EnergyPlus Files[LINK]
The following files are input to the EnergyPlus
program.
The input data dictionary (IDD) is an ascii (text)
file containing a list of all possible EnergyPlus objects and
a specification of the data each object requires. This file is
analogous to the DOE-2 keyword file. The Guide for
Interface Developers contains a full description of the
input data dictionary.
The input data file (IDF) is an ascii file
containing the data describing the building and HVAC system to
be simulated. The Guide for Interface Developers
shows examples of IDF input. Many example files are installed
as part of the EnergyPlus installation.
The input macro file (IMF) is an ascii file that
is formatted for the EP-Macro program. Output from the
EP-Macro program will be the standard in.idf format. IMF files
are not directly read by EnergyPlus.
This is the EnergyPlus initialization file. It is an
optional ascii input file that allows the user to specify the
path for the directory containing Energy+.idd. This file,
using the actual directories of the install, will be created
during the install. An example is:
[program]
dir = C:\EnergyPlus
[weather]
dir =
[BasementGHT]
dir = PreProcess\GrndTempCalc
[SlabGHT]
dir = PreProcess\GrndTempCalc
Under [program], dir should indicate the folder where
EnergyPlus is installed (e.g. C:\Program
Files\EnergyPlusV2-0-0 or C:\EnergyPlusV2-0-0). This is
automatically generated during the install and may be the
“shortened form” of these folder names. The “weather” portion
of the initialization file is unused for normal EnergyPlus.
[BasementGHT] and [SlabGHT] are used by the EP-Launch program
when the Utilities tab is used to execute the Basement and
Slab programs, respectively.
The EnergyPlus weather file is an ascii file
containing the hourly or sub-hourly weather data needed by the
simulation program. The data format is described in this
document in the section: EnergyPlus Weather File (EPW) Data
Dictionary.
More information (and more up-to-date) about output files
is shown in the Output
Details and Examples Document.
A text file containing the error messages issued by
EnergyPlus. This is the first output that should be examined
after a simulation. Error messages are issued by EnergyPlus
during its input phase or during the simulation. There are
three levels of error severity: fatal,
severe, and warning as well as simple
“message” lines. A fatal error causes the program to
terminate immediately. The following table illustrates the
necessary actions.
Error Message Levels - Required Actions
| Error Level |
Action |
| "Information" |
Informative, usually a follow-on
to one of the others. No action required. |
| Warning |
Take note. Fix as
applicable. |
| Severe |
Should Fix |
| Fatal |
Program will abort |
An example of an error message due to an input syntax error
is:
** Severe ** Did not find " DessignDay" in list of Objects
** Fatal ** Errors occurred on processing IDF file -
probable incorrect IDD file. View "audit.out" for details.
************* EnergyPlus Terminated--Error(s) Detected.
eplusout.audit[LINK]
This is an text file which echoes the IDD and IDF files,
flagging syntax errors in either file. Note that both
eplusout.err and eplusout.audit will show
the error messages caused by input syntax errors; however only
eplusout.err will show errors issued during the
actual simulation. eplusout.audit can be used when
you need to see the context of the error message to fully
ascertain the cause.
The EnergyPlus Standard Output (ESO) is a text
file containing the time varying simulation output. The format
of the file is discussed in the Guide for Interface
Developers and the InputOutputReference. The
contents of the file are controlled by Report
Variable commands in the IDF file. Although the ESO is a
text file, it is not easily interpretable by a human. Usually
postprocessing will be done on this file in order to put it in
a format that can be read by a spreadsheet; however a quick
visual inspection of the file does show whether the expected
variables are output at the desired time step.
The EnergyPlus Meter Output (MTR) is a text file
containing the time varying simulation output. The format of
the file is similar to the ESO file. Meters are a powerful
reporting tool in EnergyPlus. Values are grouped onto logical
meters and can be viewed the same way that the ESO variables
are used. The contents of the file are controlled by
Report Meter commands in the IDF file. Although the
MTR is a text file, it is not easily interpretable by a human.
