function of the wet-bulb temperature of air entering the condenser coil.
If the user wishes to model an air-cooled condenser that has evaporative media placed in front of it to cool the air entering the condenser coil, then the user should specify Condenser Type = EvapCooled. The user must also enter the appropriate evaporative effectiveness for the media. In this case, the Cooling Capacity Ratio Modifier Curve (function of temperature) and the Cooling Energy Input Ratio Modifier Curve (function of temperature) input fields for this object should reference performance curves that are a function of outdoor dry-bulb temperature. Be aware that the evaporative media will significantly reduce the dry-bulb temperature of the air entering the condenser coil, so the Cooling Capacity and Cooling EIR Modifier Curves must be valid for the expected range of dry-bulb temperatures that will be entering the condenser coil.
Field: Evaporative Condenser Air Flow Rate[LINK]
The air volume flow rate, in m3 per second, entering the evaporative condenser. This value is used to calculate the amount of water used to evaporatively cool the condenser inlet air. The minimum value for this field must be greater than zero, and this input field is autosizable (equivalent to 0.000144 m3/s per watt of rated total cooling capacity [850 cfm/ton]). This field is not used when Condenser Type = AirCooled.
Field: Evaporative Condenser Pump Rated Power Consumption[LINK]
The rated power of the evaporative condenser water pump in Watts. This value is used to calculate the power required to pump the water used to evaporatively cool the condenser inlet air. The default value for this input field is zero, but it is autosizable (equivalent to 0.004266 W per watt [15 W/ton] of rated total cooling capacity). This field is not used when Condenser Type = AirCooled.
Field: Supply Water Storage Tank Name[LINK]
This alpha field defines the name of the water storage tank when an evaporatively-cooled condenser is used.
Field: Basin Heater Capacity[LINK]
This numeric field contains the capacity of the heat pump’s electric basin heater in watts per degree Kelvin. This field only applies for Condenser Type = EvaporativelyCooled. This field is used in conjunction with the Basin Heater Setpoint Temperature described in the following field. The basin heater electric power is equal to this field multiplied by the difference between the basin heater set point temperature and the outdoor dry-bulb temperature. The basin heater only operates when the heat pump compressor(s) is off, regardless of the basin heater schedule described below. The basin heater capacity must be greater than or equal to zero, with a default value of zero if this field is left blank.
Field: Basin Heater Setpoint Temperature[LINK]
This numeric field contains the set point temperature (˚C) for the basin heater described in the previous field. This field only applies for Condenser Type = EvaporativelyCooled. The basin heater is active when the outdoor air dry-bulb temperature falls below this setpoint temperature, as long as the heat pump is off. This set point temperature must be greater than or equal to 2˚C, and the default value is 2˚C if this field is left blank.
Field: Basin Heater Operating Schedule Name[LINK]
This alpha field contains the name of the basin heater operating schedule. This field only applies for Condenser Type = EvaporativelyCooled. The basin heater operating schedule is assumed to be an on/off schedule and the heater is available to operate any time the schedule value is greater than 0. The basin heater operates when scheduled on and the outdoor air dry-bulb temperature is below the set point temperature described in the previous field. If this field is left blank, the basin heater is available to operate throughout the simulation. Regardless of this schedule, the basin heater may only operate when the heat pump is off.
Field: Fuel Type[LINK]
This alpha field determines the type of fuel that this variable refrigerant flow system uses. This field has seven choices: Electricity, NaturalGas, PropaneGas, Diesel, Gasoline, FuelOil#1, FuelOil#2, OtherFuel1, and OtherFuel2. The default is Electricity. The use of alternate fuel types assumes an engine drives the variable speed compression system and also accounts for condenser air flow (i.e., a fan attached to the engine provides air flow through the outdoor condenser.
Field: Minimum Outdoor Temperature in Heat Recovery Mode[LINK]
This numeric field defines the minimum outdoor dry-bulb temperature allowed for heat recovery operation. Below this temperature, heat recovery is disabled. This input must be greater than the larger of the minimum outdoor temperature in cooling or heating mode. If this field is left blank, the default value is the higher of the Minimum Outdoor Temperature in Cooling Mode or Minimum Outdoor Temperature in Heating Mode inputs. This system may still operate in cooling or heating only mode when outdoor temperatures are below the minimum outdoor temperature in heat recovery mode. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes.
