Group - Operational
Faults[LINK]
Introduction
to Operational Faults Modeling[LINK]
Most of the buildings, either new or old, have operational
faults in the sensors, controllers, meters, equipment and
systems. Being able to model and simulate these faults and
their impact on energy performance of buildings is crucial to
improve accuracy of building simulations and to support the
retrofit of buildings.
To date, the main practitioner use of EnergyPlus has been
for new construction design. With the new high priority
attached by USDOE to retrofit and improved operation of
existing buildings, there is a need to extend the capabilities
of EnergyPlus to model existing buildings, including faulty
operation:
Retrofit analysis: starts with calibrated simulation; the
ability to estimate the severity of common faults is expected
to improve the accuracy and transparency of the calibrated
model and hence the increase accuracy of the analysis of
different retrofit measures.
Commissioning providers can use the fault models to
demonstrate the saving to be expected from fixing faults found
in retro-commissioning
Support for building operation by using the calibrated
model, including unfixed faults, as a real-time reference
model to detect, and verify the diagnosis of, newly occurring
faults.
The users in these cases are practitioners, not power
users, so it is needed to implement the fault models using
conventional EnergyPlus objects rather than the EMS, which, in
any case, could only be used to model limited types of
faults.
Operational Fault
Objects[LINK]
EnergyPlus contains a number of objects to model
operational faults of sensors, meters, equipment and systems.
The current implementation allows the modeling of the
following fault types: (1) sensor faults with air economizers,
(2) thermostat/humidistat offset faults, and (3) heating and
cooling coil fouling faults.
The objects used by EnergyPlus to model the faults are as
follows:
- FaultModel:TemperatureSensorOffset:OutdoorAir
- FaultModel:HumiditySensorOffset:OutdoorAir
- FaultModel:EnthalpySensorOffset:OutdoorAir
- FaultModel:TemperatureSensorOffset:ReturnAir
- FaultModel:EnthalpySensorOffset:ReturnAir
- FaultModel:Fouling:Coil
- FaultModel:ThermostatOffset
- FaultModel:HumidistatOffset
FaultModel:TemperatureSensorOffset:OutdoorAir[LINK]
This object defines the offset of an outdoor air dry-bulb
temperature sensor that is used to determine applicability of
an air economizer.
This is the user-defined name of the fault.
Field: Availability
Schedule Name[LINK]
This field provides the name of a schedule that will
determine if this fault is applicable. When a fault is not
applicable it is not modeled in the simulations. When it is
applicable, then a user-defined sensor offset and a severity
schedule will be applied. This schedule should be set to “1.0”
when a fault is applicable and “0.0” when it is not. If this
field is blank, the schedule has values of 1 for all time
periods.
Field: Severity Schedule
Name[LINK]
This field provides the name of a schedule that represents
severity of a fault. This is used as a multiplier to the
user-defined temperature offset. This schedule should be set
to a non-zero value when a fault is applicable and “0.0” when
it is not. If this field is blank, the schedule has values of
1 for all time periods.
Field: Controller Object
Type[LINK]
This field defines the controller object type that this
fault is associated with. Choices are from a list of
applicable controller types. Current implementation supports
air economizer - the choice is Controller:OutdoorAir.
Field: Controller Object
Name[LINK]
This field defines the name of the controller object
associated with the fault. It should be one of the objects
with the defined types.
Field: Temperature
Sensor Offset[LINK]
This field defines the offset of the temperature sensor. A
positive value means the sensor reads a temperature that is
higher than the real value. A negative value means the sensor
reads a temperature that is lower than the real value. A “0.0”
value means no offset. Default is 0.0. The units are in
degrees Celsius.
FaultModel:HumiditySensorOffset:OutdoorAir[LINK]
This object defines the offset of an outdoor air humidity
sensor that is used to determine applicability of an air
economizer.
This is the user-defined name of the fault.
