Group – Non-Zone
Equipment[LINK]
The non-zone equipment group consists of plant objects that
connect to the demand side of the plant loop but are not
associated with a a specific Zone
(and do not have their own group). There is currently one
non-zone equipment object called LoadProfile:Plant.
This object places a scheduled demand load on the plant.
Non-zone equipment allows the option of performing a
plant-only EnergyPlus simulation, i.e. without any zones. This
can be useful for comparing the performance of various plant
configurations or components without the added complexity of a
full building description.
LoadProfile:Plant[LINK]
The LoadProfile:Plant
object is used to simulate a scheduled demand profile. This
can be useful when the building loads are already known.
Demanded load and flow rate are schedules specified in the
object definition. The load profile can specify heating and
cooling loads. Cooling loads are entered as negative numbers.
The actual load met is dependent on the performance of the
supply loop components.
The LoadProfile:Plant
object must be connected on the demand side of the plant loop.
It should be located on a Branch
with its control type set to “Active.” If desired, multiple LoadProfile:Plant
objects can be combined in series and/or parallel.
The unique name of the LoadProfile:Plant
object.
Field: Inlet Node Name[LINK]
The name of the inlet node connection to the plant
loop.
This node should be on the demand side.
Field: Outlet Node Name[LINK]
The name of the outlet node connection to the plant
loop.
Field: Load Schedule
Name[LINK]
Reference to the schedule object specifying the load
profile [W].
Field: Peak Flow Rate[LINK]
The peak demanded water flow rate [m3/s]. This
value is multiplied by the flow rate fraction schedule values
(below) to determine the actual volumetric flow rate.
Field: Flow
Rate Fraction Schedule Name[LINK]
Reference to the schedule object specifying the flow rate
fraction relative to the value in the field Peak Flow Rate
(above).
An example of this object follows.
LoadProfile:Plant,
Load Profile 1, !- Name
Demand Load Profile 1 Inlet Node, !- Inlet Node Name
Demand Load Profile 1 Outlet Node, !- Outlet Node Name
Load Profile 1 Load Schedule, !- Load Schedule Name {W}
0.003, !- Peak Flow Rate {m3/s}
Load Profile 1 Flow Frac Schedule; !- Flow Rate Fraction Schedule Name
The following output variables and meters are reported for
the LoadProfile:Plant
object:
HVAC,Average,Plant Load Profile Mass Flow Rate [kg/s]
HVAC,Average,Plant Load Profile Heat Transfer Rate [W]
HVAC,Sum,Plant Load Profile Heat Transfer Energy [J]
HVAC,Sum,Plant Load Profile Heating Energy [J]
HVAC,Sum,Plant Load Profile Cooling Energy [J]
Plant Load
Profile Mass Flow Rate [kg/s][LINK]
This is the mass flow of the fluid passing through the load
profile object, in kg/s.
Plant Load
Profile Heat Transfer Rate [W][LINK]
Plant Load
Profile Heat Transfer Energy [J][LINK]
These report the overall heat transfer rate and energy for
the load profile object, in Watts or Joules.
Plant
Load Profile Cooling Energy [J]Plant Load Profile Heating
Energy [J][LINK]
These report the overall cooling or heating energy that the
load profile object places on the plant loop, in Joules.
The inlet and outlet node temperatures and mass flow rates
can be monitored using the system node output variables:
HVAC,Average,System Node Temperature [C]
HVAC,Average,System Node Mass Flow Rate [kg/s]
Group – Non-Zone Equipment[LINK]
The non-zone equipment group consists of plant objects that connect to the demand side of the plant loop but are not associated with a a specific Zone (and do not have their own group). There is currently one non-zone equipment object called LoadProfile:Plant. This object places a scheduled demand load on the plant.
Non-zone equipment allows the option of performing a plant-only EnergyPlus simulation, i.e. without any zones. This can be useful for comparing the performance of various plant configurations or components without the added complexity of a full building description.
LoadProfile:Plant[LINK]
The LoadProfile:Plant object is used to simulate a scheduled demand profile. This can be useful when the building loads are already known. Demanded load and flow rate are schedules specified in the object definition. The load profile can specify heating and cooling loads. Cooling loads are entered as negative numbers. The actual load met is dependent on the performance of the supply loop components.
The LoadProfile:Plant object must be connected on the demand side of the plant loop. It should be located on a Branch with its control type set to “Active.” If desired, multiple LoadProfile:Plant objects can be combined in series and/or parallel.
Inputs[LINK]
Field: Name[LINK]
The unique name of the LoadProfile:Plant object.
Field: Inlet Node Name[LINK]
The name of the inlet node connection to the plant loop.
This node should be on the demand side.
Field: Outlet Node Name[LINK]
The name of the outlet node connection to the plant loop.
Field: Load Schedule Name[LINK]
Reference to the schedule object specifying the load profile [W].
Field: Peak Flow Rate[LINK]
The peak demanded water flow rate [m3/s]. This value is multiplied by the flow rate fraction schedule values (below) to determine the actual volumetric flow rate.
Field: Flow Rate Fraction Schedule Name[LINK]
Reference to the schedule object specifying the flow rate fraction relative to the value in the field Peak Flow Rate (above).
An example of this object follows.
Outputs[LINK]
The following output variables and meters are reported for the LoadProfile:Plant object:
Plant Load Profile Mass Flow Rate [kg/s][LINK]
This is the mass flow of the fluid passing through the load profile object, in kg/s.
Plant Load Profile Heat Transfer Rate [W][LINK]
Plant Load Profile Heat Transfer Energy [J][LINK]
These report the overall heat transfer rate and energy for the load profile object, in Watts or Joules.
Plant Load Profile Cooling Energy [J]Plant Load Profile Heating Energy [J][LINK]
These report the overall cooling or heating energy that the load profile object places on the plant loop, in Joules.
The inlet and outlet node temperatures and mass flow rates can be monitored using the system node output variables:
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.