Field: Maximum Outdoor Temperature in Heat Recovery Mode[LINK]
This numeric field defines the maximum outdoor dry-bulb temperature allowed for heat recovery operation. Above this temperature, heat recovery is disabled. This input must be less than the smaller of the maximum outdoor temperature in cooling or heating mode. If this field is left blank, the default value is the lower of the Maximum Outdoor Temperature in Cooling Mode or Maximum Outdoor Temperature in Heating Mode inputs.. This system may still operate in cooling or heating only mode when outdoor temperatures are above the maximum outdoor temperature in heat recovery mode. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes.
Field: Heat Recovery Cooling Capacity Modifier Curve Name[LINK]
This alpha field defines the cooling capacity modifier when heat recovery mode is active. This modifier is used as a multiplier for available cooling capacity, and when in heat recovery mode, this modifier is usually less than 1. This curve is either a bi-quadratic equation using weighted average indoor temperature (i.e., the indoor terminal units weighted average inlet temperatures) and condenser entering air temperature as the independent variables or a cubic curve based on part-load ratio. This performance curve can be used to describe the cooling capacity modifier as either a constant (e.g., temperature or part-load ratio term coefficients are 0), a cooling modifier that varies with either indoor temperature and/or outdoor temperature, or part-load ratio (e.g., one or more temperature or part-load ratio term coefficients are 0), or varies with both indoor and outdoor temperatures or part-load ratio (e.g., all temperature or part-load ratio term coefficients are non-zero). If this field is left blank, and heat recovery operating mode is selected, the default constant modifier is 0.9. This modifier is applied only when heat recovery mode is active. To model a heat recovery system which has no degradation in cooling performance when heat recovery mode is active, or if the degradation is not constant at different operating conditions, a performance curve object must be used. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from cooling only mode to heat recovery mode.
Field: Initial Heat Recovery Cooling Capacity Fraction[LINK]
This numeric field defines the fraction of cooling capacity available when the system transitions from cooling only operation to simultaneous cooling and heating. It is common for the cooling capacity to decrease before the system recovers. If this field is left blank, a default value of 0.5 is used (50% reduction in cooling capacity at the start of heat recovery mode). The system will recovery according to the time constant entered in Heat Recovery Cooling Capacity Time Constant input field. If the transition period will not be modeled, this input field must be set to 1. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from cooling only mode to heat recovery mode. Refer to the engineering reference document discussion on the variable refrigerant flow heat pump model section for transition from cooling only mode to heat recovery mode for a more detailed description.
Field: Heat Recovery Cooling Capacity Time Constant[LINK]
This numeric field defines the cooling capacity time constant, in hours, used to model the time it takes for the system to change from cooling only operation to simultaneous cooling and heating. Total response time is defined as 5 time constants. If this field is left blank, a default value of 0.083 is used. If the transition period will not be modeled, the Initial Heat Recovery Cooling Capacity Fraction field must be set to 1. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from cooling only mode to heat recovery mode. Refer to the engineering reference document discussion on the variable refrigerant flow heat pump model section for transition from cooling only mode to heat recovery mode for a more detailed description.
Field: Heat Recovery Cooling Energy Modifier Curve Name[LINK]
This alpha field defines the cooling energy modifier when heat recovery mode is active. This modifier is used as a multiplier for operating cooling energy, and when in heat recovery mode, this modifier is usually greater than 1. This curve is a bi-quadratic equation using weighted average indoor temperature (i.e., the indoor terminal units weighted average inlet temperatures) and condenser entering air temperature as the independent variables. This performance curve can be used to describe the cooling energy modifier as either a constant (e.g., temperature term coefficients are 0), a cooling energy modifier that varies with indoor and/or outdoor temperatures (e.g., one or more temperature term coefficients are 0), or varies with both indoor and outdoor temperatures (e.g., temperature term coefficients are non-zero). If this field is left blank, and heat recovery operating mode is selected, the default constant modifier is 1.1. This modifier is applied only when heat recovery mode is active. To model a heat recovery system which has no degradation in cooling performance when heat recovery mode is active, or if the degradation is not constant at different operating conditions, a performance curve object must be used. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from cooling only mode to heat recovery mode.
