Group
– Internal Gains (People, Lights, Other internal zone
equipment)[LINK]
Not all the influence for energy consumption in the
building is due to envelope and ambient conditions. This group
of objects describes other internal gains that may come into
play (People, Lights,
Various Equipment Types).
The people statement is used to model the occupant’s affect
on the space conditions. The following definition addresses
the basic affects as well as providing information that can be
used to report the thermal comfort of a group of occupants.
The Fanger, Pierce Two-Node, and Kansas State University
Two-Node thermal comfort models are available in EnergyPlus. A
user may select any of these models for each People
statement by simply adding the appropriate choice keyword
after the air velocity schedule name. Thermal comfort
calculations will only be made for people statements that
include specific requests for these thermal comfort models. .
This object also requires input of carbon dioxide generation
rate based on people activity level for zone carbon dioxide
simulations.
The name of the People
object. Must be unique across all People
objects.
Field: Zone or ZoneList
Name[LINK]
This field is the name of the zone (ref:
Zone](page-011.html#zone)) or [ZoneList](../input-output-reference/page-011.html#zonelist)
(ref: [ZoneList](../input-output-reference/page-011.html#zonelist))
and links a particular people statement to a thermal zone or
set of thermal zones in the building. When the [ZoneList](../input-output-reference/page-011.html#zonelist)
option is used then this people definition is applied to each
of the zones in the zone list effecting a global definition
for the number of people in the zone. The Zonelist option can
be used effectively with the people/area and area/person
options of the Number of [People Calculation Method.
The name of the actual people object becomes
<Zone](page-011.html#zone) Name> <[People Object
Name> and should be less than the standard length (100
characters) for a name field. If it is greater than this
standard length, it may be difficult to specify in output
reporting as it will be truncated. A warning will be shown if
the generated name is greater than 100 characters. If it
duplicates another such concatenated name, there will be a
severe error and terminate the run.
Field: Number of
People Schedule Name[LINK]
This field is the name of the schedule (ref: Schedules)
that modifies the number of people parameter (see Number of People
Calculation Method and related fields). The schedule values
can be any positive number. The actual number of people in a
zone as defined by this statement is the product of the number
of people field and the value of the schedule specified by
name in this field.
Field:
Number of People Calculation Method[LINK]
This field is a key/choice field that tells which of the
next three fields are filled and is descriptive of the method
for calculating the nominal number of occupants (people) in
the [Zone](../input-output-reference/page-011.html#zone).
The key/choices are:
- People
- With this choice, the method used will be a straight
insertion of the number of occupants (people). (The Number of
People field should be filled.)
- People/Area
- With this choice, the method used will be a factor per
floor area of the zone. (The People per Zone Floor Area field should be
filled).
- Area/Person
- With this choice, the method used will be a factor of
floor area per person. (The Zone Floor Area per Person field
should be filled).
Field: Number of People[LINK]
This field is used to represent the maximum number of
people in a zone that is then multiplied by a schedule
fraction (see schedule field). In EnergyPlus, this is slightly
more flexible in that the number of people could be a
“diversity factor” applied to a schedule of real numbers. Note
that while the schedule value can vary from hour to hour, the
number of people field is constant for all simulation
environments.
Field: People per
Zone Floor Area[LINK]
This factor (person/m2) is used, along with the
Zone](page-011.html#zone) Floor Area to determine the maximum
number of people as described in the Number of [People field.
The choice from the method field should be “people/area”.
Field: Zone Floor
Area per Person[LINK]
This factor (m2/person) is used, along with the
Zone](page-011.html#zone) Floor Area to determine the maximum
number of people as described in the Number of [People field.
The choice from the method field should be “area/person”.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the type of heat being given off by
people in a zone. The number specified in this field will be
multiplied by the total sensible energy emitted by people to
give the amount of long wavelength radiation gain from human
beings in a zone. The remainder of the sensible load is
assumed to be convective heat gain. Note that latent gains
from people are not included in either the radiant or
convective heat gains. See the Engineering Reference document
for more details.
Field: Sensible Heat
Fraction[LINK]
The user can use this field to specify a fixed sensible
fraction for the heat gain due to this PEOPLE object. Normally
the program calculates the sensible/latent split; this field
gives the user control over this split. This field is
autocalculated: if the field is blank or
autocalculate, the program will calculate the
sensible/latent split; if a value is entered, it will be used
as the sensible fraction of the current total heat gain.
Field: Activity
Level Schedule Name[LINK]
This field is the name of the schedule that determines the
amount of heat gain per person in the zone under design
conditions. This value is modified somewhat based on a
correlation to account for variations in space temperature.
The schedule values may be any positive number and the units
for this parameter is Watts per person. This schedule
represents the total heat gain per person including
convective, radiant, and latent. An internal algorithm is used
to determine what fraction of the total is sensible and what
fraction is latent. Then, the sensible portion is divided into
radiant and convective portions using the value specified for
Fraction Radiant (above). See the Engineering Reference
document for more details.
Values for activity level can range anywhere from
approximately 100-150 Watts per person for most office
activities up to over 900 Watts per person for strenuous
physical activities such as competitive wrestling. The
following table (Table 11) is based on Table 4 from the 2005
ASHRAE Handbook of Fundamentals, page 8.6. In addition to the
information from the ASHRAE HOF, there is an added column of
values in W/Person such as necessary for the activity level
schedule values. This column uses the standard adult body
surface area of 1.8 m2 to multiply the activity
levels in W/m2 that are used in the table. Warnings
are produced when the activity level schedule values fall
outside normal ranges. Having too low or too high values can
also skew thermal comfort reporting values.
Field: Carbon
Dioxide Generation Rate[LINK]
This numeric input field specifies carbon dioxide
generation rate per person with units of m3/s-W. The total
carbon dioxide generation rate from this object is:
Number of People
* People
Schedule * People
Activity * Carbon Dioxide Generation Rate. The default value
is 3.82E-8 m3/s-W (obtained from ASHRAE Standard 62.1-2007
value at 0.0084 cfm/met/person over the general adult
population). The maximum value can be 10 times the default
value.
Field: Enable
ASHRAE 55 comfort warnings[LINK]
This field accepts either “Yes” or “No” as values. When
“Yes” is specified, warnings are generated when the space
conditions are outside of the ASHRAE 55 comfort range as
discussed in the sections that follow titled “Simplified
ASHRAE 55-2004 Graph Related Outputs” and “Simplified ASHRAE
55 Warnings.” The default is not to provide these warnings so
if you want to know if your space is outside this comfort
range you must set this field to Yes.
Table: Metabolic Rates for Various Activities
Activity|Activity Level W/Person EnergyPlus Schedule
Value|Activity Level W/m2|met*
——–|————————————————-|———————|—– Resting
Sleeping|72|40|0.7 Reclining|81|45|0.8 Seated, quiet|108|60|1
Standing, relaxed|126|70|1.2 Walking (on level
surface) 3.2 km/h (0.9 m/s)|207|115|2 4.3 km/h (1.2
m/s)|270|150|2.6 6.4 km/h (1.8 m/s)|396|220|3.8 Office
Activities Reading, seated|99|55|1 Writing|108|60|1
Typing|117|65|1.1 Filing, seated|126|70|1.2 Filing,
standing|144|80|1.4 Walking about|180|100|1.7
Lifting/packing|216|120|2.1 Miscellaneous Occupational
Activities Cooking|171 to 207|95 to 115|1.6 to 2.0
Housecleaning|207 to 360|115 to 200|2.0 to 3.4 Seated, heavy
limb movement|234|130|2.2 Machine work| || sawing (table
saw)|189|105|1.8 light (electrical industry)|207 to 252|115 to
140|2.0 to 2.4 heavy|423|235|4 Handling 50 kg bags|423|235|4
Pick and shovel work|423 to 504|235 to 280|4.0 to 4.8
Miscellaneous Leisure Activities Dancing, social|252
to 459|140 to 255|2.4 to 4.4 Calisthenics/exercise|315 to
423|175 to 235|3.0 to 4.0 Tennis, singles|378 to 486|210 to
270|3.6 to 4.0 Basketball|522 to 792|290 to 440|5.0 to 7.6
Wrestling, competitive|738 to 909|410 to 505|7.0 to 8.7
*Note that one met = 58.1
W/m2
Field:
Mean Radiant Temperature Calculation Type[LINK]
This field specifies the type of Mean Radiant Temperature
(MRT) calculation the user wishes to use for the thermal
comfort model. At the present time, there are two options for
MRT calculation type: zone averaged and surface weighted. The
default calculation is “ZoneAveraged”. In the zone averaged
MRT calculation, the MRT used for the thermal comfort
calculations is for an “average” point in the zone. MRT is
calculated based on an area-emissivity weighted average of all
of the surfaces in the zone. In cases where the emissivity of
all of the surfaces are sufficiently small (near zero), the
mean radiant temperature will be set to the mean air
temperature of the space to avoid divide by zero errors. The
other MRT calculation type is “SurfaceWeighted”. The goal of
this calculation type is to estimate a person in the space
close to a particular surface without having to define exact
view factors for all of the surfaces and the location of the
person in the space. The MRT used in the thermal comfort
calculations when the “surface weighted” calculation type is
selected is actually the average of the temperature of the
surface to which the person is closest (defined by the next
field “Surface Name”) and the zone averaged MRT (defined
above). The surface temperature alone is not used because in
theory the maximum view factor from a person to any flat
surface is roughly 0.5. In the “surfaceweighted” calculation,
the surface in question actually gets slightly more weighting
than 50% since the surface selected is still a part of the
zone average MRT calculation. Again, this simplification was
made to avoid the specification of view factors and the exact
location of the person.
A third option is to use “anglefactor”. This option allows
for more explicit positioning of the person within the space
by defining the angle factors from the person to the various
surfaces in the zone. This option requires the user to list
the surfaces that the person can see from a radiation
standpoint and also define the angle (or view) factor for each
surface. The AngleFactorList object (see next object
description) is intended to give the user this
opportunity.
Field:
Surface Name/Angle Factor List Name[LINK]
This field is only valid when the user selects
“surfaceweighted” for the MRT calculation type (see the
previous input field description). In this case, the field is
the name of a surface within the zone the people are residing.
This surface will be used in the MRT calculation as defined
above to come up with a more representative MRT for a person
near a particular surface. The MRT used for thermal comfort
calculations using the “surface weighted” MRT calculation
method is the average of the temperature of the surface
specified in this field and the “zone averaged” MRT (see the
Mean Radiant Temperature calculation type field above).
Field: Work
Efficiency Schedule Name[LINK]
This field is the name of the schedule that determines the
efficiency of energy usage within the human body that will be
used for thermal comfort calculations. Note that all energy
produced by the body is assumed to be converted to heat for
the zone heat balance calculation. A value of zero corresponds
to all of the energy produced in the body being converted to
heat. A value of unity corresponds to all of the energy
produced in the body being converted to mechanical energy. The
values for this parameter defined in the schedule must be
between 0.0 and 1.0. Any value greater than zero will result
in a reduction of heat that impacts the thermal comfort energy
balance of a person within the space.
Field:
Clothing Insulation Schedule Name[LINK]
This field is the name of the schedule that defines the
amount of clothing being worn by a typical zone occupant
during various times in the simulation period. This parameter
must be a positive real number and has units of Clo. Typical
values for Clo can be seen in the ASHRAE 2009 HOF Table 7,
page 9.8 (for clothing ensembles) and Table 8, page 9.9 (for
garment values).
Field: Air Velocity
Schedule Name[LINK]
This field is the name of the schedule that approximates
the amount of air movement in the space as a function of time
throughout the simulation period. The user has control over
this parameter through the schedule that requires the
individual numbers in the schedule to be positive real numbers
having units of meters per second.
Field:
Thermal Comfort Model Type (up to 5 allowed)[LINK]
The final one to five fields are optional and are intended
to trigger various thermal comfort models within EnergyPlus.
By entering the keywords Fanger, Pierce, KSU, AdaptiveASH55,,
and AdaptiveCEN15251, the user can request the Fanger, Pierce
Two-Node, Kansas State UniversityTwo-Node, and the adaptive
comfort models of the ASHRAE Standard 55 and CEN Standard
15251 results for this particular people statement. Note that
since up to five models may be specified, the user may opt to
have EnergyPlus calculate the thermal comfort for people
identified with this people statement using all five models if
desired. Note that the KSU model is computationally intensive
and may noticeably increase the execution time of the
simulation. For descriptions of the thermal comfort
calculations, see the Engineering Reference document.
The following IDF example allows for a maximum of 31 people
with scheduled occupancy of “Office Occupancy”, 60% radiant
using an Activity Schedule of “Activity Sch”. The example
allows for thermal comfort reporting.
People,
Kitchen_ZN_1_FLR_1, !- Name
Kitchen_ZN_1_FLR_1, !- Zone or ZoneList Name
BLDG_OCC_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
25.2000,,, !- Number of People, People per Zone Floor Area, Zone Floor Area per Person
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
3.82E-8 !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
Fanger; !- Thermal Comfort Model 1 Type
A simpler example, without using the thermal comfort
reporting option:
People,
RIGHT FORK, !- Name
RIGHT FORK, !- Zone or ZoneList Name
Dorm Occupancy, !- Number of People Schedule Name
people, !- Number of People Calculation Method
8.00000, !- Number of People,
, !- People per Zone Floor Area
, !- Zone Floor Area per Person
0.6000000, !- Fraction Radiant
Autocalculate, !- Sensible Heat Fraction
Activity Sch, !- Activity level Schedule Name
And with the sensible fraction specified:
People,
SPACE1-1 People 1, !- Name
SPACE1-1, !- Zone or ZoneList Name
OCCUPY-1, !- Number of People Schedule Name
people, !- Number of People Calculation Method
11, !- Number of People
, !- People per Zone Floor Area
, !- Zone Floor Area per Person
0.3, !- Fraction Radiant
0.55, !- Sensible Heat Fraction
ActSchd; !- Activity level Schedule Name
Global People
Object:
ZoneList,AllOccupiedZones,SPACE1-1,SPACE2-1,SPACE3-1,SPACE4-1,SPACE5-1;
People,
AllZones with People, !- Name
AllOccupiedZones, !- Zone or ZoneList Name
OCCUPY-1, !- Number of People Schedule Name
People/Area, !- Number of People Calculation Method
, !- Number of People
.11, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
0.3, !- Fraction Radiant
, !- Sensible Heat Fraction
ActSchd; !- Activity Level Schedule Name
People Outputs[LINK]
People
objects have output variables for individual objects and for
zone totals.
People
specific outputs include:
Zone,Average,People Occupant Count []
Zone,Sum,People Radiant Heating Energy [J]
Zone,Average,People Radiant Heating Rate [W]
Zone,Sum,People Convective Heating Energy [J]
Zone,Average,People Convective Heating Rate [W]
Zone,Sum,People Sensible Heating Energy [J]
Zone,Average,People Sensible Heating Rate [W]
Zone,Sum,People Latent Gain Energy [J]
Zone,Average,People Latent Gain Rate [W]
Zone,Sum,People Total Heating Energy [J]
Zone,Average,People Total Heating Rate [W]
Zone,Average,Zone People Occupant Count []
Zone,Sum,Zone People Radiant Heating Energy [J]
Zone,Average,Zone People Radiant Heating Rate [W]
Zone,Sum,Zone People Convective Heating Energy [J]
Zone,Average,Zone People Convective Heating Rate [W]
Zone,Sum,Zone People Sensible Heating Energy [J]
Zone,Average,Zone People Sensible Heating Rate [W]
Zone,Sum,Zone People Latent Gain Energy [J]
Zone,Average,Zone People Latent Gain Rate [W]
Zone,Sum,Zone People Total Heating Energy [J]
Zone,Average,People Air Temperature [C]
Zone,Average,People Air Relative Humidity [%]
Zone,Average,Zone People Total Heating Rate [W]
Zone,Average,Zone Thermal Comfort Mean Radiant Temperature [C]
Zone,Average,Zone Thermal Comfort Operative Temperature [C]
Zone,Average,Zone Thermal Comfort Fanger Model PMV []
Zone,Average,Zone Thermal Comfort Fanger Model PPD [%]
Zone,Average,Zone Thermal Comfort Clothing Surface Temperature [C]
Zone,Average,Zone Thermal Comfort Pierce Model Effective Temperature PMV []
Zone,Average,Zone Thermal Comfort Pierce Model Standard Effective Temperature PMV []
Zone,Average,Zone Thermal Comfort Pierce Model Discomfort Index []
Zone,Average,Zone Thermal Comfort Pierce Model Thermal Sensation Index []
Zone,Average,Zone Thermal Comfort KSU Model Thermal Sensation Index []
Zone,Average,Zone Thermal Comfort ASHRAE 55 Adaptive Model 80% Acceptability Status []
Zone,Average,Zone Thermal Comfort ASHRAE 55 Adaptive Model 90% Acceptability Status []
Zone,Average,Zone Thermal Comfort ASHRAE 55 Adaptive Model Running Average Outdoor Air Temperature [C]
Zone,Average,Zone Thermal Comfort ASHRAE 55 Adaptive Model Temperature [C]
Zone,Average,Zone Thermal Comfort CEN 15251 Adaptive Model Category I Status []
Zone,Average,Zone Thermal Comfort CEN 15251 Adaptive Model Category II Status []
Zone,Average,Zone Thermal Comfort CEN 15251 Adaptive Model Category III Status
Zone,Average,Zone Thermal Comfort CEN 15251 Adaptive Model Running Average Outdoor Air Temperature [C]
Zone,Average,Zone Thermal Comfort CEN 15251 Adaptive Model Temperature [C]
People Occupant Count [][LINK]
This field is the number of people for this PEOPLE object
during the timestep in question.
People Radiant Heating
Rate [W][LINK]
People Radiant
Heating Energy [J][LINK]
These output variables are the amount of radiant heat gain
for this People
object in Watts (for rate) or Joules. This is determined by
the current sensible heat gain from people to the zone and the
“Fraction Radiant” specified in the input. The radiant gains
from people are distributed to the surfaces using an area
weighting scheme.
People Convective
Heating Rate [W][LINK]
People Convective
Heating Energy [J][LINK]
These output variables are the amount of convective heat
gain for this People
object in Watts (for rate) or Joules. This is determined by
the current sensible heat gain from people to the zone and the
“Fraction Radiant” specified in input. Note that the radiant
and convective gains should add up to the sensible heat gain
from people. The convective heat gain from people is added to
the zone air heat balance directly.
People Latent Gain Rate
[W][LINK]
People Latent Gain Energy
[J][LINK]
These output variables are the amount of latent heat gain
for this People
object in Watts (for rate) or Joules. This amount is based on
the number of people in the space as well as the total amount
of energy produced by a typical person defined by the activity
schedule in the input. An internal algorithm is used to
determine what fraction of the total is sensible and what
fraction is latent. Details about this split are included in
the Engineering Reference document.
People Sensible
Heating Rate [W][LINK]
People Sensible
Heating Energy [J][LINK]
These output variables are the amount of sensible heat gain
for this People
object in Watts (for rate) or Joules. This amount is based on
the number of people in the space as well as the total amount
of energy produced by a typical person defined by the activity
schedule in the input. An internal algorithm (described in the
Engineering Reference document) is used to determine what
fraction of the total is sensible and what fraction is latent.
The sensible plus the latent heat gain from people equals the
total gain specified in the input.
People Total Heating Rate
[W][LINK]
People Total Heating
Energy [J][LINK]
These output variables are the total amount of heat gain
for this People
object in Watts (for rate) or Joules. This is derived from the
activity level times the number of occupants.
People Air Temperature
[C][LINK]
This output variable represents the zone air temperature
based on the Fanger thermal comfort model. If there is a
ZoneControl:Thermostat:ThermalComfort](page-037.html#zonecontrolthermostatthermalcomfort)
object specified and the thermal zone is occupied, then the
value of “[People Air Temperature” is determined based on the
thermal comfort hat satisfies the thermal comfort setpoint PMV
value specified; othwesie, it is set to average zone air
temperature.
People Air Relative
Humidity [%][LINK]
This output variable represents the zone air relative
humidity based on the Fanger thermal comfort model. If there
is a
ZoneControl:Thermostat:ThermalComfort](page-037.html#zonecontrolthermostatthermalcomfort)
object specified and the thermal zone is occupied, then the
value of “[People Air Relative Humidity” is determined from
the mean zone air temperature and zone air humidity ratio that
satisfies the thermal comfort setpoint PMV value specified;
othwesie, it is calculated from the zone air temperature and
humidity ratio averaged over the time step.
Zone People Occupant Count
[][LINK]
This field is the total number of people within the zone
during the timestep in question.
Zone People
Radiant Heating Rate [W][LINK]
Zone People
Radiant Heating Energy [J][LINK]
These output variables are the amount of radiant heat gain
from people within the zone in Watts (for rate) or Joules.
This is determined by the current sensible heat gain from
people to the zone and the “Fraction Radiant” specified in the
input. The radiant gains from people are distributed to the
surfaces using an area weighting scheme.
Zone People
Convective Heating Rate [W][LINK]
Zone People
Convective Heating Energy [J][LINK]
These output variables are the amount of convective heat
gain from people within the zone in Watts (for rate) or
Joules. This is determined by the current sensible heat gain
from people to the zone and the “Fraction Radiant” specified
in input. Note that the radiant and convective gains should
add up to the sensible heat gain from people. The convective
heat gain from people is added to the zone air heat balance
directly.
Zone People Latent
Gain Rate [W][LINK]
Zone People Latent
Gain Energy [J][LINK]
These output variables are the amount of latent heat gain
from people within the zone in Watts (for rate) or Joules.
This amount is based on the number of people in the space as
well as the total amount of energy produced by a typical
person defined by the activity schedule in the input. An
internal algorithm is used to determine what fraction of the
total is sensible and what fraction is latent. Details about
this split are included in the Engineering Reference
document.
Zone People
Sensible Heating Rate [W][LINK]
Zone People
Sensible Heating Energy [J][LINK]
These output variables are the amount of sensible heat gain
from people within the zone in Watts (for rate) or Joules.
This amount is based on the number of people in the space as
well as the total amount of energy produced by a typical
person defined by the activity schedule in the input. An
internal algorithm (described in the Engineering Reference
document) is used to determine what fraction of the total is
sensible and what fraction is latent. The sensible plus the
latent heat gain from people equals the total gain specified
in the input.
Zone People Total
Heating Rate [W][LINK]
Zone People Total
Heating Energy [J][LINK]
These output variables are the total amount of heat gain
from people within the zone in Watts (for rate) or Joules.
Derived from the activity level times the number of occupants,
this is summed for each people object within a zone.
Zone
Thermal Comfort Mean Radiant Temperature [C][LINK]
This output variable is the mean radiant temperature used
in the thermal comfort calculations. This value is computed
according to the “MRT Calculation Type” specified in the
PEOPLE object. If a high temperature radiant system is present
in the zone, this value will be adjusted according to the
current heater operation and the “Fraction of radiant energy
incident on people” specified in the HIGH TEMP RADIANT SYSTEM
object.
Zone
Thermal Comfort Operative Temperature [C][LINK]
This output variable is the operative temperature as
defined by the thermal comfort operations. Specifically, it is
the average of the thermal comfort mean radiant temperature
and the zone air temperature.
Note for all Thermal Comfort reporting: Though the
published values for thermal comfort “vote” have a discrete
scale (e.g. –3 to +3 or –4 to +4), the calculations in
EnergyPlus are carried out on a continuous scale and, thus,
reporting may be “off the scale” with specific conditions
encountered in the space. This is not necessarily an error in
EnergyPlus – rather a different approach that does not take
the “limits” of the discrete scale values into account.
Zone Thermal
Comfort Fanger Model PMV [][LINK]
This field is the “predicted mean vote” (PMV) calculated
using the Fanger thermal comfort model.
Zone Thermal
Comfort Fanger Model PPD [%][LINK]
This field is the “predicted percentage of dissatisfied”
(PPD) calculated using the Fanger thermal comfort model.
Zone
Thermal Comfort Clothing Surface Temperature [C][LINK]
This output variable is the calculation of the clothing
surface temperature using the Fanger thermal comfort
model.
Zone
Thermal Comfort Pierce Model Effective Temperature PMV [][LINK]
This field is the “predicted mean vote” (PMV) calculated
using the effective temperature and the Pierce two-node
thermal comfort model.
Zone
Thermal Comfort Pierce Model Standard Effective Temperature
PMV [][LINK]
This field is the “predicted mean vote” (PMV) calculated
using the “standard” effective temperature and the Pierce
two-node thermal comfort model.
Zone
Thermal Comfort Pierce Model Discomfort Index [][LINK]
This field is the “discomfort index” calculated using the
the Pierce two-node thermal comfort model.
Zone
Thermal Comfort Pierce Model Thermal Sensation Index [][LINK]
This field is the “thermal sensation index” (PMV)
calculated using the Pierce two-node thermal comfort
model.
Zone
Thermal Comfort KSU Model Thermal Sensation Vote [][LINK]
This field is the “thermal sensation vote” (TSV) calculated
using the KSU two-node thermal comfort model.
Zone
Thermal Comfort ASHRAE 55 Adaptive Model 90% Acceptability
Status [][LINK]
This field is to report whether the operative temperature
falls into the 90% acceptability limits of the adaptive
comfort in ASHRAE 55-2010. A value of 1 means within
(inclusive) the limits, a value of 0 means outside the limits,
and a value of -1 means not applicable.
Zone
Thermal Comfort ASHRAE 55 Adaptive Model 80% Acceptability
Status [ ][LINK]
This field is to report whether the operative temperature
falls into the 80% acceptability limits of the adaptive
comfort in ASHRAE 55-2010. A value of 1 means within
(inclusive) the limits, a value of 0 means outside the limits,
and a value of -1 means not applicable.
Zone
Thermal Comfort ASHRAE 55 Adaptive Model Running Average
Outdoor Air Temperature [C][LINK]
This field reports the mean monthly outdoor air
temperature, an input parameter for the ASHRAE-55 adaptive
comfort model. This can be computed in two ways. If the .stat
file is provided for the simulation, this field will reflect
the monthly daily average temperature.
If the .epw file is used, the field reports the simple
running average of the daily average outdoor dry-bulb
temperatures of the previous 30 days.
Zone
Thermal Comfort ASHRAE 55 Adaptive Model Temperature [C][LINK]
This field reports the ideal indoor operative temperature,
or comfort temperature, as determined by the ASHRAE-55
adaptive comfort model. The 80% acceptability limits for
indoor operative temperature are defined as no greater than
2.5 degrees C from the adaptive comfort temperature. The 90%
acceptability limits are defined as no greater than 3.5
degrees C from the adaptive comfort temperature.
Zone
Thermal Comfort CEN 15251 Adaptive Model Category I
Status[LINK]
This field is to report whether the operative temperature
falls into the Category I (90% acceptability) limits of the
adaptive comfort in the European Standard EN15251-2007. A
value of 1 means within (inclusive) the limits, a value of 0
means outside the limits, and a value of -1 means not
applicable.