Usually postprocessing will be done on this file in order to
put it in a format that can be read by a spreadsheet; however
a quick visual inspection of the file does show whether the
expected variables are output at the desired time step.
The EnergyPlus Invariant Output (EIO) is a text
file containing output that does not vary with time. For
instance, location information (latitude, longitude, time
zone, altitude) appears on this file.
The Report (variable) Data Dictionary (RDD) is a
text file listing those variables available for reporting (on
the ESO or MTR) for this particular simulation. Which
variables are available for output on the ESO or MTR depends
on the actual simulation problem described in the IDF. A
simulation with no chiller would not permit the output of any
chiller report variables. The user may need to examine the RDD
to find out which report variables are available in a
particular simulation. The RDD is written only if
Output:VariableDictionary, <either Regular or IDF>;
appears in the input (IDF) file.
This is a text file containing debug output for
use by EnergyPlus developers. Generally developers will add
debug print statements wherever in the code that that they
wish. There is a “standard” debug output that prints out
conditions at all the HVAC nodes. This output is triggered by
placing
DEBUG OUTPUT,1;
in the IDF file. If DEBUG OUTPUT, 0 is entered, you will
get an empty eplusout.dbg file.
This is a file in AutoCad DXF format showing all the
surfaces defined in the IDF file. It provides a means of
viewing the building geometry. The DXF file from EnergyPlus
highlights different building elements (shading, walls,
subsurfaces) in differing colors. A number of programs can
read and display DXF files. One that works well is Volo View
Express, available free from the Autodesk web site. Output of
this file is triggered by
Report, Surfaces, DXF;
in the IDF.
A text file containing the coordinates of the vertices of
the surfaces in the IDF.
Output of this file is triggered by
Report, Surfaces, Lines;
in the IDF.
Postprocessing
Program/Files[LINK]
A postprocessing program ReadVarsESO.exe is
available that will read an ESO or MTR file and produce a file
that can be read by ExcelTM. It can use an input
file or not. In batch mode it is run by the little batch file
RunReadESO.bat: Further information on this program
is provided in the Input
Output Reference as well as the Output
Details and Examples documents.
You can also used the CSVProc and convertESOMTR described
earlier in this document as part of your post processing
strategy.
EnergyPlus Files[LINK]
Input Files[LINK]
The following files are input to the EnergyPlus program.
Energy+.idd[LINK]
The input data dictionary (IDD) is an ascii (text) file containing a list of all possible EnergyPlus objects and a specification of the data each object requires. This file is analogous to the DOE-2 keyword file. The Guide for Interface Developers contains a full description of the input data dictionary.
in.idf[LINK]
The input data file (IDF) is an ascii file containing the data describing the building and HVAC system to be simulated. The Guide for Interface Developers shows examples of IDF input. Many example files are installed as part of the EnergyPlus installation.
in.imf[LINK]
The input macro file (IMF) is an ascii file that is formatted for the EP-Macro program. Output from the EP-Macro program will be the standard in.idf format. IMF files are not directly read by EnergyPlus.
Energy+.ini[LINK]
This is the EnergyPlus initialization file. It is an optional ascii input file that allows the user to specify the path for the directory containing Energy+.idd. This file, using the actual directories of the install, will be created during the install. An example is:
Under [program], dir should indicate the folder where EnergyPlus is installed (e.g. C:\Program Files\EnergyPlusV2-0-0 or C:\EnergyPlusV2-0-0). This is automatically generated during the install and may be the “shortened form” of these folder names. The “weather” portion of the initialization file is unused for normal EnergyPlus. [BasementGHT] and [SlabGHT] are used by the EP-Launch program when the Utilities tab is used to execute the Basement and Slab programs, respectively.
in.epw[LINK]
The EnergyPlus weather file is an ascii file containing the hourly or sub-hourly weather data needed by the simulation program. The data format is described in this document in the section: EnergyPlus Weather File (EPW) Data Dictionary.
