eplustbl.<ext>[LINK]
The eplustbl file contains the tabular output results that
are created when using the following objects:
- Output:Table:SummaryReports
- Output:Table:TimeBins
- Output:Table:Monthly
- UtilityCost:Tariff
- ComponentCost:Line Item
The format and the extension for the file depends on the
setting of the ColumnSeparator field of the Output:Table:Style
object. The choices of HTML, tab, fixed, comma, and XML result
in eplustbl.htm, eplustbl.tab, eplustbl.txt, eplustbl.csv,
eplustbl.xml respectively. The HTML version of the report also
includes a table of contents that allows easier navigation
through the file.
By default the energy units reported in all of the eplustbl
files are in Joules (J) but the UnitConversion field of the
Output:Table:Style object allows for the values to be reported
in MJ, GJ or in kWh. In addition, the Output:Table:Style
object can specify for the tables to be in IP units for all
fields.
Output:Table:SummaryReports[LINK]
Several predefined reports are available from the Output:Table:SummaryReports
object including the following. (spaces are inserted in names
for readability; keys are included in the Input Data
Dictionary or by just removing the spaces):
All Summary
Lists all following applicable tables with “Summary” in
the name.
All Monthly
Lists all following applicable tables with “Monthly” in
the name.
All Summary And Monthly
Lists all following applicable tables with both
“Summary” and “Monthly” in the name. This does not include the
Zone
Component Load Summary report.
All Summary and Sizing Period
Lists the All Summary tables as well as the Zone
Component Load report (currently the only Sizing Period
report). Please note that the Zone
Component Load report does increase the run time because it
repeats sizing periods.
All Summary Monthly and Sizing Period
Lists the All Summary tables, the Monthly tables as
well as the Zone
Component Load report (currently the only Sizing Period
report). Please note that the Zone
Component Load report does increase the run time because it
repeats sizing periods.
Annual Building
Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Climatic Data Summary
Equipment Summary
Envelope Summary
Surface Shadowing Summary
Shading Summary
Lighting Summary
HVAC Sizing Summary
System Summary
Component Sizing Summary
Outdoor Air Summary
Object Count Summary
Component Cost Economics Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
Zone
Component Load Summary
Zone
Cooling Summary Monthly
Zone
Heating Summary Monthly
Zone
Electric Summary Monthly
Space Gains Monthly
Peak Space Gains Monthly
Space Gain Components At Cooling Peak Monthly
Energy Consumption Electricity Natural Gas
Monthly
Energy Consumption Electricity Generated Propane
Monthly
Energy Consumption Diesel FuelOil Monthly
Energy Consumption District Heating Cooling
Monthly
Energy Consumption Coal Gasoline Monthly
End Use Energy Consumption Electricity Monthly
End Use Energy Consumption NaturalGas Monthly
End Use Energy Consumption Diesel Monthly
End Use Energy Consumption FuelOil Monthly
End Use Energy Consumption Coal Monthly
End Use Energy Consumption Propane Monthly
End Use Energy Consumption Gasoline Monthly
Peak Energy End Use Electricity Part1 Monthly
Peak Energy End Use Electricity Part2 Monthly
Electric Components Of Peak Demand Monthly
Peak Energy End Use NaturalGas Monthly
Peak Energy End Use Diesel Monthly
Peak Energy End Use FuelOil Monthly
Peak Energy End Use Coal Monthly
Peak Energy End Use Propane Monthly
Peak Energy End Use Gasoline Monthly
Setpoints Not Met With Temperatures Monthly
Comfort Report Simple55 Monthly
Unglazed Transpired Solar Collector Summary
Monthly
Occupant Comfort Data Summary Monthly
Chiller Report Monthly
Tower Report Monthly
Boiler Report Monthly
DX Report Monthly
Window
Report Monthly
Window
Energy Report Monthly
Window
Zone
Summary Monthly
Window
Energy Zone
Summary Monthly
Average Outdoor Conditions Monthly
Outdoor Conditions Maximum DryBulb Monthly
Outdoor Conditions Minimum DryBulb Monthly
Outdoor Conditions Maximum WetBulb Monthly
Outdoor Conditions Maximum DewPoint Monthly
Outdoor Ground Conditions Monthly
WindowAC Report Monthly
Water Heater Report Monthly
Generator Report Monthly
Daylighting Report Monthly
Coil Report Monthly
PlantLoop
Demand Report Monthly
Fan Report Monthly
Pump Report Monthly
CondLoop Demand Report Monthly
Zone
Temperature Oscillation Report Monthly
AirLoop System Energy And Water Use Monthly
AirLoop System Component Loads Monthly
AirLoop System Component Energy Use Monthly
Mechanical Ventilation Loads Monthly
Each of these reports is made up of several sub-tables of
information. Examples of some of the tables are shown below.
To enable all of the reports the single All Summary may be
specified.
The Annual Building
Utility Performance Summary report provides an overview of
energy consumption in the building for different end uses. The
following is an example this report (some columns may be
truncated due to page size). The key used to obtain this
report is AnnualBuildingUtilityPerformanceSummary.
In the Comfort and Setpoint Not Met Summary
sub-table, facility hours represents the total number of hours
that any single zone did not meet the comfort or setpoint
criteria. It is not weighted by number of zones or number of
occupants.
The values in the End Uses sub-table are from
report meters. To determine which components are attached to
each end-use meter, consult the meter details output file
(*.mtd).
Report: Annual Building
Utility Performance Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Values gathered over 8760.00 hours
Site and Source Energy
| |
Total Energy (GJ) |
Energy Per Total Building Area
(MJ/m2) |
Energy Per Conditioned Building
Area (MJ/m2) |
| Total Site Energy |
194.80 |
210.09 |
210.09 |
| Net Site Energy |
194.80 |
210.09 |
210.09 |
| Total Source Energy |
532.25 |
574.04 |
574.04 |
| Net Source Energy |
532.25 |
574.04 |
574.04 |
Source to Site Energy Converstion Factors
| |
Source=>Site Conversion
Factor |
| Electricity |
3.167 |
| Natural Gas |
1.084 |
| District Cooling |
1.056 |
| District Heating |
3.613 |
| Steam |
0.300 |
| Gasoline |
1.050 |
| Diesel |
1.050 |
| Coal |
1.050 |
| Fuel Oil #1 |
1.050 |
| Fuel Oil #2 |
1.050 |
| Propane |
1.050 |
Building
Area
| |
Area (m2) |
| Total Building Area |
927.20 |
| Net Conditioned Building
Area |
927.20 |
| Unconditioned Building Area |
0.00 |
End Uses
| |
Electricity (GJ) |
Natural Gas (GJ) |
Other Fuel (GJ) |
District Cooling (GJ) |
District Heating (GJ) |
Water (m3) |
| Heating |
0.00 |
40.65 |
0.00 |
0.00 |
0.00 |
0.00 |
| Cooling |
18.18 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
81.24 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
47.70 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
7.03 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| |
|
|
|
|
|
|
| Total End Uses |
154.15 |
40.65 |
0.00 |
0.00 |
0.00 |
0.00 |
Note: Natural gas appears to be the principal heating
source based on energy usage.
End Uses By Subcategory
| |
Subcategory |
Electricity (GJ) |
Natural Gas (GJ) |
Other Fuel (GJ) |
District Cooling (GJ) |
District Heating (GJ) |
Water (m3) |
| Heating |
General |
0.00 |
40.65 |
0.00 |
0.00 |
0.00 |
0.00 |
| Cooling |
General |
18.18 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
GeneralLights |
81.24 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
General |
47.70 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
General |
7.03 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Normalized Metrics
Utility Use Per Conditioned Floor Area
| |
Electricity Intensity
(MJ/m2) |
Natural Gas Intensity
(MJ/m2) |
Other Fuel Intensity
(MJ/m2) |
District Cooling Intensity
(MJ/m2) |
District Heating Intensity
(MJ/m2) |
Water Intensity (m3/m2) |
| Lighting |
87.62 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| HVAC |
27.19 |
43.84 |
0.00 |
0.00 |
0.00 |
0.00 |
| Other |
51.44 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Total |
166.25 |
43.84 |
0.00 |
0.00 |
0.00 |
0.00 |
Utility Use Per Total Floor Area
| |
Electricity Intensity
(MJ/m2) |
Natural Gas Intensity
(MJ/m2) |
Other Fuel Intensity
(MJ/m2) |
District Cooling Intensity
(MJ/m2) |
District Heating Intensity
(MJ/m2) |
Water Intensity (m3/m2) |
| Lighting |
87.62 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| HVAC |
27.19 |
43.84 |
0.00 |
0.00 |
0.00 |
0.00 |
| Other |
51.44 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Total |
166.25 |
43.84 |
0.00 |
0.00 |
0.00 |
0.00 |
Electric Loads Satisfied
| |
Electricity (GJ) |
Percent Electricity (%) |
| Fuel-Fired Power Generation |
0.00 |
0.00 |
| High Temperature
Geothermal* |
0.00 |
0.00 |
| Photovoltaic Power |
0.00 |
0.00 |
| Wind Power* |
0.00 |
0.00 |
| Net Decrease in On-Site
Storage |
0.00 |
0.00 |
| Total On-Site Electric
Sources |
0.00 |
0.00 |
| |
|
|
| Electricity Coming From
Utility |
154.15 |
100.00 |
| Surplus Electricity Going To
Utility |
0.00 |
0.00 |
| Net Electricity From
Utility |
154.15 |
100.00 |
| |
|
|
| Total On-Site and Utility
Electric Sources |
154.15 |
100.00 |
| Total Electricity End Uses |
154.15 |
100.00 |
On-Site Thermal Sources
| |
Heat (GJ) |
Percent Heat (%) |
| Water-Side Heat Recovery |
0.00 |
|
| Air to Air Heat Recovery for
Cooling |
0.00 |
|
| Air to Air Heat Recovery for
Heating |
0.00 |
|
| High-Temperature
Geothermal* |
0.00 |
|
| Solar Water Thermal |
0.00 |
|
| Solar Air Thermal |
0.00 |
|
| Total On-Site Thermal
Sources |
0.00 |
|
Water Source Summary
| |
Water (m3) |
Percent Water (%) |
| Rainwater Collection |
0.00 |
- |
| Condensate Collection |
0.00 |
- |
| Groundwater Well |
0.00 |
- |
| Total On Site Water Sources |
0.00 |
- |
| - |
- |
- |
| Initial Storage |
0.00 |
- |
| Final Storage |
0.00 |
- |
| Change in Storage |
0.00 |
- |
| - |
- |
- |
| Water Supplied by Utility |
0.00 |
- |
| - |
- |
- |
| Total On Site, Change in
Storage, and Utility Water Sources |
0.00 |
- |
| Total Water End Uses |
0.00 |
- |
Comfort and Setpoint Not Met Summary
| |
Facility (Hours) |
| Time Set Point Not Met During
Occupied Heating |
0.00 |
| Time Set Point Not Met During
Occupied Cooling |
406.00 |
| Time Not Comfortable Based on
Simple ASHRAE 55-2004 |
1033.00 |
Note 1: An asterisk (*) indicates that the feature is not
yet implemented.
The Input Verification and Results Summary report provides
a summary of some of the most common input assumptions that
are not included in any of the other predefined reports.
Directly following is an example of the report. The key used
to obtain this report is
InputVerificationandResultsSummary.
Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
General
| |
Value |
| Program Version and Build |
EnergyPlus, Version 3.1 |
| Weather |
Chicago IL United States TMY2
94846 WMO#=725340 |
| Latitude (deg) |
41.78 |
| Longitude (deg) |
-87.8 |
| Elevation (m) |
190.00 |
| Time Zone |
-6.0 |
| North Axis Angle (deg) |
30.00 |
| Hours Simulated (hrs) |
8760.00 |
ENVELOPE
Window-Wall Ratio
| |
Total |
North (315 to 45 deg) |
East (45 to 135 deg) |
South (135 to 225 deg) |
West (225 to 315 deg) |
| Gross Wall Area (m2) |
274.20 |
91.50 |
45.60 |
91.50 |
45.60 |
| Window Opening Area (m2) |
61.65 |
20.85 |
9.12 |
22.56 |
9.12 |
| Window-Wall Ratio (%) |
22.48 |
22.79 |
20.00 |
24.66 |
20.00 |
Skylight-Roof Ratio
| |
Total |
| Gross Roof Area (m2) |
463.60 |
| Skylight Area (m2) |
0.00 |
| Skylight-Roof Ratio (%) |
0.00 |
PERFORMANCE
Zone
Summary
| |
Area (m2) |
Conditioned (Y/N) |
Volume (m3) |
Multipliers |
Gross Wall Area (m2) |
Window Glass Area (m2) |
Lighting (W/m2) |
People (m2/person) |
Plug and Process(W/m2) |
| PLENUM-1 |
463.60 |
Yes |
283.20 |
1.00 |
54.84 |
0.00 |
0.0000 |
|
0.0000 |
| SPACE1-1 |
99.16 |
Yes |
239.25 |
1.00 |
73.20 |
22.56 |
15.9742 |
9.01 |
10.6495 |
| SPACE2-1 |
42.73 |
Yes |
103.31 |
1.00 |
36.48 |
9.12 |
16.0056 |
8.55 |
10.6704 |
| SPACE3-1 |
96.48 |
Yes |
239.25 |
1.00 |
73.20 |
20.85 |
16.4179 |
8.77 |
10.9453 |
| SPACE4-1 |
42.73 |
Yes |
103.31 |
1.00 |
36.48 |
9.12 |
16.0056 |
8.55 |
10.6704 |
| SPACE5-1 |
182.49 |
Yes |
447.68 |
1.00 |
0.00 |
0.00 |
16.2420 |
9.12 |
10.8280 |
| Total |
927.20 |
|
1416.00 |
|
274.20 |
61.65 |
8.0889 |
17.83 |
5.3926 |
| Conditioned Total |
927.20 |
|
1416.00 |
|
274.20 |
61.65 |
8.0889 |
17.83 |
5.3926 |
| Unconditioned Total |
0.00 |
|
0.00 |
|
0.00 |
0.00 |
|
|
|
Demand End Use
Components Summary[LINK]
The Demand End Use Components Summary report shows the
demand breakdown by component end use at the time that the
peak demand for each source of energy is set. The time of the
peak demand is shown in the first row. The contributions of
each end use at the time of the peak demand of the energy
source is shown in this report. The key used to obtain this
report is DemandEndUseComponentsSummary.
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
End Uses
| |
Electricity (W) |
Natural Gas (W) |
Propane (W) |
District Cooling (W) |
Steam (W) |
Water (m3/s) |
| Time of Peak |
02-JUL-14:00 |
31-DEC-07:15 |
- |
- |
- |
- |
| Heating |
0.00 |
81764.44 |
0.00 |
0.00 |
0.00 |
0.00 |
| Cooling |
12342.62 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
7500.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
4000.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
1498.36 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| |
|
|
|
|
|
|
| Total End Uses |
25340.97 |
81764.44 |
0.00 |
0.00 |
0.00 |
0.00 |
End Uses By Subcategory
| |
Subcategory |
Electricity (W) |
Natural Gas (W) |
Propane (W) |
District Cooling (W) |
Steam (W) |
Water (m3/s) |
| Heating |
General |
0.00 |
81764.44 |
0.00 |
0.00 |
0.00 |
0.00 |
| Cooling |
General |
12342.62 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
GeneralLights |
7500.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
General |
4000.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
General |
1498.36 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Source
Energy End Use Components Summary[LINK]
The Source Energy End Use Components Summary report
produces a report that includes three tables. These tables
display source energy by fuel type that is calculated based on
site to source energy factors specified by the user in the EnvironmentalImpactFactors
and FuelFactors
objects. The last two tables display the source energy in
terms of area normalized metrics. Directly following is an
example of the three tables. The key used to obtain this
report is SourceEnergyEndUseComponentsSummary.
