The air-to-air flat plate heat exchanger is an HVAC
component typically used for exhaust or relief air heat
recovery. The user can choose the flow arrangement type:
counter flow, parallel flow, or cross flow with both streams
unmixed. The input requires no geometric data. Performance is
defined by specifying primary outlet air temperature at
nominal (user specified) inlet conditions. In addition, the
ratio (h\(^{.}\)A)\(_{p}\) / (h\(^{.}\)A)\(_{s}\) at nominal flow needs to
be input, where h is the convective heat transfer coefficient,
A is the surface area, p stands for primary side, s for
secondary side.
If the heat exchanger is operated in conjunction with an
outdoor air economizer (economizer lockout set to
Yes), the nominal supply air flow rate should be set
equal to the minimum outdoor air flow rate specified in the Controller:OutdoorAir.
The heat exchanger detects that the economizer is operating by
the fact that its inlet air flow rate is greater than its
nominal supply air flow rate.
A unique user-assigned name for a particular air-to-air
flat plate heat exchanger unit. Any reference to this unit by
another object will use this name.
The name of the schedule (ref: Schedule) that denotes
whether the unit can run during a given time period. A
schedule value of 0 indicates that the unit is off for that
time period. A schedule value greater than 0 indicates that
the unit can operate during the time period. If this field is
blank, the schedule has values of 1 for all time periods.
This input denotes whether the heat exchanger unit is
locked out (bypassed) when the air-side economizer is
operating. Both the economizer and high humidity control (Ref.
Controller:OutdoorAir) activate the heat exchanger lockout as
specified by this input. The input choices are Yes
(meaning locked out) or No. The default input for
this field is Yes.
Field:
Ratio of Supply to Secondary hA Values[LINK]
The ratio (h\(^{.}\)A)\(_{p}\) / (h\(^{.}\)A)\(_{s}\) at nominal flow. h is the
surface convective heat transfer coefficient, A is the heat
transfer area, and p and s stand for primary side and
secondary side respectively. A typical value for this ratio is
1.0.
The nominal primary side air flow rate in cubic meters per
second. If the unit is operated in conjunction with an outdoor
air economizer this should be equal to the minimum outdoor air
flow rate. This field is autosizable.
The nominal secondary side air flow rate in cubic meters
per second. This field is autosizable. It is equal to the
primary side air flow rate defined above, if autosized.
Field:
Nominal Secondary Air Inlet Temperature[LINK]
The nominal secondary side air inlet temperature in
Celsius.
The electric consumption rate of the unit in watts.
Electric power is considered constant whenever the unit
operates. This input can be used to model electric power
consumption by controls (transformers, relays, etc.) and/or a
motor for a rotary heat exchanger. None of this electric power
contributes thermal load to the supply or exhaust air streams.
The default value for this field is 0.
The name of the HVAC system node to which the unit sends
its secondary outlet air.
An IDF example:
HeatExchanger:AirToAir:FlatPlate,
OA Heat Recovery 1, !- Name
FanAndCoilAvailSched, !- Availability Schedule Name
CounterFlow, !- Flow Arrangement Type
Yes, !- Economizer Lockout
1.0, !- Ratio of Supply to Secondary hA Values
0.4333, !- Nominal Supply Air Flow Rate {m3/s}
5.0, !- Nominal Supply Air Inlet Temperature {C}
15.0, !- Nominal Supply Air Outlet Temperature {C}
0.4333, !- Nominal Secondary Air Flow Rate {m3/s}
20.0, !- Nominal Secondary Air Inlet Temperature {C}
0.0, !- Nominal Electric Power {W}
Desiccant Process Outlet Node, !- Supply Air Inlet Node Name
Heat Recovery Outlet Node, !- Supply Air Outlet Node Name
Relief Air Outlet Node, !- Secondary Air Inlet Node Name
Heat Recovery Secondary Outlet Node; !- Secondary Air Outlet Node Name
This output is the sensible heating rate of the supply air
by the heat exchanger in Watts. This rate is determined using
the supply air mass flow rate through the heat exchanger unit,
the supply air inlet and outlet conditions, and the specific
heat of the inlet supply air. A positive value is reported if
the supply air is heated by the heat exchanger, else the rate
is set to zero.
This output is the latent heating rate (humidification) of
the supply air by the heat exchanger in Watts. This rate is
determined by taking the difference between the Heat Exchanger
Total Heating Rate and the Heat Exchanger Sensible Heating
Rate. A positive value is reported if the supply air is
humidified by the heat exchanger, else the rate is set to
zero.
This output is the total heating rate of the supply air by
the heat exchanger in Watts. This rate is determined using the
supply air mass flow rate through the heat exchanger unit, and
the enthalpy of the supply air entering and leaving the unit.
A positive value is reported if the enthalpy of the supply air
is increased by the heat exchanger, else the rate is set to
zero.
This output is the total heating energy added to the supply
air by the heat exchanger in Joules over the timestep being
reported.This output is also added to a meter with ResouceType
= EnergyTransfer, EndUseKey = HeatRecoveryforHeating, GroupKey
= System (ref. Output:Meter
objects).
This output is the sensible cooling rate of the supply air
by the heat exchanger in Watts. This rate is determined using
the supply air mass flow rate through the heat exchanger unit,
the supply air inlet and outlet conditions, and the specific
heat of the inlet supply air. A positive value is reported if
the supply air is cooled by the heat exchanger, else the rate
is set to zero.
This output is the latent cooling rate (dehumidification)
of the supply air by the heat exchanger in Watts. This rate is
determined by taking the difference between the Heat Exchanger
Total Cooling Rate and the Heat Exchanger Sensible Cooling
Rate. A positive value is reported if the supply air is
dehumidified by the heat exchanger, else the rate is set to
zero.
This output is the total cooling rate of the supply air by
the heat exchanger in Watts. This rate is determined using the
supply air mass flow rate through the heat exchanger unit, and
the enthalpy of the supply air entering and leaving the unit.
A positive value is reported if the enthalpy of the supply air
is decreased by the heat exchanger, else the rate is set to
zero.
This output is the total cooling energy added to the supply
air by the heat exchanger in Joules over the timestep being
reported. This output is also added to a meter with
ResouceType = EnergyTransfer, EndUseKey =
HeatRecoveryforCooling, GroupKey = System (ref. Output:Meter
objects).
This output is the electric consumption rate of the unit in
Watts. This rate is applicable whenever the unit operates
(i.e., whenever the unit is scheduled to be available and
supply and exhaust air flows exist).
This output is the electric consumption of the unit in
Joules for the timestep being reported. This ouput is also
added to a meter with ResourceType = Electricity, EndUseKey =
HeatRecovery, GroupKey = System (ref. Output:Meter
objects).
Schematic of the Sensible and
Latent Air-to-Air Heat Exchanger
The sensible and latent air-to-air heat exchanger is an
HVAC component typically used for exhaust or relief air heat
recovery (Figure 150). Heat exchanger performance can be
specified to transfer sensible energy, latent energy or both
between the supply and exhaust air streams. The input requires
no geometric data. Performance is defined by specifying
sensible and/or latent effectiveness at 75% and 100% of the
nominal (rated) supply air flow rate at two operating
conditions as shown in Table [table:operating-conditions-for-defining-heat].
Operating Conditions for Defining Heat Exchanger
Performance
Parameter
Conditions
Heating
Cooling
Entering supply air
temperature:
Dry-bulb:
1.7°C (35°F)
35°C (95°F)
Wet-bulb:
0.6°C (33°F)
26°C (78°F)
Entering exhaust air
temperature:
Dry-bulb:
21°C (70°F)
24°C (75°F)
Wet-bulb:
14°C (58°F)
17C (63F)
Note: Conditions consistent with the Air-Conditioning and
Refrigeration Institute s (ARI) Standard 1060-2001.
This object models the basic operation of an air-to-air
heat exchanger. Heat exchange between the supply and exhaust
air streams occurs whenever the unit is scheduled to be
available (Availability schedule) and supply/exhaust air flow
is present. This heat exchanger object can be used in
conjunction with a conventional air-side economizer (i.e.,
specify ModulateFlow in the Controller:OutdoorAir
object), whereby heat exchange is suspended whenever the
air-side economizer (or high humidity control) is active
(i.e., air flow is fully bypassed around a fixed-plate heat
exchanger or the rotation of a rotary heat exchanger is
stopped). This object is also able to suspend heat exchange
for the purpose of providing free cooling operation in the
absence of a conventional air-side economizer (i.e., specify
MinimumFlowWithBypass in the Controller:OutdoorAir
object).
During winter weather, humid exhaust air entering the heat
exchanger can form frost on the cold heat exchanger surfaces,
which can reduce air flow and the amount of energy recovery.
Several methods are used to control or eliminate frost
formation, and the following types can be modeled for this
heat exchanger object: supply air preheat, minimum exhaust air
temperature, exhaust air recirculation and exhaust only. For
preheat frost control, a separate heating coil object must be
placed in the supply inlet air stream to keep the air
temperature above the frost threshold temperature. The other
frost control types are modeled within this object itself
(i.e., do not require a separate object to be defined) based
on alpha and numeric inputs to this heat exchanger object.
Air-to-air heat exchangers are sometimes controlled to
maintain a fixed supply air outlet temperature to avoid
overheating when the heat exchanger is heating the supply
(primary) air. To model this control in EnergyPlus, a set
point manager object is used to establish a temperature set
point at the supply air outlet node of the heat exchanger.
Wheel speed modulation or plate supply air bypass is used to
control the supply air exiting conditions to this set point.
The set point for supply air temperature control should be set
at the minimum economizer temperature set point if an air-side
economizer is also being used by the air system. If frost
control and supply air outlet temperature control are used,
frost control takes precedence over supply air temperature
control (e.g., frost control defrost time fraction is
determined as if wheel speed modulation or plate supply air
bypass is not used).
To model a sensible and latent air-to-air heat exchanger
located in an air loop, the input data file should include the
following objects:
The sensible and latent air-to-air heat exchanger can also
be used in a number of other applications, including
conditioning outdoor ventilation air and supplying it directly
to a zone without an air loop. See object ZoneHVAC:EnergyRecoveryVentilator
for further details on this specific application.
A description of each input field for this object is
provided below.
A unique user-assigned name for a particular
sensible/latent air-to-air heat exchanger. Any reference to
this heat exchanger by another object will use this name.
The name of the schedule (ref: Schedule) that denotes
whether the unit can operate during a given time period. A
schedule value of less than or equal to 0 indicates that the
unit is off for that time period. A schedule value greater
than 0 indicates that the unit can operate during the time
period. If this field is blank, the schedule has values of 1
for all time periods.
The nominal primary side (supply) air flow rate in cubic
meters per second. The actual supply and exhaust air flow
rates must be between 50% and 130% of this value or a warning
will be issued.
Field:
Sensible Effectiveness at 100% Heating Air Flow[LINK]
The sensible heat exchange effectiveness at the
heating condition defined in Table [table:operating-conditions-for-defining-heat]
above with both the supply and exhaust air volume flow rates
equal to 100% of the nominal supply air flow rate specified in
the previous input field. The default value for this field is
0.
Field:
Latent Effectiveness at 100% Heating Air Flow[LINK]
The latent heat exchange effectiveness at the
heating condition defined in Table [table:operating-conditions-for-defining-heat]
with both the supply and exhaust air volume flow rates equal
to 100% of the nominal supply air flow rate. Specify this
value as 0.0 if the heat exchanger does not transfer latent
energy. The default value for this field is 0.
Field:
Sensible Effectiveness at 75% Heating Air Flow[LINK]
The sensible heat exchange effectiveness at the
heating condition defined in Table [table:operating-conditions-for-defining-heat]
with both the supply and exhaust air volume flow rates equal
to 75% of the nominal supply air flow rate. The default value
for this field is 0.
Field:
Latent Effectiveness at 75% Heating Air Flow[LINK]
The latent heat exchange effectiveness at the
heating condition defined in Table [table:operating-conditions-for-defining-heat]
with both the supply and exhaust air volume flow rates equal
to 75% of the nominal supply air flow rate. Specify this value
as 0.0 if the heat exchanger does not transfer latent energy.
The default value for this field is 0.
Field:
Sensible Effectiveness at 100% Cooling Air Flow[LINK]
The sensible heat exchange effectiveness at the
cooling condition defined in Table [table:operating-conditions-for-defining-heat]
with both the supply and exhaust air volume flow rates equal
to 100% of the nominal supply air flow rate. The default value
for this field is 0.
Field:
Latent Effectiveness at 100% Cooling Air Flow[LINK]
The latent heat exchange effectiveness at the
cooling condition defined in Table [table:operating-conditions-for-defining-heat]
with both the supply and exhaust air volume flow rates equal
to 100% of the nominal supply air flow rate. Specify this
value as 0.0 if the heat exchanger does not transfer latent
energy. The default value for this field is 0.
Field:
Sensible Effectiveness at 75% Cooling Air Flow[LINK]
The sensible heat exchange effectiveness at the
cooling condition defined in Table [table:operating-conditions-for-defining-heat]
with both the supply and exhaust air volume flow rates equal
to 75% of the nominal supply air flow rate. The default value
for this field is 0.
