There are five main zone equipment statements that must be
used to describe a block of zone equipment as shown in the
below figure “Zone
Equipment Input Syntax Map”.
Types of Zone
equipment are listed below and shown below in figure “Zone
Equipment”.
Available Zone Equipment Types
Air Distribution Equipment
AirTerminal:SingleDuct:Uncontrolled
AirTerminal:SingleDuct:ConstantVolume:Reheat
AirTerminal:SingleDuct:VAV:Reheat
AirTerminal:SingleDuct:VAV:NoReheat
AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan
AirTerminal:DualDuct:ConstantVolume AirTerminal:DualDuct:VAV
Powered Induction Units (Series and Parallel)
Zone Forced Air Units
ZoneHVAC:IdealLoadsAirSystem
ZoneHVAC:FourPipeFanCoil ZoneHVAC:WindowAirConditioner
ZoneHVAC:RefrigerationChillerSet Unit Ventilator/Heater
Air-to-Air Heat Pumps Unitary Systems (heat only and
heat/cool) Furnaces (heat only and heat/cool) Energy Recovery
Ventilator:Stand Alone CoilSystem:Cooling:DX
Radiative/Convective Units
Baseboard Heaters Low Temp
Radiant Systems High Temp Radiant System
Representative Zone Equipment
[fig:representative-zone-equipment]
The following figure (Air Loop/Zone Equipment Node Diagram)
illustrates the connection between the zone equipment and the
air loop systems.
Air Loop/Zone Equipment Node
Diagram [fig:air-loopzone-equipment-node-diagram]
Each zone served by an HVAC system must have three
additional statements to complete the zone equipment
specification. An ZoneHVAC:AirDistributionUnit
allows equipment typically found within the zone inlet
ductwork (such as dampers, reheat coils, etc.) to be attached
to the supply air stream for a particular zone. A ZoneControl
statement will allow the conditions in the zone to be managed.
Finally, a ZoneHVAC:EquipmentConnections
statement describes all of the pertinent information about the
zone from an HVAC perspective. Each of these statements is
described in more detail below.
The ZoneHVAC:AirDistributionUnit
object gives further information on what air loop equipment
(air terminal units) will be serving a particular zone. The ZoneHVAC:AirDistributionUnit
is the part of the system that is supplied from a common main
air handler simulated in the Air Loop Simulation and includes
the equipment that controls or tempers the air going to each
individual zone according to the desired thermostatic control.
The current options for ZoneHVAC:AirDistributionUnit
terminal unit types are:
Connections between the air distribution unit, the supply
air duct, and the zone are specified in the input syntax for
the air distribution unit and the AirLoopHVAC:ZoneSplitter.
The input syntax also explicitly defines an outlet identifier.
This implies a connection to a zone through a NodeList
for zone inlets (see the ZoneHVAC:EquipmentConnections
statement). The air distribution unit is limited to one
combined component-controller unit; because controls are
normally based on the zone thermostat and can work in parallel
or series in complex fashion. Since the control and the flow
resolution can be complex, each air distribution unit is
unique in addressing these combinations and therefore only one
is allowed per zone.
The Air Distribution unit also allows the user to specify
leaks in the supply air duct system. These inputs are used in
the EnergyPlus Simplified Duct
Leakage Model (SDLM). This model simulates a specific
configuration: supply leaks to a return plenum in a commercial
VAV or CV system. The system must have a constant static
pressure setpoint. Within these limitations SDLM allows the
user to easily evaluate the energy penalty due to duct
leakage.
This is the leakage upstream of the terminal unit as a
fraction of the design flow rate through the unit. It is the
leakage fraction at the design flow rate. It is used to
calculate a leakage flow rate which is then held constant
while the system air flow varies. This input is optional; the
default is zero.
This is the leakage downstream of the terminal unit as a
fraction of the current flow rate through the terminal unit.
This fraction is held constant, so the leakage flow rate will
vary proportinally with the supply air flow rate. This input
is optional; the default is zero.