Report: Source Energy End Use Components
Summary
For: Entire Facility
Timestamp: 2011-10-07 20:53:43
Values gathered over 8760.00 hoursSource Energy End
Use Components Summary
| |
Source Electricity [GJ] |
Source Natural Gas [GJ] |
Source Other Fuel [GJ] |
Source District Cooling
[GJ] |
Source District Heating
[GJ] |
| Heating |
0.00 |
140.03 |
0.00 |
0.00 |
0.00 |
| Cooling |
167.65 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
569.39 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
325.49 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
55.72 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
7.57 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| |
|
|
|
|
|
| Total Source Energy End Use
Components |
1125.82 |
140.03 |
0.00 |
0.00 |
0.00 |
Normalized MetricsSource Energy End Use Components
Per Conditioned Floor Area
| |
Source Electricity [MJ/m2] |
Source Natural Gas [MJ/m2] |
Source Other Fuel [MJ/m2] |
Source District Cooling
[MJ/m2] |
Source District Heating
[MJ/m2] |
| Heating |
0.00 |
151.02 |
0.00 |
0.00 |
0.00 |
| Cooling |
180.82 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
614.09 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
351.05 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
60.10 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
8.16 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| |
|
|
|
|
|
| Total Source Energy End Use
Components |
1214.22 |
151.02 |
0.00 |
0.00 |
0.00 |
Source Energy End Use Components Per Total Floor
Area
| |
Source Electricity [MJ/m2] |
Source Natural Gas [MJ/m2] |
Source Other Fuel [MJ/m2] |
Source District Cooling
[MJ/m2] |
Source District Heating
[MJ/m2] |
| Heating |
0.00 |
151.02 |
0.00 |
0.00 |
0.00 |
| Cooling |
180.82 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
614.09 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
351.05 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
60.10 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
8.16 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| |
|
|
|
|
|
| Total Source Energy End Use
Components |
1214.22 |
151.02 |
0.00 |
0.00 |
0.00 |
Equipment Summary[LINK]
The Equipment Summary report provides a summary of the HVAC
related equipment in the building. The central chiller example
shows the most common type of chillers, boilers and towers
used in EnergyPlus. The remaining subtables cover DX coils,
fans and water heating equipment. Not every type of HVAC
equipment is represented in this report. Directly following is
an example of the report. The key used to obtain this report
is EquipmentSummary.
Report: Equipment Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Central Plant
| |
Type |
Nominal Capacity (W) |
Nominal Efficiency (W/W) |
| None |
|
|
|
Cooling Coils
| |
Type |
Nominal Total Capacity (W) |
Nominal Sensible Capacity
(W) |
Nominal Latent Capacity (W) |
Nominal Sensible Heat Ratio |
Nominal Efficiency (W/W) |
| MAIN COOLING COIL 1 |
Coil:Cooling:DX:TwoSpeed |
37506.82 |
25504.64 |
12002.18 |
0.68 |
3.00 |
Heating Coils
| |
Type |
Nominal Total Capacity (W) |
Nominal Efficiency (W/W) |
| SPACE1-1 ZONE COIL |
Coil:Heating:Gas |
17614.83 |
0.80 |
| SPACE2-1 ZONE COIL |
Coil:Heating:Gas |
14619.82 |
0.80 |
| SPACE3-1 ZONE COIL |
Coil:Heating:Gas |
16093.74 |
0.80 |
| SPACE4-1 ZONE COIL |
Coil:Heating:Gas |
18942.35 |
0.80 |
| SPACE5-1 ZONE COIL |
Coil:Heating:Gas |
19146.73 |
0.80 |
| MAIN HEATING COIL 1 |
Coil:Heating:Gas |
19754.61 |
0.80 |
Fans
| |
Type |
Total Efficiency (W/W) |
Delta Pressure (pa) |
Max Flow Rate (m3/s) |
Rated Power (W) |
Motor Heat In Air Fraction |
End Use |
| SUPPLY FAN 1 |
Fan:VariableVolume |
0.70 |
600.00 |
2.27 |
1942.10 |
1.00 |
General |
Pumps
| |
Type |
Control |
Head (pa) |
Power (W) |
Motor Efficiency (W/W) |
| None |
|
|
|
|
|
Service Water Heating
| |
Type |
Storage Volume (m3) |
Input(W) |
Thermal Efficiency (W/W) |
Recovery Efficiency (W/W) |
Energy Factor |
| None |
|
|
|
|
|
|
Envelope Summary[LINK]
The Envelope Summary report provides a summary of the
elements of the envelope of the building. The first table
describes the exterior opaque elements and the second table
describes the fenestration elements. Reflectance is defined as
one minus the thermal absorptance. Directly following is an
example of the report. The key used to obtain this report is
EnvelopeSummary.
Report: Envelope Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Opaque Exterior
| |
Construction |
Reflectance |
U-Factor with Film (W/m2-K) |
U-Factor no Film (W/m2-K) |
Gross Area (m2) |
Azimuth (deg) |
Tilt (deg) |
Cardinal Direction |
| WALL-1PF |
WALL-1 |
0.22 |
0.384 |
0.41 |
18.30 |
210.00 |
90.00 |
S |
| WALL-1PR |
WALL-1 |
0.22 |
0.384 |
0.41 |
9.12 |
120.00 |
90.00 |
E |
| WALL-1PB |
WALL-1 |
0.22 |
0.384 |
0.41 |
18.30 |
30.00 |
90.00 |
N |
| WALL-1PL |
WALL-1 |
0.22 |
0.384 |
0.41 |
9.12 |
300.00 |
90.00 |
W |
| TOP-1 |
ROOF-1 |
0.35 |
0.268 |
0.28 |
463.60 |
210.00 |
0.00 |
|
| FRONT-1 |
WALL-1 |
0.22 |
0.384 |
0.41 |
73.20 |
210.00 |
90.00 |
S |
| F1-1 |
FLOOR-SLAB-1 |
0.35 |
1.454 |
2.25 |
99.16 |
30.00 |
180.00 |
|
| RIGHT-1 |
WALL-1 |
0.22 |
0.384 |
0.41 |
36.48 |
120.00 |
90.00 |
E |
| F2-1 |
FLOOR-SLAB-1 |
0.35 |
1.454 |
2.25 |
42.73 |
300.00 |
180.00 |
|
| BACK-1 |
WALL-1 |
0.22 |
0.384 |
0.41 |
73.20 |
30.00 |
90.00 |
N |
| F3-1 |
FLOOR-SLAB-1 |
0.35 |
1.454 |
2.25 |
96.48 |
74.22 |
180.00 |
|
| LEFT-1 |
WALL-1 |
0.22 |
0.384 |
0.41 |
36.48 |
300.00 |
90.00 |
W |
| F4-1 |
FLOOR-SLAB-1 |
0.35 |
1.454 |
2.25 |
42.73 |
120.00 |
180.00 |
|
| F5-1 |
FLOOR-SLAB-1 |
0.35 |
1.454 |
2.25 |
182.49 |
30.00 |
180.00 |
|
Fenestration
| |
Construction |
Area of One Opening (m2) |
Area of Openings (m2) |
U-Factor |
SHGC |
Visible Transmittance |
Shade Control |
Parent Surface |
Azimuth (deg) |
Cardinal Direction |
| WF-1 |
DBL CLR 3MM/13MM AIR |
16.56 |
16.56 |
2.72 |
0.763 |
0.812 |
No |
FRONT-1 |
210.00 |
S |
| DF-1 |
SGL GREY 3MM |
6.00 |
6.00 |
5.89 |
0.708 |
0.611 |
No |
FRONT-1 |
210.00 |
S |
| WR-1 |
DBL CLR 3MM/13MM AIR |
9.12 |
9.12 |
2.72 |
0.763 |
0.812 |
No |
RIGHT-1 |
120.00 |
E |
| WB-1 |
DBL CLR 3MM/13MM AIR |
16.44 |
16.44 |
2.72 |
0.763 |
0.812 |
No |
BACK-1 |
30.00 |
N |
| DB-1 |
SGL GREY 3MM |
4.41 |
4.41 |
5.89 |
0.708 |
0.611 |
No |
BACK-1 |
30.00 |
N |
| WL-1 |
DBL CLR 3MM/13MM AIR |
9.12 |
9.12 |
2.72 |
0.763 |
0.812 |
No |
LEFT-1 |
300.00 |
W |
| Total or Average |
|
|
61.65 |
3.26 |
0.753 |
0.778 |
|
|
|
|
| North Total or Average |
|
|
20.85 |
3.39 |
0.751 |
0.769 |
|
|
|
|
| Non-North Total or Average |
|
|
40.80 |
3.19 |
0.755 |
0.782 |
|
|
|
|
Surface Shadowing
Summary[LINK]
The Surface Shadowing Summary report summarizes how the
surfaces may cast shadows on other surfaces. Directly
following is an example of the report. The key used to obtain
this report is SurfaceShadowingSummary.
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other
Surfaces
| |
Possible Shadow Casters |
| FRONT-1 |
MAIN SOUTH OVERHANG; Mir-MAIN
SOUTH OVERHANG |
| SOUTH DOOR OVERHANG |
Mir-MAIN SOUTH OVERHANG;
WALL-1PF; FRONT-1 |
| WALL-1PF |
Mir-MAIN SOUTH OVERHANG; SOUTH
DOOR OVERHANG; Mir-SOUTH DOOR OVERHANG |
| MAIN SOUTH OVERHANG |
FRONT-1 |
Subsurfaces (Windows and Doors) that may be Shadowed by
Surfaces
| |
Possible Shadow Casters |
| WF-1 |
FRONT-1 |
| DF-1 |
FRONT-1 |
| WR-1 |
RIGHT-1 |
| WB-1 |
BACK-1 |
| DB-1 |
BACK-1 |
| WL-1 |
LEFT-1 |
Shading Summary[LINK]
The Shading Summary report shows how much of each window is
sunlit at different times of the year and also includes a
summary of the window controls. Directly following is an
example of the report. The key used to obtain this report is
ShadingSummary.
Report: Shading Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Sunlit Fraction
| |
March 21 9am |
March 21 noon |
March 21 3pm |
June 21 9am |
June 21 noon |
June 21 3pm |
December 21 9am |
December 21 noon |
December 21 3pm |
| WF-1 |
0.00 |
0.00 |
0.43 |
0.00 |
0.00 |
0.00 |
0.30 |
0.52 |
0.86 |
| DF-1 |
0.73 |
0.26 |
0.62 |
0.00 |
0.00 |
0.28 |
0.90 |
0.69 |
0.92 |
| WR-1 |
1.00 |
1.00 |
0.00 |
1.00 |
1.00 |
0.00 |
1.00 |
1.00 |
0.00 |
| WB-1 |
0.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| DB-1 |
0.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| WL-1 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
1.00 |
Window
Control
| |
Name |
Type |
Shaded Construction |
Control |
Glare Control |
| none |
|
|
|
|
|
Lighting Summary[LINK]
The Lighting Summary report provides a description of the
interior and exterior lighting systems being simulated. It
also provides a summary of daylighting controls. The Interior
Lighting table has three columns that are explained below:
Scheduled Hours/Week [hr] - In the schedule shown, this
represents the average weekly sum of hourly values. It is
based on a full year even if the simulation is only performed
for part of the year. It is not affected by daylighting.
Hours/Week > 1% [hr] - This represents the average hours
per week that are above 1% of the design value.
Full Load Hours/Week [hr] - This is based on consumption
and hours that the consumption occurred. It is dependent on
the run period used. When simulating only a portion of the
year, the value depends on which days of the year (the number
of weekdays versus weekend days, for example) are simulated.
It also indicates the impact of daylighting control. Directly
following is an example of the report. The key used to obtain
this report is LightingSummary.
Report: Lighting Summary
For: Entire Facility
Timestamp: 2012-09-05 12:10:52
Interior Lighting
| |
Zone |
Lighting Power Density
[W/m2] |
Zone Area [m2] |
Total Power [W] |
End Use Subcategory |
Schedule Name |
Scheduled Hours/Week [hr] |
Hours/Week > 1% [hr] |
Full Load Hours/Week [hr] |
Return Air Fraction |
Conditioned (Y/N) |
Consumption [GJ] |
| SPACE1-1 LIGHTS 1 |
SPACE1-1 |
15.9742 |
99.16 |
1584.00 |
GeneralLights |
LIGHTS-1 |
57.70 |
168.00 |
57.70 |
0.2000 |
Y |
17.16 |
| SPACE2-1 LIGHTS 1 |
SPACE2-1 |
16.0056 |
42.73 |
684.00 |
GeneralLights |
HALFPERCENT |
0.60 |
0.00 |
0.59 |
0.2000 |
Y |
0.08 |
| SPACE3-1 LIGHTS 1 |
SPACE3-1 |
16.4179 |
96.48 |
1584.00 |
GeneralLights |
ALWAYSON |
168.00 |
168.00 |
168.00 |
0.2000 |
Y |
49.95 |
| SPACE4-1 LIGHTS 1 |
SPACE4-1 |
16.0056 |
42.73 |
684.00 |
GeneralLights |
LIGHTS-1 |
57.70 |
168.00 |
57.70 |
0.2000 |
Y |
7.41 |
| SPACE5-1 LIGHTS 1 |
SPACE5-1 |
16.2420 |
182.49 |
2964.00 |
GeneralLights |
LIGHTS-1 |
57.70 |
168.00 |
57.70 |
0.2000 |
Y |
32.11 |
| Interior Lighting Total |
|
16.1777 |
463.60 |
7500.00 |
|
|
|
|
|
|
|
106.70 |
Daylighting
| |
Zone |
Daylighting Type |
Control Type |
Fraction Controlled |
Lighting Installed in Zone
[W] |
Lighting Controlled [W] |
| None |
|
|
|
|
|
|
Exterior Lighting
| |
Total Watts |
Astronomical Clock/Schedule |
Schedule Name |
Scheduled Hours/Week [hr] |
Hours/Week > 1% [hr] |
Full Load Hours/Week [hr] |
Consumption [GJ] |
| Exterior Lighting Total |
0.00 |
|
|
|
|
|
0.00 |
HVAC Sizing Summary[LINK]
The HVAC Sizing Summary report provides information on the
zone cooling and heating sizing and the peak load conditions
as well as information about the system air flow sizing.
Directly following is an example of the report. The key used
to obtain this report is HVACSizingSummary.