Field:
Latent Effectiveness at 75% Cooling Air Flow[LINK]
The latent heat exchange effectiveness at the
cooling condition defined in Table [table:operating-conditions-for-defining-heat]
with both the supply and exhaust air volume flow rates equal
to 75% of the nominal supply air flow rate. Specify this value
as 0.0 if the heat exchanger does not transfer latent energy.
The default value for this field is 0.
The electric consumption rate of the unit in watts.
Electric power is considered constant whenever the unit
operates. This numeric input can be used to model electric
power consumption by controls (transformers, relays, etc.)
and/or a motor for a rotary heat exchanger. None of this
electric power contributes thermal load to the supply or
exhaust air streams. The default value for this field is
0.
Field:
Supply Air Outlet Temperature Control[LINK]
This alpha field determines if the heat exchanger’s supply
air outlet is controlled to a temperature set point when the
heat exchanger is actively conditioning the supply (primary)
air. The choices for this input field are Yes or No, with the
default being No. When supply air outlet temperature control
is used, the wheel rotational speed modulates or supply air is
bypassed around the plate heat exchanger to maintain the
desired setpoint temperature. A setpoint manager object is
required to establish the desired set point at the supply air
outlet node (reference: SetpointManager:Scheduled). When an
air-side economizer is also being modeled for this air system,
the heat exchanger is deactivated during economizer operation.
Additionally, the set point for the supply air outlet
temperature control should be equal to the economizer outdoor
air temperature lower limit (reference: Controller:OutdoorAir,
field Economizer Minimum Limit Dry-Bulb Temperature), however,
any temperature set point may be used.
This alpha field denotes the type of heat exchanger being
modeled: Plate (e.g., fixed plate) or Rotary (e.g., rotating
cylinder or wheel). The default choice for this field is Plate
. The heat exchanger type affects the modeling of frost
control options and supply air outlet temperature control. For
rotary heat exchangers, rotational speed is varied to control
frost formation or the supply air outlet temperature. For
plate exchangers, air bypass around the heat exchanger is used
to obtain the desired effect.
This alpha field has four choices: None,
ExhaustAirRecirculation, ExhaustOnly and
MinimumExhaustTemperature. If this field is left blank, the
default frost control type is None . For modeling preheat
frost control, specify None for this input field and insert a
separate heating coil object in the supply inlet air stream to
keep the air temperature above the desired frost threshold
temperature.
ExhaustAirRecirculation: dampers are used to
direct exhaust air back into the zone through the supply side
of the heat exchanger when the supply (outdoor) air inlet
temperature falls below a threshold temperature (defined in
the next input field). The fraction of time that exhaust air
is circulated through the supply side of the heat exchanger is
dependent on the supply (outdoor) air inlet temperature with
respect to the threshold temperature, the initial defrost time
fraction, and the rate of change of defrost time fraction (see
Field: Rate of Defrost Time Fraction Increase). When
exhaust air is being recirculated, no supply (outdoor
ventilation) air is being provided through the heat exchanger
unit (which may or may not be acceptable regarding ventilation
for occupants).
ExhaustOnly (supply air bypass): this control
cycles off the supply air flow through the heat exchanger for
a certain period of time while the exhaust air continues to
flow through the exhaust side of the heat exchanger. The
fraction of time that the supply flow through the heat
exchanger is cycled off is dependent on the supply (outdoor)
air inlet temperature with respect to the threshold
temperature, the initial defrost time fraction, and the rate
of change of defrost time fraction (see Field: Rate of
Defrost Time Fraction Increase). When implemented in real
applications, provisions are usually made to avoid building
depressurization when this frost control is operating
(automatic or pressure-operated dampers, or a bypass air
damper around the supply side of the heat exchanger). For this
frost control type, it is assumed that the supply air is
bypassed around the heat exchanger during frost control
operation (i.e., the total supply flow is not reduced during
defrost, but merely bypassed around the heat exchanger).
MinimumExhaustTemperature: the temperature of the
exhaust air leaving the heat exchanger is monitored and the
heat exchanger effectiveness is decreased (by slowing heat
exchanger rotation or bypassing supply air around the plate
exchanger) to keep the exhaust air from falling below the
threshold temperature.
This numeric field defines the dry-bulb temperature of air
which is used to initiate frost control. The default value is
1.7 °C. For ExhaustAirRecirculation and ExhaustOnly frost
control, the threshold temperature defines the supply
(outdoor) air inlet temperature below which frost control is
active. For MinimumExhaustTemperature frost control, heat
exchanger effectiveness is controlled to keep the exhaust air
outlet temperature from falling below this threshold
temperature value.
The appropriate threshold temperature varies with exhaust
(inlet) air temperature and humidity, frost control type, heat
exchanger type, and whether the heat exchanger transfers
sensible energy alone or both sensible and latent energy
(enthalpy). Typical threshold temperatures are provided in
Table [table:typical-threshold-temperatures]
below. However, it is recommended that the user consult
manufacturer s information for the specific air-to-air heat
exchanger being modeled.
** To model preheat frost control, specify frost control
type as None and place a heating coil in the supply inlet air
stream controlled to the keep the air temperature above the
frost threshold temperature.
This numeric field defines the fraction of the simulation
timestep when frost control will be invoked when the threshold
temperature is reached. This field is only used for the
ExhaustAirRecirculation and ExhaustOnly frost control types.
The value for this field must be ≥ 0 and ≤ 1. The default time
fraction is 0.083 (e.g., 5 min / 60 min) which is typical for
ExhaustAirRecirculation frost control. Higher initial defrost
time fractions (e.g., 0.167 = 10 min / 60 min) are typically
required for ExhaustOnly frost control. For best results, the
user should obtain this information from the manufacturer.
Field:
Rate of Defrost Time Fraction Increase[LINK]
This numeric field defines the rate of increase in the
defrost time fraction as the supply (outdoor) air inlet
temperature falls below the threshold temperature. This field
is only used for the ExhaustAirRecirculation and ExhaustOnly
frost control types. The value for this field must be ≥ 0. The
default value is 0.012 (e.g., 0.72 min / 60 min per degree C
temperature difference) which is typical for
ExhaustAirRecirculation frost control. Higher values (e.g.,
0.024 = 1.44 min / 60 min per degree C temperature difference)
are typically required for ExhaustOnly frost control. For best
results, the user should obtain this information from the
manufacturer.
This value is used to determine the total defrost time
fraction as follows:
Total defrost time fraction = Initial Defrost Time Fraction
+
Rate of Defrost Time Fraction Increase \* (T$_{threshold}$ T$_{supply\\ air\\ inlet}$)
The model does not allow the total defrost time fraction to
exceed 1.0 or be less than 0.
This input denotes whether the heat exchanger unit is
locked out (bypassed for plate type heat exchangers or the
rotation is suspended for rotary type heat exchangers) when
the air-side economizer is operating. Both the economizer and
high humidity control (Ref. Controller:OutdoorAir) activate
the heat exchanger lockout as specified by this input. The
input choices are Yes (meaning locked out) or
No. The default input for this field is Yes.
Following is an example input for this heat exchanger
object:
HeatExchanger:AirToAir:SensibleAndLatent,
OA Heat Recovery 1, !- Name
FanAndCoilAvailSched, !- Availability Schedule Name
0.4333, !- Nominal Supply Air Flow Rate {m3/s}
.76, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
.68, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
.81, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
.73, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
.76, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
.68, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
.81, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
.73, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
Outside Air Inlet Node Preheated, !- Supply Air Inlet Node Name
Heat Recovery Outlet Node, !- Supply Air Outlet Node Name
Relief Air Outlet Node, !- Exhaust Air Inlet Node Name
Heat Recovery Secondary Outlet Node, !- Exhaust Air Outlet Node Name
200.0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Plate, !- Heat Exchanger Type
None; !- Frost Control Type
This output is the sensible heating rate of the supply air
by the heat exchanger in Watts. This rate is determined using
the supply air mass flow rate through the heat exchanger unit,
the supply air inlet and outlet conditions, and the specific
heat of the inlet supply air. A positive value is reported if
the supply air is heated by the heat exchanger, else the rate
is set to zero.
This output is the latent heating rate (humidification) of
the supply air by the heat exchanger in Watts. This rate is
determined by taking the difference between the Heat Exchanger
Total Heating Rate and the Heat Exchanger Sensible Heating
Rate. A positive value is reported if the supply air is
humidified by the heat exchanger, else the rate is set to
zero.
This output is the total heating rate of the supply air by
the heat exchanger in Watts. This rate is determined using the
supply air mass flow rate through the heat exchanger unit, and
the enthalpy of the supply air entering and leaving the unit.
A positive value is reported if the enthalpy of the supply air
is increased by the heat exchanger, else the rate is set to
zero.
This output is the total heating energy added to the supply
air by the heat exchanger in Joules over the timestep being
reported.This output is also added to a meter with ResouceType
= EnergyTransfer, EndUseKey = HeatRecoveryforHeating, GroupKey
= System (ref. Output:Meter
objects).
This output is the sensible cooling rate of the supply air
by the heat exchanger in Watts. This rate is determined using
the supply air mass flow rate through the heat exchanger unit,
the supply air inlet and outlet conditions, and the specific
heat of the inlet supply air. A positive value is reported if
the supply air is cooled by the heat exchanger, else the rate
is set to zero.
This output is the latent cooling rate (dehumidification)
of the supply air by the heat exchanger in Watts. This rate is
determined by taking the difference between the Heat Exchanger
Total Cooling Rate and the Heat Exchanger Sensible Cooling
Rate. A positive value is reported if the supply air is
dehumidified by the heat exchanger, else the rate is set to
zero.
This output is the total cooling rate of the supply air by
the heat exchanger in Watts. This rate is determined using the
supply air mass flow rate through the heat exchanger unit, and
the enthalpy of the supply air entering and leaving the unit.
A positive value is reported if the enthalpy of the supply air
is decreased by the heat exchanger, else the rate is set to
zero.
This output is the total cooling energy added to the supply
air by the heat exchanger in Joules over the timestep being
reported. This output is also added to a meter with
ResouceType = EnergyTransfer, EndUseKey =
HeatRecoveryforCooling, GroupKey = System (ref. Output:Meter
objects).
This output is the electric consumption rate of the unit in
Watts. This rate is applicable whenever the unit operates
(i.e., whenever the unit is scheduled to be available and
supply and exhaust air flows exist).
This output is the electric consumption of the unit in
Joules for the timestep being reported. This ouput is also
added to a meter with ResourceType = Electricity, EndUseKey =
HeatRecovery, GroupKey = System (ref. Output:Meter
objects).
This output is the average latent effectiveness of the heat
exchanger (excluding bypass air, if any) over the timestep
being reported.
Heat
Exchanger Supply Air Bypass Mass Flow Rate [kg/s][LINK]
This output is the average mass flow rate in kg/second of
the supply (primary) air stream that is bypassing the heat
exchanger over the timestep being reported. This flow rate is
equal to the total supply mass flow rate through the heat
exchanger unit minus the amount passing
through the supply side of the heat exchanger
core.
Heat
Exchanger Exhaust Air Bypass Mass Flow Rate [kg/s][LINK]
This output is the average mass flow rate in kg/second of
the exhaust (secondary) air stream that is bypassing the heat
exchanger over the timestep being reported. This flow rate is
equal to the total exhaust mass flow rate through the heat
exchanger unit minus the amount passing
through the exhaust side of the heat exchanger
core.
This desiccant heat exchanger object is an HVAC component
used to model both temperature (sensible) and moisture
(latent) heat exchange between two air streams (Figure [fig:schematic-of-the-balanced-flow-desiccant-heat]).
The model assumes balanced air flow through the regeneration
and process sides of the heat exchanger (i.e., regeneration
and process air volume flow rates and face velocities are the
same). Heat exchanger performance is specified through a
performance data type object (e.g.,
HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1).
Schematic of the Balanced Flow
Desiccant Heat Exchanger [fig:schematic-of-the-balanced-flow-desiccant-heat]
Currently, this desiccant heat exchanger model can be
referenced by two compound objects: CoilSystem:Cooling:DX:HeatExchangerAssisted
and Dehumidifier:Desiccant:System,
both of which are used to provide enhanced dehumidification
over conventional systems. If this heat exchanger is
referenced by a compound object, the compound object will
control heat exchanger operation (i.e., tell the heat
exchanger if heat exchange is needed or not for each
simulation timestep).
This desiccant heat exchanger object may also be specified
directly in an AirLoopHVAC
(air loop BranchList) or in an AirLoopHVAC:OutdoorAirSystem
(AirLoopHVAC:OutdoorAirSystem:EquipmentList) without being
referenced by a compound object. If specified directly in an
AirLoopHVAC
or AirLoopHVAC:OutdoorAirSystem,
then the heat exchanger can be controlled to provide heat
exchange based on a maximum and/or minimum humidity set point
placed on the process air outlet node (ref. Setpoint
Managers). If no humidity set points are provided on this
node, then heat exchange will be provided whenever the heat
exchanger is available to operate (via its availability
schedule) and there is a temperature and/or humidity ratio
difference between the two air streams.