Field:
Design Specification Air Terminal Sizing Name[LINK]
Two example IDF excerpts (one with duct leakage, one
without):
ZoneHVAC:AirDistributionUnit,
SPACE1-1 ATU, !- Air Distribution Unit Name
SPACE1-1 In Node, !- Air Dist Unit Outlet Node Name
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT, !- KEY--System Component Type 1
SPACE1-1 VAV Reheat; !- Component Name 1
ZoneHVAC:AirDistributionUnit,
SPACE4-1 ATU, !- Air Distribution Unit Name
SPACE4-1 In Node, !- Air Dist Unit Outlet Node Name
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT, !- KEY--System Component Type 1
SPACE4-1 VAV Reheat, !- Component Name 1
0.05, !- upstream nominal leakage fraction
0.07; !- downstream constant leakage fraction
Finally, the ZoneHVAC:EquipmentConnections
statement defines the remaining details about each thermal
zone from an HVAC perspective (besides the controls which were
defined above). As with other statements, the first two items
in this object are the keyword and an identifying name which
links the zone back to its geometrical input, internal gains,
etc. and other statements in the HVAC section of the input.
The next three items are names of lists (equipment, air inlet
nodes, and air exhaust nodes) that are described in more
detail below. Note that if there are no air exhaust nodes from
the zone that field is left blank. And if there are no air
inlet nodes, that field is left blank. Finally, two node names
are necessary to complete the zone-HVAC description. The first
node is the main air node for the zone upon which the air heat
balance is performed. The other node(s) begins the return air
path(s) from the zone.
Note that all nodes mentioned in the ZoneHVAC:EquipmentConnections
input must be unique. That is, all nodes in all the ZoneHVAC:EquipmentConnections
statements referenced by the “Zone
Air Inlet Nodes”, “Zone
Air Exhaust Nodes”, “Zone
Air Node Name” and “Zone
Return Air Node Name” cannot have any node name appearing more
than once.
Name links this equipment list back to the heat balance for
the zone.
Field:
Zone Conditioning Equipment List Name[LINK]
List of zone equipment for this zone in a ZoneHVAC:EquipmentList
object. This list will consist of air distribution units or
other direct convection or radiant equipment, i.e. window air
conditioner, baseboard, fan coils, etc.
There can be more than one air inlet node depending on how
many pieces of equipment are in the ZoneHVAC:EquipmentList.
Generally there will be one air inlet node for each piece of
zone equipment that delivers conditioned air to the zone.
Components such as electric or hot water baseboards and
radiant systems do not require zone air inlet nodes. If there
is only one node – its name can be put in this field. If there
is more than one node, this must be the name of a node list
object (a node list object can also contain only one node
name). If this field is not required (as in the baseboard
system), it should be blank.
Field:
Zone Air Exhaust Node or NodeList Name[LINK]
List of exhaust nodes leaving the zone for exhaust fans,
zone energy recovery, etc. However these nodes are also used
as sources of zone air for zone components such as fan coil
units, unit heaters and ventilators, and window air
conditioners. For each such component attached to a zone there
should be a unique zone exhaust node acting as the inlet node
to the component. If there is only one node – its name can be
put in this field. If there is more than one node, this must
be the name of a node list object (a node list object can also
contain only one node name). If there are no air exhaust
nodes, this field should be blank.
The conditions at this node represent the average state of
the air in the zone. For zones modeled as fully mixed the
conditions at this node are assumed to represent the air in
the entire zone. This field is required for all ZoneHVAC:EquipmentConnections
statements.
Field:
Zone Return Air Node or NodeList Name[LINK]
The name of one or more return air nodes which attach the
zone to an air loop return air path. Even if there is no
return air or no return air path, a unique name must be
entered in this field. The conditions at each return node
represent the state of the air leaving the zone including any
heat gain assigned to that return node from Lights,
refrigeration equipment or airflow windows.
Field:
Zone Return Air Node 1 Flow Rate Fraction Schedule Name[LINK]
The name of a schedule to specify the return air flow rate
for the first return air node as a fraction of the base return
air. If the next field is blank, then the return air flow rate
is the total supply inlet flow rate to the zone less the total
exhaust node flow rate from the zone multiplied by this
schedule name. If this field is left blank, the schedule
defaults to 1.0 at all times.
Field:
Zone Return Air Node 1 Flow Rate Basis Node or NodeList
Name[LINK]
The name of a node or list of nodes (NodeList) that is used
to calculate the return air flow rate for the first return air
node in this zone. The sum of the current flow rates for this
node(s) multiplied by the Zone
Return Air Node 1 Flow Rate Fraction Schedule determines the
return air flow rate. If this field is blank, then the base
return air flow rate is the total supply inlet flow rate to
the zone less the total exhaust node flow rate from the zone
in the case of a single air loop serving this zone. If there
are multiple air loops serving this zone, the base return air
flow rate is governed by the corresponding supply inlet flow
rate and the AirloopHVAC Design Return Air Flow Fraction of
Supply Air Flow.