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2011-09-23 15:09:34
Zone
Cooling
|Calculated Design Load [W]|User Design Load
[W]|Calculated Design Air Flow [m3/s]|User Design Air Flow
[m3/s]|Design Day Name|Date/Time Of Peak|Temperature at Peak
[C]|Humidity Ratio at Peak [kgWater/kgAir]
SPACE1-1|2647.33|2647.33|0.223|0.223|CHICAGO_IL_USA ANNUAL
COOLING 1% DESIGN CONDITIONS DB/MCWB|7/21
15:45:00|31.02|0.01459
SPACE2-1|2234.38|2234.38|0.188|0.188|CHICAGO_IL_USA ANNUAL
COOLING 1% DESIGN CONDITIONS DB/MCWB|7/21
10:00:00|27.43|0.01459
SPACE3-1|2506.34|2506.34|0.211|0.211|CHICAGO_IL_USA ANNUAL
COOLING 1% DESIGN CONDITIONS DB/MCWB|7/21
15:00:00|31.50|0.01459
SPACE4-1|2464.72|2464.72|0.207|0.207|CHICAGO_IL_USA ANNUAL
COOLING 1% DESIGN CONDITIONS DB/MCWB|7/21
17:30:00|29.47|0.01459
SPACE5-1|2628.69|2628.69|0.221|0.221|CHICAGO_IL_USA ANNUAL
COOLING 1% DESIGN CONDITIONS DB/MCWB|7/21
15:00:00|31.50|0.01459
Zone
Heating
|Calculated Design Load [W]|User Design Load
[W]|Calculated Design Air Flow [m3/s]|User Design Air Flow
[m3/s]|Design Day Name|Date/Time Of Peak|Temperature at Peak
[C]|Humidity Ratio at Peak [kgWater/kgAir]
SPACE1-1|3860.76|3860.76|0.117|0.117|CHICAGO_IL_USA ANNUAL
HEATING 99% DESIGN CONDITIONS DB|1/21 24:00:00|-17.30|0.00084
SPACE2-1|1625.15|1625.15|0.049|0.049|CHICAGO_IL_USA ANNUAL
HEATING 99% DESIGN CONDITIONS DB|1/21 24:00:00|-17.30|0.00084
SPACE3-1|3753.07|3753.07|0.113|0.113|CHICAGO_IL_USA ANNUAL
HEATING 99% DESIGN CONDITIONS DB|1/21 24:00:00|-17.30|0.00084
SPACE4-1|1625.15|1625.15|0.049|0.049|CHICAGO_IL_USA ANNUAL
HEATING 99% DESIGN CONDITIONS DB|1/21 24:00:00|-17.30|0.00084
SPACE5-1|2981.57|2981.57|0.090|0.103|CHICAGO_IL_USA ANNUAL
HEATING 99% DESIGN CONDITIONS DB|1/21
24:00:00|-17.30|0.00084
System Design Air Flow Rates
Calculated cooling [m3/s] User cooling [m3/s] Calculated
heating [m3/s] User heating [m3/s]
VAV SYS 1 1.05 1.05 0.43 0.43
Plant Loop Coincident Design Fluid Flow Rate
Adjustments
| |
Previous Design Volume Flow Rate
[m3/s] |
Algorithm Volume Flow Rate
[m3/s] |
Coincident Design Volume Flow
Rate [m3/s] |
Coincident Size Adjusted |
Peak Sizing Period Name |
Peak Day into Period |
Peak Hour Of Day |
Peak Step Start Minute |
| COOLSYS1 Sizing Pass 1 |
0.120672 |
0.141525 |
0.141525 |
Yes |
CHICAGO ANN CLG .4% CONDNS
WB=>MDB HVAC Sizing Pass 1 |
1 |
2 |
30.0 |
| HEATSYS1 Sizing Pass 1 |
0.060598 |
0.049054 |
0.049054 |
Yes |
CHICAGO ANN HTG 99.6% CONDNS DB
HVAC Sizing Pass 1 |
1 |
7 |
20.0 |
System Summary[LINK]
The System Summary report provides information about some
of the primary components in the system including the
economizer and demand controlled ventilation. In addition,
this report describes when the zone conditions are not
comfortable or when set points are not met.
In the Time Not Comfortable Based on Simple ASHRAE
55-2004 and **Time Setpoint Not Met sub-tables, The
reported time represents the total number of hours that a
given zone did not meet the comfort or setpoint criteria. For
the Facility row, this is the total numbers of hours that one
or more zones were out of range. The values are not weighted
by number of zones or number of occupants.
Directly following is an example of the report. The key
used to obtain this report is SystemSummary.
Report: System Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Economizer
| |
High Limit Shutoff Control |
Minimum Outside Air (m3/s) |
Maximum Outside Air (m3/s) |
Return Air Temp Limit |
Return Air Enthalpy Limit |
Outside Air Temperature Limit
(C) |
Outside Air Enthalpy Limit
(C) |
| none |
|
|
|
|
|
|
|
Demand Controlled Ventilation using
VENTILATION:MECHANICAL
| |
Ventilation:Mechanical Name |
Outside Air Per
Person(m3/s-person) |
Outside Air Per Area
(m3/s-m2) |
| none |
|
|
|
Time Not Comfortable Based on Simple ASHRAE 55-2004
| |
Winter Clothes (hr) |
Summer Clothes (hr) |
Summer or Winter Clothes (hr) |
| SPACE1-1 |
429.00 |
1913.75 |
79.25 |
| SPACE2-1 |
739.25 |
1719.75 |
22.50 |
| SPACE3-1 |
482.00 |
1885.50 |
85.50 |
| SPACE4-1 |
588.25 |
2039.75 |
59.50 |
| SPACE5-1 |
14.75 |
2535.75 |
14.75 |
| PLENUM-1 |
0.00 |
0.00 |
0.00 |
| Facility |
1041.75 |
2564.75 |
97.00 |
Time Setpoint Not Met
| |
During Heating (hr) |
During Cooling (hr) |
During Occupied Heating
(hr) |
During Occupied Cooling
(hr) |
| SPACE1-1 |
321.00 |
45.25 |
35.00 |
45.25 |
| SPACE2-1 |
104.25 |
44.00 |
0.25 |
10.75 |
| SPACE3-1 |
297.50 |
0.75 |
36.25 |
0.75 |
| SPACE4-1 |
77.75 |
27.00 |
0.25 |
0.00 |
| SPACE5-1 |
292.25 |
1.00 |
13.75 |
1.00 |
| PLENUM-1 |
0.00 |
0.00 |
0.00 |
0.00 |
| Facility |
333.50 |
117.00 |
37.25 |
56.75 |
Component Sizing
Summary[LINK]
The Component Sizing Summary report includes details on
many of the HVAC components in the simulation. For each of the
components, one or more parameters are shown. Directly
following is an example of the report. The key used to obtain
this report is ComponentSizingSummary.
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
SINGLE DUCT:VAV:REHEAT
| |
Maximum air flow rate
[m3/s] |
Max Reheat Water Flow
[m3/s] |
| SPACE1-1 VAV REHEAT |
0.226630 |
0.000059 |
| SPACE2-1 VAV REHEAT |
0.176548 |
0.000046 |
| SPACE3-1 VAV REHEAT |
0.209331 |
0.000054 |
| SPACE4-1 VAV REHEAT |
0.222526 |
0.000058 |
| SPACE5-1 VAV REHEAT |
0.221695 |
0.000057 |
COIL:Water:SimpleHeating
| |
Max Water Flow Rate of Coil
[m3/s] |
Design Coil Load [W] |
UA of the Coil [W/delK] |
| SPACE1-1 ZONE COIL |
0.000059 |
2698.50 |
66.13 |
| SPACE2-1 ZONE COIL |
0.000046 |
2102.17 |
51.51 |
| SPACE3-1 ZONE COIL |
0.000054 |
2492.52 |
61.08 |
| SPACE4-1 ZONE COIL |
0.000058 |
2649.63 |
64.93 |
| SPACE5-1 ZONE COIL |
0.000057 |
2639.74 |
64.69 |
| OA HEATING COIL 1 |
0.000148 |
6812.27 |
84.72 |
| MAIN HEATING COIL 1 |
0.000075 |
3458.59 |
55.80 |
BRANCH
| |
Maximum Branch Flow Rate
[m3/s] |
| VAV SYS 1 MAIN BRANCH |
1.06 |
AIR PRIMARY LOOP
| |
Primary air design volumetric
flow rate [m3/s] |
| VAV SYS 1 |
1.06 |
CONTROLLER:OUTSIDE AIR
| |
maximum outside air flow rate
[m3/s] |
minimum outside air flow rate
[m3/s] |
| OA CONTROLLER 1 |
1.06 |
0.264118 |
COIL:Water:Cooling
| |
Max Water Flow Rate of Coil
[m3/s] |
Max Air Flow Rate of Coil
[m3/s] |
Design Air Inlet Temperature
[C] |
Design Air Outlet Temperature
[C] |
Design Water Inlet Temperature
[C] |
Design Air Inlet Humidity
Ratio |
Design Air Outlet Humidity
Ratio |
| OA COOLING COIL 1 |
0.001145 |
0.264118 |
30.01 |
11.00 |
7.00 |
0.014595 |
0.008000 |
| MAIN COOLING COIL 1 |
0.000916 |
1.06 |
21.55 |
12.80 |
7.00 |
0.009333 |
0.008000 |
FAN:SIMPLE:VARIABLEVOLUME
| |
Max Flow Rate [m3/s] |
Min Flow Rate [m3/s] |
| SUPPLY FAN 1 |
1.06 |
0.353263 |
CONTROLLER:SIMPLE
| |
Max Actuated Flow [m3/s] |
| OA CC CONTROLLER 1 |
0.001145 |
| OA HC CONTROLLER 1 |
0.000148 |
| CENTRAL COOLING COIL CONTROLLER
1 |
0.000916 |
| CENTRAL HEATING COIL CONTROLLER
1 |
0.000075 |
PLANT LOOP
| |
Maximum Loop Volumetric Flow
Rate [m3/s] |
Volume of the plant loop
[m3] |
| HOT WATER LOOP |
0.000497 |
0.559158 |
| CHILLED WATER LOOP |
0.002061 |
2.32 |
BOILER:SIMPLE
| |
Nominal Capacity [W] |
Design Boiler Water Flow Rate
[m3/s] |
| CENTRAL BOILER |
22853.43 |
0.000497 |
CHILLER:ELECTRIC
| |
Nominal Capacity [W] |
Design Evaporator Volumetric
Water Flow Rate [m3/s] |
| CENTRAL CHILLER |
34468.25 |
0.002061 |
PUMP:VARIABLE SPEED
| |
Rated Volumetric Flow Rate
[m3/s] |
Rated Power Consumption [W] |
| HW CIRC PUMP |
0.000497 |
126.98 |
| CW CIRC PUMP |
0.002061 |
526.69 |
Outdoor Air Summary[LINK]
The Outdoor Air Summary provides information for each zone
on the average and minimum ventilation provided.
The reports described so far in this section are displayed
when specified in the Output:Table:Predefined object. They are
either on or off and are not customizable. The next few types
of tabular reports are customizable. You can specify the
report variables being used in each one.
Directly following is an example of the report. The key
used to obtain this report is OutdoorAirSummary.
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Average Outside Air During Occupied Hours
| |
Average Number of Occupants |
Nominal Number of Occupants |
Zone Volume (m3) |
Mechanical Ventilation
(ach) |
Infiltration (ach) |
Simple Ventilation (ach) |
| SPACE1-1 |
9.50 |
11.00 |
239.25 |
0.365 |
0.050 |
0.000 |
| SPACE2-1 |
4.32 |
5.00 |
103.31 |
0.630 |
0.051 |
0.000 |
| SPACE3-1 |
9.50 |
11.00 |
239.25 |
0.338 |
0.050 |
0.000 |
| SPACE4-1 |
4.32 |
5.00 |
103.31 |
0.708 |
0.051 |
0.000 |
| SPACE5-1 |
17.27 |
20.00 |
447.68 |
0.214 |
0.052 |
0.000 |
Minimum Outside Air During Occupied Hours
| |
Average Number of Occupants |
Nominal Number of Occupants |
Zone Volume (m3) |
Mechanical Ventilation
(ach) |
Infiltration (ach) |
Simple Ventilation (ach) |
| SPACE1-1 |
9.50 |
11.00 |
239.25 |
0.000 |
0.000 |
0.000 |
| SPACE2-1 |
4.32 |
5.00 |
103.31 |
0.000 |
0.000 |
0.000 |
| SPACE3-1 |
9.50 |
11.00 |
239.25 |
0.000 |
0.000 |
0.000 |
| SPACE4-1 |
4.32 |
5.00 |
103.31 |
0.000 |
0.000 |
0.000 |
| SPACE5-1 |
17.27 |
20.00 |
447.68 |
0.000 |
0.000 |
0.000 |
Climatic Data Summary[LINK]
The Climatic Data Summary provides some statistics from the
.STAT file concerning the selected weather. The Stat file must
be available (it is included with all the weather files on the
EnergyPlus website) for the report to be fully produced.
Directly following is an example of the report. The key used
to obtain this report is ClimaticDataSummary.
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2009-02-10 13:27:45
SizingPeriod:DesignDay
| |
Maximum Dry Bulb (C) |
Daily Temperature Range (C) |
Humidity Value |
Humidity Type |
Wind Speed (m/s) |
Wind Direction |
| CHICAGO_IL_USA ANNUAL HEATING
99% DESIGN CONDITIONS DB |
-17.30 |
0.00 |
-17.30 |
WETBULB |
4.90 |
270.00 |
| CHICAGO_IL_USA ANNUAL COOLING 1%
DESIGN CONDITIONS DB/MCWB |
31.50 |
10.70 |
23.00 |
WETBULB |
5.30 |
230.00 |
Weather Statistics File
| |
Value |
| Reference |
USA_Chicago-OHare_TMY2 |
| Site:Location |
Chicago IL USA |
| Latitude |
N 41° 58’ |
| Longitude |
W 87° 54’ |
| Time Zone |
GMT -6.0 Hours |
| Elevation |
190m above sea level |
| Standard Pressure at
Elevation |
99063Pa |
| Data Source |
Release Test |
| WMO Station |
725300 |
| Design Conditions |
Climate Design Data 2005 ASHRAE
Handbook |
| Heating Design Temperature 99.6%
(C) |
-20.6 |
| Heating Design Temperature 99%
(C) |
-17.3 |
| Cooling Design Temperature 0.4%
(C) |
33.2 |
| Cooling Design Temperature 1%
(C) |
31.5 |
| Cooling Design Temperature 2%
(C) |
29.9 |
| Maximum Dry Bulb Temperature
(C) |
35.6° |
| Maximum Dry Bulb Occurs on |
Jul 9 |
| Minimum Dry Bulb Temperature
(C) |
-22.8° |
| Minimum Dry Bulb Occurs on |
Jan 7 |
| Maximum Dew Point Temperature
(C) |
25.6 |
| Maximum Dew Point Occurs on |
Aug 4 |
| Minimum Dew Point Temperature
(C) |
-28.9 |
| Minimum Dew Point Occurs on |
Dec 31 |
| Heating Degree-Days (base
10°C) |
1745 |
| Cooling Degree-Days (base
18°C) |
464 |
| Köppen Classification |
Dfa |
| Köppen Description |
Humid continental (hot summer,
cold winter, no dry season, lat. 30-60°N) |
| Köppen Recommendation |
Unbearably humid periods in
summer, but passive cooling is possible |
| ASHRAE Climate Zone |
5A |
| ASHRAE Description |
Cool-Humid |
Object Count Summary[LINK]
This report provides the count on the number of specific
objects in the file. Directly following is an example of the
report. The key used to obtain this report is
ObjectCountSummary.
Report: Object Count Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Surfaces by Class
| |
Total |
Outdoors |
| Wall |
24 |
8 |
| Floor |
10 |
5 |
| Roof |
6 |
1 |
| Internal Mass |
0 |
0 |
| Building Detached Shading |
0 |
0 |
| Fixed Detached Shading |
0 |
0 |
| Window |
6 |
6 |
| Door |
0 |
0 |
| Glass Door |
0 |
0 |
| Shading |
4 |
4 |
| Overhang |
0 |
0 |
| Fin |
0 |
0 |
| Tubular Daylighting Device
Dome |
0 |
0 |
| Tubular Daylighting Device
Diffuser |
0 |
0 |
HVAC
| |
Count |
| HVAC Air Loops |
1 |
| Conditioned Zones |
6 |
| Unconditioned Zones |
0 |
| Supply Plenums |
0 |
| Return Plenums |
1 |
Energy Meters[LINK]
This report provides the details on all the energy meters
generated by the simulation. Directly following is an example
of the report. The key used to obtain this report is
EnergyMeters.
