Group
- Zone Controls - Thermostats and Humidistats[LINK]
Zone
Control objects are used to control zone conditions to a
specific setpoint. The six types of zone control are described
in this section. They are, by name,
ZoneControl:<name>.. These types
are:
Thermostat - The object provides the
traditional approach to space control using air temperatures.
Each controlled zone contains a thermostat object.
Humidistat - The object is used to control
a zone to a specified relative humidity.
Thermostat:ThermalComfort - The object
provides a method to control a zone to a dry-bulb temperature
setpoint based on a thermal comfort model (e.g. Fanger) and a
user-specified thermal comfort setpoint schedule.
Thermostat:OperativeTemperature - The
operative temperature control is formulated to reuse all of
the traditional thermostat objects. One input object will be
used for each thermal zone to indicate if that zone’s
thermostat control mode should be overridden to effect
operative temperature control rather than traditional air
temperature control. The user will still have to input all the
traditional ZoneControl:Thermostat
and setpoint objects.
Thermostat:TemperatureAndHumidity - This
thermostat control works together with the traditional ZoneControl:Thermostat
object to modify temperature control based on zone air
humidity conditions. Currently, this object resets the
thermostat’s cooling setpoint temperature downward based on
elevated zone air humidity levels, typically yielding
additional cooling coil operation and associated
dehumidification. A ZoneControl:Thermostat:TemperatureAndHumidity
object should be specified to indicate if a zone’s traditional
thermostat control mode should be overridden to provide
enhanced dehumidification. The user must still input the
traditional ZoneControl:Thermostat
and setpoint objects.
Thermostat:StagedDualSetpoint
- This thermostat control works alone with “Dual Setpoint”
type only. The object provides heating and cooling setpoints,
throttling range and offsets, so that zone temperature
setpoint used for system load calculation is adjusted by the
setpoint and throttling range based on the zone temperature at
the previous time step. The stage number is determined by the
temperature difference between the setpoint and zone
temperature at the previous time step, and offset values. If
this object and other zone control thermostat and humidistat
are assigned to the same controlled zone, this object takes
precedence when the controlled zone is specified in the
Controlling Zone
or Thermostat Location field of the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object.
ZoneControl:Thermostat[LINK]
The thermostatic zone control object is used to control a
zone to a specified temperature. ZoneControl:Thermostat
references a control type schedule and one or more control
type objects which in turn reference one or more setpoint
schedules. The example at the end of this section illustrates
a complete zone thermostat specification including the control
type and setpoint schedules.
The control type schedule and the list of control type/name
pairs are directly related. The schedule defines the type of
control that is to be used throughout the simulation. Valid
Control Types are:
0 - Uncontrolled (No specification or default)
1 - Single Heating Setpoint
2 - Single Cooling SetPoint
3 - Single Heating/Cooling Setpoint
4 - Dual Setpoint (Heating and Cooling) with deadband
Thus, if the schedule referenced in the ZoneControl:Thermostat
statement has a control type of 4 for a particular time
period, this indicates that during that time period “Dual
Setpoint with deadband” control is to be used. The specific
“Dual Setpoint (Heating and Cooling) with deadband” control
object to be used is specified in the list of control
type/name pairs. Then the specific control type objects
reference the thermostat setpoint temperature schedule to be
used. Because only one control can be specified for each
control type in a ZoneControl:Thermostat
statement, there are only four pairs possible in a particular
ZoneControl:Thermostat
type/name list. This is because individual controls can be
defined throughout the simulation, thus giving the user a full
range of flexibility. Since putting in the name of the control
type directly in the schedule would be very cumbersome, the
control types are assigned a number which is used in the
schedule profile.
Unique identifying name for the thermostat.
Field: Zone or
ZoneList Name[LINK]
Name of the zone or set of zones that is being controlled.
When the ZoneList
option is used then this thermostat definition is applied to
each of the zones in the zone list effecting a global
definition for thermostatic control in the zone.
Field: Control Type
Schedule Name[LINK]
Schedule which defines what type of control is active
during the simulation. Valid Control Types are:
0 - Uncontrolled (No specification or default)
1 - Single Heating Setpoint
2 - Single Cooling SetPoint
3 - Single Heating Cooling Setpoint
4 - Dual Setpoint with Deadband (Heating and Cooling)
Each non-zero control type which is used in this schedule
must appear in the following fields which list the specific
thermostat control objects to be used for this zone.
Field Set
(Control Object Type, Control Name)[LINK]
Up to four pairs of Control Object Type and Control Name
may be listed to specify which control objects are used for
this zone. This list is not order-dependent, and the position
in this list has no impact on the control type schedule. In
the control type schedule, a value of 1 always means “Single
Heating Setpoint”, even if that control type is not first in
this list.
Field: Control Object
<x>Type[LINK]
This field specifies the control type to be used for this
zone. Available control types are:
ThermostatSetpoint:SingleHeating
ThermostatSetpoint:SingleCooling
ThermostatSetpoint:SingleHeatingOrCooling
ThermostatSetpoint:DualSetpoint
Field: Control <x>
Name[LINK]
The corresponding control type name. The name is used in an
object with the name of the control type and specifies the
schedule.
Field:
Temperature Difference Between Cutout And Setpoint[LINK]
This optional choice field provides a temperature
difference between cutout temperature and setpoint. When the
temperature difference is greater than 0.0, the difference is
applied to both heating and cooling by possibly revising
setpoints based on control types.
If MAT is defined as zone air temperature at previous time
step, DeltaT represents the temperature difference between
cutout and setpoint and is greater than 0.0, and PredictedLoad
represents predicted load calculated in the
ZoneTempPredictorCorrector, following action will be
taken:
0 - Uncontrolled (No specification or default)
No change
1 - Single Heating Setpoint
If ( MAT < ThermostatSetpoint:SingleHeating )
ThermostatSetpoint:SingleHeating = ThermostatSetpoint:SingleHeating + DeltaT
Else
No change
End If
2 - Single Cooling SetPoint
If ( MAT > ThermostatSetpoint:SingleCooling )
ThermostatSetpoint:SingleCooling = ThermostatSetpoint:SingleCooling - DeltaT
Else
No change
End If
3 - Single Heating/Cooling Setpoint
No change
4 - Dual Setpoint (Heating and Cooling) with deadband
If ( MAT < HeatingSetpoint )
HeatingSetpoint = HeatingSetpoint + DeltaT
CoolingSetpoint = No change
Else If ( MAT > CoolingSetpoint )
HeatingSetpoint = No change
CoolingSetpoint = CoolingSetpoint - DeltaT
Else
No change
End If
Note that this option should be used in caution. Following
recommendations may be used to input the value of Temperature
Difference Between Cutout And Setpoint:
1. The heating and cooling setpoints must be separated by at least 2 times the Temperature Difference Between Cutout And Setpoint or there will be a fatal error.
2. The thermostat setpoint not met hours are incorrect with this option.
3. This option will cause excess operation of heat pump system supplemental heating coils.
An example of this statement in an IDF is:
ZoneControl:Thermostat, Zone 3 Thermostat, NORTH ZONE,
Zone Control Type Sched,
DUAL SETPOINT WITH DEADBAND, VAV Setpoints;
An example of a global thermostat:
ZoneList,AllControlledZones,SPACE1-1,SPACE2-1,SPACE3-1,SPACE4-1,SPACE5-1;
ZoneControl:Thermostat,
AllControlledZones Thermostat, !- Name
AllControlledZones, !- Zone Name
Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:SingleCooling, !- Control 1 Object Type
CoolingSetPoint, !- Control 1 Name
ThermostatSetpoint:SingleHeating, !- Control 2 Object Type
HeatingSetpoint, !- Control 2 Name
ThermostatSetpoint:DualSetpoint, !- Control 3 Object Type
DualSetPoint; !- Control 3 Name
A complete zone thermostat example showing this statement
and all of the objects it must reference is:
! Zone control object which links thermostats to a particular zone
ZoneControl:Thermostat, Zone 2 Thermostat, EAST ZONE,
Zone Control Type Sched,
ThermostatSetpoint:SingleCooling, Cooling Setpoint with SB,
ThermostatSetpoint:SingleHeating; Heating Setpoint with SB;
! Control type objects these may be used in more than one zone
ThermostatSetpoint:SingleCooling,
Cooling Setpoint with SB,
Cooling Setpoints;
ThermostatSetpoint:SingleHeating,
Heating Setpoint with SB,
Heating Setpoints;
! Schedule type definitions
ScheduleTypeLimits,Temperature,-60:200,CONTINUOUS;
ScheduleTypeLimits,Control Type,0:4,DISCRETE;
! Control type schedule definition
Schedule:Compact, Zone Control Type Sched, Control Type,
Through: 3/31,
For: AllDays,
Until: 24:00, 1, !- Single Heating
Through: 9/30,
For: AllDays,
Until: 24:00, 2, !- Single Cooling
Through: 12/31,
For: AllDays,
Until: 24:00, 1; !- Single Heating
! Heating setpoint schedule definition
Schedule:Compact, Heating Setpoints, Temperature,
Through: 12/31,
For: AllDays,
Until: 7:00, 15.,
Until: 17:00,20.,
Until: 24:00,15.;
! Cooling setpoint schedule definition
Schedule:Compact, Cooling Setpoints, Temperature,
Through: 12/31,
For: AllDays,
Until: 7:00, 30.,
Until: 20:00,23.,
Until: 24:00,30.;
Outputs available from controlled zones. The “key” in the
below is the Zone
Name.
HVAC,Average,Zone Predicted Sensible Load to Setpoint
Heat Transfer Rate [W]
HVAC,Average,Zone Predicted Sensible Load to Heating
Setpoint Heat Transfer Rate [W]
HVAC,Average,Zone Predicted Sensible Load to Cooling
Setpoint Heat Transfer Rate [W]
Zone,Average,Zone Thermostat Control Type []
Zone,Average,Zone Thermostat Heating Setpoint
Temperature [C]
Zone,Average,Zone Thermostat Cooling Setpoint
Temperature [C]
HVAC,Sum,Facility Any Zone
Oscillating Temperatures Time [hr]
Zone,Sum,Zone Heating Setpoint Not Met Time
[hr]
Zone,Sum,Zone Heating Setpoint Not Met While Occupied
Time [hr]
Zone,Sum,Zone Cooling Setpoint Not Met Time
[hr]
Zone,Sum,Zone Cooling Setpoint Not Met While Occupied
Time [hr]
Zone,Sum,Facility Heating Setpoint Not Met Time
[hr]
Zone,Sum,Facility Cooling Setpoint Not Met Time
[hr]
Zone,Sum,Facility Heating Setpoint Not Met While
Occupied Time [hr]
Zone,Sum,Facility Cooling Setpoint Not Met While
Occupied Time [hr]
Zone
Predicted Sensible Load to Setpoint Heat Transfer Rate
[W][LINK]
This is the predicted sensible load in W required to meet
the current zone thermostat setpoint. A positive value
indicates a heating load, a negative value indicates a cooling
load. This is calculated and reported from the Predict step in
the Zone
Predictor-Corrector module. For nearly all equipment types,
the Predictor-Corrector evaluates the active heating and/or
cooling setpoints, determines if the zone requires heating or
cooling or is in the deadband, and then passes this single
load to the equipment. This value is not multiplied by zone or
group multipliers.
Zone
Predicted Sensible Load to Heating Setpoint Heat Transfer Rate
[W][LINK]
This is the predicted sensible load in W required to meet
the current zone thermostat heating setpoint. A positive value
indicates a heating load, a negative value indicates a cooling
load. This is calculated and reported from the Predict step in
the Zone
Predictor-Corrector module. This value is not multiplied by
zone or group multipliers.
Zone
Predicted Sensible Load to Cooling Setpoint Heat Transfer Rate
[W][LINK]
This is the predicted sensible load in W required to meet
the current zone thermostat cooling setpoint. A positive value
indicates a heating load, a negative value indicates a cooling
load. This is calculated and reported from the Predict step in
the Zone
Predictor-Corrector module. This value is not multiplied by
zone or group multipliers.
Zone Thermostat Control
Type [][LINK]
This is the current zone thermostat control type (0 through
4). This value is set at each zone timestep. Using the
averaged value for longer reporting frequencies (hourly, for
example) may not be meaningful in some applications.
Zone
Thermostat Heating Setpoint Temperature [C][LINK]
This is the current zone thermostat heating setpoint in
degrees C. If there is no heating thermostat active, then the
value will be 0. This value is set at each zone timestep.
Using the averaged value for longer reporting frequencies
(hourly, for example) may not be meaningful in some
applications.
When the Thermostat:StagedDualSetpoint object is applied to
the current zone, this output variable reports staged zone
heating setpoint. When the staged number is not equal to zero,
both staged heating and cooling setpoints are the same. When
no cooling or heating is required, the staged heating setpoint
is equal to the scheduled heating setpoint 0.5 * heating
throttling range, and the staged cooling setpoint is equal to
the scheduled cooling setpoint + 0.5 * cooling throttling
range.
Zone
Thermostat Cooling Setpoint Temperature [C][LINK]
This is the current zone thermostat cooling setpoint in
degrees C. If there is no cooling thermostat active, then the
value will be 0. This value is set at each zone timestep.
Using the averaged value for longer reporting frequencies
(hourly, for example) may not be meaningful in some
applications.
When the Thermostat:StagedDualSetpoint object is applied to
the current zone, this output variable reports staged zone
cooling setpoint. When the staged number is not equal to zero,
both staged heating and cooling setpoints are the same. When
no cooling or heating is required, the staged heating setpoint
is equal to the scheduled heating setpoint 0.5 * heating
throttling range, and the staged cooling setpoint is equal to
the scheduled cooling setpoint + 0.5 * cooling throttling
range.
Zone Thermostat Stage
Number [][LINK]
This is the current zone thermostat stage number when the
ZoneControl:Thermostat:StagedDualSetpoint
object is specified in this zone. When no heating or cooling
is required, the stage number is set to 0. When heating is
required, the stage number is positive. When cooling is
required, the stage number is negative. The absolute number is
sent to the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object to specify the speed number accordingly.
Zone Heating
Setpoint Not Met Time [hr][LINK]
Hours when the zone temperature is lower than 0.2 (default)
degrees C below the heating setpoint. See the OutputControl:ReportingTolerances
object to change the reporting range from 0.2 degrees C.
Zone
Heating Setpoint Not Met While Occupied Time [hr][LINK]
Hours when the zone temperature is lower than 0.2 (default)
degrees C below the heating setpoint and when people are
present in the zone. To change the reporting range from 0.2
degrees C, see the OutputControl:ReportingTolerances
object.
Zone Cooling
Setpoint Not Met Time [hr][LINK]
Hours when the zone temperature is greater than 0.2
(default) degrees C above the cooling setpoint. See the OutputControl:ReportingTolerances
object to change the reporting range from 0.2 degrees C.
Zone
Cooling Setpoint Not Met While Occupied Time [hr][LINK]
Hours when the zone temperature is greater than 0.2
(default) degrees C above the cooling setpoint and when people
are present in the zone. To change the reporting range from
0.2 degrees C, see the OutputControl:ReportingTolerances
object.
Facility
Heating Setpoint Not Met Time [hr][LINK]
Hours when the zone temperature is lower than 0.2 (default)
degrees C below the heating setpoint in any one or more zones.
See the OutputControl:ReportingTolerances
object to change the reporting range from 0.2 degrees C.
Facility
Heating Setpoint Not Met While Occupied Time [hr][LINK]
Hours when the zone temperature is lower than 0.2 (default)
degrees C below the heating setpoint and when people are
present in any one or more zones. To change the reporting
range from 0.2 degrees C, see the OutputControl:ReportingTolerances
object.
Facility
Cooling Setpoint Not Met Time [hr][LINK]
Hours when the zone temperature is greater than 0.2
(default) degrees C above the cooling setpoint in any one or
more zones. See the OutputControl:ReportingTolerances
object to change the reporting range from 0.2 degrees C.
Facility
Cooling Setpoint Not Met While Occupied Time [hr][LINK]
Hours when the zone temperature is greater than 0.2
(default) degrees C above the cooling setpoint and when people
are present in any one or more zones. To change the reporting
range from 0.2 degrees C, see the OutputControl:ReportingTolerances
object.
Zone Oscillating
Temperatures Time[hr][LINK]
Hours when the temperature in the zone is oscillating back
and forth. Oscillation is defined as times when the three
differences between zone temperatures during successive
timesteps are greater in magnitude than 0.15 degrees C and the
sign of the differences changes from positive to negative to
positive or from negative to positive to negative.
This may indicate a simulation with reduced reliability
during the oscillation. Some oscillating hours should be
expected in all simulations but excessive oscillations call
into question the overall validity of the results. If
excessive oscillations are occurring, try reducing the minimum
system timestep (see ConvergenceLimits
object) and the zone timestep (see the TimeStep object).
Reducing these timestep lengths does increase the total
computer time needed to complete the simulation. Having the
zone timestep and the minimum system timestep the same length
of time can also cause more oscillations. What amount of
oscillations is considered excessive is difficult to quantify.
One approach is comparing the number of oscillations to the
case with 15 minute zone timesteps (4 per hour) and 1 minute
minimum system timesteps. Often this variable is used as an
indicator of the validity of the results when trying to
decrease the time needed to perform the simulation.