An example of this statement in an IDF is:
ZoneHVAC:EquipmentConnections,
SPACE3-1, !- Zone Name
SPACE3-1 Eq, !- List Name: Zone Equipment
SPACE3-1 In Nodes, !- List Name: Zone Air Inlet Nodes
, !- List Name: Zone Air Exhaust Nodes
SPACE3-1 Node, !- Zone Air Node Name
SPACE3-1 Out Node; !- Zone Return Air Node or NodeList Name
The following HVAC equipment types are allowed as zone
equipment. The component matrix shows which coils and fans are
allowed with which equipment models.
The first list encountered in the ZoneHVAC:EquipmentConnections
statement is the ZoneHVAC:EquipmentList.
This object lists all HVAC equipment serving the zone. Each
item in the list has four fields associated with it: Object
Type, Name, Cooling Sequence and Heating or No-Load Sequence
The Object Type and Name identify the specific equipment
object. Cooling Sequence and Heating or No-Load Sequence
specify the order of simulation for zones with more than one
type of HVAC equipment.
The Load Distribution Scheme selects the algorithm used to
allocate the current zone load across the zone equipment.
There are four choices: SequentialLoad, UniformLoad,
UniformPLR, and SequentialUniformPLR. The default is
SequentialLoad. In all cases, the equipment operates in the
order specifed by the Zone
Equipment Cooling Sequence and Heating or No-Load Sequence
fields.
SequentialLoad loads each piece of available equipment
sequentially with the full remaining load.
UniformLoad evenly distributes the total load equally
among all available components on the equipment list for the
current load type.
UniformPLR evenly distributes the total load among all
available components on the equipment list for the current
load type at a uniform part load ratio (PLR).
SequentialUniformPLR determines how many of the
available components are required to meet the current load,
then distributes the load at a uniform part load ratio
(PLR).
Field
Set (Zone Equipment: Object Type, Name, Cooling Sequence,
Heating or No-Load Sequence, Sequential Cooling Fraction
Schedule, Sequential Heating Fraction Schedule)[LINK]
This set is used together in order to sequence the
equipment for heating and cooling. The #1 sequence equipment
will try to meet the entire demand with its capacity and then
pass the results on to the #2 and so on for both heating and
cooling. This field set is extensible by duplicating the last
four fields.
Equipment is simulated in the order specified by Zone
Equipment Cooling Sequence and Zone
Equipment Heating or No-Load Sequence, depending on the
current thermostat request. For equipment of similar type,
assign sequence 1 to the first system intended to serve that
type of load, assign sequence 2 to the next system, and so on.
For situations where one or more equipment types has limited
capacity or limited control capability, order the sequence so
that the most controllable piece of equipment runs last. For
example, with a dedicated outdoor air system (DOAS), the air
terminal for the DOAS should be assigned Heating Sequence = 1
and Cooling Sequence = 1. Any other equipment should be
assigned sequence 2 or higher so that it will see the net load
after the DOAS air is added to the zone.
Type of zone equipment such as air distribution unit,
baseboard, window air conditioner, etc. The current legal
types are listed in the following table:
Legal Zone Equipment Types
(ZoneHVAC:EquipmentList)
Specifies the zone equipment simulation order when the zone
thermostat requests cooling.
Field:
Zone Equipment <x> Heating or No-Load Sequence[LINK]
Specifies the zone equipment simulation order when the zone
thermostat requests heating or no load.
Field:
Zone Equipment <x> Sequential Cooling Fraction Schedule
Name[LINK]
References a schedule that specifies the fraction of the
remaining cooling load this equipment will attempt to serve.
Only applies if the load distribution scheme is
SequentialLoad. Leaving this blank indicates a constant
schedule of 1.0.
Field:
Zone Equipment <x> Sequential Heating Fraction Schedule
Name[LINK]
References a schedule that specifies the fraction of the
remaining heating load this equipment will attempt to serve.
Only applies if the load distribution scheme is
SequentialLoad. Leaving this blank indicates a constant
schedule of 1.0.