Inputs to this model include an availability schedule name,
inlet and outlet air node names, and the type and name of the
heat exchanger performance data object. A description of each
input field for this object is provided below.
A unique, user-assigned name for a particular balanced flow
desiccant heat exchanger. Any reference to this heat exchanger
by another object will use this name.
The name of the schedule (ref: Schedule) that denotes
whether the heat exchanger can operate during a given time
period. A schedule value of less than or equal to 0 indicates
that the unit is off for that time period. A schedule value
greater than 0 indicates that the unit can operate during the
time period. If this field is blank, the schedule has values
of 1 for all time periods.
This alpha field contains the type of model used to
simulate the desiccant heat exchanger s thermal performance
and electrical energy use. Currently, the only valid choice is
HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1.
This alpha field contains the identifying name of the
specific heat exchanger performance type object (e.g.,
HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1)
that defines the performance for this heat exchanger. A single
heat exchanger performance type object may be used to define
performance for many HeatExchanger:Desiccant:BalancedFlow
objects (i.e., the same name may be used in this input field
for more than one balanced flow desiccant heat exchanger).
This input denotes whether the heat exchanger unit is
locked out (heat exchanger rotation is suspended) when the
air-side economizer is operating. Both the economizer and high
humidity control (Ref. Controller:OutdoorAir) activate the
heat exchanger lockout as specified by this input. The input
choices are Yes (meaning locked out) or No.
Economizer lockout is typically not used for this
type of heat exchanger. For this reason, the default input for
this field is No.
Following is an example input for this heat exchanger
object:
HeatExchanger:Desiccant:BalancedFlow,
Desiccant Heat Exchanger 1, !- Name
OfficeHeatCoolAvail, !- Availability Schedule Name
DXSystem 1 Mixed Air Node, !- Regeneration Air Inlet Node Name
DX Cooling Coil Air Inlet Node, !- Regeneration Air Outlet Node Name
DX Cooling Coil Air Outlet Node, !- Process Air Inlet Node Name
DXSystem 1 Fan Air Inlet Node, !- Process Air Outlet Node Name
HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1, !- Heat Exchanger Performance Object Type
HXDesPerf1; !- Heat Exchanger Performance Name
This output is the sensible heating rate of the process air
by the heat exchanger in Watts. This rate is determined using
the process air mass flow rate through the heat exchanger
unit, the process air inlet and outlet temperatures, and the
specific heat of the inlet process air. A positive value is
reported if the process air is heated by the heat exchanger,
else the rate is set to zero.
This output is the latent heating rate (humidification) of
the process air by the heat exchanger in Watts. This rate is
determined by taking the difference between the heat exchanger
s total heat recovery rate and the sensible heat recovery
rate. A positive value is reported if the process air is
humidified by the heat exchanger, else the rate is set to
zero.
This output is the total heating rate of the process air by
the heat exchanger in Watts. This rate is determined using the
process air mass flow rate through the heat exchanger unit and
the enthalpy of the air entering and leaving the process side
of the unit. A positive value is reported if the enthalpy of
the process air is increased by the heat exchanger, else the
rate is set to zero.
This output is the total heating energy added to the
process air by the heat exchanger in Joules over the timestep
being reported.This output is also added to a meter with
ResouceType = EnergyTransfer, EndUseKey =
HeatRecoveryforHeating, GroupKey = System (ref. Output:Meter
objects).
This output is the sensible cooling rate of the process air
by the heat exchanger in Watts. This rate is determined using
the process air mass flow rate through the heat exchanger
unit, the process air inlet and outlet temperatures, and the
specific heat of the inlet process air. A positive value is
reported if the process air is cooled by the heat exchanger,
else the rate is set to zero.
This output is the latent cooling rate (dehumidification)
of the process air by the heat exchanger in Watts. This rate
is determined by taking the difference between the heat
exchanger s total heat recovery rate and the sensible heat
recovery rate. A positive value is reported if the process air
is dehumidified by the heat exchanger, else the rate is set to
zero.
This output is the total cooling rate of the process air by
the heat exchanger in Watts. This rate is determined using the
process air mass flow rate through the heat exchanger unit and
the enthalpy of the air entering and leaving the process side
of the unit. A positive value is reported if the enthalpy of
the process air is decreased by the heat exchanger, else the
rate is set to zero.
This output is the total cooling energy added to the
process air by the heat exchanger in Joules over the timestep
being reported. This output is also added to a meter with
ResouceType = EnergyTransfer, EndUseKey =
HeatRecoveryforCooling, GroupKey = System (ref. Output:Meter
objects).
This output is the average electric consumption rate of the
unit in Watts. This average rate includes portions of the
simulation timestep when the heat exchanger may be cycled off
(i.e., average of on and off periods, as appropriate).
This output is the electric consumption of the unit in
Joules for the timestep being reported. This ouput is also
added to a meter with ResourceType = Electricity, EndUseKey =
HeatRecovery, GroupKey = System (ref. Output:Meter
objects).
This object specifies a performance model and model
coefficients for a balanced flow desiccant heat exchanger. A
HeatExchanger:Desiccant:BalancedFlow
object will reference a HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1
object. This performance data object is used to specify the
thermal performance and electric consumption of the heat
exchanger. Some representative inputs for this object are
provided in the EnergyPlus Reference DataSets (PerfCurves.idf
and AllDataSets.idf).
This model predicts the regeneration air stream outlet
temperature and humidity ratio values based on the entering
regeneration and process air stream temperature, humidity
ratio and face velocity. The process air stream outlet
humidity ratio and temperatures are calculated based on a
simple heat and moisture balance. The model requires that the
user enter the nominal volumetric flow rate and a nominal face
velocity, electric power consumption, empirical model
coefficients for the regeneration outlet air temperature and
humidity ratio equations, and the applicable minimum and
maximum values for both the independent and dependent
variables for the empirical model coefficients provided. This
model is based on the following equations:
The dry-bulb temperature of the regeneration outlet air is
defined using the following equation:
\(RTO\) = Regeneration
outlet air dry-bulb temperature (C)
\(RWI\) = Regeneration
inlet air humidity ratio (kgWater/kgDryAir)
\(RTI\) = Regeneration
inlet air dry-bulb temperature (C)
\(PWI\) = Process inlet
air humidity ratio (kgWater/kgDryAir)
\(PTI\) = Process inlet
air dry-bulb temperature (C)
\(RFV\) = Regeneration
(and process) face velocity (m/s)
The humidity ratio of the regeneration outlet air is
defined using the same empirical equation form; however,
different coefficients are used as follows:
\(RWO\) = Regeneration
outlet air humidity ratio (kgWater/kgDryAir)
The process outlet air conditions are then calculated
based on the regeneration outlet air conditions (temperature
or humidity ratio) calculated above, the actual regeneration
inlet air conditions entering the heat exchanger, and assuming
the same amount of sensible and total energy transfer across
both the process and regeneration sides of the heat exchanger.
The difference between the actual inlet air conditions and
RTI/RWI/PTI/PWI is made here because user-defined limits for
RTI/RWI/PTI/PWI may result in a difference between the actual
conditions and those used in the equations shown above (see
the EnergyPlus Engineering Reference for further
discussion).
A description of each input field for this object is
provided below.
This alpha field contains the identifying name for this set
of desiccant heat exchanger performance data. Any reference to
this performance data set by another object (e.g.,
HeatExchanger:Desiccant:BalancedFlow) will use this name.
The nominal air volume flow rate in cubic meters per
second. This model assumes balanced air flow (i.e., the same
air volume flow rate across the process and regeneration sides
of the heat exchanger). The minimum value should be greater
than 0. This field is autosizable.
This numeric field contains the nominal air velocity across
the heat exchanger face area in meters per second. It is
assumed that this air velocity is the same for both sides of
the heat exchanger. This value, along with the Nominal Air
Flow Rate sets the heat exchanger face area. With this fixed
face area, the air face velocity is calculated every
simulation timestep based on the actual air volume flow rate
for the timestep. The minimum value should be greater than 0
and less than or equal to 6. The default value is 3.0.
This numeric field contains the nominal electric
consumption rate of the heat exchanger in watts. This electric
power is considered constant and is consumed only when the
heat exchanger operates (e.g., for all or a portion of the
simulation timestep, as appropriate). This numeric input can
be used to model electric power consumption by controls
(transformers, relays, etc.) and/or a motor for a rotary heat
exchanger. None of this electric power contributes thermal
load to the process or regeneration air streams. The minimum
value should be greater than or equal to 0. The default value
for this field is also 0.
The coefficients for the regeneration air outlet
temperature equation described above are defined in the
following eight fields:
The coefficient (B\(_{8}\)) in the temperature
equation shown above (RTO).
The following 16 fields are used to establish the valid
range for the dependent and independent variables associated
with the coefficients defined above (B\(_{1}\) through B\(_{8}\)) for the regeneration
outlet air temperature equation.
Field:
Minimum Regeneration Inlet Air Humidity Ratio for Temperature
Equation[LINK]
The minimum allowable value of RWI in the temperature
equation shown above (kgWater/kgDryAir). Values of RWI less
than the minimum will be replaced by this minimum when
calculating the regeneration outlet air temperature and a
warning message will be issued. The valid range for this input
field is 0.0 to 1.0.
Field:
Maximum Regeneration Inlet Air Humidity Ratio for Temperature
Equation[LINK]
The maximum allowable value of RWI in the temperature
equation shown above (kgWater/kgDryAir). Values of RWI greater
than the maximum will be replaced by this maximum when
calculating the regeneration outlet air temperature and a
warning message will be issued. The valid range for this input
field is 0.0 to 1.0.
Field:
Minimum Regeneration Inlet Air Temperature for Temperature
Equation[LINK]
The minimum allowable value of RTI in the temperature
equation shown above (C). Values of RTI less than the minimum
will be replaced by this minimum when calculating the
regeneration outlet air temperature and a warning message will
be issued.
Field:
Maximum Regeneration Inlet Air Temperature for Temperature
Equation[LINK]
The maximum allowable value of RTI in the temperature
equation shown above (C). Values of RTI greater than the
maximum will be replaced by this maximum when calculating the
regeneration outlet air temperature and a warning message will
be issued.
Field:
Minimum Process Inlet Air Humidity Ratio for Temperature
Equation[LINK]
The minimum allowable value of PWI in the temperature
equation shown above (kg/kg). Values of PWI less than the
minimum will be replaced by this minimum when calculating the
regeneration outlet air temperature and a warning message will
be issued. The valid range for this input field is 0.0 to
1.0.
Field:
Maximum Process Inlet Air Humidity Ratio for Temperature
Equation[LINK]
The maximum allowable value of PWI in the temperature
equation shown above (kg/kg). Values of PWI greater than the
maximum will be replaced by this maximum when calculating the
regeneration outlet air temperature and a warning message will
be issued. The valid range for this input field is 0.0 to
1.0.
Field:
Minimum Process Inlet Air Temperature for Temperature
Equation[LINK]
The minimum allowable value of PTI in the temperature
equation shown above (C). Values of PTI less than the minimum
will be replaced by this minimum when calculating the
regeneration outlet air temperature and a warning message will
be issued.
Field:
Maximum Process Inlet Air Temperature for Temperature
Equation[LINK]
The maximum allowable value of PTI in the temperature
equation shown above (C). Values of PTI greater than the
maximum will be replaced by this maximum when calculating the
regeneration outlet air temperature and a warning message will
be issued.
Field:
Minimum Regeneration Air Velocity for Temperature
Equation[LINK]
The minimum allowable value of RFV in the temperature
equation shown above (m/s). Values of RFV less than the
minimum will be replaced by this minimum when calculating the
regeneration outlet air temperature and a warning message will
be issued. The minimum value for this input field should be
greater than 0.
Field:
Maximum Regeneration Air Velocity for Temperature
Equation[LINK]
The maximum allowable value of RFV in the temperature
equation shown above (m/s). Values of RFV greater than the
maximum will be replaced by this maximum value when
calculating the regeneration outlet air temperature and a
warning message will be issued. The minimum value for this
input field should be greater than 0.
Field:
Minimum Regeneration Outlet Air Temperature for Temperature
Equation[LINK]
The minimum value of RTO resulting from the temperature
equation shown above (C). If RTO is less than this value, RTO
will be replaced by this minimum value and a warning message
will be issued.
Field:
Maximum Regeneration Outlet Air Temperature for Temperature
Equation[LINK]
The maximum value of RTO resulting from the temperature
equation shown above (C). If RTO is greater than this value,
RTO will be replaced by this maximum value and a warning
message will be issued.
Field:
Minimum Regeneration Inlet Air Relative Humidity for
Temperature Equation[LINK]
The minimum relative humidity of the regeneration inlet air
for the temperature equation shown above (percent). If the
relative humidity of the regeneration inlet air is below this
value, a warning message will be issued. The valid range for
this input field is 0.0 to 100.0.
Field:
Maximum Regeneration Inlet Air Relative Humidity for
Temperature Equation[LINK]
The maximum relative humidity of the regeneration inlet air
for the temperature equation shown above (percent). If the
relative humidity of the regeneration inlet air is above this
value, a warning message will be issued. The valid range for
this input field is 0.0 to 100.0.