Field: Initial Heat Recovery Cooling Energy Fraction[LINK]
This numeric field defines the fraction of cooling energy consumed when the system transitions from cooling only operation to simultaneous cooling and heating. It is common for the cooling energy to drop before the system recovers. If this field is left blank, a default value of 1 is used (no change in energy at the start of heat recovery mode). If the transition period will not be modeled, this input field must be set to 1. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from cooling only mode to heat recovery mode. Refer to the engineering reference document discussion on the variable refrigerant flow heat pump model section for transition from cooling only mode to heat recovery mode for a more detailed description.
Field: Heat Recovery Cooling Energy Time Constant[LINK]
This numeric field defines the cooling energy time constant, in hours, used to model the time it takes for the system to transition from cooling only operation to simultaneous cooling and heating. Total response time is defined as 5 time constants. If this field is left blank, a default value of 0.0 is used. If the transition period will not be modeled, the Initial Heat Recovery Cooling Energy Fraction field must be set to 1. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from cooling only mode to heat recovery mode. Refer to the engineering reference document discussion on the variable refrigerant flow heat pump model section for transition from cooling only mode to heat recovery mode for a more detailed description.
Field: Heat Recovery Heating Capacity Modifier Curve Name[LINK]
This alpha field defines the heating capacity modifier when heat recovery mode is active. This modifier is used as a multiplier for available heating capacity, and when in heat recovery mode, this modifier is usually less than 1. This curve is a bi-quadratic equation using weighted average indoor temperature (i.e., the indoor terminal units weighted average inlet temperatures) and condenser entering air temperature as the independent variables. This performance curve can be used to describe the heating capacity modifier as either a constant (e.g., temperature term coefficients are 0), a heating modifier that varies with indoor and/or outdoor temperatures (e.g., one or more temperature term coefficients are 0), or varies with both indoor and outdoor temperatures (e.g., temperature term coefficients are non-zero). If this field is left blank, and heat recovery operating mode is selected, the default constant modifier is 0.9. This modifier is applied only when heat recovery mode is active. To model a heat recovery system which has no degradation in heating performance when heat recovery mode is active, or if the degradation is not constant at different operating conditions, a performance curve object must be used. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from heating only mode to heat recovery mode.
Field: Initial Heat Recovery Heating Capacity Fraction[LINK]
This numeric field defines the fraction of heating capacity available when the system changes from heating only operation to simultaneous heating and cooling. It is common for the heating capacity to decrease before the system recovers. If this field is left blank, a default value of 0.5 is used (50% reduction in heating capacity at the start of heat recovery mode). The system will recovery according to the time constant entered in Heat Recovery Heating Capacity Time Constant input field. If the transition period will not be modeled, this input field must be set to 1. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from heating only mode to heat recovery mode. Refer to the engineering reference document discussion on the variable refrigerant flow heat pump model section for transition from cooling only mode to heat recovery mode for a more detailed description.
Field: Heat Recovery Heating Capacity Time Constant[LINK]
This numeric field defines the heating capacity time constant, in hours, used to model the time it takes for the system to transition from cooling only operation to simultaneous cooling and heating. Total response time is defined as 5 time constants. If this field is left blank, a default value of 0.083 is used. If the transition period will not be modeled, the Initial Heat Recovery Heating Capacity Fraction field must be set to 1. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from heating only mode to heat recovery mode. Refer to the engineering reference document discussion on the variable refrigerant flow heat pump model section for transition from cooling only mode to heat recovery mode for a more detailed description.