Zone
Thermal Comfort CEN 15251 Adaptive Model Category II
Status[LINK]
This field is to report whether the operative temperature
falls into the Category II (80% acceptability) limits of the
adaptive comfort in the European Standard EN15251-2007. A
value of 1 means within (inclusive) the limits, a value of 0
means outside the limits, and a value of -1 means not
applicable.
Zone
Thermal Comfort CEN 15251 Adaptive Model Category III
Status[LINK]
This field is to report whether the operative temperature
falls into the Category III (65% acceptability) limits of the
adaptive comfort in the European Standard EN15251-2007. A
value of 1 means within (inclusive) the limits, a value of 0
means outside the limits, and a value of -1 means not
applicable.
Zone
Thermal Comfort CEN 15251 Adaptive Model Running Average
Outdoor Air Temperature[LINK]
This field reports the weighted average of the outdoor air
temperature of the previous five days, an input parameter for
the CEN-15251 adaptive comfort model.
Zone
Thermal Comfort CEN 15251 Adaptive Model Temperature[LINK]
This field reports the ideal indoor operative temperature,
or comfort temperature, as determined by the CEN-15251
adaptive comfort model. Category I, II, and II limits for
indoor operative temperature are defined as no greater than 2,
3, and 4 degrees C from this value respectively.
The following output variables are all based on whether the
humidity ratio and the operative temperature is within the
region shown in ASHRAE Standard 55-2004 in Figure 5.2.1.1. For
these outputs the operative temperature is simplified to be
the average of the air temperature and the mean radiant
temperature. For summer, the 0.5 Clo level is used and, for
winter, the 1.0 Clo level is used. The graphs below are based
on the following tables which extend the ASHRAE values to zero
humidity ratio.
Winter Clothes (1.0 Clo)
| Operative Temperature (C) |
Humidity Ratio
(kgWater/kgDryAir) |
| 19.6 |
0.012 |
| 23.9 |
0.012 |
| 26.3 |
0.000 |
| 21.7 |
0.000 |
Summer Clothes (0.5 Clo)
| Operative Temperature (C) |
Humidity Ratio
(kgWater/kgDryAir) |
| 23.6 |
0.012 |
| 26.8 |
0.012 |
| 28.3 |
0.000 |
| 25.1 |
0.000 |
Zone
Thermal Comfort ASHRAE 55 Simple Model Summer Clothes Not
Comfortable Time[hr][LINK]
The time when the zone is occupied that the combination of
humidity ratio and operative temperature is not in the ASHRAE
55-2004 summer clothes region (see above)
Zone
Thermal Comfort ASHRAE 55 Simple Model Winter Clothes Not
Comfortable Time[hr][LINK]
The time when the zone is occupied that the combination of
humidity ratio and operative temperature is not in the ASHRAE
55-2004 winter clothes region (see above)
Zone
Thermal Comfort ASHRAE 55 Simple Model Summer or Winter
Clothes Not Comfortable Time[hr][LINK]
The time when the zone is occupied that the combination of
humidity ratio and operative temperature is not in the ASHRAE
55-2004 summer or winter clothes region (see above)
Facility
Thermal Comfort ASHRAE 55 Simple Model Summer Clothes Not
Comfortable Time[hr][LINK]
The time when any zone is occupied that the combination of
humidity ratio and operative temperature is not in the ASHRAE
55-2004 summer clothes region (see above)
Facility
Thermal Comfort ASHRAE 55 Simple Model Winter Clothes Not
Comfortable Time [hr][LINK]
The time when any zone is occupied that the combination of
humidity ratio and operative temperature is not in the ASHRAE
55-2004 winter clothes region (see above)
Facility
Thermal Comfort ASHRAE 55 Simple Model Summer Clothes Not
Comfortable Time [hr][LINK]
The time when any zone is occupied that the combination of
humidity ratio and operative temperature is not in the ASHRAE
55-2004 summer or winter clothes region (see above)
Simplified ASHRAE 55
Warnings[LINK]
The simplified ASHRAE 55 calculations may be computed for
occupied zones and, possibly, warnings are shown on the .err
file at the end of each simulated environment. To enable this
option set the “Enable ASHRAE 55 comfort warnings” field of
the People
object to Yes. These warnings will not be generated by
default.
If you enable the warnings, the simplified ASHRAE 55
calculations are done for occupied zones and, possibly,
warnings are shown on the .err file at the end of each
simulated environment.
** Warning ** More than 4% of time (350.4 hours) uncomfortable in zone ZSF1
** ~~~ ** 553.0 hours were uncomfortable based on ASHRAE 55-2004 graph (Section 5.2.1.1)
** ~~~ ** During Environment [10/01 - 09/30]: CHICAGO IL USA TMY2-94846 WMO#=725300
** Warning ** More than 4% of time (350.4 hours) uncomfortable in zone ZNF1
** ~~~ ** 827.8 hours were uncomfortable based on ASHRAE 55-2004 graph (Section 5.2.1.1)
** ~~~ ** During Environment [10/01 - 09/30]: CHICAGO IL USA TMY2-94846 WMO#=725300
** Warning ** More than 4% of time (350.4 hours) uncomfortable in zone ZSF2
** ~~~ ** 593.5 hours were uncomfortable based on ASHRAE 55-2004 graph (Section 5.2.1.1)
** ~~~ ** During Environment [10/01 - 09/30]: CHICAGO IL USA TMY2-94846 WMO#=725300
** Warning ** More than 4% of time (350.4 hours) uncomfortable in zone ZNF2
** ~~~ ** 875.8 hours were uncomfortable based on ASHRAE 55-2004 graph (Section 5.2.1.1)
** ~~~ ** During Environment [10/01 - 09/30]: CHICAGO IL USA TMY2-94846 WMO#=725300
You may decide if you need to change parameters to reduce
these “uncomfortable” hours. The individual output variables
shown previously may help you get more details on when these
are occurring.
Following are some suggestions that might be
applicable:
- Eliminate occupancy when conditioning equipment is
off.
- Note that the ASHRAE graph lower limit is (19.6C to 21.7C)
– heating setpoints may need to be nearer 22.2C (72F) than
21.1C (70F).
- Unoccupied heating setpoint should be nearer 16.7C (62F)
rather than 12.8C (55F) to reduce the start up recovery.
- Start the occupied setpoint schedule, fan availability
schedule, cooling pump availability schedule, reheat coil
availability, one hour before occupancy. Seasonal turn on and
off of equipment may cause more warnings (but potentially more
energy consumption).
- Unoccupied cooling setpoint should be nearer 29.4C (85F)
rather than 40.0 (104F) to reduce the start up recovery.
ComfortViewFactorAngles[LINK]
When requesting EnergyPlus to do a thermal comfort
calculation, the program user has three options for defining
how the mean radiant temperature will be calculated. The user
may select “zoneaveraged” which results in a mean radiant
temperature that is characteristic of an “average” location
near the center of the zone. The user may also elect to place
the person near a particular surface by selecting
“surfaceweighted” in the People
statement. This takes the average of the zone mean radiant
temperature and the temperature of the surface that the person
is near and uses this value as the mean radiant temperature
when calculating thermal comfort.
The third option is for the user to more explicitly
position the person within the space by defining the angle
factors from the person to the various surfaces in the zone.
This option requires the user to list the surfaces that the
person can see from a radiation standpoint and also define the
angle (or view) factor for each surface. The AngleFactorList
input line is intended to give the user this opportunity.
This field is an unique user assigned name for the list of
surfaces that can be seen radiantly by the person for whom
thermal comfort is to be evaluated. Any reference to this list
by a People
statement will use this name.
Field: Zone Name[LINK]
[Zone](../input-output-reference/page-011.html#zone)
Name for this surface list. Each of the surfaces listed must
be in this zone.
Field: Surface <#> Name[LINK]
This field is the name of a surface in the zone seen by the
person.
Field: Angle Factor <#>[LINK]
This field is the fraction that this surface contributes to
the total mean radiant temperature. This can be thought of as
a weighting factor for this surface and the actual mean
radiant temperature used in the thermal comfort model is
simply the sum of all angle factors multiplied by the
corresponding inside surface temperature. Note that the
Surface Name/Angle Factor pair can be repeated up to 20 times.
The sum of all angle factors within any angle factor list must
equal unity, otherwise the program will not accept the input
as valid.
An example IDF with an electric low temperature radiant
system is shown below.
ComfortViewFactorAngles,
South Zone Angle Factors, !- name of angle factor list
Sourth Zone, !- Zone Name
Zn001:Flr001, !- Surface name 1
0.75, !- Angle factor for surface 1
Zn001:Wall001, !- Surface name 2
0.15, !- Angle factor for surface 2
Zn001:Roof001, !- Surface name 3
0.10; !- Angle factor for surface 3
The Lights
statement allows you to specify information about a zone’s
electric lighting system, including design power level and
operation schedule, and how the heat from lights is
distributed thermally.
A zone may have multiple Lights
statements. For example, one statement may describe the
general lighting in the zone and another the task lighting. Or
you can use multiple Lights
statements for a zone that has two or more general lighting
systems that differ in design level, schedule, etc.
The name of the Lights
object.
Field: Zone or ZoneList
Name[LINK]
The field is the name of the thermal zone (ref:
Zone](page-011.html#zone)) or [ZoneList](../input-output-reference/page-011.html#zonelist)
(ref: ZoneLIst) and links this [Lights statement to a thermal
zone or set of thermal zones in the buidling. When the [ZoneList](../input-output-reference/page-011.html#zonelist)
option is used then this lights definition is applied to each
of the zones in the zone list effecting a global definition
for the amount of light wattage in the zone. The Zonelist
option can be used effectively with the watts/area and
watts/person options of the Design Level Calculation
Method.
The name of the actual lights object becomes
<Zone](page-011.html#zone) Name> <[Lights Object
Name> and should be less than the standard length (100
characters) for a name field. If it is greater than this
standard length, it may be difficult to specify in output
reporting as it will be truncated. A warning will be shown if
the generated name is greater than 100 characters. If it
duplicates another such concatenated name, there will be a
severe error and terminate the run.
Field: Schedule Name[LINK]
The name of the schedule that modifies the lighting power
design level (see Design Level Calculation Method field and
related subsequent fields). The schedule values can be any
positive number. The electrical input for lighting in a
particular timestep is the product of the design level and the
value of this schedule in that timestep. If the design level
is the maximum lighting power input the schedule should
contain values between 0.0 and 1.0.
Field: Design
Level Calculation Method[LINK]
This field is a key/choice field that tells which of the
next three fields are filled and is descriptive of the method
for calculating the nominal lighting level in the [Zone](../input-output-reference/page-011.html#zone).
The key/choices are:
- LightingLevel
- With this choice, the method used will be a straight
insertion of the lighting level (Watts) for the Zone. (The Lighting Level field
should be filled.)
- Watts/Area
- With this choice, the method used will be a factor per
floor area of the zone. (The Watts per Zone Floor Area field should be
filled).
- Watts/Person
- With this choice, the method used will be a factor of
lighting level (watts) per person. (The Watts per person field
should be filled).
Field: Lighting Level[LINK]
This is typically the maximum electrical power input (in
Watts) to lighting in a zone, including ballasts, if present.
This value is multiplied by a schedule fraction (see previous
field) to get the lighting power in a particular timestep. In
EnergyPlus, this is slightly more flexible in that the
lighting design level could be a “diversity factor” applied to
a schedule of real numbers.
Field: Watts per Zone
Floor Area[LINK]
This factor (watts/m2) is used, along with the
[Zone](../input-output-reference/page-011.html#zone)
Floor Area to determine the maximum lighting level as
described in the Lighting Level field. The choice from the
method field should be “watts/area”.
Field: Watts per Person[LINK]
This factor (watts/person) is used, along with the number
of occupants (people) to determine the maximum lighting level
as described in the Lighting Level field. The choice from the
method field should be “watts/person”.
Heat Gains from Lights:[LINK]
The electrical input to lighting ultimately appears as heat
that contributes to zone loads or to return air heat gains. In
EnergyPlus this heat is divided into four different fractions.
Three of these are given by the input fields Return Air
Fraction, Fraction Radiant and Fraction Visible. A fourth,
defined as the fraction of the heat from lights convected to
the zone air, is calculated by the program as:
fconvected = 1.0 – (Return Air Fraction +
Fraction Radiant + Fraction Visible)
You will get an error message if Return Air Fraction +
Fraction Radiant + Fraction Visible exceeds 1.0.
These fractions depend on the type of lamp and luminaire,
whether the luminaire is vented to the return air, etc.
Field: Return Air
Fraction[LINK]
The fraction of the heat from lights that goes into the
zone return air (i.e., into the zone outlet node). If the
return air flow is zero or the zone has no return air system,
the program will put this fraction into the zone air. Return
Air Fraction should be non-zero only for luminaires that are
return-air ducted (see Table 14 and Figure 43). (However, see
the field “Return Air Fraction Is Calculated from Plenum
Temperature,” below, for an approach to modeling the case
where Return Air Fraction is caused by conduction
between a luminaire that is in contact with a return-air
plenum.)
Field: Fraction Radiant[LINK]
The fraction of heat from lights that goes into the zone as
long-wave (thermal) radiation. The program calculates how much
of this radiation is absorbed by the inside surfaces of the
zone according the area times thermal absorptance product of
these surfaces.
Field: Fraction Visible[LINK]
The fraction of heat from lights that goes into the zone as
visible (short-wave) radiation. The program calculates how
much of this radiation is absorbed by the inside surfaces of
the zone according the area times solar absorptance product of
these surfaces.
Approximate values of Return Air Fraction, Fraction Radiant
and Fraction Visible are given in Table 14 for overhead
fluorescent lighting for the luminaire configurations shown in
Figure 43.
Approximate values of Return Air Fraction, Fraction
Radiant and Fraction Visible for overhead fluorescent lighting
for different luminaire configurations. These values assume
that no light heat goes into an adjacent zone. Source:
Lighting Handbook: Reference & Application,
8th Edition, Illuminating Engineering Society of
North America, New York, 1993, p. 355.
| Field Name |
Luminaire Configuration,
Fluorescent Lighting |
| Suspended |
Surfacemount |
| Return Air Fraction |
0.0 |
| Fraction Radiant |
0.42 |
| Fraction Visible |
0.18 |
| fconvected |
0.40 |
Field: Fraction
Replaceable[LINK]
This field defines the daylighting control for the LIGHTS
object.
If Daylighting:Controls
or Daylighting:DELight:Controls
is specified for the zone, this field is used as an on/off
flag for dimming controls. If set to 0.0, the lights are not
dimmed by the daylighting controls. If set to 1.0, the lights
are allowed to be dimmed by the daylighting controls.
Field: End-Use
Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory,
e.g., “Task Lights”, “Hall Lights”, etc. A new meter for
reporting is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly)
and). Subcategories are also reported in the ABUPS table. If
this field is omitted or blank, the lights will be assigned to
the “General” end-use subcategory.
Field:
Return Air Fraction Calculated from Plenum Temperature[LINK]
Accepts values Yes or No (the default). Yes is for advanced
used only. In this case the program will calculate the return
air fraction by assuming that it is due to conduction of some
of the light heat into the zone’s return air plenum and that
the amount of the conduction depends on the plenum air
temperature. A Yes value should only be used for luminaires
that are recessed and non-vented, as shown in Figure 44.
The value you enter for the Return Air Fraction field will
be ignored and you can enter, for fluorescent lighting,
Fraction Radiant = 0.37 and Fraction Visible = 0.18, as
indicated in Table 14.
This feature requires that the coefficients described below
be determined from measurements or detailed calculations since
they are very sensitive to the luminaire type, lamp type,
thermal resistance between fixture and plenum, etc.
If “Return Air Fraction Is Calculated from Plenum
Temperature” = Yes, the return air fraction is calculated
each timestep from the following empirical
correlation:
(Return Air Fraction)calculated = C1
– C2 x Tplenum
where Tplenum is the previous-time-step value of
the return plenum air temperature (C),
and C1 and C2 are the values of the
coefficients entered in the next two fields.
To compensate for the change in the return air fraction
relative to its input value, the program modifies Fraction
Radiant and fconvected by a scale factor such
that
(Return Air Fraction)calculated + (Fraction
Radiant)modified+
(fconvected)modified + (Fraction
Visible)input = 1.0
It is assumed that Fraction Visible is a constant equal to
its input value.
Field:
Return Air Fraction Function of Plenum Temperature Coefficient
1[LINK]
The coefficient C1 in the equation for (Return
Air Fraction)calculated.
Field:
Return Air Fraction Function of Plenum Temperature Coefficient
2[LINK]
The coefficient C2 in the equation for (Return
Air Fraction)calculated. Its units are
1/OC.
An IDF example:
Lights,
RIGHT FORK Lights 1, !- Name
RIGHT FORK, !- Zone Name
Office Lighting, !- SCHEDULE Name
LightingLevel, !- Design Level calculation method
1039.706,,, !- Lighting Level {W}
0.0000000E+00, !- Return Air Fraction
0.4000000, !- Fraction Radiant
0.2000000, !- Fraction Visible
1.0, !- Fraction Replaceable
GeneralLights; !- End-Use Subcategory
Global Lights
Object:
ZoneList,AllOccupiedZones,SPACE1-1,SPACE2-1,SPACE3-1,SPACE4-1,SPACE5-1;
Lights,
AllZones with Lights, !- Name
AllOccupiedZones, !- Zone or ZoneList Name
LIGHTS-1, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
16, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.2, !- Return Air Fraction
0.59, !- Fraction Radiant
0.2, !- Fraction Visible
0, !- Fraction Replaceable
GeneralLights; !- End-Use Subcategory
Lights Report Outputs[LINK]
If daylighting controls are operating in the zone, all of
the Lights
objects with a Fraction Replaceble greater than zero will be
reduced by a multiplicative factor that accounts for how much
the electric lighting is lowered due to daylighting.
Lights
objects have output variables for individual objects and for
zone totals.
Zone,Average,Lights Electric Power [W]
Zone,Sum,Lights Radiant Heat Gain [J]
Zone,Average,Lights Radiant Heating Rate [W]
Zone,Sum,Lights Visible Radiation Heating Energy [J]
Zone,Average,Lights Visible Radiation Heating Rate [W]
Zone,Sum,Lights Convective Heating Energy [J]
Zone,Average,Lights Convective Heating Rate [W]
Zone,Sum,Lights Return Air Heating Energy [J]
Zone,Average,Lights Return Air Heating Rate [W]
Zone,Sum,Lights Total Heating Energy [J]
Zone,Average,Lights Total Heating Rate [W]
Zone,Sum,Lights Electric Energy [J]
Zone,Average,Zone Lights Electric Power [W]
Zone,Sum,Zone Lights Radiant Heating Energy [J]
Zone,Average,Zone Lights Radiant Heating Rate [W]
Zone,Sum,Zone Lights Visible Radiation Heating Energy [J]
Zone,Average,Zone Lights Visible Radiation Heating Rate [W]
Zone,Sum,Zone Lights Convective Heating Energy [J]
Zone,Average,Zone Lights Convective Heating Rate [W]
Zone,Sum,Zone Lights Return Air Heating Energy [J]
Zone,Average,Zone Lights Return Air Heating Rate [W]
Zone,Sum,Zone Lights Total Heating Energy [J]
Zone,Average,Zone Lights Total Heating Rate [W]
Zone,Sum,Zone Lights Electric Energy [J]
Lights Electric Power
[W][LINK]
The electric power input for the lights.
Lights Radiant Heating
Rate [W][LINK]
Lights Radiant
Heating Energy [J][LINK]
The amount of heat gain from lights that is in the form of
long-wave (thermal) radiation entering the zone. This heat is
absorbed by the inside surfaces of the zone according to an
area times long-wave absorptance weighting scheme.
Lights
Visible Radiation Heating Rate [W][LINK]
Lights
Visible Radiation Heating Energy [J][LINK]
The amount of heat gain from lights that is in the form of
visible (short-wave) radiation entering the zone. This heat is
absorbed by the inside surfaces of the zone according to an
area times short-wave absorptance weighting scheme.
Lights Convective
Heating Rate [W][LINK]
Lights Convective
Heating Energy [J][LINK]
The amount of heat gain from lights that is convected to
the zone air.
Lights Return Air
Heating Rate [W][LINK]
Lights Return Air
Heating Energy [J][LINK]
The amount of heat gain from lights that goes into the
zone’s return air (and, therefore, does not directly
contribute to the zone load). If the zone has no return air
system or the zone’s air system is off, this heat will be
added to the zone air.
Lights Total Heating Rate
[W][LINK]
Lights Total Heating
Energy [J][LINK]
The total heat gain from lights. It is the sum of the
following four outputs, i.e., Total Heat Gain = Return Air
Heat Gain + Radiant Heat Gain + Visible Heat Gain + Convective
Heat Gain. It is also equal to the electrical input to the
lights.
Lights Electric Energy
[J][LINK]
The lighting electrical consumption including ballasts, if
present. These will have the same value as Lights
Total Heating Energy (above).
Zone Lights Electric
Power [W][LINK]
The electric power input for all lights in the zone.
Zone Lights
Radiant Heating Rate [W][LINK]
Zone Lights
Radiant Heating Energy [J][LINK]
The amount of heat gain from all lights in the zone that is
in the form of long-wave (thermal) radiation entering the
zone. This heat is absorbed by the inside surfaces of the zone
according to an area times long-wave absorptance weighting
scheme.
Zone
Lights Visible Radiation Heating Rate [W][LINK]
Zone
Lights Visible Radiation Heating Energy [J][LINK]
The amount of heat gain from all lights in the zone that is
in the form of visible (short-wave) radiation entering the
zone. This heat is absorbed by the inside surfaces of the zone
according to an area times short-wave absorptance weighting
scheme.
Zone Lights
Convective Heating Rate [W][LINK]
Zone Lights
Convective Heating Energy [J][LINK]
The amount of heat gain from all lights in the zone that is
convected to the zone air.
Zone Lights
Return Air Heating Rate [W][LINK]
Zone Lights
Return Air Heating Energy [J][LINK]
The amount of heat gain from all lights in the zone that
goes into the zone’s return air (and, therefore, does not
directly contribute to the zone load). If the zone has no
return air system or the zone’s air system is off, this heat
will be added to the zone air.
Zone Lights Total
Heating Rate [W][LINK]
Zone Lights Total
Heating Energy [J][LINK]
The total heat gain from all lights in the zone. It is the
sum of the following four outputs, i.e., Total Heat Gain =
Return Air Heat Gain + Radiant Heat Gain + Visible Heat Gain +
Convective Heat Gain. It is also equal to the electrical input
to the lights.
Zone Lights Electric
Energy [J][LINK]
The lighting electrical consumption for all lights in the
zone including ballasts, if present. This will have the same
value as Zone](page-011.html#zone) [Lights Total Heating
Energy (above). However, this amount is also shown in the
Electricity meters that are associated with the zone:
Electricity:Facility,
Electricity:Building,
Electricity:Zone:.
In addition, depending on use, it will be shown in:
InteriorLights: Electricity and
InteriorLights:Electricity:Zone :.
Meters for Lights
Outputs[LINK]
As described in the Lights
Outputs, values for lights will show up on the following
meters:
Distribution of Lights to Meters
| Meter Name |
Scope |
Lights Specfics |
| Electricity:Facility |
Entire Facility |
All |
| Electricity:Building |
All Zones |
All |
| Electricity:Zone: |
Specific Zone |
All |
| InteriorLights:Electricity |
All Zones |
Lights Use |
| InteriorLights:Electricity:Zone: |
Specific Zone |
Lights Use |
| :InteriorLights:Electricity |
Specific Subcategory |
Lights Use |
ElectricEquipment[LINK]
The name of the ElectricEquipment
object.
Field: Zone or ZoneList
Name[LINK]
This field is the name of the zone (ref: [Zone](../input-output-reference/page-011.html#zone))
or [ZoneList](../input-output-reference/page-011.html#zonelist)
(ref: [ZoneList](../input-output-reference/page-011.html#zonelist))
and attaches a particular electric equipment statement to a
thermal zone or set of thermal zones in the building. When the
[ZoneList](../input-output-reference/page-011.html#zonelist)
option is used then this electric equipment definition is
applied to each of the zones in the zone list effecting a
global definition for the amount of electric wattage in the
zone. The Zonelist option can be used effectively with the
watts/area and watts/person options of the Design Level
Calculation Method.
The name of the actual electric equipment object becomes
<Zone](page-011.html#zone) Name> <[ElectricEquipment
Object Name> and should be less than the standard length
(100 characters) for a name field. If it is greater than this
standard length, it may be difficult to specify in output
reporting as it will be truncated. A warning will be shown if
the generated name is greater than 100 characters. If it
duplicates another such concatenated name, there will be a
severe error and terminate the run.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the
design level parameter for electric equipment (see Design
Level Calculation Method field and related subsequent fields).
The schedule values can be any positive number. The actual
electrical input for equipment in a zone as defined by this
statement is the product of the design level field and the
value of the schedule specified by name in this field.
Field: Design
Level Calculation Method[LINK]
This field is a key/choice field that tells which of the
next three fields are filled and is descriptive of the method
for calculating the nominal electric equipment level in the [Zone](../input-output-reference/page-011.html#zone).
The key/choices are:
- EquipmentLevel
- With this choice, the method used will be a straight
insertion of the electric equipment level (Watts) for the Zone. (The Design Level field
should be filled.)
- Watts/Area
- With this choice, the method used will be a factor per
floor area of the zone. (The Watts per Zone Floor Area field should be
filled).
- Watts/Person
- With this choice, the method used will be a factor of
equipment level (watts) per person. (The Watts per Person
field should be filled).
Field: Design Level[LINK]
This field (in Watts) is typically used to represent the
maximum electrical input to equipment in a zone that is then
multiplied by a schedule fraction (see previous field). In
EnergyPlus, this is slightly more flexible in that the
electric equipment design level could be a “diversity factor”
applied to a schedule of real numbers. Note that while the
schedule value can vary from hour to hour, the design level
field is constant for all simulation environments.
Field: Watts per
Zone Floor Area[LINK]
This factor (watts/m2) is used, along with the
[Zone](../input-output-reference/page-011.html#zone)
Area to determine the maximum equipment level as described in
the Design Level field. The choice from the method field
should be “Watts/Area”.
Field: Watts per Person[LINK]
This factor (watts/person) is used, along with the number
of occupants (people) to determine the maximum equipment level
as described in the Design Level field. The choice from the
method field should be “Watts/Person”.
Heat Gains from
Electric Equipment:[LINK]
The electrical input to the equipment ultimately appears as
heat that contributes to zone loads. In EnergyPlus this heat
is divided into four different fractions. Three of these are
given by the input fields Fraction Latent, Fraction Radiant
and Fraction Lost. A fourth, defined as the fraction of the
heat from electric equipment convected to the zone air, is
calculated by the program as:
fconvected = 1.0 – (Fraction Latent + Fraction
Radiant + Fraction Lost)
You will get an error message if Fraction Latent + Fraction
Radiant + Fraction Lost exceeds 1.0.