Examples of this statement in an IDF are:
ZoneHVAC:EquipmentList,
Zone1Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Zone1TermReheat, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1, !- Zone Equipment 1 Heating or No-Load Sequence
, !- Zone Equipment 1 Sequential Cooling Fraction Schedule Name
; !- Zone Equipment 1 Sequential Heating Fraction Schedule Name
ZoneHVAC:EquipmentList,
Zone1Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
Zone1DirectAir, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1, !- Zone Equipment 1 Heating or No-Load Sequence
0.5, !- Zone Equipment 1 Sequential Cooling Fraction
0.5, !- Zone Equipment 1 Sequential Heating Fraction
ZoneHVAC:WaterToAirHeatPump, !- Zone Equipment 2 Object Type
Zone1WTAHP, !- Zone Equipment 2 Name
2, !- Zone Equipment 2 Cooling Sequence
2, !- Zone Equipment 2 Heating or No-Load Sequence
0.5, !- Zone Equipment 2 Sequential Cooling Fraction
0.5; !- Zone Equipment 2 Sequential Heating Fraction
Group - Zone Equipment[LINK]
There are five main zone equipment statements that must be used to describe a block of zone equipment as shown in the below figure “Zone Equipment Input Syntax Map”.
Types of Zone equipment are listed below and shown below in figure “Zone Equipment”.
![ZoneEquipmentSyntax (media/image261.png)
Figure 99. Zone Equipment Input Syntax Map
The following figure (Air Loop/Zone Equipment Node Diagram) illustrates the connection between the zone equipment and the air loop systems.
Each zone served by an HVAC system must have three additional statements to complete the zone equipment specification. An ZoneHVAC:AirDistributionUnit allows equipment typically found within the zone inlet ductwork (such as dampers, reheat coils, etc.) to be attached to the supply air stream for a particular zone. A ZoneControl statement will allow the conditions in the zone to be managed. Finally, a ZoneHVAC:EquipmentConnections statement describes all of the pertinent information about the zone from an HVAC perspective. Each of these statements is described in more detail below.
ZoneHVAC:AirDistributionUnit[LINK]
The ZoneHVAC:AirDistributionUnit object gives further information on what air loop equipment (air terminal units) will be serving a particular zone. The ZoneHVAC:AirDistributionUnit is the part of the system that is supplied from a common main air handler simulated in the Air Loop Simulation and includes the equipment that controls or tempers the air going to each individual zone according to the desired thermostatic control. The current options for ZoneHVAC:AirDistributionUnit terminal unit types are:
AirTerminal:DualDuct:ConstantVolume
AirTerminal:DualDuct:VAV
AirTerminal:DualDuct:VAV:OutdoorAir
AirTerminal:SingleDuct:ConstantVolume:Reheat
AirTerminal:SingleDuct:VAV:Reheat
AirTerminal:SingleDuct:VAV:NoReheat
AirTerminal:SingleDuct:SeriesPIU:Reheat
AirTerminal:SingleDuct:ParallelPIU:Reheat
AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction
AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan
AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat
AirTerminal:SingleDuct:VAV:HeatAndCool:NoReheat
AirTerminal:SingleDuct:ConstantVolume:CooledBeam
AirTerminal:SingleDuct:UserDefined
AirTerminal:SingleDuct:Mixer
Connections between the air distribution unit, the supply air duct, and the zone are specified in the input syntax for the air distribution unit and the AirLoopHVAC:ZoneSplitter. The input syntax also explicitly defines an outlet identifier. This implies a connection to a zone through a NodeList for zone inlets (see the ZoneHVAC:EquipmentConnections statement). The air distribution unit is limited to one combined component-controller unit; because controls are normally based on the zone thermostat and can work in parallel or series in complex fashion. Since the control and the flow resolution can be complex, each air distribution unit is unique in addressing these combinations and therefore only one is allowed per zone.
The Air Distribution unit also allows the user to specify leaks in the supply air duct system. These inputs are used in the EnergyPlus Simplified Duct Leakage Model (SDLM). This model simulates a specific configuration: supply leaks to a return plenum in a commercial VAV or CV system. The system must have a constant static pressure setpoint. Within these limitations SDLM allows the user to easily evaluate the energy penalty due to duct leakage.
Inputs[LINK]
Field: Name[LINK]
Unique identifying name of the air distribution unit.
Field: Air Distribution Unit Outlet Node Name[LINK]
Outlet node name for the air distribution unit to the attached zone.
Field: Air Terminal Object Type[LINK]
Single combined component/controller unit for that attached zone. Selection of components as listed above.
Field: Air Terminal Name[LINK]
The unique identifying component name.
Field: Nominal Upstream Leakage Fraction[LINK]
This is the leakage upstream of the terminal unit as a fraction of the design flow rate through the unit. It is the leakage fraction at the design flow rate. It is used to calculate a leakage flow rate which is then held constant while the system air flow varies. This input is optional; the default is zero.