Field:
Availability Schedule Name[LINK]
This field provides the name of a schedule that will
determine if this fault is applicable. When a fault is not
applicable it is not modeled in the simulations. When it is
applicable, then a user-defined sensor offset and a severity
schedule will be applied. This schedule should be set to “1.0”
when a fault is applicable and “0.0” when it is not. If this
field is blank, the schedule has values of 1 for all time
periods.
Field: Severity
Schedule Name[LINK]
This field provides the name of a schedule that represents
severity of a fault. This is used as a multiplier to the
user-defined temperature offset. This schedule should be set
to a non-zero value when a fault is applicable and “0.0” when
it is not. If this field is blank, the schedule has values of
1 for all time periods.
Field: Controller
Object Type[LINK]
This field defines the controller object type that this
fault is associated with. Choices are from a list of
applicable controller types. Current implementation supports
air economizer - the choice is Controller:OutdoorAir.
Field: Controller
Object Name[LINK]
This field defines the name of the controller object
associated with the fault. It should be one of the objects
with the defined types.
Field: Humidity Sensor
Offset[LINK]
This field defines the offset of the humidity ratio sensor.
A positive value means the sensor reads a humidity ratio that
is higher than the real value. A negative value means the
sensor reads a humidity ratio that is lower than the real
value. A “0.0” value means no offset. Default is 0.0. The
units are in kgWater/kgDryAir.
FaultModel:EnthalpySensorOffset:OutdoorAir[LINK]
This object defines the offset of an outdoor enthalpy
sensor that is used to determine applicability of an air
economizer.
This is the user-defined name of the fault.
Field:
Availability Schedule Name[LINK]
This field provides the name of a schedule that will
determine if this fault is applicable. When a fault is not
applicable it is not modeled in the simulations. When it is
applicable, then a user-defined sensor offset and a severity
schedule will be applied. This schedule should be set to “1.0”
when a fault is applicable and “0.0” when it is not. If this
field is blank, the schedule has values of 1 for all time
periods.
Field: Severity
Schedule Name[LINK]
This field provides the name of a schedule that represents
severity of a fault. This is used as a multiplier to the
user-defined temperature offset. This schedule should be set
to a non-zero value when a fault is applicable and “0.0” when
it is not. If this field is blank, the schedule has values of
1 for all time periods.
Field: Controller
Object Type[LINK]
This field defines the controller object type that this
fault is associated with. Choices are from a list of
applicable controller types. Current implementation supports
air economizer - the choice is Controller:OutdoorAir.
Field: Controller
Object Name[LINK]
This field defines the name of the controller object
associated with the fault. It should be one of the objects
with the defined types.
Field: Enthalpy Sensor
Offset[LINK]
This field defines the offset of the enthalpy sensor. A
positive value means the sensor reads an enthalpy that is
higher than the real value. A negative value means the sensor
reads an enthalpy that is lower than the real value. A “0.0”
value means no offset. Default is 0.0. The units are in
J/kg.
FaultModel:TemperatureSensorOffset:ReturnAir[LINK]
This object defines the offset of a return air dry-bulb
temperature sensor that is used to determine applicability of
an air economizer.
This is the user-defined name of the fault.
Field:
Availability Schedule Name[LINK]
This field provides the name of a schedule that will
determine if this fault is applicable. When a fault is not
applicable it is not modeled in the simulations. When it is
applicable, then a user-defined sensor offset and a severity
schedule will be applied. This schedule should be set to “1.0”
when a fault is applicable and “0.0” when it is not. If this
field is blank, the schedule has values of 1 for all time
periods.
Field: Severity
Schedule Name[LINK]
This field provides the name of a schedule that represents
severity of a fault. This is used as a multiplier to the
user-defined temperature offset. This schedule should be set
to a non-zero value when a fault is applicable and “0.0” when
it is not. If this field is blank, the schedule has values of
1 for all time periods.
Field: Controller
Object Type[LINK]
This field defines the controller object type that this
fault is associated with. Choices are from a list of
applicable controller types. Current implementation supports
air economizer - the choice is Controller:OutdoorAir.
Field: Controller
Object Name[LINK]
This field defines the name of the controller object
associated with the fault. It should be one of the objects
with the defined types.