Field: Fraction Latent[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of latent heat given off by
electric equipment in a zone. The number specified in this
field will be multiplied by the total energy consumed by
electric equipment to give the amount of latent energy
produced by the electric equipment. This energy affects the
moisture balance within the zone.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of long-wave radiant heat
being given off by electric equipment in a zone. The number
specified in this field will be multiplied by the total energy
consumed by electric equipment to give the amount of long
wavelength radiation gain from electric equipment in a
zone.
Field: Fraction Lost[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of “lost” heat being given off
by electric equipment in a zone. The number specified in this
field will be multiplied by the total energy consumed by
electric equipment to give the amount of heat which is “lost”
and does not impact the zone energy balances. This might
correspond to electrical energy converted to mechanical work
or heat that is vented to the atmosphere.
Field: End-Use
Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory,
e.g., “Computers”, “Copy Machines”, etc. A new meter for
reporting is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly)
object). Subcategories are also reported in the ABUPS table.
If this field is omitted or blank, the equipment will be
assigned to the “General” end-use subcategory.
An IDF example:
ElectricEquipment,
DORM ROOMS AND COMMON AREAS ElecEq 1, !- Name
DORM ROOMS AND COMMON AREAS, !- Zone Name
Residence Equipment, !- SCHEDULE Name
EquipmentLevel, !- Design Level calculation method
9210.921, !- Design Level {W}
, !- Watts per Zone Floor Area {watts/m2}
, !- Watts per Person {watts/person}
0.0000000E+00, !- Fraction Latent
0.3000000, !- Fraction Radiant
0.0000000E+00, !- Fraction Lost
Computers; !- End-use Subcategory
Global ElectricEquipment
example:
ZoneList,AllOccupiedZones,SPACE1-1,SPACE2-1,SPACE3-1,SPACE4-1,SPACE5-1;
ElectricEquipment,
AllZones with Electric Equipment, !- Name
AllOccupiedZones, !- Zone or ZoneList Name
EQUIP-1, !- Schedule Name
Watts/Person, !- Design Level Calculation Method
, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
96, !- Watts per Person {W/person}
0, !- Fraction Latent
0.3, !- Fraction Radiant
0; !- Fraction Lost
The name of the GasEquipment
object.
Field: Zone or ZoneList
Name[LINK]
This field is the name of the thermal zone (ref: [Zone](../input-output-reference/page-011.html#zone))
or [ZoneList](../input-output-reference/page-011.html#zonelist)
(ref: [ZoneList](../input-output-reference/page-011.html#zonelist))
and attaches a particular gas equipment statement to a thermal
zone or set of thermal zones in the building. When the [ZoneList](../input-output-reference/page-011.html#zonelist)
option is used then this gas equipment definition is applied
to each of the zones in the zone list effecting a global
definition for the amount of gas in the zone. The Zonelist
option can be used effectively with the watts/area and
watts/person options of the Design Level Calculation
Method.
The name of the actual gas equipment object becomes
<Zone](page-011.html#zone) Name> <[GasEquipment
Object Name> and should be less than the standard length
(100 characters) for a name field. If it is greater than this
standard length, it may be difficult to specify in output
reporting as it will be truncated. A warning will be shown if
the generated name is greater than 100 characters. If it
duplicates another such concatenated name, there will be a
severe error and terminate the run.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the
design level parameter for gas equipment (see Design Level
Calculation Method field and related subsequent fields). The
schedule values can be any positive number. The actual energy
input for gas equipment in a zone as defined by this statement
is the product of the design level field and the value of the
schedule specified by name in this field.
Field: Design
Level Calculation Method[LINK]
This field is a key/choice field that tells which of the
next three fields are filled and is descriptive of the method
for calculating the nominal gas equipment level in the [Zone](../input-output-reference/page-011.html#zone).
The key/choices are:
- EquipmentLevel
- With this choice, the method used will be a straight
insertion of the gas equipment level (Watts) for the Zone. (The Design Level field
should be filled.)
- Watts/Area or Power/Area
- With this choice, the method used will be a factor per
floor area of the zone. (The Power per Zone Floor Area field should be
filled).
- Watts/Person or Power/Person
- With this choice, the method used will be a factor of
equipment level (watts) per person. (The Power per Person
field should be filled).
Field: Design Level[LINK]
This field (in Watts) is typically used to represent the
maximum energy input to gas equipment in a zone that is then
multiplied by a schedule fraction (see previous field). In
EnergyPlus, this is slightly more flexible in that the gas
equipment design level could be a “diversity factor” applied
to a schedule of real numbers. Note that while the schedule
value can vary from hour to hour, the design level field is
constant for all simulation environments.
Field: Power per Zone
Floor Area[LINK]
This factor (watts/m2) is used, along with the
[Zone](../input-output-reference/page-011.html#zone)
Area to determine the maximum equipment level as described in
the Design Level field. The choice from the method field
should be “Watts/Area” or
“Power/Area”.
Field: Power per Person[LINK]
This factor (watts/person) is used, along with the number
of occupants (people) to determine the maximum equipment level
as described in the Design Level field. The choice from the
method field should be “Watts/Person” or
“Power/Person”.
Heat Gains from Gas
Equipment:[LINK]
The fuel input to the equipment ultimately appears as heat
that contributes to zone loads. In EnergyPlus this heat is
divided into four different fractions. Three of these are
given by the input fields Fraction Latent, Fraction Radiant
and Fraction Lost. A fourth, defined as the fraction of the
heat from gas equipment convected to the zone air, is
calculated by the program as:
fconvected = 1.0 – (Fraction Latent + Fraction
Radiant + Fraction Lost)
You will get an error message if Fraction Latent + Fraction
Radiant + Fraction Lost exceeds 1.0.
Field: Fraction Latent[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of latent heat given off by
gas equipment in a zone. The number specified in this field
will be multiplied by the total energy consumed by gas
equipment to give the amount of latent energy produced by the
gas equipment. This energy affects the moisture balance within
the zone.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of long-wave radiant heat
being given off by gas equipment in a zone. The number
specified in this field will be multiplied by the total energy
consumed by gas equipment to give the amount of long
wavelength radiation gain from gas equipment in a zone.
Field: Fraction Lost[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of “lost” heat being given off
by gas equipment in a zone. The number specified in this field
will be multiplied by the total energy consumed by gas
equipment to give the amount of heat which is “lost” and does
not impact the zone energy balances. This might correspond to
input energy converted to mechanical work or heat that is
vented to the atmosphere.
Field: Carbon
Dioxide Generation Rate[LINK]
This numeric input field specifies carbon dioxide
generation rate with units of m3/s-W. The default value of 0.0
assumes the equipment is fully vented to outdoors. In the
absence of better information, the user might consider using a
value of 3.45E-8 m3/s-W which assumes the equipment is not
vented to outdoors. This value is converted from natural gas
CO2 emission rate at 11.7 lbs CO2 per
therm. The CO2~~emission rate is provided by U.S.
Energy Information Administration, “Frequently Asked Questions
- Environment, Questions About Environmental Emissions”,
http://tonto.eia.doe.gov/ask/environment_faqs.asp#CO2_quantity,
January 2010. The maximum value for this input field is
3.45E-7 m3/s-W.
Field: End-Use
Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory,
e.g., “Cooking”, “Clothes Drying”, etc. A new meter for
reporting is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly)
object). Subcategories are also reported in the ABUPS table.
If this field is omitted or blank, the equipment will be
assigned to the “General” end-use subcategory.
An IDF example:
GasEquipment,
DORM ROOMS AND COMMON AREAS GasEq 1, !- Name
DORM ROOMS AND COMMON AREAS, !- Zone Name
Gas Eq Sch, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
29287.51, !- Design Level {W}
, !- Power per Zone Floor Area {W/m2}
, !- Power per Person {W/Person}
0, !- Fraction Latent
0.3, !- Fraction Radiant
0, !- Fraction Lost
0, !- Carbon Dioxide Generation Rate {m3/s-W}
Cooking; !- End-Use Subcategory
Global Gas Equipment example:
ZoneList,OfficeZones,Left Fork, Middle Fork, Right Fork;
GasEquipment,
Office Zones with Gas Equipment, !- Name
OfficeZones, !- Zone Name
Gas Eq Sch, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
197, !- Power per Zone Floor Area {W/m2}
, !- Power per Person {W/Person}
0.0000000E+00, !- Fraction Latent
0.3000000, !- Fraction Radiant
0.0000000E+00; !- Fraction Lost
HotWaterEquipment[LINK]
The name of the HotWaterEquipment
object.
Field: Zone or ZoneList
Name[LINK]
This field is the name of the thermal zone (ref: [Zone](../input-output-reference/page-011.html#zone))
or [ZoneList](../input-output-reference/page-011.html#zonelist)
(ref: [ZoneList](../input-output-reference/page-011.html#zonelist))
and attaches a particular hot water equipment statement to a
thermal zone or set of thermal zones in the building. When the
[ZoneList](../input-output-reference/page-011.html#zonelist)
option is used then this hot water equipment definition is
applied to each of the zones in the zone list effecting a
global definition for the amount of hot water in the zone. The
Zonelist option can be used effectively with the watts/area
and watts/person options of the Design Level Calculation
Method.
The name of the actual hot water equipment object becomes
<Zone](page-011.html#zone) Name> <[HotWaterEquipment
Object Name> and should be less than the standard length
(100 characters) for a name field. If it is greater than this
standard length, it may be difficult to specify in output
reporting as it will be truncated. A warning will be shown if
the generated name is greater than 100 characters. If it
duplicates another such concatenated name, there will be a
severe error and terminate the run.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the
design level parameter for hot water equipment (see Design
Level Calculation Method field and related subsequent fields).
The schedule values can be any positive number. The actual
energy input for hot water equipment in a zone as defined by
this statement is the product of the design level field and
the value of the schedule specified by name in this field.
Field: Design
Level Calculation Method[LINK]
This field is a key/choice field that tells which of the
next three fields are filled and is descriptive of the method
for calculating the nominal hot water equipment level in the
[Zone](../input-output-reference/page-011.html#zone).
The key/choices are:
- EquipmentLevel
- With this choice, the method used will be a straight
insertion of the hot water equipment level (Watts) for the Zone. (The Design Level field
should be filled.)
- Watts/Area or Power/Area
- With this choice, the method used will be a factor per
floor area of the zone. (The Power per Zone Floor Area field should be
filled).
- Watts/Person or Power/Person
- With this choice, the method used will be a factor of
equipment level (watts) per person. (The Power per Person
field should be filled).
Field: Design Level[LINK]
This field (in Watts) is typically used to represent the
maximum energy input to hot water equipment in a zone that is
then multiplied by a schedule fraction (see previous field).
In EnergyPlus, this is slightly more flexible in that the hot
water equipment design level could be a “diversity factor”
applied to a schedule of real numbers. Note that while the
schedule value can vary from hour to hour, the design level
field is constant for all simulation environments.
Field: Power per
Zone Floor Area[LINK]
This factor (watts/m2) is used, along with the
[Zone](../input-output-reference/page-011.html#zone)
Area to determine the maximum equipment level as described in
the Design Level field. The choice from the method field
should be “Watts/Area” or
“Power/Area”.
Field: Power per Person[LINK]
This factor (watts/person) is used, along with the number
of occupants (people) to determine the maximum equipment level
as described in the Design Level field. The choice from the
method field should be “Watts/Person” or
“Power/Person”.
Heat Gains from
Hot Water Equipment:[LINK]
The fuel input to the equipment ultimately appears as heat
that contributes to zone loads. In EnergyPlus this heat is
divided into four different fractions. Three of these are
given by the input fields Fraction Latent, Fraction Radiant
and Fraction Lost. A fourth, defined as the fraction of the
heat from hot water equipment convected to the zone air, is
calculated by the program as:
fconvected = 1.0 – (Fraction Latent + Fraction
Radiant + Fraction Lost)
You will get an error message if Fraction Latent + Fraction
Radiant + Fraction Lost exceeds 1.0.
Field: Fraction Latent[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of latent heat given off by
hot water equipment in a zone. The number specified in this
field will be multiplied by the total energy consumed by hot
water equipment to give the amount of latent energy produced
by the hot water equipment. This energy affects the moisture
balance within the zone.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of long-wave radiant heat
being given off by hot water equipment in a zone. The number
specified in this field will be multiplied by the total energy
consumed by hot water equipment to give the amount of long
wavelength radiation gain from hot water equipment in a
zone.
Field: Fraction Lost[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of “lost” heat being given off
by hot water equipment in a zone. The number specified in this
field will be multiplied by the total energy consumed by hot
water equipment to give the amount of heat which is “lost” and
does not impact the zone energy balances. This might
correspond to input energy converted to mechanical work or
heat that is vented to the atmosphere.
Field: End-Use
Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory,
e.g., “Cooking”, “Clothes Drying”, etc. A new meter for
reporting is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly)
obejct). Subcategories are also reported in the ABUPS table.
If this field is omitted or blank, the equipment will be
assigned to the “General” end-use subcategory.
IDF Examples:
HotWaterEquipment,
SPACE2-1 HWEq 1, !- Name
SPACE2-1, !- Zone Name
EQUIP-1, !- SCHEDULE Name
EquipmentLevel, !- Design Level calculation method
300, !- Design Level {W}
, !- Power per Zone Floor Area {watts/m2}
, !- Power per Person {watts/person}
0.2, !- Fraction Latent
0.1, !- Fraction Radiant
0.5, !- Fraction Lost
Dishwashing; !- End-Use Subcategory
Global Hot Water Equipment example:
ZoneList,OfficeZones,Left Fork, Middle Fork, Right Fork;
HotWaterEquipment,
Office Zones with Hot Water Equipment, !- Name
OfficeZones, !- Zone Name
HotWater Eq Sch, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
50, !- Power per Zone Floor Area {W/m2}
, !- Power per Person {W/Person}
0.0000000E+00, !- Fraction Latent
0.3000000, !- Fraction Radiant
0.0000000E+00; !- Fraction Lost
SteamEquipment[LINK]
The name of the SteamEquipment
object.
Field: Zone Name[LINK]
This field is the name of the thermal zone (ref: [Zone](../input-output-reference/page-011.html#zone))
and attaches a particular steam equipment statement to a
thermal zone or set of thermal zones in the building. When the
[ZoneList](../input-output-reference/page-011.html#zonelist)
option is used then this steam equipment definition is applied
to each of the zones in the zone list effecting a global
definition for the amount of steam in the zone. This option
can be used effectively with the watts/area and watts/person
options of the Design Level Calculation Method.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the
design level parameter for steam equipment (see Design Level
Calculation Method field and related subsequent fields). The
schedule values can be any positive number. The actual energy
input for steam equipment in a zone as defined by this
statement is the product of the design level field and the
value of the schedule specified by name in this field.
Field: Design
Level Calculation Method[LINK]
This field is a key/choice field that tells which of the
next three fields are filled and is descriptive of the method
for calculating the nominal steam equipment level in the [Zone](../input-output-reference/page-011.html#zone).
The key/choices are:
- EquipmentLevel
- With this choice, the method used will be a straight
insertion of the steam equipment level (Watts) for the Zone. (The Design Level field
should be filled.)
- Watts/Area or Power/Area
- With this choice, the method used will be a factor per
floor area of the zone. (The Power per Zone Floor Area field should be
filled).
- Watts/Person or Power/Person
- With this choice, the method used will be a factor of
equipment level (watts) per person. (The Power per Person
field should be filled).
Field: Design Level[LINK]
This field (in Watts) is typically used to represent the
maximum energy input to steam equipment in a zone that is then
multiplied by a schedule fraction (see previous field). In
EnergyPlus, this is slightly more flexible in that the steam
equipment design level could be a “diversity factor” applied
to a schedule of real numbers. Note that while the schedule
value can vary from hour to hour, the design level field is
constant for all simulation environments.
Field: Power per
Zone Floor Area[LINK]
This factor (watts/m2) is used, along with the
[Zone](../input-output-reference/page-011.html#zone)
Area to determine the maximum equipment level as described in
the Design Level field. The choice from the method field
should be “Watts/Area” or
“Power/Area”.
Field: Power per Person[LINK]
This factor (watts/person) is used, along with the number
of occupants (people) to determine the maximum equipment level
as described in the Design Level field. The choice from the
method field should be “Watts/Person” or
“Power/Person”.
Heat Gains from Steam
Equipment:[LINK]
The fuel input to the equipment ultimately appears as heat
that contributes to zone loads. In EnergyPlus this heat is
divided into four different fractions. Three of these are
given by the input fields Fraction Latent, Fraction Radiant
and Fraction Lost. A fourth, defined as the fraction of the
heat from steam equipment convected to the zone air, is
calculated by the program as:
fconvected = 1.0 – (Fraction Latent + Fraction
Radiant + Fraction Lost)
You will get an error message if Fraction Latent + Fraction
Radiant + Fraction Lost exceeds 1.0.
Field: Fraction Latent[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of latent heat given off by
steam equipment in a zone. The number specified in this field
will be multiplied by the total energy consumed by steam
equipment to give the amount of latent energy produced by the
steam equipment. This energy affects the moisture balance
within the zone.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of long-wave radiant heat
being given off by steam equipment in a zone. The number
specified in this field will be multiplied by the total energy
consumed by steam equipment to give the amount of long
wavelength radiation gain from steam equipment in a zone.
Field: Fraction Lost[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of “lost” heat being given off
by steam equipment in a zone. The number specified in this
field will be multiplied by the total energy consumed by steam
equipment to give the amount of heat which is “lost” and does
not impact the zone energy balances. This might correspond to
input energy converted to mechanical work or heat that is
vented to the atmosphere.
Field: End-Use
Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory,
e.g., “Cooking”, “Clothes Drying”, etc. A new meter for
reporting is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly)
object). Subcategories are also reported in the ABUPS table.
If this field is omitted or blank, the equipment will be
assigned to the “General” end-use subcategory.
IDF Examples:
SteamEquipment,
SPACE4-1 ElecEq 1, !- Name
SPACE4-1, !- Zone Name
EQUIP-1, !- SCHEDULE Name
EquipmentLevel, !- Design Level calculation method
1050, !- Design Level {W}
, !- Power per Zone Floor Area {watts/m2}
, !- Power per Person {watts/person}
0.5, !- Fraction Latent
0.3, !- Fraction Radiant
0, !- Fraction Lost
Laundry; !- End-Use Subcategory
OtherEquipment[LINK]
Other Equipment object is provided as an additional source
for heat gains or losses directly to the zone. That is to say,
a loss can be entered by putting a negative value into the
Design Level field(s). Note, too, that this object does not
have an end-use component – gains or losses do not show up in
the bottom energy lines (except as influencing overall zone
gains or losses).
The name of the OtherEquipment
object.
Field: Zone Name[LINK]
This field is the name of the thermal zone (ref: [Zone](../input-output-reference/page-011.html#zone))
and attaches a particular other equipment statement to a
thermal zone or set of thermal zones in the building. When the
[ZoneList](../input-output-reference/page-011.html#zonelist)
option is used then this other equipment definition is applied
to each of the zones in the zone list effecting a global
definition for the amount of other in the zone. This option
can be used effectively with the watts/area and watts/person
options of the Design Level Calculation Method.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the
design level parameter for other equipment (see Design Level
Calculation Method field and related subsequent fields). The
schedule values can be any positive number. The actual energy
input for other equipment in a zone as defined by this
statement is the product of the design level field and the
value of the schedule specified by name in this field.
Field: Design
Level Calculation Method[LINK]
This field is a key/choice field that tells which of the
next three fields are filled and is descriptive of the method
for calculating the nominal other equipment level in the [Zone](../input-output-reference/page-011.html#zone).
The key/choices are:
- EquipmentLevel
- With this choice, the method used will be a straight
insertion of the other equipment level (Watts) for the Zone. (The Design Level field
should be filled.)
- Watts/Area or Power/Area
- With this choice, the method used will be a factor per
floor area of the zone. (The Power per Zone Floor Area field should be
filled).
- Watts/Person or Power/Person
- With this choice, the method used will be a factor of
equipment level (watts) per person. (The Power per Person
field should be filled).
Field: Design Level[LINK]
This field (in Watts) is typically used to represent the
maximum energy input to other equipment in a zone that is then
multiplied by a schedule fraction (see previous field). In
EnergyPlus, this is slightly more flexible in that the other
equipment design level could be a “diversity factor” applied
to a schedule of real numbers. This value can be negative to
denote a loss. Note that while the schedule value can vary
from hour to hour, the design level field is constant for all
simulation environments.
Field: Power per
Zone Floor Area[LINK]
This factor (watts/m2) is used, along with the
[Zone](../input-output-reference/page-011.html#zone)
Area to determine the maximum equipment level as described in
the Design Level field. This value can be negative to denote a
loss. The choice from the method field should be
“Watts/Area” or
“Power/Area”.
Field: Power per Person[LINK]
This factor (watts/person) is used, along with the number
of occupants (people) to determine the maximum equipment level
as described in the Design Level field. This value can be
negative to denote a loss. The choice from the method field
should be “Watts/Person” or
“Power/Person”.
Heat
Gains/Losses from Other Equipment:[LINK]
The fuel input to the equipment ultimately appears as heat
that contributes to zone loads. In EnergyPlus this heat is
divided into four different fractions. Three of these are
given by the input fields Fraction Latent, Fraction Radiant
and Fraction Lost. A fourth, defined as the fraction of the
heat from other equipment convected to the zone air, is
calculated by the program as:
fconvected = 1.0 – (Fraction Latent + Fraction
Radiant + Fraction Lost)
You will get an error message if Fraction Latent + Fraction
Radiant + Fraction Lost exceeds 1.0.
Field: Fraction Latent[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of latent heat given off by
other equipment in a zone. The number specified in this field
will be multiplied by the total energy consumed by other
equipment to give the amount of latent energy produced by the
other equipment. This energy affects the moisture balance
within the zone.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of long-wave radiant heat
being given off by other equipment in a zone. The number
specified in this field will be multiplied by the total energy
consumed by other equipment to give the amount of long
wavelength radiation gain from other equipment in a zone.
Field: Fraction Lost[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the amount of “lost” heat being given off
by other equipment in a zone. The number specified in this
field will be multiplied by the total energy consumed by other
equipment to give the amount of heat which is “lost” and does
not impact the zone energy balances. This might correspond to
input energy converted to mechanical work or heat that is
vented to the atmosphere.
IDF Examples
OtherEquipment,
BASE-1 OthEq 1, !- Name
BASE-1, !- Zone Name
ALWAYSON, !- SCHEDULE Name
EquipmentLevel, !- Design Level calculation method
6766., !- Design Level {W}
, !- Power per Zone Floor Area {watts/m2}
, !- Power per Person {watts/person}
0, !- Fraction Latent
0.3, !- Fraction Radiant
0; !- Fraction Lost
Electric,
Gas, Other, HotWater, Steam Equipment Outputs[LINK]
Each type of equipment object has output variables for
individual objects and for zone totals.