Output Files[LINK]
More information (and more up-to-date) about output files is shown in the Output Details and Examples Document.
eplusout.err[LINK]
A text file containing the error messages issued by EnergyPlus. This is the first output that should be examined after a simulation. Error messages are issued by EnergyPlus during its input phase or during the simulation. There are three levels of error severity: fatal, severe, and warning as well as simple “message” lines. A fatal error causes the program to terminate immediately. The following table illustrates the necessary actions.
An example of an error message due to an input syntax error is:
eplusout.audit[LINK]
This is an text file which echoes the IDD and IDF files, flagging syntax errors in either file. Note that both eplusout.err and eplusout.audit will show the error messages caused by input syntax errors; however only eplusout.err will show errors issued during the actual simulation. eplusout.audit can be used when you need to see the context of the error message to fully ascertain the cause.
eplusout.eso[LINK]
The EnergyPlus Standard Output (ESO) is a text file containing the time varying simulation output. The format of the file is discussed in the Guide for Interface Developers and the InputOutputReference. The contents of the file are controlled by Report Variable commands in the IDF file. Although the ESO is a text file, it is not easily interpretable by a human. Usually postprocessing will be done on this file in order to put it in a format that can be read by a spreadsheet; however a quick visual inspection of the file does show whether the expected variables are output at the desired time step.
eplusout.mtr[LINK]
The EnergyPlus Meter Output (MTR) is a text file containing the time varying simulation output. The format of the file is similar to the ESO file. Meters are a powerful reporting tool in EnergyPlus. Values are grouped onto logical meters and can be viewed the same way that the ESO variables are used. The contents of the file are controlled by Report Meter commands in the IDF file. Although the MTR is a text file, it is not easily interpretable by a human. Usually postprocessing will be done on this file in order to put it in a format that can be read by a spreadsheet; however a quick visual inspection of the file does show whether the expected variables are output at the desired time step.
eplusout.eio[LINK]
The EnergyPlus Invariant Output (EIO) is a text file containing output that does not vary with time. For instance, location information (latitude, longitude, time zone, altitude) appears on this file.
eplusout.rdd[LINK]
The Report (variable) Data Dictionary (RDD) is a text file listing those variables available for reporting (on the ESO or MTR) for this particular simulation. Which variables are available for output on the ESO or MTR depends on the actual simulation problem described in the IDF. A simulation with no chiller would not permit the output of any chiller report variables. The user may need to examine the RDD to find out which report variables are available in a particular simulation. The RDD is written only if
appears in the input (IDF) file.
eplusout.dbg[LINK]
This is a text file containing debug output for use by EnergyPlus developers. Generally developers will add debug print statements wherever in the code that that they wish. There is a “standard” debug output that prints out conditions at all the HVAC nodes. This output is triggered by placing
DEBUG OUTPUT,1;
in the IDF file. If DEBUG OUTPUT, 0 is entered, you will get an empty eplusout.dbg file.
eplusout.dxf[LINK]
This is a file in AutoCad DXF format showing all the surfaces defined in the IDF file. It provides a means of viewing the building geometry. The DXF file from EnergyPlus highlights different building elements (shading, walls, subsurfaces) in differing colors. A number of programs can read and display DXF files. One that works well is Volo View Express, available free from the Autodesk web site. Output of this file is triggered by
Report, Surfaces, DXF;
in the IDF.
eplusout.sln[LINK]
A text file containing the coordinates of the vertices of the surfaces in the IDF.
Output of this file is triggered by
Report, Surfaces, Lines;
in the IDF.
Postprocessing Program/Files[LINK]
A postprocessing program ReadVarsESO.exe is available that will read an ESO or MTR file and produce a file that can be read by ExcelTM. It can use an input file or not. In batch mode it is run by the little batch file RunReadESO.bat: Further information on this program is provided in the Input Output Reference as well as the Output Details and Examples documents.
You can also used the CSVProc and convertESOMTR described earlier in this document as part of your post processing strategy.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.