Field: Constant Downstream Leakage Fraction[LINK]
This is the leakage downstream of the terminal unit as a fraction of the current flow rate through the terminal unit. This fraction is held constant, so the leakage flow rate will vary proportinally with the supply air flow rate. This input is optional; the default is zero.
Field: Design Specification Air Terminal Sizing Name[LINK]
This optional input field is the name of a DesignSpecification:AirTerminal:Sizing object which specifies sizing adjustments to be made for the air terminal unit referenced by this object. The terminal unit is initially sized according to the inputs in the corresponding Sizing:Zone object. Then the adjustment factors in the DesignSpecification:AirTerminal:Sizing object are applied. See DesignSpecification:AirTerminal:Sizing for more details. If left blank, then no adjustments are made.
Two example IDF excerpts (one with duct leakage, one without):
ZoneHVAC:EquipmentConnections[LINK]
Finally, the ZoneHVAC:EquipmentConnections statement defines the remaining details about each thermal zone from an HVAC perspective (besides the controls which were defined above). As with other statements, the first two items in this object are the keyword and an identifying name which links the zone back to its geometrical input, internal gains, etc. and other statements in the HVAC section of the input. The next three items are names of lists (equipment, air inlet nodes, and air exhaust nodes) that are described in more detail below. Note that if there are no air exhaust nodes from the zone that field is left blank. And if there are no air inlet nodes, that field is left blank. Finally, two node names are necessary to complete the zone-HVAC description. The first node is the main air node for the zone upon which the air heat balance is performed. The other node(s) begins the return air path(s) from the zone.
Note that all nodes mentioned in the ZoneHVAC:EquipmentConnections input must be unique. That is, all nodes in all the ZoneHVAC:EquipmentConnections statements referenced by the “Zone Air Inlet Nodes”, “Zone Air Exhaust Nodes”, “Zone Air Node Name” and “Zone Return Air Node Name” cannot have any node name appearing more than once.
Inputs[LINK]
Field: Zone Name[LINK]
Name links this equipment list back to the heat balance for the zone.
Field: Zone Conditioning Equipment List Name[LINK]
List of zone equipment for this zone in a ZoneHVAC:EquipmentList object. This list will consist of air distribution units or other direct convection or radiant equipment, i.e. window air conditioner, baseboard, fan coils, etc.
Field: Zone Air Inlet Node or NodeList Name[LINK]
There can be more than one air inlet node depending on how many pieces of equipment are in the ZoneHVAC:EquipmentList. Generally there will be one air inlet node for each piece of zone equipment that delivers conditioned air to the zone. Components such as electric or hot water baseboards and radiant systems do not require zone air inlet nodes. If there is only one node – its name can be put in this field. If there is more than one node, this must be the name of a node list object (a node list object can also contain only one node name). If this field is not required (as in the baseboard system), it should be blank.
Field: Zone Air Exhaust Node or NodeList Name[LINK]
List of exhaust nodes leaving the zone for exhaust fans, zone energy recovery, etc. However these nodes are also used as sources of zone air for zone components such as fan coil units, unit heaters and ventilators, and window air conditioners. For each such component attached to a zone there should be a unique zone exhaust node acting as the inlet node to the component. If there is only one node – its name can be put in this field. If there is more than one node, this must be the name of a node list object (a node list object can also contain only one node name). If there are no air exhaust nodes, this field should be blank.
Field: Zone Air Node Name[LINK]
The conditions at this node represent the average state of the air in the zone. For zones modeled as fully mixed the conditions at this node are assumed to represent the air in the entire zone. This field is required for all ZoneHVAC:EquipmentConnections statements.
Field: Zone Return Air Node or NodeList Name[LINK]
The name of one or more return air nodes which attach the zone to an air loop return air path. Even if there is no return air or no return air path, a unique name must be entered in this field. The conditions at each return node represent the state of the air leaving the zone including any heat gain assigned to that return node from Lights, refrigeration equipment or airflow windows.
Field: Zone Return Air Node 1 Flow Rate Fraction Schedule Name[LINK]
The name of a schedule to specify the return air flow rate for the first return air node as a fraction of the base return air. If the next field is blank, then the return air flow rate is the total supply inlet flow rate to the zone less the total exhaust node flow rate from the zone multiplied by this schedule name. If this field is left blank, the schedule defaults to 1.0 at all times.