Electric Equipment
Zone,Average,Electric Equipment Electric Power [W]
Zone,Sum,Electric Equipment Electric Energy [J]
Zone,Sum,Electric Equipment Radiant Heating Energy [J]
Zone,Average,Electric Equipment Radiant Heating Rate [W]
Zone,Sum,Electric Equipment Convective Heating Energy [J]
Zone,Average,Electric Equipment Convective Heating Rate [W]
Zone,Sum,Electric Equipment Latent Gain Energy [J]
Zone,Average,Electric Equipment Latent Gain Rate [W]
Zone,Sum,Electric Equipment Lost Heat Energy [J]
Zone,Average,Electric Equipment Lost Heat Rate [W]
Zone,Sum,Electric Equipment Total Heating Energy [J]
Zone,Average,Electric Equipment Total Heating Rate [W]
Zone,Average,Zone Electric Equipment Electric Power [W]
Zone,Sum,Zone Electric Equipment Electric Energy [J]
Zone,Sum,Zone Electric Equipment Radiant Heating Energy [J]
Zone,Average,Zone Electric Equipment Radiant Heating Rate [W]
Zone,Sum,Zone Electric Equipment Convective Heating Energy [J]
Zone,Average,Zone Electric Equipment Convective Heating Rate [W]
Zone,Sum,Zone Electric Equipment Latent Gain Energy [J]
Zone,Average,Zone Electric Equipment Latent Gain Rate [W]
Zone,Sum,Zone Electric Equipment Lost Heat Energy [J]
Zone,Average,Zone Electric Equipment Lost Heat Rate [W]
Zone,Sum,Zone Electric Equipment Total Heating Energy [J]
Zone,Average,Zone Electric Equipment Total Heating Rate [W]
Gas Equipment
Zone,Average,Gas Equipment Gas Rate [W]
Zone,Sum,Gas Equipment Gas Energy [J]
Zone,Sum,Gas Equipment Radiant Heating Energy [J]
Zone,Sum,Gas Equipment Convective Heating Energy [J]
Zone,Sum,Gas Equipment Latent Gain Energy [J]
Zone,Sum,Gas Equipment Lost Heat Energy [J]
Zone,Sum,Gas Equipment Total Heating Energy [J]
Zone,Average,Gas Equipment Radiant Heating Rate [W]
Zone,Average,Gas Equipment Convective Heating Rate [W]
Zone,Average,Gas Equipment Latent Gain Rate [W]
Zone,Average,Gas Equipment Lost Heat Rate [W]
Zone,Average,Gas Equipment Total Heating Rate [W]
Zone,Average,Zone Gas Equipment Gas Rate [W]
Zone,Sum,Zone Gas Equipment Gas Energy [J]
Zone,Sum,Zone Gas Equipment Radiant Heating Energy [J]
Zone,Average,Zone Gas Equipment Radiant Heating Rate [W]
Zone,Sum,Zone Gas Equipment Convective Heating Energy [J]
Zone,Average,Zone Gas Equipment Convective Heating Rate [W]
Zone,Sum,Zone Gas Equipment Latent Gain Energy [J]
Zone,Average,Zone Gas Equipment Latent Gain Rate [W]
Zone,Sum,Zone Gas Equipment Lost Heat Energy [J]
Zone,Average,Zone Gas Equipment Lost Heat Rate [W]
Zone,Sum,Zone Gas Equipment Total Heating Energy [J]
Zone,Average,Zone Gas Equipment Total Heating Rate [W]
HotWater Equipment
Zone,Average,Hot Water Equipment District Heating Rate [W]
Zone,Sum,Hot Water Equipment District Heating Energy [J]
Zone,Sum,Hot Water Equipment Radiant Heating Energy [J]
Zone,Average,Hot Water Equipment Radiant Heating Rate [W]
Zone,Sum,Hot Water Equipment Convective Heating Energy [J]
Zone,Average,Hot Water Equipment Convective Heating Rate [W]
Zone,Sum,Hot Water Equipment Latent Gain Energy [J]
Zone,Average,Hot Water Equipment Latent Gain Rate [W]
Zone,Sum,Hot Water Equipment Lost Heat Energy [J]
Zone,Average,Hot Water Equipment Lost Heat Rate [W]
Zone,Sum,Hot Water Equipment Total Heating Energy [J]
Zone,Average,Hot Water Equipment Total Heating Rate [W]
Zone,Average,Zone Hot Water Equipment District Heating Rate [W]
Zone,Sum,Zone Hot Water Equipment District Heating Energy [J]
Zone,Sum,Zone Hot Water Equipment Radiant Heating Energy [J]
Zone,Average,Zone Hot Water Equipment Radiant Heating Rate [W]
Zone,Sum,Zone Hot Water Equipment Convective Heating Energy [J]
Zone,Average,Zone Hot Water Equipment Convective Heating Rate [W]
Zone,Sum,Zone Hot Water Equipment Latent Gain Energy [J]
Zone,Average,Zone Hot Water Equipment Latent Gain Rate [W]
Zone,Sum,Zone Hot Water Equipment Lost Heat Energy [J]
Zone,Average,Zone Hot Water Equipment Lost Heat Rate [W]
Zone,Sum,Zone Hot Water Equipment Total Heating Energy [J]
Zone,Average,Zone Hot Water Equipment Total Heating Rate [W]
Steam Equipment
Zone,Average,Steam Equipment District Heating Rate [W]
Zone,Sum,Steam Equipment District Heating Energy [J]
Zone,Sum,Steam Equipment Radiant Heating Energy [J]
Zone,Average,Steam Equipment Radiant Heating Rate [W]
Zone,Sum,Steam Equipment Convective Heating Energy [J]
Zone,Average,Steam Equipment Convective Heating Rate [W]
Zone,Sum,Steam Equipment Latent Gain Energy [J]
Zone,Average,Steam Equipment Latent Gain Rate [W]
Zone,Sum,Steam Equipment Lost Heat Energy [J]
Zone,Average,Steam Equipment Lost Heat Rate [W]
Zone,Sum,Steam Equipment Total Heating Energy [J]
Zone,Average,Steam Equipment Total Heating Rate [W]
Zone,Average,Zone Steam Equipment District Heating Rate [W]
Zone,Sum,Zone Steam Equipment District Heating Energy [J]
Zone,Sum,Zone Steam Equipment Radiant Heating Energy [J]
Zone,Average,Zone Steam Equipment Radiant Heating Rate [W]
Zone,Sum,Zone Steam Equipment Convective Heating Energy [J]
Zone,Average,Zone Steam Equipment Convective Heating Rate [W]
Zone,Sum,Zone Steam Equipment Latent Gain Energy [J]
Zone,Average,Zone Steam Equipment Latent Gain Rate [W]
Zone,Sum,Zone Steam Equipment Lost Heat Energy [J]
Zone,Average,Zone Steam Equipment Lost Heat Rate [W]
Zone,Sum,Zone Steam Equipment Total Heating Energy [J]
Zone,Average,Zone Steam Equipment Total Heating Rate [W]
Other Equipment
Zone,Sum,Other Equipment Radiant Heating Energy [J]
Zone,Average,Other Equipment Radiant Heating Rate [W]
Zone,Sum,Other Equipment Convective Heating Energy [J]
Zone,Average,Other Equipment Convective Heating Rate [W]
Zone,Sum,Other Equipment Latent Gain Energy [J]
Zone,Average,Other Equipment Latent Gain Rate [W]
Zone,Sum,Other Equipment Lost Heat Energy [J]
Zone,Average,Other Equipment Lost Heat Rate [W]
Zone,Sum,Other Equipment Total Heating Energy [J]
Zone,Average,Other Equipment Total Heating Rate [W]
Zone,Sum,Zone Other Equipment Radiant Heating Energy [J]
Zone,Average,Zone Other Equipment Radiant Heating Rate [W]
Zone,Sum,Zone Other Equipment Convective Heating Energy [J]
Zone,Average,Zone Other Equipment Convective Heating Rate [W]
Zone,Sum,Zone Other Equipment Latent Gain Energy [J]
Zone,Average,Zone Other Equipment Latent Gain Rate [W]
Zone,Sum,Zone Other Equipment Lost Heat Energy [J]
Zone,Average,Zone Other Equipment Lost Heat Rate [W]
Zone,Sum,Zone Other Equipment Total Heating Energy [J]
Zone,Average,Zone Other Equipment Total Heating Rate [W]
Electric
Equipment Electric Power [W][LINK]
Gas Equipment Gas Rate
[W][LINK]
Hot Water
Equipment District Heating Rate [W][LINK]
Hot
Water Equipment District Heating Energy [J][LINK]
Steam
Equipment District Heating Energy [J][LINK]
Steam
Equipment District Heating Rate [W][LINK]
This field is the energy consumption rate or sum for the
equipment object in Watts or Joules.
Electric
Equipment Radiant Heating Rate [W][LINK]
Electric
Equipment Radiant Heating Energy [J][LINK]
Gas Equipment
Radiant Heating Rate [W][LINK]
Gas Equipment
Radiant Heating Energy [J][LINK]
Hot Water
Equipment Radiant Heating Rate [W][LINK]
Hot
Water Equipment Radiant Heating Energy [J][LINK]
Steam
Equipment Radiant Heating Rate [W][LINK]
Steam
Equipment Radiant Heating Energy [J][LINK]
Other
Equipment Radiant Heating Rate [W][LINK]
Other
Equipment Radiant Heating Energy [J][LINK]
This field is the amount of radiant heat gain for the
equipment object in Watts (for rate) or Joules. This is
determined by the current heat gain from the equipment to the
zone and the “Fraction Radiant” specified in the input. The
radiant gains (long wavelength) are distributed to the
surfaces using an area weighting scheme.
Electric
Equipment Convective Heating Rate [W][LINK]
Electric
Equipment Convective Heating Energy [J][LINK]
Gas Equipment
Convective Heating Rate [W][LINK]
Gas
Equipment Convective Heating Energy [J][LINK]
Hot
Water Equipment Convective Heating Rate [W][LINK]
Hot
Water Equipment Convective Heating Energy [J][LINK]
Steam
Equipment Convective Heating Rate [W][LINK]
Steam
Equipment Convective Heating Energy [J][LINK]
Other
Equipment Convective Heating Rate [W][LINK]
Other
Equipment Convective Heating Energy [J][LINK]
This field is the amount of convective heat gain for the
equipment object in Watts (for rate) or Joules. This is
determined by the current heat gain from the equipment to the
zone and the “Fraction Radiant”, “Fraction Lost”, “Fraction
Latent” specified in input
(1-FractionRadiant-FractionLost-FractionLatent =
FractionConvected). The convective heat gain is added to the
zone air heat balance directly.
Electric
Equipment Latent Gain Rate [W][LINK]
Electric
Equipment Latent Gain Energy [J][LINK]
Gas Equipment Latent
Gain Rate [W][LINK]
Gas Equipment
Latent Gain Energy [J][LINK]
Hot Water
Equipment Latent Gain Rate [W][LINK]
Hot Water
Equipment Latent Gain Energy [J][LINK]
Steam Equipment
Latent Gain Rate [W][LINK]
Steam Equipment
Latent Gain Energy [J][LINK]
Other Equipment
Latent Gain Rate [W][LINK]
Other Equipment
Latent Gain Energy [J][LINK]
This field is the amount of latent heat gain for the
equipment object in Watts (for rate) or Joules. This is
determined by the current heat gain from the equipment to the
zone and the “Fraction Latent” specified in the input.
Electric
Equipment Lost Heat Rate [W][LINK]
Electric
Equipment Lost Heat Energy [J][LINK]
Gas Equipment Lost
Heat Rate [W][LINK]
Gas Equipment Lost
Heat Energy [J][LINK]
Hot Water
Equipment Lost Heat Rate [W][LINK]
Hot Water
Equipment Lost Heat Energy [J][LINK]
Steam Equipment Lost
Heat Rate [W][LINK]
Steam Equipment
Lost Heat Energy [J][LINK]
Other Equipment Lost
Heat Rate [W][LINK]
Other Equipment
Lost Heat Energy [J][LINK]
This field is the amount of “lost” heat gain for the
equipment object in Watts (for rate) or Joules. This is
determined by the current heat gain from the equipment to the
zone and the “Fraction Lost” specified in the input. This
amount does not affect the energy heat balance in the
zone.
Electric
Equipment Total Heating Rate [W][LINK]
Electric
Equipment Total Heating Energy [J][LINK]
Gas Equipment
Total Heating Rate [W][LINK]
Gas Equipment
Total Heating Energy [J][LINK]
Hot Water
Equipment Total Heating Rate [W][LINK]
Hot Water
Equipment Total Heating Energy [J][LINK]
Steam Equipment
Total Heating Rate [W][LINK]
Steam
Equipment Total Heating Energy [J][LINK]
Other Equipment
Total Heating Rate [W][LINK]
Other
Equipment Total Heating Energy [J][LINK]
The total heat gain field is sum of several other fields
(radiant, latent, convective). This field is expressed in
Watts (for rate) or joules.
Electric
Equipment Electric Energy [J][LINK]
The electric equipment consumption field is sum of the
other fields (radiant, latent, convective, lost). This field
is expressed in joules.
Gas Equipment Gas Energy
[J][LINK]
The gas equipment consumption field is sum of the other
fields (radiant, latent, convective, lost). This field is
expressed in joules.
Hot
Water Equipment Purchased Heating Consumption [J][LINK]
Steam
Equipment Purchased Heating Consumption [J][LINK]
The equipment consumption field is sum of the other fields
(radiant, latent, convective, lost). This field is expressed
in joules.
Zone
Electric Equipment Electric Power [W][LINK]
Zone Gas Equipment Gas
Rate [W][LINK]
Zone
Hot Water Equipment District Heating Rate W][LINK]
Zone
Steam Equipment District Heating Rate [W][LINK]
This field is the energy consumption rate for all equipment
within the zone in Watts.
Zone
Electric Equipment Radiant Heating Rate [W][LINK]
Zone
Electric Equipment Radiant Heating Energy [J][LINK]
Zone Gas
Equipment Radiant Heating Rate [W][LINK]
Zone Gas
Equipment Radiant Heating Energy [J][LINK]
Zone
Hot Water Equipment Radiant Heating Rate [W][LINK]
Zone
Hot Water Equipment Radiant Heating Energy [J][LINK]
Zone
Steam Equipment Radiant Heating Rate [W][LINK]
Zone
Steam Equipment Radiant Heating Energy [J][LINK]
Zone
Other Equipment Radiant Heating Rate [W][LINK]
Zone
Other Equipment Radiant Heating Energy [J][LINK]
This field is the amount of radiant heat gain for all
equipment within the zone in Watts (for rate) or Joules. This
is determined by the current heat gain from the equipment to
the zone and the “Fraction Radiant” specified in the input.
The radiant gains (long wavelength) are distributed to the
surfaces using an area weighting scheme.
Zone
Electric Equipment Convective Heating Rate [W][LINK]
Zone
Electric Equipment Convective Heating Energy [J][LINK]
Zone Gas
Equipment Convective Heating Rate [W][LINK]
Zone
Gas Equipment Convective Heating Energy [J][LINK]
Zone
Hot Water Equipment Convective Heating Rate [W][LINK]
Zone
Hot Water Equipment Convective Heating Energy [J][LINK]
Zone
Steam Equipment Convective Heating Rate [W][LINK]
Zone
Steam Equipment Convective Heating Energy [J][LINK]
Zone
Other Equipment Convective Heating Rate [W][LINK]
Zone
Other Equipment Convective Heating Energy [J][LINK]
This field is the amount of convective heat gain for all
equipment within the zone in Watts (for rate) or Joules. This
is determined by the current heat gain from the equipment to
the zone and the “Fraction Radiant”, “Fraction Lost”,
“Fraction Latent” specified in input
(1-FractionRadiant-FractionLost-FractionLatent =
FractionConvected). The convective heat gain is added to the
zone air heat balance directly.
Zone
Electric Equipment Latent Gain Rate [W][LINK]
Zone
Electric Equipment Latent Gain Energy [J][LINK]
Zone Gas
Equipment Latent Gain Rate [W][LINK]
Zone Gas
Equipment Latent Gain Energy [J][LINK]
Zone Hot
Water Equipment Latent Gain Rate [W][LINK]
Zone
Hot Water Equipment Latent Gain Energy [J][LINK]
Zone Steam
Equipment Latent Gain Rate [W][LINK]
Zone Steam
Equipment Latent Gain Energy [J][LINK]
Zone Other
Equipment Latent Gain Rate [W][LINK]
Zone Other
Equipment Latent Gain Energy [J][LINK]
This field is the amount of latent heat gain for all
equipment within the zone in Watts (for rate) or Joules. This
is determined by the current heat gain from the equipment to
the zone and the “Fraction Latent” specified in the input.
Zone
Electric Equipment Lost Heat Rate [W][LINK]
Zone
Electric Equipment Lost Heat Energy [J][LINK]
Zone Gas
Equipment Lost Heat Rate [W][LINK]
Zone Gas
Equipment Lost Heat Energy [J][LINK]
Zone Hot
Water Equipment Lost Heat Rate [W][LINK]
Zone Hot
Water Equipment Lost Heat Energy [J][LINK]
Zone Steam
Equipment Lost Heat Rate [W][LINK]
Zone Steam
Equipment Lost Heat Energy [J][LINK]
Zone Other
Equipment Lost Heat Rate [W][LINK]
Zone Other
Equipment Lost Heat Energy [J][LINK]
This field is the amount of “lost” heat gain for all
equipment within the zone in Watts (for rate) or Joules. This
is determined by the current heat gain from the equipment to
the zone and the “Fraction Lost” specified in the input. This
amount does not affect the energy heat balance in the
zone.
Zone
Electric Equipment Total Heating Rate [W][LINK]
Zone
Electric Equipment Total Heating Energy [J][LINK]
Zone Gas
Equipment Total Heating Rate [W][LINK]
Zone Gas
Equipment Total Heating Energy [J][LINK]
Zone
Hot Water Equipment Total Heating Rate [W][LINK]
Zone
Hot Water Equipment Total Heating Energy [J][LINK]
Zone Steam
Equipment Total Heating Rate [W][LINK]
Zone
Steam Equipment Total Heating Energy [J][LINK]
Zone Other
Equipment Total Heating Rate [W][LINK]
Zone
Other Equipment Total Heating Energy [J][LINK]
The total heat gain field is sum of several other fields
(radiant, latent, convective) for all equipment in the zone.
This field is expressed in Watts (for rate) or joules.
Zone
Electric Equipment Electric Energy [J][LINK]
The electric equipment consumption field is sum of the
other fields (radiant, latent, convective, lost) for all
equipment in the zone. This field is expressed in joules. This
amount is also shown in the Electricity meters that are
associated with the zone – Electricity:Facility,
Electricity:Buidling, Electricity:Zone:, and
InteriorEquipment:Electricity.
Zone Gas Equipment
Gas Energy [J][LINK]
The gas equipment consumption field is sum of the other
fields (radiant, latent, convective, lost) for all equipment
in the zone. This field is expressed in joules. This amount is
also shown in the Gas meters that are associated with the zone
– Gas:Facility, Gas:Building, Gas:Zone:, and
InteriorEquipment:Gas. Gas, here, refers to “Natural Gas”
fuel.
Zone
Hot Water Equipment District Heating Energy [J][LINK]
Zone
Steam Equipment District Heating Energy [J][LINK]
The equipment consumption field is sum of the other fields
(radiant, latent, convective, lost) for all equipment in the
zone. This field is expressed in joules. These amounts are
shown on the District Heating meters.
Note that zone energy consumption is not reported for OTHER
EQUIPMENT and does not go on any meter.
ZoneContaminantSourceAndSink:CarbonDioxide[LINK]
The ZoneContaminantSourceAndSink:CarbonDioxide
object allows users to input carbon dioxide sources or sinks
in a zone. Note that carbon dioxide generation within a zone
can also be specified using People
and GasEquipment
objects. Multiple ZoneContaminantSourceAndSink:CarbonDioxide
objects can be specified for the same zone.
The name of the ZoneContaminantSourceAndSink:CarbonDioxide
object. The name for each ZoneContaminantSourceAndSink:CarbonDioxide
object must be unique.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone)
and links a particular ZoneContaminantSourceAndSink:CarbonDioxide
object to a thermal zone in the building.
Field: Design Generation
Rate[LINK]
This field denotes the design carbon dioxide generation
rate (m3/s). The design value is modified by the
schedule fraction (see Field: Schedule Name). The resulting
volumetric generation rate is converted to mass generation
rate using the current zone indoor air density at each time
step. The rate can be either positive or negative. A positive
value represents a source rate (CO2 addition to the
zone air) and a negative value represents a sink rate
(CO2 removal from the zone air).
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedules)
that modifies the design carbon dioxide generation rate (see
previous field). The schedule values can be any positive
number between 0.0 and 1.0. For each simulation time step, the
actual CO2~~generation rate in a zone is the
product of the Design Generation Rate field (above) and the
value specified by this schedule.
An IDF example is provided below:
ZoneContaminantSourceAndSink:CarbonDioxide,
NORTH_ZONE CO2, !- Name
NORTH_ZONE, !- Zone Name
1.e-6, !- Design Generation Rate {m3/s}
CO2 Source Schedule; !- Schedule Name
ZoneContaminantSourceAndSink:CarbonDioxide
Outputs[LINK]
HVAC,Average, Contaminant Source or Sink CO2 Gain Volume Flow Rate [m3/s]
HVAC,Average, Zone Contaminant Source or Sink CO2 Gain Volume Flow Rate [m3/s]
Contaminant
Source or Sink CO2 Gain Volume Flow Rate [m3/s][LINK]
This output is the net carbond dioxide internal gain/loss
in m3/s for an individual ZoneContaminantSourceAndSink:CarbonDioxide
object.
Zone
Contaminant Source or Sink CO2 Gain Volume Flow Rate
[m3/s][LINK]
This output variable reports the total (net) carbon dioxide
internal gains/losses in cubic meters per second for a zone,
including impacts from three objects: ZoneContaminantSourceAndSink:CarbonDioxide,
People,
and GasEquipment.
Positive values denote carbon dioxide generation (gain or
source), while negative values denote carbon dioxide removal
(loss or sink).
ZoneContaminantSourceAndSink:GenericContaminant:Constant[LINK]
The
ZoneContaminantSourceAndSink:GenericContaminant:Constant
object specifies the generic contaminant generation rate and
removal rate coefficient in a zone. The associated fraction
schedules are required for allowing users to change the
magnitude of sources and sinks. The object is equivalent to
the combination of the constant coefficient model and the
burst source model defined in the sources and sinks element
types of CONTAM 3.0. The basic equation used to calculate
generic contaminant source and sink for the constant model is
given below:
where
Sf~~= Contaminant generic contaminant
source strength [m3/s]
Gf~~= Generic contaminant generation
rate [m3/s]
FG~~= Fraction value from the source
fraction schedule at a given time [dimensionless]
Rf~~= Generic contaminant effective
removal rate [m3/s]
FR~~= Fraction value from the sink
fraction schedule at a given time [dimensionless]
Cf~~= Generic contaminant concentration
value at a given previous time step [ppm]
This field represents a unique identifying name in a group
referring Generic contaminantSourceAndSinkNames.
Field: Zone Name[LINK]
This field signifies the Name of the zone with constant
generic contaminant source and sink.
Field: Maximum
Generation Rate[LINK]
This field denotes the full generic contaminant maximum
generation rate (m3/s). The design generation rate
is the maximum amount of generic contaminant expected at
design conditions. The design value is modified by the
schedule fraction (see Field:Generation Schedule Name).
Field: Generation
Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the maximum design generation rate (Gf).
This fraction between 0.0 and 1.0 is noted as FG in
the above equation.
Field: Design
Removal Coefficient[LINK]
This field denotes the full generic contaminant design
removal coefficient (m3/s). The design removal rate
is the maximum amount of generic contaminant expected at
design conditions times the generic contaminant concentration
in the same zone. The design value is modified by the schedule
fraction (see Field:Removal Schedule Name).
Field: Removal Schedule
Name[LINK]
This field is the name of the schedule (ref:
Schedule) that modifies the maximum design generation rate
(Rf). This fraction between 0.0 and 1.0 is
noted as FR in the above equation.
An IDF example is provided below:
ZoneContaminantSourceAndSink:GenericContaminant:Constant,
NORTH ZONE GC, !- Name
NORTH ZONE, !- Zone Name
1.0E-6, !- Design Generation Rate {m3/s}
GC Source Schedule, !- Schedule Name
1.0E-7, !- Design Removal Coefficient {m3/s}
GC Removal Schedule; !- Removal Schedule Name
ZoneContaminantSourceAndSink:GenericContaminant:Constant
Outputs[LINK]
When a
ZoneContaminantSourceAndSink:GenericContaminant:Constant
object is specified, the following output variables are
available:
ZONE,Average, Generic Air Contaminant Constant Source Generation Volume Flow Rate [m3/s]
Generic
Air Contaminant Constant Source Generation Volume Flow Rate
[m3/s][LINK]
This output is the average generic contaminant generation
rate from each
ZoneContaminantSourceAndSink:GenericContaminant:Constant
object. The generation rate is a sum of generation and removal
rates. The zone air generic contaminant level at the previous
zone time step is used in the removal rate calculation.
SurfaceContaminantSourceAndSink:GenericContaminant:PressureDriven[LINK]
The
SurfaceContaminantSourceAndSink:GenericContaminant:PressureDriven
object specifies the generic contaminant generation rate
coefficient, which is used to calculate the generation rate
due to the pressure difference across the surface. The object
is equivalent to the pressure driven model defined in the
sources and sinks element types of CONTAM 3.0. This object
assumes to work with the AirflowNetwork model. The surface has
to be defined in the AirflowNetwork:Multizone:Surface.
Although the model is designed to be applied to radon and soil
gas entry, it is expanded to be applied to all contaminant
transport, including generic contaminant. However, it should
be used in caution. The basic equation used to calculate
generic contaminant source for the pressure driven constant
model is provided below:
where
Sf~~= Generic contaminant source
strength [m3/s]
Hf~~= Generic contaminant generation
rate coefficient [m3/s]
FG~~= Fraction value from the source
fraction schedule at a given time [dimensionless]
n= Flow power exponent
Pi~~= [Zone](../input-output-reference/page-011.html#zone)
pressure [Pa]
Pj~~= Pressure in an adjacent zone for
a interior surface or outdoor for an exterior surface [Pa]
The field signifies the unique identifying name in a group
referring GenericContaminantSourceAndSinkNames.
Field: Surface Name[LINK]
This field represents the name of the surface as a generic
contaminant source using the pressure driven model.
Field:
Design Generation Rate Coefficient[LINK]
This field denotes the generic contaminant design
generation coefficient (m3/s). The design
generation rate is the maximum amount of generic contaminant
expected at design conditions times the pressure difference
with a power exponent across a surface. The design value is
modified by the schedule fraction (see Field:Generation
Schedule Name).
Field: Generation
Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the maximum design generation rate. This fraction
between 0.0 and 1.0 is noted as FG in the above
equation.
An IDF example is provided below:
SurfaceContaminantSourceAndSink:GenericContaminant:PressureDriven,
WEST ZONE GC BLD, !- Name
Zn001:Wall001, !- Surface Name
1.0E-6, !- Design Generation Rate Coefficient {m3/s}
GC Source Schedule, !- Generation Schedule Name
0.5; !- Generation Exponent
SurfaceContaminantSourceAndSink:GenericContaminant:PressureDriven
Outputs[LINK]
When a
SurfaceContaminantSourceAndSink:GenericContaminant:PressureDriven
object is specified, the following output variables are
available:
ZONE,Average,Generic Air Contaminant Pressure Driven Generation Volume Flow Rate [m3/s]
Generic
Air Contaminant Pressure Driven Generation Volume Flow Rate
[m3/s][LINK]
This output is the average generic contaminant generation
rate from each
SurfaceContaminantSourceAndSink:GenericContaminant:PressureDriven
object.
ZoneContaminantSourceAndSink:GenericContaminant:CutoffModel[LINK]
The ZoneContaminantSourceAndSink:Generic
contaminant:CutoffModel object specifies the generic
contaminant generation rate based on the cutoff concentration
model. The basic equation used to calculate generic
contaminant source for the pressure driven constant model is
given below:
where
Sf~~= Generic contaminant source
strength [m3/s]
Gf~~= Generic contaminant generation
rate [m3/s]
FG~~= Fraction value from the source
fraction schedule at a given time [dimensionless]
Ccutoff = Cutoff concentration at which
emission ceases [ppm]
Cf~~= Generic contaminant concentration
value at a given previous time step [ppm]
The field signifies the unique identifying name in a group
referring GenericContaminantSourceAndSinkNames.
Field: Zone Name[LINK]
This field represents the name of the zone with generic
contaminant source and sink using the cutoff model.
Field: Design
Generation Rate[LINK]
This field denotes the full generic contaminant design
generation rate (m3/s). The design generation rate
is the maximum amount of generic contaminant expected at
design conditions. The design value is modified by the
schedule fraction (see Field:Generation Schedule Name).
Field: Generation
Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the maximum design generation rate (Gf).
This fraction between 0.0 and 1.0 is noted as FG in
the above equation.
Field: Cutoff
Concentration[LINK]
This field is the generic contaminant cutoff concentration
level where the source ceases its emission.
An IDF example is provided below:
ZoneContaminantSourceAndSink:GenericContaminant:CutoffModel,
NORTH ZONE GC CutoffModel, !- Name
NORTH ZONE, !- Zone Name
1.0E-5, !- Design Generation Rate {m3/s}
GC Source Schedule, !- Schedule Name
100000; !- Cutoff Concentration {ppm}
ZoneContaminantSourceAndSink:GenericContaminant:CutoffModel
Outputs[LINK]
When a
ZoneContaminantSourceAndSink:GenericContaminant:CutoffModel
object is specified, the following output variables are
available:
ZONE,Average, Generic Air Contaminant Cutoff Model Generation Volume Flow Rate [m3/s]
Generic
Air Contaminant Cutoff Model Generation Volume Flow Rate
[m3/s][LINK]
This output is the average generic contaminant generation
rate from each
SurfaceContaminantSourceAndSink:GenericContaminant:
CutoffModel object.
ZoneContaminantSourceAndSink:GenericContaminant:DecaySource[LINK]
The
ZoneContaminantSourceAndSink:GenericContaminant:DecaySource
object specifies the generic contaminant generation rate based
on the decay source model. The basic equation used to
calculate generic contaminant source for the decay source
model is given below:
where
Sf~~= Generic contaminant source
strength [m3/s]
Gf~~= Initial generic contaminant
generation rate [m3/s]
FG~~= Fraction value from the source
fraction schedule at a given time [dimensionless]
t = Time since the start of emission [second]
tc = Decay time constant [second]
This field is the unique identifying name in a group
referring GenericContaminantSourceAndSinkNames.