Report: Energy Meters
For: Entire Facility
Timestamp: 2012-05-01 17:07:24
Annual and Peak Values - Electricity
| |
Electricity Annual Value
[GJ] |
Electricity Minimum Value
[W] |
Timestamp of Minimum |
Electricity Maximum Value
[W] |
Timestamp of Maximum |
| Electricity:Facility |
156.68 |
475.00 |
01-APR-00:15 |
20165.58 |
17-JUL-15:00 |
| Electricity:Building |
128.94 |
475.00 |
01-JAN-00:15 |
12000.00 |
01-JAN-10:15 |
| Electricity:Zone:SPACE1-1 |
27.23 |
100.32 |
01-JAN-00:15 |
2534.40 |
01-JAN-10:15 |
| InteriorLights:Electricity |
81.24 |
375.00 |
01-JAN-00:15 |
7500.00 |
01-JAN-10:15 |
| InteriorLights:Electricity:Zone:SPACE1-1 |
17.16 |
79.20 |
01-JAN-00:15 |
1584.00 |
01-JAN-10:15 |
| GeneralLights:InteriorLights:Electricity |
81.24 |
375.00 |
01-JAN-00:15 |
7500.00 |
01-JAN-10:15 |
| Electricity:Zone:SPACE2-1 |
11.76 |
43.32 |
01-JAN-00:15 |
1094.40 |
01-JAN-10:15 |
| InteriorLights:Electricity:Zone:SPACE2-1 |
7.41 |
34.20 |
01-JAN-00:15 |
684.00 |
01-JAN-10:15 |
| Electricity:Zone:SPACE3-1 |
27.23 |
100.32 |
01-JAN-00:15 |
2534.40 |
01-JAN-10:15 |
| InteriorLights:Electricity:Zone:SPACE3-1 |
17.16 |
79.20 |
01-JAN-00:15 |
1584.00 |
01-JAN-10:15 |
| Electricity:Zone:SPACE4-1 |
11.76 |
43.32 |
01-JAN-00:15 |
1094.40 |
01-JAN-10:15 |
| InteriorLights:Electricity:Zone:SPACE4-1 |
7.41 |
34.20 |
01-JAN-00:15 |
684.00 |
01-JAN-10:15 |
| Electricity:Zone:SPACE5-1 |
50.96 |
187.72 |
01-JAN-00:15 |
4742.40 |
01-JAN-10:15 |
| InteriorLights:Electricity:Zone:SPACE5-1 |
32.11 |
148.20 |
01-JAN-00:15 |
2964.00 |
01-JAN-10:15 |
| InteriorEquipment:Electricity |
47.70 |
100.00 |
01-JAN-00:15 |
4500.00 |
01-JAN-09:15 |
| InteriorEquipment:Electricity:Zone:SPACE1-1 |
10.07 |
21.12 |
01-JAN-00:15 |
950.40 |
01-JAN-09:15 |
| General:InteriorEquipment:Electricity |
47.70 |
100.00 |
01-JAN-00:15 |
4500.00 |
01-JAN-09:15 |
| InteriorEquipment:Electricity:Zone:SPACE2-1 |
4.35 |
9.12 |
01-JAN-00:15 |
410.40 |
01-JAN-09:15 |
| InteriorEquipment:Electricity:Zone:SPACE3-1 |
10.07 |
21.12 |
01-JAN-00:15 |
950.40 |
01-JAN-09:15 |
| InteriorEquipment:Electricity:Zone:SPACE4-1 |
4.35 |
9.12 |
01-JAN-00:15 |
410.40 |
01-JAN-09:15 |
| InteriorEquipment:Electricity:Zone:SPACE5-1 |
18.85 |
39.52 |
01-JAN-00:15 |
1778.40 |
01-JAN-09:15 |
| ElectricityPurchased:Facility |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| ElectricityPurchased:Plant |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| Cogeneration:ElectricityPurchased |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| ElectricitySurplusSold:Facility |
0.00 |
0.00 |
01-JAN-00:15 |
0.00 |
01-JAN-00:15 |
| ElectricitySurplusSold:Plant |
0.00 |
0.00 |
01-JAN-00:15 |
0.00 |
01-JAN-00:15 |
| Cogeneration:ElectricitySurplusSold |
0.00 |
0.00 |
01-JAN-00:15 |
0.00 |
01-JAN-00:15 |
| ElectricityNet:Facility |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| ElectricityNet:Plant |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| Cogeneration:ElectricityNet |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| Electricity:HVAC |
8.87 |
0.00 |
01-APR-00:15 |
655.43 |
17-JUL-15:00 |
| Fans:Electricity |
8.87 |
0.00 |
01-APR-00:15 |
655.43 |
17-JUL-15:00 |
| General:Fans:Electricity |
8.87 |
0.00 |
01-APR-00:15 |
655.43 |
17-JUL-15:00 |
| Electricity:Plant |
18.88 |
0.00 |
01-JAN-00:15 |
8053.88 |
19-JUL-16:00 |
| Heating:Electricity |
0.00 |
0.00 |
01-JAN-00:15 |
0.00 |
01-JAN-00:15 |
| Boiler
Parasitic:Heating:Electricity |
0.00 |
0.00 |
01-JAN-00:15 |
0.00 |
01-JAN-00:15 |
| Cooling:Electricity |
16.44 |
0.00 |
01-JAN-00:15 |
7478.31 |
19-JUL-16:00 |
| Pumps:Electricity |
2.44 |
0.00 |
01-JAN-00:15 |
575.73 |
24-JUL-20:00 |
| MYGENERALLIGHTS |
81.24 |
375.00 |
01-JAN-00:15 |
7500.00 |
01-JAN-10:15 |
| MYBUILDINGELECTRIC |
128.94 |
475.00 |
01-JAN-00:15 |
12000.00 |
01-JAN-10:15 |
| MYBUILDINGOTHER |
47.70 |
375.00 |
01-JAN-00:15 |
7500.00 |
01-JAN-10:15 |
Annual and Peak Values - Gas
| |
Gas Annual Value [GJ] |
Gas Minimum Value [W] |
Timestamp of Minimum |
Gas Maximum Value [W] |
Timestamp of Maximum |
| Gas:Facility |
68.82 |
0.00 |
01-JAN-00:15 |
42092.68 |
01-FEB-06:15 |
| Gas:Plant |
68.82 |
0.00 |
01-JAN-00:15 |
42092.68 |
01-FEB-06:15 |
| Heating:Gas |
68.82 |
0.00 |
01-JAN-00:15 |
42092.68 |
01-FEB-06:15 |
| Boiler:Heating:Gas |
68.82 |
0.00 |
01-JAN-00:15 |
42092.68 |
01-FEB-06:15 |
Annual and Peak Values - Cooling
| |
Cooling Annual Value [GJ] |
Cooling Minimum Value [W] |
Timestamp of Minimum |
Cooling Maximum Value [W] |
Timestamp of Maximum |
| PlantLoopCoolingDemand:Facility |
62.41 |
0.00 |
01-JAN-00:15 |
27050.46 |
17-JUL-15:00 |
| PlantLoopCoolingDemand:HVAC |
62.41 |
0.00 |
01-JAN-00:15 |
27050.46 |
17-JUL-15:00 |
| CoolingCoils:PlantLoopCoolingDemand |
62.41 |
0.00 |
01-JAN-00:15 |
27050.46 |
17-JUL-15:00 |
Annual and Peak Values - Water
| |
Annual Value [m3] |
Minimum Value [m3/s] |
Timestamp of Minimum |
Maximum Value [m3/s] |
Timestamp of Maximum |
| None |
|
|
|
|
|
Annual and Peak Values - Other by Weight/Mass
| |
Annual Value [kg] |
Minimum Value [kg/s] |
Timestamp of Minimum |
Maximum Value [kg/s] |
Timestamp of Maximum |
| Carbon Equivalent:Facility |
0.00 |
0.000 |
01-JAN-00:15 |
0.000 |
01-JAN-00:15 |
| CarbonEquivalentEmissions:Carbon
Equivalent |
0.00 |
0.000 |
01-JAN-00:15 |
0.000 |
01-JAN-00:15 |
Annual and Peak Values - Other Volumetric
| |
Annual Value [m3] |
Minimum Value [m3/s] |
Timestamp of Minimum |
Maximum Value [m3/s] |
Timestamp of Maximum |
| None |
|
|
|
|
|
Annual and Peak Values - Other Liquid/Gas
| |
Annual Value [L] |
Minimum Value [L] |
Timestamp of Minimum |
Maximum Value [L] |
Timestamp of Maximum |
| None |
|
|
|
|
|
Annual and Peak Values - Other
| |
Annual Value [GJ] |
Minimum Value [W] |
Timestamp of Minimum |
Maximum Value [W] |
Timestamp of Maximum |
| EnergyTransfer:Facility |
415.65 |
0.00 |
01-APR-00:15 |
102784.74 |
17-JUL-15:00 |
| EnergyTransfer:Building |
97.60 |
0.00 |
01-APR-00:15 |
21488.05 |
28-JAN-06:15 |
| EnergyTransfer:Zone:PLENUM-1 |
22.50 |
0.00 |
01-APR-00:15 |
4218.21 |
07-JAN-08:15 |
| Heating:EnergyTransfer |
42.23 |
0.00 |
19-MAR-15:30 |
21488.05 |
28-JAN-06:15 |
| Heating:EnergyTransfer:Zone:PLENUM-1 |
19.63 |
0.00 |
16-JAN-21:15 |
4218.21 |
07-JAN-08:15 |
| Cooling:EnergyTransfer |
55.38 |
0.00 |
01-JAN-06:15 |
13937.19 |
17-JUL-15:00 |
| Cooling:EnergyTransfer:Zone:PLENUM-1 |
2.87 |
0.00 |
01-JAN-00:15 |
2539.33 |
18-JUL-15:00 |
| EnergyTransfer:Zone:SPACE1-1 |
17.91 |
0.00 |
01-APR-00:15 |
4012.66 |
30-DEC-06:15 |
| Heating:EnergyTransfer:Zone:SPACE1-1 |
6.51 |
0.00 |
01-JAN-10:15 |
4012.66 |
30-DEC-06:15 |
| Cooling:EnergyTransfer:Zone:SPACE1-1 |
11.40 |
0.00 |
01-JAN-00:15 |
3138.67 |
27-SEP-16:00 |
| EnergyTransfer:Zone:SPACE2-1 |
10.67 |
0.00 |
01-APR-00:15 |
3432.93 |
30-DEC-06:15 |
| Heating:EnergyTransfer:Zone:SPACE2-1 |
2.42 |
0.00 |
01-JAN-01:30 |
3432.93 |
30-DEC-06:15 |
| Cooling:EnergyTransfer:Zone:SPACE2-1 |
8.25 |
0.00 |
01-JAN-00:15 |
2460.04 |
06-SEP-10:15 |
| EnergyTransfer:Zone:SPACE3-1 |
16.79 |
0.00 |
01-APR-00:15 |
3788.83 |
30-DEC-06:15 |
| Heating:EnergyTransfer:Zone:SPACE3-1 |
6.09 |
0.00 |
01-JAN-12:00 |
3788.83 |
30-DEC-06:15 |
| Cooling:EnergyTransfer:Zone:SPACE3-1 |
10.70 |
0.00 |
01-JAN-00:15 |
2807.57 |
19-JUL-11:00 |
| EnergyTransfer:Zone:SPACE4-1 |
9.82 |
0.00 |
01-APR-00:15 |
3746.68 |
28-JAN-06:15 |
| Heating:EnergyTransfer:Zone:SPACE4-1 |
2.98 |
0.00 |
01-JAN-01:30 |
3746.68 |
28-JAN-06:15 |
| Cooling:EnergyTransfer:Zone:SPACE4-1 |
6.85 |
0.00 |
01-JAN-00:15 |
2281.99 |
25-JUN-17:15 |
| EnergyTransfer:Zone:SPACE5-1 |
19.91 |
0.00 |
01-APR-00:15 |
4037.31 |
30-DEC-06:15 |
| Heating:EnergyTransfer:Zone:SPACE5-1 |
4.60 |
0.00 |
01-JAN-00:15 |
4037.31 |
30-DEC-06:15 |
| Cooling:EnergyTransfer:Zone:SPACE5-1 |
15.31 |
0.00 |
01-JAN-06:15 |
2611.53 |
17-JUL-15:00 |
| EnergyTransfer:HVAC |
117.82 |
0.00 |
01-JAN-00:15 |
31769.77 |
07-JAN-06:15 |
| HeatingCoils:EnergyTransfer |
55.41 |
0.00 |
01-JAN-00:15 |
31769.77 |
07-JAN-06:15 |
| PlantLoopHeatingDemand:Facility |
55.41 |
0.00 |
01-JAN-00:15 |
31769.77 |
07-JAN-06:15 |
| PlantLoopHeatingDemand:HVAC |
55.41 |
0.00 |
01-JAN-00:15 |
31769.77 |
07-JAN-06:15 |
| HeatingCoils:PlantLoopHeatingDemand |
55.41 |
0.00 |
01-JAN-00:15 |
31769.77 |
07-JAN-06:15 |
| CoolingCoils:EnergyTransfer |
62.41 |
0.00 |
01-JAN-00:15 |
27050.46 |
17-JUL-15:00 |
| EnergyTransfer:Plant |
200.23 |
0.00 |
01-JAN-00:15 |
62116.41 |
19-JUL-16:00 |
| Boilers:EnergyTransfer |
55.06 |
0.00 |
01-JAN-00:15 |
33674.15 |
28-MAR-06:15 |
| Chillers:EnergyTransfer |
64.37 |
0.00 |
01-JAN-00:15 |
27319.05 |
19-JUL-16:00 |
| HeatRejection:EnergyTransfer |
80.81 |
0.00 |
01-JAN-00:15 |
34797.36 |
19-JUL-16:00 |
Sensible Heat Gain
Summary[LINK]
This report is more fully described in the Input Output
Reference but represents the major heat gain components for
each zone as well as the HVAC loads satisfied. Directly
following is an example of the report. The key used to obtain
this report is SensibleHeatGainSummary.