Field: Heat Recovery Heating Energy Modifier Curve Name[LINK]
This alpha field defines the heating energy modifier when heat recovery mode is active. This modifier is used as a multiplier for operating heating energy, and when in heat recovery mode, this modifier is usually greater than 1. This curve is a bi-quadratic equation using weighted average indoor temperature (i.e., the indoor terminal units weighted average inlet temperatures) and condenser entering air temperature as the independent variables. This performance curve can be used to describe the heating energy modifier as either a constant (e.g., temperature term coefficients are 0), a heating energy modifier that varies with indoor and/or outdoor temperatures (e.g., one or more temperature term coefficients are 0), or varies with both indoor and outdoor temperatures (e.g., temperature term coefficients are non-zero). If this field is left blank, and heat recovery operating mode is selected, the default constant modifier is 1.1. This modifier is applied only when heat recovery mode is active. To model a heat recovery system which has no degradation in heating performance when heat recovery mode is active, or if the degradation is not constant at different operating conditions, a performance curve object must be used. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from heating only mode to heat recovery mode.
Field: Initial Heat Recovery Heating Energy Fraction[LINK]
This numeric field defines the fraction of heating energy consumed when the system changes from heating only operation to simultaneous heating and cooling. It is common for the heating energy to decrease before the system recovers. If this field is left blank, a default value of 0.5 is used (50% reduction in heating energy at the start of heat recovery mode). The system will recovery according to the time constant entered in Heat Recovery Heating Energy Time Constant input field. If the transition period will not be modeled, this input field must be set to 1. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from heating only mode to heat recovery mode. Refer to the engineering reference document discussion on the variable refrigerant flow heat pump model section for transition from cooling only mode to heat recovery mode for a more detailed description.
Field: Heat Recovery Heating Energy Time Constant[LINK]
This numeric field defines the heating energy time constant, in hours, used to model the time it takes for the system to change from cooling only operation to simultaneous cooling and heating. Total response time is defined as 5 time constants. If this field is left blank, a default value of 0.0 is used. If the transition period will not be modeled, the Initial Heat Recovery Heating Energy Fraction field must be set to 1. This input is only used when Heat Pump Waste Heat Recovery is selected as Yes and the system changes from heating only mode to heat recovery mode. Refer to the engineering reference document discussion on the variable refrigerant flow heat pump model section for transition from cooling only mode to heat recovery mode for a more detailed description.
Following is an example input for a AirConditioner:VariableRefrigerantFlow system.
Outputs[LINK]
VRF Heat Pump Total Cooling Rate [W][LINK]
This output field is the operating total cooling capacity of the variable refrigerant flow heat pump in Watts. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported. This value should match the sum of the individual zone terminal unit output variables for Zone VRF Air Terminal Total Cooling Rate.
VRF Heat Pump Total Heating Rate [W][LINK]
This output field is the operating total heating capacity of the variable refrigerant flow heat pump in Watts. The capacity includes any degradation due to defrost mode. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported. This value should match the sum of the individual zone terminal unit output variables for Zone VRF Air Terminal Total Heating Rate.
VRF Heat Pump Cooling Electric Power [W][LINK]
This output field is the cooling mode electricity consumption rate of the variable refrigerant flow heat pump in Watts. The consumption includes electricity used by the compressor (including crankcase heater), and the condenser fan. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported. The choice of an alternate fuel type (see Fuel Type input) will result in a change in the output variable name (e.g., Variable Refrigerant Flow Heat Pump Cooling NaturalGas Consumption Rate).
VRF Heat Pump Cooling Electric Energy [J][LINK]
This output field is the cooling mode electricity consumption of the variable refrigerant flow heat pump in Joules for the time period being reported. The consumption includes electricity used by the compressor (including crankcase heater), and the condenser fan. This value is calculated for each HVAC system time step being simulated, and the results are summed for the time step being reported. This output is also added to a meter with Resource Type = Electricity, End Use Key = Cooling, Group Key = System (Ref. Output:Meter objects). The choice of an alternate fuel type (see Fuel Type input) will result in a change in the output variable name (e.g., Variable Refrigerant Flow Heat Pump Cooling NaturalGas Consumption). The resource type meter will also be modified to reflect the chosen fuel type (e.g., Resource Type = NaturalGas).