Field: Zone Name[LINK]
This field represents the name of the zone with a generic
contaminant decaying source.
Field: Initial
Generation Rate[LINK]
This field denotes the initial generic contaminant design
generation rate (m3/s). The generation is
controlled by a schedule, as defined in the next field.
Generic contaminant generation begins when the schedule
changes from a zero to a non-zero value (between zero and
one). The initial generation rate is equal to the schedule
value times the initial generation rate. A single schedule may
be used to initiate several emissions at different times. (see
Field:Generation Schedule Name).
Field: Generation
Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the maximum design generation rate (Gf).
This fraction between 0.0 and 1.0 is noted as FG in
the above equation. When the value is equal to 1, the
generation rate is used and time is reset to zero. When the
value is equal to zero, the schedule value is ignored in the
equation.
Field: Decay Time
Constant[LINK]
This field is the time at which the generation rate reaches
0.37 of the original rate.
Note: The variable t, time since the start of emission,
will be reset to zero, when a new run period starts, or the
generation schedule value is equal to zero.
An IDF example is provided below:
ZoneContaminantSourceAndSink:GenericContaminant:DecaySource,
WEST ZONE GC DecaySource, !- Name
WEST ZONE, !- Zone Name
1.0E-5, !- Initial Emission Rate {m3/s}
GC Source Schedule, !- Schedule Name
100000; !- Delay Time Constant {s}
ZoneContaminantSourceAndSink:GenericContaminant:DecaySource
Outputs[LINK]
When a
ZoneContaminantSourceAndSink:GenericContaminant:DecaySource
object is specified, the following output variables are
available:
Zone,Average,Generic Air Contaminant Decay Model Generation Volume Flow Rate [m3/s]
Zone,Average,Generic Air Contaminant Decay Model Generation Emission Start Elapsed Time [s]
Generic
Air Contaminant Decay Model Generation Volume Flow Rate
[m3/s][LINK]
This output is the average generic contaminant decay rate
from each
SurfaceContaminantSourceAndSink:GenericContaminant:DecaySource
object.
Generic
Air Contaminant Decay Model Generation Emission Start Elapsed
Time [s][LINK]
This output is the decay time since the start of emission.
The start time is either at the beginning of each run period,
including design day simulations, or the time when the
egenration schedule value is zero.
SurfaceContaminantSourceAndSink:GenericContaminant:BoudaryLayerDiffusion[LINK]
The
SurfaceContaminantSourceAndSink:GenericContaminant:BoudaryLayerDiffusion
object specifies the generic contaminant generation rate from
surface diffusion. The object is equivalent to the boundary
layer diffusion model driven model defined in the sources and
sinks element types of CONTAM 3.0.
The boundary layer diffusion controlled reversible
sink/source model with a linear sorption isotherm follows the
descriptions presented in [Axley 1991]. The boundary layer
refers to the region above the surface of a material through
which a concentration gradient exists between the near-surface
concentration and the air-phase concentration. The rate at
which a contaminant is transferred onto a surface (sink) is
defined as:
where
h = Average film mass transfer coefficient over
the sink [m/s]
= Film density of air [kg/m3]
A = Surface area of the adsorbent
[m2]
Cf = Concentration in the air at the
previous time step [ppm]
Cs = Concentration in the adsorbent
[ppm]
k = Henry adsorption constant or partition
coefficient [dimensionless]
This field signifies a unique identifying name in a group
referring GenericContaminanteSourceAndSinkNames.
Field: Surface Name[LINK]
This field denotes the name of the surface as a generic
contaminant reversible source or sink using the boundary layer
diffusion model.
Field: Film Transfer
Coefficient[LINK]
This field specifies the average mass transfer coefficient
of the contaminant generic contaminant within the boundary
layer (or film) above the surface of the adsorbent.
Field: Henry
Partition Coefficient[LINK]
This field denotes the generic contaminant Henry partition
coefficient in the units of dimensionless. The coefficient
relates the concentration of the contaminant generic
contaminant in the bulk-air to that at the surface of the
adsorption material.
An IDF example is provided below:
SurfaceContaminantSourceAndSink:GenericContaminant:BoudaryLayerDiffusion,
WEST ZONE GC BLD, !- Name
Zn001:Wall001, !- Surface Name
1.0E-2, !- Mass Transfer Coefficient {m/s}
GC Source Schedule, !- Schedule Name
2.0; !- Henry adsorption constant or partition coefficient
SurfaceContaminantSourceAndSink:GenericContaminant:BoundaryLayerDiffusion
Outputs[LINK]
When a
SurfaceContaminantSourceAndSink:GenericContaminant:BoudaryLayerDiffusion
object is specified, the following output variables are
available:
ZONE,Average, Generic Air Contaminant Boundary Layer Diffusion Generation Volume Flow Rate [m3/s]
ZONE,Average, Generic Air Contaminant Boundary Layer Diffusion Inside Face Concentration [ppm]
Generic
Air Contaminant Boundary Layer Diffusion Generation Volume
Flow Rate [m3/s][LINK]
This output is the average generic contaminant generation
rate from each
SurfaceContaminantSourceAndSink:GenericContaminant:BoudaryLayerDiffusion
object.
Generic
Air Contaminant Boundary Layer Diffusion Inside Face
Concentration [ppm][LINK]
This output is the average generic contaminant level at the
interior surface.
SurfaceContaminantSourceAndSink:GenericContaminant:DepositionVelocitySink[LINK]
The
SurfaceContaminantSourceAndSink:GenericContaminant:DepositionVelocitySink
object specifies the generic contaminant removal rate from a
surface. The object is equivalent to the deposition velocity
sink model defined in CONTAM 3.0 sources and sinks element
types.
The deposition velocity model provides for the input of a
sink’s characteristic in the familiar term of deposition
velocity. The removal stops when the sink concentration level
is higher than the zone air concentration level. The
deposition velocity model equation is:
where
Sf(t) = Removal rate at time t
[m3/s]
d~~ = Deposition velocity [m/s]
As = Deposition surface area
[m2]
m = Element multiplier [dimensionless]
Cf(t) = Concentration of
contaminant generic contaminant at the previous time step
[ppm]
FR = Schedule or control signal value at time
t [-]
This field denotes a unique identifying name in a group
referring GenericContaminant SourceAndSinkNames.
Field: Surface Name[LINK]
This field represents the name of the surface as a generic
contaminant sink using the deposition velocity sink model.
Field: Deposition
Velocity[LINK]
This field specifies the deposition velocity to the surface
of the adsorbent in the units of m/s.
Field: Removal Schedule
Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the maximum design removal rate (Sf). This
fraction between 0.0 and 1.0 is noted as FR in the
above equation.
An IDF example is provided below:
SurfaceContaminantSourceAndSink:GenericContaminant:DepositionVelocitySink,
EAST ZONE GC DVS, !- Name
Zn002:Wall001, !- Surface Name
1.0E-3, !- Deposition Velocity {m/s}
GC Source Schedule; !- Schedule Name
SurfaceContaminantSourceAndSink:GenericContaminant:DepositionVelocitySink
Outputs[LINK]
The following output variables are available when the
SurfaceContaminantSourceAndSink:GenericContaminant:DepositionVelocitySink
object is specified.
ZONE,Average, Generic Air Contaminant Deposition Velocity Removal Volume Flow Rate [m3/s]
Generic
Air Contaminant Deposition Velocity Removal Volume Flow Rate
[m3/s][LINK]
This output is the average generic contaminant generation
rate from each
SurfaceContaminantSourceAndSink:GenericContaminant:DepositionVelocitySink
object.
ZoneContaminantSourceAndSink:GenericContaminant:DepositionRateSink[LINK]
The
ZoneContaminantSourceAndSink:GenericContaminant:DepositionRateSink
object specifies the generic contaminant removal rate from a
zone. The object is equivalent to the deposition rate sink
model defined in CONTAM 3.0 sources and sinks element
types.
The deposition rate model provides for the input of a
sink’s characteristic in the familiar term of deposition rate
in a zone. The removal stops when the sink concentration level
is higher than the zone air concentration level. The
deposition rate model equation is:
Where
Sf(t) = Removal rate at time t
[m3/s]
kd = Deposition rate [1/T]
Vz = [Zone](../input-output-reference/page-011.html#zone)
volume [m3]
m = Element multiplier [dimensionless]
Cf(t) = Concentration of
generic contaminant at the previous time step
[ppm]
FR = Schedule or control signal value at time
t [dimensionless]
This field denotes a unique identifying name in a group
referring GenericContaminantSourceAndSinkNames.
Field: Zone Name[LINK]
This field represents the name of the zone as a generic
contaminant sink using the deposition rate sink model.
Field: Deposition Rate[LINK]
This field specifies the deposition rate to the zone in the
units of 1/s.
Field: Removal Schedule
Name[LINK]
This field is the name of the schedule (ref: Schedule) that
modifies the maximum design removal rate (Sf). This
fraction between 0.0 and 1.0 is noted as FR in the
above equation.
An IDF example is provided below:
ZoneContaminantSourceAndSink:GenericContaminant:DepositionRateSink,
NORTH ZONE GC DRS, !- Name
NORTH ZONE, !- Zone Name
1.0E-5, !- Deposition Rate {m3/s}
GC Source Schedule; !- Schedule Name
ZoneContaminantSourceAndSink:GenericContaminant:DepositionRateSink
Outputs[LINK]
When the
ZoneContaminantSourceAndSink:GenericContaminant:DepositionRateSink
object is specified, the following output variables are
available:
ZONE,Average, Generic Air Contaminant Deposition Rate Removal Volume Flow Rate [m3/s]
Generic
Air Contaminant Deposition Rate Removal Volume Flow Rate
[m3/s][LINK]
This output is the average generic contaminant generation
rate from each
ZoneContaminantSourceAndSink:GenericContaminant:DepositionRateSink
object.
ZoneBaseboard:OutdoorTemperatureControlled[LINK]
This object specifies outside temperature-controlled (OTC)
baseboard heating. The capacities (high and low) are specified
in W at the temperatures specified. The schedule allows both
capacities to change hourly on a proportional basis. This
baseboard heater does not operate if the outdoor dry-bulb is
above the high temperature limit. Between the high temperature
and the low temperature, the capacity is interpolated (linear)
between the high and the low capacity values. Below the low
temperature, the capacity is set at the low capacity value.
This allows the user to add baseboard heat to a perimeter zone
starting at a prescribed temperature and then slowly increases
this capacity to a max value.
Example:
Temperature High = 10 CCapacity High = 100,000 W
Temperature Low = 0 CCapacity Low = 500,000 W
Outdoor Temperature Controlled Baseboard Heat Temperature
vs. Capacity
Outdoor Dry-bulb(C)
Baseboard Output
>10
0
10
100,000
8
180,000
6
260,000
4
340,000
2
420,000
0
500,000
< 0
500,000
The name of the ZoneBaseboard:OutdoorTemperatureControlled
object.
Field: Zone Name[LINK]
This field is the name of the zone and attaches the
baseboard heat equipment statement to a thermal zone in the
building.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the
capacities (high and low) for baseboard heat equipment (see
next four fields). The schedule values can be any positive
number. The actual energy input for the baseboard equipment in
a zone as defined by this statement depends on the actual
outdoor temperature and where that temperature is in the range
of Low Temperature to High Temperature..
Field: Capacity at
Low Temperature[LINK]
This is the baseboard equipment capacity (Watts) at the low
temperature limit.
Field: Low Temperature[LINK]
If the outdoor dry-bulb temperature (degrees Celsius) is at
or below the low temperature the baseboard heater operates at
the low temperature capacity.
Field: Capacity at
High Temperature[LINK]
This is the baseboard equipment capacity (Watts) at the
high temperature limit.
Field: High Temperature[LINK]
If the outdoor dry-bulb temperature (degrees Celsius) is
greater than the high temperature the baseboard heater will
not operate.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is
used to characterize the type of heat being given off by
baseboard heat equipment in a zone. The number specified in
this field will be multiplied by the total energy consumed by
the baseboard heat equipment to give the amount of long
wavelength radiation gain to the zone.
Field: End-Use
Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory,
e.g., “Perimeter Baseboards”, etc. A new meter for reporting
is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly)
object). Subcategories are also reported in the ABUPS table.
If this field is omitted or blank, the baseboard equipment
will be assigned to the “General” end-use subcategory.
An IDF example:
ZoneBaseboard:OutdoorTemperatureControlled,
SPACE4-1 BBHeat 1, !- Name
SPACE4-1, !- Zone Name
EQUIP-1, !- SCHEDULE Name
1500, !- Capacity at low temperature {W}
0, !- Low Temperature {C}
500, !- Capacity at high temperature {W}
10, !- High Temperature {C}
0.5, !- Fraction Radiant
Baseboard Heat; !- End-Use Subcategory
ZoneBaseboard:OutdoorTemperatureControlled
Output[LINK]
ZoneBaseboard:OutdoorTemperatureControlled
objects have output variables for individual objects and for
zone totals. The following outputs are available:
Zone,Average,Baseboard Electric Power [W]
Zone,Sum,Baseboard Electric Energy [J]
Zone,Sum,Baseboard Radiant Heating Energy [J]
Zone,Average,Baseboard Radiant Heating Rate [W]
Zone,Sum,Baseboard Convective Heating Energy [J]
Zone,Average,Baseboard Convective Heating Rate [W]
Zone,Sum,Baseboard Total Heating Energy [J]
Zone,Average,Baseboard Total Heating Rate [W]
Zone,Average,Zone Baseboard Electric Power [W]
Zone,Sum,Zone Baseboard Electric Energy [J]
Zone,Sum,Zone Baseboard Radiant Heating Energy [J]
Zone,Average,Zone Baseboard Radiant Heating Rate [W]
Zone,Sum,Zone Baseboard Convective Heating Energy [J]
Zone,Average,Zone Baseboard Convective Heating Rate [W]
Zone,Sum,Zone Baseboard Total Heating Energy [J]
Zone,Average,Zone Baseboard Total Heating Rate [W]
Baseboard Electric Power
[W][LINK]
This field is the electric power for the ZoneBaseboard:OutdoorTemperatureControlled
object in Watts.
Baseboard Electric Energy
[J][LINK]
The outdoor temperature controlled baseboard heat option is
assumed to be fueled by electricity. This field is the same as
the Baseboard Total Heating Energy (above) in joules.
Baseboard Radiant
Heating Rate [W][LINK]
Baseboard Radiant
Heating Energy [J][LINK]
These output variables are the amount of radiant heat gain
for the ZoneBaseboard:OutdoorTemperatureControlled
object in Watts (for rate) or Joules. This is determined by
the current heat gain from the heater to the zone and the
“Fraction Radiant” specified in the input. The radiant gains
(long wavelength) are distributed to the surfaces using an
area weighting scheme.
Baseboard
Convective Heating Rate [W][LINK]
Baseboard
Convective Heating Energy [J][LINK]
These output variables are the amount of convective heat
gain for the ZoneBaseboard:OutdoorTemperatureControlled
object in Watts (for rate) or Joules. This is determined by
the current heat gain from the heater to the zone and the
“Fraction Radiant” specified in input (1-FractionRadiant =
FractionConvected). The convective heat gain is added to the
zone air heat balance directly.
Baseboard Total
Heating Rate [W][LINK]
Baseboard Total
Heating Energy [J][LINK]
These output variables are the amount of heat gain for the
ZoneBaseboard:OutdoorTemperatureControlled
object in Watts (for rate) or Joules. This is determined by
the sum of the radiant and convective heat gains from the
baseboard heat.
Zone Baseboard
Electric Power [W][LINK]
This field is the electric power for all ZoneBaseboard:OutdoorTemperatureControlled
objects within the zone in Watts.
Zone Baseboard
Electric Energy [J][LINK]
The outdoor temperature controlled baseboard heat option is
assumed to be fueled by electricity. This field is the same as
the Baseboard Total Heating Energy (above) in joules. However,
this amount is also shown in the Electricity meters that are
associated with the zone – Electricity:Facility,
Electricity:Buidling, Electricity:Zone:, and
InteriorEquipment:Electricity.
Zone Baseboard
Radiant Heating Rate [W][LINK]
Zone
Baseboard Radiant Heating Energy [J][LINK]
These output variables are the amount of radiant heat gain
for all ZoneBaseboard:OutdoorTemperatureControlled
objects within the zone in Watts (for rate) or Joules. This is
determined by the current heat gain from the heater to the
zone and the “Fraction Radiant” specified in the input. The
radiant gains (long wavelength) are distributed to the
surfaces using an area weighting scheme.
Zone
Baseboard Convective Heating Rate [W][LINK]
Zone
Baseboard Convective Heating Energy [J][LINK]
These output variables are the amount of convective heat
gain for all ZoneBaseboard:OutdoorTemperatureControlled
objects within the zone in Watts (for rate) or Joules. This is
determined by the current heat gain from the heater to the
zone and the “Fraction Radiant” specified in input
(1-FractionRadiant = FractionConvected). The convective heat
gain is added to the zone air heat balance directly.
Zone Baseboard
Total Heating Rate [W][LINK]
Zone Baseboard
Total Heating Energy [J][LINK]
These output variables are the amount of heat gain for all
ZoneBaseboard:OutdoorTemperatureControlled
objects within the zone in Watts (for rate) or Joules. This is
determined by the sum of the radiant and convective heat gains
from the baseboard heat.
Meters for Equipment
Outputs[LINK]
As described in each of the equipment sections, values for
specific equipments will show up on the following meters:
Distribution of Equipment to Meters
| Meter Name |
Scope |
Equipment Specfics |
| Electricity:Facility |
Entire Facility |
Electric Equipment, OTC
Baseboard Heat |
| Electricity:Building |
All Zones |
Electric Equipment, OTC
Baseboard Heat |
| Electricity:Zone: |
Specific Zone |
Electric Equipment, OTC
Baseboard Heat |
| InteriorEquipment:Electricity |
AllZones |
Electric Equipment, OTC
Baseboard Heat |
| :InteriorEquipment:Electricity |
Specific Subcategory |
Electric Equipment, OTC
Baseboard Heat |
| Gas:Facility |
Entire Facility |
Gas Equipment |
| Gas:Building |
All Zones |
Gas Equipment |
| Gas:Zone: |
Specific Zone |
Gas Equipment |
| InteriorEquipment:Gas |
AllZones |
Gas Equipment |
| :InteriorEquipment:Gas |
Specific Subcategory |
Gas Equipment |
Group – Internal Gains (People, Lights, Other internal zone equipment)[LINK]
Not all the influence for energy consumption in the building is due to envelope and ambient conditions. This group of objects describes other internal gains that may come into play (People, Lights, Various Equipment Types).
People[LINK]
The people statement is used to model the occupant’s affect on the space conditions. The following definition addresses the basic affects as well as providing information that can be used to report the thermal comfort of a group of occupants. The Fanger, Pierce Two-Node, and Kansas State University Two-Node thermal comfort models are available in EnergyPlus. A user may select any of these models for each People statement by simply adding the appropriate choice keyword after the air velocity schedule name. Thermal comfort calculations will only be made for people statements that include specific requests for these thermal comfort models. . This object also requires input of carbon dioxide generation rate based on people activity level for zone carbon dioxide simulations.
Field: Name[LINK]
The name of the People object. Must be unique across all People objects.
Field: Zone or ZoneList Name[LINK]
This field is the name of the zone (ref: Zone](page-011.html#zone)) or [ZoneList](../input-output-reference/page-011.html#zonelist) (ref: [ZoneList](../input-output-reference/page-011.html#zonelist)) and links a particular people statement to a thermal zone or set of thermal zones in the building. When the [ZoneList](../input-output-reference/page-011.html#zonelist) option is used then this people definition is applied to each of the zones in the zone list effecting a global definition for the number of people in the zone. The Zonelist option can be used effectively with the people/area and area/person options of the Number of [People Calculation Method.
The name of the actual people object becomes <Zone](page-011.html#zone) Name> <[People Object Name> and should be less than the standard length (100 characters) for a name field. If it is greater than this standard length, it may be difficult to specify in output reporting as it will be truncated. A warning will be shown if the generated name is greater than 100 characters. If it duplicates another such concatenated name, there will be a severe error and terminate the run.
Field: Number of People Schedule Name[LINK]
This field is the name of the schedule (ref: Schedules) that modifies the number of people parameter (see Number of People Calculation Method and related fields). The schedule values can be any positive number. The actual number of people in a zone as defined by this statement is the product of the number of people field and the value of the schedule specified by name in this field.
Field: Number of People Calculation Method[LINK]
This field is a key/choice field that tells which of the next three fields are filled and is descriptive of the method for calculating the nominal number of occupants (people) in the [Zone](../input-output-reference/page-011.html#zone). The key/choices are:
Field: Number of People[LINK]
This field is used to represent the maximum number of people in a zone that is then multiplied by a schedule fraction (see schedule field). In EnergyPlus, this is slightly more flexible in that the number of people could be a “diversity factor” applied to a schedule of real numbers. Note that while the schedule value can vary from hour to hour, the number of people field is constant for all simulation environments.
Field: People per Zone Floor Area[LINK]
This factor (person/m2) is used, along with the Zone](page-011.html#zone) Floor Area to determine the maximum number of people as described in the Number of [People field. The choice from the method field should be “people/area”.
Field: Zone Floor Area per Person[LINK]
This factor (m2/person) is used, along with the Zone](page-011.html#zone) Floor Area to determine the maximum number of people as described in the Number of [People field. The choice from the method field should be “area/person”.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the type of heat being given off by people in a zone. The number specified in this field will be multiplied by the total sensible energy emitted by people to give the amount of long wavelength radiation gain from human beings in a zone. The remainder of the sensible load is assumed to be convective heat gain. Note that latent gains from people are not included in either the radiant or convective heat gains. See the Engineering Reference document for more details.
Field: Sensible Heat Fraction[LINK]
The user can use this field to specify a fixed sensible fraction for the heat gain due to this PEOPLE object. Normally the program calculates the sensible/latent split; this field gives the user control over this split. This field is autocalculated: if the field is blank or autocalculate, the program will calculate the sensible/latent split; if a value is entered, it will be used as the sensible fraction of the current total heat gain.
Field: Activity Level Schedule Name[LINK]
This field is the name of the schedule that determines the amount of heat gain per person in the zone under design conditions. This value is modified somewhat based on a correlation to account for variations in space temperature. The schedule values may be any positive number and the units for this parameter is Watts per person. This schedule represents the total heat gain per person including convective, radiant, and latent. An internal algorithm is used to determine what fraction of the total is sensible and what fraction is latent. Then, the sensible portion is divided into radiant and convective portions using the value specified for Fraction Radiant (above). See the Engineering Reference document for more details.
Values for activity level can range anywhere from approximately 100-150 Watts per person for most office activities up to over 900 Watts per person for strenuous physical activities such as competitive wrestling. The following table (Table 11) is based on Table 4 from the 2005 ASHRAE Handbook of Fundamentals, page 8.6. In addition to the information from the ASHRAE HOF, there is an added column of values in W/Person such as necessary for the activity level schedule values. This column uses the standard adult body surface area of 1.8 m2 to multiply the activity levels in W/m2 that are used in the table. Warnings are produced when the activity level schedule values fall outside normal ranges. Having too low or too high values can also skew thermal comfort reporting values.
Field: Carbon Dioxide Generation Rate[LINK]
This numeric input field specifies carbon dioxide generation rate per person with units of m3/s-W. The total carbon dioxide generation rate from this object is:
Number of People * People Schedule * People Activity * Carbon Dioxide Generation Rate. The default value is 3.82E-8 m3/s-W (obtained from ASHRAE Standard 62.1-2007 value at 0.0084 cfm/met/person over the general adult population). The maximum value can be 10 times the default value.
Field: Enable ASHRAE 55 comfort warnings[LINK]
This field accepts either “Yes” or “No” as values. When “Yes” is specified, warnings are generated when the space conditions are outside of the ASHRAE 55 comfort range as discussed in the sections that follow titled “Simplified ASHRAE 55-2004 Graph Related Outputs” and “Simplified ASHRAE 55 Warnings.” The default is not to provide these warnings so if you want to know if your space is outside this comfort range you must set this field to Yes.
Table: Metabolic Rates for Various Activities
Activity|Activity Level W/Person EnergyPlus Schedule Value|Activity Level W/m2|met* ——–|————————————————-|———————|—– Resting Sleeping|72|40|0.7 Reclining|81|45|0.8 Seated, quiet|108|60|1 Standing, relaxed|126|70|1.2 Walking (on level surface) 3.2 km/h (0.9 m/s)|207|115|2 4.3 km/h (1.2 m/s)|270|150|2.6 6.4 km/h (1.8 m/s)|396|220|3.8 Office Activities Reading, seated|99|55|1 Writing|108|60|1 Typing|117|65|1.1 Filing, seated|126|70|1.2 Filing, standing|144|80|1.4 Walking about|180|100|1.7 Lifting/packing|216|120|2.1 Miscellaneous Occupational Activities Cooking|171 to 207|95 to 115|1.6 to 2.0 Housecleaning|207 to 360|115 to 200|2.0 to 3.4 Seated, heavy limb movement|234|130|2.2 Machine work| || sawing (table saw)|189|105|1.8 light (electrical industry)|207 to 252|115 to 140|2.0 to 2.4 heavy|423|235|4 Handling 50 kg bags|423|235|4 Pick and shovel work|423 to 504|235 to 280|4.0 to 4.8 Miscellaneous Leisure Activities Dancing, social|252 to 459|140 to 255|2.4 to 4.4 Calisthenics/exercise|315 to 423|175 to 235|3.0 to 4.0 Tennis, singles|378 to 486|210 to 270|3.6 to 4.0 Basketball|522 to 792|290 to 440|5.0 to 7.6 Wrestling, competitive|738 to 909|410 to 505|7.0 to 8.7
*Note that one met = 58.1 W/m2
Field: Mean Radiant Temperature Calculation Type[LINK]
This field specifies the type of Mean Radiant Temperature (MRT) calculation the user wishes to use for the thermal comfort model. At the present time, there are two options for MRT calculation type: zone averaged and surface weighted. The default calculation is “ZoneAveraged”. In the zone averaged MRT calculation, the MRT used for the thermal comfort calculations is for an “average” point in the zone. MRT is calculated based on an area-emissivity weighted average of all of the surfaces in the zone. In cases where the emissivity of all of the surfaces are sufficiently small (near zero), the mean radiant temperature will be set to the mean air temperature of the space to avoid divide by zero errors. The other MRT calculation type is “SurfaceWeighted”. The goal of this calculation type is to estimate a person in the space close to a particular surface without having to define exact view factors for all of the surfaces and the location of the person in the space. The MRT used in the thermal comfort calculations when the “surface weighted” calculation type is selected is actually the average of the temperature of the surface to which the person is closest (defined by the next field “Surface Name”) and the zone averaged MRT (defined above). The surface temperature alone is not used because in theory the maximum view factor from a person to any flat surface is roughly 0.5. In the “surfaceweighted” calculation, the surface in question actually gets slightly more weighting than 50% since the surface selected is still a part of the zone average MRT calculation. Again, this simplification was made to avoid the specification of view factors and the exact location of the person.