Facility
Any Zone Oscillating Temperatures Time[hr][LINK]
Hours when any zone in the building has oscillations. See
Zone
Oscillating Temperatures Time definition above.
Zone Thermostat
Setpoints[LINK]
The syntax for the current set of four zone thermostat
setpoint objects is given below. In each case, the keyword is
accompanied by an identifying name and either one or two
schedule names (depending on whether the control is a single
or dual setpoint control). The schedule defines a temperature
setpoint for the control type. The schedule would be defined
through the standard schedule syntax described earlier in this
document. For an uncontrolled zone no thermostat is specified
or necessary.
ThermostatSetpoint:SingleHeating[LINK]
This would be for a heating only thermostat. The setpoint
can be scheduled and varied throughout the simulation but only
heating is allowed with this control type.
Unique name for this control type.
Field:
Setpoint Temperature Schedule Name[LINK]
The name of the associated schedule. Values in the schedule
are temperatures {C}.
ThermostatSetpoint:SingleCooling[LINK]
This would be for a cooling only thermostat. The setpoint
can be scheduled and varied throughout the simulation but only
cooling is allowed.
Unique name for this control type.
Field:
Setpoint Temperature Schedule Name[LINK]
The name of the associated schedule. Values in the schedule
are temperatures {C}.
ThermostatSetpoint:SingleHeatingOrCooling[LINK]
This would be for heating and cooling thermostat but only
heating or cooling can be scheduled at any given time period.
The setpoint can be scheduled and varied throughout the
simulation for both heating and cooling.
Unique name for this control type.
Field:
Setpoint Temperature Schedule Name[LINK]
The name of the associated schedule. Values in the schedule
are temperatures {C}.
ThermostatSetpoint:DualSetpoint[LINK]
This would be for heating and cooling thermostat where both
a heating and cooling setpoint can be scheduled for any given
time period. The setpoint can be scheduled and varied
throughout the simulation for both heating and cooling.
Unique name for this control type.
Field:
Heating Setpoint Temperature Schedule Name[LINK]
The heating temperature schedule. Values in the schedule
are temperatures {C}.
Field:
Cooling Setpoint Temperature Schedule Name[LINK]
The cooling temperature schedule. Values in the schedule
are temperatures {C}.
Examples of these statements in an IDF are:
ThermostatSetpoint:SingleHeating, Heating Setpoint with SB, Heating Setpoints;
ThermostatSetpoint:SingleCooling, Cooling Setpoint with SB, Cooling Setpoints;
ThermostatSetpoint:SingleHeatingOrCooling, Heating Cooling Setpoint Sched, Heating Cooling Setpoints;
ThermostatSetpoint:DualSetpoint, VAV Setpoints, Heating Setpoints, Cooling Setpoints;
ZoneControl:Thermostat:OperativeTemperature[LINK]
This object is used to modify the program’s behavior for ZoneControl:Thermostat
objects. One input object is used for each thermal zone to
indicate if that zone’s thermostat control mode should be
overridden to effect operative temperature control rather than
traditional air temperature control. Zone
Control:Thermostatic and related setpoint objects also need to
be included in the input file. When this object is used, the
zone can be controlled by a weighted mixture of radiant and
air temperatures (rather than just air temperatures).
When using this object, the setpoint temperature values
(e.g. input in schedules named in ThermostatSetpoint:DualSetpoint
objects) become targets for the desired operative
temperatures. As of version 8.7 new options are added that
allow automatically generating values for the setpoint
temperature, as a function of outdoor air temperatures, using
various adaptive comfort models based on ASHRAE Standard
55-2010 and CEN 15251-2007. The adaptive comfort model relates
the zone operative temperature setpoint to the recent history
of the outdoor air temperatures. The adaptive comfort models
only apply to cooling mode and generate a single setpoint
value for each day. During summer time in hot climates, the
zone thermostat setting can be higher than the traditional
thermostat setting based on the adaptive thermal comfort
model, which results in energy savings of HVAC systems.
This thermostatic operative temperature, \({T_{OP}}\) , is defined as:
\[{T_{OP}} = \gamma {T_{MRT}} +
(1 - \gamma ){T_{drybulb}}\]
where,
\(\gamma\) is the
radiative fraction,
\({T_{MRT}}\) is the mean
radiant temperature for the thermal zone, and
\({T_{drybulb}}\) is the
mean zone air temperature.
The radiative fraction \(\gamma\) is selected by the user
and can be scheduled to vary during the simulation. A typical
value is 0.5. The maximum value needs to be less than 0.9 and
the minimum is 0.0. A value of 0.0 is the same as controlling
on only zone air temperature. If air velocities are higher
than 0.2 m/s, then lower values for radiative fraction might
apply. Niu and Burnett (1998) cite International Standard ISO
77300 in recommending the values for this fraction listed in
the following table.
Radiative Fraction vs Air Velocity (Operative
Temperature Control)
| Air Velocity (m/s) |
< 0.2 |
0.2 to 0.6 |
0.6 to 1.0 |
| \(\gamma\) |
0.5 |
0.4 |
0.3 |
When the adaptive comfort model is selected, the thermostat
setpoint temperature schedule for space cooling will be
overwritten with the calculated operative temperature based on
the selected acceptability limits of the comfort model defined
in ASHRAE 55-2010 or CEN 15251-2007. The ASHRAE adaptive
comfort model is only applicable when the running average
outdoor air temperature for the past 30 days is between 10.0
and 33.5°C; while the CEN 15251-2007 adaptive comfort model is
only applicable when the running average outdoor air
temperature for the past 7 days is between 10.0 and 30.0°C.
The user can choose whether to overwrite the cooling setpoint
temperature only when the adaptive setpoint is higher than the
user input one for the purpose of energy saving.
Reference:
Niu and J. Burnett. 1998. Integrating Radiant/Operative
Temperature Controls into Building
Energy Simulations. ASHRAE Transactions Vol. 104. Part 2. page
210. ASHRAE. Atlanta, GA.
ASHRAE Standard 55-2010. Thermal environment conditions
for human occupancy. ASHRAE, Atlanta.
Field: Thermostat Name[LINK]
Name of ZoneControl:Thermostat
object defined elsewhere in the input file whose operation is
to be modified to effect control based on operative
temperature. If the ZoneControl:Thermostat
references a ZoneList
(set of zones) then, this operative temperature thermostat
will be applied to each of those zones. If only a single
thermostat/zone is desired, then the name to be put here is
<zone name> <Thermostat Name> where the Thermostat
name is the thermostat that referenced the set of zones.
This field controls whether the input for radiative
fraction is a constant value or if it is entered using a
schedule. Enter Constant here to use a fixed
radiative fraction defined in the following field. Enter
Scheduled to vary the radiative fraction
according to the schedule named in the second field below.
Field: Fixed Radiative
Fraction[LINK]
This is the fraction, \(\gamma\), of the operative
temperature that is due to the mean radiant temperature in the
zone. This field is used by the program if the previous field
is set to Constant.
Field:
Radiative Fraction Schedule Name[LINK]
This field contains the name of a schedule, defined
elsewhere, that determines the value for radiative fraction
\(\gamma\) during the
simulation period. This schedule should have fractional values
from 0.0 to 0.9. When the value of this schedule is 0.0, the
controlling will be equivalent to control based only on zone
air temperature. This field is used by the program if the
Input Mode field is set to Scheduled.
Note that by setting the values in this schedule separately
for design days, the user can control how operative
temperature control is applied during autosizing. (Operative
temperature control tends to increase the equipment capacities
calculated during sizing.)
Field: Adaptive
Comfort Model Type[LINK]
This field controls which of the seven adaptive comfort
model is chosen, if any, listed as following:
None. The adaptive comfort model is not applied and the
setpoint temperatures are not adjusted from those input in the
thermostat setpoints.
AdaptiveASH55CentralLine. The central line of the
acceptability limits of the ASHRAE Standard 55-2010 adaptive
comfort model will be used to generate the zone operative
temperature setpoint.
AdaptiveASH5580PercentUpperLine. The upper line of the
80% acceptability limits of the ASHRAE Standard 55-2010
adaptive comfort model will be used to generate the zone
operative temperature setpoint.
AdaptiveASH5590PercentUpperLine. The upper line of the
90% acceptability limits of the ASHRAE Standard 55-2010
adaptive comfort model will be used to generate the zone
operative temperature setpoint.
AdaptiveCEN15251CentralLine. The central line of the
acceptability limits of the CEN Standard 15251-2007 adaptive
comfort model will be used to generate the zone operative
temperature setpoint.
AdaptiveCEN15251CategoryIUpperLine. The upper line of
the Category I of the acceptability limits of the CEN Standard
15251-2007 adaptive comfort model will be used to generate the
zone operative temperature setpoint.
AdaptiveCEN15251CategoryIIUpperLine. The upper line of
the Category II of the acceptability limits of the CEN
Standard 15251-2007 adaptive comfort model will be generate to
adjust the zone operative temperature setpoint; and
AdaptiveCEN15251CategoryIIIUpperLine. The upper line of
the Category III of the acceptability limits of the CEN
Standard 15251-2007 adaptive comfort model will be generate as
the zone operative temperature setpoint.
An example of this object follows.
ZoneControl:Thermostat:OperativeTemperature,
Zone 1 Thermostat, !- ZoneControl:Thermostat Name
Constant, !- Radiative Fraction Input Mode
0.5, !- Fixed Radiative Fraction
, !- Radiative Fraction Schedule
AdaptiveASH55CentralLine; !- Adaptive Comfort Model Type
Global operative temperature applied to all zones for a
global thermostat:
ZoneList,AllControlledZones,SPACE1-1,SPACE2-1,SPACE3-1,SPACE4-1,SPACE5-1;
ZoneControl:Thermostat,
AllControlledZones Thermostat, !- Name
AllControlledZones, !- Zone Name
Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:SingleCooling, !- Control 1 Object Type
CoolingSetPoint, !- Control 1 Name
ThermostatSetpoint:SingleHeating, !- Control 2 Object Type
HeatingSetpoint, !- Control 2 Name
ThermostatSetpoint:DualSetpoint, !- Control 3 Object Type
DualSetPoint; !- Control 3 Name
ZoneControl:Thermostat:OperativeTemperature,
AllControlledZones Thermostat, !- Thermostat Name
CONSTANT, !- Radiative Fraction Input Mode
0.4; !- Fixed Radiative Fraction
Global operative temperature referencing a single zone from
the list:
ZoneList,AllControlledZones,SPACE1-1,SPACE2-1,SPACE3-1,SPACE4-1,SPACE5-1;
ZoneControl:Thermostat,
AllControlledZones Thermostat, !- Name
AllControlledZones, !- Zone Name
Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:SingleCooling, !- Control 1 Object Type
CoolingSetPoint, !- Control 1 Name
ThermostatSetpoint:SingleHeating, !- Control 2 Object Type
HeatingSetpoint, !- Control 2 Name
ThermostatSetpoint:DualSetpoint, !- Control 3 Object Type
DualSetPoint; !- Control 3 Name
ZoneControl:Thermostat:OperativeTemperature,
SPACE3-1 AllControlledZones Thermostat, !- Thermostat Name
CONSTANT, !- Radiative Fraction Input Mode
0.4; !- Fixed Radiative Fraction
- Zone,Average,Zone Thermostat Operative Temperature
[C]
Zone
Thermostat Operative Temperature [C][LINK]
Operative temperature (OT) is a weighted mixture of Zone
Mean Air Temperature (MAT) and Zone
Mean Radiant Temperature (MRT), using the current value of
Radiative Fraction (RF): OT = (1-RF)*MAT + RF*MAT. This output
variable does not include the direct effect of high
temperature radiant systems. See also Zone
Operative Temperature.
ZoneControl:Thermostat:TemperatureAndHumidity[LINK]
This object is used to modify the behavior of ZoneControl:Thermostat
objects (control types ThermostatSetpoint:SingleCooling
and ThermostatSetpoint:DualSetpoint
only) based on zone air humidity conditions. Specifically,
this TemperatureAndHumidity zone control resets the
ZoneControl:Thermostat’s cooling setpoint temperature downward
when the zone air relative humidity exceeds the Dehumidifying
Relative Humidity Setpoint defined in this object. The reduced
cooling setpoint temperature typically results in longer
cooling coil runtimes and additional dehumidification. The
rate at which the cooling setpoint temperature is reduced is
dictated by the user-specified Overcool Control Ratio. The
maximum reduction in cooling setpoint temperature is defined
by the user-entered OverCool Range (user choice of a constant
value for the entire simulation or a schedule that can define
how the overcool range varies over time). For details
regarding the calculations, see the EnergyPlus Engineering
Reference.
Note: As described above, this ZoneControl:Thermostat:TemperatureAndHumidity
control object modifies the cooling setpoint temperature of ZoneControl:Thermostat
objects. The ZoneControl:Thermostat:TemperatureAndHumidity
object works independently of the ZoneControl:Humidistat
object; that is, it does not replace the need for, or
coordinate its input fields with, ZoneControl:Humidistat
objects that are required for other types of high humidity
control (e.g., ZoneControl:Humidstat objects are required for
ZoneHVAC:Dehumidifier:DX
objects, AirLoopHVAC:Unitary* objects with CoolReheat or
MultiMode dehumidification control types, etc.)
Field: Thermostat Name[LINK]
Name of ZoneControl:Thermostat
object defined elsewhere in the input file whose operation is
to be modified to effect temperature control based on zone air
humidity conditions. If the ZoneControl:Thermostat
references a ZoneList
(set of zones), then simply enter the name of the ZoneControl:Thermostat
object and this TemperatureAndHumidity thermostat control will
be applied to all zones in the ZoneList.
If the ZoneControl:Thermostat
references a ZoneList
but it is desired that only a single zone within the ZoneList
be controlled based on TemperatureAndHumidity control, then
the name to be put here is <zone name> <Thermostat
Name> where the Thermostat Name is the name of the ZoneControl:Thermostat
object.
Field:
Dehumidifying Relative Humidity Setpoint Schedule Name[LINK]
Name of a schedule that defines the dehumidifying relative
humidity setpoint, expressed as a percentage (0-100), for each
timestep of the simulation. This input field is required. This
input field has absolutely no relationship or influence on the
Dehumidifying Relative Humidity Setpoint Schedule Name
optional input field in the ZoneControl:Humidistat
object.
Field:Dehumidification
Control Type[LINK]
This input field defines what type of dehumidification
control is active during the simulation. Valid control types
are None and Overcool. The default is Overcool if this field
is left blank. Overcool resets the thermostat’s cooling
setpoint temperature lower based on the zone air relative
humidity level. None means no overcooling (i.e., traditional
zone air temperature control based on the associated ZoneControl:Thermostat
object [Thermostat Name input field above] will be in
effect).
This field controls whether the input for the overcool
(temperature) range is a constant value or if it is entered
using a schedule. Enter Constant here to use
a constant overcool range defined in the Overcool Constant
Range input field below. Enter Scheduled to
vary the overcool range according to the schedule named in the
Overcool Range Schedule Name input field below. The default is
Constant if this field is left blank.
Field: Overcool
Constant Range[LINK]
This field specifies a fixed maximum overcool temperature
range for cooling setpoint temperature reduction for zone
overcool dehumidification in units of deltaC. This field is
used if the Overcool Range Input Method is specified as
Constant. The Overcool dehumidification
control type only works with ZoneControl:Thermostat
control types ThermostatSetpoint:SingleCooling
and ThermostatSetpoint:DualSetpoint
. For ThermostatSetpoint:DualSetpoint
, the model will use the smaller of the
Overcool Constant Range input value or the difference between
the cooling and heating setpoint temperatures specified in the
ThermostatSetpoint:DualSetpoint
object. The Overcool Constant Range must be greater than or
equal to zero with a maximum value of 3 °C. A value of 0.0
indicates no zone air overcooling. The default value is 1.7 °C
(3 °F) if this input field is left blank.
Field: Overcool
Range Schedule Name[LINK]
This field contains the name of a schedule, defined
elsewhere, that determines the value for the overcool range
during the simulation period. This schedule should contain
values from 0.0 to < = 3.0 (deltaC). When the value of this
schedule is 0.0, the zone air temperature control will be
based only on zone air dry-bulb temperature (i.e., no zone
overcooling). This field is used by the program if the
Overcool Range Input Method field is set to
Scheduled. Overcool dehumidification control
type only works with ZoneControl:Thermostat
control types ThermostatSetpoint:SingleCooling
and ThermostatSetpoint:DualSetpoint
. For ThermostatSetpoint:DualSetpoint
, the model will use the smaller of the
Overcool Range values specified in this schedule or the
difference between the cooling and heating setpoint
temperatures specified in the ThermostatSetpoint:DualSetpoint
object.
Note that by setting the values in this schedule separately
for design days, the user can control how Overcool
Dehumidification Control is applied during autosizing.
(Overcool dehumidification control tends to increase the
cooling equipment capacities calculated during sizing.)
Field:Overcool Control
Ratio[LINK]
The value of this input field is used to adjust the cooling
setpoint temperature (established by the associated ZoneControl:Thermostat
object) downward based on the difference between the zone air
relative humidity level and the Dehumidifying Relative
Humidity Setpoint. This input field is only used with
Dehumidification Control Type = Overcool. Input values must be
greater than or equal to 0.0 %RH/K. The default value is 3.6
if this field is left blank.