VRF Heat Pump Heating Electric Power [W][LINK]
This output field is the heating mode electricity consumption rate of the variable refrigerant flow heat pump in Watts. The consumption includes electricity used by the compressor (including crankcase heater), additional energy required for defrost, and the condenser fan. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported. The choice of an alternate fuel type (see Fuel Type input) will result in a change in the output variable name (e.g., Variable Refrigerant Flow Heat Pump Heating NaturalGas Consumption Rate).
VRF Heat Pump Heating Electric Energy [J][LINK]
This output field is the heating mode electricity consumption of the variable refrigerant flow heat pump in Joules for the time period being reported. The consumption includes electricity used by the compressor (including crankcase heater), additional energy required for defrost, and the condenser fan. This value is calculated for each HVAC system time step being simulated, and the results are summed for the time step being reported. This output is also added to a meter with Resource Type = Electricity, End Use Key = Heating, Group Key = System (Ref. Output:Meter objects). The choice of an alternate fuel type (see Fuel Type input) will result in a change in the output variable name (e.g., Variable Refrigerant Flow Heat Pump Heating NaturalGas Consumption). The resource type meter will also be modified to reflect the chosen fuel type (e.g., Resource Type = NaturalGas).
VRF Heat Pump Cooling COP[][LINK]
This is the operating cooling coefficient of performance for the heat pump. This value is calculated using the ratio of VRF Heat Pump Total Cooling Rate and Variable Refrigerant Flow Heat Pump Cooling Electric Consumption Rate output variables. Crankcase heater (usually 0 in cooling mode), evaporative condenser water pump, and defrost (usually 0 in cooling mode) consumption rate output variables are included in this calculation. This value is specific to outdoor unit performance in cooling mode, is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported.
VRF Heat Pump Heating COP[][LINK]
This is the operating heating coefficient of performance for the heat pump. This value is calculated using the ratio of VRF Heat Pump Total Heating Rate and Variable Refrigerant Flow Heat Pump Heating Electric Consumption Rate output variables. Crankcase heater, evaporative condenser water pump (usually 0 in heating mode), and defrost consumption rate output variables are included in this calculation. This value is specific to outdoor unit performance in heating mode, is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported.
VRF Heat Pump COP[][LINK]
This is the operating coefficient of performance for the heat pump. This value is calculated using the ratio of the total terminal unit coil capacity (cooling plus heating and accounts for piping losses) and total system electric consumption rate (compressor, crankcase heater, evaporative condenser water pump, defrost, and terminal unit parasitic electric consumption rate). This output variable does not include pump power for a water-cooled system. This value is specific to overall system performance, is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported.
VRF Heat Pump Defrost Electric Power [W][LINK]
This is the electricity consumption rate of the heat pump defrost in Watts when the unit is in defrost mode (timed, reverse-cycle). . The choice of an alternate fuel type (see Fuel Type input) will result in a change in the output variable name (e.g., Variable Refrigerant Flow Heat Pump NaturalGas Defrost Consumption Rate).
VRF Heat Pump Defrost Electric Energy [J][LINK]
This is the electricity consumption of the heat pump in Joules for the time step being reported. This consumption is applicable when the unit is in defrost mode (reverse-cycle or resistive). This output is also added to a meter with Resource Type = Electricity, End Use Key = Heating, Group Key = System (Ref. Output:Meter objects). The choice of an alternate fuel type (see Fuel Type input) will result in a change in the output variable name (e.g., Variable Refrigerant Flow Heat Pump NaturalGas Defrost Consumption). The resource type meter will also be modified to reflect the chosen fuel type (e.g., Resource Type = NaturalGas).
VRF Heat Pump Part Load Ratio[LINK]
This output field is the part-load ratio of the heat pump condenser. Heat pump part-load ratio is defined as the total coil load divided by the heat pump’s maximum available capacity at the current operating conditions. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported.
VRF Heat Pump Runtime Fraction [][LINK]
This output field is the runtime fraction of the heat pump condenser’s first stage compressor. Heat pump runtime fraction is defined as the fraction of time the first stage compressor is on during a given time period and includes cycling losses. This value is calculated as the ratio of the VRF Heat Pump Cycling Ratio and the output of the Cooling Part-Load Fraction Correlation Curve object as the specific cycling ratio. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported.