Field:
Minimum Process Inlet Air Relative Humidity for Temperature
Equation[LINK]
The minimum relative humidity of the process inlet air for
the temperature equation shown above (percent). If the
relative humidity of the process inlet air is below this
value, a warning message will be issued. The valid range for
this input field is 0.0 to 100.0.
Field:
Maximum Process Inlet Air Relative Humidity for Temperature
Equation[LINK]
The maximum relative humidity of the process inlet air for
the temperature equation shown above (percent). If the
relative humidity of the process inlet air is above this
value, a warning message will be issued. The valid range for
this input field is 0.0 to 100.0.
The coefficients for the regeneration outlet air humidity
ratio equation are defined in the following eight fields:
Field:
Humidity Ratio Equation Coefficient 1[LINK]
The constant coefficient (C\(_{1}\)) in the humidity ratio
equation shown above (RWO).
Field:
Humidity Ratio Equation Coefficient 2[LINK]
The coefficient (C\(_{2}\)) in the humidity ratio
equation shown above (RWO).
Field:
Humidity Ratio Equation Coefficient 3[LINK]
The coefficient (C\(_{3}\)) in the humidity ratio
equation shown above (RWO).
Field:
Humidity Ratio Equation Coefficient 4[LINK]
The coefficient (C\(_{4}\)) in the humidity ratio
equation shown above (RWO).
Field:
Humidity Ratio Equation Coefficient 5[LINK]
The coefficient (C\(_{5}\)) in the humidity ratio
equation shown above (RWO).
Field:
Humidity Ratio Equation Coefficient 6[LINK]
The coefficient (C\(_{6}\)) in the humidity ratio
equation shown above (RWO).
Field:
Humidity Ratio Equation Coefficient 7[LINK]
The coefficient (C\(_{7}\)) in the humidity ratio
equation shown above (RWO).
Field:
Humidity Ratio Equation Coefficient 8[LINK]
The coefficient (C\(_{8}\)) in the humidity ratio
equation shown above (RWO).
The following 16 fields are used to establish the valid
range for the dependent and independent variables associated
with the coefficients defined above (C\(_{1}\) through C\(_{8}\)) for the regeneration
outlet air humidity ratio equation.
Field:
Minimum Regeneration Inlet Air Humidity Ratio for Humidity
Ratio Equation[LINK]
The minimum allowable value of RWI in the humidity ratio
equation shown above (kgWater/kgDryAir). Values of RWI less
than the minimum will be replaced by this minimum when
calculating the regeneration outlet air humidity ratio and a
warning message will be issued. The valid range for this input
field is 0.0 to 1.0.
Field:
Maximum Regeneration Inlet Air Humidity Ratio for Humidity
Ratio Equation[LINK]
The maximum allowable value of RWI in the humidity ratio
equation shown above (kgWater/kgDryAir). Values of RWI greater
than the maximum will be replaced by this maximum when
calculating the regeneration outlet air humidity ratio and a
warning message will be issued. The valid range for this input
field is 0.0 to 1.0.
Field:
Minimum Regeneration Inlet Air Temperature for Humidity Ratio
Equation[LINK]
The minimum allowable value of RTI in the humidity ratio
equation shown above (C). Values of RTI less than the minimum
will be replaced by this minimum when calculating the
regeneration outlet air humidity ratio and a warning message
will be issued.
Field:
Maximum Regeneration Inlet Air Temperature for Humidity Ratio
Equation[LINK]
The maximum allowable value of RTI in the humidity ratio
equation shown above (C). Values of RTI greater than the
maximum will be replaced by this maximum when calculating the
regeneration outlet air humidity ratio and a warning message
will be issued.
Field:
Minimum Process Inlet Air Humidity Ratio for Humidity Ratio
Equation[LINK]
The minimum allowable value of PWI in the humidity ratio
equation shown above (kgWater/kgDryAir). Values of PWI less
than the minimum will be replaced by this minimum when
calculating the regeneration outlet air humidity ratio and a
warning message will be issued. The valid range for this input
field is 0.0 to 1.0.
Field:
Maximum Process Inlet Air Humidity Ratio for Humidity Ratio
Equation[LINK]
The maximum allowable value of PWI in the humidity ratio
equation shown above (kgWater/kgDryAir). Values of PWI greater
than the maximum will be replaced by this maximum when
calculating the regeneration outlet air humidity ratio and a
warning message will be issued. The valid range for this input
field is 0.0 to 1.0.
Field:
Minimum Process Inlet Air Temperature for Humidity Ratio
Equation[LINK]
The minimum allowable value of PTI in the humidity ratio
equation shown above (C). Values of PTI less than the minimum
will be replaced by this minimum when calculating the
regeneration outlet air humidity ratio and a warning message
will be issued.
Field:
Maximum Process Inlet Air Temperature for Humidity Ratio
Equation[LINK]
The maximum allowable value of PTI in the humidity ratio
equation shown above (C). Values of PTI greater than the
maximum will be replaced by this maximum when calculating the
regeneration outlet air humidity ratio and a warning message
will be issued.
Field:
Minimum Regeneration Air Velocity for Humidity Ratio
Equation[LINK]
The minimum allowable value of RFV in the humidity ratio
equation shown above (m/s). Values of RFV less than the
minimum will be replaced by this minimum when calculating the
regeneration outlet air humidity ratio and a warning message
will be issued. The minimum value for this input field should
be greater than 0.
Field:
Maximum Regeneration Air Velocity for Humidity Ratio
Equation[LINK]
The maximum allowable value of RFV in the humidity ratio
equation shown above (m/s). Values of RFV greater than the
maximum will be replaced by this maximum when calculating the
regeneration outlet air humidity ratio and a warning message
will be issued. The minimum value for this input field should
be greater than 0.
Field:
Minimum Regeneration Outlet Air Humidity Ratio for Humidity
Ratio Equation[LINK]
The minimum value of RWO resulting from the humidity ratio
equation shown above (kgWater/kgDryAir). If RWO is less than
this value, RWO will be replaced by this minimum value and a
warning message will be issued. The valid range for this input
field is 0.0 to 1.0.
Field:
Maximum Regeneration Outlet Air Humidity Ratio for Humidity
Ratio Equation[LINK]
The maximum value of RWO resulting from the humidity ratio
equation shown above (kgWater/kgDryAir). If RWO is greater
than this value, RWO will be replaced by this maximum value
and a warning message will be issued. The valid range for this
input field is 0.0 to 1.0.
Field:
Minimum Regeneration Inlet Air Relative Humidity for Humidity
Ratio Equation[LINK]
The minimum relative humidity of the regeneration inlet air
for the humidity ratio equation shown above (percent). If the
relative humidity of the regeneration inlet air is below this
value, a warning message will be issued. The valid range for
this input field is 0.0 to 100.0.
Field:
Maximum Regeneration Inlet Air Relative Humidity for Humidity
Ratio Equation[LINK]
The maximum relative humidity of the regeneration inlet air
for the humidity ratio equation shown above (percent). If the
relative humidity of the regeneration inlet air is above this
value, a warning message will be issued. The valid range for
this input field is 0.0 to 100.0.
Field:
Minimum Process Inlet Air Relative Humidity for Humidity Ratio
Equation[LINK]
The minimum relative humidity of the process inlet air for
the humidity ratio equation shown above (percent). If the
relative humidity of the process inlet air is below this
value, a warning message will be issued. The valid range for
this input field is 0.0 to 100.0.
Field:
Maximum Process Inlet Air Relative Humidity for Humidity Ratio
Equation[LINK]
The maximum relative humidity of the process inlet air for
the humidity ratio equation shown above (percent). If the
relative humidity of the process inlet air is above this
value, a warning message will be issued. The valid range for
this input field is 0.0 to 100.0.
Following is an example input for this heat exchanger
performance data type object:
HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1,
HXDesPerf1, !- Name
1.05, !- Nominal Air Flow Rate {m3/s}
3.25, !- Nominal Air Face Velocity {m/s}
50.0, !- Nominal Electric Power {W}
-2.53636E+00, !- Temperature Equation Coefficient 1
2.13247E+01, !- Temperature Equation Coefficient 2
9.23308E-01, !- Temperature Equation Coefficient 3
9.43276E+02, !- Temperature Equation Coefficient 4
-5.92367E+01, !- Temperature Equation Coefficient 5
-4.27465E-02, !- Temperature Equation Coefficient 6
1.12204E+02, !- Temperature Equation Coefficient 7
7.78252E-01, !- Temperature Equation Coefficient 8
0.007143, !- Minimum Regeneration Inlet Air Humidity Ratio for Temperature Equation
0.024286, !- Maximum Regeneration Inlet Air Humidity Ratio for Temperature Equation
46.111110, !- Minimum Regeneration Inlet Air Temperature for Temperature Equation {C}
46.111112, !- Maximum Regeneration Inlet Air Temperature for Temperature Equation {C}
0.005000, !- Minimum Process Inlet Air Humidity Ratio for Temperature Equation
0.015714, !- Maximum Process Inlet Air Humidity Ratio for Temperature Equation
4.583333, !- Minimum Process Inlet Air Temperature for Temperature Equation {C}
21.83333, !- Maximum Process Inlet Air Temperature for Temperature Equation {C}
2.286, !- Minimum Regeneration Air Velocity for Temperature Equation {m/s}
4.826, !- Maximum Regeneration Air Velocity for Temperature Equation {m/s}
35.0, !- Minimum Regeneration Outlet Air Temperature for Temperature Equation {C}
50.0, !- Maximum Regeneration Outlet Air Temperature for Temperature Equation {C}
5.0, !- Minimum Regeneration Inlet Air Relative Humidity for Temperature Equation {percent}
45.0, !- Maximum Regeneration Inlet Air Relative Humidity for Temperature Equation {percent}
80.0, !- Minimum Process Inlet Air Relative Humidity for Temperature Equation {percent}
100.0, !- Maximum Process Inlet Air Relative Humidity for Temperature Equation {percent}
-2.25547E+01, !- Humidity Ratio Equation Coefficient 1
9.76839E-01, !- Humidity Ratio Equation Coefficient 2
4.89176E-01, !- Humidity Ratio Equation Coefficient 3
-6.30019E-02, !- Humidity Ratio Equation Coefficient 4
1.20773E-02, !- Humidity Ratio Equation Coefficient 5
5.17134E-05, !- Humidity Ratio Equation Coefficient 6
4.94917E-02, !- Humidity Ratio Equation Coefficient 7
-2.59417E-04, !- Humidity Ratio Equation Coefficient 8
0.007143, !- Minimum Regeneration Inlet Air Humidity Ratio for Humidity Ratio Equation
0.024286, !- Maximum Regeneration Inlet Air Humidity Ratio for Humidity Ratio Equation
46.111110, !- Minimum Regeneration Inlet Air Temperature for Humidity Ratio Equation {C}
46.111112, !- Maximum Regeneration Inlet Air Temperature for Humidity Ratio Equation {C}
0.005000, !- Minimum Process Inlet Air Humidity Ratio for Humidity Ratio Equation
0.015714, !- Maximum Process Inlet Air Humidity Ratio for Humidity Ratio Equation
4.583333, !- Minimum Process Inlet Air Temperature for Humidity Ratio Equation {C}
21.83333, !- Maximum Process Inlet Air Temperature for Humidity Ratio Equation {C}
2.286, !- Minimum Regeneration Air Velocity for Humidity Ratio Equation {m/s}
4.826, !- Maximum Regeneration Air Velocity for Humidity Ratio Equation {m/s}
0.007914, !- Minimum Regeneration Outlet Air Humidity Ratio for Humidity Ratio Equation
0.026279, !- Maximum Regeneration Outlet Air Humidity Ratio for Humidity Ratio Equation
5.0, !- Minimum Regeneration Inlet Air Relative Humidity for Humidity Ratio Equation {%}
45.0, !- Maximum Regeneration Inlet Air Relative Humidity for Humidity Ratio Equation {percent}
80.0, !- Minimum Process Inlet Air Relative Humidity for Humidity Ratio Equation {percent}
100.0; !- Maximum Process Inlet Air Relative Humidity for Humidity Ratio Equation {percent}
No variables are reported for this object. However, outputs
are provided by the HeatExchanger:Desiccant:BalancedFlow
object that references this PerformanceDataType1 object.
Group Heat Recovery[LINK]
HeatExchanger:AirToAir:FlatPlate[LINK]
The air-to-air flat plate heat exchanger is an HVAC component typically used for exhaust or relief air heat recovery. The user can choose the flow arrangement type: counter flow, parallel flow, or cross flow with both streams unmixed. The input requires no geometric data. Performance is defined by specifying primary outlet air temperature at nominal (user specified) inlet conditions. In addition, the ratio (h\(^{.}\)A)\(_{p}\) / (h\(^{.}\)A)\(_{s}\) at nominal flow needs to be input, where h is the convective heat transfer coefficient, A is the surface area, p stands for primary side, s for secondary side.
If the heat exchanger is operated in conjunction with an outdoor air economizer (economizer lockout set to Yes), the nominal supply air flow rate should be set equal to the minimum outdoor air flow rate specified in the Controller:OutdoorAir. The heat exchanger detects that the economizer is operating by the fact that its inlet air flow rate is greater than its nominal supply air flow rate.