An example of this object follows.
ZoneControl:Thermostat:TemperatureAndHumidity,
Zone Thermostat, !- Thermostat Name
Seasonal Relative Humidity Sch, !- Dehumidifying Relative Humidity Setpoint Schedule Name
Overcool, !- Dehumidification Control Type
Constant, !- Overcool Range Input Method
1.7, !- Overcool Constant Range {deltaC}
, !- Overcool Range Schedule Name
3.0; !- Overcool Control Ratio {percent/K}
ZoneControl:Thermostat:StagedDualSetpoint[LINK]
The thermostatic zone control staged dual setpoint object
is used to control a zone to a specified temperature based on
multiple stages. The other types of ZoneControl:Thermostat
objects reference a control type schedule and one or more
control type objects which in turn reference one or more
setpoint schedules. This control object does not require a
control type schedule and associated one or more control type
objects. Instead, the object is defined as a Dual Setpoint
type only and has two fields to provide heating and cooling
setpoints. The object also provides two fields to specify
heating and cooling throttling temperature ranges, so that
predicted zone loads may be varied within the throttling
ranges for both heating and cooling. The number of stages for
both heating and cooling varies from 1 to 4 for the time being
to match the number of speeds used in the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object. The number of stages may be expanded later to
accommodate other objects with the number of speeds higher
than 4. The object requires inputs temperature offsets for
both heating and cooling based on the number of stages. The
stage number is determined by the temperature difference
between the setpoint and zone temperature at the previous time
step, and offset values. The staged number will be assigned to
the speed number for the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
system type.
It should be pointed out that If this object and other zone
control thermostat and humidistat are assigned to the same
controlled zone, this object takes precedence when the
controlled zone is specified in the Controlling Zone
or Thermostat Location field of the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object.
Unique identifying name for the staged dual-setpoint
thermostat.
Field: Zone or
ZoneList Name[LINK]
Name of the zone or set of zones that is being controlled.
When the ZoneList
option is used then this thermostat definition is applied to
each of the zones in the zone list effecting a global
definition for thermostatic control in the zone.
Field: Number of
Heating Stages[LINK]
This numerical field defines the number of heating stages,
and must be less than or equal to the number of heating speeds
defined in the associated heating coil, such as Coil:Heating:DX:MultiSpeed.
The value for this input field defines the number of heating
temperature offsets that must be defined for heating in the
fields below. The minimum value for this field is one (1) and
the maximum value is four (4).
Field:Heating
Temperature Setpoint Schedule Name[LINK]
The name of the associated schedule to specify heating
temperature setpoint. Values in the schedule are temperatures
{C}.
Field:Heating
Throttling Temperature Range[LINK]
This numeric field defines the heating throttling
temperature range in the units of deltaC. When the zone
temperature at the previous time step is below the heating
temperature setpoint, the zone heating setpoint will be set to
the heating temperature setpoint + 0.5 * heating throttling
temperature range. Otherwise, the zone heating setpoint will
be set to the heating temperature setpoint - 0.5 * heating
throttling temperature range. The zone heating setpoint is
used in the predictor to calculate how much the heating system
load is needed to maintain the zone at the heating
setpoint.
Field: Stage
1 Heating Temperature Offset[LINK]
This numeric field defines the heating temperature offset
in the units of deltaC for Stage 1. The value entered here
must be equal to or less than 0. The heating temperature
offset fields are used to determine the heating stage number
for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object. When the temperature difference between the heating
setpoint and the controlled zone temperature at previous time
step is less than Stage 1 offset value and greater than Stage
2 offset value, the heating stage number is 1. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object is called, Speed 1 is specified.
Field: Stage
2 Heating Temperature Offset[LINK]
This numeric field defines the heating temperature offset
in the units of deltaC for Stage 2. The value entered here
must be less than the value at the previous field: Stage 1
Heating Temperature Offset. The heating temperature offset
fields are used to determine the heating stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object. When the temperature difference between the heating
setpoint and the controlled zone temperature at previous time
step is less than Stage 2 offset value and greater than Stage
3 offset value, the heating stage number is 2. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object is called, Speed 2 is specified.
Field: Stage
3 Heating Temperature Offset[LINK]
This numeric field defines the heating temperature offset
in the units of deltaC for Stage 3. The value entered here
must be less than the value at the previous field: Stage 3
Heating Temperature Offset. The heating temperature offset
fields are used to determine the heating stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object. When the temperature difference between the heating
setpoint and the controlled zone temperature at previous time
step is less than Stage 3 offset value and greater than Stage
4 offset value, the heating stage number is 3. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object is called, Speed 3 is specified.
Note: If the stage number is not equal to the number of
heating speed in the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object, the minimum value is set to the speed number for the
heat pump object.
Field: Stage
4 Heating Temperature Offset[LINK]
This numeric field defines the heating temperature offset
in the units of deltaC for Stage 4. The value entered here
must be less than the value at the previous field: Stage 4
Heating Temperature Offset. The heating temperature offset
fields are used to determine the heating stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object. When the temperature difference between the heating
setpoint and the controlled zone temperature at previous time
step is less than Stage 4 offset value, the heating stage
number is 4. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object is called, Speed 4 is specified.
Note: If the stage number is not equal to the number of
heating speed in the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object, the minimum value is set to the speed number for the
heat pump object.
Field: Number of
Cooling Stages[LINK]
This field defines the number of cooling stages, and must
be less than or equal to the number of cooling speeds defined
in the associated cooling coil, such as Coil:Cooling:DX:MultiSpeed.
The value for this input field defines the number of cooling
temperature offsets that must be defined for cooling in the
fields below. The minimum value for this field is one (1) and
the maximum value is four (4).
Field:Cooling
Temperature Setpoint Base Schedule Name[LINK]
The name of the associated schedule to specify cooling
temperature base setpoint. Values in the schedule are
temperatures {C}.
Field:Cooling
Throttling Temperature Range[LINK]
This numeric field defines the cooling throttling
temperature range in the units of deltaC. When the zone
temperature at the previous time step is above the cooling
temperature setpoint, the zone cooling setpoint will be set to
the cooling temperature setpoint - 0.5 * cooling throttling
temperature range. Otherwise, the zone cooling setpoint will
be set to the cooling temperature setpoint + 0.5 * cooling
throttling temperature range. The zone cooling setpoint is
used in the predictor to calculate how much the cooling system
load is needed to maintain the zone at the cooling
setpoint.
Field: Stage
1 Cooling Temperature Offset[LINK]
This numeric field defines the cooling temperature offset
in the units of deltaC for Stage 1. The value entered here
must be equal to or greater than 0. The cooling temperature
offset fields are used to determine the cooling stage number
for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object. When the temperature difference of the cooling
setpoint and the controlled zone temperature at previous time
step is greater than Stage 1 offset value and less than Stage
2 offset value, the cooling stage number is 1. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object is called, Speed 1 is specified.
Field: Stage
2 Cooling Temperature Offset[LINK]
This numeric field defines the cooling temperature offset
in the units of deltaC for Stage 2. The value entered here
must be greater than the value at the previous field: Stage 1
Cooling Temperature Offset. When the number of cooling stage
is equal to 1, this filed is not used in the program. The
cooling temperature offset fields are used to determine the
cooling stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object. When the temperature difference of the cooling
setpoint and the controlled zone temperature at previous time
step is greater than Stage 2 offset value and less than Stage
3 offset value, the cooling stage number is 2. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object is called, Speed 2 is specified.
Field: Stage
3 Cooling Temperature Offset[LINK]
This numeric field defines the cooling temperature offset
in the units of deltaC for Stage 3. The value entered here
must be greater than the value at the previous field: Stage 3
Cooling Temperature Offset. When the number of cooling stage
is less than 3, this filed is not used in the program. The
cooling temperature offset fields are used to determine the
cooling stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object. When the temperature difference of the cooling
setpoint and the controlled zone temperature at previous time
step is greater than Stage 3 offset value and less than Stage
4 offset value, the cooling stage number is 3. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object is called, Speed 3 is specified.
Note: If the stage number is not equal to the number of
cooling speed in the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object, the minimum value is set to the speed number for the
heat pump object.
Field: Stage
4 Cooling Temperature Offset[LINK]
This numeric field defines the cooling temperature offset
in the units of deltaC for Stage 4. The value entered here
must be greater than the value at the previous field: Stage 4
Cooling Temperature Offset. When the number of cooling stage
is less than 4, this filed is not used in the program. The
cooling temperature offset fields are used to determine the
cooling stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object. When the temperature difference of the cooling
setpoint and the controlled zone temperature at previous time
step is greater than Stage 4 offset value, the cooling stage
number is 4. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object is called, Speed 4 is specified.
Note: If the stage number is not equal to the number of
cooling speed in the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed
object, the minimum value is set to the speed number for the
heat pump object.
An example of this statement in an IDF is:
ZoneControl:Thermostat:StagedDualSetpoint,
ZoneThermostat, !- Name
AllZones, !- Zone or ZoneList Name
2, !- Number of Heating Stages
Heating Setpoints, !- Heating Temperature Setpoint Schedule Name
1.1, !- Heating Throttling Temperature Range {deltaC}
0.0, !- Stage 1 Heating Temperature Offset {deltaC}
-0.5, !- Stage 2 Heating Temperature Offset {deltaC}
-1.0, !- Stage 3 Heating Temperature Offset {deltaC}
-1.5, !- Stage 4 Heating Temperature Offset {deltaC}
4, !- Number of Cooling Stages
Cooling Setpoints, !- Cooling Setpoint Temperature Schedule Name
1.1, !- Cooling Throttling Temperature Range {deltaC}
0.0, !- Stage 1 Cooling Temperature Offset {deltaC}
1.0, !- Stage 2 Cooling Temperature Offset {deltaC}
2.0, !- Stage 3 Cooling Temperature Offset {deltaC}
3.0; !- Stage 4 Cooling Temperature Offset {deltaC}
ZoneControl:Humidistat[LINK]
The humidistat zone control object is used to control a
zone to a single relative humidity setpoint schedule, or to
dual humidity setpoint schedules (humidifying/ dehumidifying
setpoints with deadband). The single setpoint humidistat
requires single setpoint input only, and the dual-setpoint
humidistat requires inputs of both humidifying and
dehumidifying setpoints. The schedules consist of relative
humidities, expressed as a percentage (0-100), to be used
during the simulation for that zone’s moisture prediction
calculation. Only one humidistat control statement can be
specified for each zone. For a single setpoint humidistat, if
the zone relative humidity is below the control relative
humidity setpoint and the equipment specified can humidify
then that equipment will try and meet the zone’s
humidification load. The opposite is true if the zone relative
humidity is above the control relative humidity setpoint and
the equipment can dehumidify. For a dual setpoint humidistat,
if the zone relative humidity is below the
humidifying relative humidity setpoint and
the equipment specified can humidify then that equipment will
try and meet the zone’s humidification load. The opposite is
true if the zone relative humidity is above the
dehumidifying relative humidity setpoint and
the equipment can dehumidify.
If the ZoneControl:Humidistat
is used by a furnace or unitary system (Ref. Furnace and
Unitary Systems) no other objects are required. The signal
from the humidistat is used directly by that component. If the
Zone
Control:Humidistat object is used to control a Humidifier or
used in conjunction with a Controller:WaterCoil
object with control variable
TemperatureAndHumidityRatio or
HumidityRatio, the following objects are
required to determine a setpoint for those components for a
single setpoint humidistat:
For a dual setpoint humidistat, both a maximum humidity
setpoint manager object:
and a minimum humidity setpoint manager object:
are required to determine the setpoints for the
corresponding humidification and dehumidification
components.
Unique identifying name for the humidistat.
Field: Zone Name[LINK]
Name of the zone that is being controlled.
Field:
Humidifying Relative Humidity Setpoint Schedule Name[LINK]
Name of a schedule that defines the humidifying relative
humidity setpoint, expressed as a percentage (0-100), for each
timestep of the simulation.
Note: If only a single setpoint humidistat
is desired, then input the single schedule name in the
Humidifying Setpoint Schedule Name field (and leave the
Dehumidifying Setpoint Schedule Name blank).
Field:
Dehumidifying Relative Humidity Setpoint Schedule Name[LINK]
Name of a schedule that defines the dehumidifying relative
humidity setpoint, expressed as a percentage (0-100), for each
timestep of the simulation. This field is optional, only used
if a dual setpoint humidistat is to be modeled.
An example of this statement in an IDF is:
ZoneControl:Humidistat,
Zone 2 Humidistat, !- Humidistat Name
EAST ZONE, !- Zone Name
Min Rel Hum Set Sch, !- Humidifying Relative Humidity Setpoint SCHEDULE Name
Max Rel Hum Set Sch; !- Dehumidifying Relative Humidity Setpoint SCHEDULE Name
An example schedule for the Zone
Control:Humidistat
ScheduleTypeLimits,Humidity,0:100,CONTINUOUS;
Schedule:Compact,
Min Rel Hum Set Sch, !- Name
Humidity, !- ScheduleType
Through: 12/31, !- Complex Field \#1
For: AllDays, !- Complex Field \#2
Until: 24:00, !- Complex Field \#3
30.0; !- Complex Field \#4
Schedule:Compact,,
Max Rel Hum Set Sch, !- Name
Humidity, !- ScheduleType
Through: 12/31, !- Complex Field \#1
For: AllDays, !- Complex Field \#2
Until: 24:00, !- Complex Field \#3
55.0; !- Complex Field \#4
Outputs available from the ZoneControl:Humidistat:
HVAC,Average,Zone Predicted Moisture Load Moisture
Transfer Rate [kgWater/s]
HVAC,Average,Zone Predicted Moisture Load to
Humidifying Setpoint Moisture Transfer Rate
[kgWater/s]
HVAC,Average,Zone Predicted Moisture Load to
Dehumidifying Setpoint Moisture Transfer Rate
[kgWater/s]
Zone
Predicted Moisture Load Moisture Transfer Rate
[kgWater/s][LINK]
This is the predicted latent (moisture) load in kg\(_{r}\)/s required to meet the
current zone humidistat setpoint. A positive value indicates a
humidification load, a negative value indicates a
dehumidification load. For a dual setpoint humidistat, the
value is zero when the controlled zone’s relative humidity is
between the defined humidifying and dehumidifying setpoints.
This moisture load rate is calculated and reported from the
Predict step in the Zone
Predictor-Corrector module. For nearly all equipment types,
the Predictor-Corrector evaluates the active humidistat
setpoints, determines if the zone requires humidification or
dehumidification, and then passes this single load to the
equipment for the single setpoint humidistat case. This value
is not multiplied by zone or group multipliers.
Zone
Predicted Moisture Load to Humidifying Setpoint Moisture
Transfer Rate [kgWater/s][LINK]
This is the predicted latent (moisture) load in kg\(_{r}\)/s required to meet the
current zone humidistat humidifying setpoint.
This is calculated and reported from the Predict step in the
Zone
Predictor-Corrector module. For nearly all equipment types,
the Predictor-Corrector evaluates the active humidistat
humidifying setpoints, determines if the zone requires
humidification or not, and then passes this load to the
equipment for the case of a dual setpoint humidistat (see Zone
Predicted Moisture Load Moisture Transfer Rate, above, for
single setpoint humidistat case). This value is multiplied by
zone or group multipliers.
Zone
Predicted Moisture Load to Dehumidifying Setpoint Moisture
Transfer Rate [kgWater/s][LINK]
This is the predicted latent (moisture) load in kg\(_{r}\)/s required to meet the
current zone humidistat dehumidifying
setpoint. This is calculated and reported from the Predict
step in the Zone
Predictor-Corrector module. For nearly all equipment types,
the Predictor-Corrector evaluates the active humidistat
humidifying setpoints, determines if the zone requires
dehumidification or not, and then passes this load to the
equipment for a dual setpoint humidistat (see Zone
Predicted Moisture Load Moisture Transfer Rate, above, for
single setpoint humidistat case). This value is multiplied by
zone or group multipliers.
ZoneControl:Thermostat:ThermalComfort[LINK]
The thermal comfort zone control provides a method to
control a zone to a dry-bulb temperature setpoint based on a
thermal comfort model (e.g. Fanger) and a user-specified
thermal comfort setpoint schedule.
This object references a control type schedule and one or
more thermal comfort control type objects which in turn
reference one or more setpoint schedules. The example at the
end of this section illustrates a complete zone thermal
comfort control specification including the control type and
setpoint schedules. The control type schedule and the list of
control type/name pairs are directly related. The schedule
defines the type of control that is to be used during for each
hour. Valid Control Types are
0 - Uncontrolled (No thermal comfort control)
1 - Single Thermal Comfort Heating Setpoint:Fanger
2 - Single Thermal Comfort Cooling Setpoint:Fanger
3 - Single Thermal Comfort Heating Cooling
Setpoint:Fanger
4 - Dual Thermal Comfort Setpoint with Deadband:Fanger
Thus, if the schedule referenced in the ZoneControl:Thermostat:ThermalComfort
statement has a value of 4 for a particular hour, this
indicates that during that hour “Dual Thermal Comfort Setpoint
with Deadband:Fanger” is to be used. The specific “Dual
Thermal Comfort Setpoint with Deadband:Fanger” control object
to be used is specified in the list of control type/name
pairs. Then the specific control type objects reference the
thermal comfort control setpoint schedule to be used. Because
only one control can be specified for each control type in a
ZoneControl:Thermostat:ThermalComfort
statement, there are only four pairs possible in a particular
ZoneControl:Thermostat:ThermalComfort
type/name list. This is because individual controls can be
defined hourly, thus giving the user a full range of
flexibility. Since putting in the name of the control type
directly in the schedule would be very cumbersome, the control
types are assigned a number which is used in the hourly
schedule profile.