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2011-09-09 08:02:03
Annual Building
Sensible Heat Gain Components
| |
HVAC Input Sensible Air Heating
[GJ] |
HVAC Input Sensible Air Cooling
[GJ] |
HVAC Input Heated Surface
Heating [GJ] |
HVAC Input Cooled Surface
Cooling [GJ] |
People Sensible Heat Addition
[GJ] |
Lights Sensible Heat Addition
[GJ] |
Equipment Sensible Heat Addition
[GJ] |
Window Heat Addition [GJ] |
Interzone Air Transfer Heat
Addition [GJ] |
Infiltration Heat Addition
[GJ] |
Opaque Surface Conduction and
Other Heat Addition [GJ] |
Equipment Sensible Heat Removal
[GJ] |
Window Heat Removal [GJ] |
Interzone Air Transfer Heat
Removal [GJ] |
Infiltration Heat Removal
[GJ] |
Opaque Surface Conduction and
Other Heat Removal [GJ] |
| SPACE1-1 |
0.096 |
-0.070 |
0.000 |
0.000 |
0.035 |
0.131 |
0.065 |
0.220 |
0.000 |
0.000 |
0.001 |
0.000 |
-0.078 |
0.000 |
-0.004 |
-0.395 |
| SPACE2-1 |
0.051 |
-0.038 |
0.000 |
0.000 |
0.014 |
0.056 |
0.028 |
0.173 |
0.000 |
0.000 |
0.001 |
0.000 |
-0.029 |
0.000 |
-0.002 |
-0.253 |
| SPACE3-1 |
0.093 |
-0.030 |
0.000 |
0.000 |
0.034 |
0.131 |
0.065 |
0.157 |
0.000 |
0.000 |
0.000 |
0.000 |
-0.082 |
0.000 |
-0.004 |
-0.363 |
| SPACE4-1 |
0.055 |
-0.015 |
0.000 |
0.000 |
0.015 |
0.056 |
0.028 |
0.105 |
0.000 |
0.000 |
0.000 |
0.000 |
-0.032 |
0.000 |
-0.002 |
-0.211 |
| SPACE5-1 |
0.032 |
-0.072 |
0.000 |
0.000 |
0.073 |
0.244 |
0.121 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
-0.007 |
-0.392 |
| PLENUM-1 |
0.118 |
-0.024 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
-0.094 |
| Total Facility |
0.445 |
-0.248 |
0.000 |
0.000 |
0.170 |
0.618 |
0.307 |
0.655 |
0.000 |
0.000 |
0.002 |
0.000 |
-0.221 |
0.000 |
-0.017 |
-1.709 |
Peak Cooling Sensible Heat Gain Components
| |
Time of Peak |
HVAC Input Sensible Air Heating
[W] |
HVAC Input Sensible Air Cooling
[W] |
HVAC Input Heated Surface
Heating [W] |
HVAC Input Cooled Surface
Cooling [W] |
People Sensible Heat Addition
[W] |
Lights Sensible Heat Addition
[W] |
Equipment Sensible Heat Addition
[W] |
Window Heat Addition [W] |
Interzone Air Transfer Heat
Addition [W] |
Infiltration Heat Addition
[W] |
Opaque Surface Conduction and
Other Heat Addition [W] |
Equipment Sensible Heat Removal
[W] |
Window Heat Removal [W] |
Interzone Air Transfer Heat
Removal [W] |
Infiltration Heat Removal
[W] |
Opaque Surface Conduction and
Other Heat Removal [W] |
| SPACE1-1 |
14-JAN-15:00 |
0.00 |
-3502.16 |
0.00 |
0.00 |
724.60 |
1584.00 |
739.20 |
9347.85 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-8893.49 |
| SPACE2-1 |
14-JAN-10:07 |
0.00 |
-1738.94 |
0.00 |
0.00 |
345.99 |
684.00 |
410.40 |
4684.27 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-4385.71 |
| SPACE3-1 |
14-JAN-14:45 |
0.00 |
-1095.49 |
0.00 |
0.00 |
761.13 |
1584.00 |
844.80 |
356.87 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-2451.31 |
| SPACE4-1 |
14-JAN-16:00 |
0.00 |
-736.19 |
0.00 |
0.00 |
345.95 |
684.00 |
228.00 |
1157.98 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-1679.74 |
| SPACE5-1 |
14-JAN-13:35 |
0.00 |
-2315.43 |
0.00 |
0.00 |
1135.19 |
2667.60 |
1778.40 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-3265.77 |
| PLENUM-1 |
07-JUL-19:46 |
0.00 |
-1579.40 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
1579.40 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Total Facility |
14-JAN-15:00 |
0.00 |
-7822.86 |
0.00 |
0.00 |
3561.18 |
7500.00 |
3500.00 |
10470.76 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-17209.08 |
Peak Heating Sensible Heat Gain Components
| |
Time of Peak |
HVAC Input Sensible Air Heating
[W] |
HVAC Input Sensible Air Cooling
[W] |
HVAC Input Heated Surface
Heating [W] |
HVAC Input Cooled Surface
Cooling [W] |
People Sensible Heat Addition
[W] |
Lights Sensible Heat Addition
[W] |
Equipment Sensible Heat Addition
[W] |
Window Heat Addition [W] |
Interzone Air Transfer Heat
Addition [W] |
Infiltration Heat Addition
[W] |
Opaque Surface Conduction and
Other Heat Addition [W] |
Equipment Sensible Heat Removal
[W] |
Window Heat Removal [W] |
Interzone Air Transfer Heat
Removal [W] |
Infiltration Heat Removal
[W] |
Opaque Surface Conduction and
Other Heat Removal [W] |
| SPACE1-1 |
14-JAN-07:00 |
10652.50 |
0.00 |
0.00 |
0.00 |
0.00 |
79.20 |
21.12 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-1551.57 |
0.00 |
0.00 |
-9201.25 |
| SPACE2-1 |
14-JAN-07:00 |
7816.55 |
0.00 |
0.00 |
0.00 |
0.00 |
34.20 |
9.12 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-594.65 |
0.00 |
0.00 |
-7265.22 |
| SPACE3-1 |
14-JAN-07:00 |
11495.41 |
0.00 |
0.00 |
0.00 |
0.00 |
79.20 |
21.12 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-1539.09 |
0.00 |
0.00 |
-10056.64 |
| SPACE4-1 |
14-JAN-07:00 |
8837.62 |
0.00 |
0.00 |
0.00 |
0.00 |
34.20 |
9.12 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-604.20 |
0.00 |
0.00 |
-8276.74 |
| SPACE5-1 |
14-JAN-07:00 |
12359.25 |
0.00 |
0.00 |
0.00 |
0.00 |
148.20 |
39.52 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-12546.97 |
| PLENUM-1 |
14-JAN-07:18 |
5275.99 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-5275.99 |
| Total Facility |
14-JAN-07:15 |
55720.39 |
0.00 |
0.00 |
0.00 |
0.00 |
375.00 |
100.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-4289.51 |
0.00 |
0.00 |
-51905.88 |
Standard 62.1 Summary[LINK]
This report is more fully described in the Input Output
Reference. The Standard 62.1 Summary produces a report that is
consistent with many of the outputs needed when doing
calculations consistent with ASHRAE Standard 62.1-2010. The
report is generated when sizing calculations are specified.
The abbreviations used in the report are consistent with the
abbreviations used in Appendix A4 of the Standard. Directly
following is an example of the report. The key used to obtain
this report is Standard62.1Summary.
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2012-04-20 12:00:57
System Ventilation Requirements for Cooling
| |
Sum of Zone Primary Air Flow -
Vpz-sum [m3/s] |
System Population - Ps |
Sum of Zone Population -
Pz-sum |
Occupant Diversity - D |
Uncorrected Outdoor Air Intake
Airflow - Vou [m3/s] |
System Primary Airflow - Vps
[m3/s] |
Average Outdoor Air Fraction -
Xs |
System Ventilation Efficiency -
Ev |
Outdoor Air Intake Flow - Vot
[m3/s] |
Percent Outdoor Air - %OA |
| VAV SYS 1 |
1.05 |
52.00 |
52.00 |
1.00 |
0.26 |
1.05 |
0.252 |
1.000 |
0.27 |
0.26 |
System Ventilation Requirements for Heating
| |
Sum of Zone Primary Air Flow -
Vpz-sum [m3/s] |
System Population - Ps |
Sum of Zone Population -
Pz-sum |
Occupant Diversity - D |
Uncorrected Outdoor Air Intake
Airflow - Vou [m3/s] |
System Primary Airflow - Vps
[m3/s] |
Average Outdoor Air Fraction -
Xs |
System Ventilation Efficiency -
Ev |
Outdoor Air Intake Flow Vot
[m3/s] |
Percent Outdoor Air - %OA |
| VAV SYS 1 |
1.05 |
0.00 |
0.00 |
1.00 |
0.26 |
0.43 |
0.967 |
1.000 |
0.27 |
0.26 |
Zone
Ventilation Parameters
| |
AirLoop Name |
People Outdoor Air Rate - Rp
[m3/s-person] |
Zone Population - Pz |
Area Outdoor Air Rate - Ra
[m3/s-m2] |
Zone Floor Area - Az [m2] |
Breathing Zone Outdoor Airflow -
Vbz [m3/s] |
Cooling Zone Air Distribution
Effectiveness - Ez-clg |
Cooling Zone Outdoor Airflow -
Voz-clg [m3/s] |
Heating Zone Air Distribution
Effectiveness - Ez-htg |
Heating Zone Outdoor Airflow -
Voz-htg [m3/s] |
| SPACE1-1 |
VAV SYS 1 |
0.002360 |
11.00 |
0.000305 |
99.16 |
0.0562 |
0.900 |
0.0624 |
|
|
| SPACE2-1 |
VAV SYS 1 |
0.002360 |
5.00 |
0.000305 |
42.73 |
0.0248 |
0.900 |
0.0276 |
|
|
| SPACE3-1 |
VAV SYS 1 |
0.002360 |
11.00 |
0.000305 |
96.48 |
0.0554 |
1.000 |
0.0554 |
|
|
| SPACE4-1 |
VAV SYS 1 |
0.002360 |
5.00 |
0.000305 |
42.73 |
0.0248 |
1.000 |
0.0248 |
|
|
| SPACE5-1 |
VAV SYS 1 |
0.002360 |
20.00 |
0.000305 |
182.49 |
0.1029 |
1.000 |
0.1029 |
|
|
System Ventilation Parameters
| |
People Outdoor Air Rate - Rp
[m3/s-person] |
Sum of Zone Population -
Pz-sum |
Area Outdoor Air Rate - Ra
[m3/s-m2] |
Sum of Zone Floor Area - Az-sum
[m2] |
Breathing Zone Outdoor Airflow -
Vbz [m3/s] |
Cooling Zone Outdoor Airflow -
Voz-clg [m3/s] |
Heating Zone Outdoor Airflow -
Voz-htg [m3/s] |
| VAV SYS 1 |
0.002360 |
52.00 |
0.000305 |
463.60 |
0.2641 |
0.2731 |
0.0000 |
Zone
Ventilation Calculations for Cooling Design
| |
AirLoop Name |
Box Type |
Zone Primary Airflow - Vpz
[m3/s] |
Zone Discharge Airflow - Vdz
[m3/s] |
Minimum Zone Primary Airflow -
Vpz-min [m3/s] |
Zone Outdoor Airflow Cooling -
Voz-clg [m3/s] |
Primary Outdoor Air Fraction -
Zpz |
Primary Air Fraction - Ep |
Secondary Recirculation
Fraction- Er |
Supply Air Fraction- Fa |
Mixed Air Fraction - Fb |
Outdoor Air Fraction - Fc |
Zone Ventilation Efficiency -
Evz |
| SPACE1-1 |
VAV SYS 1 |
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT |
0.22 |
0.22 |
0.08 |
0.0624 |
0.280 |
1.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.900 |
| SPACE2-1 |
VAV SYS 1 |
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT |
0.19 |
0.19 |
0.03 |
0.0276 |
0.147 |
1.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.900 |
| SPACE3-1 |
VAV SYS 1 |
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT |
0.21 |
0.21 |
0.07 |
0.0554 |
0.263 |
1.000 |
0.000 |
0.000 |
0.000 |
0.000 |
1.000 |
| SPACE4-1 |
VAV SYS 1 |
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT |
0.21 |
0.21 |
0.03 |
0.0248 |
0.120 |
1.000 |
0.000 |
0.000 |
0.000 |
0.000 |
1.000 |
| SPACE5-1 |
VAV SYS 1 |
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT |
0.22 |
0.22 |
0.14 |
0.1029 |
0.465 |
1.000 |
0.000 |
0.000 |
0.000 |
0.000 |
1.000 |
System Ventilation Calculations for Cooling Design
| |
Sum of Zone Primary Airflow -
Vpz-sum [m3/s] |
System Primary Airflow - Vps
[m3/s] |
Sum of Zone Discharge Airflow -
Vdz-sum [m3/s] |
Minimum Zone Primary Airflow -
Vpz-min [m3/s] |
Zone Outdoor Airflow Cooling -
Voz-clg [m3/s] |
Zone Ventilation Efficiency -
Evz-min |
| VAV SYS 1 |
1.05 |
1.05 |
1.05 |
0.19 |
0.2731 |
1.000 |
Zone
Ventilation Calculations for Heating Design
| |
AirLoop Name |
Box Type |
Zone Primary Airflow - Vpz
[m3/s] |
Zone Discharge Airflow - Vdz
[m3/s] |
Minimum Zone Primary Airflow -
Vpz-min [m3/s] |
Zone Outdoor Airflow Heating -
Voz-htg [m3/s] |
Primary Outdoor Air Fraction -
Zpz |
Primary Air Fraction - Ep |
Secondary Recirculation
Fraction- Er |
Supply Air Fraction- Fa |
Mixed Air Fraction - Fb |
Outdoor Air Fraction - Fc |
Zone Ventilation Efficiency -
Evz |
| None |
|
|
|
|
|
|
|
|
|
|
|
|
|
System Ventilation Calculations for Heating Design
| |
Sum of Zone Primary Airflow -
Vpz-sum [m3/s] |
System Primary Airflow - Vps
[m3/s] |
Sum of Zone Discharge Airflow -
Vdz-sum [m3/s] |
Minimum Zone Primary Airflow -
Vpz-min [m3/s] |
Zone Outdoor Airflow Heating -
Voz-htg [m3/s] |
Zone Ventilation Efficiency -
Evz-min |
| VAV SYS 1 |
1.05 |
1.05 |
1.05 |
0.18+309 |
0.0000 |
1.000 |
Zone Component Loads
Summary[LINK]
The Zone
Component Loads Summary provides an estimate of the heating
and cooling peak loads for each zone broken down into various
components. This report may help determine which components of
the load have the largest impact for the heating and cooling
peak design conditions. When specified, the Zone
Component Loads Summary report is created for each zone that
is conditioned. The Sensible-Delayed column of the summary is
only an estimate based on a procedure described in the
Engineering Reference documentation. An intermediate
calculation in this procedure is the decay curves that are
shown in the the EIO file when Output:Surfaces:List
is set to show DecayCurvesFromZoneComponentLoads. The
difference between the peak design sensible load and the
estimated instant + delayed sensible load (as shown in the
Peak Conditions subtable) is an indication of how
consistent the overall total estimate may be to the computed
total peak loads for the zone. When the report is called the
zone sizing calculations are repeated twice so this may result
in longer simulation times. The key used to obtain this report
is ZoneComponentLoadSummary.