A third option is to use “anglefactor”. This option allows for more explicit positioning of the person within the space by defining the angle factors from the person to the various surfaces in the zone. This option requires the user to list the surfaces that the person can see from a radiation standpoint and also define the angle (or view) factor for each surface. The AngleFactorList object (see next object description) is intended to give the user this opportunity.
Field: Surface Name/Angle Factor List Name[LINK]
This field is only valid when the user selects “surfaceweighted” for the MRT calculation type (see the previous input field description). In this case, the field is the name of a surface within the zone the people are residing. This surface will be used in the MRT calculation as defined above to come up with a more representative MRT for a person near a particular surface. The MRT used for thermal comfort calculations using the “surface weighted” MRT calculation method is the average of the temperature of the surface specified in this field and the “zone averaged” MRT (see the Mean Radiant Temperature calculation type field above).
Field: Work Efficiency Schedule Name[LINK]
This field is the name of the schedule that determines the efficiency of energy usage within the human body that will be used for thermal comfort calculations. Note that all energy produced by the body is assumed to be converted to heat for the zone heat balance calculation. A value of zero corresponds to all of the energy produced in the body being converted to heat. A value of unity corresponds to all of the energy produced in the body being converted to mechanical energy. The values for this parameter defined in the schedule must be between 0.0 and 1.0. Any value greater than zero will result in a reduction of heat that impacts the thermal comfort energy balance of a person within the space.
Field: Clothing Insulation Schedule Name[LINK]
This field is the name of the schedule that defines the amount of clothing being worn by a typical zone occupant during various times in the simulation period. This parameter must be a positive real number and has units of Clo. Typical values for Clo can be seen in the ASHRAE 2009 HOF Table 7, page 9.8 (for clothing ensembles) and Table 8, page 9.9 (for garment values).
Field: Air Velocity Schedule Name[LINK]
This field is the name of the schedule that approximates the amount of air movement in the space as a function of time throughout the simulation period. The user has control over this parameter through the schedule that requires the individual numbers in the schedule to be positive real numbers having units of meters per second.
Field: Thermal Comfort Model Type (up to 5 allowed)[LINK]
The final one to five fields are optional and are intended to trigger various thermal comfort models within EnergyPlus. By entering the keywords Fanger, Pierce, KSU, AdaptiveASH55,, and AdaptiveCEN15251, the user can request the Fanger, Pierce Two-Node, Kansas State UniversityTwo-Node, and the adaptive comfort models of the ASHRAE Standard 55 and CEN Standard 15251 results for this particular people statement. Note that since up to five models may be specified, the user may opt to have EnergyPlus calculate the thermal comfort for people identified with this people statement using all five models if desired. Note that the KSU model is computationally intensive and may noticeably increase the execution time of the simulation. For descriptions of the thermal comfort calculations, see the Engineering Reference document.
The following IDF example allows for a maximum of 31 people with scheduled occupancy of “Office Occupancy”, 60% radiant using an Activity Schedule of “Activity Sch”. The example allows for thermal comfort reporting.
A simpler example, without using the thermal comfort reporting option:
And with the sensible fraction specified:
Global People Object:
People Outputs[LINK]
People objects have output variables for individual objects and for zone totals.
People specific outputs include:
People Occupant Count [][LINK]
This field is the number of people for this PEOPLE object during the timestep in question.
People Radiant Heating Rate [W][LINK]
People Radiant Heating Energy [J][LINK]
These output variables are the amount of radiant heat gain for this People object in Watts (for rate) or Joules. This is determined by the current sensible heat gain from people to the zone and the “Fraction Radiant” specified in the input. The radiant gains from people are distributed to the surfaces using an area weighting scheme.
People Convective Heating Rate [W][LINK]
People Convective Heating Energy [J][LINK]
These output variables are the amount of convective heat gain for this People object in Watts (for rate) or Joules. This is determined by the current sensible heat gain from people to the zone and the “Fraction Radiant” specified in input. Note that the radiant and convective gains should add up to the sensible heat gain from people. The convective heat gain from people is added to the zone air heat balance directly.
People Latent Gain Rate [W][LINK]
People Latent Gain Energy [J][LINK]
These output variables are the amount of latent heat gain for this People object in Watts (for rate) or Joules. This amount is based on the number of people in the space as well as the total amount of energy produced by a typical person defined by the activity schedule in the input. An internal algorithm is used to determine what fraction of the total is sensible and what fraction is latent. Details about this split are included in the Engineering Reference document.
People Sensible Heating Rate [W][LINK]
People Sensible Heating Energy [J][LINK]
These output variables are the amount of sensible heat gain for this People object in Watts (for rate) or Joules. This amount is based on the number of people in the space as well as the total amount of energy produced by a typical person defined by the activity schedule in the input. An internal algorithm (described in the Engineering Reference document) is used to determine what fraction of the total is sensible and what fraction is latent. The sensible plus the latent heat gain from people equals the total gain specified in the input.
People Total Heating Rate [W][LINK]
People Total Heating Energy [J][LINK]
These output variables are the total amount of heat gain for this People object in Watts (for rate) or Joules. This is derived from the activity level times the number of occupants.
People Air Temperature [C][LINK]
This output variable represents the zone air temperature based on the Fanger thermal comfort model. If there is a ZoneControl:Thermostat:ThermalComfort](page-037.html#zonecontrolthermostatthermalcomfort) object specified and the thermal zone is occupied, then the value of “[People Air Temperature” is determined based on the thermal comfort hat satisfies the thermal comfort setpoint PMV value specified; othwesie, it is set to average zone air temperature.
People Air Relative Humidity [%][LINK]
This output variable represents the zone air relative humidity based on the Fanger thermal comfort model. If there is a ZoneControl:Thermostat:ThermalComfort](page-037.html#zonecontrolthermostatthermalcomfort) object specified and the thermal zone is occupied, then the value of “[People Air Relative Humidity” is determined from the mean zone air temperature and zone air humidity ratio that satisfies the thermal comfort setpoint PMV value specified; othwesie, it is calculated from the zone air temperature and humidity ratio averaged over the time step.
Zone People Occupant Count [][LINK]
This field is the total number of people within the zone during the timestep in question.
Zone People Radiant Heating Rate [W][LINK]
Zone People Radiant Heating Energy [J][LINK]
These output variables are the amount of radiant heat gain from people within the zone in Watts (for rate) or Joules. This is determined by the current sensible heat gain from people to the zone and the “Fraction Radiant” specified in the input. The radiant gains from people are distributed to the surfaces using an area weighting scheme.
Zone People Convective Heating Rate [W][LINK]
Zone People Convective Heating Energy [J][LINK]
These output variables are the amount of convective heat gain from people within the zone in Watts (for rate) or Joules. This is determined by the current sensible heat gain from people to the zone and the “Fraction Radiant” specified in input. Note that the radiant and convective gains should add up to the sensible heat gain from people. The convective heat gain from people is added to the zone air heat balance directly.
Zone People Latent Gain Rate [W][LINK]
Zone People Latent Gain Energy [J][LINK]
These output variables are the amount of latent heat gain from people within the zone in Watts (for rate) or Joules. This amount is based on the number of people in the space as well as the total amount of energy produced by a typical person defined by the activity schedule in the input. An internal algorithm is used to determine what fraction of the total is sensible and what fraction is latent. Details about this split are included in the Engineering Reference document.
Zone People Sensible Heating Rate [W][LINK]
Zone People Sensible Heating Energy [J][LINK]
These output variables are the amount of sensible heat gain from people within the zone in Watts (for rate) or Joules. This amount is based on the number of people in the space as well as the total amount of energy produced by a typical person defined by the activity schedule in the input. An internal algorithm (described in the Engineering Reference document) is used to determine what fraction of the total is sensible and what fraction is latent. The sensible plus the latent heat gain from people equals the total gain specified in the input.
Zone People Total Heating Rate [W][LINK]
Zone People Total Heating Energy [J][LINK]
These output variables are the total amount of heat gain from people within the zone in Watts (for rate) or Joules. Derived from the activity level times the number of occupants, this is summed for each people object within a zone.
Zone Thermal Comfort Mean Radiant Temperature [C][LINK]
This output variable is the mean radiant temperature used in the thermal comfort calculations. This value is computed according to the “MRT Calculation Type” specified in the PEOPLE object. If a high temperature radiant system is present in the zone, this value will be adjusted according to the current heater operation and the “Fraction of radiant energy incident on people” specified in the HIGH TEMP RADIANT SYSTEM object.
Zone Thermal Comfort Operative Temperature [C][LINK]
This output variable is the operative temperature as defined by the thermal comfort operations. Specifically, it is the average of the thermal comfort mean radiant temperature and the zone air temperature.
Zone Thermal Comfort Fanger Model PMV [][LINK]
This field is the “predicted mean vote” (PMV) calculated using the Fanger thermal comfort model.
Zone Thermal Comfort Fanger Model PPD [%][LINK]
This field is the “predicted percentage of dissatisfied” (PPD) calculated using the Fanger thermal comfort model.
Zone Thermal Comfort Clothing Surface Temperature [C][LINK]
This output variable is the calculation of the clothing surface temperature using the Fanger thermal comfort model.
Zone Thermal Comfort Pierce Model Effective Temperature PMV [][LINK]
This field is the “predicted mean vote” (PMV) calculated using the effective temperature and the Pierce two-node thermal comfort model.
Zone Thermal Comfort Pierce Model Standard Effective Temperature PMV [][LINK]
This field is the “predicted mean vote” (PMV) calculated using the “standard” effective temperature and the Pierce two-node thermal comfort model.
Zone Thermal Comfort Pierce Model Discomfort Index [][LINK]
This field is the “discomfort index” calculated using the the Pierce two-node thermal comfort model.
Zone Thermal Comfort Pierce Model Thermal Sensation Index [][LINK]
This field is the “thermal sensation index” (PMV) calculated using the Pierce two-node thermal comfort model.
Zone Thermal Comfort KSU Model Thermal Sensation Vote [][LINK]
This field is the “thermal sensation vote” (TSV) calculated using the KSU two-node thermal comfort model.
Zone Thermal Comfort ASHRAE 55 Adaptive Model 90% Acceptability Status [][LINK]
This field is to report whether the operative temperature falls into the 90% acceptability limits of the adaptive comfort in ASHRAE 55-2010. A value of 1 means within (inclusive) the limits, a value of 0 means outside the limits, and a value of -1 means not applicable.
Zone Thermal Comfort ASHRAE 55 Adaptive Model 80% Acceptability Status [ ][LINK]
This field is to report whether the operative temperature falls into the 80% acceptability limits of the adaptive comfort in ASHRAE 55-2010. A value of 1 means within (inclusive) the limits, a value of 0 means outside the limits, and a value of -1 means not applicable.
Zone Thermal Comfort ASHRAE 55 Adaptive Model Running Average Outdoor Air Temperature [C][LINK]
This field reports the mean monthly outdoor air temperature, an input parameter for the ASHRAE-55 adaptive comfort model. This can be computed in two ways. If the .stat file is provided for the simulation, this field will reflect the monthly daily average temperature.
If the .epw file is used, the field reports the simple running average of the daily average outdoor dry-bulb temperatures of the previous 30 days.
Zone Thermal Comfort ASHRAE 55 Adaptive Model Temperature [C][LINK]
This field reports the ideal indoor operative temperature, or comfort temperature, as determined by the ASHRAE-55 adaptive comfort model. The 80% acceptability limits for indoor operative temperature are defined as no greater than 2.5 degrees C from the adaptive comfort temperature. The 90% acceptability limits are defined as no greater than 3.5 degrees C from the adaptive comfort temperature.
Zone Thermal Comfort CEN 15251 Adaptive Model Category I Status[LINK]
This field is to report whether the operative temperature falls into the Category I (90% acceptability) limits of the adaptive comfort in the European Standard EN15251-2007. A value of 1 means within (inclusive) the limits, a value of 0 means outside the limits, and a value of -1 means not applicable.
Zone Thermal Comfort CEN 15251 Adaptive Model Category II Status[LINK]
This field is to report whether the operative temperature falls into the Category II (80% acceptability) limits of the adaptive comfort in the European Standard EN15251-2007. A value of 1 means within (inclusive) the limits, a value of 0 means outside the limits, and a value of -1 means not applicable.
Zone Thermal Comfort CEN 15251 Adaptive Model Category III Status[LINK]
This field is to report whether the operative temperature falls into the Category III (65% acceptability) limits of the adaptive comfort in the European Standard EN15251-2007. A value of 1 means within (inclusive) the limits, a value of 0 means outside the limits, and a value of -1 means not applicable.
Zone Thermal Comfort CEN 15251 Adaptive Model Running Average Outdoor Air Temperature[LINK]
This field reports the weighted average of the outdoor air temperature of the previous five days, an input parameter for the CEN-15251 adaptive comfort model.
Zone Thermal Comfort CEN 15251 Adaptive Model Temperature[LINK]
This field reports the ideal indoor operative temperature, or comfort temperature, as determined by the CEN-15251 adaptive comfort model. Category I, II, and II limits for indoor operative temperature are defined as no greater than 2, 3, and 4 degrees C from this value respectively.
Simplified ASHRAE 55-2004 Graph Related Outputs[LINK]
The following output variables are all based on whether the humidity ratio and the operative temperature is within the region shown in ASHRAE Standard 55-2004 in Figure 5.2.1.1. For these outputs the operative temperature is simplified to be the average of the air temperature and the mean radiant temperature. For summer, the 0.5 Clo level is used and, for winter, the 1.0 Clo level is used. The graphs below are based on the following tables which extend the ASHRAE values to zero humidity ratio.
Zone Thermal Comfort ASHRAE 55 Simple Model Summer Clothes Not Comfortable Time[hr][LINK]
The time when the zone is occupied that the combination of humidity ratio and operative temperature is not in the ASHRAE 55-2004 summer clothes region (see above)
Zone Thermal Comfort ASHRAE 55 Simple Model Winter Clothes Not Comfortable Time[hr][LINK]
The time when the zone is occupied that the combination of humidity ratio and operative temperature is not in the ASHRAE 55-2004 winter clothes region (see above)
Zone Thermal Comfort ASHRAE 55 Simple Model Summer or Winter Clothes Not Comfortable Time[hr][LINK]
The time when the zone is occupied that the combination of humidity ratio and operative temperature is not in the ASHRAE 55-2004 summer or winter clothes region (see above)
Facility Thermal Comfort ASHRAE 55 Simple Model Summer Clothes Not Comfortable Time[hr][LINK]
The time when any zone is occupied that the combination of humidity ratio and operative temperature is not in the ASHRAE 55-2004 summer clothes region (see above)
Facility Thermal Comfort ASHRAE 55 Simple Model Winter Clothes Not Comfortable Time [hr][LINK]
The time when any zone is occupied that the combination of humidity ratio and operative temperature is not in the ASHRAE 55-2004 winter clothes region (see above)
Facility Thermal Comfort ASHRAE 55 Simple Model Summer Clothes Not Comfortable Time [hr][LINK]
The time when any zone is occupied that the combination of humidity ratio and operative temperature is not in the ASHRAE 55-2004 summer or winter clothes region (see above)
Simplified ASHRAE 55 Warnings[LINK]
The simplified ASHRAE 55 calculations may be computed for occupied zones and, possibly, warnings are shown on the .err file at the end of each simulated environment. To enable this option set the “Enable ASHRAE 55 comfort warnings” field of the People object to Yes. These warnings will not be generated by default.
If you enable the warnings, the simplified ASHRAE 55 calculations are done for occupied zones and, possibly, warnings are shown on the .err file at the end of each simulated environment.
You may decide if you need to change parameters to reduce these “uncomfortable” hours. The individual output variables shown previously may help you get more details on when these are occurring.
Following are some suggestions that might be applicable:
ComfortViewFactorAngles[LINK]
When requesting EnergyPlus to do a thermal comfort calculation, the program user has three options for defining how the mean radiant temperature will be calculated. The user may select “zoneaveraged” which results in a mean radiant temperature that is characteristic of an “average” location near the center of the zone. The user may also elect to place the person near a particular surface by selecting “surfaceweighted” in the People statement. This takes the average of the zone mean radiant temperature and the temperature of the surface that the person is near and uses this value as the mean radiant temperature when calculating thermal comfort.
The third option is for the user to more explicitly position the person within the space by defining the angle factors from the person to the various surfaces in the zone. This option requires the user to list the surfaces that the person can see from a radiation standpoint and also define the angle (or view) factor for each surface. The AngleFactorList input line is intended to give the user this opportunity.
Field: Name[LINK]
This field is an unique user assigned name for the list of surfaces that can be seen radiantly by the person for whom thermal comfort is to be evaluated. Any reference to this list by a People statement will use this name.
Field: Zone Name[LINK]
[Zone](../input-output-reference/page-011.html#zone) Name for this surface list. Each of the surfaces listed must be in this zone.
Field: Surface <#> Name[LINK]
This field is the name of a surface in the zone seen by the person.
Field: Angle Factor <#>[LINK]
This field is the fraction that this surface contributes to the total mean radiant temperature. This can be thought of as a weighting factor for this surface and the actual mean radiant temperature used in the thermal comfort model is simply the sum of all angle factors multiplied by the corresponding inside surface temperature. Note that the Surface Name/Angle Factor pair can be repeated up to 20 times. The sum of all angle factors within any angle factor list must equal unity, otherwise the program will not accept the input as valid.
An example IDF with an electric low temperature radiant system is shown below.
Lights[LINK]
The Lights statement allows you to specify information about a zone’s electric lighting system, including design power level and operation schedule, and how the heat from lights is distributed thermally.
A zone may have multiple Lights statements. For example, one statement may describe the general lighting in the zone and another the task lighting. Or you can use multiple Lights statements for a zone that has two or more general lighting systems that differ in design level, schedule, etc.
Field: Name[LINK]
The name of the Lights object.
Field: Zone or ZoneList Name[LINK]
The field is the name of the thermal zone (ref: Zone](page-011.html#zone)) or [ZoneList](../input-output-reference/page-011.html#zonelist) (ref: ZoneLIst) and links this [Lights statement to a thermal zone or set of thermal zones in the buidling. When the [ZoneList](../input-output-reference/page-011.html#zonelist) option is used then this lights definition is applied to each of the zones in the zone list effecting a global definition for the amount of light wattage in the zone. The Zonelist option can be used effectively with the watts/area and watts/person options of the Design Level Calculation Method.
The name of the actual lights object becomes <Zone](page-011.html#zone) Name> <[Lights Object Name> and should be less than the standard length (100 characters) for a name field. If it is greater than this standard length, it may be difficult to specify in output reporting as it will be truncated. A warning will be shown if the generated name is greater than 100 characters. If it duplicates another such concatenated name, there will be a severe error and terminate the run.
Field: Schedule Name[LINK]
The name of the schedule that modifies the lighting power design level (see Design Level Calculation Method field and related subsequent fields). The schedule values can be any positive number. The electrical input for lighting in a particular timestep is the product of the design level and the value of this schedule in that timestep. If the design level is the maximum lighting power input the schedule should contain values between 0.0 and 1.0.
Field: Design Level Calculation Method[LINK]
This field is a key/choice field that tells which of the next three fields are filled and is descriptive of the method for calculating the nominal lighting level in the [Zone](../input-output-reference/page-011.html#zone). The key/choices are:
Field: Lighting Level[LINK]
This is typically the maximum electrical power input (in Watts) to lighting in a zone, including ballasts, if present. This value is multiplied by a schedule fraction (see previous field) to get the lighting power in a particular timestep. In EnergyPlus, this is slightly more flexible in that the lighting design level could be a “diversity factor” applied to a schedule of real numbers.
Field: Watts per Zone Floor Area[LINK]
This factor (watts/m2) is used, along with the [Zone](../input-output-reference/page-011.html#zone) Floor Area to determine the maximum lighting level as described in the Lighting Level field. The choice from the method field should be “watts/area”.
Field: Watts per Person[LINK]
This factor (watts/person) is used, along with the number of occupants (people) to determine the maximum lighting level as described in the Lighting Level field. The choice from the method field should be “watts/person”.
Heat Gains from Lights:[LINK]
The electrical input to lighting ultimately appears as heat that contributes to zone loads or to return air heat gains. In EnergyPlus this heat is divided into four different fractions. Three of these are given by the input fields Return Air Fraction, Fraction Radiant and Fraction Visible. A fourth, defined as the fraction of the heat from lights convected to the zone air, is calculated by the program as:
fconvected = 1.0 – (Return Air Fraction + Fraction Radiant + Fraction Visible)
You will get an error message if Return Air Fraction + Fraction Radiant + Fraction Visible exceeds 1.0.
These fractions depend on the type of lamp and luminaire, whether the luminaire is vented to the return air, etc.
Field: Return Air Fraction[LINK]
The fraction of the heat from lights that goes into the zone return air (i.e., into the zone outlet node). If the return air flow is zero or the zone has no return air system, the program will put this fraction into the zone air. Return Air Fraction should be non-zero only for luminaires that are return-air ducted (see Table 14 and Figure 43). (However, see the field “Return Air Fraction Is Calculated from Plenum Temperature,” below, for an approach to modeling the case where Return Air Fraction is caused by conduction between a luminaire that is in contact with a return-air plenum.)
Field: Fraction Radiant[LINK]
The fraction of heat from lights that goes into the zone as long-wave (thermal) radiation. The program calculates how much of this radiation is absorbed by the inside surfaces of the zone according the area times thermal absorptance product of these surfaces.
Field: Fraction Visible[LINK]
The fraction of heat from lights that goes into the zone as visible (short-wave) radiation. The program calculates how much of this radiation is absorbed by the inside surfaces of the zone according the area times solar absorptance product of these surfaces.
Approximate values of Return Air Fraction, Fraction Radiant and Fraction Visible are given in Table 14 for overhead fluorescent lighting for the luminaire configurations shown in Figure 43.
Field: Fraction Replaceable[LINK]
This field defines the daylighting control for the LIGHTS object.
If Daylighting:Controls or Daylighting:DELight:Controls is specified for the zone, this field is used as an on/off flag for dimming controls. If set to 0.0, the lights are not dimmed by the daylighting controls. If set to 1.0, the lights are allowed to be dimmed by the daylighting controls.
Field: End-Use Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory, e.g., “Task Lights”, “Hall Lights”, etc. A new meter for reporting is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly) and). Subcategories are also reported in the ABUPS table. If this field is omitted or blank, the lights will be assigned to the “General” end-use subcategory.
Field: Return Air Fraction Calculated from Plenum Temperature[LINK]
Accepts values Yes or No (the default). Yes is for advanced used only. In this case the program will calculate the return air fraction by assuming that it is due to conduction of some of the light heat into the zone’s return air plenum and that the amount of the conduction depends on the plenum air temperature. A Yes value should only be used for luminaires that are recessed and non-vented, as shown in Figure 44.
The value you enter for the Return Air Fraction field will be ignored and you can enter, for fluorescent lighting, Fraction Radiant = 0.37 and Fraction Visible = 0.18, as indicated in Table 14.
This feature requires that the coefficients described below be determined from measurements or detailed calculations since they are very sensitive to the luminaire type, lamp type, thermal resistance between fixture and plenum, etc.
If “Return Air Fraction Is Calculated from Plenum Temperature” = Yes, the return air fraction is calculated each timestep from the following empirical correlation:
(Return Air Fraction)calculated = C1 – C2 x Tplenum
where Tplenum is the previous-time-step value of the return plenum air temperature (C),
and C1 and C2 are the values of the coefficients entered in the next two fields.
To compensate for the change in the return air fraction relative to its input value, the program modifies Fraction Radiant and fconvected by a scale factor such that
(Return Air Fraction)calculated + (Fraction Radiant)modified+ (fconvected)modified + (Fraction Visible)input = 1.0
It is assumed that Fraction Visible is a constant equal to its input value.
Field: Return Air Fraction Function of Plenum Temperature Coefficient 1[LINK]
The coefficient C1 in the equation for (Return Air Fraction)calculated.
Field: Return Air Fraction Function of Plenum Temperature Coefficient 2[LINK]
The coefficient C2 in the equation for (Return Air Fraction)calculated. Its units are 1/OC.
An IDF example:
Global Lights Object:
Lights Report Outputs[LINK]
If daylighting controls are operating in the zone, all of the Lights objects with a Fraction Replaceble greater than zero will be reduced by a multiplicative factor that accounts for how much the electric lighting is lowered due to daylighting.
Lights objects have output variables for individual objects and for zone totals.
Lights Electric Power [W][LINK]
The electric power input for the lights.
Lights Radiant Heating Rate [W][LINK]
Lights Radiant Heating Energy [J][LINK]
The amount of heat gain from lights that is in the form of long-wave (thermal) radiation entering the zone. This heat is absorbed by the inside surfaces of the zone according to an area times long-wave absorptance weighting scheme.
Lights Visible Radiation Heating Rate [W][LINK]
Lights Visible Radiation Heating Energy [J][LINK]
The amount of heat gain from lights that is in the form of visible (short-wave) radiation entering the zone. This heat is absorbed by the inside surfaces of the zone according to an area times short-wave absorptance weighting scheme.
Lights Convective Heating Rate [W][LINK]
Lights Convective Heating Energy [J][LINK]
The amount of heat gain from lights that is convected to the zone air.
Lights Return Air Heating Rate [W][LINK]
Lights Return Air Heating Energy [J][LINK]
The amount of heat gain from lights that goes into the zone’s return air (and, therefore, does not directly contribute to the zone load). If the zone has no return air system or the zone’s air system is off, this heat will be added to the zone air.
Lights Total Heating Rate [W][LINK]
Lights Total Heating Energy [J][LINK]
The total heat gain from lights. It is the sum of the following four outputs, i.e., Total Heat Gain = Return Air Heat Gain + Radiant Heat Gain + Visible Heat Gain + Convective Heat Gain. It is also equal to the electrical input to the lights.
Lights Electric Energy [J][LINK]
The lighting electrical consumption including ballasts, if present. These will have the same value as Lights Total Heating Energy (above).
Zone Lights Electric Power [W][LINK]
The electric power input for all lights in the zone.
Zone Lights Radiant Heating Rate [W][LINK]
Zone Lights Radiant Heating Energy [J][LINK]
The amount of heat gain from all lights in the zone that is in the form of long-wave (thermal) radiation entering the zone. This heat is absorbed by the inside surfaces of the zone according to an area times long-wave absorptance weighting scheme.
Zone Lights Visible Radiation Heating Rate [W][LINK]
Zone Lights Visible Radiation Heating Energy [J][LINK]
The amount of heat gain from all lights in the zone that is in the form of visible (short-wave) radiation entering the zone. This heat is absorbed by the inside surfaces of the zone according to an area times short-wave absorptance weighting scheme.