Field: Temperature
Sensor Offset[LINK]
This field defines the offset of the temperature sensor. A
positive value means the sensor reads a temperature that is
higher than the real value. A negative value means the sensor
reads a temperature that is lower than the real value. A “0.0”
value means no offset. Default is 0.0. The units are in
degrees Celsius.
FaultModel:EnthalpySensorOffset:ReturnAir[LINK]
This object defines the offset of a return air enthalpy
sensor that is used to determine applicability of an air
economizer.
This is the user-defined name of the fault.
Field:
Availability Schedule Name[LINK]
This field provides the name of a schedule that will
determine if this fault is applicable. When a fault is not
applicable it is not modeled in the simulations. When it is
applicable, then a user-defined sensor offset and a severity
schedule will be applied. This schedule should be set to “1.0”
when a fault is applicable and “0.0” when it is not. If this
field is blank, the schedule has values of 1 for all time
periods.
Field: Severity
Schedule Name[LINK]
This field provides the name of a schedule that represents
severity of a fault. This is used as a multiplier to the
user-defined temperature offset. This schedule should be set
to a non-zero value when a fault is applicable and “0.0” when
it is not. If this field is blank, the schedule has values of
1 for all time periods.
Field: Controller
Object Type[LINK]
This field defines the controller object type that this
fault is associated with. Choices are from a list of
applicable controller types. Current implementation supports
air economizer - the choice is Controller:OutdoorAir.
Field: Controller
Object Name[LINK]
This field defines the name of the controller object
associated with the fault. It should be one of the objects
with the defined types.
Field: Enthalpy Sensor
Offset[LINK]
This field defines the offset of the enthalpy sensor. A
positive value means the sensor reads an enthalpy that is
higher than the real value. A negative value means the sensor
reads an enthalpy that is lower than the real value. A “0.0”
value means no offset. Default is 0.0. The units are in
J/kg.
FaultModel:Fouling:Coil[LINK]
This object defines the fouling for a simple water cooling
coil or simple water heating coil.
This is the user-defined name of the fault.
Field: Coil Name[LINK]
This field defines the name of the simple cooling coil or
simple heating coil that has the fouling fault.
Field:
Availability Schedule Name[LINK]
This field provides the name of a schedule that will
determine if this fault is applicable. When a fault is not
applicable it is not modeled in the simulations. When it is
applicable, then user-defined fouling and a severity schedule
will be applied. This schedule should be set to “1.0” when a
fault is applicable and “0.0” when it is not. If this field is
blank, the schedule has values of 1 for all time periods
Field: Severity
Schedule Name[LINK]
This field provides the name of a schedule that represents
severity of a fault. This is used as a multiplier to the
user-defined fouling. If this field is blank, the schedule has
values of 1 (no changes to fouling) for all time periods.
There are two methods to input the fouling,
i.e. FouledUARated and FoulingFactor. User chooses the
appropriate method to determine the coil fouling.
Field: UAFouled[LINK]
This is the overall coil UA value including the coil
fouling when the “FouledUARated” method is used. The unit is
W/K.
Field: Water Side
Fouling Factor[LINK]
The following four fields specify the required inputs when
the “FoulingFactor” method is used. This field defines the
fouling factor for the water side. The units are in
m2-K/W.
Field: Air Side Fouling
Factor[LINK]
This field defines the fouling factor for the air side. The
units are in m2-K/W.
Field: Outside Coil
Surface Area[LINK]
This field defines outside surface area of the cooling or
heating coil. The units are in m2.
Field:
Inside to Outside Coil Surface Area Ratio[LINK]
This field specifies the inside to outside surface area
ratio of the cooling or heating coil.