Field: Zone Return Air Node 1 Flow Rate Basis Node or NodeList Name[LINK]
The name of a node or list of nodes (NodeList) that is used to calculate the return air flow rate for the first return air node in this zone. The sum of the current flow rates for this node(s) multiplied by the Zone Return Air Node 1 Flow Rate Fraction Schedule determines the return air flow rate. If this field is blank, then the base return air flow rate is the total supply inlet flow rate to the zone less the total exhaust node flow rate from the zone in the case of a single air loop serving this zone. If there are multiple air loops serving this zone, the base return air flow rate is governed by the corresponding supply inlet flow rate and the AirloopHVAC Design Return Air Flow Fraction of Supply Air Flow.
An example of this statement in an IDF is:
The following HVAC equipment types are allowed as zone equipment. The component matrix shows which coils and fans are allowed with which equipment models.
ZoneHVAC:EquipmentList[LINK]
The first list encountered in the ZoneHVAC:EquipmentConnections statement is the ZoneHVAC:EquipmentList. This object lists all HVAC equipment serving the zone. Each item in the list has four fields associated with it: Object Type, Name, Cooling Sequence and Heating or No-Load Sequence The Object Type and Name identify the specific equipment object. Cooling Sequence and Heating or No-Load Sequence specify the order of simulation for zones with more than one type of HVAC equipment.
Note that a ZoneHVAC:AirDistributionUnit or AirTerminal:SingleDuct:Uncontrolled must be listed in this statement if there is a forced air system serving the zone from an air loop.
Inputs[LINK]
Field: Name[LINK]
Unique identifying name.
Field: Load Distribution Scheme[LINK]
The Load Distribution Scheme selects the algorithm used to allocate the current zone load across the zone equipment. There are four choices: SequentialLoad, UniformLoad, UniformPLR, and SequentialUniformPLR. The default is SequentialLoad. In all cases, the equipment operates in the order specifed by the Zone Equipment Cooling Sequence and Heating or No-Load Sequence fields.
SequentialLoad loads each piece of available equipment sequentially with the full remaining load.
UniformLoad evenly distributes the total load equally among all available components on the equipment list for the current load type.
UniformPLR evenly distributes the total load among all available components on the equipment list for the current load type at a uniform part load ratio (PLR).
SequentialUniformPLR determines how many of the available components are required to meet the current load, then distributes the load at a uniform part load ratio (PLR).
Field Set (Zone Equipment: Object Type, Name, Cooling Sequence, Heating or No-Load Sequence, Sequential Cooling Fraction Schedule, Sequential Heating Fraction Schedule)[LINK]
This set is used together in order to sequence the equipment for heating and cooling. The #1 sequence equipment will try to meet the entire demand with its capacity and then pass the results on to the #2 and so on for both heating and cooling. This field set is extensible by duplicating the last four fields.
Equipment is simulated in the order specified by Zone Equipment Cooling Sequence and Zone Equipment Heating or No-Load Sequence, depending on the current thermostat request. For equipment of similar type, assign sequence 1 to the first system intended to serve that type of load, assign sequence 2 to the next system, and so on. For situations where one or more equipment types has limited capacity or limited control capability, order the sequence so that the most controllable piece of equipment runs last. For example, with a dedicated outdoor air system (DOAS), the air terminal for the DOAS should be assigned Heating Sequence = 1 and Cooling Sequence = 1. Any other equipment should be assigned sequence 2 or higher so that it will see the net load after the DOAS air is added to the zone.
Field: Zone Equipment <x> Object Type[LINK]
Type of zone equipment such as air distribution unit, baseboard, window air conditioner, etc. The current legal types are listed in the following table:
Field: Zone Equipment <x> Name[LINK]
Name of the zone equipment used in the object definition of its type.
Field: Zone Equipment <x> Cooling Sequence[LINK]
Specifies the zone equipment simulation order when the zone thermostat requests cooling.
Field: Zone Equipment <x> Heating or No-Load Sequence[LINK]
Specifies the zone equipment simulation order when the zone thermostat requests heating or no load.
Field: Zone Equipment <x> Sequential Cooling Fraction Schedule Name[LINK]
References a schedule that specifies the fraction of the remaining cooling load this equipment will attempt to serve. Only applies if the load distribution scheme is SequentialLoad. Leaving this blank indicates a constant schedule of 1.0.
Field: Zone Equipment <x> Sequential Heating Fraction Schedule Name[LINK]
References a schedule that specifies the fraction of the remaining heating load this equipment will attempt to serve. Only applies if the load distribution scheme is SequentialLoad. Leaving this blank indicates a constant schedule of 1.0.
Examples of this statement in an IDF are:
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.