Zone Lights Convective Heating Rate [W][LINK]
Zone Lights Convective Heating Energy [J][LINK]
The amount of heat gain from all lights in the zone that is convected to the zone air.
Zone Lights Return Air Heating Rate [W][LINK]
Zone Lights Return Air Heating Energy [J][LINK]
The amount of heat gain from all lights in the zone that goes into the zone’s return air (and, therefore, does not directly contribute to the zone load). If the zone has no return air system or the zone’s air system is off, this heat will be added to the zone air.
Zone Lights Total Heating Rate [W][LINK]
Zone Lights Total Heating Energy [J][LINK]
The total heat gain from all lights in the zone. It is the sum of the following four outputs, i.e., Total Heat Gain = Return Air Heat Gain + Radiant Heat Gain + Visible Heat Gain + Convective Heat Gain. It is also equal to the electrical input to the lights.
Zone Lights Electric Energy [J][LINK]
The lighting electrical consumption for all lights in the zone including ballasts, if present. This will have the same value as Zone](page-011.html#zone) [Lights Total Heating Energy (above). However, this amount is also shown in the Electricity meters that are associated with the zone:
Electricity:Facility,
Electricity:Building,
Electricity:Zone:.
In addition, depending on use, it will be shown in:
InteriorLights: Electricity and
InteriorLights:Electricity:Zone :.
Meters for Lights Outputs[LINK]
As described in the Lights Outputs, values for lights will show up on the following meters:
ElectricEquipment[LINK]
Field: Name[LINK]
The name of the ElectricEquipment object.
Field: Zone or ZoneList Name[LINK]
This field is the name of the zone (ref: [Zone](../input-output-reference/page-011.html#zone)) or [ZoneList](../input-output-reference/page-011.html#zonelist) (ref: [ZoneList](../input-output-reference/page-011.html#zonelist)) and attaches a particular electric equipment statement to a thermal zone or set of thermal zones in the building. When the [ZoneList](../input-output-reference/page-011.html#zonelist) option is used then this electric equipment definition is applied to each of the zones in the zone list effecting a global definition for the amount of electric wattage in the zone. The Zonelist option can be used effectively with the watts/area and watts/person options of the Design Level Calculation Method.
The name of the actual electric equipment object becomes <Zone](page-011.html#zone) Name> <[ElectricEquipment Object Name> and should be less than the standard length (100 characters) for a name field. If it is greater than this standard length, it may be difficult to specify in output reporting as it will be truncated. A warning will be shown if the generated name is greater than 100 characters. If it duplicates another such concatenated name, there will be a severe error and terminate the run.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the design level parameter for electric equipment (see Design Level Calculation Method field and related subsequent fields). The schedule values can be any positive number. The actual electrical input for equipment in a zone as defined by this statement is the product of the design level field and the value of the schedule specified by name in this field.
Field: Design Level Calculation Method[LINK]
This field is a key/choice field that tells which of the next three fields are filled and is descriptive of the method for calculating the nominal electric equipment level in the [Zone](../input-output-reference/page-011.html#zone). The key/choices are:
Field: Design Level[LINK]
This field (in Watts) is typically used to represent the maximum electrical input to equipment in a zone that is then multiplied by a schedule fraction (see previous field). In EnergyPlus, this is slightly more flexible in that the electric equipment design level could be a “diversity factor” applied to a schedule of real numbers. Note that while the schedule value can vary from hour to hour, the design level field is constant for all simulation environments.
Field: Watts per Zone Floor Area[LINK]
This factor (watts/m2) is used, along with the [Zone](../input-output-reference/page-011.html#zone) Area to determine the maximum equipment level as described in the Design Level field. The choice from the method field should be “Watts/Area”.
Field: Watts per Person[LINK]
This factor (watts/person) is used, along with the number of occupants (people) to determine the maximum equipment level as described in the Design Level field. The choice from the method field should be “Watts/Person”.
Heat Gains from Electric Equipment:[LINK]
The electrical input to the equipment ultimately appears as heat that contributes to zone loads. In EnergyPlus this heat is divided into four different fractions. Three of these are given by the input fields Fraction Latent, Fraction Radiant and Fraction Lost. A fourth, defined as the fraction of the heat from electric equipment convected to the zone air, is calculated by the program as:
fconvected = 1.0 – (Fraction Latent + Fraction Radiant + Fraction Lost)
You will get an error message if Fraction Latent + Fraction Radiant + Fraction Lost exceeds 1.0.
Field: Fraction Latent[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of latent heat given off by electric equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by electric equipment to give the amount of latent energy produced by the electric equipment. This energy affects the moisture balance within the zone.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of long-wave radiant heat being given off by electric equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by electric equipment to give the amount of long wavelength radiation gain from electric equipment in a zone.
Field: Fraction Lost[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of “lost” heat being given off by electric equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by electric equipment to give the amount of heat which is “lost” and does not impact the zone energy balances. This might correspond to electrical energy converted to mechanical work or heat that is vented to the atmosphere.
Field: End-Use Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory, e.g., “Computers”, “Copy Machines”, etc. A new meter for reporting is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly) object). Subcategories are also reported in the ABUPS table. If this field is omitted or blank, the equipment will be assigned to the “General” end-use subcategory.
An IDF example:
Global ElectricEquipment example:
GasEquipment[LINK]
Field: Name[LINK]
The name of the GasEquipment object.
Field: Zone or ZoneList Name[LINK]
This field is the name of the thermal zone (ref: [Zone](../input-output-reference/page-011.html#zone)) or [ZoneList](../input-output-reference/page-011.html#zonelist) (ref: [ZoneList](../input-output-reference/page-011.html#zonelist)) and attaches a particular gas equipment statement to a thermal zone or set of thermal zones in the building. When the [ZoneList](../input-output-reference/page-011.html#zonelist) option is used then this gas equipment definition is applied to each of the zones in the zone list effecting a global definition for the amount of gas in the zone. The Zonelist option can be used effectively with the watts/area and watts/person options of the Design Level Calculation Method.
The name of the actual gas equipment object becomes <Zone](page-011.html#zone) Name> <[GasEquipment Object Name> and should be less than the standard length (100 characters) for a name field. If it is greater than this standard length, it may be difficult to specify in output reporting as it will be truncated. A warning will be shown if the generated name is greater than 100 characters. If it duplicates another such concatenated name, there will be a severe error and terminate the run.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the design level parameter for gas equipment (see Design Level Calculation Method field and related subsequent fields). The schedule values can be any positive number. The actual energy input for gas equipment in a zone as defined by this statement is the product of the design level field and the value of the schedule specified by name in this field.
Field: Design Level Calculation Method[LINK]
This field is a key/choice field that tells which of the next three fields are filled and is descriptive of the method for calculating the nominal gas equipment level in the [Zone](../input-output-reference/page-011.html#zone). The key/choices are:
Field: Design Level[LINK]
This field (in Watts) is typically used to represent the maximum energy input to gas equipment in a zone that is then multiplied by a schedule fraction (see previous field). In EnergyPlus, this is slightly more flexible in that the gas equipment design level could be a “diversity factor” applied to a schedule of real numbers. Note that while the schedule value can vary from hour to hour, the design level field is constant for all simulation environments.
Field: Power per Zone Floor Area[LINK]
This factor (watts/m2) is used, along with the [Zone](../input-output-reference/page-011.html#zone) Area to determine the maximum equipment level as described in the Design Level field. The choice from the method field should be “Watts/Area” or “Power/Area”.
Field: Power per Person[LINK]
This factor (watts/person) is used, along with the number of occupants (people) to determine the maximum equipment level as described in the Design Level field. The choice from the method field should be “Watts/Person” or “Power/Person”.
Heat Gains from Gas Equipment:[LINK]
The fuel input to the equipment ultimately appears as heat that contributes to zone loads. In EnergyPlus this heat is divided into four different fractions. Three of these are given by the input fields Fraction Latent, Fraction Radiant and Fraction Lost. A fourth, defined as the fraction of the heat from gas equipment convected to the zone air, is calculated by the program as:
fconvected = 1.0 – (Fraction Latent + Fraction Radiant + Fraction Lost)
You will get an error message if Fraction Latent + Fraction Radiant + Fraction Lost exceeds 1.0.
Field: Fraction Latent[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of latent heat given off by gas equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by gas equipment to give the amount of latent energy produced by the gas equipment. This energy affects the moisture balance within the zone.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of long-wave radiant heat being given off by gas equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by gas equipment to give the amount of long wavelength radiation gain from gas equipment in a zone.
Field: Fraction Lost[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of “lost” heat being given off by gas equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by gas equipment to give the amount of heat which is “lost” and does not impact the zone energy balances. This might correspond to input energy converted to mechanical work or heat that is vented to the atmosphere.
Field: Carbon Dioxide Generation Rate[LINK]
This numeric input field specifies carbon dioxide generation rate with units of m3/s-W. The default value of 0.0 assumes the equipment is fully vented to outdoors. In the absence of better information, the user might consider using a value of 3.45E-8 m3/s-W which assumes the equipment is not vented to outdoors. This value is converted from natural gas CO2 emission rate at 11.7 lbs CO2 per therm. The CO2~~emission rate is provided by U.S. Energy Information Administration, “Frequently Asked Questions - Environment, Questions About Environmental Emissions”, http://tonto.eia.doe.gov/ask/environment_faqs.asp#CO2_quantity, January 2010. The maximum value for this input field is 3.45E-7 m3/s-W.
Field: End-Use Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory, e.g., “Cooking”, “Clothes Drying”, etc. A new meter for reporting is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly) object). Subcategories are also reported in the ABUPS table. If this field is omitted or blank, the equipment will be assigned to the “General” end-use subcategory.
An IDF example:
Global Gas Equipment example:
HotWaterEquipment[LINK]
Field: Name[LINK]
The name of the HotWaterEquipment object.
Field: Zone or ZoneList Name[LINK]
This field is the name of the thermal zone (ref: [Zone](../input-output-reference/page-011.html#zone)) or [ZoneList](../input-output-reference/page-011.html#zonelist) (ref: [ZoneList](../input-output-reference/page-011.html#zonelist)) and attaches a particular hot water equipment statement to a thermal zone or set of thermal zones in the building. When the [ZoneList](../input-output-reference/page-011.html#zonelist) option is used then this hot water equipment definition is applied to each of the zones in the zone list effecting a global definition for the amount of hot water in the zone. The Zonelist option can be used effectively with the watts/area and watts/person options of the Design Level Calculation Method.
The name of the actual hot water equipment object becomes <Zone](page-011.html#zone) Name> <[HotWaterEquipment Object Name> and should be less than the standard length (100 characters) for a name field. If it is greater than this standard length, it may be difficult to specify in output reporting as it will be truncated. A warning will be shown if the generated name is greater than 100 characters. If it duplicates another such concatenated name, there will be a severe error and terminate the run.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the design level parameter for hot water equipment (see Design Level Calculation Method field and related subsequent fields). The schedule values can be any positive number. The actual energy input for hot water equipment in a zone as defined by this statement is the product of the design level field and the value of the schedule specified by name in this field.
Field: Design Level Calculation Method[LINK]
This field is a key/choice field that tells which of the next three fields are filled and is descriptive of the method for calculating the nominal hot water equipment level in the [Zone](../input-output-reference/page-011.html#zone). The key/choices are:
Field: Design Level[LINK]
This field (in Watts) is typically used to represent the maximum energy input to hot water equipment in a zone that is then multiplied by a schedule fraction (see previous field). In EnergyPlus, this is slightly more flexible in that the hot water equipment design level could be a “diversity factor” applied to a schedule of real numbers. Note that while the schedule value can vary from hour to hour, the design level field is constant for all simulation environments.
Field: Power per Zone Floor Area[LINK]
This factor (watts/m2) is used, along with the [Zone](../input-output-reference/page-011.html#zone) Area to determine the maximum equipment level as described in the Design Level field. The choice from the method field should be “Watts/Area” or “Power/Area”.
Field: Power per Person[LINK]
This factor (watts/person) is used, along with the number of occupants (people) to determine the maximum equipment level as described in the Design Level field. The choice from the method field should be “Watts/Person” or “Power/Person”.
Heat Gains from Hot Water Equipment:[LINK]
The fuel input to the equipment ultimately appears as heat that contributes to zone loads. In EnergyPlus this heat is divided into four different fractions. Three of these are given by the input fields Fraction Latent, Fraction Radiant and Fraction Lost. A fourth, defined as the fraction of the heat from hot water equipment convected to the zone air, is calculated by the program as:
fconvected = 1.0 – (Fraction Latent + Fraction Radiant + Fraction Lost)
You will get an error message if Fraction Latent + Fraction Radiant + Fraction Lost exceeds 1.0.
Field: Fraction Latent[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of latent heat given off by hot water equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by hot water equipment to give the amount of latent energy produced by the hot water equipment. This energy affects the moisture balance within the zone.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of long-wave radiant heat being given off by hot water equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by hot water equipment to give the amount of long wavelength radiation gain from hot water equipment in a zone.
Field: Fraction Lost[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of “lost” heat being given off by hot water equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by hot water equipment to give the amount of heat which is “lost” and does not impact the zone energy balances. This might correspond to input energy converted to mechanical work or heat that is vented to the atmosphere.
Field: End-Use Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory, e.g., “Cooking”, “Clothes Drying”, etc. A new meter for reporting is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly) obejct). Subcategories are also reported in the ABUPS table. If this field is omitted or blank, the equipment will be assigned to the “General” end-use subcategory.
IDF Examples:
Global Hot Water Equipment example:
SteamEquipment[LINK]
Field: Name[LINK]
The name of the SteamEquipment object.
Field: Zone Name[LINK]
This field is the name of the thermal zone (ref: [Zone](../input-output-reference/page-011.html#zone)) and attaches a particular steam equipment statement to a thermal zone or set of thermal zones in the building. When the [ZoneList](../input-output-reference/page-011.html#zonelist) option is used then this steam equipment definition is applied to each of the zones in the zone list effecting a global definition for the amount of steam in the zone. This option can be used effectively with the watts/area and watts/person options of the Design Level Calculation Method.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the design level parameter for steam equipment (see Design Level Calculation Method field and related subsequent fields). The schedule values can be any positive number. The actual energy input for steam equipment in a zone as defined by this statement is the product of the design level field and the value of the schedule specified by name in this field.
Field: Design Level Calculation Method[LINK]
This field is a key/choice field that tells which of the next three fields are filled and is descriptive of the method for calculating the nominal steam equipment level in the [Zone](../input-output-reference/page-011.html#zone). The key/choices are:
Field: Design Level[LINK]
This field (in Watts) is typically used to represent the maximum energy input to steam equipment in a zone that is then multiplied by a schedule fraction (see previous field). In EnergyPlus, this is slightly more flexible in that the steam equipment design level could be a “diversity factor” applied to a schedule of real numbers. Note that while the schedule value can vary from hour to hour, the design level field is constant for all simulation environments.
Field: Power per Zone Floor Area[LINK]
This factor (watts/m2) is used, along with the [Zone](../input-output-reference/page-011.html#zone) Area to determine the maximum equipment level as described in the Design Level field. The choice from the method field should be “Watts/Area” or “Power/Area”.
Field: Power per Person[LINK]
This factor (watts/person) is used, along with the number of occupants (people) to determine the maximum equipment level as described in the Design Level field. The choice from the method field should be “Watts/Person” or “Power/Person”.
Heat Gains from Steam Equipment:[LINK]
The fuel input to the equipment ultimately appears as heat that contributes to zone loads. In EnergyPlus this heat is divided into four different fractions. Three of these are given by the input fields Fraction Latent, Fraction Radiant and Fraction Lost. A fourth, defined as the fraction of the heat from steam equipment convected to the zone air, is calculated by the program as:
fconvected = 1.0 – (Fraction Latent + Fraction Radiant + Fraction Lost)
You will get an error message if Fraction Latent + Fraction Radiant + Fraction Lost exceeds 1.0.
Field: Fraction Latent[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of latent heat given off by steam equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by steam equipment to give the amount of latent energy produced by the steam equipment. This energy affects the moisture balance within the zone.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of long-wave radiant heat being given off by steam equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by steam equipment to give the amount of long wavelength radiation gain from steam equipment in a zone.
Field: Fraction Lost[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of “lost” heat being given off by steam equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by steam equipment to give the amount of heat which is “lost” and does not impact the zone energy balances. This might correspond to input energy converted to mechanical work or heat that is vented to the atmosphere.
Field: End-Use Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory, e.g., “Cooking”, “Clothes Drying”, etc. A new meter for reporting is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly) object). Subcategories are also reported in the ABUPS table. If this field is omitted or blank, the equipment will be assigned to the “General” end-use subcategory.
IDF Examples:
OtherEquipment[LINK]
Other Equipment object is provided as an additional source for heat gains or losses directly to the zone. That is to say, a loss can be entered by putting a negative value into the Design Level field(s). Note, too, that this object does not have an end-use component – gains or losses do not show up in the bottom energy lines (except as influencing overall zone gains or losses).
Field: Name[LINK]
The name of the OtherEquipment object.
Field: Zone Name[LINK]
This field is the name of the thermal zone (ref: [Zone](../input-output-reference/page-011.html#zone)) and attaches a particular other equipment statement to a thermal zone or set of thermal zones in the building. When the [ZoneList](../input-output-reference/page-011.html#zonelist) option is used then this other equipment definition is applied to each of the zones in the zone list effecting a global definition for the amount of other in the zone. This option can be used effectively with the watts/area and watts/person options of the Design Level Calculation Method.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the design level parameter for other equipment (see Design Level Calculation Method field and related subsequent fields). The schedule values can be any positive number. The actual energy input for other equipment in a zone as defined by this statement is the product of the design level field and the value of the schedule specified by name in this field.
Field: Design Level Calculation Method[LINK]
This field is a key/choice field that tells which of the next three fields are filled and is descriptive of the method for calculating the nominal other equipment level in the [Zone](../input-output-reference/page-011.html#zone). The key/choices are:
Field: Design Level[LINK]
This field (in Watts) is typically used to represent the maximum energy input to other equipment in a zone that is then multiplied by a schedule fraction (see previous field). In EnergyPlus, this is slightly more flexible in that the other equipment design level could be a “diversity factor” applied to a schedule of real numbers. This value can be negative to denote a loss. Note that while the schedule value can vary from hour to hour, the design level field is constant for all simulation environments.
Field: Power per Zone Floor Area[LINK]
This factor (watts/m2) is used, along with the [Zone](../input-output-reference/page-011.html#zone) Area to determine the maximum equipment level as described in the Design Level field. This value can be negative to denote a loss. The choice from the method field should be “Watts/Area” or “Power/Area”.
Field: Power per Person[LINK]
This factor (watts/person) is used, along with the number of occupants (people) to determine the maximum equipment level as described in the Design Level field. This value can be negative to denote a loss. The choice from the method field should be “Watts/Person” or “Power/Person”.
Heat Gains/Losses from Other Equipment:[LINK]
The fuel input to the equipment ultimately appears as heat that contributes to zone loads. In EnergyPlus this heat is divided into four different fractions. Three of these are given by the input fields Fraction Latent, Fraction Radiant and Fraction Lost. A fourth, defined as the fraction of the heat from other equipment convected to the zone air, is calculated by the program as:
fconvected = 1.0 – (Fraction Latent + Fraction Radiant + Fraction Lost)
You will get an error message if Fraction Latent + Fraction Radiant + Fraction Lost exceeds 1.0.
Field: Fraction Latent[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of latent heat given off by other equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by other equipment to give the amount of latent energy produced by the other equipment. This energy affects the moisture balance within the zone.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of long-wave radiant heat being given off by other equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by other equipment to give the amount of long wavelength radiation gain from other equipment in a zone.
Field: Fraction Lost[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the amount of “lost” heat being given off by other equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by other equipment to give the amount of heat which is “lost” and does not impact the zone energy balances. This might correspond to input energy converted to mechanical work or heat that is vented to the atmosphere.
IDF Examples
Electric, Gas, Other, HotWater, Steam Equipment Outputs[LINK]
Each type of equipment object has output variables for individual objects and for zone totals.
Electric Equipment Electric Power [W][LINK]
Gas Equipment Gas Rate [W][LINK]
Hot Water Equipment District Heating Rate [W][LINK]
Hot Water Equipment District Heating Energy [J][LINK]
Steam Equipment District Heating Energy [J][LINK]
Steam Equipment District Heating Rate [W][LINK]
This field is the energy consumption rate or sum for the equipment object in Watts or Joules.
Electric Equipment Radiant Heating Rate [W][LINK]
Electric Equipment Radiant Heating Energy [J][LINK]
Gas Equipment Radiant Heating Rate [W][LINK]
Gas Equipment Radiant Heating Energy [J][LINK]
Hot Water Equipment Radiant Heating Rate [W][LINK]
Hot Water Equipment Radiant Heating Energy [J][LINK]
Steam Equipment Radiant Heating Rate [W][LINK]
Steam Equipment Radiant Heating Energy [J][LINK]
Other Equipment Radiant Heating Rate [W][LINK]
Other Equipment Radiant Heating Energy [J][LINK]
This field is the amount of radiant heat gain for the equipment object in Watts (for rate) or Joules. This is determined by the current heat gain from the equipment to the zone and the “Fraction Radiant” specified in the input. The radiant gains (long wavelength) are distributed to the surfaces using an area weighting scheme.
Electric Equipment Convective Heating Rate [W][LINK]
Electric Equipment Convective Heating Energy [J][LINK]
Gas Equipment Convective Heating Rate [W][LINK]
Gas Equipment Convective Heating Energy [J][LINK]
Hot Water Equipment Convective Heating Rate [W][LINK]
Hot Water Equipment Convective Heating Energy [J][LINK]
Steam Equipment Convective Heating Rate [W][LINK]
Steam Equipment Convective Heating Energy [J][LINK]
Other Equipment Convective Heating Rate [W][LINK]
Other Equipment Convective Heating Energy [J][LINK]
This field is the amount of convective heat gain for the equipment object in Watts (for rate) or Joules. This is determined by the current heat gain from the equipment to the zone and the “Fraction Radiant”, “Fraction Lost”, “Fraction Latent” specified in input (1-FractionRadiant-FractionLost-FractionLatent = FractionConvected). The convective heat gain is added to the zone air heat balance directly.
Electric Equipment Latent Gain Rate [W][LINK]
Electric Equipment Latent Gain Energy [J][LINK]
Gas Equipment Latent Gain Rate [W][LINK]
Gas Equipment Latent Gain Energy [J][LINK]
Hot Water Equipment Latent Gain Rate [W][LINK]
Hot Water Equipment Latent Gain Energy [J][LINK]
Steam Equipment Latent Gain Rate [W][LINK]
Steam Equipment Latent Gain Energy [J][LINK]
Other Equipment Latent Gain Rate [W][LINK]
Other Equipment Latent Gain Energy [J][LINK]
This field is the amount of latent heat gain for the equipment object in Watts (for rate) or Joules. This is determined by the current heat gain from the equipment to the zone and the “Fraction Latent” specified in the input.
Electric Equipment Lost Heat Rate [W][LINK]
Electric Equipment Lost Heat Energy [J][LINK]
Gas Equipment Lost Heat Rate [W][LINK]
Gas Equipment Lost Heat Energy [J][LINK]
Hot Water Equipment Lost Heat Rate [W][LINK]
Hot Water Equipment Lost Heat Energy [J][LINK]
Steam Equipment Lost Heat Rate [W][LINK]
Steam Equipment Lost Heat Energy [J][LINK]
Other Equipment Lost Heat Rate [W][LINK]
Other Equipment Lost Heat Energy [J][LINK]
This field is the amount of “lost” heat gain for the equipment object in Watts (for rate) or Joules. This is determined by the current heat gain from the equipment to the zone and the “Fraction Lost” specified in the input. This amount does not affect the energy heat balance in the zone.
Electric Equipment Total Heating Rate [W][LINK]
Electric Equipment Total Heating Energy [J][LINK]
Gas Equipment Total Heating Rate [W][LINK]
Gas Equipment Total Heating Energy [J][LINK]
Hot Water Equipment Total Heating Rate [W][LINK]
Hot Water Equipment Total Heating Energy [J][LINK]
Steam Equipment Total Heating Rate [W][LINK]
Steam Equipment Total Heating Energy [J][LINK]
Other Equipment Total Heating Rate [W][LINK]
Other Equipment Total Heating Energy [J][LINK]
The total heat gain field is sum of several other fields (radiant, latent, convective). This field is expressed in Watts (for rate) or joules.
Electric Equipment Electric Energy [J][LINK]
The electric equipment consumption field is sum of the other fields (radiant, latent, convective, lost). This field is expressed in joules.
Gas Equipment Gas Energy [J][LINK]
The gas equipment consumption field is sum of the other fields (radiant, latent, convective, lost). This field is expressed in joules.
Hot Water Equipment Purchased Heating Consumption [J][LINK]
Steam Equipment Purchased Heating Consumption [J][LINK]
The equipment consumption field is sum of the other fields (radiant, latent, convective, lost). This field is expressed in joules.
Zone Electric Equipment Electric Power [W][LINK]
Zone Gas Equipment Gas Rate [W][LINK]
Zone Hot Water Equipment District Heating Rate W][LINK]
Zone Steam Equipment District Heating Rate [W][LINK]
This field is the energy consumption rate for all equipment within the zone in Watts.
Zone Electric Equipment Radiant Heating Rate [W][LINK]
Zone Electric Equipment Radiant Heating Energy [J][LINK]
Zone Gas Equipment Radiant Heating Rate [W][LINK]
Zone Gas Equipment Radiant Heating Energy [J][LINK]
Zone Hot Water Equipment Radiant Heating Rate [W][LINK]
Zone Hot Water Equipment Radiant Heating Energy [J][LINK]
Zone Steam Equipment Radiant Heating Rate [W][LINK]
Zone Steam Equipment Radiant Heating Energy [J][LINK]
Zone Other Equipment Radiant Heating Rate [W][LINK]
Zone Other Equipment Radiant Heating Energy [J][LINK]
This field is the amount of radiant heat gain for all equipment within the zone in Watts (for rate) or Joules. This is determined by the current heat gain from the equipment to the zone and the “Fraction Radiant” specified in the input. The radiant gains (long wavelength) are distributed to the surfaces using an area weighting scheme.
Zone Electric Equipment Convective Heating Rate [W][LINK]
Zone Electric Equipment Convective Heating Energy [J][LINK]
Zone Gas Equipment Convective Heating Rate [W][LINK]
Zone Gas Equipment Convective Heating Energy [J][LINK]
Zone Hot Water Equipment Convective Heating Rate [W][LINK]
Zone Hot Water Equipment Convective Heating Energy [J][LINK]
Zone Steam Equipment Convective Heating Rate [W][LINK]
Zone Steam Equipment Convective Heating Energy [J][LINK]
Zone Other Equipment Convective Heating Rate [W][LINK]
Zone Other Equipment Convective Heating Energy [J][LINK]
This field is the amount of convective heat gain for all equipment within the zone in Watts (for rate) or Joules. This is determined by the current heat gain from the equipment to the zone and the “Fraction Radiant”, “Fraction Lost”, “Fraction Latent” specified in input (1-FractionRadiant-FractionLost-FractionLatent = FractionConvected). The convective heat gain is added to the zone air heat balance directly.