Report: ZoneComponentLoadSummary
For: SPACE1-1
Timestamp: 2012-09-21 15:48:46
Estimated Cooling Peak Load Components
| |
Sensible - Instant [W] |
Sensible - Delayed [W] |
Sensible - Return Air [W] |
Latent [W] |
Total [W] |
%Grand Total |
| People |
533.03 |
272.38 |
|
528.17 |
1333.58 |
30.78 |
| Lights |
15.84 |
1424.81 |
316.80 |
|
1757.45 |
40.57 |
| Equipment |
517.44 |
318.36 |
|
0.00 |
835.80 |
19.29 |
| Refrigeration |
0.00 |
|
0.00 |
0.00 |
0.00 |
0.00 |
| Water Use Equipment |
0.00 |
|
|
|
0.00 |
0.00 |
| HVAC Equipment Losses |
0.00 |
0.00 |
|
|
0.00 |
0.00 |
| Power Generation Equipment |
0.00 |
0.00 |
|
|
0.00 |
0.00 |
| Infiltration |
34.65 |
|
|
69.37 |
104.03 |
2.40 |
| Zone Ventilation |
0.00 |
|
|
0.00 |
0.00 |
0.00 |
| Interzone Mixing |
0.00 |
|
|
0.00 |
0.00 |
0.00 |
| Roof |
|
0.00 |
|
|
0.00 |
0.00 |
| Interzone Ceiling |
|
132.59 |
|
|
132.59 |
3.06 |
| Other Roof |
|
0.00 |
|
|
0.00 |
0.00 |
| Exterior Wall |
|
451.39 |
|
|
451.39 |
10.42 |
| Interzone Wall |
|
-511.9 |
|
|
-511.9 |
-11.8 |
| Ground Contact Wall |
|
0.00 |
|
|
0.00 |
0.00 |
| Other Wall |
|
0.00 |
|
|
0.00 |
0.00 |
| Exterior Floor |
|
0.00 |
|
|
0.00 |
0.00 |
| Interzone Floor |
|
0.00 |
|
|
0.00 |
0.00 |
| Ground Contact Floor |
|
-1745.4 |
|
|
-1745.4 |
-40.3 |
| Other Floor |
|
0.00 |
|
|
0.00 |
0.00 |
| Fenestration Conduction |
655.17 |
|
|
|
655.17 |
15.12 |
| Fenestration Solar |
- |
1319.55 |
|
|
1319.55 |
30.46 |
| Opaque Door |
|
0.00 |
|
|
0.00 |
0.00 |
| Grand Total |
1756.13 |
1661.76 |
316.80 |
597.54 |
4332.24 |
|
Cooling Peak Conditions
| |
Value |
| Time of Peak Load |
7/21 16:00:00 |
| Outside Dry Bulb Temperature
[C] |
30.86 |
| Outside Wet Bulb Temperature
[C] |
23.10 |
| Outside Humidity Ratio at Peak
[kgWater/kgAir] |
0.01459 |
| Zone Dry Bulb Temperature
[C] |
24.00 |
| Zone Relative Humdity [%] |
47.16 |
| Zone Humidity Ratio at Peak
[kgWater/kgAir] |
0.00876 |
| Peak Design Sensible Load
[W] |
3187.17 |
| Estimated Instant + Delayed
Sensible Load [W] |
3417.89 |
| Difference [W] |
-230.7 |
Estimated Heating Peak Load Components
| |
Sensible - Instant [W] |
Sensible - Delayed [W] |
Sensible - Return Air [W] |
Latent [W] |
Total [W] |
%Grand Total |
| People |
0.00 |
0.00 |
|
0.00 |
0.00 |
0.00 |
| Lights |
0.79 |
85.74 |
15.84 |
|
102.37 |
-3.3 |
| Equipment |
14.78 |
9.37 |
|
0.00 |
24.15 |
-0.8 |
| Refrigeration |
0.00 |
|
0.00 |
0.00 |
0.00 |
0.00 |
| Water Use Equipment |
0.00 |
|
|
|
0.00 |
0.00 |
| HVAC Equipment Losses |
0.00 |
0.00 |
|
|
0.00 |
0.00 |
| Power Generation Equipment |
0.00 |
0.00 |
|
|
0.00 |
0.00 |
| Infiltration |
-222.8 |
|
|
-93.8 |
-316.6 |
10.07 |
| Zone Ventilation |
0.00 |
|
|
0.00 |
0.00 |
0.00 |
| Interzone Mixing |
0.00 |
|
|
0.00 |
0.00 |
0.00 |
| Roof |
|
0.00 |
|
|
0.00 |
0.00 |
| Interzone Ceiling |
|
-1027.9 |
|
|
-1027.9 |
32.70 |
| Other Roof |
|
0.00 |
|
|
0.00 |
0.00 |
| Exterior Wall |
|
-762.5 |
|
|
-762.5 |
24.26 |
| Interzone Wall |
|
102.80 |
|
|
102.80 |
-3.3 |
| Ground Contact Wall |
|
0.00 |
|
|
0.00 |
0.00 |
| Other Wall |
|
0.00 |
|
|
0.00 |
0.00 |
| Exterior Floor |
|
0.00 |
|
|
0.00 |
0.00 |
| Interzone Floor |
|
0.00 |
|
|
0.00 |
0.00 |
| Ground Contact Floor |
|
889.07 |
|
|
889.07 |
-28.3 |
| Other Floor |
|
0.00 |
|
|
0.00 |
0.00 |
| Fenestration Conduction |
-2155.0 |
|
|
|
-2155.0 |
68.55 |
| Fenestration Solar |
- |
0.00 |
|
|
0.00 |
0.00 |
| Opaque Door |
|
0.00 |
|
|
0.00 |
0.00 |
| Grand Total |
-2362.2 |
-703.3 |
15.84 |
-93.8 |
-3143.5 |
|
Heating Peak Conditions
| |
Value |
| Time of Peak Load |
1/21 20:15:00 |
| Outside Dry Bulb Temperature
[C] |
-17.3 |
| Outside Wet Bulb Temperature
[C] |
-19.0 |
| Outside Humidity Ratio at Peak
[kgWater/kgAir] |
0.00084 |
| Zone Dry Bulb Temperature
[C] |
23.00 |
| Zone Relative Humdity [%] |
43.89 |
| Zone Humidity Ratio at Peak
[kgWater/kgAir] |
0.00766 |
| Peak Design Sensible Load
[W] |
-3077.1 |
| Estimated Instant + Delayed
Sensible Load [W] |
-3065.5 |
| Difference [W] |
-11.6 |
Output:Table:TimeBins[LINK]
A TimeBins report shows a grid of the number of hours that
specific report variable spend in a range of values. The first
table is broken into two parts. The first part is monthly and
the second part is for each hour of the day. The columns show
the range of values. A second table is provided to show some
statistics on the report variable for the entire year
including the maximum and minimum. These statistics are
helpful in setting the field values for the interval in the
Output Table:TimeBins object. Due to this, it is often
necessary to run two simulations to fully utilize the TimeBins
report with the first run used to find the minimum and maximum
of the variable, these values are then used in the TimeBins
object and the second run a better table of binned results are
displayed.
Report: PURCHASEDCOOLING:FACILITY J per second
For: Meter
Timestamp: 2006-08-30 07:48:55
Values in table are in hours.
| |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
|
|
| Interval Start |
less than |
0.<= |
2000.<= |
4000.<= |
6000.<= |
8000.<= |
10000.<= |
12000.<= |
14000.<= |
16000.<= |
18000.<= |
equal to or more than |
Row |
| Interval End |
0. |
2000.> |
4000.> |
6000.> |
8000.> |
10000.> |
12000.> |
14000.> |
16000.> |
18000.> |
20000.> |
20000. |
Total |
| January |
0.00 |
744.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
744.00 |
| February |
0.00 |
672.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
672.00 |
| March |
0.00 |
744.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
744.00 |
| April |
0.00 |
524.17 |
40.67 |
40.33 |
45.67 |
45.50 |
19.67 |
4.00 |
0.00 |
0.00 |
0.00 |
0.00 |
720.00 |
| May |
0.00 |
480.33 |
44.50 |
55.50 |
41.00 |
53.50 |
38.17 |
20.67 |
10.33 |
0.00 |
0.00 |
0.00 |
744.00 |
| June |
0.00 |
393.50 |
31.83 |
55.33 |
19.83 |
53.00 |
65.83 |
62.83 |
24.00 |
13.83 |
0.00 |
0.00 |
720.00 |
| July |
0.00 |
372.67 |
30.83 |
40.83 |
45.67 |
53.83 |
42.83 |
48.33 |
45.33 |
47.83 |
15.83 |
0.00 |
744.00 |
| August |
0.00 |
373.50 |
24.50 |
37.17 |
44.50 |
64.50 |
56.67 |
50.67 |
52.33 |
35.00 |
5.17 |
0.00 |
744.00 |
| September |
0.00 |
406.33 |
52.00 |
42.50 |
14.83 |
54.50 |
64.67 |
54.50 |
27.17 |
3.50 |
0.00 |
0.00 |
720.00 |
| October |
0.00 |
744.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
744.00 |
| November |
0.00 |
720.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
720.00 |
| December |
0.00 |
744.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
744.00 |
| 12:01 to 1:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 1:01 to 2:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 2:01 to 3:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 3:01 to 4:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 4:01 to 5:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 5:01 to 6:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 6:01 to 7:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 7:01 to 8:00 am |
0.00 |
294.33 |
33.83 |
25.00 |
5.17 |
2.17 |
1.67 |
1.17 |
1.00 |
0.67 |
0.00 |
0.00 |
365.00 |
| 8:01 to 9:00 am |
0.00 |
238.00 |
14.17 |
16.50 |
17.00 |
40.33 |
29.67 |
9.33 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 9:01 to 10:00 am |
0.00 |
231.83 |
14.50 |
13.00 |
21.83 |
38.83 |
31.83 |
12.00 |
1.17 |
0.00 |
0.00 |
0.00 |
365.00 |
| 10:01 to 11:00 am |
0.00 |
226.33 |
14.00 |
12.50 |
17.50 |
36.50 |
31.33 |
22.17 |
4.67 |
0.00 |
0.00 |
0.00 |
365.00 |
| 11:01 to 12:00 pm |
0.00 |
221.33 |
12.17 |
13.00 |
14.50 |
30.67 |
33.50 |
27.83 |
11.00 |
1.00 |
0.00 |
0.00 |
365.00 |
| 12:01 to 1:00 pm |
0.00 |
211.00 |
18.00 |
14.00 |
14.00 |
29.17 |
32.33 |
25.67 |
17.67 |
3.17 |
0.00 |
0.00 |
365.00 |
| 1:01 to 2:00 pm |
0.00 |
208.00 |
15.00 |
15.33 |
11.00 |
22.17 |
27.83 |
27.50 |
26.83 |
10.83 |
0.50 |
0.00 |
365.00 |
| 2:01 to 3:00 pm |
0.00 |
205.33 |
11.83 |
18.17 |
11.00 |
17.50 |
23.17 |
29.50 |
26.17 |
18.17 |
4.17 |
0.00 |
365.00 |
| 3:01 to 4:00 pm |
0.00 |
203.00 |
9.50 |
17.67 |
14.00 |
16.17 |
20.67 |
30.17 |
22.00 |
24.83 |
7.00 |
0.00 |
365.00 |
| 4:01 to 5:00 pm |
0.00 |
201.17 |
10.83 |
18.83 |
13.67 |
16.33 |
19.50 |
29.67 |
22.83 |
25.17 |
7.00 |
0.00 |
365.00 |
| 5:01 to 6:00 pm |
0.00 |
200.00 |
13.50 |
21.33 |
14.83 |
22.17 |
22.67 |
26.00 |
25.83 |
16.33 |
2.33 |
0.00 |
365.00 |
| 6:01 to 7:00 pm |
0.00 |
227.33 |
29.17 |
43.17 |
28.33 |
27.50 |
9.50 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 7:01 to 8:00 pm |
0.00 |
235.83 |
27.83 |
43.17 |
28.67 |
25.33 |
4.17 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 8:01 to 9:00 pm |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 9:01 to 10:00 pm |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 10:01 to 11:00 pm |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 11:01 to 12:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| Total |
0.00 |
6918.50 |
224.33 |
271.67 |
211.50 |
324.83 |
287.83 |
241.00 |
159.17 |
100.17 |
21.00 |
0.00 |
8760.00 |
Statistics
| |
Statistic |
| Minimum |
0.00 |
| Mean minus two standard
deviations |
-6496.35 |
| Mean |
1995.71 |
| Mean plus two standard
deviations |
10487.78 |
| Maximum |
19476.00 |
| Standard deviation |
4246.03 |
Output:Table:Monthly[LINK]
Monthly reports are not predefined. Instead each column is
defined when using the Output:Table:Monthly
object. In that object each column is defined by a variable
and how it should be aggregated. The StandardReports.idf file
is located in DataSets directory where EnergyPlus is installed
and contains a large number of examples of how to use Output:Table:Monthly
to get summaries of the performance of different components in
the building model. These examples include:
- Zone Cooling Summary
- Zone Heating Summary
- Zone Electric Summary
- Space Gains
- Peak Space Gains
- Space Gain Components at Cooling Peak
- Energy Consumption - Electricity & Natural Gas
- Energy Consumption - Electricity Generated &
Propane
- Energy Consumption - Diesel & Fuel Oil
- Energy Consumption - Purchased Heating & Cooling
- Energy Consumption - Coal & Gasoline
- End-Use Energy Consumption - Electricity
- End-Use Energy Consumption - Natural Gas
- End-Use Energy Consumption - Diesel
- End-Use Energy Consumption - Fuel Oil
- End-Use Energy Consumption - Coal
- End-Use Energy Consumption - Propane
- End-Use Energy Consumption - Gasoline
- Peak Energy End-Use - Electricity Part 1
- Peak Energy End-Use - Electricity Part 2
- Electric Components of Peak Demand
- Peak Energy End-Use - Natural Gas
- Peak Energy End-Use - Diesel
- Peak Energy End-Use - Fuel Oil
- Peak Energy End-Use - Coal
- Peak Energy End-Use - Propane
- Peak Energy End-Use - Gasoline
- Setpoints Not Met With Temperatures
- Comfort Report - Simple 55
- Unglazed Transpired Solar Collector Summary
- Occupant Comfort Data Summary
- Chiller Report
- Tower Report
- Boiler Report
- DX Report
- Window Report
- Window Energy Report
- Window Zone Summary
- Average Outdoor Conditions
- Outdoor Conditions Maximum Drybulb
- Outdoor Conditions Minimum Drybulb
- Outdoor Conditions Maximum Wetbulb
- Outdoor Conditions Maximum Dewpoint
- Outdoor Ground Conditions
- Window AC Report
- Water Heater Report
- Generator Report
- Daylighting Report
- Coil Report
- Plant Loop Demand Report
- Fan Report
- Pump Report
- Cond Loop Demand Report
- Zone Temperature Oscillation Report
- Air Loop System Energy and Water Use
- Air Loop System Component Loads
- Air Loop System Component Energy Use
- Mechanical Ventilation Loads
An example of the Zone
Cooling Summary monthly report is shown below.
Report: ZONE COOLING SUMMARY
For: SPACE2-1
Timestamp: 2006-08-29 07:21:57
| |
ZONE/SYS SENSIBLE COOLING ENERGY
[J] |
ZONE/SYS SENSIBLE COOLING RATE
{MAXIMUM}[W] |
ZONE/SYS SENSIBLE COOLING RATE
{TIMESTAMP} |
OUTDOOR DRY BULB {AT MAX/MIN}
[C] |
OUTDOOR WET BULB {AT MAX/MIN}
[C] |
ZONE TOTAL INTERNAL LATENT GAIN
[J] |
ZONE TOTAL INTERNAL LATENT GAIN
{MAXIMUM}[W] |
ZONE TOTAL INTERNAL LATENT GAIN
{TIMESTAMP} |
OUTDOOR DRY BULB {AT MAX/MIN}
[C] |
OUTDOOR WET BULB {AT MAX/MIN}
[C] |
| January |
281755456.00 |
1427.84 |
17-JAN-10:07 |
8.30 |
5.48 |
0.00 |
0.00 |
01-JAN-00:15 |
-4.32 |
-5.53 |
| February |
306879872.00 |
1440.59 |
28-FEB-10:46 |
11.27 |
6.67 |
0.00 |
0.00 |
01-FEB-00:15 |
-3.17 |
-4.91 |
| March |
419829728.00 |
1822.13 |
26-MAR-09:14 |
3.90 |
-0.20 |
0.00 |
0.00 |
01-MAR-00:15 |
-1.40 |
-2.84 |
| April |
752874688.00 |
1986.25 |
29-APR-10:22 |
21.10 |
11.44 |
0.00 |
0.00 |
01-APR-00:15 |
17.12 |
10.64 |
| May |
0.100670E+10 |
2163.18 |
22-MAY-09:45 |
25.17 |
15.42 |
0.00 |
0.00 |
01-MAY-00:15 |
3.75 |
1.60 |
| June |
0.100822E+10 |
2129.73 |
28-JUN-09:45 |
28.02 |
22.39 |
0.00 |
0.00 |
01-JUN-00:15 |
17.30 |
14.95 |
| July |
0.120671E+10 |
2312.36 |
08-JUL-09:00 |
31.70 |
23.35 |
0.00 |
0.00 |
01-JUL-00:15 |
15.60 |
12.95 |
| August |
0.109213E+10 |
2352.64 |
02-AUG-09:45 |
27.08 |
20.48 |
0.00 |
0.00 |
01-AUG-00:15 |
17.20 |
15.70 |
| September |
0.100619E+10 |
2453.23 |
06-SEP-10:15 |
28.35 |
20.53 |
0.00 |
0.00 |
01-SEP-00:15 |
16.75 |
15.45 |
| October |
771385600.00 |
2181.25 |
10-OCT-10:16 |
15.25 |
10.12 |
0.00 |
0.00 |
01-OCT-00:15 |
4.88 |
3.31 |
| November |
384831744.00 |
1566.35 |
11-NOV-10:45 |
14.00 |
8.89 |
0.00 |
0.00 |
01-NOV-00:15 |
14.65 |
11.75 |
| December |
246930448.00 |
1306.75 |
11-DEC-10:07 |
5.00 |
1.69 |
0.00 |
0.00 |
01-DEC-00:15 |
1.80 |
-0.11 |
| |
|
|
|
|
|
|
|
|
|
|
| Annual Sum or Average |
0.848444E+10 |
|
|
|
|
0.00 |
|
|
|
|
| Minimum of Months |
246930448.00 |
1306.75 |
|
3.90 |
-0.20 |
0.00 |
0.00 |
|
-4.32 |
-5.53 |
| Maximum of Months |
0.120671E+10 |
2453.23 |
|
31.70 |
23.35 |
0.00 |
0.00 |
|
17.30 |
15.70 |
UtilityCost:Tariff[LINK]
The use of UtilityCost:Tariff
objects automatically generates two reports related to the
calculation of annual utility costs. The first report is a
summary across multiple tariffs and is called the Economics
Results Summary report and is shown directly below. After that
example is an example of the Tariff report which is created
for each of the UtilityCost:Tariff
Objects defined in the IDF file (some columns may be truncated
due to page size).