IDF examples:
! example faults for an air economizer
Schedule:Compact,
OATSeveritySch, !- Name
On/Off, !- Schedule Type Limits Name
Through: 6/30, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0, !- Field 3
Through: 12/31, !- Field 4
For: AllDays, !- Field 5
Until: 24:00,1; !- Field 6
FaultModel:TemperatureSensorOffset:OutdoorAir,
OATFault, !- Name
ALWAYS_ON, !- Availability Schedule Name
OATSeveritySch, !- Severity Schedule Name
Controller:OutdoorAir, !- Controller Object Type
VAV_1_OA_Controller, !- Controller Object Name
-2.0; !- Temperature Sensor Offset, deg C
FaultModel:TemperatureSensorOffset:ReturnAir,
RATFault, !- Name
, !- Availability Schedule Name
, !- Severity Schedule Name
Controller:OutdoorAir, !- Controller Object Type
VAV_2_OA_Controller, !- Controller Object Name
-2.0; !- Temperature Sensor Offset, deg C
FaultModel:EnthalpySensorOffset:ReturnAir,
RAHFault, !- Name
, !- Availability Schedule Name
, !- Severity Schedule Name
Controller:OutdoorAir, !- Controller Object Type
VAV_2_OA_Controller, !- Controller Object Name
-2000; !- Enthalpy Sensor Offset, J/Kg
! example faults for a fouling coil
FaultModel:Fouling:Coil,
CoolingCoilFault, !- Name
VAV_2_CoolC, !- Heating or Cooling Coil Name
ALWAYS_ON, !- Availability Schedule Name
, !- Severity Schedule Name
FouledUARated, !- Fouling Input Method
3000, !- UAFouled, W/K
, !- Water Side Fouling Factor, m2-K/W
, !- Air Side Fouling Factor, m2-K/W
, !- Outside Coil Surface Area, m2
; !- Inside to Outside Coil Surface Area Ratio
FaultModel:ThermostatOffset[LINK]
This object defines the offset fault of a thermostat that
leads to inappropriate operations of the HVAC system.
This is the user-defined name of the fault.
Field: Thermostat Name[LINK]
This field defines the name of the thermostat object
associated with the fault. It should be the name of a ZoneControl:Thermostat
object.
Field:
Availability Schedule Name[LINK]
This field provides the name of a schedule that will
determine whether this fault is applicable or not. When a
fault is not applicable it is not modeled in the simulations.
When it is applicable, then a user-defined sensor offset and a
severity schedule will be applied. This schedule should be set
to “1.0” when a fault is applicable and “0.0” when it is not.
If this field is blank, the schedule has values of 1.0 for all
time periods.
Field: Severity
Schedule Name[LINK]
This field provides the name of a schedule that represents
severity of a fault. This is used as a multiplier to the
reference thermostat offset value. This schedule should be set
to a non-zero value when a fault is applicable and “0.0” when
it is not. If this field is blank, the schedule has values of
1.0 for all time periods.
Field: Reference
Thermostat Offset[LINK]
This field defines the reference offset value of the
thermostat. A positive value means the zone air temperature
reading is higher than the actual value. A negative value
means the reading is lower than the actual value. A “0.0”
value means no offset. Default is 2.0. The units are in
degrees Celsius.
FaultModel:HumidistatOffset[LINK]
This object defines the offset fault of a humidistat that
leads to inappropriate operations of the HVAC system.
This is the user-defined name of the fault.
Field: Humidistat Name[LINK]
This field defines the name of the humidistat object
associated with the fault. It should be the name of a ZoneControl:Humidistat
object.
Field: Humidistat Offset
Type[LINK]
This choice field determines the humidistat offset fault
type. Two fault types are available: (1) Type
ThermostatOffsetIndependent: humidistat offset is not related
with thermostat offset. For this type, user needs to specify
the Reference Humidistat Offset, Availability Schedule, and
Severity Schedule (2) Type ThermostatOffsetDependent:
humidistat offset is caused by thermostat offset fault. For
this type, user only needs to specify the Related Thermostat
Offset Fault Name.
Field:
Availability Schedule Name[LINK]
This field provides the name of a schedule that will
determine if this fault is applicable. This field is
applicable for the Type ThermostatOffsetIndependent. When a
fault is not applicable it is not modeled in the simulations.