Zone Electric Equipment Latent Gain Rate [W][LINK]
Zone Electric Equipment Latent Gain Energy [J][LINK]
Zone Gas Equipment Latent Gain Rate [W][LINK]
Zone Gas Equipment Latent Gain Energy [J][LINK]
Zone Hot Water Equipment Latent Gain Rate [W][LINK]
Zone Hot Water Equipment Latent Gain Energy [J][LINK]
Zone Steam Equipment Latent Gain Rate [W][LINK]
Zone Steam Equipment Latent Gain Energy [J][LINK]
Zone Other Equipment Latent Gain Rate [W][LINK]
Zone Other Equipment Latent Gain Energy [J][LINK]
This field is the amount of latent heat gain for all equipment within the zone in Watts (for rate) or Joules. This is determined by the current heat gain from the equipment to the zone and the “Fraction Latent” specified in the input.
Zone Electric Equipment Lost Heat Rate [W][LINK]
Zone Electric Equipment Lost Heat Energy [J][LINK]
Zone Gas Equipment Lost Heat Rate [W][LINK]
Zone Gas Equipment Lost Heat Energy [J][LINK]
Zone Hot Water Equipment Lost Heat Rate [W][LINK]
Zone Hot Water Equipment Lost Heat Energy [J][LINK]
Zone Steam Equipment Lost Heat Rate [W][LINK]
Zone Steam Equipment Lost Heat Energy [J][LINK]
Zone Other Equipment Lost Heat Rate [W][LINK]
Zone Other Equipment Lost Heat Energy [J][LINK]
This field is the amount of “lost” heat gain for all equipment within the zone in Watts (for rate) or Joules. This is determined by the current heat gain from the equipment to the zone and the “Fraction Lost” specified in the input. This amount does not affect the energy heat balance in the zone.
Zone Electric Equipment Total Heating Rate [W][LINK]
Zone Electric Equipment Total Heating Energy [J][LINK]
Zone Gas Equipment Total Heating Rate [W][LINK]
Zone Gas Equipment Total Heating Energy [J][LINK]
Zone Hot Water Equipment Total Heating Rate [W][LINK]
Zone Hot Water Equipment Total Heating Energy [J][LINK]
Zone Steam Equipment Total Heating Rate [W][LINK]
Zone Steam Equipment Total Heating Energy [J][LINK]
Zone Other Equipment Total Heating Rate [W][LINK]
Zone Other Equipment Total Heating Energy [J][LINK]
The total heat gain field is sum of several other fields (radiant, latent, convective) for all equipment in the zone. This field is expressed in Watts (for rate) or joules.
Zone Electric Equipment Electric Energy [J][LINK]
The electric equipment consumption field is sum of the other fields (radiant, latent, convective, lost) for all equipment in the zone. This field is expressed in joules. This amount is also shown in the Electricity meters that are associated with the zone – Electricity:Facility, Electricity:Buidling, Electricity:Zone:, and InteriorEquipment:Electricity.
Zone Gas Equipment Gas Energy [J][LINK]
The gas equipment consumption field is sum of the other fields (radiant, latent, convective, lost) for all equipment in the zone. This field is expressed in joules. This amount is also shown in the Gas meters that are associated with the zone – Gas:Facility, Gas:Building, Gas:Zone:, and InteriorEquipment:Gas. Gas, here, refers to “Natural Gas” fuel.
Zone Hot Water Equipment District Heating Energy [J][LINK]
Zone Steam Equipment District Heating Energy [J][LINK]
The equipment consumption field is sum of the other fields (radiant, latent, convective, lost) for all equipment in the zone. This field is expressed in joules. These amounts are shown on the District Heating meters.
ZoneContaminantSourceAndSink:CarbonDioxide[LINK]
The ZoneContaminantSourceAndSink:CarbonDioxide object allows users to input carbon dioxide sources or sinks in a zone. Note that carbon dioxide generation within a zone can also be specified using People and GasEquipment objects. Multiple ZoneContaminantSourceAndSink:CarbonDioxide objects can be specified for the same zone.
Field: Name[LINK]
The name of the ZoneContaminantSourceAndSink:CarbonDioxide object. The name for each ZoneContaminantSourceAndSink:CarbonDioxide object must be unique.
Field: Zone Name[LINK]
This field is the name of the zone (ref: Zone) and links a particular ZoneContaminantSourceAndSink:CarbonDioxide object to a thermal zone in the building.
Field: Design Generation Rate[LINK]
This field denotes the design carbon dioxide generation rate (m3/s). The design value is modified by the schedule fraction (see Field: Schedule Name). The resulting volumetric generation rate is converted to mass generation rate using the current zone indoor air density at each time step. The rate can be either positive or negative. A positive value represents a source rate (CO2 addition to the zone air) and a negative value represents a sink rate (CO2 removal from the zone air).
Field: Schedule Name[LINK]
This field is the name of the schedule (ref: Schedules) that modifies the design carbon dioxide generation rate (see previous field). The schedule values can be any positive number between 0.0 and 1.0. For each simulation time step, the actual CO2~~generation rate in a zone is the product of the Design Generation Rate field (above) and the value specified by this schedule.
An IDF example is provided below:
ZoneContaminantSourceAndSink:CarbonDioxide Outputs[LINK]
Contaminant Source or Sink CO2 Gain Volume Flow Rate [m3/s][LINK]
This output is the net carbond dioxide internal gain/loss in m3/s for an individual ZoneContaminantSourceAndSink:CarbonDioxide object.
Zone Contaminant Source or Sink CO2 Gain Volume Flow Rate [m3/s][LINK]
This output variable reports the total (net) carbon dioxide internal gains/losses in cubic meters per second for a zone, including impacts from three objects: ZoneContaminantSourceAndSink:CarbonDioxide, People, and GasEquipment. Positive values denote carbon dioxide generation (gain or source), while negative values denote carbon dioxide removal (loss or sink).
ZoneContaminantSourceAndSink:GenericContaminant:Constant[LINK]
The ZoneContaminantSourceAndSink:GenericContaminant:Constant object specifies the generic contaminant generation rate and removal rate coefficient in a zone. The associated fraction schedules are required for allowing users to change the magnitude of sources and sinks. The object is equivalent to the combination of the constant coefficient model and the burst source model defined in the sources and sinks element types of CONTAM 3.0. The basic equation used to calculate generic contaminant source and sink for the constant model is given below:
where
Sf~~= Contaminant generic contaminant source strength [m3/s]
Gf~~= Generic contaminant generation rate [m3/s]
FG~~= Fraction value from the source fraction schedule at a given time [dimensionless]
Rf~~= Generic contaminant effective removal rate [m3/s]
FR~~= Fraction value from the sink fraction schedule at a given time [dimensionless]
Cf~~= Generic contaminant concentration value at a given previous time step [ppm]
Field: Name[LINK]
This field represents a unique identifying name in a group referring Generic contaminantSourceAndSinkNames.
Field: Zone Name[LINK]
This field signifies the Name of the zone with constant generic contaminant source and sink.
Field: Maximum Generation Rate[LINK]
This field denotes the full generic contaminant maximum generation rate (m3/s). The design generation rate is the maximum amount of generic contaminant expected at design conditions. The design value is modified by the schedule fraction (see Field:Generation Schedule Name).
Field: Generation Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design generation rate (Gf). This fraction between 0.0 and 1.0 is noted as FG in the above equation.
Field: Design Removal Coefficient[LINK]
This field denotes the full generic contaminant design removal coefficient (m3/s). The design removal rate is the maximum amount of generic contaminant expected at design conditions times the generic contaminant concentration in the same zone. The design value is modified by the schedule fraction (see Field:Removal Schedule Name).
Field: Removal Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design generation rate (Rf). This fraction between 0.0 and 1.0 is noted as FR in the above equation.
An IDF example is provided below:
ZoneContaminantSourceAndSink:GenericContaminant:Constant Outputs[LINK]
When a ZoneContaminantSourceAndSink:GenericContaminant:Constant object is specified, the following output variables are available:
Generic Air Contaminant Constant Source Generation Volume Flow Rate [m3/s][LINK]
This output is the average generic contaminant generation rate from each ZoneContaminantSourceAndSink:GenericContaminant:Constant object. The generation rate is a sum of generation and removal rates. The zone air generic contaminant level at the previous zone time step is used in the removal rate calculation.
SurfaceContaminantSourceAndSink:GenericContaminant:PressureDriven[LINK]
The SurfaceContaminantSourceAndSink:GenericContaminant:PressureDriven object specifies the generic contaminant generation rate coefficient, which is used to calculate the generation rate due to the pressure difference across the surface. The object is equivalent to the pressure driven model defined in the sources and sinks element types of CONTAM 3.0. This object assumes to work with the AirflowNetwork model. The surface has to be defined in the AirflowNetwork:Multizone:Surface. Although the model is designed to be applied to radon and soil gas entry, it is expanded to be applied to all contaminant transport, including generic contaminant. However, it should be used in caution. The basic equation used to calculate generic contaminant source for the pressure driven constant model is provided below:
where
Sf~~= Generic contaminant source strength [m3/s]
Hf~~= Generic contaminant generation rate coefficient [m3/s]
FG~~= Fraction value from the source fraction schedule at a given time [dimensionless]
n= Flow power exponent
Pi~~= [Zone](../input-output-reference/page-011.html#zone) pressure [Pa]
Pj~~= Pressure in an adjacent zone for a interior surface or outdoor for an exterior surface [Pa]
Field: Name[LINK]
The field signifies the unique identifying name in a group referring GenericContaminantSourceAndSinkNames.
Field: Surface Name[LINK]
This field represents the name of the surface as a generic contaminant source using the pressure driven model.
Field: Design Generation Rate Coefficient[LINK]
This field denotes the generic contaminant design generation coefficient (m3/s). The design generation rate is the maximum amount of generic contaminant expected at design conditions times the pressure difference with a power exponent across a surface. The design value is modified by the schedule fraction (see Field:Generation Schedule Name).
Field: Generation Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design generation rate. This fraction between 0.0 and 1.0 is noted as FG in the above equation.
An IDF example is provided below:
SurfaceContaminantSourceAndSink:GenericContaminant:PressureDriven Outputs[LINK]
When a SurfaceContaminantSourceAndSink:GenericContaminant:PressureDriven object is specified, the following output variables are available:
Generic Air Contaminant Pressure Driven Generation Volume Flow Rate [m3/s][LINK]
This output is the average generic contaminant generation rate from each SurfaceContaminantSourceAndSink:GenericContaminant:PressureDriven object.
ZoneContaminantSourceAndSink:GenericContaminant:CutoffModel[LINK]
The ZoneContaminantSourceAndSink:Generic contaminant:CutoffModel object specifies the generic contaminant generation rate based on the cutoff concentration model. The basic equation used to calculate generic contaminant source for the pressure driven constant model is given below:
where
Sf~~= Generic contaminant source strength [m3/s]
Gf~~= Generic contaminant generation rate [m3/s]
FG~~= Fraction value from the source fraction schedule at a given time [dimensionless]
Ccutoff = Cutoff concentration at which emission ceases [ppm]
Cf~~= Generic contaminant concentration value at a given previous time step [ppm]
Field: Name[LINK]
The field signifies the unique identifying name in a group referring GenericContaminantSourceAndSinkNames.
Field: Zone Name[LINK]
This field represents the name of the zone with generic contaminant source and sink using the cutoff model.
Field: Design Generation Rate[LINK]
This field denotes the full generic contaminant design generation rate (m3/s). The design generation rate is the maximum amount of generic contaminant expected at design conditions. The design value is modified by the schedule fraction (see Field:Generation Schedule Name).
Field: Generation Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design generation rate (Gf). This fraction between 0.0 and 1.0 is noted as FG in the above equation.
Field: Cutoff Concentration[LINK]
This field is the generic contaminant cutoff concentration level where the source ceases its emission.
An IDF example is provided below:
ZoneContaminantSourceAndSink:GenericContaminant:CutoffModel Outputs[LINK]
When a ZoneContaminantSourceAndSink:GenericContaminant:CutoffModel object is specified, the following output variables are available:
Generic Air Contaminant Cutoff Model Generation Volume Flow Rate [m3/s][LINK]
This output is the average generic contaminant generation rate from each SurfaceContaminantSourceAndSink:GenericContaminant: CutoffModel object.
ZoneContaminantSourceAndSink:GenericContaminant:DecaySource[LINK]
The ZoneContaminantSourceAndSink:GenericContaminant:DecaySource object specifies the generic contaminant generation rate based on the decay source model. The basic equation used to calculate generic contaminant source for the decay source model is given below:
where
Sf~~= Generic contaminant source strength [m3/s]
Gf~~= Initial generic contaminant generation rate [m3/s]
FG~~= Fraction value from the source fraction schedule at a given time [dimensionless]
t = Time since the start of emission [second]
tc = Decay time constant [second]
Field: Name[LINK]
This field is the unique identifying name in a group referring GenericContaminantSourceAndSinkNames.
Field: Zone Name[LINK]
This field represents the name of the zone with a generic contaminant decaying source.
Field: Initial Generation Rate[LINK]
This field denotes the initial generic contaminant design generation rate (m3/s). The generation is controlled by a schedule, as defined in the next field. Generic contaminant generation begins when the schedule changes from a zero to a non-zero value (between zero and one). The initial generation rate is equal to the schedule value times the initial generation rate. A single schedule may be used to initiate several emissions at different times. (see Field:Generation Schedule Name).
Field: Generation Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design generation rate (Gf). This fraction between 0.0 and 1.0 is noted as FG in the above equation. When the value is equal to 1, the generation rate is used and time is reset to zero. When the value is equal to zero, the schedule value is ignored in the equation.
Field: Decay Time Constant[LINK]
This field is the time at which the generation rate reaches 0.37 of the original rate.
An IDF example is provided below:
ZoneContaminantSourceAndSink:GenericContaminant:DecaySource Outputs[LINK]
When a ZoneContaminantSourceAndSink:GenericContaminant:DecaySource object is specified, the following output variables are available:
Generic Air Contaminant Decay Model Generation Volume Flow Rate [m3/s][LINK]
This output is the average generic contaminant decay rate from each SurfaceContaminantSourceAndSink:GenericContaminant:DecaySource object.
Generic Air Contaminant Decay Model Generation Emission Start Elapsed Time [s][LINK]
This output is the decay time since the start of emission. The start time is either at the beginning of each run period, including design day simulations, or the time when the egenration schedule value is zero.
SurfaceContaminantSourceAndSink:GenericContaminant:BoudaryLayerDiffusion[LINK]
The SurfaceContaminantSourceAndSink:GenericContaminant:BoudaryLayerDiffusion object specifies the generic contaminant generation rate from surface diffusion. The object is equivalent to the boundary layer diffusion model driven model defined in the sources and sinks element types of CONTAM 3.0.
The boundary layer diffusion controlled reversible sink/source model with a linear sorption isotherm follows the descriptions presented in [Axley 1991]. The boundary layer refers to the region above the surface of a material through which a concentration gradient exists between the near-surface concentration and the air-phase concentration. The rate at which a contaminant is transferred onto a surface (sink) is defined as:
where
h = Average film mass transfer coefficient over the sink [m/s]
= Film density of air [kg/m3]
A = Surface area of the adsorbent [m2]
Cf = Concentration in the air at the previous time step [ppm]
Cs = Concentration in the adsorbent [ppm]
k = Henry adsorption constant or partition coefficient [dimensionless]
Field: Name[LINK]
This field signifies a unique identifying name in a group referring GenericContaminanteSourceAndSinkNames.
Field: Surface Name[LINK]
This field denotes the name of the surface as a generic contaminant reversible source or sink using the boundary layer diffusion model.
Field: Film Transfer Coefficient[LINK]
This field specifies the average mass transfer coefficient of the contaminant generic contaminant within the boundary layer (or film) above the surface of the adsorbent.
Field: Henry Partition Coefficient[LINK]
This field denotes the generic contaminant Henry partition coefficient in the units of dimensionless. The coefficient relates the concentration of the contaminant generic contaminant in the bulk-air to that at the surface of the adsorption material.
An IDF example is provided below:
SurfaceContaminantSourceAndSink:GenericContaminant:BoundaryLayerDiffusion Outputs[LINK]
When a SurfaceContaminantSourceAndSink:GenericContaminant:BoudaryLayerDiffusion object is specified, the following output variables are available:
Generic Air Contaminant Boundary Layer Diffusion Generation Volume Flow Rate [m3/s][LINK]
This output is the average generic contaminant generation rate from each SurfaceContaminantSourceAndSink:GenericContaminant:BoudaryLayerDiffusion object.
Generic Air Contaminant Boundary Layer Diffusion Inside Face Concentration [ppm][LINK]
This output is the average generic contaminant level at the interior surface.
SurfaceContaminantSourceAndSink:GenericContaminant:DepositionVelocitySink[LINK]
The SurfaceContaminantSourceAndSink:GenericContaminant:DepositionVelocitySink object specifies the generic contaminant removal rate from a surface. The object is equivalent to the deposition velocity sink model defined in CONTAM 3.0 sources and sinks element types.
The deposition velocity model provides for the input of a sink’s characteristic in the familiar term of deposition velocity. The removal stops when the sink concentration level is higher than the zone air concentration level. The deposition velocity model equation is:
where
Sf(t) = Removal rate at time t [m3/s]
d~~ = Deposition velocity [m/s]
As = Deposition surface area [m2]
m = Element multiplier [dimensionless]
Cf(t) = Concentration of contaminant generic contaminant at the previous time step [ppm]
FR = Schedule or control signal value at time t [-]
Field: Name[LINK]
This field denotes a unique identifying name in a group referring GenericContaminant SourceAndSinkNames.
Field: Surface Name[LINK]
This field represents the name of the surface as a generic contaminant sink using the deposition velocity sink model.
Field: Deposition Velocity[LINK]
This field specifies the deposition velocity to the surface of the adsorbent in the units of m/s.
Field: Removal Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design removal rate (Sf). This fraction between 0.0 and 1.0 is noted as FR in the above equation.
An IDF example is provided below:
SurfaceContaminantSourceAndSink:GenericContaminant:DepositionVelocitySink Outputs[LINK]
The following output variables are available when the SurfaceContaminantSourceAndSink:GenericContaminant:DepositionVelocitySink
object is specified.
Generic Air Contaminant Deposition Velocity Removal Volume Flow Rate [m3/s][LINK]
This output is the average generic contaminant generation rate from each SurfaceContaminantSourceAndSink:GenericContaminant:DepositionVelocitySink object.
ZoneContaminantSourceAndSink:GenericContaminant:DepositionRateSink[LINK]
The ZoneContaminantSourceAndSink:GenericContaminant:DepositionRateSink object specifies the generic contaminant removal rate from a zone. The object is equivalent to the deposition rate sink model defined in CONTAM 3.0 sources and sinks element types.
The deposition rate model provides for the input of a sink’s characteristic in the familiar term of deposition rate in a zone. The removal stops when the sink concentration level is higher than the zone air concentration level. The deposition rate model equation is:
Where
Sf(t) = Removal rate at time t [m3/s]
kd = Deposition rate [1/T]
Vz = [Zone](../input-output-reference/page-011.html#zone) volume [m3]
m = Element multiplier [dimensionless]
Cf(t) = Concentration of generic contaminant at the previous time step [ppm]
FR = Schedule or control signal value at time t [dimensionless]
Field: Name[LINK]
This field denotes a unique identifying name in a group referring GenericContaminantSourceAndSinkNames.
Field: Zone Name[LINK]
This field represents the name of the zone as a generic contaminant sink using the deposition rate sink model.
Field: Deposition Rate[LINK]
This field specifies the deposition rate to the zone in the units of 1/s.
Field: Removal Schedule Name[LINK]
This field is the name of the schedule (ref: Schedule) that modifies the maximum design removal rate (Sf). This fraction between 0.0 and 1.0 is noted as FR in the above equation.
An IDF example is provided below:
ZoneContaminantSourceAndSink:GenericContaminant:DepositionRateSink Outputs[LINK]
When the ZoneContaminantSourceAndSink:GenericContaminant:DepositionRateSink object is specified, the following output variables are available:
Generic Air Contaminant Deposition Rate Removal Volume Flow Rate [m3/s][LINK]
This output is the average generic contaminant generation rate from each ZoneContaminantSourceAndSink:GenericContaminant:DepositionRateSink object.
ZoneBaseboard:OutdoorTemperatureControlled[LINK]
This object specifies outside temperature-controlled (OTC) baseboard heating. The capacities (high and low) are specified in W at the temperatures specified. The schedule allows both capacities to change hourly on a proportional basis. This baseboard heater does not operate if the outdoor dry-bulb is above the high temperature limit. Between the high temperature and the low temperature, the capacity is interpolated (linear) between the high and the low capacity values. Below the low temperature, the capacity is set at the low capacity value. This allows the user to add baseboard heat to a perimeter zone starting at a prescribed temperature and then slowly increases this capacity to a max value.
Example:
Temperature High = 10 CCapacity High = 100,000 W
Temperature Low = 0 CCapacity Low = 500,000 W
Outdoor Temperature Controlled Baseboard Heat Temperature vs. Capacity
Outdoor Dry-bulb(C)
Baseboard Output
>10
0
10
100,000
8
180,000
6
260,000
4
340,000
2
420,000
0
500,000
< 0
500,000
Field: Name[LINK]
The name of the ZoneBaseboard:OutdoorTemperatureControlled object.
Field: Zone Name[LINK]
This field is the name of the zone and attaches the baseboard heat equipment statement to a thermal zone in the building.
Field: Schedule Name[LINK]
This field is the name of the schedule that modifies the capacities (high and low) for baseboard heat equipment (see next four fields). The schedule values can be any positive number. The actual energy input for the baseboard equipment in a zone as defined by this statement depends on the actual outdoor temperature and where that temperature is in the range of Low Temperature to High Temperature..
Field: Capacity at Low Temperature[LINK]
This is the baseboard equipment capacity (Watts) at the low temperature limit.
Field: Low Temperature[LINK]
If the outdoor dry-bulb temperature (degrees Celsius) is at or below the low temperature the baseboard heater operates at the low temperature capacity.
Field: Capacity at High Temperature[LINK]
This is the baseboard equipment capacity (Watts) at the high temperature limit.
Field: High Temperature[LINK]
If the outdoor dry-bulb temperature (degrees Celsius) is greater than the high temperature the baseboard heater will not operate.
Field: Fraction Radiant[LINK]
This field is a decimal number between 0.0 and 1.0 and is used to characterize the type of heat being given off by baseboard heat equipment in a zone. The number specified in this field will be multiplied by the total energy consumed by the baseboard heat equipment to give the amount of long wavelength radiation gain to the zone.
Field: End-Use Subcategory[LINK]
Allows you to specify a user-defined end-use subcategory, e.g., “Perimeter Baseboards”, etc. A new meter for reporting is created for each unique subcategory (ref: [Output:Meter](../input-output-reference/page-089.html#outputmeter-and-outputmetermeterfileonly) object). Subcategories are also reported in the ABUPS table. If this field is omitted or blank, the baseboard equipment will be assigned to the “General” end-use subcategory.
An IDF example:
ZoneBaseboard:OutdoorTemperatureControlled Output[LINK]
ZoneBaseboard:OutdoorTemperatureControlled objects have output variables for individual objects and for zone totals. The following outputs are available:
Baseboard Electric Power [W][LINK]
This field is the electric power for the ZoneBaseboard:OutdoorTemperatureControlled object in Watts.
Baseboard Electric Energy [J][LINK]
The outdoor temperature controlled baseboard heat option is assumed to be fueled by electricity. This field is the same as the Baseboard Total Heating Energy (above) in joules.
Baseboard Radiant Heating Rate [W][LINK]
Baseboard Radiant Heating Energy [J][LINK]
These output variables are the amount of radiant heat gain for the ZoneBaseboard:OutdoorTemperatureControlled object in Watts (for rate) or Joules. This is determined by the current heat gain from the heater to the zone and the “Fraction Radiant” specified in the input. The radiant gains (long wavelength) are distributed to the surfaces using an area weighting scheme.
Baseboard Convective Heating Rate [W][LINK]
Baseboard Convective Heating Energy [J][LINK]
These output variables are the amount of convective heat gain for the ZoneBaseboard:OutdoorTemperatureControlled object in Watts (for rate) or Joules. This is determined by the current heat gain from the heater to the zone and the “Fraction Radiant” specified in input (1-FractionRadiant = FractionConvected). The convective heat gain is added to the zone air heat balance directly.
Baseboard Total Heating Rate [W][LINK]
Baseboard Total Heating Energy [J][LINK]
These output variables are the amount of heat gain for the ZoneBaseboard:OutdoorTemperatureControlled object in Watts (for rate) or Joules. This is determined by the sum of the radiant and convective heat gains from the baseboard heat.
Zone Baseboard Electric Power [W][LINK]
This field is the electric power for all ZoneBaseboard:OutdoorTemperatureControlled objects within the zone in Watts.
Zone Baseboard Electric Energy [J][LINK]
The outdoor temperature controlled baseboard heat option is assumed to be fueled by electricity. This field is the same as the Baseboard Total Heating Energy (above) in joules. However, this amount is also shown in the Electricity meters that are associated with the zone – Electricity:Facility, Electricity:Buidling, Electricity:Zone:, and InteriorEquipment:Electricity.
Zone Baseboard Radiant Heating Rate [W][LINK]
Zone Baseboard Radiant Heating Energy [J][LINK]
These output variables are the amount of radiant heat gain for all ZoneBaseboard:OutdoorTemperatureControlled objects within the zone in Watts (for rate) or Joules. This is determined by the current heat gain from the heater to the zone and the “Fraction Radiant” specified in the input. The radiant gains (long wavelength) are distributed to the surfaces using an area weighting scheme.
Zone Baseboard Convective Heating Rate [W][LINK]
Zone Baseboard Convective Heating Energy [J][LINK]
These output variables are the amount of convective heat gain for all ZoneBaseboard:OutdoorTemperatureControlled objects within the zone in Watts (for rate) or Joules. This is determined by the current heat gain from the heater to the zone and the “Fraction Radiant” specified in input (1-FractionRadiant = FractionConvected). The convective heat gain is added to the zone air heat balance directly.
Zone Baseboard Total Heating Rate [W][LINK]
Zone Baseboard Total Heating Energy [J][LINK]
These output variables are the amount of heat gain for all ZoneBaseboard:OutdoorTemperatureControlled objects within the zone in Watts (for rate) or Joules. This is determined by the sum of the radiant and convective heat gains from the baseboard heat.
Meters for Equipment Outputs[LINK]
As described in each of the equipment sections, values for specific equipments will show up on the following meters:
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.