The ZoneControl:Thermostat:ThermalComfort
object can be used alone, or with a ZoneControl:Thermostat
object. When both control objects co-exist for a specific zone
and the thermal comfort control type value in the thermal
comfort control type schedule is non-zero the thermal comfort
object will override the value from the zone thermostat
object. If the thermal comfort control is specified as
Uncontrolled (thermal comfort control type value of 0) for a
particular period, then control will revert to thermostat
control if specified. If the thermal comfort control is
specified as Uncontrolled for a particular period and
thermostat control is not specified in the input, then
conditions will float.
This object currently allows only Fanger comfort control
(Ref. Thermal Comfort in Engineering Reference). It requires
one or more people objects in a specific zone. It also
requires inputs of Fields Activity Level Schedule Name,
Work Efficiency Schedule Name, Clothing Insulation Schedule
Name and Air Velocity Schedule Name in the
people object(s). When thermal comfort control is used in a
zone, the air velocity entered in the Air Velocity Schedule
(Ref. People) should be greater than or equal to 0.1 and less
than or equal to 0.5 m/s. A warning message will be issued if
thermal comfort control is active and the air velocity is
outside this range.
This object reads input PMV values from a given PMV
setpoint schedule to calculate a dry-bulb temperature setpoint
based on the selected thermal comfort model. The dry-bulb
temperature setpoint calculation uses zone air humidity ratio
at the previous system timestep and surface temperatures at
the previous zone timestep, along with other conditions at the
current timestep (e.g., activity level, clothing level and air
velocity from the PEOPLE object).
Unique identifying name for this thermal comfort control
object.
Field: Zone or
ZoneList Name[LINK]
Name of the zone or set of zones that is being controlled.
When the ZoneList
option is used then this thermostat definition is applied to
each of the zones in the zone list effecting a global
definition for thermostatic control in the zone.
Field: Averaging Method[LINK]
This choice field specifies the method for calculating the
thermal comfort dry-bulb temperature setpoint for a zone with
multiple People
objects defined. The available choices are:
SpecificObject,
ObjectAverage, and
PeopleAverage. This field is only used when
multiple people objects are defined for this zone. If this
field is specified as PeopleAverage and the
total number of people for all people objects is zero for a
particular timestep, the PeopleAverage method cannot be
applied and the program automatically uses the ObjectAverage
method for this timestep. The default input is
PeopleAverage.
Field:
Object Name for Specific Object Averaging Method[LINK]
This choice field specifies the name of the specific People
object to be used for calculating comfort control when
multiple People
objects are defined. Only used if the Averaging Method is
specified as SpecificObject.
Field:
Minimum Dry-Bulb Temperature Setpoint[LINK]
This field specifies the minimum dry-bulb temperature
setpoint allowed for this zone. If the dry-bulb temperature
calculated by the thermal comfort setpoint model is below this
value, then the temperature setpoint will be set to this
value. The default value is 0 ˚C.
Field:
Maximum Dry-Bulb Temperature Setpoint[LINK]
This field specifies the maximum dry-bulb temperature
setpoint allowed for this zone. If the dry-bulb temperature
calculated by the thermal comfort setpoint model exceeds this
value, then the temperature setpoint will be set to this
value. The default value is 50 ˚C.
Note the minimum and maximum temperature setpoint fields
are provided to allow the user to bound the temperature
control In a specific zone if necessary. These fields are used
to provide boundaries for the dry-bulb temperature setpoint
calculated at each system timestep when unrealistic inputs
have been specified.
Field:
Thermal Comfort Control Type Schedule Name[LINK]
Schedule which defines what type of thermal comfort control
is active during each simulation timestep.
Valid Control Types are
0 - No thermal comfort control
1 - Single Thermal Comfort Heating Setpoint:Fanger
2 - Single Thermal Comfort Cooling Setpoint:Fanger
3 - Single Thermal Comfort Heating Cooling
Setpoint:Fanger
4 - Dual Thermal Comfort Setpoint with Deadband:Fanger
Each non-zero control type used in this schedule must
appear in the following fields which list the specific thermal
comfort control objects to be used for this zone.
Field
Set (Thermal Comfort Control Object Type, Thermal Comfort
Control Name)[LINK]
Up to four pairs of Thermal Comfort Control Type and
Thermal Comfort Control Type Name fields may be listed to
specify which thermal comfort control type objects are used
for this zone. This list is not order-dependent, and the
position in this list has no impact on the control type
schedule. In the control type schedule, a value of 1 always
means “Single Thermal Comfort Heating Setpoint:Fanger”, even
if that control type is not first in this list.
Field:
Thermal Comfort Control <x> Object Type[LINK]
This field specifies the first control type name to be used
for this zone. Available control types are:
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating
ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling
ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint
Field: Thermal
Comfort Control <x> Name[LINK]
The unique name for the corresponding thermal comfort
control type.
An example of this statement in an IDF is:
ZoneControl:Thermostat:ThermalComfort,
Zone 2 Comfort Control, !- Thermal Comfort Control Name
EAST ZONE, !- Zone Name
SpecificObject, !- Averaging Method for Zones with Multiple People Objects
EAST ZONE, !- Object Name for Specific Object Averaging Method
12.8, !- Minimum dry-bulb temperature setpoint
40.0, !- Maximum dry-bulb temperature setpoint
Zone Comfort Control Type Sched, !- Thermal Comfort Control Type SCHEDULE Name
Dual Thermal Comfort Setpoint WITH DEADBAND:Fanger, !- Control Type #1
Dual Comfort Setpoint; !- Thermal Comfort Control Type Name #1
Global thermal comfort thermostat example:
ZoneList,AllControlledZones,SPACE1-1,SPACE2-1,SPACE3-1,SPACE4-1,SPACE5-1;
ZoneControl:Thermostat:ThermalComfort,
ControlledZones Comfort Control, !- Name
AllControlledZones, !- Zone Name
PeopleAverage, !- Averaging Method
, !- Specific People Name
12.8, !- Minimum Dry-Bulb Temperature Setpoint {C}
40.0, !- Maximum Dry-Bulb Temperature Setpoint {C}
Zone Comfort Control Type Sched, !- Thermal Comfort Control Type Schedule Name
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating, !- Thermal Comfort Control 1 Object Type
Single Heating Comfort Setpoint, !- Thermal Comfort Control 1 Name
ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling, !- Thermal Comfort Control 2 Object Type
Single Cooling Comfort Setpoint, !- Thermal Comfort Control 2 Name
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling, !- Thermal Comfort Control 3 Object Type
Single Heating Cooling Comfort Setpoint, !- Thermal Comfort Control 3 Name
ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint, !- Thermal Comfort Control 4 Object Type
Dual Comfort Setpoint; !- Thermal Comfort Control 4 Name
Three outputs are available from the ZoneControl:Thermostat:ThermalComfort
object. Two output variables used primarily for the
ZoneControl:Thermost object are also described here to explain
their meaning when using thermal comfort control.
ZoneControl:ThermalComfort
Zone,Average,Zone Thermal Comfort Control Type
[]
Zone,Average,Zone Thermal Comfort Control Fanger Low
Setpoint PMV []
Zone,Average,Zone Thermal Comfort Control Fanger High
Setpoint PMV []
ZoneControl:Thermostat
Zone,Average,Zone Thermostat Heating Setpoint
Temperature [C]
Zone,Average,Zone Thermostat Cooling Setpoint
Temperature [C]
Zone Thermal
Comfort Control Type [][LINK]
This is the current zone thermal comfort control type (0
through 4). This value is set at each system timestep and
averaged over the reporting interval. Using the averaged value
for longer reporting frequencies (hourly, for example) may not
be meaningful in some applications.
Zone
Thermal Comfort Control Fanger Low Setpoint PMV [][LINK]
This is the current zone thermal comfort low Predicted Mean
Vote value. Values range between -3 and +3. If there is no
heating thermal comfort active, then the value reported will
be -999. This value is set at each system timestep and
averaged over the reporting interval. Using the averaged value
for longer reporting frequencies (hourly, for example) may not
be meaningful in some applications.
Zone
Thermal Comfort Control Fanger High Setpoint PMV [][LINK]
This is the current zone thermal comfort high Predicted
Mean Vote value. Values range between -3 and +3. If there is
no cooling thermal comfort active, then the value reported
will be 999. This value is set at each system timestep and
averaged over the reporting interval. Using the averaged value
for longer reporting frequencies (hourly, for example) may not
be meaningful in some applications.
Zone
Thermostat Heating Setpoint Temperature [C][LINK]
The Zone
Control:Thermal Comfort object shares the same output variable
and overwrites the thermal setpoints defined in object Zone
Control:Thermostatic when both objects of Zone
Control:Thermostatic and Zone
Control:Thermal Comfort co-exist. It outputs the current zone
thermal comfort heating setpoint in degrees C when thermal
comfort control is active, otherwise this output variable will
report the thermostat heating setpoint (Ref. Zone
Control:Thermostatic Outputs). If there is no heating thermal
comfort active and no thermostat heating setpoint is defined
for this zone, this value will be 0. This value is set at each
system timestep and averaged over the reporting interval.
Using the averaged value for longer reporting frequencies
(hourly, for example) may not be meaningful in some
applications.
Zone
Thermostat Cooling Setpoint Temperature [C][LINK]
This output variable defined in object Zone
Control:Thermostatic. The Thermal Comfort object shares the
same output variable and overwrites the thermal setpoints
defined in object Zone
Control:Thermostatic when both objects of Zone
Control:Thermostatic and Zone
Control:Thermal Comfort co-exist. It outputs the current zone
thermal comfort cooling setpoint in degrees C when thermal
comfort control is active, otherwise this output variable will
report the thermostat cooling setpoint (Ref. Zone
Control:Thermostatic Outputs). If there is no cooling thermal
comfort active and no thermostat cooling setpoint is defined
for this zone, this value will be 0. This value is set at each
system timestep and averaged over the reporting interval.
Using the averaged value for longer reporting frequencies
(hourly, for example) may not be meaningful in some
applications.
Thermal Comfort
Setpoints[LINK]
The syntax for the current set (4) of zone thermal comfort
control types is given below. In each case, the keyword is
accompanied by an identifying name and either one or two
schedule names (depending on whether the control type is a
single or dual setpoint control). The schedule defines a
Predicted Mean Vote (PMV) setpoint for the control type. The
schedule would be defined through the standard schedule syntax
described earlier in this document. For an uncontrolled
thermal comfort zone, no Fanger thermal comfort object is
specified or necessary. However, the Fanger thermal comfort
output variables
Zone Thermal Comfort Fanger Model PMV and
Zone Thermal Comfort Fanger Model PPD are
reported regardless of whether the zone is uncontrolled (i.e.,
free floating) or controlled by a thermostat. When the zone is
controlled by a thermostat, the air temperature and humidity
used to calculate the Fanger PMV and PPD values are based on
the values of these parameters at the system time step level.
When the zone is uncontrolled, the air conditions used to
calculate the Fanger PMV and PPD are the free floating
temperature and humidity ratio calculated at the zone time
step level. The Fanger PMV and PPD are outputs variables as
outlined in the People object. For more
information on the equations used to calculate the Fanger PMV
and PPD, please consult the EnergyPlus Engineering
Reference.
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating[LINK]
This would be used for heating only thermal comfort
control. The PMV setpoint can be scheduled and varied
throughout the simulation but only heating is allowed with
this control type.
Unique name for this control type.
Field:
Fanger Thermal Comfort Schedule Name[LINK]
The name of the associated schedule containing
Zone Thermal Comfort Fanger Model PMV values.
ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling[LINK]
This would be used for cooling only thermal comfort
control. The PMV setpoint can be scheduled and varied
throughout the simulation but only cooling is allowed with
this control type.
Unique name for this control type.
Field:
Fanger Thermal Comfort Schedule Name[LINK]
The name of the associated schedule, containing
Zone Thermal Comfort Fanger Model PMV values.
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling[LINK]
This would be used for heating and cooling thermal comfort
control but only heating or cooling can be scheduled at any
given time period. The PMV setpoint can be scheduled and
varied throughout the simulation for both heating and
cooling.
Unique name for this control type.
Field:
Fanger Thermal Comfort Schedule Name[LINK]
The name of the associated schedule containing
Zone Thermal Comfort Fanger Model PMV values.
ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint[LINK]
This would be used for heating and cooling thermal comfort
control where both a heating and cooling PMV setpoint can be
scheduled for any given time period. The PMV setpoint can be
scheduled and varied throughout the simulation for both
heating and cooling.
Unique name for this control type.
Field:
Fanger Thermal Comfort Heating Schedule Name[LINK]
The name of the associated schedule containing heating
setpoint Zone Thermal Comfort Fanger Model PMV
values.
Field:
Fanger Thermal Comfort Cooling Schedule Name[LINK]
The name of the associated schedule containing cooling
setpoint Zone Thermal Comfort Fanger Model PMV
values.
An example of this statement in an IDF is:
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating,
Heating Comfort Setpoint,!- Name
Heating PMV Setpoints; !- Setpoint Temperature SCHEDULE Name
ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling,
Cooling Comfort Setpoint,!- Name
Cooling PMV Setpoints; !- Setpoint Temperature SCHEDULE Name
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling,
Heating Cooling Comfort Setpoint,!- Name
Heating Cooling PMV Setpoints; !- Setpoint Temperature SCHEDULE Name
ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint,
Dual Comfort Setpoint, !- Name
Heating PMV Setpoints, !- Fanger Thermal Comfort Heating Setpoint PMV SCHEDULE Name
Cooling PMV Setpoints; !- Fanger Thermal Comfort Cooling Setpoint PMV SCHEDULE Name
ZoneControl:ContaminantController[LINK]
The ZoneControl:ContaminantController
object is used for any of the following two purposes based on
the system outdoor air method specified in the Controller:MechanicalVentilation.
To control a zone to a specified indoor level of
contaminants. When this zone is served by an AirLoopHVAC,
the other zones served by the same AirLoopHVAC
will have the same specified indoor level, if no objects in
the other zones served by the same AirLoop are specified.
Currently, the available contaminant controls are carbon
dioxide and generic contaminant controls. The specified carbon
dioxide setpoint is used to calculate the required outdoor
airflow rate through the HVAC system to reach the setpoint.
The AirLoopHVAC
system outdoor flow rate is realized by the Controller:MechanicalVentilation
object with System Outdoor Air Method =
IndoorAirQualityProcedure.The specified generic contaminant
setpoint is used to calculate the required outdoor airflow
rate through the HVAC system to reach the setpoint. The AirLoopHVAC
system outdoor flow rate is realized by the Controller:MechanicalVentilation
object with System Outdoor Air Method =
IndoorAirQualityProcedure-GenericContaminant.
To specify minimum or maximum CO2 concentration
schedule name for a zone. The AirLoopHVAC
system outdoor flow rate is realized by the Controller:MechanicalVentilation
object with System Outdoor Air Method =
ProportionalControlBasedonOccupancySchedule or
ProportionalControlBasedOnDesignOccupancy or
ProportionalControlBasedOnDesignOARate. Carbon Dioxide Control
Availability Schedule Name determines the availability of
ProportionalControl .
For the first purpose above, when multiple zones are served
by an AirLoop, those zones that do not have a contaminant
controller object specified in the input data file are
automatically assigned a carbon dioxide setpoint. Zone
objects entered in the input data file are internally assigned
an index number from 1 to n (first defined Zone
object = 1, next Zone
object defined in the input file = 2, etc.). For zones served
by an AirLoop that do not have a contaminant controller
specified, the zone’s carbon dioxide setpoint will be the same
as the zone with the next highest zone index number that has a
contaminant controller specified. If a zone with a higher
index number and contaminant controller specified does not
exist, then the zone with the next lowest zone index number
that has a contaminant controller specified will be used. For
example, assume an AirLoop serves zones 1 through 5, but one
ZoneControl:ContaminantController
object is specified for zone 2, a second ZoneControl:ContaminantController
object is specified for zone 4, and no ZoneControl:ContaminantController
objects are specified for zones 1, 3 and 5. In this case, zone
1 will be assigned the carbon dioxide setpoint schedule that
was specified for zone 2, and zones 3 and 5 will be assigned
the carbon dioxide setpoint schedule that was specified for
zone 4.
The ZoneControl:ContaminantController
object is also used for any of the following two purposes
based on the outdoor air method specified in the DesignSpecification:OutdoorAir.
To control a zone to a specified indoor level of
contaminants. When this zone is served by a dedicated outdoor
air system AirLoopHVAC
through a terminal unit, some type of terminal units are able
to call a DesignSpecification:OutdoorAir
object with Outdoor Air Method = IndoorAirQualityProcedure, so
that the required outdoor airflow rate to reach the zone air
setpoint can be assigned to the terminal unit. The total
outdoor air flow in the AirLoopHVAC
is a sum of all terminal units. In this way, each zone served
by the same AirLoopHVAC
can reach the zone air CO2 setpoint precisely.