When it is applicable, then a user-defined sensor offset and a
severity schedule will be applied. This schedule should be set
to “1.0” when a fault is applicable and “0.0” when it is not.
If this field is blank, the schedule has values of 1 for all
time periods.
Field: Severity
Schedule Name[LINK]
This field provides the name of a schedule that represents
severity of a fault. This field is applicable for the Type
ThermostatOffsetIndependent. This is used as a multiplier to
the reference humidistat offset value. This schedule should be
set to a non-zero value when a fault is applicable and “0.0”
when it is not. If this field is blank, the schedule has
values of 1.0 for all time periods.
Field: Reference
Humidistat Offset[LINK]
This field defines the reference offset value of the
humidistat. This field is required for the Type
ThermostatOffsetIndependent. A positive value means the zone
air temperature reading is higher than the actual value. A
negative value means the reading is lower than the actual
value. A “0.0” value means no offset. Default is 5.0. The
units are in percentage.
This field provides the name of a Thermostat Offset Fault
object that causes the humidistat offset fault. It should be
the name of a FaultModel:ThermostatOffset
object. This field is required for the Type
ThermostatOffsetDependent. This is used as a multiplier to the
reference humidistat offset value. This schedule should be set
to a non-zero value when a fault is applicable and “0.0” when
it is not. If this field is blank, the schedule has values of
1.0 for all time periods.
An example of IDF codes for the thermostat/humidistat
offset fault models:
FaultModel:ThermostatOffset,
Ther_Offset_Zone1, !- Name
Zone 1 Thermostat, !- Thermostat Name
AlwaysOn, !- Availability Schedule Name
AlwaysOne, !- Severity Schedule Name
2.0; !- Reference Thermostat Offset
FaultModel:HumidistatOffset,
Humi_Offset_Zone1, !- Name
Zone 1 Humidistat, !- Humidistat Name
ThermostatOffsetDependent, !- Humidistat Offset Type
, !- Availability Schedule Name
, !- Severity Schedule Name
, !- Reference Humidistat Offset
Ther_Offset_Zone1; !- Related Thermostat Offset Fault Name
FaultModel:HumidistatOffset,
Humi_Offset_Zone2, !- Name
Zone 2 Humidistat, !- Humidistat Name
ThermostatOffsetIndependent, !- Humidistat Offset Type
AlwaysOn, !- Availability Schedule Name
AlwaysOne, !- Severity Schedule Name
10, !- Reference Humidistat Offset
; !- Related Thermostat Offset Fault Name
Group - Operational Faults[LINK]
Introduction to Operational Faults Modeling[LINK]
Most of the buildings, either new or old, have operational faults in the sensors, controllers, meters, equipment and systems. Being able to model and simulate these faults and their impact on energy performance of buildings is crucial to improve accuracy of building simulations and to support the retrofit of buildings.
To date, the main practitioner use of EnergyPlus has been for new construction design. With the new high priority attached by USDOE to retrofit and improved operation of existing buildings, there is a need to extend the capabilities of EnergyPlus to model existing buildings, including faulty operation:
Retrofit analysis: starts with calibrated simulation; the ability to estimate the severity of common faults is expected to improve the accuracy and transparency of the calibrated model and hence the increase accuracy of the analysis of different retrofit measures.
Commissioning providers can use the fault models to demonstrate the saving to be expected from fixing faults found in retro-commissioning
Support for building operation by using the calibrated model, including unfixed faults, as a real-time reference model to detect, and verify the diagnosis of, newly occurring faults.
The users in these cases are practitioners, not power users, so it is needed to implement the fault models using conventional EnergyPlus objects rather than the EMS, which, in any case, could only be used to model limited types of faults.
Operational Fault Objects[LINK]
EnergyPlus contains a number of objects to model operational faults of sensors, meters, equipment and systems. The current implementation allows the modeling of the following fault types: (1) sensor faults with air economizers, (2) thermostat/humidistat offset faults, and (3) heating and cooling coil fouling faults.