Report: Economics Results Summary Report
For: Entire Facility
Timestamp: 2006-08-29 07:21:57
Annual Cost
| |
Facility:Electric |
Facility:Gas |
Other |
Total |
| Cost ($) |
2269.11 |
612.08 |
0.00 |
2881.19 |
| Cost per Total Building Area
($/m2) |
2.45 |
0.66 |
0.00 |
3.11 |
| Cost per Net Conditioned
Building Area ($/m2) |
2.45 |
0.66 |
0.00 |
3.11 |
Tariff Summary
| — |
Selected |
Qualified |
Meter |
Group |
Annual Cost |
| EXAMPLEA |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
2359.48 |
| EXAMPLEA-GAS |
Yes |
Yes |
GAS:FACILITY |
(none) |
612.08 |
| EXAMPLEAWITHVARIABLEMONTHLYCHARGE |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
2407.36 |
| EXAMPLEB |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
2668.34 |
| EXAMPLEC |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3017.45 |
| EXAMPLED |
Yes |
Yes |
ELECTRICITY:FACILITY |
(none) |
2269.11 |
| EXAMPLEDWITHRATCHET |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3745.90 |
| EXAMPLEE |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3766.76 |
| EXAMPLEF |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3512.12 |
| EXAMPLEFMC |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3512.12 |
| EXAMPLEG |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3866.91 |
The following is an example of the Tariff report which is
created for each of the UtilityCost:Tariff
objects defined in the file.
Report: Tariff Report
For: EXAMPLEA
Timestamp: 2006-08-29 07:21:57
| |
Parameter |
| Meter |
ELECTRICITY:FACILITY |
| Selected |
No |
| Group |
(none) |
| Qualified |
Yes |
| Disqualifier |
n/a |
| Computation |
automatic |
| Units |
kWh |
Categories
| |
Jan |
Feb |
Mar |
Apr |
May |
Jun |
Jul |
Aug |
Sep |
Oct |
Nov |
Dec |
Sum |
Max |
| EnergyCharges |
181.84 |
159.97 |
170.98 |
178.85 |
207.28 |
207.97 |
249.10 |
234.09 |
202.57 |
191.20 |
169.19 |
176.34 |
2329.36 |
249.10 |
| DemandCharges |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| ServiceCharges |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
30.12 |
2.51 |
| Basis |
184.35 |
162.48 |
173.49 |
181.36 |
209.79 |
210.48 |
251.61 |
236.60 |
205.08 |
193.71 |
171.70 |
178.85 |
2359.48 |
251.61 |
| Adjustment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Surcharge |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Subtotal |
184.35 |
162.48 |
173.49 |
181.36 |
209.79 |
210.48 |
251.61 |
236.60 |
205.08 |
193.71 |
171.70 |
178.85 |
2359.48 |
251.61 |
| Taxes |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Total |
184.35 |
162.48 |
173.49 |
181.36 |
209.79 |
210.48 |
251.61 |
236.60 |
205.08 |
193.71 |
171.70 |
178.85 |
2359.48 |
251.61 |
Charges
| |
Jan |
Feb |
Mar |
Apr |
May |
Jun |
Jul |
Aug |
Sep |
Oct |
Nov |
Dec |
Sum |
Max |
Category |
| FLATENERGYCHARGE |
181.84 |
159.97 |
170.98 |
178.85 |
207.28 |
207.97 |
249.10 |
234.09 |
202.57 |
191.20 |
169.19 |
176.34 |
2329.36 |
249.10 |
none |
Ratchets
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max —–
—– —– —– —– —– —– —– —– —– —– —– —– —–
Qualifies
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max —–
—– —– —– —– —– —– —– —– —– —– —– —– —–
Native Variables
| |
Jan |
Feb |
Mar |
Apr |
May |
Jun |
Jul |
Aug |
Sep |
Oct |
Nov |
Dec |
Sum |
Max |
| TotalEnergy |
3285.70 |
2890.52 |
3089.52 |
3231.79 |
3745.42 |
3757.86 |
4501.09 |
4229.79 |
3660.28 |
3454.82 |
3057.13 |
3186.33 |
42090.24 |
4501.09 |
| TotalDemand |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| PeakEnergy |
3285.70 |
2890.52 |
3089.52 |
3231.79 |
3745.42 |
3757.86 |
4501.09 |
4229.79 |
3660.28 |
3454.82 |
3057.13 |
3186.33 |
42090.24 |
4501.09 |
| PeakDemand |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| ShoulderEnergy |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| ShoulderDemand |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| OffPeakEnergy |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| OffPeakDemand |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| MidPeakEnergy |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| MidPeakDemand |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| PeakExceedsOffPeak |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| OffPeakExceedsPeak |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| PeakExceedsMidPeak |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| MidPeakExceedsPeak |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| PeakExceedsShoulder |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| ShoulderExceedsPeak |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| IsWinter |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
12.00 |
1.00 |
| IsNotWinter |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| IsSpring |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| IsNotSpring |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
12.00 |
1.00 |
| IsSummer |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| IsNotSummer |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
12.00 |
1.00 |
| IsAutumn |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| IsNotAutumn |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
12.00 |
1.00 |
| PeakAndShoulderEnergy |
3285.70 |
2890.52 |
3089.52 |
3231.79 |
3745.42 |
3757.86 |
4501.09 |
4229.79 |
3660.28 |
3454.82 |
3057.13 |
3186.33 |
42090.24 |
4501.09 |
| PeakAndShoulderDemand |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| PeakAndMidPeakEnergy |
3285.70 |
2890.52 |
3089.52 |
3231.79 |
3745.42 |
3757.86 |
4501.09 |
4229.79 |
3660.28 |
3454.82 |
3057.13 |
3186.33 |
42090.24 |
4501.09 |
| PeakAndMidPeakDemand |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| ShoulderAndOffPeakEnergy |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| ShoulderAndOffPeakDemand |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| PeakAndOffPeakEnergy |
3285.70 |
2890.52 |
3089.52 |
3231.79 |
3745.42 |
3757.86 |
4501.09 |
4229.79 |
3660.28 |
3454.82 |
3057.13 |
3186.33 |
42090.24 |
4501.09 |
| PeakAndOffPeakDemand |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
Other Variables
| |
Jan |
Feb |
Mar |
Apr |
May |
Jun |
Jul |
Aug |
Sep |
Oct |
Nov |
Dec |
Sum |
Max |
| NotIncluded |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Computation - AutomaticFLATENERGYCHARGE FROM
TotalEnergyEnergyCharges SUM FLATENERGYCHARGEBasis SUM
EnergyCharges DemandCharges ServiceChargesSubtotal SUM Basis
Adjustment SurchargeTotal SUM Subtotal Taxes
Construction Cost
Estimate Summary[LINK]
The Construction
Cost Estimate Summary report shows the details of a simplified
cost estimate of the building along with a comparison with
reference building costs entered by the user. An example of
the Construction
Cost Estimate Summary report is shown below.
Construction
Cost Estimate Summary
| |
Reference Bldg. |
Current Bldg. Model |
Difference |
| Line Item SubTotal ($) |
665082.04 |
720964.07 |
55882.03 |
| Misc. Costs ($) |
928979.09 |
928979.09 |
0.00 |
| Regional Adjustment ($) |
216792.31 |
224392.27 |
7599.96 |
| Design Fee ($) |
108651.21 |
149946.83 |
41295.63 |
| Contractor Fee ($) |
126759.74 |
131203.48 |
4443.74 |
| Contigency ($) |
181085.34 |
187433.54 |
6348.20 |
| Permits, Bonds, Insurance
($) |
0.00 |
0.00 |
0.00 |
| Commissioning ($) |
9054.27 |
18743.35 |
9689.09 |
| Cost Estimate Total ($) |
2236404.00 |
2361662.65 |
125258.65 |
| Cost Per Conditioned Building
Area ($/m2) |
1203.69 |
1271.11 |
67.42 |
Cost Line Item Details
| |
Line No. |
Item Name |
Quantity. |
Units |
$ per Qty. |
SubTotal $ |
| – |
1 |
EXTERIOR WALLS |
627.57 |
m2 |
168.64 |
105832.65 |
| – |
2 |
INTERIOR WALLS |
854.18 |
m2 |
31.16 |
26616.23 |
| – |
3 |
ROOF |
1857.96 |
m2 |
104.69 |
194509.64 |
| – |
4 |
GROUND FLR SLAB |
1857.96 |
m2 |
56.06 |
104157.14 |
| – |
5 |
ACOUSTICAL DROP CEILINGS |
1857.96 |
m2 |
23.79 |
44200.83 |
| – |
6 |
QUAD HIGH SHGC SUPERWINDOWS |
226.22 |
m2 |
687.84 |
155604.96 |
| – |
7 |
QUAD LOW SHGC SUPERWINDOWS |
42.68 |
m2 |
687.84 |
29359.55 |
| – |
8 |
CENTRAL CHILLER |
153.48 |
kW (tot cool cap.) |
340.00 |
52183.09 |
| – |
9 |
CONTINUOUS AIR BARRIER |
1.00 |
Ea. |
8500.00 |
8500.00 |
| Line Item SubTotal |
– |
– |
– |
– |
– |
720964.07 |
XML Tabular Output[LINK]
The tables discussed in this section can also be output in
an XML format that may be easier for some other programs to
extract specific results. An excerpt of the XML file format is
shown below. This report presents the same output results as
the other tabular report formats but using XML tags.
<?xml version="1.0"?>
<EnergyPlusTabularReports>
<BuildingName>NONE</BuildingName>
<EnvironmentName>Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300</EnvironmentName>
<WeatherFileLocationTitle>Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300</WeatherFileLocationTitle>
<ProgramVersion>EnergyPlus, Version 8.0, YMD=2013.02.18 15:50</ProgramVersion>
<SimulationTimestamp>
<Date>
2013-02-18
</Date>
<Time>
15:50:33
</Time>
</SimulationTimestamp>
<AnnualBuildingUtilityPerformanceSummary>
<for>Entire Facility</for>
<SiteAndSourceEnergy>
<name>TotalSiteEnergy</name>
<TotalEnergy units="kBtu">200671.97</TotalEnergy>
<EnergyPerTotalBuildingArea units="kBtu/ft2">143.32</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units="kBtu/ft2">143.32</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
<SiteAndSourceEnergy>
<name>NetSiteEnergy</name>
<TotalEnergy units="kBtu">200671.97</TotalEnergy>
<EnergyPerTotalBuildingArea units="kBtu/ft2">143.32</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units="kBtu/ft2">143.32</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
<SiteAndSourceEnergy>
<name>TotalSourceEnergy</name>
<TotalEnergy units="kBtu">442504.19</TotalEnergy>
<EnergyPerTotalBuildingArea units="kBtu/ft2">316.04</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units="kBtu/ft2">316.04</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
<SiteAndSourceEnergy>
<name>NetSourceEnergy</name>
<TotalEnergy units="kBtu">397810.98</TotalEnergy>
<EnergyPerTotalBuildingArea units="kBtu/ft2">284.12</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units="kBtu/ft2">284.12</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
An actual file will be much longer than this example
but follows this format.
eplustbl.<ext>[LINK]
The eplustbl file contains the tabular output results that are created when using the following objects:
The format and the extension for the file depends on the setting of the ColumnSeparator field of the Output:Table:Style object. The choices of HTML, tab, fixed, comma, and XML result in eplustbl.htm, eplustbl.tab, eplustbl.txt, eplustbl.csv, eplustbl.xml respectively. The HTML version of the report also includes a table of contents that allows easier navigation through the file.
By default the energy units reported in all of the eplustbl files are in Joules (J) but the UnitConversion field of the Output:Table:Style object allows for the values to be reported in MJ, GJ or in kWh. In addition, the Output:Table:Style object can specify for the tables to be in IP units for all fields.
Output:Table:SummaryReports[LINK]
Several predefined reports are available from the Output:Table:SummaryReports object including the following. (spaces are inserted in names for readability; keys are included in the Input Data Dictionary or by just removing the spaces):
All Summary
Lists all following applicable tables with “Summary” in the name.
All Monthly
Lists all following applicable tables with “Monthly” in the name.
All Summary And Monthly
Lists all following applicable tables with both “Summary” and “Monthly” in the name. This does not include the Zone Component Load Summary report.
All Summary and Sizing Period
Lists the All Summary tables as well as the Zone Component Load report (currently the only Sizing Period report). Please note that the Zone Component Load report does increase the run time because it repeats sizing periods.
All Summary Monthly and Sizing Period
Lists the All Summary tables, the Monthly tables as well as the Zone Component Load report (currently the only Sizing Period report). Please note that the Zone Component Load report does increase the run time because it repeats sizing periods.
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Climatic Data Summary
Equipment Summary
Envelope Summary
Surface Shadowing Summary
Shading Summary
Lighting Summary
HVAC Sizing Summary
System Summary
Component Sizing Summary
Outdoor Air Summary
Object Count Summary
Component Cost Economics Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
Zone Component Load Summary
Zone Cooling Summary Monthly
Zone Heating Summary Monthly
Zone Electric Summary Monthly
Space Gains Monthly
Peak Space Gains Monthly
Space Gain Components At Cooling Peak Monthly
Energy Consumption Electricity Natural Gas Monthly
Energy Consumption Electricity Generated Propane Monthly
Energy Consumption Diesel FuelOil Monthly
Energy Consumption District Heating Cooling Monthly
Energy Consumption Coal Gasoline Monthly
End Use Energy Consumption Electricity Monthly
End Use Energy Consumption NaturalGas Monthly
End Use Energy Consumption Diesel Monthly
End Use Energy Consumption FuelOil Monthly
End Use Energy Consumption Coal Monthly
End Use Energy Consumption Propane Monthly
End Use Energy Consumption Gasoline Monthly
Peak Energy End Use Electricity Part1 Monthly
Peak Energy End Use Electricity Part2 Monthly
Electric Components Of Peak Demand Monthly
Peak Energy End Use NaturalGas Monthly
Peak Energy End Use Diesel Monthly
Peak Energy End Use FuelOil Monthly
Peak Energy End Use Coal Monthly
Peak Energy End Use Propane Monthly
Peak Energy End Use Gasoline Monthly
Setpoints Not Met With Temperatures Monthly
Comfort Report Simple55 Monthly
Unglazed Transpired Solar Collector Summary Monthly
Occupant Comfort Data Summary Monthly
Chiller Report Monthly
Tower Report Monthly
Boiler Report Monthly
DX Report Monthly
Window Report Monthly
Window Energy Report Monthly
Window Zone Summary Monthly
Window Energy Zone Summary Monthly
Average Outdoor Conditions Monthly
Outdoor Conditions Maximum DryBulb Monthly
Outdoor Conditions Minimum DryBulb Monthly
Outdoor Conditions Maximum WetBulb Monthly
Outdoor Conditions Maximum DewPoint Monthly
Outdoor Ground Conditions Monthly
WindowAC Report Monthly
Water Heater Report Monthly
Generator Report Monthly
Daylighting Report Monthly
Coil Report Monthly
PlantLoop Demand Report Monthly
Fan Report Monthly
Pump Report Monthly
CondLoop Demand Report Monthly
Zone Temperature Oscillation Report Monthly
AirLoop System Energy And Water Use Monthly
AirLoop System Component Loads Monthly
AirLoop System Component Energy Use Monthly
Mechanical Ventilation Loads Monthly
Each of these reports is made up of several sub-tables of information. Examples of some of the tables are shown below. To enable all of the reports the single All Summary may be specified.
Annual Building Utility Performance Summary[LINK]
The Annual Building Utility Performance Summary report provides an overview of energy consumption in the building for different end uses. The following is an example this report (some columns may be truncated due to page size). The key used to obtain this report is AnnualBuildingUtilityPerformanceSummary.