To specify minimum CO2 concentration schedule name for
a zone. When this zone is served by a dedicated outdoor air
system AirLoopHVAC
through a terminal unit, some type of terminal units are able
to call a DesignSpecification:OutdoorAir
object with Outdoor Air Method =
ProportionalControlBasedonOccupancySchedule or
ProportionalControlBasedOnDesignOccupancy. The outdoor airflow
rate is determined by one of proportional control procedures.
Then, the calculated outdoor airflow rate is assigned to the
terminal unit. The total outdoor air flow in the AirLoopHVAC
is a sum of all terminal units. In this way, each zone served
by the same AirLoopHVAC
will receive the outdoor airflow rate based on terminal unit
request.
Unique identifying name for the ZoneControl:ContaminantController.
Field: Zone Name[LINK]
Name of the zone that is being controlled.
Field:Carbon
Dioxide Control Availability Schedule Name[LINK]
This field contains the name of a schedule that determines
whether or not the ZoneControl:ContaminantController
is available. When the schedule value is zero, the ZoneControl:ContaminantController
is bypassed (not available to operate). When the schedule
value is greater than zero, the ZoneControl:ContaminantController
is available and will be used to calculate the required
outdoor airflow rate to reach the carbon dioxide setpoint. If
this field is left blank, the schedule has a value of 1 for
all time periods. Schedule values must be between 0 and 1.
Field:Carbon
Dioxide Setpoint Schedule Name[LINK]
This field contains the name of a schedule that contains
the zone carbon dioxide concentration setpoint as a function
of time. The units for carbon dioxide setpoint are ppm. The
setpoint values in the schedule must be between 0 and 2000
ppm. . This field is used when the field System Outdoor Air
Method = IndoorAirQualityProcedure in the Controller:MechanicalVentilation
object.
Field:Minimum
Carbon Dioxide Concentration Schedule Name[LINK]
This field contains the name of a schedule that contains
the minimum zone carbon dioxide concentration setpoint as a
function of time. The units for carbon dioxide setpoint are
ppm. This field is used when the field System Outdoor Air
Method = ProportionalControlBasedonOccupancySchedule or
ProportionalControlBasedOnDesignOccupancy, or
ProportionalControlBasedOnDesignOARate in the Controller:MechanicalVentilation
object. This field is also used when the field Outdoor Air
Method = ProportionalControlBasedonOccupancySchedule or
ProportionalControlBasedOnDesignOccupancy in the DesignSpecification:OutdoorAir
object.
Field:Maximum
Carbon Dioxide Concentration Schedule Name[LINK]
This field contains the name of a schedule that contains
the maximum zone carbon dioxide concentration as a function of
time and is used to calculate design CO2 concentration level
in the proportional ventilation control. The units for carbon
dioxide setpoint are ppm. This field is used when the field
System Outdoor Air Method =
ProportionalControlBasedonOccupancySchedule, or
ProportionalControlBasedOnDesignOccupancy, or
ProportionalControlBasedOnDesignOARate in the Controller:MechanicalVentilation
object.
Field:
Generic Contaminant Control Availability Schedule Name[LINK]
This field contains the name of a schedule that determines
whether or not the ZoneControl:ContaminantController
is available. When the schedule value is zero, the generic
contaminant control will not be performed. When the schedule
value is greater than zero, the ZoneControl:ContaminantController
is available and will be used to calculate the required
outdoor airflow rate to reach the generic contaminant
setpoint. If this field is left blank, the schedule has a
value of 1 for all time periods. Schedule values must be
between 0 and 1.
Field:
Generic Contaminant Setpoint Schedule Name[LINK]
This field contains the name of a schedule that contains
the zone generic contaminant concentration setpoint as a
function of time. The units for generic contaminant setpoint
are ppm. The setpoint values in the schedule must be> =
0.
An IDF example is provided below:
ZoneControl:ContaminantController,
CO2 Controller1, !- Name
EAST ZONE, !- Zone Name
CO2AvailSchedule, !- Carbon Dioxide Control Availability Schedule Name
CO2SetpointSchedule, !- Carbon Dioxide Setpoint Schedule Name
, !- Minimum Carbon Dioxide Concentration Schedule Name
, !- Maximum Carbon Dioxide Concentration Schedule Name
GCAvailSchedule, !- Generic Contaminant Control Availability Schedule Name
GCSetpointSchedule; !- Generic Contaminant Setpoint Schedule Name
The following output variables are available when the ZoneControl:ContaminantController
object is specified.
HVAC,Average,Zone Air CO2 Predicted Load to Setpoint
Mass Flow Rate [kg/s]
HVAC,Average,Zone Air CO2 Setpoint Concentration
[ppm]
HVAC,Average,Zone Generic Air Contaminant Predicted
Load to Setpoint Mass Flow Rate [kg/s]
HVAC,Average,Zone Generic Air Contaminant Setpoint
Concentration [ppm]
Zone
Air CO2 Predicted Load to Setpoint Mass Flow Rate [kg/s][LINK]
This output is the average predicted outdoor airflow rate
in kg/s required to meet the current zone carbon dioxide
setpoint for the time step being reported. This value is
calculated and reported from the Predict step in the Zone
Contaminant Predictor-Corrector module. The calculated outdoor
airflow rate will be specified in the Controller:MechanicalVentilation
object with System Outdoor Air Method =
IndoorAirQualityProcedureto provide enough outdoor ventilation
air to keep the zone air carbon dioxide concentration level at
or below the setpoint.
Zone Air CO2
Setpoint Concentration [ppm][LINK]
This output variable is the average carbon dioxide setpoint
value, in parts per million, for the time step being
reported.
Zone
Generic Air Contaminant Predicted Load to Setpoint Mass Flow
Rate [kg/s][LINK]
This output is the average predicted outdoor airflow rate
in kg/s required to meet the current zone generic contaminant
setpoint for the time step being reported. This value is
calculated and reported from the Predict step in the Zone
Contaminant Predictor-Corrector module. The calculated outdoor
airflow rate will be specified in the Controller:MechanicalVentilation
object with System Outdoor Air Method =
IndoorAirQualityProcedure-GenericContaminant****to provide
enough outdoor ventilation air to keep the zone air generic
contaminant concentration level at or below the setpoint.
Zone
Generic Air Contaminant Setpoint Concentration [ppm][LINK]
This output variable is the averagegeneric contaminant
setpoint value, in parts per million, for the time step being
reported.
Group - Zone Controls - Thermostats and Humidistats[LINK]
Zone Control objects are used to control zone conditions to a specific setpoint. The six types of zone control are described in this section. They are, by name, ZoneControl:<name>.. These types are:
Thermostat - The object provides the traditional approach to space control using air temperatures. Each controlled zone contains a thermostat object.
Humidistat - The object is used to control a zone to a specified relative humidity.
Thermostat:ThermalComfort - The object provides a method to control a zone to a dry-bulb temperature setpoint based on a thermal comfort model (e.g. Fanger) and a user-specified thermal comfort setpoint schedule.
Thermostat:OperativeTemperature - The operative temperature control is formulated to reuse all of the traditional thermostat objects. One input object will be used for each thermal zone to indicate if that zone’s thermostat control mode should be overridden to effect operative temperature control rather than traditional air temperature control. The user will still have to input all the traditional ZoneControl:Thermostat and setpoint objects.
Thermostat:TemperatureAndHumidity - This thermostat control works together with the traditional ZoneControl:Thermostat object to modify temperature control based on zone air humidity conditions. Currently, this object resets the thermostat’s cooling setpoint temperature downward based on elevated zone air humidity levels, typically yielding additional cooling coil operation and associated dehumidification. A ZoneControl:Thermostat:TemperatureAndHumidity object should be specified to indicate if a zone’s traditional thermostat control mode should be overridden to provide enhanced dehumidification. The user must still input the traditional ZoneControl:Thermostat and setpoint objects.
Thermostat:StagedDualSetpoint - This thermostat control works alone with “Dual Setpoint” type only. The object provides heating and cooling setpoints, throttling range and offsets, so that zone temperature setpoint used for system load calculation is adjusted by the setpoint and throttling range based on the zone temperature at the previous time step. The stage number is determined by the temperature difference between the setpoint and zone temperature at the previous time step, and offset values. If this object and other zone control thermostat and humidistat are assigned to the same controlled zone, this object takes precedence when the controlled zone is specified in the Controlling Zone or Thermostat Location field of the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object.
ZoneControl:Thermostat[LINK]
The thermostatic zone control object is used to control a zone to a specified temperature. ZoneControl:Thermostat references a control type schedule and one or more control type objects which in turn reference one or more setpoint schedules. The example at the end of this section illustrates a complete zone thermostat specification including the control type and setpoint schedules.
The control type schedule and the list of control type/name pairs are directly related. The schedule defines the type of control that is to be used throughout the simulation. Valid Control Types are:
0 - Uncontrolled (No specification or default)
1 - Single Heating Setpoint
2 - Single Cooling SetPoint
3 - Single Heating/Cooling Setpoint
4 - Dual Setpoint (Heating and Cooling) with deadband
Thus, if the schedule referenced in the ZoneControl:Thermostat statement has a control type of 4 for a particular time period, this indicates that during that time period “Dual Setpoint with deadband” control is to be used. The specific “Dual Setpoint (Heating and Cooling) with deadband” control object to be used is specified in the list of control type/name pairs. Then the specific control type objects reference the thermostat setpoint temperature schedule to be used. Because only one control can be specified for each control type in a ZoneControl:Thermostat statement, there are only four pairs possible in a particular ZoneControl:Thermostat type/name list. This is because individual controls can be defined throughout the simulation, thus giving the user a full range of flexibility. Since putting in the name of the control type directly in the schedule would be very cumbersome, the control types are assigned a number which is used in the schedule profile.
Inputs[LINK]
Field: Name[LINK]
Unique identifying name for the thermostat.
Field: Zone or ZoneList Name[LINK]
Name of the zone or set of zones that is being controlled. When the ZoneList option is used then this thermostat definition is applied to each of the zones in the zone list effecting a global definition for thermostatic control in the zone.
Field: Control Type Schedule Name[LINK]
Schedule which defines what type of control is active during the simulation. Valid Control Types are:
0 - Uncontrolled (No specification or default)
1 - Single Heating Setpoint
2 - Single Cooling SetPoint
3 - Single Heating Cooling Setpoint
4 - Dual Setpoint with Deadband (Heating and Cooling)
Each non-zero control type which is used in this schedule must appear in the following fields which list the specific thermostat control objects to be used for this zone.
Field Set (Control Object Type, Control Name)[LINK]
Up to four pairs of Control Object Type and Control Name may be listed to specify which control objects are used for this zone. This list is not order-dependent, and the position in this list has no impact on the control type schedule. In the control type schedule, a value of 1 always means “Single Heating Setpoint”, even if that control type is not first in this list.
Field: Control Object <x>Type[LINK]
This field specifies the control type to be used for this zone. Available control types are:
ThermostatSetpoint:SingleHeating
ThermostatSetpoint:SingleCooling
ThermostatSetpoint:SingleHeatingOrCooling
ThermostatSetpoint:DualSetpoint
Field: Control <x> Name[LINK]
The corresponding control type name. The name is used in an object with the name of the control type and specifies the schedule.
Field: Temperature Difference Between Cutout And Setpoint[LINK]
This optional choice field provides a temperature difference between cutout temperature and setpoint. When the temperature difference is greater than 0.0, the difference is applied to both heating and cooling by possibly revising setpoints based on control types.
If MAT is defined as zone air temperature at previous time step, DeltaT represents the temperature difference between cutout and setpoint and is greater than 0.0, and PredictedLoad represents predicted load calculated in the ZoneTempPredictorCorrector, following action will be taken:
Note that this option should be used in caution. Following recommendations may be used to input the value of Temperature Difference Between Cutout And Setpoint:
An example of this statement in an IDF is:
An example of a global thermostat:
A complete zone thermostat example showing this statement and all of the objects it must reference is:
Outputs[LINK]
Outputs available from controlled zones. The “key” in the below is the Zone Name.
HVAC,Average,Zone Predicted Sensible Load to Setpoint Heat Transfer Rate [W]
HVAC,Average,Zone Predicted Sensible Load to Heating Setpoint Heat Transfer Rate [W]
HVAC,Average,Zone Predicted Sensible Load to Cooling Setpoint Heat Transfer Rate [W]
Zone,Average,Zone Thermostat Control Type []
Zone,Average,Zone Thermostat Heating Setpoint Temperature [C]
Zone,Average,Zone Thermostat Cooling Setpoint Temperature [C]
HVAC,Sum,Facility Any Zone Oscillating Temperatures Time [hr]
Zone,Sum,Zone Heating Setpoint Not Met Time [hr]
Zone,Sum,Zone Heating Setpoint Not Met While Occupied Time [hr]
Zone,Sum,Zone Cooling Setpoint Not Met Time [hr]
Zone,Sum,Zone Cooling Setpoint Not Met While Occupied Time [hr]
Zone,Sum,Facility Heating Setpoint Not Met Time [hr]
Zone,Sum,Facility Cooling Setpoint Not Met Time [hr]
Zone,Sum,Facility Heating Setpoint Not Met While Occupied Time [hr]
Zone,Sum,Facility Cooling Setpoint Not Met While Occupied Time [hr]
Zone Predicted Sensible Load to Setpoint Heat Transfer Rate [W][LINK]
This is the predicted sensible load in W required to meet the current zone thermostat setpoint. A positive value indicates a heating load, a negative value indicates a cooling load. This is calculated and reported from the Predict step in the Zone Predictor-Corrector module. For nearly all equipment types, the Predictor-Corrector evaluates the active heating and/or cooling setpoints, determines if the zone requires heating or cooling or is in the deadband, and then passes this single load to the equipment. This value is not multiplied by zone or group multipliers.
Zone Predicted Sensible Load to Heating Setpoint Heat Transfer Rate [W][LINK]
This is the predicted sensible load in W required to meet the current zone thermostat heating setpoint. A positive value indicates a heating load, a negative value indicates a cooling load. This is calculated and reported from the Predict step in the Zone Predictor-Corrector module. This value is not multiplied by zone or group multipliers.
Zone Predicted Sensible Load to Cooling Setpoint Heat Transfer Rate [W][LINK]
This is the predicted sensible load in W required to meet the current zone thermostat cooling setpoint. A positive value indicates a heating load, a negative value indicates a cooling load. This is calculated and reported from the Predict step in the Zone Predictor-Corrector module. This value is not multiplied by zone or group multipliers.
Zone Thermostat Control Type [][LINK]
This is the current zone thermostat control type (0 through 4). This value is set at each zone timestep. Using the averaged value for longer reporting frequencies (hourly, for example) may not be meaningful in some applications.
Zone Thermostat Heating Setpoint Temperature [C][LINK]
This is the current zone thermostat heating setpoint in degrees C. If there is no heating thermostat active, then the value will be 0. This value is set at each zone timestep. Using the averaged value for longer reporting frequencies (hourly, for example) may not be meaningful in some applications.
When the Thermostat:StagedDualSetpoint object is applied to the current zone, this output variable reports staged zone heating setpoint. When the staged number is not equal to zero, both staged heating and cooling setpoints are the same. When no cooling or heating is required, the staged heating setpoint is equal to the scheduled heating setpoint 0.5 * heating throttling range, and the staged cooling setpoint is equal to the scheduled cooling setpoint + 0.5 * cooling throttling range.
Zone Thermostat Cooling Setpoint Temperature [C][LINK]
This is the current zone thermostat cooling setpoint in degrees C. If there is no cooling thermostat active, then the value will be 0. This value is set at each zone timestep. Using the averaged value for longer reporting frequencies (hourly, for example) may not be meaningful in some applications.
When the Thermostat:StagedDualSetpoint object is applied to the current zone, this output variable reports staged zone cooling setpoint. When the staged number is not equal to zero, both staged heating and cooling setpoints are the same. When no cooling or heating is required, the staged heating setpoint is equal to the scheduled heating setpoint 0.5 * heating throttling range, and the staged cooling setpoint is equal to the scheduled cooling setpoint + 0.5 * cooling throttling range.
Zone Thermostat Stage Number [][LINK]
This is the current zone thermostat stage number when the ZoneControl:Thermostat:StagedDualSetpoint object is specified in this zone. When no heating or cooling is required, the stage number is set to 0. When heating is required, the stage number is positive. When cooling is required, the stage number is negative. The absolute number is sent to the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object to specify the speed number accordingly.
Zone Heating Setpoint Not Met Time [hr][LINK]
Hours when the zone temperature is lower than 0.2 (default) degrees C below the heating setpoint. See the OutputControl:ReportingTolerances object to change the reporting range from 0.2 degrees C.
Zone Heating Setpoint Not Met While Occupied Time [hr][LINK]
Hours when the zone temperature is lower than 0.2 (default) degrees C below the heating setpoint and when people are present in the zone. To change the reporting range from 0.2 degrees C, see the OutputControl:ReportingTolerances object.
Zone Cooling Setpoint Not Met Time [hr][LINK]
Hours when the zone temperature is greater than 0.2 (default) degrees C above the cooling setpoint. See the OutputControl:ReportingTolerances object to change the reporting range from 0.2 degrees C.