The objects used by EnergyPlus to model the faults are as follows:
FaultModel:TemperatureSensorOffset:OutdoorAir[LINK]
This object defines the offset of an outdoor air dry-bulb temperature sensor that is used to determine applicability of an air economizer.
Inputs[LINK]
Field: Name[LINK]
This is the user-defined name of the fault.
Field: Availability Schedule Name[LINK]
This field provides the name of a schedule that will determine if this fault is applicable. When a fault is not applicable it is not modeled in the simulations. When it is applicable, then a user-defined sensor offset and a severity schedule will be applied. This schedule should be set to “1.0” when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods.
Field: Severity Schedule Name[LINK]
This field provides the name of a schedule that represents severity of a fault. This is used as a multiplier to the user-defined temperature offset. This schedule should be set to a non-zero value when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods.
Field: Controller Object Type[LINK]
This field defines the controller object type that this fault is associated with. Choices are from a list of applicable controller types. Current implementation supports air economizer - the choice is Controller:OutdoorAir.
Field: Controller Object Name[LINK]
This field defines the name of the controller object associated with the fault. It should be one of the objects with the defined types.
Field: Temperature Sensor Offset[LINK]
This field defines the offset of the temperature sensor. A positive value means the sensor reads a temperature that is higher than the real value. A negative value means the sensor reads a temperature that is lower than the real value. A “0.0” value means no offset. Default is 0.0. The units are in degrees Celsius.
FaultModel:HumiditySensorOffset:OutdoorAir[LINK]
This object defines the offset of an outdoor air humidity sensor that is used to determine applicability of an air economizer.
Inputs[LINK]
Field: Name[LINK]
This is the user-defined name of the fault.
Field: Availability Schedule Name[LINK]
This field provides the name of a schedule that will determine if this fault is applicable. When a fault is not applicable it is not modeled in the simulations. When it is applicable, then a user-defined sensor offset and a severity schedule will be applied. This schedule should be set to “1.0” when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods.
Field: Severity Schedule Name[LINK]
This field provides the name of a schedule that represents severity of a fault. This is used as a multiplier to the user-defined temperature offset. This schedule should be set to a non-zero value when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods.
Field: Controller Object Type[LINK]
This field defines the controller object type that this fault is associated with. Choices are from a list of applicable controller types. Current implementation supports air economizer - the choice is Controller:OutdoorAir.
Field: Controller Object Name[LINK]
This field defines the name of the controller object associated with the fault. It should be one of the objects with the defined types.
Field: Humidity Sensor Offset[LINK]
This field defines the offset of the humidity ratio sensor. A positive value means the sensor reads a humidity ratio that is higher than the real value. A negative value means the sensor reads a humidity ratio that is lower than the real value. A “0.0” value means no offset. Default is 0.0. The units are in kgWater/kgDryAir.
FaultModel:EnthalpySensorOffset:OutdoorAir[LINK]
This object defines the offset of an outdoor enthalpy sensor that is used to determine applicability of an air economizer.
Inputs[LINK]
Field: Name[LINK]
This is the user-defined name of the fault.
Field: Availability Schedule Name[LINK]
This field provides the name of a schedule that will determine if this fault is applicable. When a fault is not applicable it is not modeled in the simulations. When it is applicable, then a user-defined sensor offset and a severity schedule will be applied. This schedule should be set to “1.0” when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods.
Field: Severity Schedule Name[LINK]
This field provides the name of a schedule that represents severity of a fault. This is used as a multiplier to the user-defined temperature offset. This schedule should be set to a non-zero value when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods.
Field: Controller Object Type[LINK]
This field defines the controller object type that this fault is associated with. Choices are from a list of applicable controller types. Current implementation supports air economizer - the choice is Controller:OutdoorAir.
Field: Controller Object Name[LINK]
This field defines the name of the controller object associated with the fault. It should be one of the objects with the defined types.
Field: Enthalpy Sensor Offset[LINK]
This field defines the offset of the enthalpy sensor. A positive value means the sensor reads an enthalpy that is higher than the real value. A negative value means the sensor reads an enthalpy that is lower than the real value. A “0.0” value means no offset. Default is 0.0. The units are in J/kg.