Inputs[LINK]
Field: Name[LINK]
A unique user-assigned name for a particular air-to-air flat plate heat exchanger unit. Any reference to this unit by another object will use this name.
Field: Availability Schedule Name[LINK]
The name of the schedule (ref: Schedule) that denotes whether the unit can run during a given time period. A schedule value of 0 indicates that the unit is off for that time period. A schedule value greater than 0 indicates that the unit can operate during the time period. If this field is blank, the schedule has values of 1 for all time periods.
Field: Flow Arrangement Type[LINK]
The user specified flow arrangement of the heat exchanger. The possible inputs are CounterFlow, ParallelFlow, or CrossFlowBothUnmixed.
Field: Economizer Lockout[LINK]
This input denotes whether the heat exchanger unit is locked out (bypassed) when the air-side economizer is operating. Both the economizer and high humidity control (Ref. Controller:OutdoorAir) activate the heat exchanger lockout as specified by this input. The input choices are Yes (meaning locked out) or No. The default input for this field is Yes.
Field: Ratio of Supply to Secondary hA Values[LINK]
The ratio (h\(^{.}\)A)\(_{p}\) / (h\(^{.}\)A)\(_{s}\) at nominal flow. h is the surface convective heat transfer coefficient, A is the heat transfer area, and p and s stand for primary side and secondary side respectively. A typical value for this ratio is 1.0.
Field: Nominal Supply Air Flow Rate[LINK]
The nominal primary side air flow rate in cubic meters per second. If the unit is operated in conjunction with an outdoor air economizer this should be equal to the minimum outdoor air flow rate. This field is autosizable.
Field: Nominal Supply Air Inlet Temperature[LINK]
The nominal primary side air inlet temperature in Celsius.
Field: Nominal Supply Air Outlet Temperature[LINK]
The nominal primary side air outlet temperature in Celsius.
Field: Nominal Secondary Air Flow Rate[LINK]
The nominal secondary side air flow rate in cubic meters per second. This field is autosizable. It is equal to the primary side air flow rate defined above, if autosized.
Field: Nominal Secondary Air Inlet Temperature[LINK]
The nominal secondary side air inlet temperature in Celsius.
Field: Nominal Electric Power[LINK]
The electric consumption rate of the unit in watts. Electric power is considered constant whenever the unit operates. This input can be used to model electric power consumption by controls (transformers, relays, etc.) and/or a motor for a rotary heat exchanger. None of this electric power contributes thermal load to the supply or exhaust air streams. The default value for this field is 0.
Field: Supply Air Inlet Node Name[LINK]
The name of the HVAC system node from which the unit draws its primary inlet air.
Field: Supply Air Outlet Node Name[LINK]
The name of the HVAC system node to which the unit sends its primary outlet air.
Field: Secondary Air Inlet Node Name[LINK]
The name of the HVAC system node from which the unit draws its secondary inlet air.
Field: Secondary Air Outlet Node Name[LINK]
The name of the HVAC system node to which the unit sends its secondary outlet air.
An IDF example:
Outputs[LINK]
HVAC,Average,Heat Exchanger Sensible Heating Rate [W]
HVAC,Sum,Heat Exchanger Sensible Heating Energy [J]
HVAC,Average,Heat Exchanger Latent Gain Rate [W]
HVAC,Sum,Heat Exchanger Latent Gain Energy [J]
HVAC,Average,Heat Exchanger Total Heating Rate [W]
HVAC,Sum,Heat Exchanger Total Heating Energy [J]
HVAC,Average,Heat Exchanger Sensible Cooling Rate [W]
HVAC,Sum,Heat Exchanger Sensible Cooling Energy [J]
HVAC,Average,Heat Exchanger Latent Cooling Rate [W]
HVAC,Sum,Heat Exchanger Latent Cooling Energy [J]
HVAC,Average,Heat Exchanger Total Cooling Rate [W]
HVAC,Sum,Heat Exchanger Total Cooling Energy [J]
HVAC,Average,Heat Exchanger Electric Power[W]
HVAC,Sum,Heat Exchanger Electric Energy [J]
Heat Exchanger Sensible Heating Rate [W][LINK]
This output is the sensible heating rate of the supply air by the heat exchanger in Watts. This rate is determined using the supply air mass flow rate through the heat exchanger unit, the supply air inlet and outlet conditions, and the specific heat of the inlet supply air. A positive value is reported if the supply air is heated by the heat exchanger, else the rate is set to zero.
Heat Exchanger Sensible Heating Energy [J][LINK]
This output is the sensible heating energy added to the supply air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Latent Gain Rate [W][LINK]
This output is the latent heating rate (humidification) of the supply air by the heat exchanger in Watts. This rate is determined by taking the difference between the Heat Exchanger Total Heating Rate and the Heat Exchanger Sensible Heating Rate. A positive value is reported if the supply air is humidified by the heat exchanger, else the rate is set to zero.
Heat Exchanger Latent Heating Energy [J][LINK]
This output is the latent heating energy added to the supply air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Total Heating Rate [W][LINK]
This output is the total heating rate of the supply air by the heat exchanger in Watts. This rate is determined using the supply air mass flow rate through the heat exchanger unit, and the enthalpy of the supply air entering and leaving the unit. A positive value is reported if the enthalpy of the supply air is increased by the heat exchanger, else the rate is set to zero.
Heat Exchanger Total Heating Energy [J][LINK]
This output is the total heating energy added to the supply air by the heat exchanger in Joules over the timestep being reported.This output is also added to a meter with ResouceType = EnergyTransfer, EndUseKey = HeatRecoveryforHeating, GroupKey = System (ref. Output:Meter objects).
Heat Exchanger Sensible Cooling Rate [W][LINK]
This output is the sensible cooling rate of the supply air by the heat exchanger in Watts. This rate is determined using the supply air mass flow rate through the heat exchanger unit, the supply air inlet and outlet conditions, and the specific heat of the inlet supply air. A positive value is reported if the supply air is cooled by the heat exchanger, else the rate is set to zero.
Heat Exchanger Sensible Cooling Energy [J][LINK]
This output is the sensible cooling energy added to the supply air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Latent Cooling Rate [W][LINK]
This output is the latent cooling rate (dehumidification) of the supply air by the heat exchanger in Watts. This rate is determined by taking the difference between the Heat Exchanger Total Cooling Rate and the Heat Exchanger Sensible Cooling Rate. A positive value is reported if the supply air is dehumidified by the heat exchanger, else the rate is set to zero.
Heat Exchanger Latent Cooling Energy [J][LINK]
This output is the latent cooling energy added to the supply air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Total Cooling Rate [W][LINK]
This output is the total cooling rate of the supply air by the heat exchanger in Watts. This rate is determined using the supply air mass flow rate through the heat exchanger unit, and the enthalpy of the supply air entering and leaving the unit. A positive value is reported if the enthalpy of the supply air is decreased by the heat exchanger, else the rate is set to zero.
Heat Exchanger Total Cooling Energy [J][LINK]
This output is the total cooling energy added to the supply air by the heat exchanger in Joules over the timestep being reported. This output is also added to a meter with ResouceType = EnergyTransfer, EndUseKey = HeatRecoveryforCooling, GroupKey = System (ref. Output:Meter objects).
Heat Exchanger Electric Power [W][LINK]
This output is the electric consumption rate of the unit in Watts. This rate is applicable whenever the unit operates (i.e., whenever the unit is scheduled to be available and supply and exhaust air flows exist).
Heat Exchanger Electric Energy [J][LINK]
This output is the electric consumption of the unit in Joules for the timestep being reported. This ouput is also added to a meter with ResourceType = Electricity, EndUseKey = HeatRecovery, GroupKey = System (ref. Output:Meter objects).
HeatExchanger:AirToAir:SensibleAndLatent[LINK]
The sensible and latent air-to-air heat exchanger is an HVAC component typically used for exhaust or relief air heat recovery (Figure 150). Heat exchanger performance can be specified to transfer sensible energy, latent energy or both between the supply and exhaust air streams. The input requires no geometric data. Performance is defined by specifying sensible and/or latent effectiveness at 75% and 100% of the nominal (rated) supply air flow rate at two operating conditions as shown in Table [table:operating-conditions-for-defining-heat].
Note: Conditions consistent with the Air-Conditioning and Refrigeration Institute s (ARI) Standard 1060-2001.
This object models the basic operation of an air-to-air heat exchanger. Heat exchange between the supply and exhaust air streams occurs whenever the unit is scheduled to be available (Availability schedule) and supply/exhaust air flow is present. This heat exchanger object can be used in conjunction with a conventional air-side economizer (i.e., specify ModulateFlow in the Controller:OutdoorAir object), whereby heat exchange is suspended whenever the air-side economizer (or high humidity control) is active (i.e., air flow is fully bypassed around a fixed-plate heat exchanger or the rotation of a rotary heat exchanger is stopped). This object is also able to suspend heat exchange for the purpose of providing free cooling operation in the absence of a conventional air-side economizer (i.e., specify MinimumFlowWithBypass in the Controller:OutdoorAir object).
During winter weather, humid exhaust air entering the heat exchanger can form frost on the cold heat exchanger surfaces, which can reduce air flow and the amount of energy recovery. Several methods are used to control or eliminate frost formation, and the following types can be modeled for this heat exchanger object: supply air preheat, minimum exhaust air temperature, exhaust air recirculation and exhaust only. For preheat frost control, a separate heating coil object must be placed in the supply inlet air stream to keep the air temperature above the frost threshold temperature. The other frost control types are modeled within this object itself (i.e., do not require a separate object to be defined) based on alpha and numeric inputs to this heat exchanger object.
Air-to-air heat exchangers are sometimes controlled to maintain a fixed supply air outlet temperature to avoid overheating when the heat exchanger is heating the supply (primary) air. To model this control in EnergyPlus, a set point manager object is used to establish a temperature set point at the supply air outlet node of the heat exchanger. Wheel speed modulation or plate supply air bypass is used to control the supply air exiting conditions to this set point. The set point for supply air temperature control should be set at the minimum economizer temperature set point if an air-side economizer is also being used by the air system. If frost control and supply air outlet temperature control are used, frost control takes precedence over supply air temperature control (e.g., frost control defrost time fraction is determined as if wheel speed modulation or plate supply air bypass is not used).
To model a sensible and latent air-to-air heat exchanger located in an air loop, the input data file should include the following objects:
AirLoopHVAC:OutdoorAirSystem
Controller:OutdoorAir
OutdoorAir:Mixer
HeatExchanger:AirToAir:SensibleAndLatent
Coil:Heating:Water, Coil:Heating:Electric or Coil:Heating:Fuel (if preheat frost control is to be modeled)
SetpointManager:Scheduled (if supply air outlet temperature control is used)
The sensible and latent air-to-air heat exchanger can also be used in a number of other applications, including conditioning outdoor ventilation air and supplying it directly to a zone without an air loop. See object ZoneHVAC:EnergyRecoveryVentilator for further details on this specific application.
A description of each input field for this object is provided below.
Inputs[LINK]
Field: Name[LINK]
A unique user-assigned name for a particular sensible/latent air-to-air heat exchanger. Any reference to this heat exchanger by another object will use this name.
Field: Availability Schedule Name[LINK]
The name of the schedule (ref: Schedule) that denotes whether the unit can operate during a given time period. A schedule value of less than or equal to 0 indicates that the unit is off for that time period. A schedule value greater than 0 indicates that the unit can operate during the time period. If this field is blank, the schedule has values of 1 for all time periods.
Field: Nominal Supply Air Flow Rate[LINK]
The nominal primary side (supply) air flow rate in cubic meters per second. The actual supply and exhaust air flow rates must be between 50% and 130% of this value or a warning will be issued.
Field: Sensible Effectiveness at 100% Heating Air Flow[LINK]
The sensible heat exchange effectiveness at the heating condition defined in Table [table:operating-conditions-for-defining-heat] above with both the supply and exhaust air volume flow rates equal to 100% of the nominal supply air flow rate specified in the previous input field. The default value for this field is 0.
Field: Latent Effectiveness at 100% Heating Air Flow[LINK]
The latent heat exchange effectiveness at the heating condition defined in Table [table:operating-conditions-for-defining-heat] with both the supply and exhaust air volume flow rates equal to 100% of the nominal supply air flow rate. Specify this value as 0.0 if the heat exchanger does not transfer latent energy. The default value for this field is 0.
Field: Sensible Effectiveness at 75% Heating Air Flow[LINK]
The sensible heat exchange effectiveness at the heating condition defined in Table [table:operating-conditions-for-defining-heat] with both the supply and exhaust air volume flow rates equal to 75% of the nominal supply air flow rate. The default value for this field is 0.
Field: Latent Effectiveness at 75% Heating Air Flow[LINK]
The latent heat exchange effectiveness at the heating condition defined in Table [table:operating-conditions-for-defining-heat] with both the supply and exhaust air volume flow rates equal to 75% of the nominal supply air flow rate. Specify this value as 0.0 if the heat exchanger does not transfer latent energy. The default value for this field is 0.