Zone Cooling Setpoint Not Met While Occupied Time [hr][LINK]
Hours when the zone temperature is greater than 0.2 (default) degrees C above the cooling setpoint and when people are present in the zone. To change the reporting range from 0.2 degrees C, see the OutputControl:ReportingTolerances object.
Facility Heating Setpoint Not Met Time [hr][LINK]
Hours when the zone temperature is lower than 0.2 (default) degrees C below the heating setpoint in any one or more zones. See the OutputControl:ReportingTolerances object to change the reporting range from 0.2 degrees C.
Facility Heating Setpoint Not Met While Occupied Time [hr][LINK]
Hours when the zone temperature is lower than 0.2 (default) degrees C below the heating setpoint and when people are present in any one or more zones. To change the reporting range from 0.2 degrees C, see the OutputControl:ReportingTolerances object.
Facility Cooling Setpoint Not Met Time [hr][LINK]
Hours when the zone temperature is greater than 0.2 (default) degrees C above the cooling setpoint in any one or more zones. See the OutputControl:ReportingTolerances object to change the reporting range from 0.2 degrees C.
Facility Cooling Setpoint Not Met While Occupied Time [hr][LINK]
Hours when the zone temperature is greater than 0.2 (default) degrees C above the cooling setpoint and when people are present in any one or more zones. To change the reporting range from 0.2 degrees C, see the OutputControl:ReportingTolerances object.
Zone Oscillating Temperatures Time[hr][LINK]
Hours when the temperature in the zone is oscillating back and forth. Oscillation is defined as times when the three differences between zone temperatures during successive timesteps are greater in magnitude than 0.15 degrees C and the sign of the differences changes from positive to negative to positive or from negative to positive to negative.
This may indicate a simulation with reduced reliability during the oscillation. Some oscillating hours should be expected in all simulations but excessive oscillations call into question the overall validity of the results. If excessive oscillations are occurring, try reducing the minimum system timestep (see ConvergenceLimits object) and the zone timestep (see the TimeStep object). Reducing these timestep lengths does increase the total computer time needed to complete the simulation. Having the zone timestep and the minimum system timestep the same length of time can also cause more oscillations. What amount of oscillations is considered excessive is difficult to quantify. One approach is comparing the number of oscillations to the case with 15 minute zone timesteps (4 per hour) and 1 minute minimum system timesteps. Often this variable is used as an indicator of the validity of the results when trying to decrease the time needed to perform the simulation.
Facility Any Zone Oscillating Temperatures Time[hr][LINK]
Hours when any zone in the building has oscillations. See Zone Oscillating Temperatures Time definition above.
Zone Thermostat Setpoints[LINK]
The syntax for the current set of four zone thermostat setpoint objects is given below. In each case, the keyword is accompanied by an identifying name and either one or two schedule names (depending on whether the control is a single or dual setpoint control). The schedule defines a temperature setpoint for the control type. The schedule would be defined through the standard schedule syntax described earlier in this document. For an uncontrolled zone no thermostat is specified or necessary.
ThermostatSetpoint:SingleHeating[LINK]
This would be for a heating only thermostat. The setpoint can be scheduled and varied throughout the simulation but only heating is allowed with this control type.
Inputs[LINK]
Field: Name[LINK]
Unique name for this control type.
Field: Setpoint Temperature Schedule Name[LINK]
The name of the associated schedule. Values in the schedule are temperatures {C}.
ThermostatSetpoint:SingleCooling[LINK]
This would be for a cooling only thermostat. The setpoint can be scheduled and varied throughout the simulation but only cooling is allowed.
Inputs[LINK]
Field: Name[LINK]
Unique name for this control type.
Field: Setpoint Temperature Schedule Name[LINK]
The name of the associated schedule. Values in the schedule are temperatures {C}.
ThermostatSetpoint:SingleHeatingOrCooling[LINK]
This would be for heating and cooling thermostat but only heating or cooling can be scheduled at any given time period. The setpoint can be scheduled and varied throughout the simulation for both heating and cooling.
Inputs[LINK]
Field: Name[LINK]
Unique name for this control type.
Field: Setpoint Temperature Schedule Name[LINK]
The name of the associated schedule. Values in the schedule are temperatures {C}.
ThermostatSetpoint:DualSetpoint[LINK]
This would be for heating and cooling thermostat where both a heating and cooling setpoint can be scheduled for any given time period. The setpoint can be scheduled and varied throughout the simulation for both heating and cooling.
Inputs[LINK]
Field: Name[LINK]
Unique name for this control type.
Field: Heating Setpoint Temperature Schedule Name[LINK]
The heating temperature schedule. Values in the schedule are temperatures {C}.
Field: Cooling Setpoint Temperature Schedule Name[LINK]
The cooling temperature schedule. Values in the schedule are temperatures {C}.
Examples of these statements in an IDF are:
ZoneControl:Thermostat:OperativeTemperature[LINK]
This object is used to modify the program’s behavior for ZoneControl:Thermostat objects. One input object is used for each thermal zone to indicate if that zone’s thermostat control mode should be overridden to effect operative temperature control rather than traditional air temperature control. Zone Control:Thermostatic and related setpoint objects also need to be included in the input file. When this object is used, the zone can be controlled by a weighted mixture of radiant and air temperatures (rather than just air temperatures).
When using this object, the setpoint temperature values (e.g. input in schedules named in ThermostatSetpoint:DualSetpoint objects) become targets for the desired operative temperatures. As of version 8.7 new options are added that allow automatically generating values for the setpoint temperature, as a function of outdoor air temperatures, using various adaptive comfort models based on ASHRAE Standard 55-2010 and CEN 15251-2007. The adaptive comfort model relates the zone operative temperature setpoint to the recent history of the outdoor air temperatures. The adaptive comfort models only apply to cooling mode and generate a single setpoint value for each day. During summer time in hot climates, the zone thermostat setting can be higher than the traditional thermostat setting based on the adaptive thermal comfort model, which results in energy savings of HVAC systems.
This thermostatic operative temperature, \({T_{OP}}\) , is defined as:
\[{T_{OP}} = \gamma {T_{MRT}} + (1 - \gamma ){T_{drybulb}}\]
where,
\(\gamma\) is the radiative fraction,
\({T_{MRT}}\) is the mean radiant temperature for the thermal zone, and
\({T_{drybulb}}\) is the mean zone air temperature.
The radiative fraction \(\gamma\) is selected by the user and can be scheduled to vary during the simulation. A typical value is 0.5. The maximum value needs to be less than 0.9 and the minimum is 0.0. A value of 0.0 is the same as controlling on only zone air temperature. If air velocities are higher than 0.2 m/s, then lower values for radiative fraction might apply. Niu and Burnett (1998) cite International Standard ISO 77300 in recommending the values for this fraction listed in the following table.
When the adaptive comfort model is selected, the thermostat setpoint temperature schedule for space cooling will be overwritten with the calculated operative temperature based on the selected acceptability limits of the comfort model defined in ASHRAE 55-2010 or CEN 15251-2007. The ASHRAE adaptive comfort model is only applicable when the running average outdoor air temperature for the past 30 days is between 10.0 and 33.5°C; while the CEN 15251-2007 adaptive comfort model is only applicable when the running average outdoor air temperature for the past 7 days is between 10.0 and 30.0°C. The user can choose whether to overwrite the cooling setpoint temperature only when the adaptive setpoint is higher than the user input one for the purpose of energy saving.
Reference:
Niu and J. Burnett. 1998. Integrating Radiant/Operative Temperature Controls into Building Energy Simulations. ASHRAE Transactions Vol. 104. Part 2. page 210. ASHRAE. Atlanta, GA.
ASHRAE Standard 55-2010. Thermal environment conditions for human occupancy. ASHRAE, Atlanta.
Inputs[LINK]
Field: Thermostat Name[LINK]
Name of ZoneControl:Thermostat object defined elsewhere in the input file whose operation is to be modified to effect control based on operative temperature. If the ZoneControl:Thermostat references a ZoneList (set of zones) then, this operative temperature thermostat will be applied to each of those zones. If only a single thermostat/zone is desired, then the name to be put here is <zone name> <Thermostat Name> where the Thermostat name is the thermostat that referenced the set of zones.
Field: Radiative Fraction Input Mode[LINK]
This field controls whether the input for radiative fraction is a constant value or if it is entered using a schedule. Enter Constant here to use a fixed radiative fraction defined in the following field. Enter Scheduled to vary the radiative fraction according to the schedule named in the second field below.
Field: Fixed Radiative Fraction[LINK]
This is the fraction, \(\gamma\), of the operative temperature that is due to the mean radiant temperature in the zone. This field is used by the program if the previous field is set to Constant.
Field: Radiative Fraction Schedule Name[LINK]
This field contains the name of a schedule, defined elsewhere, that determines the value for radiative fraction \(\gamma\) during the simulation period. This schedule should have fractional values from 0.0 to 0.9. When the value of this schedule is 0.0, the controlling will be equivalent to control based only on zone air temperature. This field is used by the program if the Input Mode field is set to Scheduled.
Note that by setting the values in this schedule separately for design days, the user can control how operative temperature control is applied during autosizing. (Operative temperature control tends to increase the equipment capacities calculated during sizing.)
Field: Adaptive Comfort Model Type[LINK]
This field controls which of the seven adaptive comfort model is chosen, if any, listed as following:
None. The adaptive comfort model is not applied and the setpoint temperatures are not adjusted from those input in the thermostat setpoints.
AdaptiveASH55CentralLine. The central line of the acceptability limits of the ASHRAE Standard 55-2010 adaptive comfort model will be used to generate the zone operative temperature setpoint.
AdaptiveASH5580PercentUpperLine. The upper line of the 80% acceptability limits of the ASHRAE Standard 55-2010 adaptive comfort model will be used to generate the zone operative temperature setpoint.
AdaptiveASH5590PercentUpperLine. The upper line of the 90% acceptability limits of the ASHRAE Standard 55-2010 adaptive comfort model will be used to generate the zone operative temperature setpoint.
AdaptiveCEN15251CentralLine. The central line of the acceptability limits of the CEN Standard 15251-2007 adaptive comfort model will be used to generate the zone operative temperature setpoint.
AdaptiveCEN15251CategoryIUpperLine. The upper line of the Category I of the acceptability limits of the CEN Standard 15251-2007 adaptive comfort model will be used to generate the zone operative temperature setpoint.
AdaptiveCEN15251CategoryIIUpperLine. The upper line of the Category II of the acceptability limits of the CEN Standard 15251-2007 adaptive comfort model will be generate to adjust the zone operative temperature setpoint; and
AdaptiveCEN15251CategoryIIIUpperLine. The upper line of the Category III of the acceptability limits of the CEN Standard 15251-2007 adaptive comfort model will be generate as the zone operative temperature setpoint.
An example of this object follows.
Global operative temperature applied to all zones for a global thermostat:
Global operative temperature referencing a single zone from the list:
Outputs[LINK]
Zone Thermostat Operative Temperature [C][LINK]
Operative temperature (OT) is a weighted mixture of Zone Mean Air Temperature (MAT) and Zone Mean Radiant Temperature (MRT), using the current value of Radiative Fraction (RF): OT = (1-RF)*MAT + RF*MAT. This output variable does not include the direct effect of high temperature radiant systems. See also Zone Operative Temperature.
ZoneControl:Thermostat:TemperatureAndHumidity[LINK]
This object is used to modify the behavior of ZoneControl:Thermostat objects (control types ThermostatSetpoint:SingleCooling and ThermostatSetpoint:DualSetpoint only) based on zone air humidity conditions. Specifically, this TemperatureAndHumidity zone control resets the ZoneControl:Thermostat’s cooling setpoint temperature downward when the zone air relative humidity exceeds the Dehumidifying Relative Humidity Setpoint defined in this object. The reduced cooling setpoint temperature typically results in longer cooling coil runtimes and additional dehumidification. The rate at which the cooling setpoint temperature is reduced is dictated by the user-specified Overcool Control Ratio. The maximum reduction in cooling setpoint temperature is defined by the user-entered OverCool Range (user choice of a constant value for the entire simulation or a schedule that can define how the overcool range varies over time). For details regarding the calculations, see the EnergyPlus Engineering Reference.
Note: As described above, this ZoneControl:Thermostat:TemperatureAndHumidity control object modifies the cooling setpoint temperature of ZoneControl:Thermostat objects. The ZoneControl:Thermostat:TemperatureAndHumidity object works independently of the ZoneControl:Humidistat object; that is, it does not replace the need for, or coordinate its input fields with, ZoneControl:Humidistat objects that are required for other types of high humidity control (e.g., ZoneControl:Humidstat objects are required for ZoneHVAC:Dehumidifier:DX objects, AirLoopHVAC:Unitary* objects with CoolReheat or MultiMode dehumidification control types, etc.)
Inputs[LINK]
Field: Thermostat Name[LINK]
Name of ZoneControl:Thermostat object defined elsewhere in the input file whose operation is to be modified to effect temperature control based on zone air humidity conditions. If the ZoneControl:Thermostat references a ZoneList (set of zones), then simply enter the name of the ZoneControl:Thermostat object and this TemperatureAndHumidity thermostat control will be applied to all zones in the ZoneList. If the ZoneControl:Thermostat references a ZoneList but it is desired that only a single zone within the ZoneList be controlled based on TemperatureAndHumidity control, then the name to be put here is <zone name> <Thermostat Name> where the Thermostat Name is the name of the ZoneControl:Thermostat object.
Field: Dehumidifying Relative Humidity Setpoint Schedule Name[LINK]
Name of a schedule that defines the dehumidifying relative humidity setpoint, expressed as a percentage (0-100), for each timestep of the simulation. This input field is required. This input field has absolutely no relationship or influence on the Dehumidifying Relative Humidity Setpoint Schedule Name optional input field in the ZoneControl:Humidistat object.
Field:Dehumidification Control Type[LINK]
This input field defines what type of dehumidification control is active during the simulation. Valid control types are None and Overcool. The default is Overcool if this field is left blank. Overcool resets the thermostat’s cooling setpoint temperature lower based on the zone air relative humidity level. None means no overcooling (i.e., traditional zone air temperature control based on the associated ZoneControl:Thermostat object [Thermostat Name input field above] will be in effect).
Field: Overcool Range Input Method[LINK]
This field controls whether the input for the overcool (temperature) range is a constant value or if it is entered using a schedule. Enter Constant here to use a constant overcool range defined in the Overcool Constant Range input field below. Enter Scheduled to vary the overcool range according to the schedule named in the Overcool Range Schedule Name input field below. The default is Constant if this field is left blank.
Field: Overcool Constant Range[LINK]
This field specifies a fixed maximum overcool temperature range for cooling setpoint temperature reduction for zone overcool dehumidification in units of deltaC. This field is used if the Overcool Range Input Method is specified as Constant. The Overcool dehumidification control type only works with ZoneControl:Thermostat control types ThermostatSetpoint:SingleCooling and ThermostatSetpoint:DualSetpoint . For ThermostatSetpoint:DualSetpoint , the model will use the smaller of the Overcool Constant Range input value or the difference between the cooling and heating setpoint temperatures specified in the ThermostatSetpoint:DualSetpoint object. The Overcool Constant Range must be greater than or equal to zero with a maximum value of 3 °C. A value of 0.0 indicates no zone air overcooling. The default value is 1.7 °C (3 °F) if this input field is left blank.
Field: Overcool Range Schedule Name[LINK]
This field contains the name of a schedule, defined elsewhere, that determines the value for the overcool range during the simulation period. This schedule should contain values from 0.0 to < = 3.0 (deltaC). When the value of this schedule is 0.0, the zone air temperature control will be based only on zone air dry-bulb temperature (i.e., no zone overcooling). This field is used by the program if the Overcool Range Input Method field is set to Scheduled. Overcool dehumidification control type only works with ZoneControl:Thermostat control types ThermostatSetpoint:SingleCooling and ThermostatSetpoint:DualSetpoint . For ThermostatSetpoint:DualSetpoint , the model will use the smaller of the Overcool Range values specified in this schedule or the difference between the cooling and heating setpoint temperatures specified in the ThermostatSetpoint:DualSetpoint object.
Note that by setting the values in this schedule separately for design days, the user can control how Overcool Dehumidification Control is applied during autosizing. (Overcool dehumidification control tends to increase the cooling equipment capacities calculated during sizing.)
Field:Overcool Control Ratio[LINK]
The value of this input field is used to adjust the cooling setpoint temperature (established by the associated ZoneControl:Thermostat object) downward based on the difference between the zone air relative humidity level and the Dehumidifying Relative Humidity Setpoint. This input field is only used with Dehumidification Control Type = Overcool. Input values must be greater than or equal to 0.0 %RH/K. The default value is 3.6 if this field is left blank.
An example of this object follows.
