UtilityCost:Ratchet[LINK]
The UtilityCost:Ratchet
command allows the modeling of tariffs that include some type
of seasonal ratcheting. Ratchets are most common when used
with electric demand charges. A ratchet is when a utility
requires that the demand charge for a month with a low demand
may be increased to be more consistent with a month that set a
higher demand charge.
While the details of the UtilityCost:Ratchet
command are described further in this section, an example is
probably the easiest way to learn the basic functions.
Ratchet Example: A utility has a single ratchet that says
that the billing demand for each month of the year is the
higher value of the actual demand or 60% of the peak summer
demand
UtilityCost:Ratchet,
BillingDemand1, ! Ratchet Variable Name
ExampleTariff1, ! Tariff Name
TotalDemand, ! Baseline Source Variable
TotalDemand, ! Adjustment Source Variable
Summer, ! Season From
Annual, ! Season To
0.60, ! Multiplier Value or Variable Name
0; ! Offset Value or Variable Name
The Ratchet Variable Name (the first field) should be used
wherever the ratchet should be applied and is often the source
variable for UtilityCost:Charge:Simple
or UtilityCost:Charge:Block.
The detailed steps taken for the ratchet are the
following:
AdjSeasonal contains either:
When SeasonFrom is not set to Monthly, the maximum for
all months in Season From in the Adjustment Source Variable.
This is a single value.
When SeasonFrom is set to Monthly, the monthly values
of the Adjustment Source Variable.
AdjPeak = (AdjSeasonal + Offset) * Multiplier
MaxAdjBase = maximum value of either AdjPeak or
Baseline Source Variable
The resulting Ratchet Variable contains:
For months not in SeasonTo, the values of Baseline
Source Variable
For months in SeasonTo, the values of
MaxAdjBase
If multiple ratchets occur in the same tariff, multiple UtilityCost:Ratchet
commands should be “chained” together with the Baseline Source
Variable subsequent ratchets referencing the Ratchet Variable
Name of the previous UtilityCost:Ratchet.
Since the ratchet command can add together two variables,
mutliply two variables, or take the maximum value between two
variables, it may be used for other difficult to model tariffs
without needing to use UtilityCost:Computation.
Clever use of UtilityCost:Ratchet
should be well documented with comments.
Field: Ratchet Variable
Name[LINK]
The name of the ratchet and the name of the result of this
single ratchet.
Field: Tariff Name[LINK]
The name of the tariff that this UtilityCost:Ratchet
is associated with.
Field: Baseline Source
Variable[LINK]
The name of the variable used as the baseline value. When
the ratcheted value exceeds the baseline value for a month the
ratcheted value is used but when the baseline value is greater
then the ratcheted value the baseline value is used. Usually
the electric demand charge is used. The baseline source
variable can be the results of another ratchet object. This
allows utility tariffs that have multiple ratchets to be
modeled.
Field: Adjustment
Source Variable[LINK]
The variable that the ratchet is calculated from. It is
often but not always the same as the baseline source variable.
The ratcheting calculations using offset and multiplier are
using the values from the adjustment source variable. If left
blank, the adjustment source variable is the same as the
baseline source variable.
Field: Season From[LINK]
The name of the season that is being examined. The maximum
value for all of the months in the named season is what is
used with the multiplier and offset. This is most commonly
Summer or Annual. When Monthly is used, the adjustment source
variable is used directly for all months.
Annual
Winter
Spring
Summer
Fall
Monthly
Field: Season To[LINK]
The name of the season when the ratchet would be
calculated. This is most commonly Winter. The ratchet only is
applied to the months in the named season. The resulting
variable for months not in the Season To selection will
contain the values as appear in the baseline source
variable.
Annual
Winter
Spring
Summer
Fall
Field:
Multiplier Value or Variable Name[LINK]
Often the ratchet has a clause such as “the current month
demand or 90% of the summer month demand”. For this case a
value of 0.9 would be entered here as the multiplier. This
value may be left blank if no multiplier is needed and a value
of one will be used as a default.