Field: Sensible Effectiveness at 100% Cooling Air Flow[LINK]
The sensible heat exchange effectiveness at the cooling condition defined in Table [table:operating-conditions-for-defining-heat] with both the supply and exhaust air volume flow rates equal to 100% of the nominal supply air flow rate. The default value for this field is 0.
Field: Latent Effectiveness at 100% Cooling Air Flow[LINK]
The latent heat exchange effectiveness at the cooling condition defined in Table [table:operating-conditions-for-defining-heat] with both the supply and exhaust air volume flow rates equal to 100% of the nominal supply air flow rate. Specify this value as 0.0 if the heat exchanger does not transfer latent energy. The default value for this field is 0.
Field: Sensible Effectiveness at 75% Cooling Air Flow[LINK]
The sensible heat exchange effectiveness at the cooling condition defined in Table [table:operating-conditions-for-defining-heat] with both the supply and exhaust air volume flow rates equal to 75% of the nominal supply air flow rate. The default value for this field is 0.
Field: Latent Effectiveness at 75% Cooling Air Flow[LINK]
The latent heat exchange effectiveness at the cooling condition defined in Table [table:operating-conditions-for-defining-heat] with both the supply and exhaust air volume flow rates equal to 75% of the nominal supply air flow rate. Specify this value as 0.0 if the heat exchanger does not transfer latent energy. The default value for this field is 0.
Field: Supply Air Inlet Node Name[LINK]
The name of the HVAC system node from which the unit draws its supply (primary) inlet air.
Field: Supply Air Outlet Node Name[LINK]
The name of the HVAC system node to which the unit sends its supply (primary) outlet air.
Field: Exhaust Air Inlet Node Name[LINK]
The name of the HVAC system node from which the unit draws its exhaust (secondary) inlet air.
Field: Exhaust Air Outlet Node Name[LINK]
The name of the HVAC system node to which the unit sends its exhaust (secondary) outlet air.
Field: Nominal Electric Power[LINK]
The electric consumption rate of the unit in watts. Electric power is considered constant whenever the unit operates. This numeric input can be used to model electric power consumption by controls (transformers, relays, etc.) and/or a motor for a rotary heat exchanger. None of this electric power contributes thermal load to the supply or exhaust air streams. The default value for this field is 0.
Field: Supply Air Outlet Temperature Control[LINK]
This alpha field determines if the heat exchanger’s supply air outlet is controlled to a temperature set point when the heat exchanger is actively conditioning the supply (primary) air. The choices for this input field are Yes or No, with the default being No. When supply air outlet temperature control is used, the wheel rotational speed modulates or supply air is bypassed around the plate heat exchanger to maintain the desired setpoint temperature. A setpoint manager object is required to establish the desired set point at the supply air outlet node (reference: SetpointManager:Scheduled). When an air-side economizer is also being modeled for this air system, the heat exchanger is deactivated during economizer operation. Additionally, the set point for the supply air outlet temperature control should be equal to the economizer outdoor air temperature lower limit (reference: Controller:OutdoorAir, field Economizer Minimum Limit Dry-Bulb Temperature), however, any temperature set point may be used.
Field: Heat Exchanger Type[LINK]
This alpha field denotes the type of heat exchanger being modeled: Plate (e.g., fixed plate) or Rotary (e.g., rotating cylinder or wheel). The default choice for this field is Plate . The heat exchanger type affects the modeling of frost control options and supply air outlet temperature control. For rotary heat exchangers, rotational speed is varied to control frost formation or the supply air outlet temperature. For plate exchangers, air bypass around the heat exchanger is used to obtain the desired effect.
Field: Frost Control Type[LINK]
This alpha field has four choices: None, ExhaustAirRecirculation, ExhaustOnly and MinimumExhaustTemperature. If this field is left blank, the default frost control type is None . For modeling preheat frost control, specify None for this input field and insert a separate heating coil object in the supply inlet air stream to keep the air temperature above the desired frost threshold temperature.
ExhaustAirRecirculation: dampers are used to direct exhaust air back into the zone through the supply side of the heat exchanger when the supply (outdoor) air inlet temperature falls below a threshold temperature (defined in the next input field). The fraction of time that exhaust air is circulated through the supply side of the heat exchanger is dependent on the supply (outdoor) air inlet temperature with respect to the threshold temperature, the initial defrost time fraction, and the rate of change of defrost time fraction (see Field: Rate of Defrost Time Fraction Increase). When exhaust air is being recirculated, no supply (outdoor ventilation) air is being provided through the heat exchanger unit (which may or may not be acceptable regarding ventilation for occupants).
ExhaustOnly (supply air bypass): this control cycles off the supply air flow through the heat exchanger for a certain period of time while the exhaust air continues to flow through the exhaust side of the heat exchanger. The fraction of time that the supply flow through the heat exchanger is cycled off is dependent on the supply (outdoor) air inlet temperature with respect to the threshold temperature, the initial defrost time fraction, and the rate of change of defrost time fraction (see Field: Rate of Defrost Time Fraction Increase). When implemented in real applications, provisions are usually made to avoid building depressurization when this frost control is operating (automatic or pressure-operated dampers, or a bypass air damper around the supply side of the heat exchanger). For this frost control type, it is assumed that the supply air is bypassed around the heat exchanger during frost control operation (i.e., the total supply flow is not reduced during defrost, but merely bypassed around the heat exchanger).
MinimumExhaustTemperature: the temperature of the exhaust air leaving the heat exchanger is monitored and the heat exchanger effectiveness is decreased (by slowing heat exchanger rotation or bypassing supply air around the plate exchanger) to keep the exhaust air from falling below the threshold temperature.
Field: Threshold Temperature[LINK]
This numeric field defines the dry-bulb temperature of air which is used to initiate frost control. The default value is 1.7 °C. For ExhaustAirRecirculation and ExhaustOnly frost control, the threshold temperature defines the supply (outdoor) air inlet temperature below which frost control is active. For MinimumExhaustTemperature frost control, heat exchanger effectiveness is controlled to keep the exhaust air outlet temperature from falling below this threshold temperature value.
The appropriate threshold temperature varies with exhaust (inlet) air temperature and humidity, frost control type, heat exchanger type, and whether the heat exchanger transfers sensible energy alone or both sensible and latent energy (enthalpy). Typical threshold temperatures are provided in Table [table:typical-threshold-temperatures] below. However, it is recommended that the user consult manufacturer s information for the specific air-to-air heat exchanger being modeled.
Source: Indoor Humidity Assessment Tool, U.S. Environmental Protection Agency,http://www.epa.gov/iaq/schooldesign/saves.html
** To model preheat frost control, specify frost control type as None and place a heating coil in the supply inlet air stream controlled to the keep the air temperature above the frost threshold temperature.
Field: Initial Defrost Time Fraction[LINK]
This numeric field defines the fraction of the simulation timestep when frost control will be invoked when the threshold temperature is reached. This field is only used for the ExhaustAirRecirculation and ExhaustOnly frost control types. The value for this field must be ≥ 0 and ≤ 1. The default time fraction is 0.083 (e.g., 5 min / 60 min) which is typical for ExhaustAirRecirculation frost control. Higher initial defrost time fractions (e.g., 0.167 = 10 min / 60 min) are typically required for ExhaustOnly frost control. For best results, the user should obtain this information from the manufacturer.
Field: Rate of Defrost Time Fraction Increase[LINK]
This numeric field defines the rate of increase in the defrost time fraction as the supply (outdoor) air inlet temperature falls below the threshold temperature. This field is only used for the ExhaustAirRecirculation and ExhaustOnly frost control types. The value for this field must be ≥ 0. The default value is 0.012 (e.g., 0.72 min / 60 min per degree C temperature difference) which is typical for ExhaustAirRecirculation frost control. Higher values (e.g., 0.024 = 1.44 min / 60 min per degree C temperature difference) are typically required for ExhaustOnly frost control. For best results, the user should obtain this information from the manufacturer.
This value is used to determine the total defrost time fraction as follows:
Total defrost time fraction = Initial Defrost Time Fraction +
The model does not allow the total defrost time fraction to exceed 1.0 or be less than 0.
Field: Economizer Lockout[LINK]
This input denotes whether the heat exchanger unit is locked out (bypassed for plate type heat exchangers or the rotation is suspended for rotary type heat exchangers) when the air-side economizer is operating. Both the economizer and high humidity control (Ref. Controller:OutdoorAir) activate the heat exchanger lockout as specified by this input. The input choices are Yes (meaning locked out) or No. The default input for this field is Yes.
Following is an example input for this heat exchanger object:
Outputs[LINK]
HVAC,Average,Heat Exchanger Sensible Heating Rate [W]
HVAC,Sum,Heat Exchanger Sensible Heating Energy [J]
HVAC,Average,Heat Exchanger Latent Gain Rate [W]
HVAC,Sum,Heat Exchanger Latent Gain Energy [J]
HVAC,Average,Heat Exchanger Total Heating Rate [W]
HVAC,Sum,Heat Exchanger Total Heating Energy [J]
HVAC,Average,Heat Exchanger Sensible Cooling Rate [W]
HVAC,Sum,Heat Exchanger Sensible Cooling Energy [J]
HVAC,Average,Heat Exchanger Latent Cooling Rate [W]
HVAC,Sum,Heat Exchanger Latent Cooling Energy [J]
HVAC,Average,Heat Exchanger Total Cooling Rate [W]
HVAC,Sum,Heat Exchanger Total Cooling Energy [J]
HVAC,Average,Heat Exchanger Electric Power[W]
HVAC,Sum,Heat Exchanger Electric Energy [J]
HVAC,Average,Heat Exchanger Sensible Effectiveness[]
HVAC,Average,Heat Exchanger Latent Effectiveness[]
HVAC,Average,Heat Exchanger Supply Air Bypass Mass Flow Rate [kg/s]
HVAC,Average,Heat Exchanger Exhaust Air Bypass Mass Flow Rate [kg/s] HVAC,Average,Heat Exchanger Defrost Time Fraction[]
Heat Exchanger Sensible Heating Rate [W][LINK]
This output is the sensible heating rate of the supply air by the heat exchanger in Watts. This rate is determined using the supply air mass flow rate through the heat exchanger unit, the supply air inlet and outlet conditions, and the specific heat of the inlet supply air. A positive value is reported if the supply air is heated by the heat exchanger, else the rate is set to zero.
Heat Exchanger Sensible Heating Energy [J][LINK]
This output is the sensible heating energy added to the supply air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Latent Gain Rate [W][LINK]
This output is the latent heating rate (humidification) of the supply air by the heat exchanger in Watts. This rate is determined by taking the difference between the Heat Exchanger Total Heating Rate and the Heat Exchanger Sensible Heating Rate. A positive value is reported if the supply air is humidified by the heat exchanger, else the rate is set to zero.
Heat Exchanger Latent Gain Energy [J][LINK]
This output is the latent heating energy added to the supply air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Total Heating Rate [W][LINK]
This output is the total heating rate of the supply air by the heat exchanger in Watts. This rate is determined using the supply air mass flow rate through the heat exchanger unit, and the enthalpy of the supply air entering and leaving the unit. A positive value is reported if the enthalpy of the supply air is increased by the heat exchanger, else the rate is set to zero.
Heat Exchanger Total Heating Energy [J][LINK]
This output is the total heating energy added to the supply air by the heat exchanger in Joules over the timestep being reported.This output is also added to a meter with ResouceType = EnergyTransfer, EndUseKey = HeatRecoveryforHeating, GroupKey = System (ref. Output:Meter objects).
Heat Exchanger Sensible Cooling Rate [W][LINK]
This output is the sensible cooling rate of the supply air by the heat exchanger in Watts. This rate is determined using the supply air mass flow rate through the heat exchanger unit, the supply air inlet and outlet conditions, and the specific heat of the inlet supply air. A positive value is reported if the supply air is cooled by the heat exchanger, else the rate is set to zero.
Heat Exchanger Sensible Cooling Energy [J][LINK]
This output is the sensible cooling energy added to the supply air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Latent Cooling Rate [W][LINK]
This output is the latent cooling rate (dehumidification) of the supply air by the heat exchanger in Watts. This rate is determined by taking the difference between the Heat Exchanger Total Cooling Rate and the Heat Exchanger Sensible Cooling Rate. A positive value is reported if the supply air is dehumidified by the heat exchanger, else the rate is set to zero.
Heat Exchanger Latent Cooling Energy [J][LINK]
This output is the latent cooling energy added to the supply air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Total Cooling Rate [W][LINK]
This output is the total cooling rate of the supply air by the heat exchanger in Watts. This rate is determined using the supply air mass flow rate through the heat exchanger unit, and the enthalpy of the supply air entering and leaving the unit. A positive value is reported if the enthalpy of the supply air is decreased by the heat exchanger, else the rate is set to zero.
Heat Exchanger Total Cooling Energy [J][LINK]
This output is the total cooling energy added to the supply air by the heat exchanger in Joules over the timestep being reported. This output is also added to a meter with ResouceType = EnergyTransfer, EndUseKey = HeatRecoveryforCooling, GroupKey = System (ref. Output:Meter objects).
Heat Exchanger Electric Power [W][LINK]
This output is the electric consumption rate of the unit in Watts. This rate is applicable whenever the unit operates (i.e., whenever the unit is scheduled to be available and supply and exhaust air flows exist).