ZoneControl:Thermostat:StagedDualSetpoint[LINK]
The thermostatic zone control staged dual setpoint object is used to control a zone to a specified temperature based on multiple stages. The other types of ZoneControl:Thermostat objects reference a control type schedule and one or more control type objects which in turn reference one or more setpoint schedules. This control object does not require a control type schedule and associated one or more control type objects. Instead, the object is defined as a Dual Setpoint type only and has two fields to provide heating and cooling setpoints. The object also provides two fields to specify heating and cooling throttling temperature ranges, so that predicted zone loads may be varied within the throttling ranges for both heating and cooling. The number of stages for both heating and cooling varies from 1 to 4 for the time being to match the number of speeds used in the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object. The number of stages may be expanded later to accommodate other objects with the number of speeds higher than 4. The object requires inputs temperature offsets for both heating and cooling based on the number of stages. The stage number is determined by the temperature difference between the setpoint and zone temperature at the previous time step, and offset values. The staged number will be assigned to the speed number for the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed system type.
It should be pointed out that If this object and other zone control thermostat and humidistat are assigned to the same controlled zone, this object takes precedence when the controlled zone is specified in the Controlling Zone or Thermostat Location field of the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object.
Inputs[LINK]
Field: Name[LINK]
Unique identifying name for the staged dual-setpoint thermostat.
Field: Zone or ZoneList Name[LINK]
Name of the zone or set of zones that is being controlled. When the ZoneList option is used then this thermostat definition is applied to each of the zones in the zone list effecting a global definition for thermostatic control in the zone.
Field: Number of Heating Stages[LINK]
This numerical field defines the number of heating stages, and must be less than or equal to the number of heating speeds defined in the associated heating coil, such as Coil:Heating:DX:MultiSpeed. The value for this input field defines the number of heating temperature offsets that must be defined for heating in the fields below. The minimum value for this field is one (1) and the maximum value is four (4).
Field:Heating Temperature Setpoint Schedule Name[LINK]
The name of the associated schedule to specify heating temperature setpoint. Values in the schedule are temperatures {C}.
Field:Heating Throttling Temperature Range[LINK]
This numeric field defines the heating throttling temperature range in the units of deltaC. When the zone temperature at the previous time step is below the heating temperature setpoint, the zone heating setpoint will be set to the heating temperature setpoint + 0.5 * heating throttling temperature range. Otherwise, the zone heating setpoint will be set to the heating temperature setpoint - 0.5 * heating throttling temperature range. The zone heating setpoint is used in the predictor to calculate how much the heating system load is needed to maintain the zone at the heating setpoint.
Field: Stage 1 Heating Temperature Offset[LINK]
This numeric field defines the heating temperature offset in the units of deltaC for Stage 1. The value entered here must be equal to or less than 0. The heating temperature offset fields are used to determine the heating stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object. When the temperature difference between the heating setpoint and the controlled zone temperature at previous time step is less than Stage 1 offset value and greater than Stage 2 offset value, the heating stage number is 1. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object is called, Speed 1 is specified.
Field: Stage 2 Heating Temperature Offset[LINK]
This numeric field defines the heating temperature offset in the units of deltaC for Stage 2. The value entered here must be less than the value at the previous field: Stage 1 Heating Temperature Offset. The heating temperature offset fields are used to determine the heating stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object. When the temperature difference between the heating setpoint and the controlled zone temperature at previous time step is less than Stage 2 offset value and greater than Stage 3 offset value, the heating stage number is 2. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object is called, Speed 2 is specified.
Field: Stage 3 Heating Temperature Offset[LINK]
This numeric field defines the heating temperature offset in the units of deltaC for Stage 3. The value entered here must be less than the value at the previous field: Stage 3 Heating Temperature Offset. The heating temperature offset fields are used to determine the heating stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object. When the temperature difference between the heating setpoint and the controlled zone temperature at previous time step is less than Stage 3 offset value and greater than Stage 4 offset value, the heating stage number is 3. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object is called, Speed 3 is specified.
Note: If the stage number is not equal to the number of heating speed in the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object, the minimum value is set to the speed number for the heat pump object.
Field: Stage 4 Heating Temperature Offset[LINK]
This numeric field defines the heating temperature offset in the units of deltaC for Stage 4. The value entered here must be less than the value at the previous field: Stage 4 Heating Temperature Offset. The heating temperature offset fields are used to determine the heating stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object. When the temperature difference between the heating setpoint and the controlled zone temperature at previous time step is less than Stage 4 offset value, the heating stage number is 4. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object is called, Speed 4 is specified.
Note: If the stage number is not equal to the number of heating speed in the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object, the minimum value is set to the speed number for the heat pump object.
Field: Number of Cooling Stages[LINK]
This field defines the number of cooling stages, and must be less than or equal to the number of cooling speeds defined in the associated cooling coil, such as Coil:Cooling:DX:MultiSpeed. The value for this input field defines the number of cooling temperature offsets that must be defined for cooling in the fields below. The minimum value for this field is one (1) and the maximum value is four (4).
Field:Cooling Temperature Setpoint Base Schedule Name[LINK]
The name of the associated schedule to specify cooling temperature base setpoint. Values in the schedule are temperatures {C}.
Field:Cooling Throttling Temperature Range[LINK]
This numeric field defines the cooling throttling temperature range in the units of deltaC. When the zone temperature at the previous time step is above the cooling temperature setpoint, the zone cooling setpoint will be set to the cooling temperature setpoint - 0.5 * cooling throttling temperature range. Otherwise, the zone cooling setpoint will be set to the cooling temperature setpoint + 0.5 * cooling throttling temperature range. The zone cooling setpoint is used in the predictor to calculate how much the cooling system load is needed to maintain the zone at the cooling setpoint.
Field: Stage 1 Cooling Temperature Offset[LINK]
This numeric field defines the cooling temperature offset in the units of deltaC for Stage 1. The value entered here must be equal to or greater than 0. The cooling temperature offset fields are used to determine the cooling stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object. When the temperature difference of the cooling setpoint and the controlled zone temperature at previous time step is greater than Stage 1 offset value and less than Stage 2 offset value, the cooling stage number is 1. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object is called, Speed 1 is specified.
Field: Stage 2 Cooling Temperature Offset[LINK]
This numeric field defines the cooling temperature offset in the units of deltaC for Stage 2. The value entered here must be greater than the value at the previous field: Stage 1 Cooling Temperature Offset. When the number of cooling stage is equal to 1, this filed is not used in the program. The cooling temperature offset fields are used to determine the cooling stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object. When the temperature difference of the cooling setpoint and the controlled zone temperature at previous time step is greater than Stage 2 offset value and less than Stage 3 offset value, the cooling stage number is 2. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object is called, Speed 2 is specified.
Field: Stage 3 Cooling Temperature Offset[LINK]
This numeric field defines the cooling temperature offset in the units of deltaC for Stage 3. The value entered here must be greater than the value at the previous field: Stage 3 Cooling Temperature Offset. When the number of cooling stage is less than 3, this filed is not used in the program. The cooling temperature offset fields are used to determine the cooling stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object. When the temperature difference of the cooling setpoint and the controlled zone temperature at previous time step is greater than Stage 3 offset value and less than Stage 4 offset value, the cooling stage number is 3. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object is called, Speed 3 is specified.
Note: If the stage number is not equal to the number of cooling speed in the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object, the minimum value is set to the speed number for the heat pump object.
Field: Stage 4 Cooling Temperature Offset[LINK]
This numeric field defines the cooling temperature offset in the units of deltaC for Stage 4. The value entered here must be greater than the value at the previous field: Stage 4 Cooling Temperature Offset. When the number of cooling stage is less than 4, this filed is not used in the program. The cooling temperature offset fields are used to determine the cooling stage number for AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object. When the temperature difference of the cooling setpoint and the controlled zone temperature at previous time step is greater than Stage 4 offset value, the cooling stage number is 4. When the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object is called, Speed 4 is specified.
Note: If the stage number is not equal to the number of cooling speed in the AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed object, the minimum value is set to the speed number for the heat pump object.
An example of this statement in an IDF is:
ZoneControl:Humidistat[LINK]
The humidistat zone control object is used to control a zone to a single relative humidity setpoint schedule, or to dual humidity setpoint schedules (humidifying/ dehumidifying setpoints with deadband). The single setpoint humidistat requires single setpoint input only, and the dual-setpoint humidistat requires inputs of both humidifying and dehumidifying setpoints. The schedules consist of relative humidities, expressed as a percentage (0-100), to be used during the simulation for that zone’s moisture prediction calculation. Only one humidistat control statement can be specified for each zone. For a single setpoint humidistat, if the zone relative humidity is below the control relative humidity setpoint and the equipment specified can humidify then that equipment will try and meet the zone’s humidification load. The opposite is true if the zone relative humidity is above the control relative humidity setpoint and the equipment can dehumidify. For a dual setpoint humidistat, if the zone relative humidity is below the humidifying relative humidity setpoint and the equipment specified can humidify then that equipment will try and meet the zone’s humidification load. The opposite is true if the zone relative humidity is above the dehumidifying relative humidity setpoint and the equipment can dehumidify.
If the ZoneControl:Humidistat is used by a furnace or unitary system (Ref. Furnace and Unitary Systems) no other objects are required. The signal from the humidistat is used directly by that component. If the Zone Control:Humidistat object is used to control a Humidifier or used in conjunction with a Controller:WaterCoil object with control variable TemperatureAndHumidityRatio or HumidityRatio, the following objects are required to determine a setpoint for those components for a single setpoint humidistat:
SetpointManager:SingleZone:Humidity:Minimum
SetpointManager:MultiZone:MinimumHumidity:Average
SetpointManager:MultiZone:MaximumHumidity:Average
SetpointManager:MultiZone:Humidity:Minimum
SetpointManager:MultiZone:Humidity:Maximum
SetpointManager:SingleZone:Humidity:Minimum
For a dual setpoint humidistat, both a maximum humidity setpoint manager object:
SetpointManager:SingleZone:Humidity:Maximum
SetpointManager:MultiZone:MaximumHumidity:Average
SetpointManager:MultiZone:Humidity:Maximum
and a minimum humidity setpoint manager object:
SetpointManager:SingleZone:Humidity:Minimum
SetpointManager:MultiZone:MinimumHumidity:Average
SetpointManager:MultiZone:Humidity:Minimum
are required to determine the setpoints for the corresponding humidification and dehumidification components.
Inputs[LINK]
Field: Name[LINK]
Unique identifying name for the humidistat.
Field: Zone Name[LINK]
Name of the zone that is being controlled.
Field: Humidifying Relative Humidity Setpoint Schedule Name[LINK]
Name of a schedule that defines the humidifying relative humidity setpoint, expressed as a percentage (0-100), for each timestep of the simulation.
Note: If only a single setpoint humidistat is desired, then input the single schedule name in the Humidifying Setpoint Schedule Name field (and leave the Dehumidifying Setpoint Schedule Name blank).
Field: Dehumidifying Relative Humidity Setpoint Schedule Name[LINK]
Name of a schedule that defines the dehumidifying relative humidity setpoint, expressed as a percentage (0-100), for each timestep of the simulation. This field is optional, only used if a dual setpoint humidistat is to be modeled.
An example of this statement in an IDF is:
An example schedule for the Zone Control:Humidistat
Outputs[LINK]
Outputs available from the ZoneControl:Humidistat:
HVAC,Average,Zone Predicted Moisture Load Moisture Transfer Rate [kgWater/s]
HVAC,Average,Zone Predicted Moisture Load to Humidifying Setpoint Moisture Transfer Rate [kgWater/s]
HVAC,Average,Zone Predicted Moisture Load to Dehumidifying Setpoint Moisture Transfer Rate [kgWater/s]
Zone Predicted Moisture Load Moisture Transfer Rate [kgWater/s][LINK]
This is the predicted latent (moisture) load in kg\(_{r}\)/s required to meet the current zone humidistat setpoint. A positive value indicates a humidification load, a negative value indicates a dehumidification load. For a dual setpoint humidistat, the value is zero when the controlled zone’s relative humidity is between the defined humidifying and dehumidifying setpoints. This moisture load rate is calculated and reported from the Predict step in the Zone Predictor-Corrector module. For nearly all equipment types, the Predictor-Corrector evaluates the active humidistat setpoints, determines if the zone requires humidification or dehumidification, and then passes this single load to the equipment for the single setpoint humidistat case. This value is not multiplied by zone or group multipliers.
Zone Predicted Moisture Load to Humidifying Setpoint Moisture Transfer Rate [kgWater/s][LINK]
This is the predicted latent (moisture) load in kg\(_{r}\)/s required to meet the current zone humidistat humidifying setpoint. This is calculated and reported from the Predict step in the Zone Predictor-Corrector module. For nearly all equipment types, the Predictor-Corrector evaluates the active humidistat humidifying setpoints, determines if the zone requires humidification or not, and then passes this load to the equipment for the case of a dual setpoint humidistat (see Zone Predicted Moisture Load Moisture Transfer Rate, above, for single setpoint humidistat case). This value is multiplied by zone or group multipliers.
Zone Predicted Moisture Load to Dehumidifying Setpoint Moisture Transfer Rate [kgWater/s][LINK]
This is the predicted latent (moisture) load in kg\(_{r}\)/s required to meet the current zone humidistat dehumidifying setpoint. This is calculated and reported from the Predict step in the Zone Predictor-Corrector module. For nearly all equipment types, the Predictor-Corrector evaluates the active humidistat humidifying setpoints, determines if the zone requires dehumidification or not, and then passes this load to the equipment for a dual setpoint humidistat (see Zone Predicted Moisture Load Moisture Transfer Rate, above, for single setpoint humidistat case). This value is multiplied by zone or group multipliers.
ZoneControl:Thermostat:ThermalComfort[LINK]
The thermal comfort zone control provides a method to control a zone to a dry-bulb temperature setpoint based on a thermal comfort model (e.g. Fanger) and a user-specified thermal comfort setpoint schedule.
This object references a control type schedule and one or more thermal comfort control type objects which in turn reference one or more setpoint schedules. The example at the end of this section illustrates a complete zone thermal comfort control specification including the control type and setpoint schedules. The control type schedule and the list of control type/name pairs are directly related. The schedule defines the type of control that is to be used during for each hour. Valid Control Types are
0 - Uncontrolled (No thermal comfort control)
1 - Single Thermal Comfort Heating Setpoint:Fanger
2 - Single Thermal Comfort Cooling Setpoint:Fanger
3 - Single Thermal Comfort Heating Cooling Setpoint:Fanger
4 - Dual Thermal Comfort Setpoint with Deadband:Fanger
Thus, if the schedule referenced in the ZoneControl:Thermostat:ThermalComfort statement has a value of 4 for a particular hour, this indicates that during that hour “Dual Thermal Comfort Setpoint with Deadband:Fanger” is to be used. The specific “Dual Thermal Comfort Setpoint with Deadband:Fanger” control object to be used is specified in the list of control type/name pairs. Then the specific control type objects reference the thermal comfort control setpoint schedule to be used. Because only one control can be specified for each control type in a ZoneControl:Thermostat:ThermalComfort statement, there are only four pairs possible in a particular ZoneControl:Thermostat:ThermalComfort type/name list. This is because individual controls can be defined hourly, thus giving the user a full range of flexibility. Since putting in the name of the control type directly in the schedule would be very cumbersome, the control types are assigned a number which is used in the hourly schedule profile.
The ZoneControl:Thermostat:ThermalComfort object can be used alone, or with a ZoneControl:Thermostat object. When both control objects co-exist for a specific zone and the thermal comfort control type value in the thermal comfort control type schedule is non-zero the thermal comfort object will override the value from the zone thermostat object. If the thermal comfort control is specified as Uncontrolled (thermal comfort control type value of 0) for a particular period, then control will revert to thermostat control if specified. If the thermal comfort control is specified as Uncontrolled for a particular period and thermostat control is not specified in the input, then conditions will float.
This object currently allows only Fanger comfort control (Ref. Thermal Comfort in Engineering Reference). It requires one or more people objects in a specific zone. It also requires inputs of Fields Activity Level Schedule Name, Work Efficiency Schedule Name, Clothing Insulation Schedule Name and Air Velocity Schedule Name in the people object(s). When thermal comfort control is used in a zone, the air velocity entered in the Air Velocity Schedule (Ref. People) should be greater than or equal to 0.1 and less than or equal to 0.5 m/s. A warning message will be issued if thermal comfort control is active and the air velocity is outside this range.
This object reads input PMV values from a given PMV setpoint schedule to calculate a dry-bulb temperature setpoint based on the selected thermal comfort model. The dry-bulb temperature setpoint calculation uses zone air humidity ratio at the previous system timestep and surface temperatures at the previous zone timestep, along with other conditions at the current timestep (e.g., activity level, clothing level and air velocity from the PEOPLE object).
Inputs[LINK]
Field: Name[LINK]
Unique identifying name for this thermal comfort control object.
Field: Zone or ZoneList Name[LINK]
Name of the zone or set of zones that is being controlled. When the ZoneList option is used then this thermostat definition is applied to each of the zones in the zone list effecting a global definition for thermostatic control in the zone.
Field: Averaging Method[LINK]
This choice field specifies the method for calculating the thermal comfort dry-bulb temperature setpoint for a zone with multiple People objects defined. The available choices are: SpecificObject, ObjectAverage, and PeopleAverage. This field is only used when multiple people objects are defined for this zone. If this field is specified as PeopleAverage and the total number of people for all people objects is zero for a particular timestep, the PeopleAverage method cannot be applied and the program automatically uses the ObjectAverage method for this timestep. The default input is PeopleAverage.