Field: Offset
Value or Variable Name[LINK]
A less common strategy is to say that the ratchet must be
all demand greater than a value, in this case an offset that
is added to the demand may be entered here. If entered, it is
common for the offset value to be negative representing that
the demand be reduced. If no value is entered it is assumed
to be zero and not affect the ratchet.
UtilityCost:Ratchet[LINK]
The UtilityCost:Ratchet command allows the modeling of tariffs that include some type of seasonal ratcheting. Ratchets are most common when used with electric demand charges. A ratchet is when a utility requires that the demand charge for a month with a low demand may be increased to be more consistent with a month that set a higher demand charge.
While the details of the UtilityCost:Ratchet command are described further in this section, an example is probably the easiest way to learn the basic functions.
Ratchet Example: A utility has a single ratchet that says that the billing demand for each month of the year is the higher value of the actual demand or 60% of the peak summer demand
The Ratchet Variable Name (the first field) should be used wherever the ratchet should be applied and is often the source variable for UtilityCost:Charge:Simple or UtilityCost:Charge:Block.
The detailed steps taken for the ratchet are the following:
AdjSeasonal contains either:
When SeasonFrom is not set to Monthly, the maximum for all months in Season From in the Adjustment Source Variable. This is a single value.
When SeasonFrom is set to Monthly, the monthly values of the Adjustment Source Variable.
AdjPeak = (AdjSeasonal + Offset) * Multiplier
MaxAdjBase = maximum value of either AdjPeak or Baseline Source Variable
The resulting Ratchet Variable contains:
For months not in SeasonTo, the values of Baseline Source Variable
For months in SeasonTo, the values of MaxAdjBase
If multiple ratchets occur in the same tariff, multiple UtilityCost:Ratchet commands should be “chained” together with the Baseline Source Variable subsequent ratchets referencing the Ratchet Variable Name of the previous UtilityCost:Ratchet.
Since the ratchet command can add together two variables, mutliply two variables, or take the maximum value between two variables, it may be used for other difficult to model tariffs without needing to use UtilityCost:Computation. Clever use of UtilityCost:Ratchet should be well documented with comments.
Inputs[LINK]
Field: Ratchet Variable Name[LINK]
The name of the ratchet and the name of the result of this single ratchet.
Field: Tariff Name[LINK]
The name of the tariff that this UtilityCost:Ratchet is associated with.
Field: Baseline Source Variable[LINK]
The name of the variable used as the baseline value. When the ratcheted value exceeds the baseline value for a month the ratcheted value is used but when the baseline value is greater then the ratcheted value the baseline value is used. Usually the electric demand charge is used. The baseline source variable can be the results of another ratchet object. This allows utility tariffs that have multiple ratchets to be modeled.
Field: Adjustment Source Variable[LINK]
The variable that the ratchet is calculated from. It is often but not always the same as the baseline source variable. The ratcheting calculations using offset and multiplier are using the values from the adjustment source variable. If left blank, the adjustment source variable is the same as the baseline source variable.
Field: Season From[LINK]
The name of the season that is being examined. The maximum value for all of the months in the named season is what is used with the multiplier and offset. This is most commonly Summer or Annual. When Monthly is used, the adjustment source variable is used directly for all months.
Annual
Winter
Spring
Summer
Fall
Monthly
Field: Season To[LINK]
The name of the season when the ratchet would be calculated. This is most commonly Winter. The ratchet only is applied to the months in the named season. The resulting variable for months not in the Season To selection will contain the values as appear in the baseline source variable.
Annual
Winter
Spring
Summer
Fall
Field: Multiplier Value or Variable Name[LINK]
Often the ratchet has a clause such as “the current month demand or 90% of the summer month demand”. For this case a value of 0.9 would be entered here as the multiplier. This value may be left blank if no multiplier is needed and a value of one will be used as a default.
Field: Offset Value or Variable Name[LINK]
A less common strategy is to say that the ratchet must be all demand greater than a value, in this case an offset that is added to the demand may be entered here. If entered, it is common for the offset value to be negative representing that the demand be reduced. If no value is entered it is assumed to be zero and not affect the ratchet.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.