VRF Heat Pump Cycling Ratio [][LINK]
This output field is the cycling ratio of the heat pump condenser’s first stage compressor. Heat pump cycling ratio is defined as the fraction of time the first stage compressor is on during a given time period. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported.
VRF Heat Pump Operating Mode [][LINK]
This output field is an integer representation of the operating mode of the variable refrigerant flow heat pump. The operating mode for cooling mode is indicated by a 1 and heating mode is indicated by a 2. A value of 0 is reported if the heat pump is off. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported.
VRF Heat Pump Condenser Inlet Temperature [C][LINK]
This is the inlet air temperature entering the condenser coil in degrees C. This value can represent the outdoor air dry-bulb temperature, wet-bulb temperature, or somewhere in between from the weather data being used, depending on the value used in the input field “Evaporative Condenser Effectiveness”. The temperature reported here is used in the various modifier curves related to temperature (e.g., Total Cooling Capacity Modifier Curve [function of temperature]). (The use of the word Condenser here is taken from cooling operation – the same device can also be an evaporator during heating operation.)
VRF Heat Pump Condenser Outlet Temperature [C][LINK]
This is the condenser coil outlet water temperature in degrees C. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported. This value is only reported for water-cooled systems. (The use of the word Condenser here is taken from cooling operation – the same device can also be an evaporator during heating operation.)
VRF Heat Pump Condenser Mass Flow Rate [kg/s][LINK]
This is the condenser coil outlet water mass flow rate in kilograms per second. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported. This value is only reported for water-cooled systems. (The use of the word Condenser here is taken from cooling operation – the same device can also be an evaporator during heating operation.)
VRF Heat Pump Condenser Heat Transfer Rate [W][LINK]
This is the condenser coil heat transfer rate in Watts. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported. This value is only reported for water-cooled systems. (The use of the word Condenser here is taken from cooling operation – the same device can also be an evaporator during heating operation.)
VRF Heat Pump Condenser Heat Transfer Energy [J][LINK]
This is the condenser coil heat transfer in Joules. This value is calculated for each HVAC system time step being simulated, and the results are summed for the time step being reported. This value is only reported for water-cooled systems. (The use of the word Condenser here is taken from cooling operation – the same device can also be an evaporator during heating operation.)
VRF Heat Pump Maximum Capacity Cooling Rate [W][LINK]
This output field is the maximum available terminal unit cooling capacity in Watts allowed for the current time step being reported. If the terminal units request more capacity than is actually available from the variable refrigerant flow heat pump, the individual terminal units will be limited to this value. A maximum limit of 1E+20 is reported when there is sufficient capacity available to meet all requests from the terminal units. This output variable easily identifies times when the total terminal unit cooling load exceeds the heat pump’s available cooling capacity.
VRF Heat Pump Maximum Capacity Heating Rate [W][LINK]
This output field is the maximum available terminal unit heating capacity in Watts allowed for the current time step being reported. If the terminal units request more capacity than is actually available from the variable refrigerant flow heat pump, the individual terminal units will be limited to this value. A maximum limit of 1E+20 is reported when there is sufficient capacity available to meet all requests from the terminal units. This output variable easily identifies times when the total terminal unit heating load exceeds the heat pump’s available heating capacity.
VRF Heat Pump Terminal Unit Cooling Load Rate [W][LINK]
This output field is the sum of the terminal unit cooling coil loads in Watts for the current time step being reported. This value is derived directly from the cooling coils and represents the total cooling load on the VRF system after piping losses have been accounted for. The total cooling load will be less than the variable refrigerant flow total cooling capacity reported when piping losses are modeled (i.e., when piping losses are < 1).
VRF Heat Pump Terminal Unit Heating Load Rate [W][LINK]
This output field is the sum of the terminal unit heating coil loads in Watts for the current time step being reported. This value is derived directly from the heating coils and represents the total heating load on the VRF system after piping losses have been accounted for. The total heating load will be less than the variable refrigerant flow total heating capacity reported when piping losses are modeled (i.e., when piping losses are < 1).