Field: Object Name for Specific Object Averaging Method[LINK]
This choice field specifies the name of the specific People object to be used for calculating comfort control when multiple People objects are defined. Only used if the Averaging Method is specified as SpecificObject.
Field: Minimum Dry-Bulb Temperature Setpoint[LINK]
This field specifies the minimum dry-bulb temperature setpoint allowed for this zone. If the dry-bulb temperature calculated by the thermal comfort setpoint model is below this value, then the temperature setpoint will be set to this value. The default value is 0 ˚C.
Field: Maximum Dry-Bulb Temperature Setpoint[LINK]
This field specifies the maximum dry-bulb temperature setpoint allowed for this zone. If the dry-bulb temperature calculated by the thermal comfort setpoint model exceeds this value, then the temperature setpoint will be set to this value. The default value is 50 ˚C.
Note the minimum and maximum temperature setpoint fields are provided to allow the user to bound the temperature control In a specific zone if necessary. These fields are used to provide boundaries for the dry-bulb temperature setpoint calculated at each system timestep when unrealistic inputs have been specified.
Field: Thermal Comfort Control Type Schedule Name[LINK]
Schedule which defines what type of thermal comfort control is active during each simulation timestep.
Valid Control Types are
0 - No thermal comfort control
1 - Single Thermal Comfort Heating Setpoint:Fanger
2 - Single Thermal Comfort Cooling Setpoint:Fanger
3 - Single Thermal Comfort Heating Cooling Setpoint:Fanger
4 - Dual Thermal Comfort Setpoint with Deadband:Fanger
Each non-zero control type used in this schedule must appear in the following fields which list the specific thermal comfort control objects to be used for this zone.
Field Set (Thermal Comfort Control Object Type, Thermal Comfort Control Name)[LINK]
Up to four pairs of Thermal Comfort Control Type and Thermal Comfort Control Type Name fields may be listed to specify which thermal comfort control type objects are used for this zone. This list is not order-dependent, and the position in this list has no impact on the control type schedule. In the control type schedule, a value of 1 always means “Single Thermal Comfort Heating Setpoint:Fanger”, even if that control type is not first in this list.
Field: Thermal Comfort Control <x> Object Type[LINK]
This field specifies the first control type name to be used for this zone. Available control types are:
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating
ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling
ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint
Field: Thermal Comfort Control <x> Name[LINK]
The unique name for the corresponding thermal comfort control type.
An example of this statement in an IDF is:
Global thermal comfort thermostat example:
Outputs[LINK]
Three outputs are available from the ZoneControl:Thermostat:ThermalComfort object. Two output variables used primarily for the ZoneControl:Thermost object are also described here to explain their meaning when using thermal comfort control.
ZoneControl:ThermalComfort
Zone,Average,Zone Thermal Comfort Control Type []
Zone,Average,Zone Thermal Comfort Control Fanger Low Setpoint PMV []
Zone,Average,Zone Thermal Comfort Control Fanger High Setpoint PMV []
ZoneControl:Thermostat
Zone,Average,Zone Thermostat Heating Setpoint Temperature [C]
Zone,Average,Zone Thermostat Cooling Setpoint Temperature [C]
Zone Thermal Comfort Control Type [][LINK]
This is the current zone thermal comfort control type (0 through 4). This value is set at each system timestep and averaged over the reporting interval. Using the averaged value for longer reporting frequencies (hourly, for example) may not be meaningful in some applications.
Zone Thermal Comfort Control Fanger Low Setpoint PMV [][LINK]
This is the current zone thermal comfort low Predicted Mean Vote value. Values range between -3 and +3. If there is no heating thermal comfort active, then the value reported will be -999. This value is set at each system timestep and averaged over the reporting interval. Using the averaged value for longer reporting frequencies (hourly, for example) may not be meaningful in some applications.
Zone Thermal Comfort Control Fanger High Setpoint PMV [][LINK]
This is the current zone thermal comfort high Predicted Mean Vote value. Values range between -3 and +3. If there is no cooling thermal comfort active, then the value reported will be 999. This value is set at each system timestep and averaged over the reporting interval. Using the averaged value for longer reporting frequencies (hourly, for example) may not be meaningful in some applications.
Zone Thermostat Heating Setpoint Temperature [C][LINK]
The Zone Control:Thermal Comfort object shares the same output variable and overwrites the thermal setpoints defined in object Zone Control:Thermostatic when both objects of Zone Control:Thermostatic and Zone Control:Thermal Comfort co-exist. It outputs the current zone thermal comfort heating setpoint in degrees C when thermal comfort control is active, otherwise this output variable will report the thermostat heating setpoint (Ref. Zone Control:Thermostatic Outputs). If there is no heating thermal comfort active and no thermostat heating setpoint is defined for this zone, this value will be 0. This value is set at each system timestep and averaged over the reporting interval. Using the averaged value for longer reporting frequencies (hourly, for example) may not be meaningful in some applications.
Zone Thermostat Cooling Setpoint Temperature [C][LINK]
This output variable defined in object Zone Control:Thermostatic. The Thermal Comfort object shares the same output variable and overwrites the thermal setpoints defined in object Zone Control:Thermostatic when both objects of Zone Control:Thermostatic and Zone Control:Thermal Comfort co-exist. It outputs the current zone thermal comfort cooling setpoint in degrees C when thermal comfort control is active, otherwise this output variable will report the thermostat cooling setpoint (Ref. Zone Control:Thermostatic Outputs). If there is no cooling thermal comfort active and no thermostat cooling setpoint is defined for this zone, this value will be 0. This value is set at each system timestep and averaged over the reporting interval. Using the averaged value for longer reporting frequencies (hourly, for example) may not be meaningful in some applications.
Thermal Comfort Setpoints[LINK]
The syntax for the current set (4) of zone thermal comfort control types is given below. In each case, the keyword is accompanied by an identifying name and either one or two schedule names (depending on whether the control type is a single or dual setpoint control). The schedule defines a Predicted Mean Vote (PMV) setpoint for the control type. The schedule would be defined through the standard schedule syntax described earlier in this document. For an uncontrolled thermal comfort zone, no Fanger thermal comfort object is specified or necessary. However, the Fanger thermal comfort output variables
Zone Thermal Comfort Fanger Model PMVandZone Thermal Comfort Fanger Model PPDare reported regardless of whether the zone is uncontrolled (i.e., free floating) or controlled by a thermostat. When the zone is controlled by a thermostat, the air temperature and humidity used to calculate the Fanger PMV and PPD values are based on the values of these parameters at the system time step level. When the zone is uncontrolled, the air conditions used to calculate the Fanger PMV and PPD are the free floating temperature and humidity ratio calculated at the zone time step level. The Fanger PMV and PPD are outputs variables as outlined in thePeopleobject. For more information on the equations used to calculate the Fanger PMV and PPD, please consult the EnergyPlus Engineering Reference.ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating[LINK]
This would be used for heating only thermal comfort control. The PMV setpoint can be scheduled and varied throughout the simulation but only heating is allowed with this control type.
Inputs[LINK]
Field: Name[LINK]
Unique name for this control type.
Field: Fanger Thermal Comfort Schedule Name[LINK]
The name of the associated schedule containing
Zone Thermal Comfort Fanger Model PMVvalues.ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling[LINK]
This would be used for cooling only thermal comfort control. The PMV setpoint can be scheduled and varied throughout the simulation but only cooling is allowed with this control type.
Inputs[LINK]
Field: Name[LINK]
Unique name for this control type.
Field: Fanger Thermal Comfort Schedule Name[LINK]
The name of the associated schedule, containing
Zone Thermal Comfort Fanger Model PMVvalues.ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling[LINK]
This would be used for heating and cooling thermal comfort control but only heating or cooling can be scheduled at any given time period. The PMV setpoint can be scheduled and varied throughout the simulation for both heating and cooling.
Inputs[LINK]
Field: Name[LINK]
Unique name for this control type.
Field: Fanger Thermal Comfort Schedule Name[LINK]
The name of the associated schedule containing
Zone Thermal Comfort Fanger Model PMVvalues.ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint[LINK]
This would be used for heating and cooling thermal comfort control where both a heating and cooling PMV setpoint can be scheduled for any given time period. The PMV setpoint can be scheduled and varied throughout the simulation for both heating and cooling.
Inputs[LINK]
Field: Name[LINK]
Unique name for this control type.
Field: Fanger Thermal Comfort Heating Schedule Name[LINK]
The name of the associated schedule containing heating setpoint
Zone Thermal Comfort Fanger Model PMVvalues.Field: Fanger Thermal Comfort Cooling Schedule Name[LINK]
The name of the associated schedule containing cooling setpoint
Zone Thermal Comfort Fanger Model PMVvalues.An example of this statement in an IDF is:
ZoneControl:ContaminantController[LINK]
The ZoneControl:ContaminantController object is used for any of the following two purposes based on the system outdoor air method specified in the Controller:MechanicalVentilation.
To control a zone to a specified indoor level of contaminants. When this zone is served by an AirLoopHVAC, the other zones served by the same AirLoopHVAC will have the same specified indoor level, if no objects in the other zones served by the same AirLoop are specified. Currently, the available contaminant controls are carbon dioxide and generic contaminant controls. The specified carbon dioxide setpoint is used to calculate the required outdoor airflow rate through the HVAC system to reach the setpoint. The AirLoopHVAC system outdoor flow rate is realized by the Controller:MechanicalVentilation object with System Outdoor Air Method = IndoorAirQualityProcedure.The specified generic contaminant setpoint is used to calculate the required outdoor airflow rate through the HVAC system to reach the setpoint. The AirLoopHVAC system outdoor flow rate is realized by the Controller:MechanicalVentilation object with System Outdoor Air Method = IndoorAirQualityProcedure-GenericContaminant.
To specify minimum or maximum CO2 concentration schedule name for a zone. The AirLoopHVAC system outdoor flow rate is realized by the Controller:MechanicalVentilation object with System Outdoor Air Method = ProportionalControlBasedonOccupancySchedule or ProportionalControlBasedOnDesignOccupancy or ProportionalControlBasedOnDesignOARate. Carbon Dioxide Control Availability Schedule Name determines the availability of ProportionalControl .
For the first purpose above, when multiple zones are served by an AirLoop, those zones that do not have a contaminant controller object specified in the input data file are automatically assigned a carbon dioxide setpoint. Zone objects entered in the input data file are internally assigned an index number from 1 to n (first defined Zone object = 1, next Zone object defined in the input file = 2, etc.). For zones served by an AirLoop that do not have a contaminant controller specified, the zone’s carbon dioxide setpoint will be the same as the zone with the next highest zone index number that has a contaminant controller specified. If a zone with a higher index number and contaminant controller specified does not exist, then the zone with the next lowest zone index number that has a contaminant controller specified will be used. For example, assume an AirLoop serves zones 1 through 5, but one ZoneControl:ContaminantController object is specified for zone 2, a second ZoneControl:ContaminantController object is specified for zone 4, and no ZoneControl:ContaminantController objects are specified for zones 1, 3 and 5. In this case, zone 1 will be assigned the carbon dioxide setpoint schedule that was specified for zone 2, and zones 3 and 5 will be assigned the carbon dioxide setpoint schedule that was specified for zone 4.
The ZoneControl:ContaminantController object is also used for any of the following two purposes based on the outdoor air method specified in the DesignSpecification:OutdoorAir.
To control a zone to a specified indoor level of contaminants. When this zone is served by a dedicated outdoor air system AirLoopHVAC through a terminal unit, some type of terminal units are able to call a DesignSpecification:OutdoorAir object with Outdoor Air Method = IndoorAirQualityProcedure, so that the required outdoor airflow rate to reach the zone air setpoint can be assigned to the terminal unit. The total outdoor air flow in the AirLoopHVAC is a sum of all terminal units. In this way, each zone served by the same AirLoopHVAC can reach the zone air CO2 setpoint precisely.
To specify minimum CO2 concentration schedule name for a zone. When this zone is served by a dedicated outdoor air system AirLoopHVAC through a terminal unit, some type of terminal units are able to call a DesignSpecification:OutdoorAir object with Outdoor Air Method = ProportionalControlBasedonOccupancySchedule or ProportionalControlBasedOnDesignOccupancy. The outdoor airflow rate is determined by one of proportional control procedures. Then, the calculated outdoor airflow rate is assigned to the terminal unit. The total outdoor air flow in the AirLoopHVAC is a sum of all terminal units. In this way, each zone served by the same AirLoopHVAC will receive the outdoor airflow rate based on terminal unit request.
Inputs[LINK]
Field: Name[LINK]
Unique identifying name for the ZoneControl:ContaminantController.
Field: Zone Name[LINK]
Name of the zone that is being controlled.
Field:Carbon Dioxide Control Availability Schedule Name[LINK]
This field contains the name of a schedule that determines whether or not the ZoneControl:ContaminantController is available. When the schedule value is zero, the ZoneControl:ContaminantController is bypassed (not available to operate). When the schedule value is greater than zero, the ZoneControl:ContaminantController is available and will be used to calculate the required outdoor airflow rate to reach the carbon dioxide setpoint. If this field is left blank, the schedule has a value of 1 for all time periods. Schedule values must be between 0 and 1.
Field:Carbon Dioxide Setpoint Schedule Name[LINK]
This field contains the name of a schedule that contains the zone carbon dioxide concentration setpoint as a function of time. The units for carbon dioxide setpoint are ppm. The setpoint values in the schedule must be between 0 and 2000 ppm. . This field is used when the field System Outdoor Air Method = IndoorAirQualityProcedure in the Controller:MechanicalVentilation object.
Field:Minimum Carbon Dioxide Concentration Schedule Name[LINK]
This field contains the name of a schedule that contains the minimum zone carbon dioxide concentration setpoint as a function of time. The units for carbon dioxide setpoint are ppm. This field is used when the field System Outdoor Air Method = ProportionalControlBasedonOccupancySchedule or ProportionalControlBasedOnDesignOccupancy, or ProportionalControlBasedOnDesignOARate in the Controller:MechanicalVentilation object. This field is also used when the field Outdoor Air Method = ProportionalControlBasedonOccupancySchedule or ProportionalControlBasedOnDesignOccupancy in the DesignSpecification:OutdoorAir object.
Field:Maximum Carbon Dioxide Concentration Schedule Name[LINK]
This field contains the name of a schedule that contains the maximum zone carbon dioxide concentration as a function of time and is used to calculate design CO2 concentration level in the proportional ventilation control. The units for carbon dioxide setpoint are ppm. This field is used when the field System Outdoor Air Method = ProportionalControlBasedonOccupancySchedule, or ProportionalControlBasedOnDesignOccupancy, or ProportionalControlBasedOnDesignOARate in the Controller:MechanicalVentilation object.
Field: Generic Contaminant Control Availability Schedule Name[LINK]
This field contains the name of a schedule that determines whether or not the ZoneControl:ContaminantController is available. When the schedule value is zero, the generic contaminant control will not be performed. When the schedule value is greater than zero, the ZoneControl:ContaminantController is available and will be used to calculate the required outdoor airflow rate to reach the generic contaminant setpoint. If this field is left blank, the schedule has a value of 1 for all time periods. Schedule values must be between 0 and 1.
Field: Generic Contaminant Setpoint Schedule Name[LINK]
This field contains the name of a schedule that contains the zone generic contaminant concentration setpoint as a function of time. The units for generic contaminant setpoint are ppm. The setpoint values in the schedule must be> = 0.
An IDF example is provided below:
Outputs[LINK]
The following output variables are available when the ZoneControl:ContaminantController object is specified.
HVAC,Average,Zone Air CO2 Predicted Load to Setpoint Mass Flow Rate [kg/s]
HVAC,Average,Zone Air CO2 Setpoint Concentration [ppm]
HVAC,Average,Zone Generic Air Contaminant Predicted Load to Setpoint Mass Flow Rate [kg/s]
HVAC,Average,Zone Generic Air Contaminant Setpoint Concentration [ppm]
Zone Air CO2 Predicted Load to Setpoint Mass Flow Rate [kg/s][LINK]
This output is the average predicted outdoor airflow rate in kg/s required to meet the current zone carbon dioxide setpoint for the time step being reported. This value is calculated and reported from the Predict step in the Zone Contaminant Predictor-Corrector module. The calculated outdoor airflow rate will be specified in the Controller:MechanicalVentilation object with System Outdoor Air Method = IndoorAirQualityProcedureto provide enough outdoor ventilation air to keep the zone air carbon dioxide concentration level at or below the setpoint.
Zone Air CO2 Setpoint Concentration [ppm][LINK]
This output variable is the average carbon dioxide setpoint value, in parts per million, for the time step being reported.
Zone Generic Air Contaminant Predicted Load to Setpoint Mass Flow Rate [kg/s][LINK]
This output is the average predicted outdoor airflow rate in kg/s required to meet the current zone generic contaminant setpoint for the time step being reported. This value is calculated and reported from the Predict step in the Zone Contaminant Predictor-Corrector module. The calculated outdoor airflow rate will be specified in the Controller:MechanicalVentilation object with System Outdoor Air Method = IndoorAirQualityProcedure-GenericContaminant****to provide enough outdoor ventilation air to keep the zone air generic contaminant concentration level at or below the setpoint.
Zone Generic Air Contaminant Setpoint Concentration [ppm][LINK]
This output variable is the averagegeneric contaminant setpoint value, in parts per million, for the time step being reported.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.