FaultModel:TemperatureSensorOffset:ReturnAir[LINK]
This object defines the offset of a return air dry-bulb temperature sensor that is used to determine applicability of an air economizer.
Inputs[LINK]
Field: Name[LINK]
This is the user-defined name of the fault.
Field: Availability Schedule Name[LINK]
This field provides the name of a schedule that will determine if this fault is applicable. When a fault is not applicable it is not modeled in the simulations. When it is applicable, then a user-defined sensor offset and a severity schedule will be applied. This schedule should be set to “1.0” when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods.
Field: Severity Schedule Name[LINK]
This field provides the name of a schedule that represents severity of a fault. This is used as a multiplier to the user-defined temperature offset. This schedule should be set to a non-zero value when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods.
Field: Controller Object Type[LINK]
This field defines the controller object type that this fault is associated with. Choices are from a list of applicable controller types. Current implementation supports air economizer - the choice is Controller:OutdoorAir.
Field: Controller Object Name[LINK]
This field defines the name of the controller object associated with the fault. It should be one of the objects with the defined types.
Field: Temperature Sensor Offset[LINK]
This field defines the offset of the temperature sensor. A positive value means the sensor reads a temperature that is higher than the real value. A negative value means the sensor reads a temperature that is lower than the real value. A “0.0” value means no offset. Default is 0.0. The units are in degrees Celsius.
FaultModel:EnthalpySensorOffset:ReturnAir[LINK]
This object defines the offset of a return air enthalpy sensor that is used to determine applicability of an air economizer.
Inputs[LINK]
Field: Name[LINK]
This is the user-defined name of the fault.
Field: Availability Schedule Name[LINK]
This field provides the name of a schedule that will determine if this fault is applicable. When a fault is not applicable it is not modeled in the simulations. When it is applicable, then a user-defined sensor offset and a severity schedule will be applied. This schedule should be set to “1.0” when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods.
Field: Severity Schedule Name[LINK]
This field provides the name of a schedule that represents severity of a fault. This is used as a multiplier to the user-defined temperature offset. This schedule should be set to a non-zero value when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods.
Field: Controller Object Type[LINK]
This field defines the controller object type that this fault is associated with. Choices are from a list of applicable controller types. Current implementation supports air economizer - the choice is Controller:OutdoorAir.
Field: Controller Object Name[LINK]
This field defines the name of the controller object associated with the fault. It should be one of the objects with the defined types.
Field: Enthalpy Sensor Offset[LINK]
This field defines the offset of the enthalpy sensor. A positive value means the sensor reads an enthalpy that is higher than the real value. A negative value means the sensor reads an enthalpy that is lower than the real value. A “0.0” value means no offset. Default is 0.0. The units are in J/kg.
FaultModel:Fouling:Coil[LINK]
This object defines the fouling for a simple water cooling coil or simple water heating coil.
Inputs[LINK]
Field: Name[LINK]
This is the user-defined name of the fault.
Field: Coil Name[LINK]
This field defines the name of the simple cooling coil or simple heating coil that has the fouling fault.
Field: Availability Schedule Name[LINK]
This field provides the name of a schedule that will determine if this fault is applicable. When a fault is not applicable it is not modeled in the simulations. When it is applicable, then user-defined fouling and a severity schedule will be applied. This schedule should be set to “1.0” when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods
Field: Severity Schedule Name[LINK]
This field provides the name of a schedule that represents severity of a fault. This is used as a multiplier to the user-defined fouling. If this field is blank, the schedule has values of 1 (no changes to fouling) for all time periods.
Field: Fouling Input Method[LINK]
There are two methods to input the fouling, i.e. FouledUARated and FoulingFactor. User chooses the appropriate method to determine the coil fouling.
Field: UAFouled[LINK]
This is the overall coil UA value including the coil fouling when the “FouledUARated” method is used. The unit is W/K.