VRF Heat Pump Crankcase Heater Electric Power [W][LINK]
This output field is the average electricity consumption rate of the heat pump’s crankcase heaters in Watts for the time step being reported.
VRF Heat Pump Crankcase Heater Electric Energy [J][LINK]
This output field is the electricity consumption rate of the heat pump’s crankcase heaters in Joules for the time step being reported. This output is also added to a meter with Resource Type = Electricity, End Use Key = Cooling, Group Key = System (ref. Output:Meter objects).
VRF Heat Pump Evaporative Condenser Water Use Volume [m3][LINK]
This output is the amount of water used to evaporatively cool the condenser coil inlet air, in cubic meters. This output is also added to a meter with Resource Type = Water, End Use Key = Cooling, Group Key = System (ref. Output:Meter objects).
VRF Heat Pump Evaporative Condenser Pump Electric Power [W][LINK]
This is the average electricity consumption rate of the evaporative condenser water pump in Watts for the time step being reported.
VRF Heat Pump Evaporative Condenser Pump Electric Energy [J][LINK]
This is the electricity consumption rate of the evaporative condenser water pump in Joules for the time step being reported. This output is also added to a meter with Resource Type = Electricity, End Use Key = Cooling, Group Key = System (ref. Output:Meter objects).
VRF Heat Pump Basin Heater Electric Power [W][LINK]
This output is the electric consumption rate of the heat pump’s basin heater (for evaporatively-cooled condenser type) in Watts. This basin heater only operates when the variable refrigerant flow heat pump’s compressor(s) is off and therefore is reported as 0 anytime the compressor operates. If the compressor is cycling (see VRF Heat Pump Cycling Ratio output variable above), the basin heater electric power is proportional to one minus the cycling ratio of the compressor (i.e., the basin heater is on when the compressor is off).
VRF Heat Pump Basin Heater Electric Energy [J][LINK]
This output is the electric consumption of the heat pump’s basin heater (for evaporatively-cooled condenser type) in Joules. This output is also added to a meter with Resource Type = Electricity, End Use Key = Cooling, Group Key = System (Ref. Output:Meter objects).
VRF Heat Pump Heat Recovery Status Change Multiplier [][LINK]
This output applies only when heat recovery is used and represents the multiplier used to derate the capacity of the system when transitioning from cooling or heating mode to heat recovery mode. This value is 1 when derating does not apply (i.e., the system has not recently changed modes to provide heat recovery). Derating during a transition period is applied according to the inputs for Heat Recovery Fraction and Heat Recovery Time Constant. To turn transition derating off, set Heat Recovery Fraction to 1. Refer to the engineering reference document discussion on the variable refrigerant flow heat pump model section for transition from cooling only mode to heat recovery mode for a more detailed description.
ZoneTerminalUnitList[LINK]
The zone terminal unit list defines the names of the terminal units connected to a single variable refrigerant flow air-conditioning system. The zone terminal unit list is used exclusively in the variable refrigerant flow (VRF) air conditioner object (ref: AirConditioner:VariableRefrigerantFlow). Up to 20 terminal units may be connected to a single VRF outdoor condensing unit. This list is extensible if additional indoor terminal units are required. The name of this zone terminal unit list object is then input into the corresponding variable refrigerant flow air conditioner object. The following figure demonstrates this concept.
Inputs[LINK]
Field: Zone Terminal List Name[LINK]
This alpha field specifies the name of the zone terminal unit list. This name must be specified in the AirConditioner:VariableRefrigerantFlow object.
Field: Zone Terminal Unit Name [LINK]
This alpha field defines the name of the zone terminal unit used in a variable refrigerant air conditioner. The zone terminal unit must be connected to a zone using the ZoneHVAC:EquipmentConnections object. The terminal unit air inlet node is the same name as a zone exhaust node. The terminal unit air outlet node is the same name as a zone inlet node. The IDD is supplied with 20 fields for this. The object is extensible and you can change the IDD by adding more fields or, if you are using text editor for your input file, just add to the list of names.
Following is an example input for a ZoneTerminalUnitList object.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.