Heat Exchanger Electric Energy [J][LINK]
This output is the electric consumption of the unit in Joules for the timestep being reported. This ouput is also added to a meter with ResourceType = Electricity, EndUseKey = HeatRecovery, GroupKey = System (ref. Output:Meter objects).
Heat Exchanger Sensible Effectiveness [][LINK]
This output is the average sensible effectiveness of the heat exchanger (excluding bypass air, if any) over the timestep being reported.
Heat Exchanger Latent Effectiveness [][LINK]
This output is the average latent effectiveness of the heat exchanger (excluding bypass air, if any) over the timestep being reported.
Heat Exchanger Supply Air Bypass Mass Flow Rate [kg/s][LINK]
This output is the average mass flow rate in kg/second of the supply (primary) air stream that is bypassing the heat exchanger over the timestep being reported. This flow rate is equal to the total supply mass flow rate through the heat exchanger unit minus the amount passing through the supply side of the heat exchanger core.
Heat Exchanger Exhaust Air Bypass Mass Flow Rate [kg/s][LINK]
This output is the average mass flow rate in kg/second of the exhaust (secondary) air stream that is bypassing the heat exchanger over the timestep being reported. This flow rate is equal to the total exhaust mass flow rate through the heat exchanger unit minus the amount passing through the exhaust side of the heat exchanger core.
Heat Exchanger Defrost Time Fraction [][LINK]
This output is the average fraction of the reporting timestep when frost control is being implemented.
HeatExchanger:Desiccant:BalancedFlow[LINK]
This desiccant heat exchanger object is an HVAC component used to model both temperature (sensible) and moisture (latent) heat exchange between two air streams (Figure [fig:schematic-of-the-balanced-flow-desiccant-heat]). The model assumes balanced air flow through the regeneration and process sides of the heat exchanger (i.e., regeneration and process air volume flow rates and face velocities are the same). Heat exchanger performance is specified through a performance data type object (e.g., HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1).
Currently, this desiccant heat exchanger model can be referenced by two compound objects: CoilSystem:Cooling:DX:HeatExchangerAssisted and Dehumidifier:Desiccant:System, both of which are used to provide enhanced dehumidification over conventional systems. If this heat exchanger is referenced by a compound object, the compound object will control heat exchanger operation (i.e., tell the heat exchanger if heat exchange is needed or not for each simulation timestep).
This desiccant heat exchanger object may also be specified directly in an AirLoopHVAC (air loop BranchList) or in an AirLoopHVAC:OutdoorAirSystem (AirLoopHVAC:OutdoorAirSystem:EquipmentList) without being referenced by a compound object. If specified directly in an AirLoopHVAC or AirLoopHVAC:OutdoorAirSystem, then the heat exchanger can be controlled to provide heat exchange based on a maximum and/or minimum humidity set point placed on the process air outlet node (ref. Setpoint Managers). If no humidity set points are provided on this node, then heat exchange will be provided whenever the heat exchanger is available to operate (via its availability schedule) and there is a temperature and/or humidity ratio difference between the two air streams.
Inputs to this model include an availability schedule name, inlet and outlet air node names, and the type and name of the heat exchanger performance data object. A description of each input field for this object is provided below.
Inputs[LINK]
Field: Name[LINK]
A unique, user-assigned name for a particular balanced flow desiccant heat exchanger. Any reference to this heat exchanger by another object will use this name.
Field: Availability Schedule Name[LINK]
The name of the schedule (ref: Schedule) that denotes whether the heat exchanger can operate during a given time period. A schedule value of less than or equal to 0 indicates that the unit is off for that time period. A schedule value greater than 0 indicates that the unit can operate during the time period. If this field is blank, the schedule has values of 1 for all time periods.
Field: Regeneration Air Inlet Node Name[LINK]
The name of the HVAC system node from which the unit draws its regeneration inlet air.
Field: Regeneration Air Outlet Node Name[LINK]
The name of the HVAC system node to which the unit sends its regeneration outlet air.
Field: Process Air Inlet Node Name[LINK]
The name of the HVAC system node from which the unit draws its process inlet air.
Field: Process Air Outlet Node Name[LINK]
The name of the HVAC system node to which the unit sends its process outlet air.
Field: Heat Exchanger Performance Object Type[LINK]
This alpha field contains the type of model used to simulate the desiccant heat exchanger s thermal performance and electrical energy use. Currently, the only valid choice is HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1.
Field: Heat Exchanger Performance Name[LINK]
This alpha field contains the identifying name of the specific heat exchanger performance type object (e.g., HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1) that defines the performance for this heat exchanger. A single heat exchanger performance type object may be used to define performance for many HeatExchanger:Desiccant:BalancedFlow objects (i.e., the same name may be used in this input field for more than one balanced flow desiccant heat exchanger).
Field: Economizer Lockout[LINK]
This input denotes whether the heat exchanger unit is locked out (heat exchanger rotation is suspended) when the air-side economizer is operating. Both the economizer and high humidity control (Ref. Controller:OutdoorAir) activate the heat exchanger lockout as specified by this input. The input choices are Yes (meaning locked out) or No. Economizer lockout is typically not used for this type of heat exchanger. For this reason, the default input for this field is No.
Following is an example input for this heat exchanger object:
Outputs[LINK]
HVAC,Average,Heat Exchanger Sensible Heating Rate [W]
HVAC,Sum,Heat Exchanger Sensible Heating Energy [J]
HVAC,Average,Heat Exchanger Latent Gain Rate [W]
HVAC,Sum,Heat Exchanger Latent Gain Energy [J]
HVAC,Average,Heat Exchanger Total Heating Rate [W]
HVAC,Sum,Heat Exchanger Total Heating Energy [J]
HVAC,Average,Heat Exchanger Sensible Cooling Rate [W]
HVAC,Sum,Heat Exchanger Sensible Cooling Energy [J]
HVAC,Average,Heat Exchanger Latent Cooling Rate [W]
HVAC,Sum,Heat Exchanger Latent Cooling Energy [J]
HVAC,Average,Heat Exchanger Total Cooling Rate [W]
HVAC,Sum,Heat Exchanger Total Cooling Energy [J]
HVAC,Average,Heat Exchanger Electric Power[W]
HVAC,Sum,Heat Exchanger Electric Energy [J]
Heat Exchanger Sensible Heating Rate [W][LINK]
This output is the sensible heating rate of the process air by the heat exchanger in Watts. This rate is determined using the process air mass flow rate through the heat exchanger unit, the process air inlet and outlet temperatures, and the specific heat of the inlet process air. A positive value is reported if the process air is heated by the heat exchanger, else the rate is set to zero.
Heat Exchanger Sensible Heating Energy [J][LINK]
This output is the sensible heating energy added to the process air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Latent Gain Rate [W][LINK]
This output is the latent heating rate (humidification) of the process air by the heat exchanger in Watts. This rate is determined by taking the difference between the heat exchanger s total heat recovery rate and the sensible heat recovery rate. A positive value is reported if the process air is humidified by the heat exchanger, else the rate is set to zero.
Heat Exchanger Latent Gain Energy [J][LINK]
This output is the latent heating energy added to the process air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Total Heating Rate [W][LINK]
This output is the total heating rate of the process air by the heat exchanger in Watts. This rate is determined using the process air mass flow rate through the heat exchanger unit and the enthalpy of the air entering and leaving the process side of the unit. A positive value is reported if the enthalpy of the process air is increased by the heat exchanger, else the rate is set to zero.
Heat Exchanger Total Heating Energy [J][LINK]
This output is the total heating energy added to the process air by the heat exchanger in Joules over the timestep being reported.This output is also added to a meter with ResouceType = EnergyTransfer, EndUseKey = HeatRecoveryforHeating, GroupKey = System (ref. Output:Meter objects).
Heat Exchanger Sensible Cooling Rate [W][LINK]
This output is the sensible cooling rate of the process air by the heat exchanger in Watts. This rate is determined using the process air mass flow rate through the heat exchanger unit, the process air inlet and outlet temperatures, and the specific heat of the inlet process air. A positive value is reported if the process air is cooled by the heat exchanger, else the rate is set to zero.
Heat Exchanger Sensible Cooling Energy [J][LINK]
This output is the sensible cooling energy added to the process air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Latent Cooling Rate [W][LINK]
This output is the latent cooling rate (dehumidification) of the process air by the heat exchanger in Watts. This rate is determined by taking the difference between the heat exchanger s total heat recovery rate and the sensible heat recovery rate. A positive value is reported if the process air is dehumidified by the heat exchanger, else the rate is set to zero.
Heat Exchanger Latent Cooling Energy [J][LINK]
This output is the latent cooling energy added to the process air by the heat exchanger in Joules over the timestep being reported.
Heat Exchanger Total Cooling Rate [W][LINK]
This output is the total cooling rate of the process air by the heat exchanger in Watts. This rate is determined using the process air mass flow rate through the heat exchanger unit and the enthalpy of the air entering and leaving the process side of the unit. A positive value is reported if the enthalpy of the process air is decreased by the heat exchanger, else the rate is set to zero.
Heat Exchanger Total Cooling Energy [J][LINK]
This output is the total cooling energy added to the process air by the heat exchanger in Joules over the timestep being reported. This output is also added to a meter with ResouceType = EnergyTransfer, EndUseKey = HeatRecoveryforCooling, GroupKey = System (ref. Output:Meter objects).
Heat Exchanger Electric Power [W][LINK]
This output is the average electric consumption rate of the unit in Watts. This average rate includes portions of the simulation timestep when the heat exchanger may be cycled off (i.e., average of on and off periods, as appropriate).
Heat Exchanger Electric Energy [J][LINK]
This output is the electric consumption of the unit in Joules for the timestep being reported. This ouput is also added to a meter with ResourceType = Electricity, EndUseKey = HeatRecovery, GroupKey = System (ref. Output:Meter objects).
HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1[LINK]
This object specifies a performance model and model coefficients for a balanced flow desiccant heat exchanger. A HeatExchanger:Desiccant:BalancedFlow object will reference a HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1 object. This performance data object is used to specify the thermal performance and electric consumption of the heat exchanger. Some representative inputs for this object are provided in the EnergyPlus Reference DataSets (PerfCurves.idf and AllDataSets.idf).
This model predicts the regeneration air stream outlet temperature and humidity ratio values based on the entering regeneration and process air stream temperature, humidity ratio and face velocity. The process air stream outlet humidity ratio and temperatures are calculated based on a simple heat and moisture balance. The model requires that the user enter the nominal volumetric flow rate and a nominal face velocity, electric power consumption, empirical model coefficients for the regeneration outlet air temperature and humidity ratio equations, and the applicable minimum and maximum values for both the independent and dependent variables for the empirical model coefficients provided. This model is based on the following equations:
\[RTO = B1 + B2*RWI + B3*RTI + B4*\left( {\frac{{RWI}}{{RTI}}} \right) + B5*PWI + B6*PTI + B7*\left( {\frac{{PWI}}{{PTI}}} \right) + B8*RFV\]
where,
\(RTO\) = Regeneration outlet air dry-bulb temperature (C)
\(RWI\) = Regeneration inlet air humidity ratio (kgWater/kgDryAir)
\(RTI\) = Regeneration inlet air dry-bulb temperature (C)
\(PWI\) = Process inlet air humidity ratio (kgWater/kgDryAir)
\(PTI\) = Process inlet air dry-bulb temperature (C)
\(RFV\) = Regeneration (and process) face velocity (m/s)
\[RWO = C1 + C2*RWI + C3*RTI + C4*\left( {\frac{{RWI}}{{RTI}}} \right) + C5*PWI + C6*PTI + C7*\left( {\frac{{PWI}}{{PTI}}} \right) + C8*RFV\]
where,
\(RWO\) = Regeneration outlet air humidity ratio (kgWater/kgDryAir)
A description of each input field for this object is provided below.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for this set of desiccant heat exchanger performance data. Any reference to this performance data set by another object (e.g., HeatExchanger:Desiccant:BalancedFlow) will use this name.
Field: Nominal Air Flow Rate[LINK]
The nominal air volume flow rate in cubic meters per second. This model assumes balanced air flow (i.e., the same air volume flow rate across the process and regeneration sides of the heat exchanger). The minimum value should be greater than 0. This field is autosizable.
Field: Nominal Air Face Velocity[LINK]
This numeric field contains the nominal air velocity across the heat exchanger face area in meters per second. It is assumed that this air velocity is the same for both sides of the heat exchanger. This value, along with the Nominal Air Flow Rate sets the heat exchanger face area. With this fixed face area, the air face velocity is calculated every simulation timestep based on the actual air volume flow rate for the timestep. The minimum value should be greater than 0 and less than or equal to 6. The default value is 3.0.
Field: Nominal Electric Power[LINK]
This numeric field contains the nominal electric consumption rate of the heat exchanger in watts. This electric power is considered constant and is consumed only when the heat exchanger operates (e.g., for all or a portion of the simulation timestep, as appropriate). This numeric input can be used to model electric power consumption by controls (transformers, relays, etc.) and/or a motor for a rotary heat exchanger. None of this electric power contributes thermal load to the process or regeneration air streams. The minimum value should be greater than or equal to 0. The default value for this field is also 0.