In the Comfort and Setpoint Not Met Summary sub-table, facility hours represents the total number of hours that any single zone did not meet the comfort or setpoint criteria. It is not weighted by number of zones or number of occupants.
The values in the End Uses sub-table are from report meters. To determine which components are attached to each end-use meter, consult the meter details output file (*.mtd).
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Values gathered over 8760.00 hours
Site and Source Energy
Source to Site Energy Converstion Factors
Building Area
End Uses
Note: Natural gas appears to be the principal heating source based on energy usage.
End Uses By Subcategory
Normalized Metrics
Utility Use Per Conditioned Floor Area
Utility Use Per Total Floor Area
Electric Loads Satisfied
On-Site Thermal Sources
Water Source Summary
Comfort and Setpoint Not Met Summary
Note 1: An asterisk (*) indicates that the feature is not yet implemented.
Input Verification and Results Summary[LINK]
The Input Verification and Results Summary report provides a summary of some of the most common input assumptions that are not included in any of the other predefined reports. Directly following is an example of the report. The key used to obtain this report is InputVerificationandResultsSummary.
Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
General
ENVELOPE
Window-Wall Ratio
Skylight-Roof Ratio
PERFORMANCE
Zone Summary
Demand End Use Components Summary[LINK]
The Demand End Use Components Summary report shows the demand breakdown by component end use at the time that the peak demand for each source of energy is set. The time of the peak demand is shown in the first row. The contributions of each end use at the time of the peak demand of the energy source is shown in this report. The key used to obtain this report is DemandEndUseComponentsSummary.
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
End Uses
End Uses By Subcategory
Source Energy End Use Components Summary[LINK]
The Source Energy End Use Components Summary report produces a report that includes three tables. These tables display source energy by fuel type that is calculated based on site to source energy factors specified by the user in the EnvironmentalImpactFactors and FuelFactors objects. The last two tables display the source energy in terms of area normalized metrics. Directly following is an example of the three tables. The key used to obtain this report is SourceEnergyEndUseComponentsSummary.
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2011-10-07 20:53:43
Values gathered over 8760.00 hoursSource Energy End Use Components Summary
Normalized MetricsSource Energy End Use Components Per Conditioned Floor Area
Source Energy End Use Components Per Total Floor Area
Equipment Summary[LINK]
The Equipment Summary report provides a summary of the HVAC related equipment in the building. The central chiller example shows the most common type of chillers, boilers and towers used in EnergyPlus. The remaining subtables cover DX coils, fans and water heating equipment. Not every type of HVAC equipment is represented in this report. Directly following is an example of the report. The key used to obtain this report is EquipmentSummary.
Report: Equipment Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Central Plant
Cooling Coils
Heating Coils
Fans
Pumps
Service Water Heating
Envelope Summary[LINK]
The Envelope Summary report provides a summary of the elements of the envelope of the building. The first table describes the exterior opaque elements and the second table describes the fenestration elements. Reflectance is defined as one minus the thermal absorptance. Directly following is an example of the report. The key used to obtain this report is EnvelopeSummary.
Report: Envelope Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Opaque Exterior
Fenestration
Surface Shadowing Summary[LINK]
The Surface Shadowing Summary report summarizes how the surfaces may cast shadows on other surfaces. Directly following is an example of the report. The key used to obtain this report is SurfaceShadowingSummary.
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces
Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces
Shading Summary[LINK]
The Shading Summary report shows how much of each window is sunlit at different times of the year and also includes a summary of the window controls. Directly following is an example of the report. The key used to obtain this report is ShadingSummary.
Report: Shading Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Sunlit Fraction
Window Control
Lighting Summary[LINK]
The Lighting Summary report provides a description of the interior and exterior lighting systems being simulated. It also provides a summary of daylighting controls. The Interior Lighting table has three columns that are explained below:
Scheduled Hours/Week [hr] - In the schedule shown, this represents the average weekly sum of hourly values. It is based on a full year even if the simulation is only performed for part of the year. It is not affected by daylighting.
Hours/Week > 1% [hr] - This represents the average hours per week that are above 1% of the design value.
Full Load Hours/Week [hr] - This is based on consumption and hours that the consumption occurred. It is dependent on the run period used. When simulating only a portion of the year, the value depends on which days of the year (the number of weekdays versus weekend days, for example) are simulated. It also indicates the impact of daylighting control. Directly following is an example of the report. The key used to obtain this report is LightingSummary.
Report: Lighting Summary
For: Entire Facility
Timestamp: 2012-09-05 12:10:52
Interior Lighting
Daylighting
Exterior Lighting
HVAC Sizing Summary[LINK]
The HVAC Sizing Summary report provides information on the zone cooling and heating sizing and the peak load conditions as well as information about the system air flow sizing. Directly following is an example of the report. The key used to obtain this report is HVACSizingSummary.
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2011-09-23 15:09:34
Zone Cooling
|Calculated Design Load [W]|User Design Load [W]|Calculated Design Air Flow [m3/s]|User Design Air Flow [m3/s]|Design Day Name|Date/Time Of Peak|Temperature at Peak [C]|Humidity Ratio at Peak [kgWater/kgAir] SPACE1-1|2647.33|2647.33|0.223|0.223|CHICAGO_IL_USA ANNUAL COOLING 1% DESIGN CONDITIONS DB/MCWB|7/21 15:45:00|31.02|0.01459 SPACE2-1|2234.38|2234.38|0.188|0.188|CHICAGO_IL_USA ANNUAL COOLING 1% DESIGN CONDITIONS DB/MCWB|7/21 10:00:00|27.43|0.01459 SPACE3-1|2506.34|2506.34|0.211|0.211|CHICAGO_IL_USA ANNUAL COOLING 1% DESIGN CONDITIONS DB/MCWB|7/21 15:00:00|31.50|0.01459 SPACE4-1|2464.72|2464.72|0.207|0.207|CHICAGO_IL_USA ANNUAL COOLING 1% DESIGN CONDITIONS DB/MCWB|7/21 17:30:00|29.47|0.01459 SPACE5-1|2628.69|2628.69|0.221|0.221|CHICAGO_IL_USA ANNUAL COOLING 1% DESIGN CONDITIONS DB/MCWB|7/21 15:00:00|31.50|0.01459
Zone Heating
|Calculated Design Load [W]|User Design Load [W]|Calculated Design Air Flow [m3/s]|User Design Air Flow [m3/s]|Design Day Name|Date/Time Of Peak|Temperature at Peak [C]|Humidity Ratio at Peak [kgWater/kgAir] SPACE1-1|3860.76|3860.76|0.117|0.117|CHICAGO_IL_USA ANNUAL HEATING 99% DESIGN CONDITIONS DB|1/21 24:00:00|-17.30|0.00084 SPACE2-1|1625.15|1625.15|0.049|0.049|CHICAGO_IL_USA ANNUAL HEATING 99% DESIGN CONDITIONS DB|1/21 24:00:00|-17.30|0.00084 SPACE3-1|3753.07|3753.07|0.113|0.113|CHICAGO_IL_USA ANNUAL HEATING 99% DESIGN CONDITIONS DB|1/21 24:00:00|-17.30|0.00084 SPACE4-1|1625.15|1625.15|0.049|0.049|CHICAGO_IL_USA ANNUAL HEATING 99% DESIGN CONDITIONS DB|1/21 24:00:00|-17.30|0.00084 SPACE5-1|2981.57|2981.57|0.090|0.103|CHICAGO_IL_USA ANNUAL HEATING 99% DESIGN CONDITIONS DB|1/21 24:00:00|-17.30|0.00084
System Design Air Flow Rates
Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
VAV SYS 1 1.05 1.05 0.43 0.43
Plant Loop Coincident Design Fluid Flow Rate Adjustments
System Summary[LINK]
The System Summary report provides information about some of the primary components in the system including the economizer and demand controlled ventilation. In addition, this report describes when the zone conditions are not comfortable or when set points are not met.
In the Time Not Comfortable Based on Simple ASHRAE 55-2004 and **Time Setpoint Not Met sub-tables, The reported time represents the total number of hours that a given zone did not meet the comfort or setpoint criteria. For the Facility row, this is the total numbers of hours that one or more zones were out of range. The values are not weighted by number of zones or number of occupants.
Directly following is an example of the report. The key used to obtain this report is SystemSummary.
Report: System Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Economizer
Demand Controlled Ventilation using VENTILATION:MECHANICAL
Time Not Comfortable Based on Simple ASHRAE 55-2004
Time Setpoint Not Met
Component Sizing Summary[LINK]
The Component Sizing Summary report includes details on many of the HVAC components in the simulation. For each of the components, one or more parameters are shown. Directly following is an example of the report. The key used to obtain this report is ComponentSizingSummary.
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
SINGLE DUCT:VAV:REHEAT
COIL:Water:SimpleHeating
BRANCH
AIR PRIMARY LOOP
CONTROLLER:OUTSIDE AIR
COIL:Water:Cooling
FAN:SIMPLE:VARIABLEVOLUME
CONTROLLER:SIMPLE
PLANT LOOP
BOILER:SIMPLE
CHILLER:ELECTRIC
PUMP:VARIABLE SPEED
Outdoor Air Summary[LINK]
The Outdoor Air Summary provides information for each zone on the average and minimum ventilation provided.
The reports described so far in this section are displayed when specified in the Output:Table:Predefined object. They are either on or off and are not customizable. The next few types of tabular reports are customizable. You can specify the report variables being used in each one.
Directly following is an example of the report. The key used to obtain this report is OutdoorAirSummary.
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Average Outside Air During Occupied Hours
Minimum Outside Air During Occupied Hours
Climatic Data Summary[LINK]
The Climatic Data Summary provides some statistics from the .STAT file concerning the selected weather. The Stat file must be available (it is included with all the weather files on the EnergyPlus website) for the report to be fully produced. Directly following is an example of the report. The key used to obtain this report is ClimaticDataSummary.
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2009-02-10 13:27:45
SizingPeriod:DesignDay
Weather Statistics File
Object Count Summary[LINK]
This report provides the count on the number of specific objects in the file. Directly following is an example of the report. The key used to obtain this report is ObjectCountSummary.
Report: Object Count Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Surfaces by Class
HVAC
Energy Meters[LINK]
This report provides the details on all the energy meters generated by the simulation. Directly following is an example of the report. The key used to obtain this report is EnergyMeters.
Report: Energy Meters
For: Entire Facility
Timestamp: 2012-05-01 17:07:24
Annual and Peak Values - Electricity
Annual and Peak Values - Gas
Annual and Peak Values - Cooling
Annual and Peak Values - Water
Annual and Peak Values - Other by Weight/Mass
Annual and Peak Values - Other Volumetric
Annual and Peak Values - Other Liquid/Gas
Annual and Peak Values - Other
Sensible Heat Gain Summary[LINK]
This report is more fully described in the Input Output Reference but represents the major heat gain components for each zone as well as the HVAC loads satisfied. Directly following is an example of the report. The key used to obtain this report is SensibleHeatGainSummary.
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2011-09-09 08:02:03
Annual Building Sensible Heat Gain Components
Peak Cooling Sensible Heat Gain Components
Peak Heating Sensible Heat Gain Components
Standard 62.1 Summary[LINK]
This report is more fully described in the Input Output Reference. The Standard 62.1 Summary produces a report that is consistent with many of the outputs needed when doing calculations consistent with ASHRAE Standard 62.1-2010. The report is generated when sizing calculations are specified. The abbreviations used in the report are consistent with the abbreviations used in Appendix A4 of the Standard. Directly following is an example of the report. The key used to obtain this report is Standard62.1Summary.
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2012-04-20 12:00:57
System Ventilation Requirements for Cooling
System Ventilation Requirements for Heating
Zone Ventilation Parameters
System Ventilation Parameters
Zone Ventilation Calculations for Cooling Design
System Ventilation Calculations for Cooling Design
Zone Ventilation Calculations for Heating Design
System Ventilation Calculations for Heating Design
Zone Component Loads Summary[LINK]
The Zone Component Loads Summary provides an estimate of the heating and cooling peak loads for each zone broken down into various components. This report may help determine which components of the load have the largest impact for the heating and cooling peak design conditions. When specified, the Zone Component Loads Summary report is created for each zone that is conditioned. The Sensible-Delayed column of the summary is only an estimate based on a procedure described in the Engineering Reference documentation. An intermediate calculation in this procedure is the decay curves that are shown in the the EIO file when Output:Surfaces:List is set to show DecayCurvesFromZoneComponentLoads. The difference between the peak design sensible load and the estimated instant + delayed sensible load (as shown in the Peak Conditions subtable) is an indication of how consistent the overall total estimate may be to the computed total peak loads for the zone. When the report is called the zone sizing calculations are repeated twice so this may result in longer simulation times. The key used to obtain this report is ZoneComponentLoadSummary.
Report: ZoneComponentLoadSummary
For: SPACE1-1
Timestamp: 2012-09-21 15:48:46
Estimated Cooling Peak Load Components
Cooling Peak Conditions
Estimated Heating Peak Load Components
Heating Peak Conditions
Output:Table:TimeBins[LINK]
A TimeBins report shows a grid of the number of hours that specific report variable spend in a range of values. The first table is broken into two parts. The first part is monthly and the second part is for each hour of the day. The columns show the range of values. A second table is provided to show some statistics on the report variable for the entire year including the maximum and minimum. These statistics are helpful in setting the field values for the interval in the Output Table:TimeBins object. Due to this, it is often necessary to run two simulations to fully utilize the TimeBins report with the first run used to find the minimum and maximum of the variable, these values are then used in the TimeBins object and the second run a better table of binned results are displayed.
Report: PURCHASEDCOOLING:FACILITY J per second
For: Meter
Timestamp: 2006-08-30 07:48:55
Values in table are in hours.
Statistics
Output:Table:Monthly[LINK]
Monthly reports are not predefined. Instead each column is defined when using the Output:Table:Monthly object. In that object each column is defined by a variable and how it should be aggregated. The StandardReports.idf file is located in DataSets directory where EnergyPlus is installed and contains a large number of examples of how to use Output:Table:Monthly to get summaries of the performance of different components in the building model. These examples include:
An example of the Zone Cooling Summary monthly report is shown below.
Report: ZONE COOLING SUMMARY
For: SPACE2-1
Timestamp: 2006-08-29 07:21:57
UtilityCost:Tariff[LINK]
The use of UtilityCost:Tariff objects automatically generates two reports related to the calculation of annual utility costs. The first report is a summary across multiple tariffs and is called the Economics Results Summary report and is shown directly below. After that example is an example of the Tariff report which is created for each of the UtilityCost:Tariff Objects defined in the IDF file (some columns may be truncated due to page size).
Report: Economics Results Summary Report
For: Entire Facility
Timestamp: 2006-08-29 07:21:57
Annual Cost
Tariff Summary
The following is an example of the Tariff report which is created for each of the UtilityCost:Tariff objects defined in the file.
Report: Tariff Report
For: EXAMPLEA
Timestamp: 2006-08-29 07:21:57
Categories
Charges
Ratchets
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max —– —– —– —– —– —– —– —– —– —– —– —– —– —–
Qualifies
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max —– —– —– —– —– —– —– —– —– —– —– —– —– —–
Native Variables
Other Variables
Computation - AutomaticFLATENERGYCHARGE FROM TotalEnergyEnergyCharges SUM FLATENERGYCHARGEBasis SUM EnergyCharges DemandCharges ServiceChargesSubtotal SUM Basis Adjustment SurchargeTotal SUM Subtotal Taxes
Construction Cost Estimate Summary[LINK]
The Construction Cost Estimate Summary report shows the details of a simplified cost estimate of the building along with a comparison with reference building costs entered by the user. An example of the Construction Cost Estimate Summary report is shown below.
Construction Cost Estimate Summary
Cost Line Item Details
XML Tabular Output[LINK]
The tables discussed in this section can also be output in an XML format that may be easier for some other programs to extract specific results. An excerpt of the XML file format is shown below. This report presents the same output results as the other tabular report formats but using XML tags.
An actual file will be much longer than this example but follows this format.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.