Field: Water Side Fouling Factor[LINK]
The following four fields specify the required inputs when the “FoulingFactor” method is used. This field defines the fouling factor for the water side. The units are in m2-K/W.
Field: Air Side Fouling Factor[LINK]
This field defines the fouling factor for the air side. The units are in m2-K/W.
Field: Outside Coil Surface Area[LINK]
This field defines outside surface area of the cooling or heating coil. The units are in m2.
Field: Inside to Outside Coil Surface Area Ratio[LINK]
This field specifies the inside to outside surface area ratio of the cooling or heating coil.
IDF examples:
FaultModel:ThermostatOffset[LINK]
This object defines the offset fault of a thermostat that leads to inappropriate operations of the HVAC system.
Inputs[LINK]
Field: Name[LINK]
This is the user-defined name of the fault.
Field: Thermostat Name[LINK]
This field defines the name of the thermostat object associated with the fault. It should be the name of a ZoneControl:Thermostat object.
Field: Availability Schedule Name[LINK]
This field provides the name of a schedule that will determine whether this fault is applicable or not. When a fault is not applicable it is not modeled in the simulations. When it is applicable, then a user-defined sensor offset and a severity schedule will be applied. This schedule should be set to “1.0” when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1.0 for all time periods.
Field: Severity Schedule Name[LINK]
This field provides the name of a schedule that represents severity of a fault. This is used as a multiplier to the reference thermostat offset value. This schedule should be set to a non-zero value when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1.0 for all time periods.
Field: Reference Thermostat Offset[LINK]
This field defines the reference offset value of the thermostat. A positive value means the zone air temperature reading is higher than the actual value. A negative value means the reading is lower than the actual value. A “0.0” value means no offset. Default is 2.0. The units are in degrees Celsius.
FaultModel:HumidistatOffset[LINK]
This object defines the offset fault of a humidistat that leads to inappropriate operations of the HVAC system.
Inputs[LINK]
Field: Name[LINK]
This is the user-defined name of the fault.
Field: Humidistat Name[LINK]
This field defines the name of the humidistat object associated with the fault. It should be the name of a ZoneControl:Humidistat object.
Field: Humidistat Offset Type[LINK]
This choice field determines the humidistat offset fault type. Two fault types are available: (1) Type ThermostatOffsetIndependent: humidistat offset is not related with thermostat offset. For this type, user needs to specify the Reference Humidistat Offset, Availability Schedule, and Severity Schedule (2) Type ThermostatOffsetDependent: humidistat offset is caused by thermostat offset fault. For this type, user only needs to specify the Related Thermostat Offset Fault Name.
Field: Availability Schedule Name[LINK]
This field provides the name of a schedule that will determine if this fault is applicable. This field is applicable for the Type ThermostatOffsetIndependent. When a fault is not applicable it is not modeled in the simulations. When it is applicable, then a user-defined sensor offset and a severity schedule will be applied. This schedule should be set to “1.0” when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1 for all time periods.
Field: Severity Schedule Name[LINK]
This field provides the name of a schedule that represents severity of a fault. This field is applicable for the Type ThermostatOffsetIndependent. This is used as a multiplier to the reference humidistat offset value. This schedule should be set to a non-zero value when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1.0 for all time periods.
Field: Reference Humidistat Offset[LINK]
This field defines the reference offset value of the humidistat. This field is required for the Type ThermostatOffsetIndependent. A positive value means the zone air temperature reading is higher than the actual value. A negative value means the reading is lower than the actual value. A “0.0” value means no offset. Default is 5.0. The units are in percentage.
Field: Related Thermostat Offset Fault Name[LINK]
This field provides the name of a Thermostat Offset Fault object that causes the humidistat offset fault. It should be the name of a FaultModel:ThermostatOffset object. This field is required for the Type ThermostatOffsetDependent. This is used as a multiplier to the reference humidistat offset value. This schedule should be set to a non-zero value when a fault is applicable and “0.0” when it is not. If this field is blank, the schedule has values of 1.0 for all time periods.
An example of IDF codes for the thermostat/humidistat offset fault models:
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.