The coefficients for the regeneration air outlet temperature equation described above are defined in the following eight fields:
Field: Temperature Equation Coefficient 1[LINK]
The constant coefficient (B\(_{1}\)) in the temperature equation shown above (RTO).
Field: Temperature Equation Coefficient 2[LINK]
The coefficient (B\(_{2}\)) in the temperature equation shown above (RTO).
Field: Temperature Equation Coefficient 3[LINK]
The coefficient (B\(_{3}\)) in the temperature equation shown above (RTO).
Field: Temperature Equation Coefficient 4[LINK]
The coefficient (B\(_{4}\)) in the temperature equation shown above (RTO).
Field: Temperature Equation Coefficient 5[LINK]
The coefficient (B\(_{5}\)) in the temperature equation shown above (RTO).
Field: Temperature Equation Coefficient 6[LINK]
The coefficient (B\(_{6}\)) in the temperature equation shown above (RTO).
Field: Temperature Equation Coefficient 7[LINK]
The coefficient (B\(_{7}\)) in the temperature equation shown above (RTO).
Field: Temperature Equation Coefficient 8[LINK]
The coefficient (B\(_{8}\)) in the temperature equation shown above (RTO).
The following 16 fields are used to establish the valid range for the dependent and independent variables associated with the coefficients defined above (B\(_{1}\) through B\(_{8}\)) for the regeneration outlet air temperature equation.
Field: Minimum Regeneration Inlet Air Humidity Ratio for Temperature Equation[LINK]
The minimum allowable value of RWI in the temperature equation shown above (kgWater/kgDryAir). Values of RWI less than the minimum will be replaced by this minimum when calculating the regeneration outlet air temperature and a warning message will be issued. The valid range for this input field is 0.0 to 1.0.
Field: Maximum Regeneration Inlet Air Humidity Ratio for Temperature Equation[LINK]
The maximum allowable value of RWI in the temperature equation shown above (kgWater/kgDryAir). Values of RWI greater than the maximum will be replaced by this maximum when calculating the regeneration outlet air temperature and a warning message will be issued. The valid range for this input field is 0.0 to 1.0.
Field: Minimum Regeneration Inlet Air Temperature for Temperature Equation[LINK]
The minimum allowable value of RTI in the temperature equation shown above (C). Values of RTI less than the minimum will be replaced by this minimum when calculating the regeneration outlet air temperature and a warning message will be issued.
Field: Maximum Regeneration Inlet Air Temperature for Temperature Equation[LINK]
The maximum allowable value of RTI in the temperature equation shown above (C). Values of RTI greater than the maximum will be replaced by this maximum when calculating the regeneration outlet air temperature and a warning message will be issued.
Field: Minimum Process Inlet Air Humidity Ratio for Temperature Equation[LINK]
The minimum allowable value of PWI in the temperature equation shown above (kg/kg). Values of PWI less than the minimum will be replaced by this minimum when calculating the regeneration outlet air temperature and a warning message will be issued. The valid range for this input field is 0.0 to 1.0.
Field: Maximum Process Inlet Air Humidity Ratio for Temperature Equation[LINK]
The maximum allowable value of PWI in the temperature equation shown above (kg/kg). Values of PWI greater than the maximum will be replaced by this maximum when calculating the regeneration outlet air temperature and a warning message will be issued. The valid range for this input field is 0.0 to 1.0.
Field: Minimum Process Inlet Air Temperature for Temperature Equation[LINK]
The minimum allowable value of PTI in the temperature equation shown above (C). Values of PTI less than the minimum will be replaced by this minimum when calculating the regeneration outlet air temperature and a warning message will be issued.
Field: Maximum Process Inlet Air Temperature for Temperature Equation[LINK]
The maximum allowable value of PTI in the temperature equation shown above (C). Values of PTI greater than the maximum will be replaced by this maximum when calculating the regeneration outlet air temperature and a warning message will be issued.
Field: Minimum Regeneration Air Velocity for Temperature Equation[LINK]
The minimum allowable value of RFV in the temperature equation shown above (m/s). Values of RFV less than the minimum will be replaced by this minimum when calculating the regeneration outlet air temperature and a warning message will be issued. The minimum value for this input field should be greater than 0.
Field: Maximum Regeneration Air Velocity for Temperature Equation[LINK]
The maximum allowable value of RFV in the temperature equation shown above (m/s). Values of RFV greater than the maximum will be replaced by this maximum value when calculating the regeneration outlet air temperature and a warning message will be issued. The minimum value for this input field should be greater than 0.
Field: Minimum Regeneration Outlet Air Temperature for Temperature Equation[LINK]
The minimum value of RTO resulting from the temperature equation shown above (C). If RTO is less than this value, RTO will be replaced by this minimum value and a warning message will be issued.
Field: Maximum Regeneration Outlet Air Temperature for Temperature Equation[LINK]
The maximum value of RTO resulting from the temperature equation shown above (C). If RTO is greater than this value, RTO will be replaced by this maximum value and a warning message will be issued.
Field: Minimum Regeneration Inlet Air Relative Humidity for Temperature Equation[LINK]
The minimum relative humidity of the regeneration inlet air for the temperature equation shown above (percent). If the relative humidity of the regeneration inlet air is below this value, a warning message will be issued. The valid range for this input field is 0.0 to 100.0.
Field: Maximum Regeneration Inlet Air Relative Humidity for Temperature Equation[LINK]
The maximum relative humidity of the regeneration inlet air for the temperature equation shown above (percent). If the relative humidity of the regeneration inlet air is above this value, a warning message will be issued. The valid range for this input field is 0.0 to 100.0.
Field: Minimum Process Inlet Air Relative Humidity for Temperature Equation[LINK]
The minimum relative humidity of the process inlet air for the temperature equation shown above (percent). If the relative humidity of the process inlet air is below this value, a warning message will be issued. The valid range for this input field is 0.0 to 100.0.
Field: Maximum Process Inlet Air Relative Humidity for Temperature Equation[LINK]
The maximum relative humidity of the process inlet air for the temperature equation shown above (percent). If the relative humidity of the process inlet air is above this value, a warning message will be issued. The valid range for this input field is 0.0 to 100.0.
The coefficients for the regeneration outlet air humidity ratio equation are defined in the following eight fields:
Field: Humidity Ratio Equation Coefficient 1[LINK]
The constant coefficient (C\(_{1}\)) in the humidity ratio equation shown above (RWO).
Field: Humidity Ratio Equation Coefficient 2[LINK]
The coefficient (C\(_{2}\)) in the humidity ratio equation shown above (RWO).
Field: Humidity Ratio Equation Coefficient 3[LINK]
The coefficient (C\(_{3}\)) in the humidity ratio equation shown above (RWO).
Field: Humidity Ratio Equation Coefficient 4[LINK]
The coefficient (C\(_{4}\)) in the humidity ratio equation shown above (RWO).
Field: Humidity Ratio Equation Coefficient 5[LINK]
The coefficient (C\(_{5}\)) in the humidity ratio equation shown above (RWO).
Field: Humidity Ratio Equation Coefficient 6[LINK]
The coefficient (C\(_{6}\)) in the humidity ratio equation shown above (RWO).
Field: Humidity Ratio Equation Coefficient 7[LINK]
The coefficient (C\(_{7}\)) in the humidity ratio equation shown above (RWO).
Field: Humidity Ratio Equation Coefficient 8[LINK]
The coefficient (C\(_{8}\)) in the humidity ratio equation shown above (RWO).
The following 16 fields are used to establish the valid range for the dependent and independent variables associated with the coefficients defined above (C\(_{1}\) through C\(_{8}\)) for the regeneration outlet air humidity ratio equation.
Field: Minimum Regeneration Inlet Air Humidity Ratio for Humidity Ratio Equation[LINK]
The minimum allowable value of RWI in the humidity ratio equation shown above (kgWater/kgDryAir). Values of RWI less than the minimum will be replaced by this minimum when calculating the regeneration outlet air humidity ratio and a warning message will be issued. The valid range for this input field is 0.0 to 1.0.
Field: Maximum Regeneration Inlet Air Humidity Ratio for Humidity Ratio Equation[LINK]
The maximum allowable value of RWI in the humidity ratio equation shown above (kgWater/kgDryAir). Values of RWI greater than the maximum will be replaced by this maximum when calculating the regeneration outlet air humidity ratio and a warning message will be issued. The valid range for this input field is 0.0 to 1.0.
Field: Minimum Regeneration Inlet Air Temperature for Humidity Ratio Equation[LINK]
The minimum allowable value of RTI in the humidity ratio equation shown above (C). Values of RTI less than the minimum will be replaced by this minimum when calculating the regeneration outlet air humidity ratio and a warning message will be issued.
Field: Maximum Regeneration Inlet Air Temperature for Humidity Ratio Equation[LINK]
The maximum allowable value of RTI in the humidity ratio equation shown above (C). Values of RTI greater than the maximum will be replaced by this maximum when calculating the regeneration outlet air humidity ratio and a warning message will be issued.
Field: Minimum Process Inlet Air Humidity Ratio for Humidity Ratio Equation[LINK]
The minimum allowable value of PWI in the humidity ratio equation shown above (kgWater/kgDryAir). Values of PWI less than the minimum will be replaced by this minimum when calculating the regeneration outlet air humidity ratio and a warning message will be issued. The valid range for this input field is 0.0 to 1.0.
Field: Maximum Process Inlet Air Humidity Ratio for Humidity Ratio Equation[LINK]
The maximum allowable value of PWI in the humidity ratio equation shown above (kgWater/kgDryAir). Values of PWI greater than the maximum will be replaced by this maximum when calculating the regeneration outlet air humidity ratio and a warning message will be issued. The valid range for this input field is 0.0 to 1.0.
Field: Minimum Process Inlet Air Temperature for Humidity Ratio Equation[LINK]
The minimum allowable value of PTI in the humidity ratio equation shown above (C). Values of PTI less than the minimum will be replaced by this minimum when calculating the regeneration outlet air humidity ratio and a warning message will be issued.
Field: Maximum Process Inlet Air Temperature for Humidity Ratio Equation[LINK]
The maximum allowable value of PTI in the humidity ratio equation shown above (C). Values of PTI greater than the maximum will be replaced by this maximum when calculating the regeneration outlet air humidity ratio and a warning message will be issued.
Field: Minimum Regeneration Air Velocity for Humidity Ratio Equation[LINK]
The minimum allowable value of RFV in the humidity ratio equation shown above (m/s). Values of RFV less than the minimum will be replaced by this minimum when calculating the regeneration outlet air humidity ratio and a warning message will be issued. The minimum value for this input field should be greater than 0.
Field: Maximum Regeneration Air Velocity for Humidity Ratio Equation[LINK]
The maximum allowable value of RFV in the humidity ratio equation shown above (m/s). Values of RFV greater than the maximum will be replaced by this maximum when calculating the regeneration outlet air humidity ratio and a warning message will be issued. The minimum value for this input field should be greater than 0.
Field: Minimum Regeneration Outlet Air Humidity Ratio for Humidity Ratio Equation[LINK]
The minimum value of RWO resulting from the humidity ratio equation shown above (kgWater/kgDryAir). If RWO is less than this value, RWO will be replaced by this minimum value and a warning message will be issued. The valid range for this input field is 0.0 to 1.0.
Field: Maximum Regeneration Outlet Air Humidity Ratio for Humidity Ratio Equation[LINK]
The maximum value of RWO resulting from the humidity ratio equation shown above (kgWater/kgDryAir). If RWO is greater than this value, RWO will be replaced by this maximum value and a warning message will be issued. The valid range for this input field is 0.0 to 1.0.
Field: Minimum Regeneration Inlet Air Relative Humidity for Humidity Ratio Equation[LINK]
The minimum relative humidity of the regeneration inlet air for the humidity ratio equation shown above (percent). If the relative humidity of the regeneration inlet air is below this value, a warning message will be issued. The valid range for this input field is 0.0 to 100.0.
Field: Maximum Regeneration Inlet Air Relative Humidity for Humidity Ratio Equation[LINK]
The maximum relative humidity of the regeneration inlet air for the humidity ratio equation shown above (percent). If the relative humidity of the regeneration inlet air is above this value, a warning message will be issued. The valid range for this input field is 0.0 to 100.0.
Field: Minimum Process Inlet Air Relative Humidity for Humidity Ratio Equation[LINK]
The minimum relative humidity of the process inlet air for the humidity ratio equation shown above (percent). If the relative humidity of the process inlet air is below this value, a warning message will be issued. The valid range for this input field is 0.0 to 100.0.
Field: Maximum Process Inlet Air Relative Humidity for Humidity Ratio Equation[LINK]
The maximum relative humidity of the process inlet air for the humidity ratio equation shown above (percent). If the relative humidity of the process inlet air is above this value, a warning message will be issued. The valid range for this input field is 0.0 to 100.0.
Following is an example input for this heat exchanger performance data type object:
Outputs[LINK]
No variables are reported for this object. However, outputs are provided by the HeatExchanger:Desiccant:BalancedFlow object that references this PerformanceDataType1 object.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.